Safety Practices Fire Protection Equipment Cold Weather

Size: px
Start display at page:

Download "Safety Practices Fire Protection Equipment Cold Weather"

Transcription

1 Page 1 of 14 Safety Practices Fire Protection Equipment Cold Weather Cold weather freeze-ups can damage or place vital fire protection systems out of service. Past losses include a single freezing-wind and snow storm which caused $880 million of property damage in 41 states. If preventive maintenance is not perform on your automatic sprinkler system, cold weather may result in sprinkler pipe breakage, major water damage and an impaired automatic sprinkler system. A preventive maintenance program should be ongoing; however, it is particularly crucial during cold weather where there is a need for "winterizing" automatic sprinkler systems through basic steps of preventive maintenance. To maintain sprinkler protection in your property when cold weather has approached, here are some areas of concern to investigate: WET PIPE SPRINKLER SYSTEMS All portions of the building which are sprinkled, including attics, hallways, stairways and areas above ceilings should be heated to at least 40 o F. Windows, skylights and doors should be in good repair, tight fitting and weather-stripped where feasible. Ventilators in attics or concealed spaces should be closed if not needed in cold weather. A special thermometer may be used to obtain a record of minimum temperatures. Special anti-freeze systems should be properly serviced and maintained. Cold-weather valves, if present in your system, should be closed. All other normally open control valves should remain open. DRY PIPE SPRINKLER SYSTEMS All piping should drain properly back to the dry valve, or to auxiliary drains if installed. Water trapped in a dry system may freeze and cause breakage and the entire system to be shut down. All auxiliary drains located in cold places should be checked frequently during freezing weather to be sure they contain no water. The dry-valve enclosure should be kept in good repair. The heating arrangement for the dry-valve enclosure should be safe, and adequate to at least 40 0 F. WATER SUPPLIES Check pressure, ground storage tanks, and gravity tanks to see if tanks, supports and boxing around riser and expansion joints are in good condition. The heating facility for tanks should be in safe condition, and should be of adequate size to prevent freezing. The heating facility for the fire pump installation should be maintained and tested before cold weather arrives. It is recommended that the temperature of a pump house or room not drop below 70 0 F. GENERAL Extinguishers which will freeze should not be exposed to cold. Listed non-freeze extinguishers should be hung in those locations. All heaters and flues should be in good operating condition; repair if necessary; clean out smoke and vent flues if necessary. Oil burners should be checked and serviced if necessary for proper performance. For more information on establishing a "winterized" sprinkler protection program please contact our Loss Control Department at or , ext 240. To help you keep your fire sprinklers, water tanks, or other fire protection equipment from freezing during cold weather, Philadelphia Insurance Company has included the attached preventive maintenance checklist. We ask you to review the list and pass it along to the individuals in your organization who are responsible for the maintenance of your fire protection equipment. The list includes basic precautions. Depending on the complexity of your sprinkler systems, additional precautions may be needed. We hope you find the checklist useful.

2 Page 2 of 14 Freeze Protection Checklist---General Items General Items Present Not Present Is there an Inspection program to ensure adequate building heat? Are all building openings covered, sealed and secured? Is the building temperature monitored? Security personnel trained regarding freeze-up potential? More frequent watch rounds and checks during periods of extreme cold? Low temperature alarms in buildings? Contingency plans for alternate fuel supplies? Portable heaters used UL approved and properly serviced? Alarms on heat exchanger pumps? Heat tracing equipment used on pipes, equipment and instrumentation exposed to potential freezing? Heat tracing equipment checked prior to cold weather with regular follow-up inspections? Outside process lines drained during shutdowns? Exposed process lines and boiler feed water pipes insulated? Management concern and awareness, and communication with maintenance personnel? Management reviews winterization procedures months before cold weather? Individual department responsible for preparation of shutdowns as related to freeze precautions? Existing effective, active freeze-up prevention programs? Prompt corrective action when deficiencies are found? Computerized preventive maintenance checklist programs? Air-drying equipment provided for all shop air? Dry instrument and process air closely monitored with back-up moisture separator on site? Permanent buildings constructed around key equipment?

3 Page 3 of 14 Water Supplies Freeze Protection Checklist--- Water Supplies Present Not Present Fire hydrants checked for proper drainage? Are identification markers provided at buried sprinkler control valves or valve pits subject to heavy snow covering? Heating systems for water storage tanks should be checked for proper operation and placed in service. Insulation on water tanks or stand pipes checked for good repair? Jacket heaters for diesel engine driven fire pumps operational? Wet Pipe Sprinkler System Present Not Present All portions of buildings that are sprinkled including above suspended ceiling should be heated to at least 40. Antifreeze systems checked for proper strength? Heat tracing provided on any piping subject to freezing? Dry or Pre-Action Sprinkler Systems Present Not Present Dry lines should be carefully inspected to make sure that the piping is properly pitched for drainage. (Look for broken hanger and repair) Any condensation that collects at the low points should be drain/removed. Drain auxiliary drains and all low points Dry pipe valves properly set? Excess priming water should be removed. Low air pressure alarms calibrated and connected to constantly attended location (low pressure switches should be set about 5 psi above trip point of dry pipe valve). Air pressure checked regularly with records maintained to indicate normal pressure? Heated, insulated enclosure provided for dry/deluge or pre-action valves. (Flood lamps are not recommended.) Thermostatically controlled heating system should be provided. Low point drains provided with drum drips and records maintained of regular inspections? Air drying equipment provided to supply air to system? Small hose stations located in areas subject to freezing should be supplied from dedicated dry pipe valve. If stations are supplied from wet piping, the control valve should be shut in winter. Double interlocked pre-action system should be provided for freezer areas. A dry pipe valve or single interlock pre-action system not recommended. Notes: Dry pipe valves should be installed in accordance with NFPA 25. If a building is normally heated, a wet pipe system is preferred. If a wet pipe system has been converted to a dry system, piping should slope to a drain and fire department and two inch drain connections should be piped in below the valve. What to do if you discover your sprinkler system frozen? 1. Shut the control valve to the affected sprinkler system. 2. Place plastic tarps in the area of any actual pipe breakage and in area of high valued commodities to help limit water damage to stock and supplies. 3. Then open the 2-inch drain on the riser and any low point drains on the system. 4. Notify the local fire department at that the system is out of service. 5. Notify the Philadelphia Insurance company Loss Control Department at or , ext Indicate that the system is out of service, and: You have notified the fire department, That your sprinkler impairment program will be followed

4 Page 4 of 14 That the Sprinkler contractor has been called Rough estimated of time expected before the system is placed in service What Immediate action should be taken to limit the exposure of breakage/damage? 6. Restore heat in the area. Do not attempt to thaw out piping in the building by using a torch or open flame device. 7. If temporary heat is necessary, use only portable units listed by Underwriter s Laboratories or approved by Factory Mutual. Additionally these units should have constant supervision. 8. Electrical resistance heating should not be directly attached to overhead piping. If it is used to thaw underground piping, it should only be used by well-trained personnel. What action should be taken to reduce the possibility of fire when the system is impaired? 9. All or any Cutting and Welding or other operations employing an open flame should be prohibited in the area where the sprinkler system is out of service. 10. All or any Hazardous operations such as spray painting, dipping or others using flammable liquids or producing a combustible dust should be suspended while the sprinklers are out of service. 11. A strict No Smoking policy should be enforced throughout the affected area. 12. Extra fire extinguishers should be distributed throughout the area. 13. If extensive repairs are required, efforts should be directed toward restoring as much protection as possible by plugging or blocking of the damaged section. This should be done by your Sprinkler Contractor. Example: If a single branch line breaks, it is often possible to blank off that one line and return the rest of the system to service until permanent repairs are completed. Be sure to keep records of all plugs or blind flanges used so you can check they have all been removed when repairs have been completed. 14. Watch service should be provided on a 24-hour basis until repairs are completed and all valves have been reopened. In the event of a fire, the watchman should be instructed to first notify the public fire department and then reopen any closed valves. 15. Before the sprinkler system is restored to service, examine the system for cracked fittings, split pipes or leaking sprinkler heads. 16. Finally, open all control valves and notify the local fire department and Philadelphia Loss Control that the system is back in service.

5 Page 5 of 14 Other Preventative Maintenance and testing activities of Fire Protection equipment Weekly Fire Protection Inspection Fire Pump - Test run by starting the fire pump by operating the test valve on the water pressure test line to the fire pump controller. Diesel driven fire pump should be allowed to run 20 minutes. Electric driven fire pumps run five to seven minutes. - Complete the fire pump checklist - Dry Pipe Sprinkler System - Inspect air pressure and water pressure gauges. Be sure that air and water pressures are within the normal range for that particular system. Record pressure readings. It is recommended that the normal pressure be noted on the gauge or a tag attached to it. A loss of pressure of more than 10% should be investigated. Monthly Fire Protection Inspections The following inspections and tests should be performed monthly. The results should be recorded on the monthly fire protection equipment report form. Repairs and corrective action should be completed promptly. a. Fire Extinguishers.- Check all to be certain they are accessible, not damaged, hung properly, charged with the seal intact and current annual inspection tag is in place. Initial this tag monthly. b. Sprinkler Control Valves - Check and test all sprinkler riser control valves, yard main divisional valves, and water supply pit valves to make sure they are accessible, open and sealed or locked. Sprinkler control valves accessible to the public should be locked open. All other sprinkler control valves should be sealed open. c. Fire Hoses - should be checked to insure the hose is ready for use, mounted on its rack (or reel)with nozzle attached and the hose should be visually inspected as to condition (creases are not worn or split and there is no water in the hose). d. Fire Hydrants should be visually inspected to make sure they are unobstructed, undamaged and ready for use. e. Fire Department Connections - check to see they are unobstructed, caps are in place and couplings are free to rotate f. Fire Safe Conditions (1) Smoking is limited to designated areas. (2) Stairwells and corridors free of obstructions. (3) Emergency lights and exit lamps in working order. (4) Evacuation Drawings are posted (5) All flammable and combustible liquids and aerosol cans are stored in approved flammable liquid cabinets with the doors kept closed. Liquids stored outside of cabinets do not exceed one days supply or 25 gallons of Class IA liquids (flash point less than 73 o f) or 120 gallons of Class IB, IC, II or III liquids (flash point less than 200 o f). Safety cans with self-closing lids are used for the handling and storage of small amounts of gasoline and other flammable liquids. Oxygen and acetylene cylinders are chained in the upright position, separated by 20 feet or a noncombustible barrier, and protective caps in place when not in use. (6) In sprinklered buildings, no combustibles should be stored in areas shielded from automatic sprinklers. Likely shielded areas are: under conveyors in the pit beneath stairwells (7) General Housekeeping There is no storage in electrical rooms or on electrical equipment Waste combustible materials are kept in proper containers Excess pallets are stored outside 50 feet from buildings Packing materials, such as cardboard boxes, Styrofoam filler and plastic bags, are stored in a clean area away from possible ignition sources. In packing areas materials kept to a minimum and the area is clean and free of clutter

6 Page 6 of 14 Used rags contaminated with grease, oil or solvents are stored in an approved fire can with a self closing lid while awaiting pick up from the vendor. Materials are kept clear of light fixtures and bulbs. Wire mesh guards are provided to protect bulbs and fixtures from damage where needed. Quarterly Inspections Prior to performing the following test call the alarm company to alert them you are testing. Verify all alarms tested were received by the alarm service. a. Sprinkler water flow - test each sprinkler system water flow alarm by operating the inspector s test connection on wet pipe systems or the alarm by-pass valves on dry pipe systems. The alarm by-pass valve may be used on wet pipe systems. However, it is preferred that the inspector s test connection be used since this simulates the operation of one sprinkler. b. Valve Tamper Devices - Test each valve tamper device by turning each control valve three complete turns. c. Two-inch drain test - This involves noting and recording the pressure on the gauge on the lower side of the sprinkler valve (static water supply pressure). Open the 2-inch main drain fully; after the flow has stabilized, note and record the pressure on the gauge again (residual water supply pressure). d. Dry pipe system - Determine priming water level by slowly opening the priming water level test valve. If only air escapes, close the test valve and add priming water. This is done by closing the lower priming valve, opening the upper priming valve, and adding approximately 1 quart of water through the priming funnel. The upper priming valve is then closed and the lower priming valve opened, which allows the water to run into the dry pipe valve. Again, check the test valve. If water dose not run out, repeat the procedure. When sufficient water has been added so that water drains from the test valve, allow it to drain until air begins to escape, and then close the valve securely. Also be sure that upper and lower priming valves are closed securely. Annual Tests Fire Extinguishers: Annually all fire extinguishers should be serviced by a fire extinguisher service contractor. Also, depending on the type of extinguisher, discharge and hydrostatic tests are required at specific intervals. The National Fire Protection Association Code 10 gives the recommended intervals for each type of extinguisher. The extinguisher contractor should be able to show you the test intervals for the extinguishers. All Sprinkler Systems: Lubricate all valve stems. Graphite or graphite in light oil should be applied to the valve stem. The valve should be fully closed and reopened to test its operation and distribute the lubricant on the valve stem. Clean strainers if provided. This will generally involve shutting off the water supply and removing the strainer to clean it. Some strainers are self-cleaning and simply require rotation of the operating wheel. Fire Pumps: Full water flow tests are performed annually to evaluate performance of the fire pumps. A maximum load is induced on the pump and driver to make sure the unit is ready and able to perform under an actual fire load condition. Pump capacity tests are performed by discharging water through an approved meter or through hoses attached to a hose header or through yard hydrants. Most installations have a test header. The test should be performed by a qualified fire pump service contractor or your Philadelphia Loss Control representative. It should be performed when a high volume of water can be discharged into the yard. A copy of the manufacturer s test curve and previous test results, including the field acceptance tests, should be available for comparison of results. Should the annual results not be within 10 % of previous test results an investigation should be made to determine the problem. Corrective action should be implemented as soon as possible. Equipment needed to perform this test may include: 50-foot length of 2 1 /2 lined hose with underwriter s playpipe nozzle. A length of hose and play pipe is needed for each test header outlet. Also, a method to secure the hose and pipe is needed. Pitot tube with gauge and test pressure gauges Previous test data, field acceptance data sheet and manufacturer pump curve

7 Page 7 of 14 RPM meter and amp meter Hose wrench and spanner During the pump performance test the all controller functions and alarms should be tested and verified and the strainer should be dismantled and cleaned. For additional maintenance needs consult the manufacturer s guidelines. Dry Pipe Valves: Trip test the dry pipe valve. Before the trip test, the main drain valve should be fully opened and the water supply flushed out until the water flows clean. If a hydrant is located on the system supply, it should be flushed before the main drain is flushed. This flushing will help to reduce the amount of debris getting into the dry pipe system. Each dry pipe valve, including quick opening devices if provided, should be trip tested. This test should be done in the spring after freezing weather, with the water supply control valve only partially open. Once the valve trips, the water control valve can be quickly closed so that the system is not filled with water. (Caution: some dry pipe valves will not operate properly without an adequate flow of water to fully lift the clapper valve.) The valve is tripped by opening the inspector s test valve which release air pressure within the system. After the test, open the 2-inch main drain valve to drain the system. Remove the valve cover and thoroughly clean the valve interior. Renew worn or damaged parts as required, reset the valve, and replace the cover. Add priming water and open the air supply to fill the system with air. When the air pressure has reached its proper level, open the 2-inch drain to reduce the chance of a water hammer tripping the system, and then slowly open the water supply valve. When the water supply valve is fully open, slowly close the 2-inch main drain. Every three years fully trip test the dry pipe valve with the water supply valve fully open. The test should be terminated when clean water flows from the inspector s test connection. A full trip test should also be conducted whenever the sprinkler system undergoes a major alteration or extension. Water should reach the inspector s test connection within 60 seconds. If greater than 60 seconds then an accelerator may need to be provided. In addition, at 10-year intervals (at five year intervals if a full flushing is ever required) a flushing investigation should be performed by a qualified sprinkler contractor in accordance with NFPA 13A. The insurance carriers local fire protection office should be notified in advance so they may have a representative present during the testing. Hydrants: Inspect dry barrel yard hydrants to be sure the barrel is drained. Inspect wall hydrants to be sure the pipe to the outside outlets is free of water. All hydrants should be flow tested every three years to make sure they are working properly and to keep the threads and working parts free of foreign material. Fire Hose: Hydrostatic test by a service contractor five and eight years after installation and every two years thereafter.

8 Page 8 of 14 INSPECTION FORMS SAMPLE 1 (Inspect these items at least weekly) SPRINKLERS Automatic Sprinklers Present Not Present Spare heads available? Obstructed by high piling? (18-36 inch clearance) Adequate heat to prevent freezing? (40 min. temp) Water pressure (from sprinkler riser) lbs. at yard level Comments: (note any broken windows, disconnected or missing heads, etc.) DRY PIPE VALVES Valve Room Temp/Air Pressure Temperature (42 F) Air Pressure Measured No. 1 F lbs No. 2 F lbs No. 3 F lbs No. 4 F lbs Comments: WATER SUPPLIES Fire Pump pressure (start automatically at pressure drop) Start Stop Jockey Pump pressure Start Stop Packings cool? Yes No Properly ventilated? Yes No Fire pump in automatic mode? Yes No Pump room properly heated? ( F) Yes No Pump running alarm activated? Yes No Fuel tank level (3/4 Minimum) Comments: Full? Heating system in use? Circulation good? Time to overflow tank? (minutes) Temperature at cold water return? (42 minimum) Comments: TANK/RESERVOIR Yes No

9 Page 9 of 14 INSPECTION FORMS SAMPLE 2 (Inspect these items at least monthly) MANUAL PROTECTION Fire Extinguishers/Hoses/Hydrants Yes No All extinguishers charged? Any extinguishers missing? All extinguishers accessible? Hoses in good condition? (Inside/Outside) Are hoses accessible? (Inside/Outside) No. 1 hydrant in good condition? No. 2 hydrant in good condition? No. 3 hydrant in good condition? No. 4 hydrant in good condition? No. 5 hydrant in good condition? Hydrants drained? Comments: (note any units missing, poor condition, etc.) HOUSEKEEPING Yes No General order and neatness good? Combustible waste removed on schedule? 3 ft clearance around electrical and/or combustible? Combustible dust, lint, or oil within allowable limits? Comments:? inches FLAMMABLE LIQUIDS Yes No Defects noted? Safety cans used? Stored in flammable liquid cabinet? Excess supply in manufacturing area? Grounding straps, self closing faucets, safety bungs in use? Drainage provided? Vent fans on? Comments:

10 Page 10 of 14 SMOKING REGULATIONS Locations where violations are noted: Corrective actions taken against violations: Permits issued for all hot work applications? Listed precautions taken? Well arranged? Aisles Clear? Maintain flue spaces in racks? Clear of lamps, heaters? (minimum 36 inches) In good condition? Close properly? Obstructed? Blocked open? Comments: INSPECTION FORMS SAMPLE 2, pg. 2 (Inspect these items at least monthly) HOT WORK YES NO STORAGE YES NO DOORS AT CUT OFF WALLS YES NO SPRINKLER ALARMS INSPECTION FORMS SAMPLE 3, pg. 2 (COMPLETE THIS FORM QUARTERLY) Water flow alarm tested? Time for alarm? Yes No Tamper alarm tested? Time for alarm? Yes No Main 2inch drain test Static Residual Water gong working properly? Yes No Operation Satisfactory? Yes No Comments:

11 Page 11 of 14 FIRE PREVENTION INSPECTION FACILITY LOCATION DATE VALVE INSPECTIONS Visually inspect all locked valves monthly. All inside and outside valves controlling sprinklers or fire protection water supplies are listed below. Check the condition of the valve as found. Physically try gate valves including non-indicating and indicator post gate valves. Do not report a valve open unless you have personally tried it. Factory Mutual approved post indicator-valve assemblies, IBV s (Indicating Butterfly Valves) and standard outside screw and yoke valves do not have to be tried, but should be visually checked at close range. NO VALVE LOCATION AREA CONTROLLED OPEN SHUT LOCKED SEALED Were any valves closed since the last inspection? Yes No Is Impairment Program followed? Yes No Was the valve(s) reopened fully and a 2 inch drain test made before the valve(s) was relocked or resealed? Yes No COMMENTS:

12 Page 12 of 14 Fire Extinguisher Inventory Facility: Location: Date: Inspector: No. Location Fully Charged Check lock pin and seal Inspected w/i last year Problems Found: Date problems repaired:

13 Page 13 of 14 DRY PIPE VALVE TRIP RECORD Name: Location: Valve Location: Area Protected: Valve Manufacturer: Size: Year Manufactured: Model Number: *Low Air Pressure Switch Yes No Calibrated to actuate at psi Accelerator Yes No An individual record should be maintained for each valve. The records should be maintained on file for review by the visiting Royal representative. Date Normal Air Pressure Time for Valve to Trip Time for Water at Inspector's Test Normal Water Pressure Valve Tripped at (psi) Accelerator Tripped at (psi) Notes *Note #1: The low air pressure switch should be set to actuate about 5 psi higher than the trip point of the dry pipe valve without the accelerator in-service. Note #2: Dry pipe valves should be trip tested annually. Throttle test should normally be conducted with full flow test being made every third year. (Refer to NFPA 25 section for details)

14 Page 14 of 14 Snow Loading Precautions--Roof Collapse Potential Has the live load roof design been reduced due to: installation of new equipment on the roof: new roofing system such as stone ballast type; additional interior loads suspended from the roof? Has a new building addition been constructed which has a higher roof elevation than the existing adjacent roof level? Drifting can occur on the older roof areas which normally did not occur in the past. Are building support columns in good condition? Are signs of buckling or fatigue evident? Has the building structure been altered such as the removal or relocation of a structural member? If the answer to any of the above questions is "yes", a structural engineer should be consulted to determine if reinforcement should be provided. If reinforcing is impractical or conditions indicate the potential for roof collapse exist due to snow loading, the following precautions should be taken for effective manual snow removal: Yes No Pre-emergency planning should consider: a Acquiring snow blowers of sufficient size to handle the volume of snow a Provision of dependable means of transporting the blowers to the roof a Maintaining a stand-by crew when storm warnings exist a Determination of when snow removal should begin (i.e., 50% of live load design) a How to transport snow from the roof. Avoid relocating to another portion of the roof. Roof hatches or making a new opening should be considered. a Set snow blower blades to maximum height to avoid damage to the roof covering. Date Review Performed

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Building/Business Name: Address of Property: Inspector Name: Joe Price THE CORNERSTONE 1425 NE 7TH AVENUE PORTLAND OR Date

More information

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805) Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including

More information

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT SANTA MONICA FIRE DEPARTMENT Fire Prevention Division 333 Olympic Drive 2 nd Floor Santa Monica, CA 90401 310-458-8915 / Fax 310-395-3395 FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

More information

Self Inspection Program

Self Inspection Program Self Inspection Program Munich Re Self Inspection Program Inspection and testing of fire protection systems Introduction Engineered fire protection systems are a vital factor in the reduction of potential

More information

PROTECTING FIRE SPRINKLER SYSTEM PIPES FROM FREEZING IN CHAPTER FACILITIES

PROTECTING FIRE SPRINKLER SYSTEM PIPES FROM FREEZING IN CHAPTER FACILITIES James R. Favor & Company PROTECTING FIRE SPRINKLER SYSTEM PIPES FROM FREEZING IN CHAPTER FACILITIES A resource for Fraternity and Sorority House Corporation Officers Prevent Your Sprinkler System from

More information

CITY OF PASADENA FIRE DEPARTMENT

CITY OF PASADENA FIRE DEPARTMENT Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in

More information

Evaluating Your Property and Work for Safety Hazards

Evaluating Your Property and Work for Safety Hazards Evaluating Your Property and Work for Safety Hazards One of the best ways to reduce the potential for insurable losses arising on or from your premises is to ensure that unsafe conditions and practices

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE

More information

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

HOW COMMERCIAL FIRE PROTECTION SPRINKLER SYSTEMS REALLY OPERATE

HOW COMMERCIAL FIRE PROTECTION SPRINKLER SYSTEMS REALLY OPERATE A Guide for Fire Sprinkler Maintenance and Operation Commercial fire protection sprinkler systems have been saving lives and reducing property damage for more than a century. New England s textile mills

More information

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Inspection of Fire Sprinkler Systems NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Objective To familiarize Facility Managers with the process of routine inspection

More information

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: From: Subject: Whom It May Concern Carl Ray Austerman, Fire Marshal Contractor s Guide Welcome to the Glendale Fire Department s Contractors Guide. This

More information

System Test Report CLEAN AGENT

System Test Report CLEAN AGENT City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information

More information

Progressive Safety Services LLC 2

Progressive Safety Services LLC 2 Progressive Safety Services LLC 2 Oxygen - to sustain combustion Heat - to raise material to ignition temperature Fuel or combustible material Chemical - exothermic reaction Progressive Safety Services

More information

Element 14.7 Fire Prevention and Control 2018

Element 14.7 Fire Prevention and Control 2018 Scope This program 1 applies to all buildings and employees, and is intended to serve as a basis for ensuring the physical condition of those buildings on a continuing basis. Purpose The purpose of the

More information

Risk Management Services

Risk Management Services Risk Management Services FIRE PROTECTION IMPAIRMENT PROGRAM Introduction Fire protection systems represent a significant capital investment for organizations. Companies want to make sure that they are

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

False Sense of Security???

False Sense of Security??? IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire

More information

Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.

Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225. Fraternity, Sorority and Dormitory Buildings R-2 Fire and Life Safety Standards Inspection Form Fire Code of New York State (19 NYCRR Part 1225.1) House Name Date Address Inspector(s) No. of Residents

More information

ADDENDUM #1 ITB# Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015

ADDENDUM #1 ITB# Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015 ADDENDUM #1 ITB# 2015-09-002 Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015 1. Building #222, The UPS Building, has one (1) dry Sprinkler riser, valve. (This is a

More information

OUTLINE FOR FIRE PREVENTION ACTIVITY

OUTLINE FOR FIRE PREVENTION ACTIVITY OUTLINE FOR FIRE PREVENTION ACTIVITY Background Buildings under construction present unique fire exposures that require special attention. Fires can result in major losses and long delays in the completion

More information

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition

More information

CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY

CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY PURPOSE The fire prevention plan provides information and procedures to minimize the occurrence of an accidental fire at the job site or office, and an efficient

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE PUMP REVIEW Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT 58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the

More information

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

FIRE SAFETY INSPECTIONS

FIRE SAFETY INSPECTIONS FIRE SAFETY INSPECTIONS RCG002 (E)-v2-01/2017 Page 1 2017 Royal & Sun Alliance Insurance plc Introduction Most of us give little thought to our surroundings until an accident occurs. Who left the power

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review Minooka Fire Protection District Maintaining Your Fire Safety Systems Fire continues to be a major threat

More information

Impairments to Fire Protection Equipment

Impairments to Fire Protection Equipment Impairments to Fire Protection Equipment INTRODUCTION Buildings and equipment are provided with fire protection and/or detection systems to reduce property damage and interruption to business in the event

More information

Clackamas Fire District #1 Self Inspection Program. Oregon Fire Code (OFC)

Clackamas Fire District #1 Self Inspection Program. Oregon Fire Code (OFC) Clackamas Fire District #1 Self Inspection Program Oregon Fire Code (OFC) Access Access No parking in the fire access lanes at any time. Even if they are not painted red. An unobstructed width of not less

More information

Fire Safety Plan (Single-Stage Fire Alarm System):

Fire Safety Plan (Single-Stage Fire Alarm System): Fire Safety Plan (Single-Stage Fire Alarm System): Fire Safety Plan for building with Single-Stage Fire Alarm System: (Building/Business Name) (Building Address) The reproduction or use of this fire safety

More information

Freezing of Water-Based Fire Protection Systems

Freezing of Water-Based Fire Protection Systems Risk Solutions Freezing of Water-Based Fire Protection Systems Freezing of water in fire protection piping can seriously compromise a property s fire protection. This report provides information on methods

More information

Builders Risk - Fire Prevention Inspection Checklist

Builders Risk - Fire Prevention Inspection Checklist Builders Risk - Fire Prevention Inspection Checklist Use our inspection checklist tool to help you identify and monitor risk related to builders risk of fire on the job site. Inspection Details: Inspector

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Inspection, testing, and maintenance (ITM) Fixed fire protection and detection July 2016

Inspection, testing, and maintenance (ITM) Fixed fire protection and detection July 2016 July 2016 Author: Global Risk Engineering Technical Center Property Cover photo source: Rich Gallagher, Zurich Table of contents 1. Executive Summary... 1 1.1 Are systems in service?... 1 1.2 Are systems

More information

Fire Prevention Plan

Fire Prevention Plan Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........

More information

Fire Prevention Plan

Fire Prevention Plan Fire Prevention Plan TABLE OF CONTENTS Section Title Page 1.0 Objective. 3 2.0 Background 3 3.0 Assignment of Responsibility.. 4 4.0 Plan Implementation..... 5 5.0 Types of Hazards...... 6 6.0 Training........

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

West Chester Fire Dept. Fire Code Maintenance Handbook. Fire Prevention Saves Lives and Property

West Chester Fire Dept. Fire Code Maintenance Handbook. Fire Prevention Saves Lives and Property Fire Code Maintenance Handbook Fire Prevention Saves Lives and Property 8/10/2006 Our Mission The West Chester Fire Department Loss Prevention Bureau is committed to the safety of its firefighters, and

More information

Stillwater Area Community Services Center Inc.

Stillwater Area Community Services Center Inc. Fire Prevention Plan 1. Purpose The purpose of this Fire Prevention Plan is to eliminate the causes of fire, prevent loss of life and property by fire, and to comply with the Occupational Safety and Health

More information

Checklist For Building Inspection & Fire Safety

Checklist For Building Inspection & Fire Safety INSPECTION CHECKLIST Date of Inspection: Location/Address: Weather Condition: Inspector: AFTER COMPLETING YOUR INSPECTION, TRANSFER YOUR CONCERNS/OBSERVATIONS TO THIS AREA Facility: Name: Staff Contact:

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

Procedure DESCRIPTION/OVERVIEW

Procedure DESCRIPTION/OVERVIEW Applies To: UNMH Responsible Department: Life Safety Revised: 07.08.16 Procedure Patient Age Group: (X ) N/A ( ) All Ages ( ) Newborns ( ) Pediatric ( ) Adult DESCRIPTION/OVERVIEW To assure the safety

More information

TOTALPAC2 Integrated Fire Protection System

TOTALPAC2 Integrated Fire Protection System TOTALPAC2 Integrated Fire Protection System Page 1 of 8 General 1. Applicable Standards The TOTALPAC2 Surefire complies with the following standards: - NFPA-13 Sprinkler Systems; - NFPA-15 Water Spray

More information

A. This section includes design and performance information for fire protection and suppression systems.

A. This section includes design and performance information for fire protection and suppression systems. SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials

More information

Flammable and Combustible Liquids

Flammable and Combustible Liquids Flammable and Combustible Liquids Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids requires the

More information

WELDING, CUTTING, AND BRAZING SAFETY PROGRAM

WELDING, CUTTING, AND BRAZING SAFETY PROGRAM WELDING, CUTTING, AND BRAZING SAFETY PROGRAM HOT WORK TABLE OF CONTENTS 1.0 Introduction 1.1 Purpose 1.2 Scope 2.0 Responsibilities 2.1 Building Office 2.2 Building Personnel 2.3 Individuals Performing

More information

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!! Sample Written Program For Your Company For BOILER SAFETY Provided By: P.O. Box 2136 Slidell, LA 70458 Phone: 985-781-1444 Fax: 985-781-1446 Email: info@se-safety.com Purpose Boiler Safety Program The

More information

Fire Safety Plan (No Fire Alarm System):

Fire Safety Plan (No Fire Alarm System): Fire Safety Plan (No Fire Alarm System): Fire Safety Plan No Fire Alarm System for: (Business Name) (Business Address) Submission Date - Submitted by - Signature The reproduction or use of this fire safety

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

FIRE SAFETY PRACTICES AND PROCEDURES

FIRE SAFETY PRACTICES AND PROCEDURES FIRE SAFETY PRACTICES AND PROCEDURES One of the most costly and destructive causes for loss of life and property that the City could experience would be from a major fire. Reporting Fires All employees

More information

Department Of Public Works: Internal Operations

Department Of Public Works: Internal Operations Department Of Public Works: Internal Operations A Checklist There are over 800 municipalities in the Michigan Municipal League s Pool and Fund Programs. Most perform public works functions of one type

More information

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL NO. 05602 FOR AMEREX STORED PRESSURE, HAND PORTABLE DRY CHEMICAL FIRE EXTINGUISHERS. ABC (Ammonium Phosphate Base)

More information

School Fire Safety Checklist

School Fire Safety Checklist Community Risk Reduction The (SFSC) includes many of the most common fire prevention and life safety issues found in schools. The SFSC is not intended to be an all inclusive list, but rather highlights

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level II Content Outline The candidate for NICET certification at Level II in the Inspection and Testing of Water- Based

More information

Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):

Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment): Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment): Fire Safety Plan Single-Stage Fire Alarm System for: (Business Name) (Business Address) Submission Date - Submitted by - Signature

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

Informational Bulletin

Informational Bulletin Informational Bulletin Date Issued: July 11, 2010 Bulletin No: 2010-11N Topic: Code Reference For Use By: Inspection Guide - General Sonoma County Code California Fire Code California Health and Safety

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

Flammable Materials SC-127

Flammable Materials SC-127 Risk Management Flammable Materials Safety Challenges Many types of flammable and combustible materials/liquids are used in today s workplace. As the person responsible for safety at your company, you

More information

Business Fire Inspection. City of Guadalupe

Business Fire Inspection. City of Guadalupe Business Fire Inspection City of Guadalupe Intent Provide general information on the California Fire Code (CFC) and City of Guadalupe Municipal Code (GMC) requirements. Provide information and the most

More information

Fire Prevention Program

Fire Prevention Program Fire Prevention Program Updated February 2010 REGULATORY AUTHORITY California Code of Regulations, Title 8, Section 3221, Title 19 (19CCR) and Title 24 (24CCR), along with National Fire Protection Association

More information

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) 2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) Reference: Documents referenced for this bulletin are as follows: San

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information

Building and Grounds Self-Inspection Program

Building and Grounds Self-Inspection Program www.alterisus.com Building and Grounds Self-Inspection Program Each building and its accompanying grounds should be inspected at regular intervals, ideally on a monthly or quarterly basis. In this way,

More information

Owner s Manual. FMI BRANDS INC th Avenue Surrey, B.C. Canada V3Z 3V7 Toll Free Fax Model number FMPPC2A

Owner s Manual. FMI BRANDS INC th Avenue Surrey, B.C. Canada V3Z 3V7 Toll Free Fax Model number FMPPC2A Owner s Manual Model number FMPPC2A Series number 890 FMI BRANDS INC. 309-19133 26th Avenue Surrey, B.C. Canada V3Z 3V7 Toll Free 1-888-514-1663 Fax 1-888-797-9931 Owner & Safety Manual Model number FMPPC2A,

More information

A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE

A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE Fire Department Core Values Protect lives, property, and the environment through preparedness, prevention,

More information

August Safety Subject

August Safety Subject August Safety Subject Housekeeping Don t overload the top drawers of a file cabinet or open more than one drawer at a time. Do not leave drawers open while unattended. All cords, cables and wires should

More information

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: Contractors From: Charles Jenkins, Fire Marshal Subject: Contractor s Guide This guide is provided by the Fire Marshal as a service to the construction

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following: SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.

More information

General Industry Safety and Health Checklist Guidelines. Building and Premises. Loss Control Bulletin

General Industry Safety and Health Checklist Guidelines. Building and Premises. Loss Control Bulletin The purpose of a monthly self-inspection program is to identify unsafe conditions in the work environment and unsafe employee actions. Management can then correct these safety hazards, reducing the potential

More information

Family Foster Home Fire Safety Evaluation Checklist Instructions

Family Foster Home Fire Safety Evaluation Checklist Instructions Family Foster Home Fire Safety Evaluation Checklist Instructions Please read these instructions prior to commencing your inspection. This checklist is provided to specific Foster Family Homes for the purpose

More information

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6 Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 20 00 05 Mechanical - General Requirements.2 Section 22 05 00 Plumbing - General Requirements.3 UBC Standard Fire Hydrant Drawings.4 Section

More information

Common Area Cleaning Guide

Common Area Cleaning Guide 1 P a g e Common Area Cleaning Guide It is the responsibility of every occupant, owner, tenant, contractor, employee & visitor and ALL users of this facility to ensure they take all reasonably practical

More information

Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA

Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA 31548 912-510-4302 February 9, 2011 Greetings Camden County Businesses, As always, our department is working vigilantly

More information

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION INSTALLATION AND OPERATING INSTRUCTIONS FOR THE HARDY Fuel Oil Furnace Models D-140 & D-350 HARDY MANUFACTURING COMPANY, INC. 12345 ROAD 505 PHILADELPHIA, MS 39350 PHONE: (601) 656-5866 FAX: (601) 656-4559

More information

Fire Safety Plan. (Business Name) (Business Address)

Fire Safety Plan. (Business Name) (Business Address) 1 Fire Safety Plan (Business Name) (Business Address) (Submission Date) The reproduction or use of this fire safety plan for non-commercial purposes is permitted and encouraged. Permission to reproduce

More information

Denver Fire Department Fire Prevention Division

Denver Fire Department Fire Prevention Division /A 505.1 505.1 Address: Clearly marked from street, Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Address identification characters shall contrast with their background. Each

More information

TAMUCC Fire Safety Training

TAMUCC Fire Safety Training TAMUCC Fire Safety Training TAMUCC Fire Safety Meeting Fire Chemistry, Classification, Types Fire Fighting Fire Prevention Fire Detections Fire Safety Activities TAMUCC Fire Safety Meeting Fire: A rapid

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

TECHNICAL DATA. Wet 26a. February 22, 2009

TECHNICAL DATA. Wet 26a. February 22, 2009 February 22, 2009 Wet 26a 1. DESCRIPTION The Viking Alarm Check Valve serves as a check valve by trapping pressurized water above the clapper and preventing reverse flow from sprinkler piping. The valve

More information

Iowa State Fire Marshal

Iowa State Fire Marshal Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

PLAN REVIEW CHECKLIST

PLAN REVIEW CHECKLIST PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor

More information

FIRE SAFETY AND PREVENTION POLICY

FIRE SAFETY AND PREVENTION POLICY Effective Date: July 26, 2011 Supersedes /Amends: VRS-49/April 2006 Originating Office: Office of the Vice-President, Services Policy Number: VPS-49 PREAMBLE Concordia University (the University ) has

More information

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E Advanced Integrated Fire Protection Systems TOTALPAC 2 Owner's Operation and Maintenance Manual FIRECYCLE III September 2009 FM-086G-0-5E TOTALPAC2 OWNER'S OPERATION & MAINTENANCE MANUAL Manufactured by

More information

John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES

John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES Last Updated: July 18, 2013 1 TABLE OF CONTENTS A. PURPOSE 3 B. SCOPE 3 C. POLICIES AND PROCEDURES 3 1. Facility Hot Work

More information

Hot Work Program & Operational Guidelines. Environmental Health, Safety and Emergency Management (828)

Hot Work Program & Operational Guidelines. Environmental Health, Safety and Emergency Management (828) Hot Work Program & Operational Guidelines Environmental Health, Safety and Emergency Management (828) 262-4008 HOT WORK INTRODUCTION Purpose: This program is designed to recognize potential fire and explosion

More information

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community. CNM WAY PROCESS CNM Process Name Fire Safety Program (04/10/2018 Revision) Overview of Fire Safety Program Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All

More information

Introduction. Program Description. Section C.20 University of South Carolina Safety Program Guide FLAMMABLE AND COMBUSTIBLE LIQUIDS

Introduction. Program Description. Section C.20 University of South Carolina Safety Program Guide FLAMMABLE AND COMBUSTIBLE LIQUIDS Section C.20 University of South Carolina Safety Program Guide FLAMMABLE AND COMBUSTIBLE LIQUIDS Introduction This Program Guide applies to the storage of flammable and combustible liquids. This guide

More information

Safety & Security Services Services de Sûreté et Sécurité. Hot Work Protocol

Safety & Security Services Services de Sûreté et Sécurité. Hot Work Protocol Article 1 Purpose Vanier College has established a to minimize the potential for injuries and loss of property due to fire or explosion as a result of hot work. Article 2 Scope This protocol applies to

More information