1. NFPA 70, The National Electrical Code (including Article 760) 2. National Fire Protection Standards (including but not limited to):

Size: px
Start display at page:

Download "1. NFPA 70, The National Electrical Code (including Article 760) 2. National Fire Protection Standards (including but not limited to):"

Transcription

1 SECTION FIRE ALARM/SECURITY SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section includes 1. Fire alarm/security system: a. Insure that each of the devices listed in this specification are incorporated into the design of the fire alarm system and the security alarm system. b. Provide one control panel for the fire alarm system and a separate control panel for the security alarm system. Combining of the systems will not be permitted. c. Provide fire alarm wiring to fire alarm system devices and wiring to make connection between fire alarm panel and HVAC control system panel to shut down all air handlers 1.2 STANDARDS A. The equipment and installation shall comply with the current applicable provisions of the following standards: 1. NFPA 70, The National Electrical Code (including Article 760) 2. National Fire Protection Standards (including but not limited to): a. NFPA 71 Central Station Signaling Systems-Protected Premises Unit b. NFPA 72 National Fire Alarm and Signaling Code c. NFPA 72 Automatic Fire Detectors d. NFPA 101 Life Safety Code 3. Local and State building codes; 4. Requirements of the Local Authority Having Jurisdiction (AHJ); 5. Underwriters Laboratories, Inc. B. The system and all components shall be listed by Underwriters Laboratories, Inc. for use in Fire Protective Signaling Systems under the following standards as applicable. Not all of the standards will apply to all projects, see Drawings for more information: 1. UL 864 Control Units for Fire Protective Signaling Systems (including UUKL sublisting) 2. UL 268 Smoke Detectors for Fire Protective Signaling Systems 3. UL 268A Smoke Detectors for Duct Applications 4. UL 217 Smoke Detectors, Single and Multiple Station 5. UL 521 Heat Detectors for Fire Protective Signaling Systems 6. UL 228 Door Closers-Holders for Fire Protective Signaling Systems 7. UL 464 Audible Signaling Appliances 8. UL 1638 Visual Signaling Appliances FIRE ALARM/SECURITY SYSTEM

2 9. UL 1971 Signaling Devices for the Hearing Impaired 10. UL 38 Manually Actuated Signaling Boxes 11. UL 346 Water flow Indicators for Fire Protective Signaling Systems 12. UL 1481 Power supplies for Fire Protective Signaling Systems. 13. UL 609, 1610, 1635 Commercial Fire and Intrusion Alarm systems. 1.3 FIRE ALARM SYSTEM OPERATION A. When a fire alarm condition is detected by one of the system initiating devices, the following functions shall occur simultaneously. 1. System point shall be shown on the keypad by type of device, location and time of day. 2. The audio-visual alarm devices shall activate throughout out the building. 3. The digital dialer shall notify the monitoring company (as listed in the execution portion of this specification) that an alarm condition exists. 4. Shut down all air handlers, unless specifically forbidden by the authority having jurisdiction. 5. If the alarm is on an elevator related smoke detector, the elevator shall be captured and returned to the predetermined floor. Refer to Division 14 Section "Hydraulic Elevators" for further elevator-related requirements. B. When a trouble or supervisory condition occurs, the following functions shall occur simultaneously. 1. System point shall be shown on the keypad by type of device, location and time of day. 2. A distinct trouble sound shall occur at the keypad. 3. The digital dialer shall notify the monitoring company (as listed in the execution portion of this specification) that a trouble or supervisory condition exists. C. Whenever a smoke, duct or heat detector is tripped, alarm verification shall function and a timer shall start. After a program time delay compliant with prevailing codes, the horn strobes shall sound if the detector is still in alarm. D. The system shall monitor for head sensitivity and give a warning message if the smoke or duct detector needs cleaning. E. The system shall be fully field-programmable with the equipment on site or a programmer. While programming, the system shall continue to operate, polling devices currently in the program. F. Other features of the system shall include the following. 1. Walk test 2. Device Disabling: Feature pass code protected for use by manufacturer s authorized technician only. Pass code not available to end user. 3. Read status of any point. 4. Field programmable at keypad. 5. Multiple password protection (for remote programming). 6. Manual on/off for any output point. 7. Calibrated smoke detector test. FIRE ALARM/SECURITY SYSTEM

3 8. Low air pressure monitoring of air compressor of any dry pipe system. 1.4 SUBMITTALS A. General: 1. Pay application fees and obtain approval of submittals in writing from the State Fire Marshal s office and/or the local authority having jurisdiction prior to submittal to Owner s Representative for review. 2. Submit fire alarm submittals to the Owner s Representative within 30 calendar days after award of Contract. 3. Permit Drawings and other Submittals shall be prepared by a fire alarm installer certified by the approved manufacturer of the fire alarm system. B. Product Data: Complete documentation for the fire alarm system showing the model number, type, rating, size, style, manufacturer's names, and manufacturer's catalog data sheets for items to ensure compliance with these specifications. C. Shop Drawings 1. Complete set of permit drawings showing conduit sizes and number of conductors required to components plus detailed wiring connections required at each type of device based on the level of the fire alarm system indicated in the Contract Documents. 2. Detailed drawings showing the intended location of field devices and their connections to the system along with room identification and a graphic symbol legend. Prepare submittal drawings utilizing AutoCad Release 2009 or newer Computer Aided Drafting system. 3. Detailed wiring diagrams and riser diagrams showing color-coding of wiring per manufacturer recommendations. Include calculations showing adequate capacity of the standby batteries, where applicable, as required by prevailing codes. D. Monitoring Data Form: Complete per the directions and in coordination with Owner and return to the addresses shown a minimum of 30 days prior to system testing and activation. E. Technician Install/Conversion Form: Complete per the directions and return to the addresses shown a minimum of 30 days prior to system testing and activation. 1.5 QUALITY ASSURANCE A. Installer Qualifications: A qualified firm that is approved, authorized, or licensed by fire alarm/security system manufacturer to install manufacturer's product and that is eligible to receive manufacturer's special warranty. 1. Installing and programming technicians shall be individually certified by fire alarm/security system manufacturer. B. The alarm control panel shall be supplied with all cards and future expansion slots needed for a complete operating system. FIRE ALARM/SECURITY SYSTEM

4 C. Provide system with a 3-year warranty for the control panel starting from the time this system is operational. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Manufacturer: Provide products identified in other Part 2 articles by Bosch Security Systems, Inc. (Fire and Intrusion). Contact Bosch pre-sales at option 2 for questions regarding the equipment and/or applications. For escalated issues please contact Christopher Dunn: (585) , chris.dunn@us.bosch.com or request to speak to the applicable regional sales manager. No substitutions are allowed. 1. This specification requires that a Bosch certified security dealer be contracted to install a complete system, honor the warranty, provide the training and service the system after the warranty period expires. Bosch should not be contacted for project bids or to provide equipment to the electrical installers. a. Installing and programming technicians shall be individually certified by fire alarm/security system manufacturer. 2. Products (other than products by Bosch Security Systems, Inc.) identified as Basis of Design in other Part 2 articles are identified to set the standard of quality for equipment used. 2.2 APPROVED INSTALLERS A. Local installer certified by equipment manufacturer: 1. Equipment Manufacturer: Bosch Security Systems. 2. Certified Installer Locator: At B. National certified installers: 1. Carter Brothers LLC - A Certified Minority Business Enterprise. a. Steve Board: (404) , sboard@carterbrothers.com. b. Scott Dexter: (404) , sdexter@carterbrothers.com. 2. Tel-Aid a. Scott Patsiga: spatsiga@telaid.com. 3. CoLiant Solutions. a. DeeAnna Duncan: (678) , deeanna.duncan@coliantsolutions.com. b. Jeff Cullop: (678) , jeff.cullop@coliantsolutions.com. 4. Niscayah Group. FIRE ALARM/SECURITY SYSTEM

5 a. Ross Balano: (913) 5. Simplex/Grinnell, a Tyco International Company. a. Steve Stigell: (513) , sstigall@simplexgrinnell.com. 2.3 GENERAL A. Incorporate each of the devices listed in this specification into the design of the Fire Alarm System and the Security Alarm System. B. Provide a complete addressable fire alarm system throughout the building as shown on the drawings and in accordance with NFPA 72 and authorities having jurisdiction. Equipment shall be UL listed. C. Each smoke detector shall be addressable for the exact location in the building and provide dirty maintenance type messages at the annunciator, central station and remote programming software. Manual stations, sprinkler devices and all other "contact only" closing devices shall be addressable. 2.4 PANELS A. Main Fire Alarm Control Panel (FACP/FAP): Bosch Security Systems; Model D7412GV4/D9412GV4 and shall be located in the ECR room. 1. Provide Bosch Security Systems; Model 7024FPD only where elevator recall is required by authority having jurisdiction (AHJ). 2. Locate main fire alarm control panel in Network Equipment Room (ECR) room. 3. CPU (Central Processing Unit): Include the following: a. Programming protection in the event of a power failure. b. Addressable communication transmission. c. History of the last activities. d. LEDs for AC power, fire alarm, security alarm, supervisory signal, system trouble, disabled points and alarm silenced. e. Main power supply for the panel and for peripheral devices with 120VAC 60HZ input power or transformer and an integral charger for batteries usable for peripherals. f. SIC data loop board(s) capable of handling 255 or 120 detectors/modules per board. g. A serial interface board for printer or display terminal. h. Battery backup shall comply with Section of NFPA -72. i. Local or remote programming. j. Two different passwords required for programming. 4. DIA Display Interface Board: a. 32 or 16-character liquid crystal display command center. FIRE ALARM/SECURITY SYSTEM

6 5. Equip control panel to provide the following capacities: a. Data loops: 2 b. On-board points: 4 or 8 c. Addressable points: 255 or 238 d. Programmable horn circuits: 2 or 3 e. Integrated network communications capable, dialer capture module will not be accepted 1) Number of Boards (i.e. cards ) determined by system designer. f. Real Time clock 6. Digital Communications: Provide system capable of communicating with a digital receiver such as the Bosch/Radionics D6600 receiver. 7. Remote programming access codes must remain at the factory default code. IT IS FORBIDDEN FOR INSTALLERS TO INSERT THEIR OWN CODES. 2.5 CIRCUITS AND WIRING A. Provide a Class B wiring system. B. Provide 15 percent capacity for future expansion of A/V alarm device and data loop circuits. C. Separate alarm wiring from any open conductors or power, or Class 1 circuits. Do not place in any conduit, junction box or raceway containing these conductors, per NEC Article D. Wiring for 24 volt DC control, alarm notification, emergency communication and similar power-limited auxiliary function may be run in the same conduit as initiating and signaling line circuits. Provide circuits with transient suppression devices and design system to permit simultaneous operation of all circuits without interference or loss of signals. E. Wire: 1. Provide new fire alarm system wiring except where existing alarm wiring in existing facility is to remain in place. 2. Provide wiring meeting local, state and national codes (e.g., NEC Article 760) and as recommended by the manufacturer of the fire alarm system. Provide number and size of conductors as recommended by the fire alarm system manufacturer, but not less than 18 AWG (1.02 mm). a. Line Voltage Circuits: Standard 14 gage copper wire with THHN insulation. b. Low voltage Circuits: Twisted shielded 16 gage stranded copper wire. 3. Provide wire and cable listed and approved by a recognized testing agency for use with a protective signaling system. 4. Provide wire and cable not installed in conduit with a fire resistance rating suitable for the installation as indicated in NFPA 70 (e.g., FPLR). 5. Field wiring shall be electrically supervised for open circuit and ground fault. FIRE ALARM/SECURITY SYSTEM

7 F. Terminal Boxes, Junction Boxes and Cabinets: UL listed for use and purpose. 2.6 MANUAL PULL STATIONS A. Product: Bosch Security Systems; FMM-7045-D or FMM-462-D. B. Provide at customer service for building evacuation. C. The unit shall be dual action (i.e. requiring two motions to activate the station) and shall be addressable for connections to the fire alarm control panel(s). D. Unit shall meet UL 38, standard for manually actuated signaling boxes. E. Mount manual pull stations 48 inches above the finished floor and in accordance with local building codes and as called out in NFPA CEILING/WALL SMOKE DETECTORS A. Bosch Security Systems; D7050 with D7050-B6 base or F220 series smoke with F220-B6PM/S POPIT bases. B. Provide base for all applications where auxiliary contacts are required. 2.8 DUCT SMOKE DETECTORS A. Intelligent Addressable Duct Mounted Photoelectric Smoke Detectors: 1. Bosch Security Systems; D341P Series Duct Detector Housings. a. If used with 9000 Series panel provide D9127U addressable single point module. b. If used with the D7024 or FPD7024 provide D7044M addressable single point module. 2. Provide UL 268A listed unit with two LEDs that will provide local alarm indication and a remote alarm output will be required for use with auxiliary devices. 3. Operating Velocities: 300 to 4000 feet/minute. 4. Provide sampling tube per NFPA, test station and all other required accessories. 5. The shutdown of air handlers shall occur via a signal from the Fire Alarm Panel should any smoke detector be activated, unless specifically forbidden by the authority having jurisdiction, in which case provide auxiliary contact as required to shut down equipment and wire into the stop circuit of the associated air handler starter. 6. Provide remote key activated test station (with status/alarm/trouble indicating LEDs), on the column or wall beneath the duct detector as indicated on Drawings or as determined in field. a. Provide electrical conduit from duct detector to remote test station for column and wall mounted applications. (Refer to Division 26 Section "Common Work Results for Electrical. ) FIRE ALARM/SECURITY SYSTEM

8 b. Provide engraved (or approved machine-generated equivalent method) plate at each remote station to read: #### Duct Smoke Detector, where #### is the RTU or AHU identification number used on Drawings. Install test stations at 80-inches above finish floor (AFF). 7. Provide required power and control wiring so that upon detection of smoke, the following sequence of operations occurs where applicable: a. A supervisory signal is sent by the fire alarm control panel to the monitoring central station. b. All HVAC units shut down (including applicable dampers). c. Associated smoke dampers close (wired to automatically re-open on duct detector reset). 2.9 HEAT DETECTORS A. Addressable Heat Detectors: 1. Bosch Security Systems; F220 series detectors with applicable base. 2. Provide both rate of rise and fixed temperature with 135 degrees F. alarm threshold FIRE ALARM NOTIFICATION DEVICES A. General: 1. Comply with requirements of NEC and NFPA Provide weather resistant back boxes for units installed in refrigerators and freezers to diminish the risk of damage due to condensation. B. Horn/Strobe Units 1. Manufacturers: a. Cooper Industries; Wheelock Brand b. Gentex Corporation 2. Comply with ANSI S3.41 temporal code, when required by authority having jurisdiction. 3. Synchronize strobe units. 4. Color: Red 5. Strobe Luminous Intensity: ADA-compliant. a. Main Sales Area: Minimum 75 candela. b. Smaller Areas: Minimum candela units as required to comply with ADA and the equivalent NFPA 72 requirements resulting in the minimum number of devices. 6. Mounting: Semi-flush mounting plates, ceiling or bottom of open steel structure whenever possible, wall mounted (only when required) at 80-inches as shown on Drawings. C. Strobe-Only Units FIRE ALARM/SECURITY SYSTEM

9 1. Manufacturers: a. Cooper Industries; Wheelock Brand b. Gentex Corporation 2. Comply with ANSI S3.41 temporal code, when required by authority having jurisdiction. 3. Synchronize strobe units. 4. Color: Red. 5. Luminous Intensity: ADA-compliant. a. Main Sales Area: Minimum 75 candelas. b. Smaller Areas: Minimum candela units as required to comply with ADA and the equivalent NFPA 72 requirements resulting in the minimum number of devices. 6. Mounting: On ceiling or to the bottom of open steel structure whenever possible, Wall mounted (only when required) at 80-inches as shown on Drawings ACCESSORY DEVICES A. Remote Annunciators 1. Bosch model D1256RB 2. Locate remote annunciator in customer service area, exact location shall be coordinated with Owner and local fire department. 3. Locate additional remote annunciator in or near the main entrance when required by the local fire department. 4. Mount remote annunciator on wall 60 inches above finish floor to center of unit or as required by local fire department. B. Sprinkler Devices 1. Sprinkler tamper and flow switches will be provided by the fire protection installer. C. Monitor Modules 1. Provide as required to interface "non-intelligent" devices into the system as shown on the Drawings (i.e. Sprinkler Flow Switches, Tamper Switches, Pressure Switches, Kitchen Hoods, etc. as applicable). a. Provide electrical conduit for wall mounted applications, and for ceiling mounted applications if the above-ceiling space acts as a plenum return. (Refer to Division 26 Section "Common Work Results for Electrical. ) D. Provide required relays for auxiliary devices including door closures and supervised control functions such as air handler shut-downs DIGITAL COMMUNICATOR ( DIALER ) A. Description: Digital communicator programmed to report to the Owner s UL LISTED CENTRAL STATION monitoring agency via two non-dedicated telephone lines. Do not install FIRE ALARM/SECURITY SYSTEM

10 network module unless directed by Owner. Configure phone lines, if non-dedicated, to allow the FACP to have line seizure. Configure phone lines going through a PBX or BCM to allow remote programming. Phone lines will be set up to allow long distance calling. 1. UL station will be the Owner s central alarm control monitoring company (KCAC 04002/31A). COMPLETE THE CENTRAL ALARM CONTROL MONITORING DATA FORM INCLUDED AT THE END OF THIS SPECIFICATION. 2. The dialer and/or network module will be UL listed for fire alarm use. 3. Mounting: Mount in single equipment housing containing battery charger and battery with coupler cable. B. Provide one duplex telephone outlet connected to a non-dedicated telephone line (with two RJ31X connecting block jacks) within two feet of the Fire Alarm Panel/Digital Communicator for back up connection to telephone system SECURITY ALARM SYSTEM A. Security Alarm Control Panel 1. Main Control Panel: Bosch Security Systems; D7412GV4/D9412GV4. 2. Configure system to accommodate the needs of this store. Supply panel with all security modules and future expansion slots needed for a complete operating system. B. Keypads: Pharmacy and customer service office locations. 1. Product: Bosch Security Systems; D Provide separate keypads for each area of the system. 3. Keypad installation shall be located customer service office, exact location field verified with Owner. Mount keypads 48 inches above finished floor to center of keypad. 4. Provide an additional keypad inside the pharmacy beyond reach from the security grille to control the pharmacy alarm, verify exact location with Owner. 5. Fred Meyer Jewelry: Provide a keypad in to control the jewelry store alarm. Verify exact location with Owner. C. Keypads: Freight Receiving Driver Entry (DSD) door location. 1. Product: Bosch Security Systems; Mount 48 inches above finished floor to center of keypad near the Driver Entry door. D. Door Switch 1. Basis of Design: a. Rolling Doors: UTS Fire and Security, GE Security; Sentrol 2300 Series, track mounted contacts. b. Other Doors: UTS Fire and Security, GE Security; Sentrol 1078T Series, recessed contact. FIRE ALARM/SECURITY SYSTEM

11 2. Provide at doors that enter the space. When door is equipped with a delayed egress device utilize activation contact and delete door switch. Typical areas include but are not limited to the following: a. Auxiliary customer entrances such as at outdoor seating areas and Starbucks. b. Employee entrance doors. c. Emergency egress doors [including emergency egress doors from Fred Meyer Jewelry Store]. d. Dock, and Other Rolling Doors: Install magnet and sensor on wall and top of door. e. Roof hatch f. Gates/ Grilles, drop down or horizontally rolling. 3. Install wiring for door switch in conduit to a junction box adjacent to door jam. Install wiring from junction box to door switch in surface raceway or flexible conduit depending on the installation. E. Remote Security Sounder: 1. Bosch Security Systems; Model D Provide one remote security sounder at each door, grille or roof hatch and 3. Locate sounder just below roof deck. 4. When emergency exit door is equipped with a delayed egress device delete remote security sounder. F. Motion Sensors 1. Bosch Security Systems; ISC-PDL1-WA18G wall-mount motion, DS9360 (up to 17 feet) and DS9370 (above 17 feet) ceiling mount motions. 2. Install on ceiling or on wall 80 inches above finished floor to provide a curtain of protection just inside the potential access point in locations shown on the Drawings. Typical areas include but are not limited to the following: G. Contact Switch a. Pharmacy: Provide sensors above and below ceiling to detect motion. b. Entrance vestibule. c. Accounting room (with safe). d. Front main aisle of sales floor. e. Fred Meyer Jewelry. 1) Provide two sensors, one at each end of the sales floor. 2) Provide one sensor in jeweler s room. 3) Provide one sensor in the workroom. 1. Basis of Design: GE Security; Sentrol. 2. Install on other areas where operation of entry gates/grilles may be desired. Typical locations would include but are not limited to the following: a. Pharmacy rolling gate, one on each gate. b. Fred Meyer Jewelry: Install one contact on the left side and one on the right side of each roll up gate. Each contact to be wired to a different point for FIRE ALARM/SECURITY SYSTEM

12 H. Safe Seismic independent operation. Gates which slide and fold into the wall will not have contact coverage. 1. Basis of Design: Special DS1525 Safe and Vault Sensor 2. Install (Epoxy bond) on safes, mount on the top front corner on either side of the safe. Protect wiring in 3/8 inch (10 mm) armored cable and secure the safe. I. Glass Break Sensors 1. Basis of Design: Intellisense-N FG Wall/Ceiling Glass break-square 2. Equip each display window with a glass break sensor, install so that cable is not exposed and the detector and is hidden from customer view. J. Security System Monitoring Devices 1. Basis of Design: GE Security; Sentrol. 2. Provide in selective equipment as indicated. The equipment typically monitored using the security system include but are not limited to the following: a. CPC refrigeration failure. b. Generator fault indicator. c. Elevators. 3. Monitoring of the specialized equipment will require coordination with the equipment manufacturers. Provide supplemental equipment needed to monitor this equipment for a complete and operational system. K. Siren Strobe for Fred Meyer Jewelry: 1. Bosch model D Provide a siren strobe on back sales area wall that will activate on the initiation of a burglary alarm in the Jewelry store area only. Verify exact location of siren with Owner. PART 3 - EXECUTION 3.1 GENERAL A. The Authority Having Jurisdiction (AHJ) shall be notified prior to installation of equipment and wiring. 3.2 INSTALLATION A. General: FIRE ALARM/SECURITY SYSTEM

13 1. Install equipment in accordance with the NEC, NFPA 72, local and state codes, as shown on the Drawings, and as recommended by the manufacturer. Refer to Section "Low Voltage Electrical Power Conductors and Cables" for additional recommendations. 2. Conceal wiring, cabling, conduit, junction boxes, conduit supports and hangers from view in finished ceiling areas and remain exposed in open structure areas. Place alarm wiring in conduit when installed down a column and unfinished walls in backroom areas. 3. Do not install smoke detectors prior to the system programming and test period. If construction is ongoing during this period, protect smoke detectors from contamination and physical damage. 4. Flush mount fire detection and alarm system devices, control panels and remote annunciators when located in finished areas. Devices may be surface mounted when located in unfinished areas. B. Connect 120VAC power for fire alarm equipment to emergency panels where applicable. C. Provide required 20A/120VAC power as required to energize components of the security and fire alarm system. Include home-runs for fire alarm control panels as well as home-runs and wiring for any accessory devices such as remote power supplies/panels, printer, dialer, etc. as applicable. 1. This requirement applies whether or not such power work is shown on the Drawings. 2. Dedicate branch circuits serving fire alarm equipment to fire alarm equipment only. Label circuit at the main power distribution panel as FIRE ALARM. Ground control panel cabinet securely to either a cold water pipe or a grounding rod. D. Smoke or Heat Detector Locations: 1. Do not exceed the rated coverage of the detector. 2. Install no more than 15-feet from a wall or 30-feet apart. 3. Do not install within 3-feet of a supply air diffuser. E. Duct Smoke Detector Installation: 1. Duct smoke detectors are typically shown schematically at the respective air handling unit on the Drawings, but shall actually be installed maximizing the distances between ductwork offsets, and installed ahead of the first branch duct take-off. Coordinate with HVAC installer and fire alarm manufacturer s representative in field. 2. In fully ducted systems, install duct smoke detectors in the appropriate side of air handling equipment as required by the authority having jurisdiction. Where more than one detector is indicated associated with a particular piece of air handling equipment, there are special reasons for the additional detectors (i.e. split returns, return risers serving multiple floors, etc.); coordinate all locations for same with the HVAC installer. F. Digital Communicator (Dialer) Installation 1. Connect each jack to a separate phone line and install as the first in-house device tied to the respective phone line. Do not connect the jacks to a party line or a ground start telephone circuit. FIRE ALARM/SECURITY SYSTEM

14 2. Connect digital communicator to operate from three sets of dry contacts on fire alarm control panel; one set each for alarm, trouble and supervisory (existing conventional fire panels only). G. Delayed Egress Electronic Exit Door Locking System Connection 1. Connect wiring to each door control to automatically unlatch the lock instantly in the event of a fire alarm activation. 3.3 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust field-assembled components and equipment installation, including connections, and to assist in field testing. B. Upon completion of installation, the system shall be checked and tested by a fire alarm inspector that is State-Licensed, NICET Level II Certified, or approved equivalent. Contact system manufacturer for this service if installer cannot provide on their own. C. After making tests and corrections, conduct a system demonstration for Owner and the authority having jurisdiction. 3.4 ADJUSTING A. Occupancy Adjustments: When requested within 12 months of date of Substantial Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to two visits to Project outside normal occupancy hours for this purpose. B. Follow-Up Tests and Inspections: After date of Substantial Completion, test the fire alarm system complying with testing and visual inspection requirements in NFPA 72. Perform tests and inspections listed for three monthly, and one quarterly, periods. 3.5 DEMONSTRATION A. Engage a manufacturer certified service representative to train Owner's personnel to operate the fire alarm system. 1. Provide onsite training and User Guide documentation at no cost to Owner. Training includes but is not limited to: a. How to arm and disarm the Intrusion system. b. How to check point status and identify faults on the Intrusion system. c. How to silence a trouble signal on the Intrusion or Fire system. d. How to silence the horns on the Fire system. e. How to reset the smoke and/or duct detectors on the Fire system. f. How to reset a pull station on the Fire system. g. How to identify phone line, A/C power, and battery fails on the Intrusion or Fire system. FIRE ALARM/SECURITY SYSTEM

15 2. Provide 24 hour/7 days per week/365 days per year technical support at no cost to Owner. FIRE ALARM/SECURITY SYSTEM

16 Kroger Central Alarm Control Monitoring Data Form Call KCAC toll free To schedule Conversion & Programming call All fields marked with * must be completed to enable monitoring service *Store Name: *Division #: *Store #: *Address: *Zone/District *Time Zone *City: *State: *Zip Code: *Store Main Phone Number: *Alarm Panel Type *Does your jurisdiction require an alarm permit? If Yes, permit # *Is this store using Best Practices? *Pharmacy Phone #: *RX Dr. s line *Fuel kiosk direct phone # *Local Fire Dispatch phone # (Not 911): *Local Police Dispatch phone # (Not 911): Secondary Police and/or Fire Dispatch # if available: *Business Hours: *Are Associates inside 24 hours a day? Emergency Call List: These people will be notified if no one is contacted at the store or in an emergency *Store Manager Name: EUID: Cell #: *1st Responder (Name & Position) EUID: Cell #: *2nd Responder (Name & Position) EUID: *3rd Responder (Name & Position) EUID: FIRE ALARM/SECURITY SYSTEM

17 Call KCAC toll free To schedule Conversion & Programming call th Responder (Name & Position) EUID: 5th Responder EUID: *Pharmacy Manager EUID: *2nd Pharmacy Responder EUID: *3rd Pharmacy Responder EUID: Additional Responder (Name & Position) EUID: Additional Responder (Name & Position) EUID: Additional Responder (Name & Position) EUID: Home # Additional Responder (Name & Position) EUID: IF NEEDED, ADDITIONAL RESPONDERS CAN BE ADDED ON A SEPARATE SHEET Authorized Contact List These additional people will also be able to contact KCAC Please TYPE/Print *Name *Name *Name Name Name Name Position EUID: Position EUID: Position EUID: Position EUID: Position EUID: Position EUID: IF NEEDED, ADDITIONAL CONTACTS CAN BE ADDED ON A SEPARATE SHEET FIRE ALARM/SECURITY SYSTEM

18 Call KCAC toll free To schedule Conversion & Programming call Please indicate the arm/disarm schedule for all areas monitored on the burglary system. PLEASE TYPE/PRINT Area Time ON (ARM) Time OFF (Disarm) EXAMPLE: Premise (All Customer Doors) 2330 hours (11:30 PM) 0600 hours (6:00 AM) Every Day * Day(s) of the Week *Do you want KCAC to notify you if system is not armed on time? PLEASE NOTE: Fire Systems are monitored 24 hours a day. The fire department is dispatched immediately on all fire alarms. If your system is being serviced or needs to be disregarded for any period of time, call KCAC prior to servicing. Special Instructions (if any) *Name of person completing form Please TYPE/Print: *Position of person completing form Please TYPE/Print: Please this completed form to: alarmcontrol@kroger.com For Additional Information Contact: Joy or Lindy, Program & Conversion Coordinating Carroll Wall, KCAC Manager Date FIRE ALARM/SECURITY SYSTEM

19 Kroger Central Alarm Control Technician Install/Conversion Form Call KCAC toll free To schedule Conversion & Programming call To be completed by service company completing install or conversion - Entire form Must be completed & submitted to KCAC a minimum of 48 hours prior to scheduled install with KCAC Store Name: Division #: Store #: Address: City: State: Zip Code: Company Name: Phone # Installer s Name: Cell # Panel Manufacturer: Panel Model #: Format: Primary Panel Phone #: Secondary Panel Phone #: AREA POINT # Type of Alarm Description Example: Perimeter 158 Burglary Emergency Exit in garden center Fire 201 Fire Alarm Man pull in hallway END OF SECTION % of Fire Initiating Devices have to be tested at time of conversion Don't forget to program the daily timer test for every 24 hours Attach additional sheet if necessary FIRE ALARM/SECURITY SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

Fire alarm system specification for multiple tenant retail buildings

Fire alarm system specification for multiple tenant retail buildings Date: June 20, 2011 Project name: Baederwood Shopping Center Multiple Tenant Buildings B & C City/ State: Abington, PA Landlord s Vendor Contact: Dan Morrin Jr., NECCO Security Phone: (215)638-7999 Email:

More information

SECTION FIRE ALARM

SECTION FIRE ALARM SECTION 16740 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode. Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,

More information

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM OSU PROJECT NO. 30-04-15 PAGE 1 PART 1 GENERAL 1.1 WORK INCLUDED A. Provide all labor, materials, and equipment required to provide a complete and operating system of manual and automatic detection devices,

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.

More information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

The following information shall become and form part of the contract documents.

The following information shall become and form part of the contract documents. October 4, 206 To: Attention: Re: All Bidders All Bidders JCBE Gymnasium HVAC Upgrades BC#: 206433 Edmonds Project No.: BHM6090 All bidders, The following information shall become and form part of the

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system.

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system. SECTION 283111 - PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 DIGITAL, ADDRESSABLE FIRE ALARM PART 1 - GENERAL 1.1 GENERAL A. This Section includes the following: 1. Fire-alarm control panel. 2. Manual fire-alarm boxes. 3. Smoke detectors. 4. Heat

More information

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 283111 A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

OKLAHOMA STATE UNIVERSITY

OKLAHOMA STATE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL

More information

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number: 109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr

More information

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION ADDRESSABLE FIRE ALARM SYSTEM

SECTION ADDRESSABLE FIRE ALARM SYSTEM SECTION 16723 ADDRESSABLE FIRE ALARM SYSTEM 1 PART 1 GENERAL 1.1 DESCRIPTION A. This section outlines the requirements for the installation, programming and configuration of Addressable Fire Alarm System

More information

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM SECTION 2 8 31 00 FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Request For Proposal apply to this Section.

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM SECTION 13966 TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Total

More information

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3 Technical Service Note Detection Systems, Inc. Fairport, New York 14450-9199 Technical Service (800) 374-7454 Sales: (800) 289-0096 and (585) 223-4060 Fax: (585) 223-9180 Concerns: Affects: Dated: June

More information

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS SECTION 280500 COMMON WORK RESULTS FOR SAFETY AND SECURITY PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 28 work shall, in addition to all division 1 specification sections, comply with all of

More information

16721 FIRE ALARM AND DETECTION SYSTEMS

16721 FIRE ALARM AND DETECTION SYSTEMS 16721 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

Environmental Health & Safety

Environmental Health & Safety Environmental Health & Safety Oklahoma State University ADDRESSABLE FIRE ALARM SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu

More information

SECTION (13730) - INTRUSION DETECTION

SECTION (13730) - INTRUSION DETECTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: SECTION 28 16 00 (13730) - INTRUSION DETECTION 1. Intrusion Detection Sensors 2. Signal Equipment 3. System Controls 4. Alarm Displays 5. Alarm Indicating

More information

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5 Construction Standards Page 1 of 5.1 General Description.1 The University requires that all new fire alarm system control panel, components, and devices, as required for the project, be Secutron 2900 Series

More information

Brighton Area Fire Authority

Brighton Area Fire Authority 615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY

DIVISION 28 ELECTRONIC SAFETY AND SECURITY 281300 - ACCESS CONTROL A. General DIVISION 28 ELECTRONIC SAFETY AND SECURITY At the beginning of the project, schedule a meeting with the Facilities Access/Maintenance Coordinator with questions and concerns.

More information

IN2 Digital, Addressable Fire-alarm System

IN2 Digital, Addressable Fire-alarm System Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Digital, Addressable Fire-alarm System Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi 50 (P/N 10-071) is a state-of-the-art true intelligent digital peer-to-peer modular suppression control system.

More information

ONYX FirstVision Specification Interactive Firefighters Display

ONYX FirstVision Specification Interactive Firefighters Display ONYX FirstVision Specification Interactive Firefighters Display NOTIFIER is a registered trademark, and ONYX FirstVision, NOTI FIRE NET, and VeriFire are trademarks of Honeywell International Inc. Microsoft

More information

Division 28 - Electronic Safety and Security

Division 28 - Electronic Safety and Security Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm

More information

16721 FIRE ALARM AND DETECTION SYSTEMS

16721 FIRE ALARM AND DETECTION SYSTEMS 16721 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR

SECTION COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR SECTION 08734 COMMERCIAL DOOR OPERATORS OVERHEAD RSX FIRE DOOR OPERATOR Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Overhead

More information

APPENDIX H (DESIGN SUBMISSION CRITERIA)

APPENDIX H (DESIGN SUBMISSION CRITERIA) APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation

More information

B. Special Documentation Requirements. C. Materials and methods of Construction

B. Special Documentation Requirements. C. Materials and methods of Construction DIVISION 13 SPECIAL CONSTRUCTION 13100 LIGHTNING PROTECTION 1. Lightning Protection: Each building shall be considered individually to determine the necessity for lightning protection. The building location,

More information

Control/Communicator

Control/Communicator Architectural & Engineering Specifications Control/Communicator 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 2400CA - CLEAN AGENT CHEMICAL SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200 1.0 General 1.1 Manufacturer Manufacturer of the Fire Alarm Control Panel (FACP) equipment shall be: Digital Monitoring Products, Incorporated 2500 N.

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 283112 DIGITAL ADDRESSABLE FIRE ALARM SYSTEM VOICE NOTIFICATION PART 1 GENERAL 1.1 SUMMARY NETWORK FIRE ALARM CONTROL PANEL (NODE) A. Network fire alarm control panels shall include all features

More information

LifeAlarm Fire Alarm Control Panels

LifeAlarm Fire Alarm Control Panels LifeAlarm Fire Alarm Control Panels UL, ULC Approved* Features Control panel operator convenience features: Wide viewing angle 2 x 20 (40 character) alphanumeric LCD and dedicated LEDs provide convenient

More information

SECTION ADDRESSABLE FIRE ALARM SYSTEM

SECTION ADDRESSABLE FIRE ALARM SYSTEM SECTION 16720 - ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

CARD ACCESS CONTROL SYSTEM

CARD ACCESS CONTROL SYSTEM SECTION 13851 CARD ACCESS CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested, integrated proximity access control system, to operate on a proximity principle where

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

Voice Annunicated Fire Alarm System Page 1 of 26

Voice Annunicated Fire Alarm System Page 1 of 26 Last Update: May 12, 2017 Consultant s Handbook Page 1 of 26 A. General: 1. Voice annunciated, intelligent, addressable fire alarm systems at BSU are used in all residence halls, high rise buildings and

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

FIRE ALARM AND DETECTION SYSTEMS

FIRE ALARM AND DETECTION SYSTEMS 283100 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125

More information

Addressable Fire Alarm Control Panel

Addressable Fire Alarm Control Panel PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

OJD ITB No Attachment E Duress Alarm Equipment Specifications

OJD ITB No Attachment E Duress Alarm Equipment Specifications Duress Alarm Equipment Specifications PART 1 GENERAL 1.1 SECTION INCLUDES A. Duress devices. B. Alarm control panel. C. Signaling devices. 1.2 REFERENCE STANDARDS A. NFPA 70 - National Electrical Code;

More information

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800)

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800) The CWSI System The CWSI wireless fire alarm product line offers system versatility like none other. Frequency Hopping Spread Spectrum Technology (FHSS), coupled with Bi-directional RF Communication, Repeater

More information

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel DS9400 Series EN Release Notes for Firmware V2.07 Fire Alarm Control Panel DS9400 Series Release Notes for Firmware V2.07 Trademarks Trademarks Gentex is a trademark of Gentex Corporation, Fire Protection

More information

HARRIS COUNTY HOUSING AUTHORITY

HARRIS COUNTY HOUSING AUTHORITY HARRIS COUNTY HOUSING AUTHORITY 8933 Interchange Houston, Texas 77054 713.669-4514 P AMENDMENT OF SOLICITATION ADDENDUM # 3 DATE: 06-03-16 ISSUED BY: Harris County Housing Authority AMENDMENT TO SOLICITATION

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

FMR Installation Instructions. Addressable Fire System Controller

FMR Installation Instructions. Addressable Fire System Controller FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 46 00 SPEC WRITER NOTES: 1. The A/E must obtain a copy of the VA ENGINEERING GUIDE FOR FIRE PROTECTION DESIGN which provides fire alarm system criteria that

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Anywhere, USA 30303 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable

More information

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website. 4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE

More information

0 4 / 0 4 / 1 4. GE Concord 4 Quick User Guide. GE Concord 4 Quick User Guide Page 1

0 4 / 0 4 / 1 4. GE Concord 4 Quick User Guide. GE Concord 4 Quick User Guide Page 1 0 4 / 0 4 / 1 4 GE Concord 4 Quick User Guide GE Concord 4 Quick User Guide Page 1 Before Calling Is the keypad beeping? Press *. This will silence the beeping and let you know where the trouble is. Is

More information

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR SECTION 08 71 13 LOW ENERGY AUTOMATIC OPERATORS Specifier Note: Coordinate and edit articles

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

Contact ID as of 2/2/2015

Contact ID as of 2/2/2015 Contact ID as of 2/2/2015 100 Medical Zone A non-specific medical exists 101 Personal Emergency Zone Emergency Assistance request 102 Fail to report in Zone A user has failed to activate a monitoring device

More information

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide System Reset Trou ble Silence Ala rm Silence Manual Ala rm ENTER NO YES Letters Numb ers Keyword Radionics System Reset Trouble Silence Alarm Silence Manual Alarm ENTER NO YES Le ters Numbers Keyw ord

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information