Lodam Condensing Unit Controller. Modbus Interface. Version 2.0 LMC341 DIWE

Size: px
Start display at page:

Download "Lodam Condensing Unit Controller. Modbus Interface. Version 2.0 LMC341 DIWE"

Transcription

1 Lodam Condensing Unit Controller Modbus Interface Version 2.0 LMC341 DIWE

2 Contents 1. Read this first Installation Safety General Definitions How to Connection samples Communication recommendations Connections Connections on the LMC341 DIWE controller Cable specification Configuration RS485 Repeater Recommended guidelines for cable routing Setup Modbus configuration Data values, scaling and data types Modbus function codes Modbus exception codes Functions Status information Inputs Outputs Alarms Control Modbus sample communication Standards Trouble shooting Index Notes Page 2

3 Modbus Interface manual LMC341 DIWE Page 3

4 1. Read this first The contents of this manual are subject to change without notice. Lodam electronics holds the copyright to this user s manual. The user must follow any instructions given in this user manual entirely and not only partly. Any non-following of this user manual result in exclusion of all warranties, guarantees, and liabilities. Copyright 2013 by Lodam electronics a/s. All Rights Reserved. Disposing of the parts of the controller: INFORMATION FOR USERS ON THE COR- RECT HANDLING OF WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE) In reference to European Union directive 2012/19/EU and the related national legislation, please note that: 1. WEEE cannot be disposed of as municipal waste and such waste must be collected and disposed of separately; 2. The public or private waste collection systems defined by local legislation must be used. In addition, the equipment can be returned to the distributor at the end of its working life when buying new equipment; 3. The equipment may contain hazardous substances: the improper use or incorrect disposal of such may have negative effects on human health and on the environment; 4. The symbol (crossed-out wheeled bin) shown on the product or on the packaging and on the instruction sheet indicates that the equipment must be disposed of separately; 5. In the event of illegal disposal of electrical and electronic waste, the penalties are specified by local waste disposal legislation Installation Before installation, the user should be thoroughly familiarized with this technical manual, especially with purposes, installation, settings and operation. Special care should be taken when installing and connecting external equipment (sensor, high voltage etc.) and handling the PCB s correctly according to protection against ESD. Installation of the LMC341 DIWE Condensing Unit Controller must be performed by authorized personnel only. All warranties are excluded in case installation is performed by unauthorized personnel or in case the LMC341 DIWE has not been correctly installed. Electrical plant failures are to be immediately solved, even though no immediate danger exists; the LMC341 DIWE must not be operating Safety The LMC341 DIWE is not a safety component and cannot be used in medical or life support equipment. The LMC341 DIWE is not a safety component according to the Machinery Directive. Before commissioning, the service technician shall ensure that personal safety requirements are met in conformity with the Machinery Directive based on safety estimations. The LDH105 should not be apart when operating. Fuses can only be replaced and NOT left out. Operation staff must in detail be informed about operating the LMC341 DIWE before operating the LMC341 DIWE. Only use recommended parts/spare parts on the LMC341 DIWE. All warranties are excluded in case unoriginal part/ spare parts are installed. Page 4

5 Modbus Interface manual LMC341 DIWE 2. General 3. Definitions Lodam s Condensing Unit Controller, LMC341 DIWE enable you to gain total control of your condensing unit to deliver cooling to one or more evaporators thereby optimizing your system to save energy, time and money. Remote control of the controller is via Modbus over a RS485 connection and this document describes the settings for this. BEST BEST software HW Hardware/electronics LMT Lodam Multi Tool (PC communication tool for Lodam controllers) Modbus Application-layer messaging protocol - RS485 Hardware communication standard Page 5

6 4. How to Connection samples The Modbus communication is connected using a shielded, 2-wired, twisted pair cable (RS485).The two signal wires must be in the same pair of wires. The end points, first and last controller on the string must have a 120 ohm termination resistor. All LMC341 DIWE controllers are grounded, the signal ground is not needed as PE (Protective Earth) is used as signal ground. The following installation is not guaranteed to work! The connection can be multi-drop with up to 10 LMC341 DIWE controllers on the same communication line. For larger installations or from building to building, a RS-485 repeater with galvanic isolation must be used. Modbus (RTU) via RS485 LMC341 DIWE #1 The cable must be installed as a string, not a star. The LMC341 DIWE is always the client (slave unit). Master Controller LMC341 DIWE #2 LMC341 DIWE #3 One master controller and one LMC341 DIWE.... Master Controller 120 ohm Termination resistor Modbus (RTU) via RS485 (2-wire) 120 ohm Termination resistor One master controller and several LMC341 DIWE. Master Controller Modbus (RTU) via RS485 (2-wire) 120 ohm Termination resistor LMC341 DIWE LMC341 DIWE LMC341 DIWE #1 #2 LMC341 DIWE # Communication recommendations The poll-interval setting in the master controller must be considered. The processor of the LMC341 DIWE controller can only handle a certain amount of requests per second. Beyound this, request from the master controller will be lost. The data in the LMC341 DIWE controller don t change very rapidly so a poll interval of seconds will be sufficient for the monitoring purpose. LMC341 DIWE # ohm Termination resistor LMC341 DIWE #10 Page 6

7 Modbus Interface manual LMC341 DIWE 5. Connections All LMC341 DIWE controllers have internally connected signal ground and protective earth. The signal ground is hence not needed as protective earth is used as signal ground Connections on the LMC341 DIWE controller 5.2. Cable specification Communication is half duplex. Use shielded, tinned copper, twisted-pair cable twisted all the way to the controllers. Max 200 m cable length. Characteristic impedance between 100 Ohm and 130 Ohm Foil or braided shield shield grounded at the master controller Shunt capacitance < 100 pf/m, AWG24, 2 * 120 Ohm termination. Receiver impedance >= 12 kohm Configuration There can be up to 10 LMC341 DIWE controllers on the same Modbus string. If other equipment than LMC341 DIWE controllers are connected on the same string, the maximum current sourcing Data+ +12V Data+ Data- GND Data- Modbus (RTU) of the other equipment must be observed! The network should be configured in sections, possible with RS 485 repeaters between sections in large installations and when connecting different buildings in one network. Up to 3 repeaters may be used. Ethernet RS485 2 x USB Host RS485 Repeater The repeater should be an isolated (galvaniccally isolated) RS485 repeater to separate the sections of the network. The following products have been tested and verified to work right out of the box: ICP CON 7510AR Terminal CN32 - RS485 GND: Data- Data+ Description Modbus connection Do not use as all LMC341 DIWE controllers are grounded(1). Protective earth is used as signal ground. Inverted signal Signal +12V Power supply for RS485 connection. Not used for Modbus communication! ICP CON 7510A Moxa TCC-120/120I BLACK BOX ICD202A Other RS485 repeater brands and models should be tested and verified before use in installations. Note (1): The LMC341 DIWE controller has internally connected signal ground to PE (Protective Earth). Page 7

8 5.5. Recommended guidelines for cable routing Signal, control and communication cables should be shielded with braided shielding and the shield connected to the earth connection preferrable at the master controller. Signal, control and communication cables should be routed so the influence from the power cables is minimized. When crossing power cables, an 90 degrees angle should be achieved 6. Setup Communication with the LMC341 DIWE is via Modbus (RTU). Configuration and reading of settings and readings from the LMC341 DIWE is described in the following sections. Client Server Signal and power cables that run in parallel should be separated by the largest possible appropriate clearance distance, approx cm. A grounded shield plate or grounded metal duct can be used instead. The cable shielding must not be interrupted. The cables should be kept as short as possible. Initiate request Receive the response Function code Data Request Function code Perform the action. Initiate the response Data Response Route cables using grounded, metal cable trays or cable ducts. Sections of cable tray or ducts must be connected together with as large areas as possible. Communication cables should be twisted pair for the data wires Modbus configuration Specification of the protocol: Protocol: Modbus (RTU mode) See Modbus node address: LMC341 DIWE uses default address 1; can be changed on the LUP200 display (option) Baud rate: Default ; 4800, 9600, 19200, 38400, are selectable Number of data bits: 8 Parity: Default Even; None and Odd parity are selectable Number of stop bits: Default 1; 2 (2 only if Parity is None) Packet size: Maximum 32 register in a row Settings are configured on the LUP200 display of the LMC341 DIWE controller in the Service->LOM MB config menu. Please observe that register numbers used in this manual are zero-based as the LMC341 DIWE uses PDU telegrams. Page 8

9 Modbus Interface manual LMC341 DIWE 6.2. Data values, scaling and data types Following is a description of used scaling and data types., 10 and 100 refers to where the decimal point is implied, as a decimal value can t be transmitted via Modbus. : 0: 00: : : : uint32: sint32: The value is the exact value To transmit a value it must be multiplied by 10; i.e > 123 A received value must be divided by 10; i.e > 12.3 To transmit a value it must be multiplied by 100; i.e > 123 A received value must be divided by 100; i.e > 1.23 Unsigned 8-bit integer Unsigned 16-bit integer Signed 16-bit integer Unsigned 32-bit integer Signed 32-bit integer 6.3. Modbus function codes Function Code (hexadecimal) Read Holding Registers Read Input Register Code (decimal) Read/Write Multiple Registers Modbus exception codes Code Name Meaning 01 Illegal function The function code is not valid. 02 Illegal data address The specified register is not valid 03 Illegal data value The value is not allowed Page 9

10 7. Functions For all registers apply that a more specific description of the parameters are to be found in the User manual for the LMC341 DIWE. The parameter names in brackets are the complete parameter name as listed in LMT or BEST Status information This section contains status information parameters. Many are directly visible on the main menu of the LUP200 display (option). Name Possible Values Default Description Register type Address 2ndSetp 0 2nd Setpoint is active (Animation.2ndSetp) Input register 1537 LowSound 0 LowSound fan mode is active (Animation.LowSound) Input register 1538 WinterStart 0 WinterStart is enabled (Animation.WinterStart) 1: Enabled Input register 1539 HeatRecover 0 Heat recovery is enabled (Animation.HeatRecover) 1: Enabled Input register 1540 SetPointSrc 0 What setpoint is used right now (Animation.SetPointSrc) 0: User setpoint 1: 2nd Setpoint 2: Week program Input register 1541 StatusIcon 0 Unit status - as on the displays main menu (Animation.StatusIcon) 0: Normal 1: Min run 2: Min pause 3: Oil return 4: Stopped 5: Li m Tc 6: Lim Tdis 7: Lim Tfc 8: Lim dp 9: Lim Psuc 10: Lim Ifc 11: Off 12: Manual 13: Restarting 14: FC Emergency 15: Psuc Emergency 16: Critical Stop Input register 1542 MinRun 0 Min. compressor run time is active (Animation.MinRun) Input register 1543 MinPause 0 Min. compressor pause is active (Animation.MinPause) Input register 1544 LimTc 0 TC limiter is active (Animation.LimTc) Input register 1545 Page 10

11 Modbus Interface manual LMC341 DIWE Name Possible Values Default Description Register type Address LimTdis 0 Tdis limiter is active (Animation.LimTdis) Input register 1546 LimTfi 0 Temp. FI limiter is active (Animation.LimTfi) Input register 1547 LimdP 0 dp limiter is active (Animation.LimdP) Input register 1548 LimPsuc 0 Psuc limiter is active (Animation.LimPsuc) Input register 1549 LimIFI 0 FI current limiter is active (Animation.LimIfi) Input register Inputs The section lists analogue and digital readings from the LMC341 DIWE controller. Name Possible Values T0 Unit C 00 Troom Unit C 00 TC Unit C 00 Tdis Unit C 00 Tamb Unit C 00 Tsuc Unit C 00 Tsh Unit C 00 TFC Unit C 00 IFC Ext_Ref Psuc Pdis Pressure switch input Unit A Unit bar 00 Unit bar 00 Default Description - Saturated suction temperature (Input.T0) C C - Room temperature (Input.Troom) C C - Saturated discharge (condenser) temperature (Input.TC) C C - Discharge temperature (Input.Tdis) C C - Ambient temperature (Input.Tamb) C C - Suction temperature (Input.Tsuc) C C - Suction superheat temperature (Input.Tsh) C C - Frequency inverter temperature (Input.TFC) C C - Frequency inverter current (Input.IFC) 000 A A - External input offset The offset range is set under capacity regulation (Input.Ext_Ref) C C - Suction pressure (Input.Psuc) 000 bar 1300 bar - Discharge pressure (Input.Pdis) 100 bar 3300 bar - High pressure switch input (Input.HP_Switch) Register type Input register 1552 Input register 1553 Input register 1554 Input register 1555 Input register 1556 Input register 1557 Input register 1558 Input register 1560 Input register 1561 Input register 1562 Input register 1563 Input register 1564 Input register 1565 Address Page 11

12 Name Possible Values Default Description Register type Address Oil_Sensor - Oil level failure (Input.Oil_Switch) Input register 1566 SE-B1 - Compressor overheated (Input.Cpr_OH) 0: Ok 1: Failure Input register 1567 Fan1_Fault - Fan1 failure (Input.Fan1_OH) 0: Ok 1: Failure Input register 1568 Fan2_Fault - Fan2 failure (Input.Fan2_OH) 0: Ok 1: Failure Input register 1569 DigIn1 - Digital input 1 (Input.DigIn1) Input register 1570 DigIn2 - Digital input 2 (Input.DigIn2) Input register 1571 ExtOnOff - External release input (Input.ExtOnOff) Input register 1572 SC_Cpr1 - Security chain for compressor 1 (Only valid in dual compressor mode) (Input.SC_Cpr1) 0: Ok 1: Failure Input register 1573 SC_Cpr2 - Security chain for compressor 2 (Only valid in dual compressor mode) (Input.SC_Cpr2) 0: Ok 1: Failure Input register Outputs Status of relay outputs. Name Possible Values Default Description Register type Address RE1 - Contactor K1 for frequency inverter /compressor (Output.RE1) Input register 1584 RE2 - Liquid Line Valve / Oil Return signal (Output.RE2) Input register 1585 RE3 - Crankcase heater (Output.RE3) Input register 1586 RE4 - Power for ΔpII and SE-B1 (Output.RE4) Input register 1587 RE5 - Alarm relay (Output.RE5) Input register 1588 RE6 - RI (Refrigerant Injection) (Output.RE6) Input register 1589 Page 12

13 Modbus Interface manual LMC341 DIWE Name Possible Values Default Description Register type Address RE7 - Fan 1 (Output.RE7) Input register 1590 RE8 - Fan 2 (Output.RE8) Input register 1591 RE9 - Compressor running for ΔpII (Output.RE9) Input register Alarms Alarm section with up to 16 alarms at a time. The alarms are sorted with highest priority in Code1 parameter. When an alarm becomes inactive the priority is less and it is moved to a new parameter CodeNo > Code1. An alarm number is coded, meaning status, severity level and alarm number are encoded in the number in the parameters Code1 Code16. Leftmost bit = Bit16; rightmost bit = Bit0. Bit1 Bit10: Alarm number; Code1 AND 1023 dec = alarm number. Bit11 Bit13: Alarm level; 0 6 as listed for Level in the table below. Code1 AND 7168 dec = level. Bit16: Alarm status; 1: Alarm active; 0: Alarm inactive. Code1 AND dec = status. Name Count Possible Values Default Description 0 Number of alarms in the list, active and inactive (Alarm.Count) 0-16 alarms CountActive 0 Number of active alarms (Alarm.CountActive) 0 16 Level Alarm Reset 0 Highest alarm level of the active alarms (Alarm.Level) 0: None 1: Log 2: Event 3: Info 4: Warning 5: Critical 6: Fault - Alarm reset command variable (Alarm.Reset) Range : Resets the specific alarm if the alarm is resettable 65535: Reset all resettable alarms Register type Input register 1600 Input register 1601 Input register 1602 Holding register 1603 Address Page 13

14 Name Possible Values Default Description Register type Address Code1 0 Alarm number of most severe alarm (Alarm.Code1) : Alarm number Input register 1604 Code2 (Alarm.Code2) Input register 1605 Code3 (Alarm.Code3) Input register 1606 Code4 (Alarm.Code4) Input register 1607 Code5 (Alarm.Code5) Input register 1608 Code6 (Alarm.Code6) Input register 1609 Code7 (Alarm.Code7) Input register 1610 Code8 (Alarm.Code8) Input register 1611 Code9 (Alarm.Code9) Input register 1612 Code10 (Alarm.Code10) Input register 1613 Code11 (Alarm.Code11) Input register 1614 Code12 (Alarm.Code12) Input register 1615 Code13 (Alarm.Code13) Input register 1616 Code14 (Alarm.Code14) Input register 1617 Code15 (Alarm.Code15) Input register 1618 Code16 0 Alarm number of least severe alarm (Alarm.Code16) Input register 1619 Page 14

15 Modbus Interface manual LMC341 DIWE 7.5. Control Parameters used to view and control operation of the LMC341 DIWE controller. Name Mode Control Mode Runtime Hours MBExtOnOff Possible Values TC Setpoint Unit C 00 Fan Mode Ambient Comp. Setpoint Unit C 00 2nd Setpoint Unit C 00 Act. Setpoint Unit C 00 Cap. Request Unit % 00 Cap. Actual Unit % 00 FI frequency Cpr. Running Unit Hz 00 Default Description 0 Overall unit mode (Control.PM_Mode) 2: Manual 0 Temperature control mode (Control.CapMode) 0: Suction pressure 1: Room temp control mode - Runtime in hours, wrap around after 7.5 years (Control.RuntimeHours) 0 Same function as Input.ExtOnOff, but for Modbus (Control.MBExtOnOff) 0: Unit Stopped 1: Unit Released - Condenser TC setpoint Only used if ambient compensation = Off (Condens.TC_set) 000 C C 0 Fan control mode (Condens.Economy) 0: Eco 1: LowSound 1 Use ambient compensation or fixed condenser setpoint (Condens.AmbComp) - Capacity controller setpoint Range depends on compressor and refrigerant (Capacity.Tset) C C - Secondary setpoint Activated by a digital input Range depends on compressor and refrigerant (Capacity.2ndTset) C C - Actual setpoint (read only) (Capacity.ActTset) C C - Capacity request Calculated capacity request (Capacity.CapReq) % - Actual capacity Actual capacity request limiters might have reduced the requested capacity (Capacity.CapAct) % - Actual FI frequency in Hz (Capacity.FrqAct) Hz Register type Holding register 1632 Holding register 1633 Input register 1634 Holding register 1635 Holding register 1636 Holding register 1637 Holding register 1638 Holding register 1639 Holding register 1640 Holding register 1641 Input register 1642 Input register 1643 Input register Future use Input register 1645 Address Page 15

16 7.6. Modbus sample communication Note: The following sample is a general Modbus communication sample and is not for the LMC341 DIWE! Request: 0b e75a4 Response: 0b041cffff b0e4a b000108e108f1ffff000f0002fff39f8e Request (Input register) 0x0b Slave address 1 byte 0x04 Function code 1 byte 0x1000 Start addr 2 bytes 0x000e Quantity 2 bytes 0x75a4 CRC 2 bytes Response 0x0b Address 1 byte 0x04 Function code 1 byte 0x1c NB bytes of data 1 byte 0xffff Value1 2 bytes 0x0000 Value2 2 bytes 0x0950 Value3 2 bytes 0x08b0 Value4 2 bytes 0xe4a8 Value5 2 bytes 0x0014 Value6 2 bytes 0x000b Value7 2 bytes 0x0001 Value8 2 bytes 0x08e1 Value9 2 bytes 0x08f1 Value10 2 bytes 0xffff Value11 2 bytes 0x000f Value12 2 bytes 0x0002 Value13 2 bytes 0xfff3 Value14 2 bytes 0x9f8e CRC 2 bytes 8. Standards The product is manufactured according to the following standards. RoHS 2002/95/EC Low voltage 206/95/EC EMC 2004/108/EC x Generic EMC The following standards have been used: EN Safety requirement for electrical equipment for measurement and control. EN Immunity standard for industrial environments. EN Emission standard for residential, commercial and lightindustrial environments. CE approved. Request Response: 0b f60 0b Request (Holding register) 0x0b Slave address 1 byte 0x03 Function code 1 byte 0x2000 Address 2 bytes 0x0001 Quantity 2 bytes 0x8f60 CRC 2 bytes Reponse 0x0b Slave address 1 byte 0x03 Function code 1 byte 0x02 Quantity 1 byte 0x0000 Value1 2 bytes 0x2045 CRC 2 bytes Page 16

17 Modbus Interface manual LMC341 DIWE 9. Trouble shooting Check if there is power to the LMC341 DIWE, range VDC/12 24 VAC. Check if Data+ and Data- wires have been switched. Check if the communication node adress setting matches the selected. Note: Node address should be between 1 and 247, both included. Check if the communication speed matches the selected. Check if communication is running. The LUP200 display will show readings and commands. Page 17

18 10. Index A Alarms 13 C Cable routing 8 Control 15 D Data types and scaling 9 Definitions 5 Disposing 4 F Functions 10 G General 5 I Inputs 11 Installation 4 Internally connected 7 M Master controller 6 Modbus configuration 8 Modbus exception codes 9 Modbus function codes 9 Modbus sample communication 16 O Outputs 12 S Safety 4 Setup 8 Standards 16 Status information 10 Page 18

19 Modbus Interface manual LMC341 DIWE 11. Notes Page 19

20 Innovative and energy saving climate control When it comes to climate control Lodam is one of the most experienced you can turn to. For more than four decades we have developed, produced and implemented electronic solutions dedicated to optimising applications like: Compressors Condensing units Heat pumps Air conditioning Refrigerated truck and trailer Reefer containers We know the importance of reliable, energy-efficient operation and constantly push technological boundaries to bring you the most innovative and forward-thinking solutions. As part of the BITZER Group we are backed by one of the world s leading players in the refrigeration and air conditioning industry. This alliance provides us with extensive network and application knowhow and allows us to stay at the forefront of climate control innovation. And to help ensure comfortable surroundings for humans and reliable protection of valuable goods anywhere in the world Contents are subject to change without notice. Lodam electronics a/s Kærvej Sønderborg Denmark Tel Fax lodam@lodam.com For more information visit:

Lodam Compressor Protection Module. Technical manual. Version 3.0 SE-G1

Lodam Compressor Protection Module. Technical manual. Version 3.0 SE-G1 Lodam Compressor Protection Module Technical manual Version 3.0 SE-G1 Contents 1. Read this first... 4 1.1. Reading instructions... 4 1.2. User manual... 4 1.3. Safety... 4 2. General... 5 3. Definitions...

More information

Lodam Heat Pump Controller. User manual. Version 5.0. LMC320

Lodam Heat Pump Controller. User manual. Version 5.0. LMC320 Lodam Heat Pump Controller User manual Version 5.0. LMC320 Contents 1. Read this first... 4 1.1. Installation... 4 1.2. Safety... 4 2. General... 5 3. Definitions... 5 4. Mounting of LMC320 controller

More information

RS485 MODBUS Module 8AI

RS485 MODBUS Module 8AI Version 1.4 15/04/2013 Manufactured for Thank you for choosing our product. This manual will help you with proper support and proper operation of the device. The information contained in this manual have

More information

Installation and User Guide

Installation and User Guide Installation and User Guide User CTS 2 602 manual by Nilan VPM 360 Modbus Version: 2.00 08-05-2014 Software-version: 2.20 The following information describes how to connect to Nilan CTS 602 controls by

More information

EXD-HP1/2 Stand-alone Superheat/Economizer Controller

EXD-HP1/2 Stand-alone Superheat/Economizer Controller Technical Bulletin EXD-HP1/2 are stand-alone universal superheat and or economizer controllers for heat pumps, heating units, air conditioning and precision cooling such as telecom and shelter applications.

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

FieldServer Driver - Serial FS McQuay Microtech Open Protocol Description FieldServer Driver - Serial FS-8700-80 McQuay Microtech Open Protocol This is an active client protocol. The driver is capable of acting as a master or slave. As a master, the Fieldserver polls

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

I/O logger box. User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT!

I/O logger box. User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT! I/O logger box User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT! H i g h E f f i c i e n c y S o l u t i o n s WARNING DISPOSAL CAREL bases the development of its products on decades

More information

Installation and User Guide

Installation and User Guide Installation and User Guide User CTS 2 602 manual by Nilan VPM 360 Modbus Version: 4.00 28-07-2017 Software-version: 2.37 The following information describes how to connect to Nilan CTS 602 controls by

More information

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability Technical Bulletin EXD-SH1/2 are stand-alone universal superheat and or temperature controllers for air conditioning units or refrigeration

More information

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability Technical Bulletin EXD-SH1/2 are stand-alone universal superheat and or temperature controllers for air conditioning units or refrigeration

More information

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer Installation and interface must be performed by a qualified controls technician. IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND CONFIGURATION OF THIS EQUIPMENT. READ

More information

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS.  A4741 / Rev.1 DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS User Manual and Menu Map A4741 / Rev.1 www.entes.com.tr ATTENTION -Disconnect all power before connecting the device. -Don t remove

More information

Symmetra MW Modbus Data Points

Symmetra MW Modbus Data Points Symmetra MW Modbus Data Points Version 0.11.19.05 rev 1 General Information: There are two devices that constitute the Symmetra MW system: the UPS and the EBS. There is a separate point mapping for each

More information

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL 1 Operations Manual for the VTI Model itc5000 Heat Tracing Control System Description The VTI Model itc5000 Heat Tracing Control System consists

More information

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1- DPR-45 User Manual V-2.0 (2..206) DPR-45 TEMPERATURE PROTECTION RELAY PT00 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT 9-50VDC SUPPLY DESCRIPTION DPR-45 is a precision unit designed for the temperature

More information

NCU Mounting Details

NCU Mounting Details Revision Date December 4, 2013 RS-485 Modbus RTU Networking Room Thermostats with LCD for Fan Coil Units Installation and Operation Instructions Dimensions in mm Power Control Unit Display Control Unit

More information

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1 NGC-40 Bridge Overview Raychem-AR-H58862-NGC40BridgeOV-EN-1805 nvent.com 1 Table of Contents 1. NGC-40 Overview... 9 1.1 Example NGC-40 System... 10 2. Legal stuff... 11 3. Protocols... 12 3.1 Data es...

More information

Database for CTS6000 MODBUS

Database for CTS6000 MODBUS Database for CTS6000 MODBUS Valid for: LONcard SW1.7.4B, Variable List V2.02 Version 1.08-4, 01-05-2016 Contents Contents... 2 1. Installation... 3 1.1. Installation and operating instructions... 3 2.

More information

User Manual. Dryer Controller M720

User Manual. Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 1.00 Software version 1.00 Preliminary version Manual M720 Dryer controller Page 1 of 42 Document history Preliminary version: - Created in April, 2009

More information

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations. 1 P age Ezeio v9-120317 Eze Cloud Based Monitoring Systems. Created by Intech Instruments Ltd December 2014 Important Supplementary Manual to the main Ezeio manual. Ezeio Controller and the 2400-A16 input

More information

TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106

TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106 Critical Environments TSI Model 8630 PRESSURA Room Pressure Monitor Modbus Communications Application Note LC-106 Modbus communications are installed in all Model 8630 hospital room pressure controllers

More information

P2267 NETWORK INTERFACE

P2267 NETWORK INTERFACE P2267 NETWORK INTERFACE USER MANUAL FOR OPERATING SYSTEMS: 22031-03 23636-01 October 2009 Associated Controls (Australia) Pty. Limited 2-4 Norfolk Road Greenacre, NSW, 2190. PH +61 2 9642 4922, FAX +61

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min

More information

Endura AZ40 Oxygen and carbon monoxide equivalent (COe) analyzer

Endura AZ40 Oxygen and carbon monoxide equivalent (COe) analyzer ABB MEASUREMENT & ANALYTICS OPERATING INSTRUCTION SUPPLEMENT COM/AZ40/MOD-EN REV. A Endura AZ40 Oxygen and carbon monoxide equivalent (COe) analyzer Communications supplement Measurement made easy Oxygen

More information

F500 Elite. FIELDBUS ADAPTER. Watchdog NTC to Modbus RTU communications. (Software Version 3.3.0)

F500 Elite. FIELDBUS ADAPTER. Watchdog NTC to Modbus RTU communications. (Software Version 3.3.0) F500 Elite. FIELDBUS ADAPTER. Watchdog NTC to Modbus RTU communications. (Software Version 3.3.0) Approvals: Suitable for use in Hazardous Locations CL II Div 1 GPS E, F & G (CANADA ONLY) CL II Div 2 GPS

More information

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

LINEAR HEAT DETECTION CABLE DURÁN-SAFE LINEAR HEAT DETECTION CABLE DURÁN-SAFE Installation & User Manual 2018 DURAN ELECTRONICA S.L. - All rights reserved www.duranelectronica.com I-manSAFECABLE-v05 TABLE OF CONTENTS Pages 1. INTRODUCTION...

More information

FlameGard 5 MSIR HART

FlameGard 5 MSIR HART FlameGard 5 MSIR HART Multi-Spectral Infrared Flame Detector HART Communication with the FlameGard 5 Multi-spectral Infrared Detector The information and technical data disclosed in this document may be

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-7 Group: Controls Part Number: ED 15121 Date: July 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHRAE 135-2004, BACnet

More information

DiMM Unit. LST Digital Interface Monitor Module (LST-DiMM) MAN3109

DiMM Unit. LST Digital Interface Monitor Module (LST-DiMM) MAN3109 LST Digital Interface Monitor Module (LST-DiMM) MAN3109 TABLE OF CONTENTS: Page No. 1 Important Guidelines... 3 2 General Description... 4 Digital Interface Monitor Module... 4 3 Specifications... 5 Leader

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

DMFPM-2R MULTIFUNCTIONAL

DMFPM-2R MULTIFUNCTIONAL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND

More information

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control

Model 8682-KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control Critical Environments Model 8682KET Sequenced Offset (Flow Tracking) and Static Pressure Controller with Dual Exhaust Modulation for Temperature Control Manual Supplement Contents of this manual supplement

More information

Technical data Humidity Temperatur General data Electrical data Two designs duct version (LK) wall mounting

Technical data Humidity Temperatur General data Electrical data Two designs duct version (LK) wall mounting Galltec Mess- und Regeltechnik GmbH MELA Sensortechnik GmbH Boschstr. 4 Raasdorfer Str. 18 71149 Bondorf. Deutschland 07987 Mohlsdorf-Teichwolframsdorf. Deutschland Tel. +49 (0)7457-9453-0 Tel. +49(0)3661-62704-0

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The nvent RAYCHEM NGC-40 is a multipoint

More information

Dryer Controller M720

Dryer Controller M720 User Manual Dryer Controller M720 Hardware version 2.00 Software version 2.00 Manual M720 Dryer controller Page 1 of 60 Document history Preliminary version: - Created in April, 2009 Hardware Version 2.00,

More information

READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS XXXXXXX-0 EN 1904 READ AND SAVE THESE INSTRUCTIONS BASIC-PLC CONTROLLER MANUAL For all Condair desiccant dryer with equipped with Basic- PLC valid from version: PLC-35/PLC-45 18.04.03 Dehumidification

More information

USER MANUAL FOR OPERATING SYSTEM

USER MANUAL FOR OPERATING SYSTEM P2262 ALARM PANEL USER MANUAL FOR OPERATING SYSTEM 21765-07 September 1999 Associated Controls (Aust) PTY. LTD. 29 Smith Street, Hillsdale, NSW, 2036. PH (02) 9311 3255, FAX (02) 9311 3779 Page 1 of 177

More information

CHILLGARD M-100. Refrigerant Sensor. Operating Manual. Order No.: /02

CHILLGARD M-100. Refrigerant Sensor. Operating Manual. Order No.: /02 CHILLGARD M-100 Refrigerant Sensor Operating Manual GB Order No.: 10086391/02 For the Declaration of Conformity, please visit the product page on MSAsafety.com. MSA Europe GmbH Schlüsselstrasse 12 8645

More information

Multi-utility pulse concentrator

Multi-utility pulse concentrator 046 87 EMDX³ D47C Multi-utility pulse concentrator N292554/00 GB Contents Operating instructions DANGER AND WARNING 3 PRELIMINARY OPERATIONS 3 PRESENTATION 4 MODBUS COMMUNICATION 5 INSTALLATION 6 CONFIGURATION

More information

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI E N G L I S H FIRE ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL0EI, MI-FL0EI AND MI-FL0EI mm mm 0 mm DESCRIPTION The LT MI-FL0 Series is part of the Fire Alarm

More information

EC3-X33 Stand-alone Superheat Controller Technical Data

EC3-X33 Stand-alone Superheat Controller Technical Data Technical Data EC3-X33 is a stand-alone universal superheat controller for air conditioning, refrigeration and industrial applications such as chillers, industrial process cooling, rooftops, heat pumps,

More information

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12 AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual RST-5000 Series Web Enabled Input Module Rev. A2, 1/12 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com RST-5000

More information

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV CyCLO User Guide Version 2.00 19 th December 2017 REV 2.00 1 Contents 1. Hardware... 3 1.1. Introduction... 3 1.2. Electrical Specification... 3 1.3. Board Overview... 4 1.4. Electrical Installation...

More information

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM Local configuration and monitoring with Raychem Touch 1500 touch screen display PRODUCT OVERVIEW The Raychem NGC-40 is a multipoint electronic

More information

CTT8 TEMPERATURE MONITOR DEVICE

CTT8 TEMPERATURE MONITOR DEVICE INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

Nov 08 PRODUCT SPECIFICATION SHEET

Nov 08 PRODUCT SPECIFICATION SHEET Honeywell UDC1200 and UDC1700 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS 51-52-03-35 Nov 08 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC1200 & UDC1700 are microprocessor-based 1/16 DIN and 1/8 DIN

More information

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS Firmware versions up to V2.0.X INDUSTRIAL HEAT TRACING SOLUTIONS EN-RaychemNGCUIT2Protocol-IM-H57880 06/15 1/32 Contents Section I Introduction

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

FlameGard 5 UV/IR HART

FlameGard 5 UV/IR HART FlameGard 5 UV/IR HART HART Communication Manual The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically authorized

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

Figure 1. Proper Method of Holding the ToolStick. Figure 2. Improper Method of Holding the ToolStick

Figure 1. Proper Method of Holding the ToolStick. Figure 2. Improper Method of Holding the ToolStick CAN OBD READER REFERENCE DESIGN KIT USER GUIDE 1. Standard ToolStick Handling Recommendations The ToolStick Base Adapter and daughter cards are distributed without any protective plastics. To prevent damage

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

F Technical Bulletin SC 370 SMART Modbus Interface

F Technical Bulletin SC 370 SMART Modbus Interface F7904502 Document Revision History Document Versiosion Modbus Map Ver- Date Author Notes 1 10 9/26/17 JGG Document Created Flash Technology, 332 Nichol Mill Lane, Franklin, TN 37067 www.flashtechnology.com

More information

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM 2 Line, 16 Characters/row LCD Display Temperature Input Range -50 C to +500 C -58 F to + 932 F Enclosure NEMA Type 4X Current Rating 30A max (resistive load only) Ambient Temperature -40 C to + 40 C -40

More information

Unit Controller (UC8) Quick Reference Operation and Fault Diagnosis

Unit Controller (UC8) Quick Reference Operation and Fault Diagnosis Unit Controller (UC8) Quick Reference Operation and Fault Diagnosis (To be read in conjunction with labels TZ243 (Air-to-Air) & TZ245 (Water-to-Air) Date: 20 October 2015 Issue: 1 Index 1. Introduction...

More information

Added password for IP setup page : Password must be in IP format!

Added password for IP setup page : Password must be in IP format! NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP

More information

DIGITAL TEMPERATURE RELAY TR-100

DIGITAL TEMPERATURE RELAY TR-100 LTD Research-and-Manufacture Company DIGITAL TEMPERATURE RELAY USER S MANUAL www.novatek-electro.com - 2 - Service manual is intended for getting acquaints with hardware, operation principals, modes of

More information

Installation Manual Tracker 221

Installation Manual Tracker 221 Installation Manual Tracker 221 KSR KUEBLER AG Im Kohlstatterfeld 17 D-69439 Zwingenberg / Germany www.ksr-kuebler.com Contents About this Installation Manual...4 Description Tracker 220-series...4 Installing

More information

Danfoss gas detection units

Danfoss gas detection units Data sheet Danfoss gas detection units Types GD Premium, Premium+, Premium Duplex, Premium Remote, Premium Flex and Premium Uptime The Premium line gas detection units are used for monitoring and warning

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

DTSX200 Communications(Modbus) Guide

DTSX200 Communications(Modbus) Guide User s Manual DTSX200 Communications(Modbus) Guide 4th Edition Blank Page < Introduction > i Introduction About this Manual Thank you for purchasing the DTSX200 Distributed Temperature Sensor. This document

More information

ModBus DE-1 INSTALLATION AND USER MANUAL

ModBus DE-1 INSTALLATION AND USER MANUAL ModBus DE-1 INSTALLATION AND USER MANUAL INTESIS Software, SL Distributed by DURAN ELECTRONICA S.L Tomás Bretón 50 28045 MADRID, España duran@duranelectronica.com www.duranelectronica.com 2 2010 DURAN

More information

WIO500 and WIOI500 Water in oil sensor

WIO500 and WIOI500 Water in oil sensor WIO500 and WIOI500 Water in oil sensor User manual Rev. 1.08 111881-942 Rev. 1.08 User manual 500 Date: 2017-01-20 03-01-0501-CRJ-04 Side 1 af 79 Table of contents Table of contents... 2 Introduction...

More information

RSMFM-2R MULTIFUNCTIONAL

RSMFM-2R MULTIFUNCTIONAL MULTIFUNCTIONAL ROOM Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL

More information

CLEANROOM MONITOR CR3A Network - Installation Instructions

CLEANROOM MONITOR CR3A Network - Installation Instructions CLEANROOM MONITOR CR3A Network - Installation Instructions INTRODUCTION The CR3 Series Cleanroom Monitor, was developed specifically to allow for monitoring of confined spaces with accuracy and reliability.

More information

PROFIBUS-PA Display RID 261 PROFIBUS-PA

PROFIBUS-PA Display RID 261 PROFIBUS-PA Technical Information TI 071R/09/en Mat.-Nr.: 510 01194 PROFIBUS-PA Display RID 261 PROFIBUS-PA Display of process values and set point alarms on PROFIBUS-PA systems R Applications Direct connection to

More information

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems Honeywell Life Safety Iberia C/Pau Vila 15-19; 08911 Badalona Barcelona T. 902 03 05 45; Internacional:+34932424236 www.honeywelllifesafety.es infohlsiberia@honeywell.com ibox Modbus Server Gateway for

More information

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number Innovation In and Out of Parlour Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual Version - 1.0 Date - June 2016 Part Number - 39-0038 Index Manual Version... 3 About the Remote Vacuum

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

OWNER S OPERATION MANUAL

OWNER S OPERATION MANUAL DUTY P P STDBY Run 1 2 Run STDBY P P FAULT Run 3 4 OK: Change mode PUMPCONTROL OWNER S OPERATION MANUAL Advanced Multi Pump Controller Installation and Operating Instructions MODEL: FPC-15607-S AUTO: RUNNING

More information

M1000 Alarm Annunciator

M1000 Alarm Annunciator Data Sheet Alarm Annunciator Reliable Supervision and Control 10 inputs with LED indications Supports both NO/NC input contacts 10 open collector outputs Built-in siren relay Text label for alarm descriptions

More information

Gas Detection System TOX ALARM DG2000-Garage

Gas Detection System TOX ALARM DG2000-Garage Gas Detection System TOX ALARM DG2000-Garage Gas Detection System 32 independent programmable channels 2 programmable alarm levels for each gas = up to 6 for each channel LCD alphanumeric display of gas

More information

Series Digital Controller Instruction Sheet

Series Digital Controller Instruction Sheet 216/3/11 Series Digital Controller Instruction Sheet Thank you very much for purchasing DELTA DTC Series Temperature Controller. Please read this instruction sheet before using your DTC series to ensure

More information

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm. E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0E FL0E FL0E mm mm 0 mm DESCRIPTION The LT FL0 Series is part of the Fire Alarm Aspiration

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C

Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C 1. General The hand-held micro terminal is used for setting the motor parameters of the SILVER C. 2. Installation

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

Open Protocol Data Communications

Open Protocol Data Communications MicroTech Series-100 Centrifugal Chiller Open Protocol Data Communications Information Packet Version 3.2 April, 1996 - C O N F I D E N T I A L - This Document may not be copied or reproduced in any way

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-6 Group: Controls Part Number: ED 15121 Date: March 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHAE 135-2004, BACnet

More information

REMOTE CONTROL FOR CHILLER MYCHILLER

REMOTE CONTROL FOR CHILLER MYCHILLER REMOTE CONTROL FOR CHILLER MYCHILLER GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD... 5 BOARD CONFIGURATION... 7 LIST OF MAIN PARAMETERS... 7 CONFIGURATION OF MAIN

More information

Poolsmart Plus Touchscreen Heating Controller. Installation & Operating Manual

Poolsmart Plus Touchscreen Heating Controller. Installation & Operating Manual Poolsmart Plus Touchscreen Heating Controller Installation & Operating Manual Important Notes Congratulations on purchasing the PoolSmart Plus touchscreen heating controller, manufactured in England to

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

Danfoss gas detection unit Type GD Heavy Duty

Danfoss gas detection unit Type GD Heavy Duty Data sheet Danfoss gas detection unit Type GD Heavy Duty The Heavy Duty gas detection units are used for monitoring and warning of hazardous Ammonia gas concentrations. They are intended for ATEX/ IECEx

More information

Instruction Bulletin

Instruction Bulletin Instruction Bulletin 435-54-26A 9/99 Monroe, NC, USA MODEL 98 Digital Temperature Controller For Medium Voltage Transformers Class 3, 4 Retain for future use. NOTICE Read these instructions carefully and

More information

For Raychem ACS-30 Controls Systems

For Raychem ACS-30 Controls Systems ACS-30 Protocol Interface Mapping For Raychem ACS-30 Controls Systems Firmware Version 5.05 THERMAL BUILDING SOLUTIONS EN-RaychemACS30-AR-H58324 03/16 Table of Content Section 1. Introduction... 3 1.1

More information

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions Description The NGC-UIT-ORD is a panel mounted display used in conjunction with other approved Raychem control and

More information

02/11/2015

02/11/2015 MIC48 With RS 485 link Part number 89422418 Heating and / or cooling function 2 independent alarms Load break detection 2 setpoint which can be selected remotely Manual / automatic power adjustment RS

More information

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1 VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER 1. INTRODUCTION This manual contains information for the installation and operation and tuning of our Vertex VT10 series self-tuning

More information

Module Features are-configurable, no module jumpers to set

Module Features are-configurable, no module jumpers to set December 2011 PACSystems* RX3i Isolated Thermocouple Input Module, 6 Channels, IC695ALG306 Isolated Thermocouple Input Module, 12 Channels, IC695ALG312 Isolated Thermocouple Input module IC695ALG306 provides

More information

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47 WSHP Open v3 CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-539-01 2/8/2017 Verify that you have the most current version of this document

More information

Installation & Maintenance

Installation & Maintenance Installation & Maintenance CM.comm Host Communications Software Table Of Contents System Overview System Features System Requirements Communications Overview CM.comm Quick Start Hardware Setup RS-232 Identification

More information

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM Card Rack Modules CABLE DUCT MAIN SWITCH 800 mm USER INTERFACE TERMINAL PRODUCT OVERVIEW The nvent

More information

TTSIM-1 Sensor Interface Module

TTSIM-1 Sensor Interface Module R Sensor Interface Module Installation/Operation Guide General Information Please read these instructions and keep them in a safe place. These instructions must be followed carefully to ensure proper operation.

More information

User Guide

User Guide ABS control panel CP 112 212 ON ON ON ON ON ON User Guide www.absgroup.com ii ABS CONTROL PANEL CP 112 212, USER GUIDE Copyright 2008 ABS Group. All rights reserved. This manual, as well as the software

More information

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com

FL500 Modbus Communication Operating Manual. Order No.: /00. MSAsafety.com FL500 Modbus Communication Operating Manual Order No.: 10193214/00 MSAsafety.com 1000 Cranberry Woods Drive Cranberry Township, PA 16066 A Phone 1-800-MSA-2222 Fax 1-800-967-0398 For your local MSA contacts

More information

UDC 700 Universal Digital Controllers and Indicator Specifications

UDC 700 Universal Digital Controllers and Indicator Specifications UDC 700 Universal Digital Controllers and Indicator Specifications 51-52-03-28 August 2002 Overview The UDC 700 is a 1/32 DIN (49 x 25 mm) controller which combines a high degree of technology and quality

More information