MEVO3_ Three-Phase Voltage Measurement

Size: px
Start display at page:

Download "MEVO3_ Three-Phase Voltage Measurement"

Transcription

1 1MRS MUM Issued: 10/1997 Version: F/ Data subject to change without notice Three-Phase Voltage Measurement Contents 1. Introduction Features Application Input description Output description Description of operation Configuration Measuring mode Registers Actual voltage measurement Maximum and minimum s Zero value supervision and zero value detection Threshold supervision with absolute threshold Threshold supervision with integrator algorithm Threshold supervision with time-based function Limit value supervision Parameters and events General Control settings Measurement values Input data Recorded data Events Technical data... 17

2 Substation Automation 1. Introduction 1.1 Features True RMS measurement of phase or phase-to-phase voltages Actual voltage values displayed in voltages and as p.u. values Average voltage supervision with adjustable time intervals Threshold supervision for voltages by the integration, absolute or time-based method Limit value monitoring for each voltage with up to four adjustable limits Voltages to be measured by means of conventional voltage transformers or voltage dividers Voltage outputs to be used in the freely programmable logic of the Relay Configuration Tool included in the CAP 505 Tool Box Virtual phase-to-phase voltage measurement channels can be used instead of the corresponding analogue measurement channels 1.2 Application This document specifies the functions of the three-phase voltage measurement function blocks MEVO3A and MEVO3B that are identical in operation. The three-phase voltage measurement function blocks can be used in various applications and products based on the RED 500 Platform, e.g. feeder terminals, infeeder terminals, motor protection terminals and transformer protection terminals. Figure 1. Function block symbols MEVO3A and MEVO3B 2

3 Substation Automation 1.3 Input description Name Type Description UL1_U12 Analogue signal (SINT) Input for measuring voltage U L1 / U 12 UL2_U23 Analogue signal (SINT) Input for measuring voltage U L2 / U 23 UL3_U31 Analogue signal (SINT) Input for measuring voltage U L3 / U 31 RESET Reset signal (BOOL, pos. edge) Input signal for resetting the registers of the function block 1.4 Output description Name Type Description UL1_U12MEAS Analogue signal (REAL) Measured value of voltage U L1 / U 12 (kv) UL2_U23MEAS Analogue signal (REAL) Measured value of voltage U L2 / U 23 (kv) UL3_U31MEAS Analogue signal (REAL) Measured value of voltage U L3 / U 31 (kv) HighWarning HighAlarm LowWarning LowAlarm ERR Digital signal (BOOL, active high) Digital signal (BOOL, active high) Digital signal (BOOL, active high) Digital signal (BOOL, active high) Digital signal (BOOL, active high) Indication of an exceeded high warning limit Indication of an exceeded high alarm limit Indication of an exceeded low warning limit Indication of an exceeded low alarm limit Indication of a configuration error 3

4 Substation Automation 2. Description of Operation 2.1 Configuration The analogue channel numbers for the corresponding UL1_U12, UL2_U23 and UL3_U31 inputs are selected by means of the Relay Configuration Tool. Conventional voltage transformers or voltage dividers can be used for measuring the voltages. The function block automatically adapts its operation to the channels and measuring devices selected in the configuration tool. The following voltages can be connected to each Uchx input: Input name Measured voltage UL1_U12 U L1, U L1b, U L1c, U 12, U 12b, U 12s or U 12bs, UL2_U23 UL3_U31 U L2, U L2b, U 23, U 23b, U 23s or U 23bs U L3, U L3b, U 31, U 31b, U 31s or U 31bs Both phase-to-phase and phase-to-earth voltages can be connected to the function block at the same time. Two voltage inputs can also be left without a connection. When all three voltage inputs are unconnected, the output signal ERR is set to TRUE. 2.2 Measuring mode The function block measures true RMS phase-to-earth or phase-to-phase voltages. If voltage dividers are used, only phase-to-earth voltages can be measured. Note that RMS measurement must be selected for the voltage inputs via the Special Measurements dialogue of the configuration tool. The voltage values are updated once per fundamental frequency cycle, i.e. the integration time for true RMS calculation is one fundamental cycle. 2.3 Registers The following values are recorded: maximum for each channel with date and time stamps minimum for each channel with date and time stamps The registers can be reset via the RESET input, or over the serial bus or the local MMI. 4

5 Substation Automation 2.4 Actual voltage measurement Actual voltage values are displayed in voltages and as p.u. values. The parameter Phase selection is used for selecting the voltages to be measured. If a voltage has not been selected, the actual voltage value will be zero and the supervision functions are not executed on that particular voltage. 2.5 Maximum and minimum s Maximum and minimum average functions are implemented by means of a function that calculates the linear average of the voltages measured over a settable average time interval (parameter Average interval ). A new average value is obtained once a minute, indicating the actual over the average time interval preceding the update time. The actual rolling average values are stored in the memory until the value is updated at the end of the following time interval. Actual s are measured separately in each channel. If the new value exceeds the maximum average value recorded, the actual average value will replace the maximum average value recorded. Should the new actual average be smaller than the minimum average recorded, the actual average value will replace the recorded minimum average. Maximum and minimum values are provided with date and time stamps. Maximum and minimum values are cleared when the registers are reset. 2.6 Zero value supervision and zero value detection A voltage below 1.0% U n is forced to 0% U n. This allows the noise in the input voltage to be ignored. The zero value supervision is fixed to 1.0% U n and is always active. The zero value detection function is used to force a voltage value update if it deviates slightly from zero or is zero. Zero value detection operates so that once a voltage passes (upwards or downwards) the limit 1.0% U n, the new voltage value is spontaneously reported to the master device (MicroSCADA), provided the threshold supervision with an absolute threshold or the integration method is in use (see the control parameter Threshold select ). 5

6 Substation Automation 2.7 Threshold supervision with absolute threshold Three different methods can be used for threshold supervision (also known as delta supervision) and the method to be used is selected with the parameter Threshold select. Parameter Phase selection can be used to select which phases are supervised. In absolute threshold supervision, the function block compares the actual voltage value with the last reported value. If the actual value exceeds the last reported value plus the set Threshold value or is below the last reported value minus the set Threshold value, the actual value is spontaneously reported to the master device and will replace the last reported value. Voltage Voltage value update Voltage value update Reported value + Threshold value - Threshold value Reported value Minimum threshold 0 Execution task cycle Figure 2. Operation of threshold supervision with absolute algorithm Note that the setting Time interval has no effect on the absolute method. 6

7 Substation Automation 2.8 Threshold supervision with integrator algorithm In threshold supervision with integrator algorithm, the function block calculates the difference between the last reported voltage value and the actual value for each task cycle. The difference is added to the internal accumulated (integrated) value register. If the accumulated delta exceeds the set Threshold value multiplied by time interval, the actual value is spontaneously reported to the master device and will replace the last reported value. Also the internal threshold difference register is reset and the supervision starts over. The settings Threshold value and Time interval can be interpreted as follows: threshold defines the accuracy of the measured quantity and time interval defines the response time, i.e. the longest time period the changed value can wait before being transmitted. Figure 3. Operation of threshold supervision with integrator algorithm Example 1: Measurement value has changed 1% after the last sent measurement value. Threshold value = 1% and Time interval = 1s -> new measurement value is sent after 1 second. Example 2: 7

8 Substation Automation Measurement value has changed 1% after the last sent measurement value. Threshold value = 1% and Time interval = 2s -> new measurement value is sent after 2 seconds. Example 3: Measurement value has changed 2% after the last sent measurement value. Threshold value = 10% and Time interval = 2s -> new measurement value is sent after 10 seconds. 2.9 Threshold supervision with time-based function If the time-based threshold supervision is used, the function block sends the values to the master device at intervals selected with the control parameter Time interval. Note that threshold setting has no effect on the time-based method Limit value supervision For all three phase voltages, up to four different limits can be monitored. The parameter Limit selection is used to specify the limit to be supervised and monitored. Each phase and limit is checked independently, which means that if a phase voltage exceeds several limits during an execution task cycle, each exceeding of limit is reported to the master device independently. The hysteresis of each limit is fixed to 1% of the nominal value and taken into account as shown below. Each exceeding of limit with a time stamp is stored with the FIFO method. The outputs HighWarning, HighAlarm, LowWarning and LowAlarm are activated as shown below. The warning and alarm limits can be changed on-line. 8

9 Substation Automation Figure 4. Operation of limit value monitoring 9

10 Substation Automation 3. Parameters and Events 3.1 General Each function block has a specific channel number for serial communication parameters and events. The channel for MEVO3A is 204 and that for MEVO3B 206. The data direction of the parameters defines the use of each parameter as follows: Data direction Description R, R/M Read only W R/W Write only Read and write The different event mask parameters (see section Control settings ) affect the visibility of events on the MMI or on serial communication (LON or SPA) as follows: Event mask 1 (FxxxV101/102) Event mask 2 (FxxxV103/104) Event mask 3 (FxxxV105/106) Event mask 4 (FxxxV107/108) SPA / MMI (LON) LON LON LON For example, if only the events E3, E4 and E5 are to be seen on the MMI of the relay terminal, the event mask value 56 ( ) is written to the Event mask 1 parameter (FxxxV101). In case a function block includes more than 32 events, there are two parameters instead of e.g. the Event mask 1 parameter: the parameter Event mask 1A (FxxxV101) covers the events and Event mask 1B (FxxxV102) the events

11 Substation Automation 3.2 Control settings Parameter Code Values Unit Default Data directio n Explanation Phase selection V ) - 0 R/W Selection of channels to be measured Average interval V ) - 1 R/W Time interval for average value Threshold select V ) - 0 R/W Selection of threshold supervision algorithm Threshold value V x Un 0.01 R/W Threshold value for threshold supervision Limit selection V ) - 0 R/W Selection of monitored limits High warning V x Un 1.00 R/W High warning limit value High alarm V x Un 1.10 R/W High alarm limit value Low warning V x Un 0.00 R/W Low warning limit value Low alarm V x Un 0.00 R/W Low alarm limit value Time interval V s 1 R/W Time interval for threshold supervision Event mask 1A V R/W Event mask 1 for event transmission (E0...E29) Event mask 1B V R/W Event mask 1 for event transmission (E32...E61) Event mask 2A V R/W Event mask 2 for event transmission (E0...E29) Event mask 2B V R/W Event mask 2 for event transmission (E32...E61) Event mask 3A V R/W Event mask 3 for event transmission (E0...E29) Event mask 3B V R/W Event mask 3 for event transmission (E32...E61) Event mask 4A V R/W Event mask 4 for event transmission (E0...E29) Event mask 4B V R/W Event mask 4 for event transmission (E32...E61) 1) Phase selection 0 = Uch1&Uch2&Uch3; 1 = Uch1 & Uch2; 2 = Uch2 & Uch3; 3 = Uch1 & Uch3; 4 = Uch1; 5 = Uch2; 6 = Uch3 2) Average interval 0 = 1 min; 1 = 5 min; 2 = 10 min; 3 = 15 min; 4 = 30 min; 5 = 60 min 3) Threshold select 0 = Not in use; 1 = Absolute alg.; 2 = Integrat. alg.; 3 = Time interval 4) Limit selection 0 = Not in use; 1 = HW, HA, LW, LA; 2 = HW, HA; 3 = LW, LA; 4 = HW, LW; 5 = HA, LA; 6 = HW; 7 = HA; 8 = LW; 9 = LA 11

12 Substation Automation 3.3 Measurement values Input data Parameter Code Values Unit Default Data direction Explanation UL1_U12 I kv 0.00 R/M Voltage U L1 _U 12 in voltages UL2_U23 I kv 0.00 R/M Voltage U L2 _U 23 in voltages UL3_U31 I kv 0.00 R/M Voltage U L3 _U 31 in voltages UL1_U12 I x Un 0.00 R/M Voltage U L1 _U 12 in percent UL2_U23 I x Un 0.00 R/M Voltage U L2 _U 23 in percent UL3_U31 I x Un 0.00 R/M Voltage U L3 _U 31 in percent UL1_U12 average I kv 0.00 R/M Average value of U L1 _U 12 in voltages UL2_U23 average I kv 0.00 R/M Average value of U L2 _U 23 in voltages UL3_U31 average I kv 0.00 R/M Average value of U L3 _U 31 in voltages UL1_U12 average I x Un 0.00 R/M Average value of U L1 _U 12 in percent UL2_U23 average I x Un 0.00 R/M Average value of U L2 _U 23 in percent UL3_U31 average I x Un 0.00 R/M Average value of U L3 _U 31 in percent Input RESET I13 0 or 1 1) - 0 R/M Signal for resetting the demand values and registers of the function block 1) Input RESET 0 = Not active; 1 = Active 12

13 Substation Automation Recorded data Parameter Code Values Unit Default Data direction Explanation U1_12 max date V201 YYYY-MM-DD - - R/M Date of U L1 _U 12 maximum U1_12 max time V202 hh:mm:ss R/M Time of U L1 _U 12 maximum U1_12 max (kv) V kv 0.00 R/M Maximum average of U L1 _U 12 in voltages U1_12 max (pu) V x Un 0.00 R/M Maximum average of U L1 _U 12 in percent U2_23 max date V205 YYYY-MM-DD - - R/M Date of U L2 _U 23 maximum U2_23 max time V206 hh:mm:ss R/M Time of U L2 _U 23 maximum U2_23 max (kv) V kv 0.00 R/M Maximum average of U L2 _U 23 in voltages U3_23 max (pu) V x Un 0.00 R/M Maximum average of U L2 _U 23 in percent U3_31 max date V209 YYYY-MM-DD - - R/M Date of U L3 _U 31 maximum U3_31 max time V210 hh:mm:ss R/M Time of U L3 _U 31 maximum U3_31 max (kv) V kv 0.00 R/M Maximum average of U L3 _U 31 in voltages U3_31 max (pu) V x Un 0.00 R/M Maximum average of U L3 _U 31 in percent U1_12 min date V213 YYYY-MM-DD - - R/M Date of U L1 _U 12 minimum U1_12 min time V214 hh:mm:ss R/M Time of U L1 _U 12 minimum U1_12 min (kv) V kv R/M Minimum average of U L1 _U 12 in voltages U1_12 min (pu) V x Un 2.00 R/M Minimum average of U L1 _U 12 in percent U2_23 min date V217 YYYY-MM-DD - - R/M Date of U L2 _U 23 minimum U2_23 min time V218 hh:mm:ss R/M Time of U L2 _U 23 minimum U2_23 min (kv) V kv R/M Minimum average of U L2 _U 23 in voltages Table continues on the next page. 13

14 Substation Automation Parameter Code Values Unit Default Data direction Explanation U2_23 min (pu) V x Un 2.00 R/M Minimum average of U L2 _U 23 in percent U3_31 min date V221 YYYY-MM-DD - - R/M Date of U L3 _U 31 minimum U3_31 min time V222 hh:mm:ss R/M Time of U L3 _U 31 minimum U3_31 min (kv) V kv R/M Minimum average of U L3 _U 31 in voltages U3_31 min (pu) V x Un 2.00 R/M Minimum average of U L3 _U 31 in percent Events Events : Code Weighting coefficient Default mask Event reason Event state E0 1 0 UL1 High warning reset E1 2 0 UL1 High warning activated E2 4 0 UL2 High warning reset E3 8 0 UL2 High warning activated E UL3 High warning reset E UL3 High warning activated E UL1 High alarm reset E UL1 High alarm activated E UL2 High alarm reset E UL2 High alarm activated E UL3 High alarm reset E UL3 High alarm activated E UL1 Low warning reset E UL1 Low warning activated E UL2 Low warning reset E UL2 Low warning activated E UL3 Low warning reset E UL3 Low warning activated E UL1 Low alarm reset E UL1 Low alarm activated Table continues on the next page. 14

15 Substation Automation Code Weighting coefficient Default mask Event reason Event state E UL2 Low alarm reset E UL2 Low alarm activated E UL3 Low alarm reset E UL3 Low alarm activated E UL1 Delta E UL2 Delta E UL3 Delta 15

16 Substation Automation Events : Code Weighting coefficient Default mask Event reason Event state E U12 High warning reset E U12 High warning activated E U23 High warning reset E U23 High warning activated E U31 High warning reset E U31 High warning activated E U12 High alarm reset E U12 High alarm activated E U23 High alarm reset E U23 High alarm activated E U31 High alarm reset E U31 High alarm activated E U12 Low warning reset E U12 Low warning activated E U23 Low warning reset E U23 Low warning activated E U31 Low warning reset E U31 Low warning activated E U12 Low alarm reset E U12 Low alarm activated E U23 Low alarm reset E U23 Low alarm activated E U31 Low alarm reset E U31 Low alarm activated E U12 Delta E U23 Delta E U31 Delta 16

17 Substation Automation 4. Technical Data Operation accuracies Depends on the frequency of the voltage measured: f/f n = : ±1.0% of set value or ± 0.01 x U n Accuracy class of the operation Accuracy class of the operation is 1.0 Configuration data Task execution interval (Relay Configuration Tool): 40 ms at the rated frequency f n = 50 Hz Technical revision history Function block Technical revision MEVO3A B - Change C Event reason and event state in the event table changed as follows (an example): Event reason: U1 high warning U1 Event state: Reset High warning reset D Input data: Units removed from parameter names Warning and alarm outputs added Names of the voltage inputs changed: E U1_12 UL1_U12, etc. Added time-based threshold function: - a new value for Threshold select : Time interval - parameter Time interval added MEVO3B A - B Input data: Units removed from parameter names Names of the voltage inputs changed: C U1_12 UL1_U12, etc. See above: MEVO3A E 17

COCB_ Circuit Breaker (2 state inputs/ 2 control inputs)

COCB_ Circuit Breaker (2 state inputs/ 2 control inputs) MRS752348-MUM Issued: 0/997 Version: F/23.6.2005 Data subject to change without notice COCB_ Circuit Breaker (2 state inputs/ 2 control inputs) Contents. Introduction... 3. Features... 3.2 Application...

More information

SPEF 3A2 C. Fault indicator. User s manual and Technical description SPEF 3A2 C. f n SPA. Serial port. RS AA Ser.No.

SPEF 3A2 C. Fault indicator. User s manual and Technical description SPEF 3A2 C. f n SPA. Serial port. RS AA Ser.No. SPEF 3A2 C Fault indicator User s manual and Technical description SPA f n = 50Hz x 60Hz U aux =24V- REGISTERS 0 1 I L1 [ A] 2 I L2 [ A] 3 I L3 [ A] 4 t ( I > )[%] 5 I o [ A] 6 t ( I o > )[%] 7 I [%] 8

More information

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage LINETRAXX VME420 Multi-functional monitoring relay for undervoltage, overvoltage and frequency monitoring in AC/DC systems with separate supply voltage VME420_D00026_01_D_XXEN/06.2016 LINETRAXX VME420

More information

Analog Annunciator Unit SACO 16 A3. Product Guide

Analog Annunciator Unit SACO 16 A3. Product Guide Issued: Aprill 1999 Status: Updated Version: C/20.03.2006 Data subject to change without notice Features Powerful, flexible and field-customizable 16-channel analog input signal annunciator unit A full

More information

Installer Manual KNX Touchscreen Thermostat

Installer Manual KNX Touchscreen Thermostat Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY

More information

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry LINETRAXX VMD420 Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry VMD420_D00137_02_D_XXEN/06.2016 LINETRAXX VMD420 Multi-functional

More information

02/11/2015

02/11/2015 MIC48 With RS 485 link Part number 89422418 Heating and / or cooling function 2 independent alarms Load break detection 2 setpoint which can be selected remotely Manual / automatic power adjustment RS

More information

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual Revision 6/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

ICS Regent. Fire Detector Input Modules PD-6032 (T3419) ICS Regent Fire Detector Input Modules (T3419) Issue 1, March, 06 Fire detector input modules provide interfaces for 16 fire detector inputs such as smoke detectors, flame detectors, temperature detectors,

More information

ECO N DATE DESCRIPTION OF CHANGE CHG

ECO N DATE DESCRIPTION OF CHANGE CHG Model Number: M21E-24-DIN Description: The product is a loop powered device which controls an unsupervised dual pole output channel suitable to manage 24VAC loads. The M21E-24-DIN is micro-controller operated,

More information

02/11/2015

02/11/2015 CTH 46 - CTD 43 / 46 CTD 46 Part number 89422108 CTH 46 Heating / cooling function Measurement and setpoint display CTD 43 Heating or cooling function Measurement display Measurement deviation display-setpoint

More information

REA 105 Arc Protection Module. Operator s Manual

REA 105 Arc Protection Module. Operator s Manual REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5

More information

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number ST71-KHJV.3 Temperature controller Order number 921.8 Wiring diagram Product description The switching outputs of the thermal controller can be programmed as -two-point controller with alarm -three-point

More information

LineGuard 2300 Program User Manual (FloBoss 107)

LineGuard 2300 Program User Manual (FloBoss 107) Form A6251 Part Number D301346X012 November 2012 LineGuard 2300 Program User Manual (FloBoss 107) Remote Automation Solutions Revision Tracking Sheet November 2012 This manual may be revised periodically

More information

FUNCTIONAL DESCRIPTION DIS01

FUNCTIONAL DESCRIPTION DIS01 We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB FUNCTIONAL DESCRIPTION

More information

Advanced Autoclave Controller with Recording + 4 Channel Mapping + Pressure Indication with PC Software & Printer Module

Advanced Autoclave Controller with Recording + 4 Channel Mapping + Pressure Indication with PC Software & Printer Module Clavex Plus Advanced Autoclave Controller with Recording + 4 Channel Mapping + Pressure Indication with PC Software & Printer Module PC Software Controller with Graphic Display Printer Module Features

More information

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description DPB52 True RMS 3-Phase, Multifunction monitoring relay Description Benefits Measuring Voltage Range. Very wide input voltage range: from 125 to 624V ( 208V 40% to 480 + 30% ). Adjustable Voltage Ranges

More information

Annunciator Unit SACO 16 D1. Product Guide

Annunciator Unit SACO 16 D1. Product Guide Issued: Aprill 1999 Status: Updated Version: C/20.03.2006 Data subject to change without notice Features Flexible, field-customizable 16-channel annunciator unit Alarm channels activated by normally open

More information

MO n : 12JMC rév A

MO n : 12JMC rév A CTT8 MO n : rév A Page 2 / 18 MODIFICATIONS Rev. Description Date Checked by Approuved by Z Creation 2012/02/12 JMC LA A First issue 2012/02/14 JMC LA INDEX Page 3 / 18 GENERALITY 4 INTRODUCTION 4 ACCESSORIES

More information

Operating instructions

Operating instructions MA00929301 09/2015 Operating instructions ED10429002 ESYLUX GmbH An der Strusbek 40 22926 Ahrensburg Germany info@esylux.com www.esylux.com 1 Table of contents 1 Using the manual 8 2 Safety instructions

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

WIO200 Water In Oil measuring instrument

WIO200 Water In Oil measuring instrument WIO200 Water In Oil measuring instrument You have made the right decision by choosing a measuring instrument from PAJ Systemteknik. Many customers buy our high standard products every year. There are at

More information

RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C. Operating Manual

RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C. Operating Manual Operating Manual RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C Residual current monitor with one analogue output signal for monitoring AC-, DC- and pulsed DC currents in TN- and TT systems Software

More information

DOCUMENTATION IPS640

DOCUMENTATION IPS640 DOCUMENTATION IPS640 TECHNICAL AND APPLICATION DESCRIPTION Authors: Nebojša Božič, Peter Hauner Last modification: 2017-01-25 2001-2017 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details,

More information

DOCUMENTATION IPS640

DOCUMENTATION IPS640 DOCUMENTATION IPS640 TECHNICAL AND APPLICATION DESCRIPTION Authors: Nebojša Božič, Peter Hauner Last modification: 2018-07-06 2001-2018 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details,

More information

FlameGard 5 MSIR HART

FlameGard 5 MSIR HART FlameGard 5 MSIR HART Multi-Spectral Infrared Flame Detector HART Communication with the FlameGard 5 Multi-spectral Infrared Detector The information and technical data disclosed in this document may be

More information

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) IRDH375_D00124_01_D_XXEN/07.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product

More information

Description of the application programme for KNX occupancy detectors version 3.1

Description of the application programme for KNX occupancy detectors version 3.1 Contents 1. General...1 1.1 Basics for the KNX/EIB BUS...1 1.2 Application versions...1 1.2 Application versions Switchgear application Version 3.1: BEG_SWI_HKL_V3.1 Part numbers: 1.3 Symbols used...1

More information

CTT8 TEMPERATURE MONITOR DEVICE

CTT8 TEMPERATURE MONITOR DEVICE INSTRUCTION MANUAL IM302-U v2.3 CTT8 TEMPERATURE MONITOR DEVICE GENERALITY The device of control temperatures CTT8 is used in the control of electric machine, transformer, motor, etc. where it s possible

More information

1. General Safety Block diagram Description of operation Connections Commissioning...11

1. General Safety Block diagram Description of operation Connections Commissioning...11 5($ 2SHUDWRU V0DQXDO 056080 Issued: 01.07.2002 Version: A/04.07.2002 Checked: HS Approved: RH 5($ We reserve the right to change data without prior notice. &RQWHQWV 1. General...4 1.1. Features...4 2.

More information

REPEATER FS5200R INSTRUCTION MANUAL

REPEATER FS5200R INSTRUCTION MANUAL REPEATER FS5200R INSTRUCTION MANUAL Instruction Manual Page1 CONTENTS 1. Introduction... 3 2. Function... 3 3. Technical data... 3 4. Contents of delivery... 4 5. General information... 5 6. Duty Mode...

More information

ST Wiring diagram. Product description. Standard temperature controller. Order number

ST Wiring diagram. Product description. Standard temperature controller. Order number ST64-31.10 Standard temperature controller Order number 900197.007 Old Id.Nr.: 386169 Wiring diagram Product description The controller ST64-31.10 was developed for simple thermostatic controls. The round

More information

FIRERAY 5000 range USER GUIDE

FIRERAY 5000 range USER GUIDE FIRERAY 5000 range USER GUIDE 0044-003-04 IMPORTANT PLEASE NOTE: The beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the Detector initiating a Fire or Fault signal.

More information

EasyTronic III MANUAL SERVICE

EasyTronic III MANUAL SERVICE rev.6 EasyTronic III MANUAL SERVICE General characteristics: Power supply 24 Vac ±15% Max consumption at 24Vac 300mA Relay outputs 6 Maximum relay current 8 A res. Serial standard RS232 2 Serial standard

More information

Dew point set DS 400

Dew point set DS 400 set DS 400 Dew point set DS 400 for stationary dew point monitoring of refrigeration or adsorption dryers. The touch screen graphic display enables an intuitive operation and shows the progress of the

More information

Installation Manual Tracker 221

Installation Manual Tracker 221 Installation Manual Tracker 221 KSR KUEBLER AG Im Kohlstatterfeld 17 D-69439 Zwingenberg / Germany www.ksr-kuebler.com Contents About this Installation Manual...4 Description Tracker 220-series...4 Installing

More information

Communications None RS-232C RS-422* RS-485* BCD Transmission output*/** (4 to 20 ma) E5AX- E5AX- L(M)A02 L(M)A03

Communications None RS-232C RS-422* RS-485* BCD Transmission output*/** (4 to 20 ma) E5AX- E5AX- L(M)A02 L(M)A03 Digital Controller A 96 x 96-mm (DIN) Digital Process Controller Optimum PID control with feed-forward control circuitry. High accuracy (+0.3% FS +1 digit max.). Replaceable Output Units. Models with communications

More information

Fire Control Panel FS5100

Fire Control Panel FS5100 Fire Control Panel FS5100 INSTRUCTION MANUAL Revision 6/02.11 Contents 1. Introduction... 5 2. Terminology... 5 3. Function... 7 4. Technical data... 7 4.1. Modules... 7 4.1.1. Type of modules... 7 4.1.2.

More information

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63 Fire Extinguishing Control Panel FS5200Е INSTRUCTION MANUAL Revision 8/01.17 Instruction Manual Page 1 1. 2. 3. 4. 4.1. 4.2. 4.2.1. 4.2.2. 4.2.3. 4.2.4. 4.2.5. 4.2.6. 4.2.7. 4.2.8. 4.2.9. 4.2.10. 4.2.11.

More information

SD2. Differential Controller. Operating and Installation Instructions F2 72.3

SD2. Differential Controller. Operating and Installation Instructions F2 72.3 SD2 Differential Controller Operating and Installation Instructions F2 72.3 i Please follow the safety information and read these Instructions carefully before putting the system into operation. Safety

More information

SCHMIDT LED Measured Value Display MD Instructions for Use

SCHMIDT LED Measured Value Display MD Instructions for Use SCHMIDT LED Measured Value Display MD 10.010 Instructions for Use Table of Contents 1 Important Information... 3 2 Application range... 4 3 Mounting instructions... 4 4 Electrical connection... 6 5 Signalizations...

More information

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number Worldwide Supplier of Safety Solutions GfG Instrumentation 1194 Oak Valley Drive #20 Phone: 734-769-0573 Fax: 734-769-1888 E-Mail: info@gfg-inc.com Internet: www.gfg-inc.com GMA 301 Operation Manual Part

More information

Modbus protocol REGO I

Modbus protocol REGO I Modbus protocol REGO 5200 6 720 814 720-01.1I MODBUS PROTOCOL REGO 5200 REGO 5200, program version: 1.1-0-04 Document version 1.0 --------- Data types, Type, Scale, Offset & Function ----------------------------------------------------------------------

More information

ENV 06. Update Electronics Service Mode and Alarms

ENV 06. Update Electronics Service Mode and Alarms ENV 06 Update Electronics Service Mode and Alarms ENV 06 Introduction ENV 06 = Electrolux New Vision 2006 New electronic platform for washing machines and tumble dryers New design for all Electrolux household

More information

Wireless Weather Station with Solar Transmitter Instruction Manual

Wireless Weather Station with Solar Transmitter Instruction Manual Wireless Weather Station with Solar Transmitter Instruction Manual Table of Contents Page 1. Introduction...2 2. Inventory of contents......2 Feature of the base station.... 2 Feature of wind sensor...

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

Local Control Network - building controls in perfection

Local Control Network - building controls in perfection Installation guide Local Control Network - building controls in perfection Sensor module for DIN rail mounting The is a sensor module for building installation in Bus technology. It has the same functions

More information

Annunciator unit. Application

Annunciator unit. Application Issued: April 1999 Status: April 1999 Version: B/09.11.2001 Data subject to change without notice Features Flexible, field-customizable 16-channel annunciator unit Alarm channels activated by normally

More information

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems LINETRAXX RCMA420 Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems RCMA420_D00059_01_D_XXEN/06.2016 LINETRAXX RCMA420 Residual current monitor for monitoring AC,

More information

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow

More information

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax: Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 505 Grünberg Tel.: 060 807-0 Fax: 060 807-59 A-ISOMETER IRDH575 Insulation monitoring device for unearthed AC, DC and AC/DC systems (IT systems) with

More information

Connections, displays and operating elements C D E G H. Installing the control unit

Connections, displays and operating elements C D E G H. Installing the control unit 1 2 3 GB Control unit 0-10 V REG-K/3-gang with manual mode Operating instructions Art. no. MTN646991 ¼ DANGER Risk of fatal injury from electrical current. All work on the device should only be carried

More information

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011 October 2011 PACSystems* RX3i Thermocouple Input Module, 12 Channels, IC695ALG412 The PACSystems * Thermocouple Input module IC695ALG412 provides twelve isolated differential thermocouple input channels.

More information

Ethernet General Purpose

Ethernet General Purpose Ethernet General Purpose Technical Manual Revision 1.03 8 November 2013 Pakton Technologies IO PAE224 Ethernet GPIO Manual.docx Page 1 of 22 Revision 1.03 Last updated 8/11/2013 Table of Contents INTRODUCTION...3

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual Revision 4/01.17 Contents 1. Introduction... 6 2. Terminology... 6 3. Function... 8 4. Technical data... 8 4.1. Physical configuration...

More information

FCD-wire Contents. List of Figures

FCD-wire Contents. List of Figures FCD-wire Contents FCD-X21 Configuration 1 Introduction... 1 2 Opening the FCD Application... 1 3 FCD Window... 2 4 FCD LEDs... 3 5 Configuration Operations... 4 FCD Info...4 FCD System Info...5 FCD Interface

More information

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual Revision 1.03 8 November 2013 JVA Technologies Ethernet General Purpose IO Technical Manual www.jva-fence.com.au Table of Contents INTRODUCTION...3 Scope and Purpose...3 Glossary...3 SPECIFICATIONS...4

More information

FCR 05, FCR 07. Power factor correction controller. User and service manual

FCR 05, FCR 07. Power factor correction controller. User and service manual FCR 05, FCR 07 Power factor correction controller User and service manual version 2.3 Czech Republic Czech Republic 1 Content 1. Control and signal elements... 3 2. Device description... 4 3. Instruction

More information

APPLICATION NOTE. Document Type. Application Note. Document Title. Date January Version DS0167/Iss 2. ESP Technical Summary

APPLICATION NOTE. Document Type. Application Note. Document Title. Date January Version DS0167/Iss 2. ESP Technical Summary APPLICATION NOTE Document Type Document Title Application Note ESP Technical Summary Date January 2001 Version DS0167/Iss 2 ESP TECHNICAL SUMMARY ESP the communication solution for today's intelligent

More information

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new

More information

and Channel indicator and monitoring unit B Operating Instructions 2.00/

and Channel indicator and monitoring unit B Operating Instructions 2.00/ and Channel indicator and monitoring unit B 70.0202 Operating Instructions 2.00/00375947 Contents 1 Instrument functions... 3 1.1 Ordering details... 3 1.2 Functions of the LMD-96... 4 1.3 Functions of

More information

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems) ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits (IT systems) IR425-D4_D00039_04_D_XXEN/05.2017 ISOMETER IR425 Insulation monitoring device for unearthed AC/DC control circuits

More information

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

EARTH LEAKAGE RELAY. User Manual - Issue 1.0 Earth Leakage Relay www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters EARTH

More information

PTE0705 Electric Fence Monitor

PTE0705 Electric Fence Monitor PTE0705 Electric Fence Monitor The JVA logo is a registered trademark of JVA Technologies. JVA Technologies. TABLE OF CONTENTS DESCRIPTION... 2 QUICK START GUIDE... 3 FEATURES... 4 EXPLANATION OF TERMS...

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current

More information

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17

Q-SMART MODBUS KIT. Modbus Protocol & Parameters. Cod EN rev.a ed.08/2018. Q-SMART Software Version AE17 Q-SMART MODBUS KIT Modbus Protocol & Parameters Cod.001085120EN rev.a ed.08/2018 Q-SMART Software Version AE17 Index 1 Modbus Protocol on Q-SMART... 4 1.1 Broadcasting... 4 1.2 Data Protection... 4 1.3

More information

Operating Manual RCM420

Operating Manual RCM420 Operating Manual RCM420 Residual current monitor for AC current monitoring in TN and TT systems Software version: D240 V1.2x TGH1410en/03.2012 Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Germany

More information

Sentry G3 Machinery Protection Monitor

Sentry G3 Machinery Protection Monitor TECHNICAL INFORMATION Sentry G3 Machinery Protection Monitor CONDITION MONITORING SOLUTIONS The Sentry G3 Machinery Protection Monitor is a high performance signal conditioning unit; providing a universal

More information

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12 AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual RST-5000 Series Web Enabled Input Module Rev. A2, 1/12 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com RST-5000

More information

NOVALYNX CORPORATION MODEL 200-WS-21-A DUAL SET POINT WIND ALARM INSTRUCTION MANUAL

NOVALYNX CORPORATION MODEL 200-WS-21-A DUAL SET POINT WIND ALARM INSTRUCTION MANUAL NOVALYNX CORPORATION MODEL 200-WS-21-A DUAL SET POINT WIND ALARM INSTRUCTION MANUAL REVISION DATE: JAN 2005 Receiving and Unpacking Carefully unpack all components and compare to the packing list. Notify

More information

Tubular motor with encoder for awnings series EUROPLUS

Tubular motor with encoder for awnings series EUROPLUS Tubular motor with encoder for awnings series EUROPLUS ALLMATIC S.r.l 00 Lentiai - Belluno Italy Via dell-artigiano, n Z.A. Tel. 07 77 76 r.a. Fax 07 706 http://www.allmatic.com - E-mail: info@allmatic.com

More information

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS NOVA PD56 Series Thermocouple, RTD, & Process Inputs Universal Power Supply 1-24 VAC Up to 3 Alarm Relays Retransmitting 4-2 ma Output Input Max/Min

More information

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller

Mounting and Operating Instructions EB 5610 EN. TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller TROVIS 5600 Automation System TROVIS 5610 Heating and District Heating Controller Mounting and Operating Instructions Electronics from SAMSON EB 5610 EN Firmware version 1.40 Edition December 2014 Controller

More information

www. ElectricalPartManuals. com Annunciator unit Features Self-contained microprocessor-based annunciator unit with 64 alarm channels Application

www. ElectricalPartManuals. com Annunciator unit Features Self-contained microprocessor-based annunciator unit with 64 alarm channels Application Features Self-contained microprocessor-based annunciator unit with 64 alarm channels pplication larm channels activated by normally open or normally closed contact Small and large stand-alone annunciator

More information

TER Active Room Temperature Sensor (Controller),

TER Active Room Temperature Sensor (Controller), Product sheet SN1.415 Type TER TER Active Room Temperature Sensors (Controllers) The TER active sensors are designed to detect temperature in the room spaces. The TER sensors have linear 0..10V signals

More information

ADDENDUM TO: RE: INSTALLATION INSTRUCTIONS FOR 5140XM CONTROL USE WITH ISSUE: N6019V1 Feature Changes and New Program Fields This addendum applies to 5140XM Controls which are shipped with firmware EPROM

More information

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006 PolyGard Controller LGC/LG2-04 Multi-Point Controller Serial Number S00 User Manual Preliminary Version August 11, 2006 January 04, 2016 Revision Specifications subject to change without notice. USA 160104

More information

FUNCTIONAL DESCRIPTION AIS01

FUNCTIONAL DESCRIPTION AIS01 We reserve all rights in this document and in the information contained therein. Reproduction,use or disclosure to third parties without express authority is strictly forbidden. ABB AB; 2002 FUNCTIONAL

More information

ST Wiring diagram. Product description. Four-stage controller. Order number

ST Wiring diagram. Product description. Four-stage controller. Order number ST96-35.16 Four-stage controller Order number 99.2 Wiring diagram Product description The four-stage controller with 4-digit setpoint and actual value display, 3 keys and 4 relays was developed for the

More information

Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e

Micro-controller X C C1 C2 AL1 AL2 AL3. Model: PXR4/5/9. Operation Manual SEL PXR. ECNO:406e C C1 C2 AL1 AL2 AL3 Micro-controller X Model: PXR4/5/9 PXR SEL Operation Manual ECNO:46e Table of Contents Part Names and Functions... 6 Operations... 7 2-1 Parameter list... 7 2-2 Basic operations...

More information

SBEx-4 BISTATE SEPARATOR 1, 2, 3 or 4 channels in rail housing (TS35, 22,5mm width)

SBEx-4 BISTATE SEPARATOR 1, 2, 3 or 4 channels in rail housing (TS35, 22,5mm width) SBEx-4 BISTATE SEPARATOR,, 3 or 4 channels in rail housing (TS3,,mm width) - group I category (M), group II and III category () accompanying device, - intrinsically safe input circuits with ia protection

More information

Module Features are-configurable, no module jumpers to set

Module Features are-configurable, no module jumpers to set December 2011 PACSystems* RX3i Isolated Thermocouple Input Module, 6 Channels, IC695ALG306 Isolated Thermocouple Input Module, 12 Channels, IC695ALG312 Isolated Thermocouple Input module IC695ALG306 provides

More information

Independent Zone Control (I.Z.C.)

Independent Zone Control (I.Z.C.) Operation and Installation Guide Independent Zone Control (I.Z.C.) DELAYED INSTANT ARMED 1 2 3 4 7 5 6 8 9 * * fi Radionics R D279A Operation & Installation Guide 46456B Page 2 Copyright 2000 Radionics

More information

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15 with coupling device AGH675-7 and AGH675-7MV15 Device combination for insulation monitoring in unearthed AC, AC/DC and DC power systems (IT systems) IRDH275BM-7_D00123_03_D_XXEN/01.2017 with coupling device

More information

Process & TeMPerATUre UniversAl input DigiTAl MeTers

Process & TeMPerATUre UniversAl input DigiTAl MeTers Process & TeMPerATUre UniversAl input DigiTAl MeTers nova PD56 series Thermocouple, rtd, & Process inputs Universal Power supply 1-24 va c Up to 3 Alarm relays retransmitting 4-2 ma output input Max/Min

More information

Stand Alone DYNAGARD SP Operation Manual

Stand Alone DYNAGARD SP Operation Manual Stand Alone DYNAGARD SP Operation Manual Contents Page General Description 1 Detection Principle 1 For Your Safety 1 Design 2 Mounting 2 Mounting Position of DYNAGARD SP 2 Installation of Electrical Connections

More information

Product Description...3 Communication Interface...4 Client Interface...4. Accessible Registers...4 Data Format...4

Product Description...3 Communication Interface...4 Client Interface...4. Accessible Registers...4 Data Format...4 FAAST Fire Alarm Aspiration Sensing Technology Modbus USER GUIDE Table of Contents Product Description...3 Communication Interface...4 Client Interface...4 Accessible Registers...4 Data Format...4 Device

More information

VAC PLC. System Description

VAC PLC. System Description VAC PLC System Description Contents 1 General... 5 1.1 Expressions and phrases... 5 1.2 Locations... 5 1.3 Abbreviations and terms... 6 1.4 Function... 6 1.5 Parts... 7 1.5.1 PLC... 7 1.5.2 Point IO...

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and

More information

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Modular Standard HP Chiller 1/4 screw compressor with Carel driver Program for pco¹ pco 2 and pcoc Modular Standard HP Chiller 1/4 screw compressor with Carel driver Manual version 1.0 25 September 2003 Program code: FLSTDmMSDE Do we want you to save you time and money?

More information

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68)

Testing the System. Battery Test. Dialer Test. Fire Drill Test (Code + [#] + 69) One-Man Fire Walk-Test (Code + [#] + 68) F A 1 7 0 0 c Testing the System Battery Test When AC power is present, the FA1700C runs a brief battery test every 60 seconds to determine if there is a battery connected, and runs an extended battery

More information

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev. TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL Microener- Copyright 2010 FW 2.1 Date 01.12.2008 Rev. 0 1. Generality 3 2. Introduction 3 3. Accessories and Options 3 4. Installation 3 5. Connection

More information

USER MANUAL S203. Controller for three circuits. - control for 2 heating circuits - 1 domestic hot water control. Saving energy, creating comfort

USER MANUAL S203. Controller for three circuits. - control for 2 heating circuits - 1 domestic hot water control. Saving energy, creating comfort USER MANUAL S203 Controller for three circuits - control for 2 heating circuits - 1 domestic hot water control Saving energy, creating comfort This user manual consists of two parts. Issues that are intended

More information

N M AirControl AHU. Control manual

N M AirControl AHU. Control manual N 10.63 M 03-2016 AirControl AHU Control manual EN CONTENTS PAGE 1 - MONITORING AND CONTROL 2 1.1 The program 2 1.2 The HMI terminal 2 1.3 The controller 4 1.4 Description of the air handling units 4

More information

Applications and Examples

Applications and Examples Applications and Examples Comat AG Bernstrasse 4 CH-3076 Worb Tel. +41 (0)31 838 55 77 www.comat.ch info@comat.ch Fax +41 (0)31 838 55 99 Contents General remarks to the examples... 3 Applications, Examples

More information

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors Product sheet SN1.402 Type CDR-AL CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors CDR-AL sensors are designed to detect carbon dioxide concentration and temperature in the room spaces. The units

More information

SUPERINTEND VRE-08/16/32/64

SUPERINTEND VRE-08/16/32/64 SUPERINTEND VRE-08/16/32/64 Residual Current Monitoring System (RCM) for Grounded Electrical Systems 8/16/32/64 supervision points Operator Manual v2.00 Superintend VRE-08/16/32/64 operator manual v2.00

More information

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1- DPR-45 User Manual V-2.0 (2..206) DPR-45 TEMPERATURE PROTECTION RELAY PT00 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT 9-50VDC SUPPLY DESCRIPTION DPR-45 is a precision unit designed for the temperature

More information