Automatic Sprinkler Systems Care and Maintenance
|
|
- Veronica Bradley
- 6 years ago
- Views:
Transcription
1 0-0.0 January 2012 Country of Origin: United Kingdom Automatic Sprinkler Systems Care and Maintenance Introduction...1 Weekly Inspection and Tests...2 Monthly Inspection and Tests...3 Service and Maintenance Schedule...3 Quarterly Inspections...3 Half-Yearly Inspection and Tests...4 Annual Inspection and Tests...5 Three-Yearly Inspection and Tests...5 Ten-Yearly Inspection and Tests...6 Twenty Five Year Inspections...6 Planning for Repair or Extension Works...7 Action on Alarm and/or Sprinkler Operation...8 Summary...8 Useful References...9 Introduction Automatic sprinkler systems form a vitally important part of fire protection, and a properly installed system is an extremely effective means of fighting fire and protecting life and property. The management and maintenance of fire water supplies and sprinkler systems are essential risk control measures. To ensure that sprinkler performance is not impaired, it is essential that designated staff are given the responsibility of overall care and maintenance standards and that faults are identified, reported and acted upon immediately. A competent person should be nominated to undertake specified tasks relating to the care and maintenance of the sprinkler systems. Only appropriately trained personnel shall be permitted to undertake testing of the sprinkler systems or emergency actions.
2 Weekly Inspection and Tests The following checks are to be performed by trained staff or an approved contractor on at least a weekly basis or more frequently as required. All valves, especially the main stop valve and alarm isolation valves, are in the correct standby position and secured by padlocks and straps. All gauges showing correct pressure and indicator lamps showing normal condition. Pump and valve rooms kept clear of combustible storage and are readily accessible. Water in private reservoirs, rivers, canals, water storage tanks and pump priming tanks are at correct levels. Visual inspection of sprinkler system. Sprinklers, pipework and hangers undamaged. Each water motor alarm bell tested to ensure they provide a good continuous ring for no less than 30 seconds. Check functionality of remote signalling to alarm monitoring control room and, ensure this is reset following the tests. Complete sprinkler test card for each main installation valve. Any unusual deviations which cannot be easily corrected should be reported to management, and if unresolved to Zurich or your insurance advisor. On air pressure tanks, the air compressor and water make-up pump should be tested to ensure they are operational. The water level and air pressure needs to be checked and the sight level glass drained and isolated. The whole system should be checked for leaks. On water storage tanks the water level indicator should be checked. If low, the operation of the ball valve should be tested and the tank water level verified and topped up as necessary. In winter, the pipe insulation, electric trace heating cables and immersion heaters should be checked for being operational. Tests on the automatic pumps should include the following: Check the fuel and lubricating oil levels. The automatic pumps should be individually started by reducing the pressure on the pump initiation pressure switch and the pressure at which each pump activates should be recorded. Check the cooling water from the pump cooling system. On engines with closed cooling systems, the coolant levels should be checked. Check the diesel pump oil pressure. If automatic ventilation louvres are fitted, check that these open when the diesel pump starts. 2
3 Immediately after the pump start test, each diesel pump is to be run for 30 minutes or the time recommended by the pump manufacturer. After the test the engine is to be stopped and immediately restarted using the manual start test button. NOTE - Any anomalies found during this testing should be reported and if significant, rectified by an approved fire pump specialist. Heating Systems and Pipework Trace Heating Wet systems are susceptible to frost. Freezing of a small part of the system may result in water damage that could render the protection inoperable. During the winter months, all localised heating and trace heating systems, fitted to prevent freezing of the sprinkler systems, are to be checked for correct function. The temperature is to be maintained above 4 C in all areas where wet sprinkler systems are fitted. In pumphouses containing diesel pumps the temperature must be maintained above 10 C, at all times. Dry and alternate valves are to be checked to ensure that they are protected from frost. Monthly Inspection and Tests To be performed by trained staff, or an approved contractor, at least monthly, or more frequently as required. The electrolyte level of all batteries is to be checked including the diesel engine starter batteries. The water storage tank is to be externally inspected ensuring that the ball float housing is locked and the access ladders are secured against unauthorised use. Service and Maintenance Schedule The tasks identified below should be undertaken by a competent person such as from a sprinkler servicing contractor or fire pump specialist. Quarterly Inspections Review of Hazard A review of any changes to the structure, occupancy, storage arrangements, heating or equipment of a building should be carried out in order that the appropriate corrective action may be taken. The review should include the following: Have there been any building alterations, such as: new mezzanines, offices, ceilings or have there been any changes to the occupation with different plant or machinery? All these may necessitate alterations to the sprinkler protection to ensure the protection remains effective. Is the ambient temperature of the building and pumphouse within the acceptable limits for the design of the sprinkler system? Are other frost protection measures adequate and has the electrical supply feeding trace heating cables been checked? 3
4 Has there been any painting or redecoration works undertaken since the last inspection and have any sprinkler heads been contaminated? Is the storage type still consistent with the sprinkler system design i.e. free standing storage has not been changed to rack storage? Are rack flues (both longitudinal and transverse) being maintained as designated by the design requirements. Are adequate clearances being maintained below the sprinkler heads? Clearances should be 1000mm for high piled storage, 500mm for normal ordinary hazard areas and 150mm for in-rack sprinklers. Has the nature of stored goods or packaging materials changed? This may alter the category of storage. Have there been any changes to the storage arrangements i.e. plastic pallets, shelving, boxes or totes? Have there been changes to the storage heights? Is a suitable maintenance contract in force for any smoke or heat detection systems that interact with a sprinkler system (e.g. pre-action valves)? Have there been any alterations to the sprinkler system? Have there been any problems with the sprinkler system? Additional Checks All sprinkler heads, multiple jet controls and sprayers should be inspected for deposits. Any fly, dust or debris, with the exception of paint deposits, should be carefully removed or cleaned. Painted or damaged sprinkler heads, multiple jet controls or sprayers will need to be replaced. Flow switches on life safety systems need to be checked for correct function and operation. Half-Yearly Inspection and Tests The moving parts of dry valves, pre-action valves and any accelerators should be exercised at intervals of no more than six months, in accordance with the manufacturers instructions. Alternate valves are deemed to meet this requirement as they are by their very nature exercised twice yearly when they are changed from air to water, in the spring and water to air for the winter. Where flow-test equipment is installed at the main control valve sets they should be tested to verify the specified flows and pressures are achieved. Each sprinkler pump set should undergo a minor service by a fire pump specialist, in accordance with the manufacturer s recommendations. Each water supply pump needs to be tested at the full load condition, by use of the flow meter test line normally provided in the sprinkler pumphouse. Each pump should be able to achieve the pressure/flow stated on the pump data plate and the maximum calculated flow demand (if available) as determined by the sprinkler system design criteria. Low water level switches in the suction pump priming tanks should be tested for correct operation. 4
5 All stop valves, controlling the flow of water to the sprinkler systems, should be fully exercised to ensure they are in full working order and securely fastened in the correct position. Annual Inspection and Tests Each sprinkler pump set should undergo a major service by a fire pump specialist, in accordance with the manufacturer s recommendations. All float valves should be inspected in accordance with the manufacturers recommendations and be checked to ensure that they operate correctly. The valves should be exercised and greased as appropriate. Each sprinkler alarm valve to be internally inspected and cleaned. Any defects to be rectified. Alarm valve rubbers should be replaced at least every third year. Pipework and supports need to be checked for integrity and condition and rectified or replaced as necessary. Pipework found to be rusting should be cleaned and suitable red oxide paint applied. The electrical installation necessary to provide a remote alarm signal should be checked at least annually. The settling chambers, screens and filters on natural water supplies i.e. fed from rivers, canals and reservoirs, should be inspected and cleaned as necessary. Additional Measures for Foam Enhancement Systems Fire fighting foam induction facilities (bladder tanks, proportioners and associated trim) should be inspected and serviced by an approved specialist contractor. Checks and tests to include: A check for the presence of foam in the water surrounding the bladder. Samples of the foam concentrate to be taken and tested for correct composition, deterioration or solidification. Verification of the correct foam induction rate. That the foam bladder tank is full. That all valves and actuators are in good condition and in good working order. Three-Yearly Inspection and Tests The settling chambers, jackwells and screens, on natural water supplies i.e. fed from rivers, canals and reservoirs, should be inspected and cleaned. Pump suction foot valves should be removed and serviced. 5
6 Ten-Yearly Inspection and Tests Water Storage Tanks At no more that ten-year intervals water storage tanks need to be: Fully drained. Examined internally and externally for corrosion and fitness for purpose. Any corrosion or pin hole leaks should be repaired. Cleaned, as necessary. If the tank is fitted with a butyl liner then this should be inspected and fixed or restored in accordance with the manufacturers recommendations. Additional Measures for Foam Enhancement Systems Foam tank sight glass shall be removed & cleaned. The proportioner and all associated components to be inspected, removed if necessary, and checked for corrosion and correct operation. Any defective part subsequently found will need to be refurbished or replaced as appropriate. Twenty Five Year Inspections After 25 years the pipes and sprinkler heads should be inspected. The pipework should be thoroughly flushed and hydrostatically tested to a pressure equal to the maximum standing pressure or 12 bars, whichever is the greater. The pipework should be externally & internally inspected. At least 1 metre of range pipe for every 100 sprinklers should be taken out of the system for inspection. A minimum of two 1 metre sections for each diameter of pipework should be inspected. In the case of wet systems, at least 1 sprinkler installation per building should be checked up to a maximum of 10% of installations for large buildings with multiple systems. A sample of sprinkler heads should be taken from the system and sent to an approved testing laboratory to establish that the sprinklers installed still function correctly. The number of sprinklers chosen to be sent for testing should be based on the total number of sprinklers installed at the site and a sample should be taken from differing areas of the building. The table below shows how many heads should be tested. Total Number of Sprinkler Heads Number of Heads to be Tested Up to 5, Up to 10, Up to 20, Up to 30, Up to 40, Should any of the tests show serious defects in the pipework or the sprinkler heads, further investigations should be carried out to determine the best course of action, which may ultimately include the replacement of all the sprinkler heads of a given type in a particular area or even the replacement of complete sections of the system. 6
7 Planning for Repair or Extension Works Where maintenance of a sprinkler system or building fabric is anticipated that will result in impairment of the sprinkler protection, a written maintenance plan should be prepared by the user prior to commencement of the work. Before Work Begins The following procedures should be included in the plan: Notification of the works provided to the authorities (including the insurers) and any central alarm station. Designation of named person to undertake specified tasks, liaise with contractors and relevant authorities. Identification of resources required for the maintenance period. Inspection, review and repair of passive and other fire protection measures including doors, gaseous extinguishing systems and portable fire extinguishers. Reduction of stocking levels of hazardous goods such as flammable liquids and aerosols. Notification to the sprinkler contractors of the company procedures and regulations with which they are required to comply e.g. work permits, hot work prohibitions etc. Considerations to minimising the area of protection isolated at any one time. Review of a written method statement prepared by the sprinkler contractor. Ensuring that all necessary tools, equipment and trained personnel are available. Consultation with staff about the work plan, increasing awareness and precautionary measures. Procurement of additional portable fire extinguishing appliances in the affected area and ensuring that personnel are trained. Issue of work permit to commence. While Maintenance Work is in Progress Suspension of operations, in particular any hazardous processes, machinery or plant. Implementation of regular fire patrols. Before and After Re-commissioning the System Hydrostatic pressure testing of the modified pipework or pipe extensions. Water supply performance tests to be carried out if changes have been made to the water supply. Notification of all key personnel, authorities and the alarm receiving station of the reinstatement of the sprinkler protection. 7
8 Checks to ensure that all valves, switches and control equipment have been restored to their correct setting. Provision of a written statement or certificate by the sprinkler contractor that the work has been completed and the system is fully operational. Action on Alarm and/or Sprinkler Operation When the Alarm Sounds Staff should be instructed to call the fire and rescue service on hearing the alarm and follow the normal fire procedures for the premises. The fire and rescue service should be called, even if there is an automatic remote alarm station connection, in order to confirm that an alarm has been received. Only after contacting the fire and rescue service should the cause of the alarm be investigated, if it appears safe to do so. On no account, other than the express command of the fire and rescue service, should sprinkler isolating valves be closed unless it is certain that there is no fire or that it has been extinguished. Even if the fire has been extinguished in one area, the entire building should be searched before any valves are closed as there may be more than one seat of fire. The decision to shutdown a sprinkler installation, zone or pumped water supply, which has operated because of a fire, should only be taken by the fire and rescue service. Reinstatement Following the shutdown after operation of an installation, the operated sprinklers are to be replaced by heads of the correct type and temperature rating. The water supply can then be restored. Unopened sprinklers around the area in which operation took place shall be checked for damage by heat or other causes and replaced as necessary. False Alarms Damaged pipework, leaks and sprinkler heads can cause alarms to sound. Repair and reinstatement should be carried out immediately. Action Following Sprinkler Operation Components removed from the system should be retained by the user for possible examination by an authority or insurance company. Incident Report The building and contents insurers should be informed of any incident whether or not an insurance claim has been made. Summary Once installed, sprinkler systems can provide fire protection to a building for many years. Maintaining the system is essential to ensuring that the installation continues to operate effectively. Like any working system, a sprinkler installation is more likely to fail if it is not being maintained. This Risktopic includes details on a range of maintenance details of weekly tests that can be undertaken by a trained member of your own staff, through to 25 yearly checks that should be undertaken by a specialist sprinkler engineer. By following the recommendations in this Risktopic your sprinkler system is more likely to operate effectively in the event of a fire. 8
9 Useful References 1. BS EN Technical Bulletin 203: 2009: 1 9
10 The information contained in this document has been compiled and obtained from sources believed to be reliable and credible but no representation or warranty, express or implied, is made by Zurich Insurance plc (UK Branch) or any of its associated companies (collectively the "Zurich Group") as to their accuracy or completeness. Please note that some of the information contained herein may be time sensitive. Information relating to risk engineering is intended as a general description of certain types of risk engineering services available to relevant customers. The Zurich Group does not assume any liability of any kind whatsoever, resulting from the use, or reliance upon any information, material or procedure contained herein. The Group does not guarantee particular outcomes and there may be conditions on your premises or within your organisation which may not be apparent to us. You are in the best position to understand your business and your organisation and to take steps to minimise risk, and we wish to assist you by providing the information and tools to assess your changing risk environment. CONTACT Risk Engineering Risk Support Services 126 Hagley Road Edgbaston Birmingham B16 9PF Phone +44 (0) For more information please visit: Zurich Management Services Limited, Registered in England and Wales no , Registered Office: The Zurich Centre, 3000 Parkway, Whiteley, Fareham, Hampshire PO15 7JZ UKGI484 01/12
Management Practices: Fire Protection Impairments November 2015
RiskTopics Management Practices: Fire Protection Impairments November 2015 When business capital is invested in fire protection, it is difficult to explain any fire protection outage that allows a fire
More informationStatutory Compliance Checklist
Date of Issue: April 2017 Statutory Compliance Checklist This document is for clergy and churchwardens to help them in the maintenance of their Churches. Refer to supplementary notes for further guidance.
More informationCold weather regions where temperatures can fall below freezing present a threat to any building housing water-filled systems.
RiskTopics Management practices Cold weather freeze-ups August 2015 Cold weather regions where temperatures can fall below freezing present a threat to any building housing water-filled systems. Introduction
More informationLegal Requirements. There is no general legal requirement to install sprinklers. in places of work
01 A sprinkler system is a pipework distribution system charged with water, with a network of heatsensitive sprinkler heads supplied via a tank/reservoir or a water main. If the temperature rises above
More informationFixed Fire Protection Getting it right, Ensuring Performance and Value
Fixed Fire Protection Getting it right, Ensuring Performance and Value 18 th May 2017 Stuart Lloyd, EngTech TIFireE Principal Risk Engineer Practice Leader Fire Protection Engineering Zurich Risk Engineering
More informationFIRE PROCEDURES 1. APPOINTMENTS
12b FIRE PROCEDURES 1. APPOINTMENTS Responsible Person In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO), the School s Head, Mrs C Cameron is appointed as the Responsible Person for
More informationEMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be
EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety
More informationNitin Ventures FZE. (A Division of Nitin Fire Protection Industries Ltd.)
Model : A TECHNICAL DATA : Model Nominal Size Maximum Service Pressure Threaded Opening Mounting Flange Connection Trim Factory Hydrostatic Test Pressure Frictional Loss in Terms of Equivalent Length of
More informationElectrical Safety Policy and Management System
TITLE: PAGE: 1 OF 14 Housing Solutions Limited Electrical Safety Policy and Management System Page 1 of 15 TITLE: PAGE: 2 OF 14 FOREWORD This document details the system for the management of electrical
More informationMaintenance of Fire Systems
Maintenance of Fire Systems Duty Holder Facilities Manager Responsible Person By John Briggs All Fire Facilities, equipment, systems and devices are required by law to be subject to a suitable system of
More informationLogbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater
APPROVED BY: JBJ Precept EN Fire Detection/Alarm Panel & Precept EN Repeater Logbook PAGE 1 of 19 List of Contents 1. FIRE ALARM SYSTEM MAINTENANCE... 3 2. USER RESPONSIBILITIES... 3 2.1. RESPONSIBLE PERSON...
More informationMAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES
SHIPPING NOTICE Maritime Authority of the Cayman Islands Head Office 3 rd Floor, Government Administration Building, 133 Elgin Avenue PO Box 2256, Grand Cayman, KY1-1107, Cayman Islands Tel: +1 345 949
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationINTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3
INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change
More informationUltra cold freezer storage. Risk management guide for research materials
Ultra cold freezer storage Risk management guide for research materials An education establishment s research can underpin their financial strength and reputation Grants worth millions of pounds are often
More informationFalse Sense of Security???
IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire
More information161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures
161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means
More informationLocal Rules: Fire Safety
1. Potential Effects of a Fire A small fire is most likely to cause damage to equipment and furniture, with the potential to cause additional smoke damage to the room of origin. A large and protracted
More informationFire Safety Management
Fire Safety Management Procedure () FIRE SAFETY MANAGEMENT PROCEDURE Contents Section 1: Management of Fire Safety Procedure in Operation Section 2 Organisational responsibilities Section 3: Emergency
More informationFIRE SAFETY LOG BOOK
FIRE SAFETY LOG BOOK Regulatory Reform (Fire Safety) Order 2005 If you own, manage or operate a business, you will need to comply with fire safety law. The main law is the Regulatory Reform (Fire Safety)
More informationMAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and
More informationFIRE RISK ASSESSMENT Self Assessment
FIRE RISK ASSESSMENT Self Assessment Important! This fire risk assessment form is to be filled in by the responsible person within a business or organisation. As this is a free download for the use of
More informationF I R E S A F E T Y R E G I S T E R
F I R E S A F E T Y R E G I S T E R (Short Version) Cork County Fire Department www.corkcoco.ie April 2015 Introduction 1.1 Section 18(2) of the Fire Services Acts, 1981 and 2003 generally applies to all
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationPREMISES FIRE SAFETY LOGBOOK
0844 740 3473 PREMISES FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: AN INTRODUCTION TO YOUR LOG BOOK. The Regulatory Reform (Fire Safety) Order 2005 (FSO) requires that the
More informationNFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,
NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101
More informationFire Safety Log Book 41 page fire safety log book to record all your fire S afety checks Unique Fire Bordesley Green East Stechford Birmingham B33 8RU
Fire Safety Log Book 41 page fire safety log book to record all your fire Safety checks Unique Fire Bordesley Green East Stechford Birmingham B33 8RU Bordesley Green East Stechford Birmingham B33 8RU 0121
More informationCharlotte Building, 17 Gresse Street, London W1T 1QL
Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of
More informationISLE OF WIGHT FIRE & RESCUE SERVICE
ISLE OF WIGHT FIRE & RESCUE SERVICE Record of Fire Safety Equipment Testing Fire Drills & Training CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS
More informationSlight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk
Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review Minooka Fire Protection District Maintaining Your Fire Safety Systems Fire continues to be a major threat
More informationIndex. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9
Index Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8 Fire Risk Assessments 9 Fire Alarm Systems 10-20 Locations 10 Servicing 11 12 Activations 13 14 Weekly Checks
More informationWell managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.
Record of significant findings Risk assessment for : Assessment undertaken by : Horsefair House Nigel Billing CMIOSH Date: 28/3/17 Overview of Premises: 2 buildings on 3 stories in an L shaped configuration,
More informationModel: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance
Model: 400E-5M Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset Installation Operation Maintenance Application Engineering Bermad 1. Safety First BERMAD believes
More informationSheetz Inc. Fire Protection Service Guidelines
Sheetz Inc. Fire Protection Service Guidelines Overview The following are guidelines for Sheetz Fire Protection Services for the 2016/2018 contract year. Each key area is listed below with the appropriate
More informationLoss Prevention Standards
Introduction Fire compartmentation is an essential part of an effective fire safety design of a building. The primary objective of fire compartmentation or passive fire protection is to prevent a building
More informationLoss Prevention Standards
Introduction Arson continues to be a significant risk to organisations in the UK, and is one of the leading causes of fires within commercial premises, accounting for nearly half of all fires attended
More informationCanadian Fire Alarm Association. Fire Alarm System Activation. Fire Alarm with malfunction history
Canadian Fire Alarm Association Discussion topics False alarms Shut off notices Owner s responsibilities Documents required by AHJ Fire Alarm System Activation Fire detection (early warning at insipient
More informationBERMAD Fire Protection
Model: 400E-3M Bermad Electro-Pneumatically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with
More informationGuidelines for Fire Safety Plans at Construction or Demolition Sites
Guidelines for Fire Safety Plans at Construction or Demolition Sites Sun Peaks Fire Rescue P.O. Box 1000, Sun Peaks, V0E 5N0 Phone 250-578-8985 Fax 250-578-8905 Guidelines for Fire Safety Plans at Construction
More informationGuidance on Statutory Inspections Scheduling Tool
Guidance on Statutory Inspections Scheduling Tool This Guideline has been produced solely for use by State Authorities that come within the remit of the State Claims Agency, as established by the National
More informationFuture Fit Risk Engineering 2017 Global Risk Engineering Conference
Future Fit Risk Engineering 2017 Global Risk Engineering Conference 18 th / 19 th May 2017 Gary Howe EngTech FIFireE MIFPO Senior Fire Protection Engineer Fixed Fire Protection Getting it right, Case studies
More informationEquipment Maintenance Checklist
The Hartford Steam Boiler Inspection and Insurance Co. One State Street P.O. Box 5024 Hartford, CT 06102-5024 Tel: 800-333-4677 Fax: 484-582-1811 Internet: http://www.hsb.com Equipment Maintenance Checklist
More informationHealth, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service
Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in
More informationFire safety management issues identified by fire risk assessments
Health and Safety Safety Team The University of Manchester Waterloo Place, 180 Oxford Road, Manchester Health and M13 Safety 9GP www.manchester.ac.uk To From Vice-Presidents/Deans, Heads of Schools and
More informationBuilding Standards Division. Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems
Building Standards Division Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems Crown Copyright 2015 Produced by the Buildings Standards Division February 2015 Version
More information1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.
Record of significant findings Risk assessment for : Assessment undertaken by : 71a The Close Nigel Billing CMIOSH Date: 21/3/17 Overview of Premises: 1970s building housing main school reception and support
More informationNOTTINGHAM CITY HOMES
APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes
More informationClassNK Technical Information No. TEC-0970 For any questions about the above, please contact: NIPPON KAIJI KYOKAI (ClassNK) Survey Department, Adminis
Subject Maintenance, inspection and test of Fire-Protection Systems and Appliances on board the Panama-registered ships To whom it may concern Technical Information No. TEC-0970 Date 31 October 2013 The
More informationH&S Forum. Fire Safety Policy Glascote Academy
Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote
More informationGovernment of Bermuda Bermuda Shipping and Maritime Authority BERMUDA SHIPPING NOTICE
Government of Bermuda Bermuda Shipping and Maritime Authority 2017 021 BERMUDA SHIPPING NOTICE Maintenance and Inspection of Fire Protection Systems, Appliances and Certain Emergency Equipment Ref: SOLAS
More informationDIRECTIVE NO: D-B
DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting
More informationFire Safety Register
Fire Safety Register Introduction 1.1 Section 18(2) of the Fire Services Acts, 1981 and 2003 generally applies to all premises other than a dwelling house occupied as a single private dwelling. This section
More informationFixed fire protection solutions
Risk Engineering Fixed fire protection solutions At a glance Fixed fire protection can reduce the severity of fire events and positively impact Risk Engineering Assessments. To provide an effective solution
More informationAllfire Site No. a division of Allsaved Ltd. Fire Safety Log Book. Premises Address: Responsible Person:
Site No. a division of Allsaved Ltd. Fire Safety Log Book Premises Address: Responsible Person: Introduction An Introduction to Your Fire Safety Log Book The Regulatory Reform (Fire Safety) Order 2005
More informationFIRE SAFETY LOGBOOK ADDRESS OF PREMISES NOMINATED RESPONSIBLE PERSON
FIRE SAFETY LOGBOOK ADDRESS OF PREMISES NOMINATED RESPONSIBLE PERSON SURESITE LTD. All rights reserved. Not to be reproduced without prior permission 23 AN INTRODUCTION TO YOUR LOG BOOK This fire safety
More informationFire Risk Management Policy. UK September 2017
UK September 2017 5 & 7 Diamond Court, Opal Drive, Eastlake Park, Fox Milne, Milton Keynes MK15 0DU, T: 01908 396250, F: 01908 396251, www.cognitaschools.co.uk Registered in England Cognita Limited No
More informationHealth & Safety Policy
THE HOME OF CYCLING Health & Safety Policy It is the policy of Quench (UK) Limited and all of its subsidiaries to have a commitment to the health & safety of all its employees whilst in the workplace,
More informationFire risk management plan. MH/05/Revised/06/17
Fire risk management plan MH/05/Revised/06/17 1 1. Scope This policy applies to fire safety arrangements in all workplaces, common areas of residential premises and any other premises managed and/or owned
More informationFIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre
FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job
More information3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL
3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:
More informationInspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems
Inspection of Fire Sprinkler Systems NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Objective To familiarize Facility Managers with the process of routine inspection
More informationControl Panel User Guide
Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification
More information6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL
6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)
More informationQualification Specification Highfield Level 1 Award in the Principles of Fire Safety Awareness (RQF)
Qualification Specification Highfield Level 1 Award in the Principles of Fire Safety Awareness (RQF) Qualification Number: 603/1564/7 Version 1.1 July 2017 Copyright 2017 HABC Ltd. All rights reserved
More informationA basic guide to... Fire Safety for Scout Premises
A basic guide to... Fire Safety for Scout Premises A basic guide to Fire Safety for Scout Premises This Guide has been designed and produced by Chubb Fire to assist persons responsible for fire safety
More informationPlanned Preventative Maintenance Schedule. Fire Suppression PPM Schedule
Planned Preventative Maintenance Schedule Fire Suppression PPM Schedule Support Planned and contracted maintenance services To ensure that data centre or building services are always operating to their
More informationFire Risk Assessment
Fire Risk Assessment Premises Description Address Area Post Code Tel no. Num of Employees Normal Occupancy Max Allowed Use of Premises Building Length Building Breadth Area 0.00 M² Floors Storeys Below
More informationChapter 4: Fire Protection Systems
Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE
FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification
More informationFor the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems
BAFE Scheme: SP203-1 Version 7.1: January 2019 FIRE SAFETY REGISTER Fire Protection Industry Scheme, Reference SP203-1 For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire
More informationEMERGENCY LIGHTING COMPLETION CERTIFICATE For small installations and verification of existing installations
A DETAILS OF THE CLIENT Client/ B DETAILS OF THE EMERGENCY LIGHTING INSTALLATION Extent of the installation covered by this certificate The Owner 19 Walker Grove, Hatfield, Hertfordshire 19 Walker Grove,
More informationFIRE SAFETY INSPECTIONS
FIRE SAFETY INSPECTIONS RCG002 (E)-v2-01/2017 Page 1 2017 Royal & Sun Alliance Insurance plc Introduction Most of us give little thought to our surroundings until an accident occurs. Who left the power
More information3500 CONVENTIONAL FIRE ALARM CONTROL PANEL
3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:
More informationTOTALPAC2 Integrated Fire Protection System
TOTALPAC2 Integrated Fire Protection System Page 1 of 8 General 1. Applicable Standards The TOTALPAC2 Surefire complies with the following standards: - NFPA-13 Sprinkler Systems; - NFPA-15 Water Spray
More informationFire Safety Management Audit Specification August 2017
Fire Safety Management Audit Specification August 2017 Membership Training Qualifications Audit and Consultancy Policy and Opinion Awards Contents Page 1 Introduction to the Fire Safety Management Audit
More informationhighline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10
highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned
More informationTHE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE
FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification
More informationSt Edward s Oxford FIRE SAFETY POLICY
FIRE SAFETY POLICY 1 CONTENTS Section Page No.(s) 1. Policy Statement 3-5 2. Organisation and Responsibilities 6 3. Responsibilities of Responsible Person 7-8 4. Responsibilities of Senior Management 9
More informationJune 2017 (Updated 18 January 2018) Fire Safety Policy. Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited
June 2017 (Updated 18 January 2018) Fire Safety Policy Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited Trusted provider of quality homes, excellent landlord and support services,
More informationAttachment 1. to ClassNK Technical Information No. TEC-1077 Isle of Man Ship Registry Manx Shipping Notice SOLAS II-2 The Maintenance and inspection o
Subject Periodical inspection, maintenance and tests of fire extinguishing system etc. on board for the Isle of Man flagged ships To whom it may concern Technical Information No. TEC-1077 Date 20 July
More informationDevelopments in Australian Standard AS (Emergency Lighting)
Developments in Australian Standard AS2293.2 (Emergency Lighting) Russell Porteous Chief Executive Officer, Firewize Australian Standards Committee LG-007 Disclaimer Firewize policy is one of continuous
More informationTHE FIRE SAFETY GUIDE FOR BUSINESS OWNERS
THE FIRE SAFETY GUIDE FOR BUSINESS OWNERS 0800 2211 8034 Table of Contents Part 1: Introduction Part 2: Who is Responsible? Part 3: What is Required? Fire Risk Assessments Appointment of Competent Persons
More informationSafety Practices Fire Protection Equipment Cold Weather
Page 1 of 14 Safety Practices Fire Protection Equipment Cold Weather Cold weather freeze-ups can damage or place vital fire protection systems out of service. Past losses include a single freezing-wind
More informationFIRE SAFETY MANAGEMENT PLAN
FIRE SAFETY MANAGEMENT PLAN February 2014 2 Document Control Revision: 1 Date: 4 February 2014 Status: Document change control: Approved by EPC Revision # Change Description Date Author 1 Initial document
More informationFebruary 2011 Country of Origin: United Kingdom. Arson Prevention
February 2011 Country of Origin: United Kingdom Arson Prevention Introduction... 2 Risk Assessment... 2 Exposure... 2 Type of Business/Occupation... 3 Location of Premises... 3 Relationships...4 Risk Controls...
More informationNewport City Council Bettws High School Fire Fighting Performance Specification CONTRACT C1
Fire Fighting Performance Specification CONTRACT C1 Fire Fighting Performance Specification August 2008 4 Pierhead Street, Capital Waterside, CF10 4QP Tel +44 2920 473727 Fax +44 2920 472277 This report
More informationManufacturing safety solutions
Manufacturing safety solutions 4 th Quarter 2011 Inside this issue Manufacturing property conservation and protection Manufacturing property conservation and protection by Robert Mauerman Upcoming events
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL
SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationTHE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY
THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY 8619 Westwood Center Drive Suite 300 Vienna, Virginia 22182, USA Tel: +1 703 790 3434 Fax: +1 703 790 5655 Email: safety@liscr.com Web: www.liscr.com
More information2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)
2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) Reference: Documents referenced for this bulletin are as follows: San
More informationFIRE SAFETY PLAN FIRST & JASPER JASPER AVENUE
FIRE SAFETY PLAN FIRST & JASPER 10065 JASPER AVENUE March 2014 Fire/Emergency Evacuation Procedures Introduction GWL Realty Advisors is the property management company responsible for the building located
More informationPurging of Fired Heater Coils Using Steam (Winterizing)
Purging of Fired Heater Coils Using Steam (Winterizing) What happened? Recently a serious injury occurred to a chemical truck operator s assistant when a diesel fired heater was being winterized by purging
More informationContractor Worksheet Underground Fires Major Hazard Standard
WMC Environment, Health & Safety Management System Worksheet Major Hazard Standard MHS-02 DocsOpen Ref: 57267, 17/10/2001 Uncontrolled copy check web for latest revision Revision Reviewed Description of
More informationPART 3-O REQUIREMENTS FOR SPRINKLER SYSTEMS MAINTENANCE AND SUPERVISION. 3-O Introduction O.1 Scope of Maintenance and Supervision...
CONTENTS Schedule of amendments for this part of the scheme document Page 1 of 14 3-O Introduction...3 3-O.1 Scope of Maintenance and Supervision...3 3-O.2 Certification conditions...5 3-O.3 LPS 1233 Service
More informationPre-Pack INTEGRATED PRE-ACTION SYSTEM
Pre-Pack INTEGRATED PRE-ACTION SYSTEM HD FIRE PROTECT TECHNICAL DATA MODEL Pre-Pack SIZE DELUGE VALVE MODEL RISER CHECK VALVE MODEL WATER MOTOR GONG BELL MAXIMUM WORKING PRESSURE SYSTEM END CONNECTION
More informationControl Panel User Guide (TO BE RETAINED BY THE USER)
Fire Detection & Alarm System Control Panel V3 (Suitable for Quadnet control panels from V2.00) Control Panel User Guide (TO BE RETAINED BY THE USER) 26-0585 Issue 7 Fike s policy is one of continual improvement
More informationT UNI 7000 F. Operating instructions For the user (2006/05) AU/GB
6 720 648 662-00.1T UNI 7000 F Operating instructions For the user AU/G 2 Contents Contents Contents 2 1 Safety information and explanation of symbols 3 1.1 For your safety 3 1.2 Explanation of symbols
More informationBMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT
BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT Guidance and Instructions for Ship-owners, Managers, Masters, Bahamas Recognised Organisations and Bahamas Approved Nautical Inspectors Note: This
More informationFire and Life Safety Review Form
Exits/Egress Fire and Life Safety Review Form 1. Doors shall swing in the direction of egress travel where serving and occupancy load of 50 or more. IFC 1010.1.2.1 2. Egress shall be readily openable from
More information