1 September Edmonton, AB Technician Tools CAN/ULC-S CAN/ULC-S Presented By: Mark Wilson
2 Disclaimer The following presentation is in no way affiliated with, or presented on behalf of any particular company, brand name or product. The purpose of this presentation is to highlight the proper tools required and does endorse or recommend any particular brand or product that may be shown.
3 Introduction Verify Test Inspect
4 Why is this important? Case Study Villeray Apartment Fire (Aug ) It was the smell of smoke, not the sound of a fire alarm, that sent several residents of an apartment building in Villeray running from an early morning fire. When firefighters arrived at the scene around 4 a.m. Wednesday, they had to rescue at least a dozen people still trapped inside. Fire department will investigate why the building's smoke detectors did not go off
5 Who can benefit? Fire Alarm Technicians Supervisors Engineers/Consultants Building Operators Maintenance Staff The customer!
6 CAN/ULC-S During the verification of a newly installed or modified fire alarm system, certain tools will be required in order to meet the intent of the ULC standard. Artificial Smoke Heat Source Air Velocity Meter Decibel Meter Electrical Meter Audibility Meter Screen/Pattern UV/IR Test Lamp CO Gas Smoke Det. Sensitivity Meter VI Stickers
7 CAN/ULC-S During the test and inspection of an active fire alarm system, certain tools will be required in order to meet the intent of the ULC standard. Artificial Smoke Extendable Pole Heat Source Decibel Meter Electrical Meter Audibility Meter Screen/Pattern UV/IR Test Lamp CO Gas Smoke Det. Sensitivity Meter Vacuum Inspection Stickers
8 Similarities: Verification Test/Inspection Artificial Smoke Extendable Pole Heat Source Air Velocity Meter Decibel Meter Electrical Meter Screen/Pattern UV/IR Test Lamp CO Gas Two way radios Smoke Det. Sensitivity Meter Intelligibility Meter Verification Stickers Artificial Smoke Extendable Pole Heat Source Air Velocity Meter Decibel Meter Electrical Meter Screen/Pattern UV/IR Test Lamp CO Gas Two way radios Smoke Det. Sensitivity Meter Battery Capacity Meter Vacuum Inspection Stickers
9 Smoke Each smoke detector shall be tested for operation by introducing smoke or simulated smoke to the detecting chamber in accordance with the manufacturer s instruction.
10 Heat Source Each heat detector shall be tested to confirm operability. NOTE: An open flame shall not be used for testing the operation of heat detectors.
11 Extendible Poles Can allow access up to 9m (30ft) without leaving the ground.
12 Multi-Stimulus Testers Smoke Heat CO Each combination type detector, using a combination of detection principles shall be tested to the requirements appropriate to each principle of operation and as recommended by the manufacturer.
13 Air Velocity Meter The positive airflow and/or sampling tube differential pressure in air duct type smoke detectors shall be tested to confirm that it is within manufacturer s specified limits.
14 Decibel Meter Appendix G (537-13) Sound Level Measurements G1.1 The sound level meter shall have a range as low as 35 dba. G2.1 The meter is to be held approx 1.5m above the floor and at least 0.5m away from hard reflecting surfaces. G2.2 The meter is to be set to the A weighted scale and to the fast response setting.
15 Electrical Multimeter
16 Beam Detector Testing Each beam type smoke detector shall be inspected and tested to confirm operability, including the following functions/features, as applicable: -Activation by the use of a manufacturer s recommended testing method for the device (e.g. screens, filters, etc.)
17 Flame Detector Testing Each flame detector shall be inspected and tested to confirm the operability as recommended by the manufacturer. All functions/features of the device shall be tested.
18 Testing CO Detectors Follow manufacturers recommendations for testing CO detectors
19 Two Way Radios
20 Smoke Sensitivity Tester Each smoke detector shall be tested to confirm that it is within its rated operating range using a test method described in clause Acceptable methods of determining the smoke detector sensitivity are: A- Manufacturers recommended test instrument, equipment, or method; B- Installed control units or transponders designed to test the sensitivity of individual smoke detectors; and C- Test instruments that provide calibrated sensitivity measuring operation as described in CAN/ULC-S529 Standard for Smoke Detectors for Fire Alarm Systems, acceptable to the AHJ.
21 Summary In order to complete the tests required by the ULC standards, we must ensure that the proper tools are made available for technicians to use. Being trained on what tools are required, as well as the proper way to use them is important. We owe it to our customers and the public to ensure that the life safety systems that are installed in buildings are installed properly, tested properly and will be ready to function when we need them.
22
Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS
HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable
More informationSOME OF THE MOST COMMON TESTING MISTAKES MADE BY TECHNICIANS PERFORMING VERIFICATIONS TO CAN/ULC S537-04
SOME OF THE MOST COMMON TESTING MISTAKES MADE BY TECHNICIANS PERFORMING VERIFICATIONS TO CAN/ULC S537-04 OR Some of the things that I done have wrong and was told how stupid I was! Why is it hard to make
More informationCanadian Fire Alarm Association. Fire Alarm System Activation. Fire Alarm with malfunction history
Canadian Fire Alarm Association Discussion topics False alarms Shut off notices Owner s responsibilities Documents required by AHJ Fire Alarm System Activation Fire detection (early warning at insipient
More informationAUSTIN FIRE DEPARTMENT SIA PROCEDURES FOR ANNUAL TESTING OF BUILDINGS WITH STAIRWELL AND VESTIBULE PRESSURIZATION SYSTEMS
AUSTIN FIRE DEPARTMENT SIA PROCEDURES FOR ANNUAL TESTING OF BUILDINGS WITH STAIRWELL AND VESTIBULE PRESSURIZATION SYSTEMS Building stairwell and vestibule pressurization systems must be retested and recertified
More informationFire Alarm and Life Safety System Inspection Certificate
Fire Alarm and Life Safety System Inspection Certificate For City of Rock Hill 757 S. Anderson Rd Rock Hill, AC 29730 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable
More informationA Building Manager s Guide to Maintaining Fire Code Compliance
A Building Manager s Guide to Maintaining Fire Code Compliance Know your role in conducting fire protection system inspections : Fire Alarm Codes and Standards Maintaining your compliance with fire code
More informationLouis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015
Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015 UL and the UL logo are trademarks of UL LLC 2012 GOALS OF INSPECTING AND TESTING POWER SUPPLIES Verify/inspect
More informationCOMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.
4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE
More informationAutomatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems
Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life
More informationCERTIFICATION BULLETIN
File: ULC-S527-11 ULC-G5.2 June 1, 2012 CERTIFICATION BULLETIN 2012-04 Effective Date Announcement CAN/ULC-S527-11, 3 rd Edition of the Standard for Control Unit for Fire Alarm Systems To: Subscribers
More informationPROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-02-07 Ontario-NBC CODE REFERENCE: Division B / 3.2.4.22. and 3.2.4.23. DESCRIPTION
More informationsolo detectortesters single testing system. complete range of testing tools. detectortesters testing technology from No Climb
solo TM A A single testing system. complete range of testing tools. testing technology from No Climb solotm A complete range of test and maintenance equipment for smoke, heat and CO detectors. Testing
More informationTrueAlarm Analog Sensing
TrueAlarm Analog Sensing UL, ULC Listed, CSFM Approved* Features Air aspiration duct smoke detection** system provides remote sensor location for ducts with difficult service access: Available as either
More informationMichigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE
PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationsolo detectortesters single testing system. complete range of testing tools. testing technology from No Climb
TM A A single testing system. complete range of testing tools. testing technology from No Climb TM A complete range of test and maintenance equipment for smoke, heat and CO detectors. Testing equipment
More informationCOURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE
COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE 100130 Description The first part of the course presents the requirements for fire alarm systems. It describes the buildings
More informationRF280THS. Installation Instructions Wireless (RF) Photoelectric Smoke Detectors
RF80THS EN Installation Instructions Wireless (RF) Photoelectric Smoke Detectors RF80THS Installation Instructions Trademarks Trademarks Chamber Check is a registered trademark of Bosch Security Systems
More informationGuidance Note. Guidance Document on Best Practice for Fire Detector Testing/Test Equipment
Guidance Note Guidance Document on Best Practice for Fire Detector Testing/Test Equipment Guidance Document on Best Practice for Fire Detector Testing/Test Equipment 1. SCOPE OF THIS DOCUMENT... 3 2. COMPETENCY
More informationProject No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10
Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction
More informationBOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm
1 BOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm Association 2 Presentation Overview The Codes Your responsibilities
More informationVERIFICATION OF FIRE ALARM SYSTEMS
DEVELOPMENT, BUILDINGS AND LICENSING Chief Building Official (CBO) and Building Code and Policy Building Policy Branch The intent of this bulletin is to clarify requirements of verification of the fire
More informationClarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group
Summary of Changes CAN/ULC-S524-06 Installation of Fire Alarm Systems Alan Cavers Area Manager Fire & Security Systems Group Course Title Rev Date: Summary of Changes Correct Deficiencies noted CAN/ULC-S524-01
More informationSmoke Detector Testing
Smoke Detector Testing Allen Hess CFAA Presentation April 2011 1 Building Technologies Agenda Requirements Consumer Needs Challenges with Industry Acceptance How siemens a Detector sans italic Works Effects
More informationAddressable Detectors & Bases
Edwards Signaling Catalog u Intelligent Initiating Addressable Detectors & Bases Detectors: E-PD, E-PHD, E-HD Bases: B4U, RB4U, IB4U, SB4U Overview Edwards intelligent addressable detectors are meticulously
More informationIncident Summary (Reference # )
Incident Summary (Reference #5605195) Incident Date September 13, 2016 Location White Rock Regulated industry sector Natural gas system and low voltage electrical system (30V to 750V) SUPPORTING INFORMATION
More informationTrueAlarm ES Analog Sensing
TrueAlarm ES Analog Sensing UL, ULC, CSFM Listed; FM Approved* Features TrueAlarm addressable sensor base with 520 Hz sounder TrueAlarm sensor bases with 520 Hz tone require a TrueAlarm photoelectric,
More informationType of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:
DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional
More informationSTUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017
STUDY AND TEST MATERIAL FOR THE FA2 and FA4 ASSESSMENTS (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 This document contains sample questions to help participants study for the FA2 and FA4
More informationBritish Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety
Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These
More informationBUILDING CODE INTERPRETATION
BUILDING CODE INTERPRETATION November 2017 14-BCI-009 Page 1 of 6 FIRE ALARM AND FIRE SUPPRESSION SYSTEM VERIFICATION AND TESTING CERTIFICATES PURPOSE This STANDATA has been developed to give municipalities
More informationCAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED
More informationCAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region
More informationLatest update: Ordinance of the Ministry of Internal Affairs and Communications No. 25 of March 27, 2013
This translation is provisional translation for reference, formally refer to the original text. Ordinance for Technical Specifications pertaining to Transmitters (Ordinance of the Ministry of Home Affairs
More informationCOMMISSIONING OF LIFE SAFETY AND FIRE PROTECTION SYSTEMS: WHAT, WHERE AND HOW?
COMMISSIONING OF LIFE SAFETY AND FIRE PROTECTION SYSTEMS: WHAT, WHERE AND HOW? By: Ark Tsisserev, P.Eng. Senior Technical Manager Applied Engineering Solutions Ltd. CFAA Technical Seminar April 15, 2015
More informationEl Reno Fire Department Fire Alarm Plan Review Worksheet
El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us
More informationRENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3
REPORT NUMBER: 101207560COQ-001b ORIGINAL ISSUE DATE: June 12, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Vipco Industries
More information275HVD NON-CONTACT, HIGH VOLTAGE DETECTOR DETECTOR DE ALTA TENSIÓN SIN CONTACTO
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com 275HVD NON-CONTACT, HIGH VOLTAGE DETECTOR DETECTOR DE ALTA TENSIÓN SIN CONTACTO
More informationI am Rick Jeffress and I handle sales for Fike Video Image Detection. We thank the AFAA for coordinating the venue for this presentation, and we
I am Rick Jeffress and I handle sales for Fike Video Image Detection. We thank the AFAA for coordinating the venue for this presentation, and we appreciate your taking the time to learn more about this
More informationSTANDARDS BULLETIN
June 2, 2008 STANDARDS BULLETIN 2008-08 CAN/ULC-S319-05, Electronic Access Control Systems FREQUENTLY ASKED QUESTIONS The following frequently asked questions (FAQ) is being issued in response to a request
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015
CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?
More informationBuilding Name: Our Lady of Sorrows Date: July 10, 2013
1 E1. FIRE ALARM SYSTEM ANNUAL TEST AND INSPECTION REPORT (Reference: 5.1.2) Building Name: Our Lady of Sorrows Date: July 10, 2013 Address 19 Mohns Avenue Petawawa, ON System Manufacturer: Siemens Model
More informationMAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS
FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are
More informationPresented to Resident Services, Operations and Personnel (RSOP) Committee September , 2015
San Francisco Housing Authority (SFHA) Work Order, Inspection and Fire Safety Analysis August 215 Presented to Resident Services, Operations and Personnel (RSOP) Committee September ------, 215 Table of
More informationTrueAlarm Analog Sensing
TrueAlarm Analog Sensing UL, ULC Listed* Addressable Duct Sensor Housings with TrueAlarm Photoelectric Sensor; Available with Multiple Relay Features Compact air duct sensor housing with clear cover to
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY
More informationAir Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)
FORM ASX-40021 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SM-501 Series Smoke Detectors, Model EXSAC and EXSAD (Ionization), EXSAJ and EXSAK (Photoelectric) Air Specialties Express, 448 S. Main
More informationConsultant Specification AGILE Wireless Fire Detection System
Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More informationCanadian Fire Alarm Association (CFAA)
An Overview of Changes in the New CAN/ULC-S524-06 Installation of Fire Alarm Systems Canadian Fire Alarm Association (CFAA) CAN/ULC - S524-01 STANDARD FOR THE INSTALLATION OF FIRE ALARM SYSTEMS Installation
More informationEarly Warning Fire Detection Engineering
Early Warning Fire Detection Engineering Conference Presentation Author: Adrian Haenni Senior Project Manager EARL WARNING Objective Nature of an Early Warning System Structured method for a successful
More informationStandards Manager Web Standards List ULC-Underwriters Laboratories of Canada
Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada Id Number Title Year Organization Page 1 ANSI.CAN.UL. NULL 2016 ULC 64 1201 2 CAN.ULC- NULL 2016 ULC 176 60839-11-1-2016 3 CAN.ULC-IEC
More informationElevator Emergency Equipment Instructor s Guide
Table of Contents Overview.......4 Sensory Inspection 11 Emergency Equipment in Elevator Systems..14 Fire Service Phase I & II 24 Summary..35 1 Icons Used In This Guide Agenda Topic # Topic Title Duration
More informationFire Alarm Inspection, Testing, Maintenance. Assuring the System s Operational Reliability
Fire Alarm Inspection, Testing, Maintenance Assuring the System s Operational Reliability What does AFAA-NE do? Education We supply the tools our members require to perform within the guidelines of our
More informationIntelligent Detection Devices
Intelligent Detection Devices Multi-Criteria Fire Detector [with ASAtechnology TM ] Advanced multi-criteria fire detector that has dual-optical and thermal sensors Differentiates between deceptive phenomena
More informationDetecting Your Needs Signaling Change
Detecting Your Needs Signaling Change The 2016 CFAA Alberta Technical Seminar Wednesday, September 21, 2016 The Canadian Fire Alarm Association 85 Citizen Court, Units 3 & 4, Markham, Ontario L6G 1A8 www.cfaa.ca
More informationGuidance Note. Fire Alarm Detector Applications and Documentation of the Selection
Guidance Note Fire Alarm Detector Applications and Documentation of the Selection Fire Alarm Detector Applications and Documentation of the Selection INTRODUCTION... 3 FLOW CHART FOR THE SELECTION OF...
More informationDNRHS Intelligent Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS DNRHS Intelligent Air Duct Smoke Detector Specifications Length: Width: Depth: Weight: Operating Temperature Range: Operating Humidity Range: Duct Air Velocity:
More informationAnnual Testing of Stairwell Pressurization Systems & Other Smoke Management Systems
Annual Testing of Stairwell Pressurization Systems & Other Smoke Management Systems Presented by Mike Locke, MechTech Inc. SIA All SIAs are listed in this presentation April 13, 2016 1 Reasons for Revisions
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationOWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE. John Percy, Public Education Officer Waterloo Fire Rescue
OWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE John Percy, Public Education Officer Waterloo Fire Rescue AGENDA: Fire Protection and Prevention Act and Ontario Fire Code Role of Assistants to
More informationTECHNICAL SPECIFICATIONS BUTTONS
Maxlogic beam type smoke detector consists of 2 parts as a receiver and transmitter. Should be mounted as facing each other between the distance of 5-100 m. The detector works on the principle of light
More informationAir Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)
FORM ASX-40020 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SL-2000 Series Smoke Detectors, Model EXSAA and EXSAB (Ionization), EXSAG and EXSAH (Photoelectric) Air Specialties Express, 448 S. Main
More informationFull Service Central Station Fire Alarm Listing Evaluation
Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm
More informationBY-LAW CONCERNING THE SERVICE DE SÉCURITÉ INCENDIE DE MONTRÉAL. In view of section 62 of the Municipal Powers Act (R.S.Q., chapter C-47.
VILLE DE MONTRÉAL BY-LAW RCG 12-003 BY-LAW CONCERNING THE SERVICE DE SÉCURITÉ INCENDIE DE MONTRÉAL In view of section 62 of the Municipal Powers Act (R.S.Q., chapter C-47.1); In view of the Civil Protection
More informationFIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES
FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationTitle: BFST1505 Syllabus
DEPARTMENT OF FINANCIAL SERVICES Division of State Fire Marshal Bureau of Fire Standards and Training Title: BFST1505 Syllabus Revision: April 5, 2018 Section I - Course Information Course Title: Fire
More informationSMOKE DETECTOR TESTERS
SMOKE DETECTOR TESTERS efficient universal integrated safe lightweight 9m reach endorsed Why testing is required... Codes and standards throughout the world define the testing and maintenance of fire detection
More information11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies
11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies Visible Signals Agenda 1. Physics 2. Installation Considerations
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationSK-Duct Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3432-001R 12 Clintonville Road Northford, CT 06472 203.484.7161; Fax: 203.484.7118 SK-Duct Air Duct Smoke Detector http://www.silentknight.com Specifications
More informationMODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces
MODULE 8 Tying the Systems Together: Emergency Control Functions and Interfaces 1 OVERVIEW OF MODULE 8 In this module we will: Describe all components, their arrangements and how the systems work Describe
More informationA Comparison of Rate Compensated Heat Detector Test Methods
A Comparison of Rate Compensated Heat Detector Test Methods Overview of Rate Compensated Fire Detectors Thermal switch technology invented by Wilfred J. Turenne in the 1920 s Have been mass produced as
More informationCity of Duluth Festival Center 04/25
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationSita200plus. 200detectors. Single loop analogue addressable System
Single loop analogue addressable System Fast short circuit isolator in every device 15 combinations of smoke & heat detection modes Loop length up to 2km long with spurs INTELLIGENT FIRE TECHNOLOGY A D
More informationGuidance on Video Smoke Detection Technology (VSD)
Guidance Note Guidance on Video Smoke Detection Technology (VSD) Guidance on Video Smoke Detection Technology (VSD) SCOPE... 3 INTRODUCTION... 4 WHAT IS VSD?... 5 STANDARDS... 7 GENERAL GUIDANCE ON THE
More informationTX7100. Intelligent Addressable Optical Smoke Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.
TX7100 Intelligent Addressable Optical Smoke Detector Installation and Operation Manual Technology Copyright 2015, All right reserved. Product Safety To prevent severe injury and loss of life or property,
More informationThe six tests conducted included three smoldering and three fast flaming type tests.
The Mayfield Village Tests On May 9, May 12 and May 13, 2014 NEOFPA conducted six full-scale, real-world smoke alarm comparison tests in the city of Mayfield Village, Ohio. Tests 5 and 6 conducted on May
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationD350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS
D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-1975-004R Before installing detectors, please thoroughly read the NEMA Guide for
More informationPQS Independent type-testing protocol
PQS Independent type-testing protocol WHO/XXX Original: English Distribution: General TITLE: Integrated electronic maximum-minimum thermometer, with factory programmed alarms, for vaccine refrigerators
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationInstallation Instructions
48/50A2,A3,A4,A5020-060, 48/50P2,P3,P4,P5030-100, 48/50N 75 to 105 Ton Return Smoke Detector Accessory Installation Instructions Part No. CRSMKDET002C00 CONTENTS GENERAL........................................
More informationSILENT KNIGHT. IntelliKnight Smoke Detector Cleaning and Testing Instruction. Equipment Needed. Testing Equipment. Cleaning Equipment
SILENT KNIGHT IntelliKnight Smoke Detector Cleaning and Testing Instruction This document contains information necessary to properly test and clean analog photoelectric and ionization smoke detectors connected
More informationDate Issued: December 14, 2017 Revision: 2.1
2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,
More informationFire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC
PART 1 GENERAL 1.01 SUMMARY SECTION 23 08 00 COMMISSIONING OF HVAC A. This section covers the Contractor's and Commissioning Authority (CA) responsibilities for commissioning; each subcontractor or installer
More informationStandard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.
A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable
More informationEmis. Unit Description:
1030459 88666 PERCHLOROETHYLENE DRY CLEANERS COMPLIANCE INSPECTION CHECKLIST INSPECTION TYPE: ANNUAL (INS1, INS2) COMPLAINT/DISCOVERY (CI) RE-INSPECTION (FUI) ARMS COMPLAINT NO: AIRS ID#:103 0459 Date:
More informationFire Signal Receiving Centres vs. Proprietary Fire Signal Receiving Centres CAN/ULC-S561 ALAN CAVERS ULC
Fire Signal Receiving Centres vs. Proprietary Fire Signal Receiving Centres CAN/ULC-S561 ALAN CAVERS ULC Reliable Fire Alarm Monitoring Why is it important? Codes and Standards? What is a fire alarm monitoring?
More informationAustralian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670.
AS 1670.1 2004 (Incorporating Amendment No. 1) AS 1670.1 2004 Australian Standard Fire detection, warning, control and intercom systems System design, installation and commissioning Part 1: Fire This Australian
More informationInstructions. Duct Mount Accessory Q Rev: 11/
Instructions Duct Mount Accessory Q5016 Rev: 11/16 95-8752 Table of Contents DESCRIPTION...1 FEATURES...1 OPERATION...1 SPECIFICATIONS.... 2 INSTALLATION... 2 Detector Location...2 Tools for Assembly...4
More informationSynco living combines individual room control with consumption data acquisition
Synco living combines individual room control with consumption data acquisition Saving energy with innovative home automation Answers for infrastructure. Synco living so many ways to save energy You can
More informationBULLETIN BU/EL Revised August 11, 2015
BULLETIN 2000-019-BU/EL Revised August 11, 2015 TRANSMITTING UNIT FROM PROTECTED PREMISES TO FIRE SIGNAL RECEIVING CENTRE IN CONFORMANCE WITH CAN/ULC-S561 The intent of this bulletin is to clarify the
More information97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL
Page 2 of 16 EXPLANATORY MATERIAL In November 1996, the Fire Technical Council introduced a guideline entitled "Approved Fire Safety Guidelines for Apartment Buildings". The guideline was established under
More informationDNR-AUS Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3642-000R DNR-AUS Duct Smoke Detector Specifications Operating Temperature: 20 to 70 C ( 4 to 158 F) 0 C to 49 C (32 F to 120 F) with module installed in the
More informationIce*Meister Model 9734-SYSTEM INDUSTRIAL ICE DETECTING SENSOR SYSTEM Technical Data Sheet
1 Ice*Meister Model 9734-SYSTEM INDUSTRIAL ICE DETECTING SENSOR SYSTEM Technical Data Sheet Figure 1 Ice*Meister Model 9734-SYSTEM optical ice sensing detector system is easy to install and completely
More informationShut Down The Fan: A Reprise by Dean K. Wilson, P.E.
Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Shut Down The Fan: A Reprise by Dean K. Wilson, P.E. Question: My grandfather passed away last summer. He had spent many years as a fire fighter. Among
More informationPRODUCT GUIDE. Fire Alarm & Life Safety Test & Maintenance Products
PRODUCT GUIDE Fire Alarm & Life Safety Test & Maintenance Products SDi is the world s leading provider of specialized equipment for the fire protection and security industries. With a commitment to offering
More informationDUCT LEAKAGE (Page 1 of 3)
(Page 1 of 3) Note: Submit one Certificate of Acceptance for each system that Enforcement Agency Use: Checked by/date must demonstrate compliance. HERS verification required. This form used for duct pressure
More information