CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003

Size: px
Start display at page:

Download "CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES to 2003"

Transcription

1 CUMULATIVE ANALYSIS OF UNIFORM MECHANICAL CODE CHANGES 2000 to 2003

2 The following pages contain comments regarding the changes to the 2000 edition of the UNIFORM MECHANICAL CODE (UMC ) that were made to develop the 2003 edition of the UMC. Some of the comments made are general in nature because the existing language was significantly changed by amendment, deletion or replacement of existing code language. Deleted language is shown by strikeouts and new language is underlined (when possible). Besides minor section changes that occurred within the book to keep section numbers consistent and in order, two general term changes were also made throughout the entire Code book. 1) Administrative Authority Authority Having Jurisdiction 2) Chapter 16, Part II Chapter 17, Part II Section Administrative Authority is the individual official, board, depart, or agency established and authorized by the stat, county, city, or other political subdivision created by law to administer and enforce the provisions of the mechanical code as adopted or amended. This definition shall include the Administrative Authority s duly authorized representative. Authority Having Jurisdiction The organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, installations, or procedures. The authority having jurisdiction shall be a federal, state, local or other regional department or an individual such as a plumbing official; mechanical official; labor department official; health department official; building official or others having statutory authority. In the absence of a statutory authority, the authority having jurisdiction may be some other responsible party. This definition shall include the Authority Having Jurisdiction s duly authorized representative. Analysis: The term Administrative Authority has been deleted and replaced by the term Authority Having Jurisdiction in all of the chapters and sections of the UMC. This change was made to make the code consistent with language used in other codes and standards. This change also makes the term consistent with the IAPMO rules and regulations. Section New definitions for Brine, Building Code, and Building Official Brine. As determined in accordance with NFPA 30 Building Code is the building code that is adopted by this jurisdiction Building Official. See Authority Having Jurisdiction.

3 Analysis: This adds new required definitions to Chapter 2. The term code has been amended to make the code consistent with language used in other codes and standards. This change also makes the term consistent with the IAPMO rules and regulations. Section New definitions for Clothes Dryer, Type 1, Clothes Dryer, Type 2, Code, and Combustion Air. Clothes Dryer, Type I is a factory-built package, multiply produced. Primarily used in family living environment. May or may not be coin operated for public use. Clothes Dryer, Type II is a factory-built package, multiply produced. Used in business with direct intercourse of the function with the public. May or may not be operated by public or hired attendant. May or may not be coin operated. Code A standard that is an extensive compilation of provisions covering broad subject matter or that is suitable for adoption into law independently of other codes and standards. Analysis: This adds new required definitions to Chapter 2. The term code has been amended to make the code consistent with language used in other codes and standards. These changes also make the terms consistent with the IAPMO rules and regulations. Section Labeled refers to equipment or materials to which has been attached a label, symbol, or other identifying mark of an organization that is acceptable to the Authority Having Jurisdiction and concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer indicates compliance with appropriate standards or performance in a specified manner. Analysis: This adds a new required definition to Chapter 2. The term code has been amended to make the code consistent with language used in other codes and standards. This change also makes the terms consistent with the IAPMO rules and regulations. Section New definitions for Shall, Should, Standard, and Stationary Fuel Cell Power Plant Shall indicates a mandatory requirement. Should indicates a recommendation or that which is advised but not required.

4 Standard is a document, the main text of which contains only mandatory provisions using the word "shall" to indicate requirements and which is in a form generally suitable for mandatory reference by another standard or code or for adoption into law. Nonmandatory provisions shall be located in and appendix, footnote, or fine-print note and are not to be considered a part of the requirements of a standard. Stationary Fuel Cell Power Plant is a self-contained package or factory-matched packages that constitute and automatically operated assembly of integrated systems for generating useful electrical energy an recoverable energy that is permanently connected and fixed in place. Analysis: This adds new required definitions to Chapter 2. The term code has been amended to make the code consistent with language used in other codes and standards. These changes also make the terms consistent with the IAPMO rules and regulations. Section Chapter 16, Part II Referenced Standards, provides guidance as to available nationally recognized standards. A list of accepted mechanical equipment and material standards is included in Chapter 17, Part II. Analysis: This change was made to reflect that Chapter 16 was moved to Chapter 17 and will make it consistent with the wording in Section of the Uniform Plumbing Code. Section Oil-Burning Appliances. The tank, piping, and valves for appliances burning oil shall be installed in accordance with the requirements of standards referenced in Chapter 16, Part II NFPA 31, Standard for the Installation of Oil-Burning Equipment. Analysis: This section was formerly Section in the previous version of this code and has been moved and renumbered as Section The change in wording is to correlate the UMC and NFPA 31, Standard for the Installation of Oil Burning Equipment. The reference to NFPA 31 already exists in Chapter 17, Part II; this makes the source of the requirement easier for the user to identify. Section Type of Fuel and Fuel Connections Connecting Gas Equipment. Deleted existing Section language and replaced the section with text from NFPA 54, National Fuel Gas Code, paragraphs through Analysis: This change was made to correlate the UMC and NFPA 54, National Fuel Gas Code.

5 Section LPG Appliances. Liquefied petroleum gas-burning appliances shall not be installed in a pit, basement or similar location where heavier-than-air gas might collect. Appliances so fueled shall not be installed in an above-grade under-floor space or basement unless such location is provided with an approved means for removal of unburned gas. Analysis: This section was deleted since there is no justification for this prohibition and NFPA has provided statistics in the past to demonstrate that incidents involving below grade propane incidents are not greater than those for natural gas. A similar prohibition does not exist in NFPA 54. Installations of LP-gas appliances are common in basements in cities and states that adopt NFPA 54. Section Appliances installed in garages, warehouses, or other areas where they may be subjected to mechanical damage shall be suitably guarded against such damage by being installed behind protected barriers or by being elevated or located out of the normal path of vehicles. Analysis: This change was made to make the code consistent with language used in other codes and standards. This change also makes the term consistent with the IAPMO rules and regulations. Table 3-1, Note A central heating boiler or furnace shall be installed in accordance with the manufacturer s instructions and shall be installed on a floor of noncombustible construction with noncombustible flooring and surface finish an with no combustible material against the underside thereof, or on fire-resistive slabs or arches having no combustible material against the underside thereof. Exception No. 1: Appliances listed for installation on a combustible floor. Exception No. 2: Installation on a floor protected in an approved manner. [NFPA 54:9.3.3] Analysis: This language was extracted from NFPA 54 Section and was added as Note 11 to Table 3-1. This change was made to correlate the UMC and NFPA 54, National Fuel Gas Code. Section Ventilation (outdoor) air for occupants shall be designed in accordance with ANSI/ASHRAE Analysis: A reference to ANSI /ASHRAE has been added. This is the standard for outdoor ventilation requirements.

6 Chapter 5 This Chapter has been extensively changed to make it consistent with the language used in NFPA 96 Standard for Commercial Kitchen Equipment. Some of these provisions have been extracted in their entirety. Also, there are new drawings from NFPA 96 for duct joints and Table 5-5 and 5-6 were previously in Chapter 6 in the 2000 UMC. Section New definitions for: Access Panel Easily Accessible Liquidtight Air Intakes Factory-Built Grease Enclosures Listed Air Pollution Control Devices Field-Applied Grease Duct Enclosures Noncombustible Material Appurtenance Fire Barrier Wall Open Combustible Construction Automatic Fire Partition Pitched Baffle Plate Fire Resistance Rating Recirculating Systems Classified Fume Incinerators Removable Clearly Identified Fusible Link Replacement Air Closed Combustible Construction Grease Salamander Boiler Combustible Material Grease Ducts Shall Commercial Food Heat-Processing Equipment Grease Filters Single Hazard Area Compensating Hood Grease Filter, Mesh Type Solid Cooking Fuel Concealed Spaces Grease Removal Devices Solid-Fuel Cooking Equipment Continuous Enclosure Greasetight Solvent Continuous Weld High Boiler Spark Arrestor Cooking Appliance Flue Outlet High Limit Control Standard Damper Hood Termination Detection Devices Interconnected Thermal Recovery Unit Dips Labeled Trap Discharge Limited-Combustible Material Upright Boiler Analysis: New definitions from NFPA 96 have been added to aid the user to better understand the code. Section Ducts for domestic range hoods shall only serve cooking appliances. Analysis: This sentence was inserted because there is currently no provision to prohibit an environmental air fan, a domestic range hood, and a clothes dryer from sharing the same exhaust duct. Section Clothes dryer moisture-exhaust ducts shall not be connected to a gas vent connector, gas vent or chimney, and shall serve no other appliance or exhaust system.

7 Analysis: This sentence was inserted because there is currently no provision to prohibit an environmental air fan, a domestic range hood, and a clothes dryer from sharing the same exhaust duct. Section Exception: Approved flexible duct connectors Listed clothes dryer transition ducts not more than six (6) feet (1829 mm) in length may be used in connection with domestic dryer exhausts. Flexible clothes dryer transition ducts connectors shall not be concealed with construction. Analysis: There are clothes dryer transition ducts specifically listed for this purpose. These ducts are either rigid or flexible. UL Subject 2158A, Outline of Investigation for Clothes Dryer Transition Duct, is used for investigating and listing these ducts. Section Incompatible materials shall not be conveyed in the same system. Analysis: This change is to correlate the UMC and NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists and Noncombustible Particulate Solids. Section In systems conveying flammable vapors, gases, or mists, the concentration shall not exceed 25 percent of the lower flammability limit (LFL). Exception: Higher concentrations shall be permitted if the exhaust system is designed and protected in accordance with the Standard on Explosion Prevention Systems in Chapter 17, using one or more of the following techniques: (a) Combustible concentration reduction (b) Oxidant concentration reduction (c) Deflagration suppression (d) Deflagration pressure containment Analysis: This change is to correlate the UMC and NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists and Noncombustible Particulate Solids. Section (1) Class 1 product-conveying ducts that operate at less than four (4) inches water column (995.6 Pa) negative pressure and convey noncorrosive, nonflammbale, and nonexplosive

8 materials at temperatures not exceeding 250 F (121 C) may be constructed in accordance with Tables 6-1, 6-2, 6-3, 6-4, 6-5, 6-7, 6-8, or with prior approval, UMC Standard 6-2. Analysis: With the changes occurring in Chapter 6, previously referenced tables were renumbered and additional tables were added. This change is to reflect that the correct tables are referenced in Exception 1 for Product-Conveying Ducts. Section If a room or building contains a dust explosion hazard that is external to protected equipment, as defined in of NFPA 654, such areas shall be provided with deflagration venting to a safe outside location. Analysis: This change is to correlate the UMC and NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing, Processing, and Handling of Combustible Particulate Solids. Section Under Section 506.5, new sub-sections, through , were inserted containing language that was extracted from NFPA 91, paragraphs through Analysis: This change is to correlate the UMC and NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists and Noncombustible Particulate Solids. Section Duct Clearances. Deleted existing text for Section and replaced with the following language that was extracted from NFPA 91, paragraphs through along with any tables or figures that are referenced within those sections. Analysis: This change is to correlate the UMC and NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists and Noncombustible Particulate Solids. Part II Commercial Hoods and Kitchen Ventilation Section through The new language that was inserted in these sections has been extracted from NFPA 96. The following are the main topics that are discussed: Section General Requirements, Clearances and Alternative Methods

9 Section Hood Construction, Exhaust Hood Assemblies with Integrated Supply-Air Plenums, Listed Hood Assemblies, and Solid-Fuel Assemblies Section Grease Removal Devices in Hoods, Installation and Solid-Fuel Grease Removal Devices Section Exhaust Duct Systems, General Requirements, Non-Grease Ducts, Clearance, Openings, Listed Grease Ducts, Materials and Installation for Other Grease Ducts, Exterior Installations, Interior Installation, Termination of Exhaust System, Rooftop Terminations, Wall Terminations, and Solid- Fuel Systems Section Air Movement, In-Line Exhaust Fans, Airflow, Replacement Air, Common Duct (Manifold) Systems, and Solid-Fuel Air Movement Requirements Section Auxiliary Equipment, Dampers, Electrical Equipment, Other Equipment, and Solid-Fuel Auxiliary Equipment Section Fire Extinguishing Equipment, General Requirements, Types of Equipment, Simultaneous Operation, Fuel Shutoff, Manual Activation, System Annunciation, System Supervision, Special Design and Application, Review and Certification, Portable Fire Extinguishers, and Solid-Fuel Fire Extinguishing Equipment Section Procedures for the Use and Maintenance of Equipment, Operating Procedures, Inspection, Cleaning, and Operation, Maintenance, and Inspection of Solid Fuel Cooking Equipment Section Minimum Safety Requirements for Cooking Equipment, Cooking Equipment Approval, Installation, and Operating Controls Section Recirculating Systems, General Requirements, Design Restrictions, Interlocks, Location and Application Restrictions, Additional Fire Safety Requirements, and Use and Maintenance Section Solid-Fuel Cooking Operations, Venting Application, Location of Appliances, Hoods for Solid-Fuel Cooking, Exhaust Systems for Solid-Fuel Cooking, Grease Removal Devices for Solid-Fuel Cooking, Air Movement for Solid-Fuel Cooking, Fire-Extinguishing Equipment for Solid-Fuel Cooking, and Other Safety Requirements Analysis: This change is to correlate the UMC and NFPA 96, Standard for Ventilation Control and Fire Protection for Commercial Cooking Operations. NFPA 96 is nationally recognized and an applied standard. By including a reference to NFPA 96 within the UMC, the result is a complete operational and fire protection package for commercial cooking operations. The sections retained in the UMC are those not specifically addressed in NFPA 96. Sections that were deleted from the UMC are those specifically addressed in NFPA 96 in greater detail. Section General. Supply air, return air, and outside air for heating, cooling, or evaporative cooling systems shall be conducted through duct systems constructed of metal as set forth in Tables 6-1, 6-2, 6-3, 6-4, 6-7, 6-8, 6-9, and 6-10, or metal ducts complying with UMC

10 Standard No. 6-2 or the referenced HVAC duct construction standard in Chapter 17, Part II with prior approval. Rectangular ducts in excess of 2 inches w.g. shall comply with UMC Standard No. 6-2 or the referenced HVAC duct construction standard in Chapter 17, Part II. Analysis: Additional tables were inserted into Chapter 6. This section was updated to include references to the SMACNA tables and the requirements currently used in modern rectangular duct construction up to 2-inch water gauge static pressure. Section Combustibles within Ducts or Plenums. Materials exposed within ducts or plenums shall have a flame-spread index of not more than 25 and a smoke-developed rating index of not more than 50 when tested in accordance with the test for surface burning characteristics of building materials. (See the building code standards based on ASTM E84-91a and ANSIUL ) as a composite product in accordance with ASTM E84 or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, or as a composite product in accordance with NFPA 255 Standard Method of Test of Surface Burning Characteristics of Building Materials, ASTM E or ANSI Analysis: This revision is a clarification for an existing requirement and to address the references to ASTM E 84, ANSI/UL 723, and NFPA 255. Section (1) Return-air and outside-air ducts, plenums or concealed spaces which that serve a dwelling unit may be shall be permitted to be of combustible construction. Analysis: Editorial change for clarification purposes. Section (5) Electrical wiring in plenums shall comply with the NFPA 70, National Electrical Code. Analysis: Clarifies that the Electrical Code is NFPA 70, National Electrical Code since the International Electrical Code exists as well. Section (5)(b) Produce smoke having an average optical density not greater than 0.15 and having a peak optical density of 0.5 or less when tested in accordance with UMC Standard No. 6-3 NFPA

11 262, Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces. Analysis: UMC Standard No. 6-3 has been removed from the 2003 UMC. NFPA 262 is the replacement standard since cables and sprinkler pipe are referenced. Section (6)(b) Produce smoke having an average optical density not greater than 0.15 and having a peak optical density of 0.5 or less when tested in accordance with UMC Standard No. 6-3 UL 1887, Standard for Fire Test of Plastic Sprinkler Pipe for Flame and Smoke Characteristics. Analysis: UMC Standard No. 6-3 has been removed from the 2003 UMC. UL 1887 is the replacement standard since nonmetallic sprinkler pipe in plenums are referenced. Section (7)(8)(9) (7) Nonmetallic pneumatic tubing in plenums shall be listed and shall meet the following requirements: (a) Exhibit flame travel of five (5) feet (1524 mm) or less, and (b) Produce smoke having an average optical density not greater than 0.15 and having a peak optical density of 0.5 or less when tested in accordance with UL 1820, Standard for Fire Test of Pneumatic Tubing for Flame and Smoke Characteristics. (8) Loudspeakers and recessed luminaries including their assembles and accessories in plenums shall be listed and shall meet the following requirements: (a) Have a peak rate of heat release not greater than 100 kilowatts. (b) Produce smoke having an average optical density not greater than 0.15 and having a peak optical density of 0.5 or less when tested in accordance with UL 2043, Standard for Fire Test for Heat and Visible Smoke Release of Discrete Products and Their Accessories Installed in Air-Handling Spaces. (9) Smoke detectors. Analysis: These exceptions were inserted into Section since they are allowed in NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. Section Crimp joints for residential round ducts shall have a contact lap of at least 1-1/2 inch (38 mm) and shall be mechanically fastened by means of at least three sheet-metal screws equally spaced around the joint, or an equivalent fastening method.

12 Joints and seams and all reinforcements for factory-made air ducts and plenums shall meet with the conditions of prior approval in accordance with the installation instructions that shall accompany the products. Closure systems for rigid Class 1 air ducts and plenums shall be listed in accordance with UL 181A, Ducts and Air Connectors. and flexible Class 1 Flexible air ducts shall conform to the referenced standards for air ducts in closure systems in Chapter 16, Part II be listed in accordance with UL 181B, Standard for Closure Systems for Use with Flexible Air Ducts and Air Connectors. Analysis: Residential was deleted since crimp joints are also used in commercial and industrial applications. With the referencing of UL 181A and 181B, Class 1 was removed because UL 181 requires both Class 0 and 1 air ducts to be installed in closure systems. Section Metal. Every duct, plenum, or fitting of metal shall comply with Table 6-1 or Exceptions: (1) Ducts, plenums, and fittings for systems serving single-dwelling units may comply with Table (2) Duct systems complying with UMC Standard or the referenced HVAC duct construction standard in Chapter 17, Part II with prior approval or duct systems complying with UL 181, Standard for Factory-Made Air Ducts and Air Connectors. Analysis: Besides minor editorial changes to reference the correct tables within Chapter 6 in Exception (1), in Exception (2), the reference to UMC Standard No. 6-1 was changed because No. 6-1 is no longer part of the 2003 UMC and was replaced by UL 181. Section Tin. Existing tin ducts may be used when cooling coils are added to a heating system, provided the first ten (10) feet (3048 mm) of the duct or plenum measured form the cooling coil discharge are constructed of metal of the gage thickness set forth in Tables 6-1, , or of this chapter or are of approved material and construction. Tin ducts completely enclosed in inaccessible concealed areas need not be replaced. All accessible ducts shall be insulated to comply with Table of this chapter. Analysis: Minor editorial changes to reference the correct tables within Chapter 6. Section Metal Ducts. Ducts shall be securely fastened in place at each change of direction and as set forth in Table Vertical rectangular ducts and vertical round ducts shall be

13 supported as set forth in Table , Part I A. Riser ducts shall be held in place by means of metal straps or angles and channels to secure the riser to the structure. Analysis: Minor editorial changes to reference the correct tables within Chapter 6. Section Factory-Made Air Ducts. Approved Listed Class 0 or Class 1 factory-made air ducts may be installed in any occupancy covered by this code. Analysis: Listed Class 0 and Class 1 factory-made air ducts are readily available in the industry: such ducts need to be listed to demonstrate compliance with Section Section Insulation of Ducts. Supply- and return-air ducts and plenums of a heating or cooling system shall be insulated to achieve the minimum thermal (R) value as set forth in Tables 6-4, except for ducts and plenums used exclusively for evaporative cooling systems 6-6A and B. Exceptions: (A) Factory-installed plenums, casings, or ductwork furnished as a part of HVAC equipment tested and rated in accordance with approved energy efficiency standards. (B) Ducts or plenums located in conditioned spaces. (C) For runouts less than 10 feet (3 m) in length to air terminal or air outlets, the rated R value of insulation need not exceed R-3.5 (R-0.6). (D) Backs of air outlets and outlet plenums exposed to unconditioned or indirectly conditioned spaces with face areas exceeding 5 sq. ft. (0.5 m 2 ) need not exceed R-2 (R- 0.4); those 5 sq. ft. (0.5 m 2 ) or smaller need not be insulated. (E) Ducts and plenums used exclusively for evaporative cooling system. Analysis: These revisions make the tables 6-6A and B easier to use by directly stating the insulation R-value required for a given application without having to read the table footnotes. The R-value selections are consistent with both ASHRAE 90.1 and International Energy Conservation Code. Section Insulation applied to the exterior surface of ducts, including duct coverings and linings, located in buildings shall have, when tested as a composite installation in the form in which they are used, a maximum flame spread index of not more than 25 and a maximum smokedensity not exceeding developed index of 50 when tested as a composite installation including insulation, facing materials, tapes and adhesives as normally applied in accordance with NFPA , Standard Method of Test of Surface Burning

14 Characteristics of Building Materials or in accordance with ASTM E a, Standard Test Method for Surface Burning Characteristics of Building Materials or in the provisions of UL , Standard for Test of Surface Burning Characteristics of Building Materials. Where these products are to be applied with adhesives, they shall be tested with such adhesives applied. Air duct coverings and lining shall not flame, glow, smolder, or smoke when tested in accordance with ASTM C411-97, Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation, at the temperature to which they are exposed in service. In no case shall the test temperature be below 250 F (121 C). Factory-made air ducts and faced insulations intended for installation on the exterior of ducts shall be legibly printed with the name of the manufacturer, the thermal resistance (R) value at installed thickness and the flame-spread index and smoke-developed rating index of the composite material. Analysis: The modified language reinstates testing of duct coverings and lining as a composite installation and eliminates referencing panels and plenums to avoid any potential confusion. The terminology adopted by ASTM committee E5 on Fire Standards is now clear in that the terms recommended to be used are flame spread index and smoke developed index. Section Ductwork shall be connected to damper sleeves or assemblies in such a way that collapse of the ductwork will not dislodge the damper or impair its proper operation accordance with the fire damper manufacturer s installation instructions. Analysis: Due to the many types of fire dampers that are now available, this change assures that the methods for connecting ductwork to each manufacturer s fire damper will be addressed accordingly and allow for proper operation of the damper and enhanced safety to the building occupants. Section Ceiling Radiation Dampers. Ceiling radiation dampers shall comply with the standard for ceiling radiation dampers referenced in Chapter 16 17, Part II, and shall be installed in accordance with manufacturer s approved installation instructions in the fire-resistive ceiling element of floor-ceiling and roof-ceiling assemblies when required by the Building Code. Fire dampers not meeting the temperature limitation of ceiling dampers shall not be used as a substitute. Ceiling radiation dampers shall be labeled by an approved agency. Analysis: The term radiation was inserted throughout the section to be consistent in the terminology of ceiling radiation dampers.

15 Section Use of Under-Floor Space as Supply Plenum for Dwelling Units. Analysis: Additional language was inserted into the title for clarification that the requirements of this section only deal with residential occupancies. Section The entire ground surface of the under-floor space shall be covered with a vapor barrier having a minimum thickness of four (4) mils ( mm) and a flame spread rating index of 200 or less. Analysis: The terminology adopted by ASTM committee E5 on Fire Standards is now clear in that the term recommended to be used is flame spread index. Section (5) Smoke detectors that are factory installed in listed air-moving equipment may be used in lieu of smoke detectors installed in the main supply-air duct served by such equipment. Analysis: This additional exception in Section would allow factory installed smoke detectors in the unit instead of the SA duct. Section All language in Section regarding Product-Conveying Ducts, has been removed from Chapter 6 in the 2003 UMC. Analysis: The exact same language is addressed in Section of Chapter 5 in the 2003 UMC. Tables 6-1, 6-2, 6-6A, and 6-6B Additional of dealing with duct construction for 4 and 5 foot duct lengths and minimum duct insulation R-values were inserted into Chapter 6 of the 2003 UMC. Analysis: Table 6-1 from the 2000 UMC has been replaced with the new SMACNA tables (6-1 and 6-2) since they contain the requirements currently used in modern rectangular duct construction up to 2-inch water gauge static pressure. The R-value tables were inserted for consistency with ASHRAE 90.1 and the International Energy Conservation Code.

16 Chapter 7 Table 7-1 and all previous language except Section in Chapter 7 of the UMC 2000 has been revised and replaced by extracted language and figures from NFPA 54, Sections 8.3 and A8.3. The following are the main topics that are discussed: Section General Requirements for Combustion and Ventilation Air Section Indoor Combustion Air Section Indoor Opening Size and Location Section Outdoor Combustion Air Section Combination Indoor and Outdoor Combustion Air Section Engineered Installations Section Mechanical Combustion Air Supply Section Mechanical Combustion Air Requirements Section Louvers and Grilles Section Combustion Air Ducts Section Dampers Prohibited (formerly numbered in 2000 UMC) Analysis: This change is to correlate the UMC and NFPA 54, National Fuel Gas Code. NFPA 54 is nationally recognized and an applied standard. By including a reference to NFPA 54 within the UMC, the result is to ease comparison of the two documents. Chapter 8 All previous language has been deleted and replaced with new language, figures and tables that have been extracted from NFPA 54, Chapters 10 and 13. Some tables were also moved from the 2000 UMC Appendix C into Chapter 8. The following are the main topics that are discussed: Section The Scope for Venting of Fuel Appliances Section General Requirements for Vents Section Specifications for Venting Section Design and Construction Section Type of Venting System to Be Used Section Masonry, Metal, and Factory-Built Chimneys Section Gas Vents Section Single-Wall Metal Pipe Section Through-the-Wall Vent Termination Section Condensation Drain Section Vent Connectors for Category I Gas Utilization Equipment Section Vent Connectors for Category II, Category III, and Category IV Gas Utilization Equipment Section Draft Hoods and Draft Controls Section Manually Operated Dampers Section Automatically Operated Vent Dampers

17 Section Obstructions Section Sizing of Category I Venting Systems Section Additional Requirements to Multiple Appliance Vent Analysis: This change is to correlate the UMC and NFPA 54, National Fuel Gas Code. NFPA 54 is nationally recognized and an applied standard. By including a reference to NFPA 54 within the UMC, the result is to ease comparison of the two documents. Chapter 9 Some sections from this chapter have been deleted and replaced with new language, figures and tables that have been extracted from NFPA 54, Chapter 9. The following are the main topics that are discussed: Section General Requirements Section Air-Conditioning Equipment (Gas-Fired Air Conditioners and Heat Pumps) Section Central Heating Boilers and Furnaces Section Equipment on Roof Section Clothes Dryers Section Conversion Burners Section Decorative Appliances for Installation in Vented Fireplaces Section Gas Fireplaces, Vented Section Non-Recirculating Direct Gas-Fired Industrial Air Heaters Section Recirculating Direct Gas-Fired Industrial Air Heaters Section Duct Furnaces Section Floor Furnaces Section Food Service Equipment, Floor Mounted Section Food Service Equipment, Counter Appliances Section Hot Plates and Laundry Stoves Section Household Cooking Appliance Section Illuminating Appliances Section Incinerators, Commercial-Industrial Section Infrared Heaters Section Open-Top Broiler Units (formerly numbered in 2000 UMC) Section Outdoor Cooking Appliances Section Pool Heaters Section Refrigerators Section Room Heaters (formerly numbered in 2000 UMC) Section Stationary Gas Engines Section Gas-Fired Toilets Section Unit Heaters Section Wall Furnaces Section Appliances for Installation in Manufactured Section Small Ceramic Kilns (formerly numbered in 2000 UMC)

18 Analysis: This change is to correlate the UMC and NFPA 54, National Fuel Gas Code. NFPA 54 is nationally recognized and an applied standard. By including a reference to NFPA 54 within the UMC, the result is to ease comparison of the two documents. Chapter Fuel Piping, Tanks, and Valves. Fuel piping shall conform to Chapter 16 Part II, Referenced Standards - Tanks, piping, and valves for oil-burning appliances, Chapter 2 and 3 of shall be installed in accordance with NFPA , Standard for the Installation of Oil-Burning Equipment. Analysis: This change is to correlate the UMC and NFPA 31, Standard for Installation of Oil-Burning Equipment. Section Human Comfort. Cooling systems used for human comfort shall comply with the return-air and outside-air provisions for furnaces in Section and of this code. Cooling equipment used for human comfort in dwelling units shall be sized to satisfy the calculated loads determined in accordance with the reference standards in Chapter 17, Part II or other approved methods. Analysis: The existing text in Section was retained because it provides guidance on return air and outside air for cooling systems. The new requirements were limited to residential. Section (4) Cooling or refrigeration equipment, using Group A1 and B1 refrigerants or brine, located on a roof or on an exterior wall of a building may be provided access as for furnaces in Section of this code. Analysis: With all the new language that was changed in Chapter 9, this change is to reflect the correct referenced section for equipment on roofs. Section Exceptions: 1. Systems containing less than thirty-five (35) pounds (16 kg) of refrigerant R-717 and located in an approved exterior location. 2. Direct and indirect-fired lithium bromide absorption systems using water as the refrigerant.

19 Refrigeration machinery rooms shall house all refrigerant-containing portions of the system other than the piping and evaporators permitted by Section , discharge piping required of this chapter, and cooling towers regulated by this chapter, Part II, and their essential piping. Analysis: The 1997 UMC included provisions that required a machinery room for equipment with refrigerants other than A1. Since Section requires a machinery room for A1 refrigerants, when equipment exceeds 100 HP, it is important to require protection for equipment containing refrigerants other than A1, as they are either toxic, flammable or both. The deleted language has been moved to Section in the 2003 UMC. Section The system contains other than a Group A1 refrigerant. Exceptions: (1) Lithium bromide absorption systems using water as the refrigerant. (2) Ammonia-water absorption unit systems installed outdoors, provided that the quantity of refrigerant in a single system does not exceed Table 11-1 amounts and the discharge is shielded and dispersed. (3) Systems containing less than 300 pounds (136kg) of refrigerant R-123 and located in an approved exterior location. (4) Systems containing less than 35 pounds (16 kg) of refrigerant R-717 and located in an approved exterior location. Refrigeration machinery rooms shall house all refrigerant-containing portions of the system other than the piping and evaporators permitted by Section , discharge piping required of this chapter, and cooling towers regulated by this chapter, Part II, and their essential piping. Analysis: The 1997 UMC included provisions that required a machinery room for equipment with refrigerants other than A1. Since Section requires a machinery room for A1 refrigerants, when equipment exceeds 100 HP, it is more important to require protection for equipment containing refrigerants other than A1, as they are either more toxic, more flammable or both. Exception (4) and the proceeding paragraph came from Section in the 2000 UMC Section Ferrous Materials. Iron and steel refrigeration piping, valves, fittings and related parts shall be approved for the intended use. Pipe more than two (2) inches (50 mm) iron pipe size shall be electric-resistance welded or seamless pipe. (See UMC Standard 11-3 in Appendix A.) Analysis: UMC Standard No has been removed from the 2003 UMC. This was an outdated transcribed standard and was replaced by current standards referenced to make and keep the UMC current.

20 Section Identification. Piping shall be meet the reference standard for identified in accordance with UMC Standard No The type of refrigerant, function and pressure shall be indicated. Analysis: UMC Standard No has been removed from the 2003 UMC. This was an outdated transcribed standard and was replaced by current standards referenced to make and keep the UMC current. Section Stop valves shall be identified by tagging in accordance with UMC Standard No the referenced standard for identification. A valve chart shall be mounted under glass at an approved location near the principal entrance to a refrigeration machinery room. Analysis: UMC Standard No has been removed from the 2003 UMC. This was an outdated transcribed standard and was replaced by current standards referenced to make and keep the UMC current. Table 11-1 Additional refrigerant data was inserted into Table This data was reprint with the permission from the American Society of Heating, Refrigerant, and Air-Conditioning Engineering. Analysis: Updated Table 11-1 to the current ASHRAE standard. Section Insulation. Covering and insulation used for hot water pipes shall be of material suitable for the operating temperature of the system. The insulation, jackets, and lap-seal adhesives, including pipe coverings and linings, shall be tested as a composite product installation and shall have a flame-spread index of not more than 25 and a smokedeveloped rating index of not more than 50 when tested in accordance with building code standards NFPA , Standard Method of Test of Surface Burning Characteristics of Building Materials; in accordance with ASTM E a, Standard Test Method for Surface Burning Characteristics of Building Materials; or in accordance with the provisions of UL , Standard for test of Surface Burning Characteristics of Building Materials. Insulation coverings and linings shall not flame, glow, smolder, or smoke when tested in accordance with ASTM C , Standard Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation, at the temperature to which they are exposed in service. In no case shall the test temperature be below 250 F (121 C).

21 Analysis: These changes are consistent with proposals made to NFPA 90A and to the IMC, and with changes to Section and in the UMC. This revision is a clarification for an existing requirement and to address the references to ASTM E 84, ANSI/UL 723, ASTM C 411 and NFPA 255. The terminology adopted by ASTM committee E5 on Fire Standards is now clear in that the terms recommended to be used are flame spread index and smoke developed index. Section Those portions of the hot water piping systems in which the continuous pressure temperature relationship does not exceed the following shall be permitted to be constructed of cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) piping conforming to specification ASTM F1281. Additional PEX-AL-PEX requirements are mentioned within sub-sections of Refer to 2003 UMC for detail of these requirements. Analysis: Requirements for PEX-AL-PEX were inserted into Chapter 12. This material has been demonstrated to be suitable for the application mentioned. Chapter 13 All previous language has been deleted and replaced with new language, figures and tables that have been extracted from Chapters 1, 5, 6, 7, 8, and 12 in NFPA 54, Appendix B in the 2000 UMC, and sections in NFPA 501A. The following are the main topics that are discussed: Part I Fuel Piping Appliance Fuel Connector Fuel Gas Gas Piping Inspection of gas piping Certification of Inspection Authority to Render Gas Service Authority to Disconnect Temporary Use of Gas Gas Piping System Design, Materials, and Components Interconnections Between Gas Piping Systems Sizing of Gas Piping Systems Acceptable Piping Materials and Joining Methods Gas Meters Gas Pressure Regulators Venting of Gas Appliance Pressure Regulators Gas Piping Installation Installation of Piping

22 Concealed Piping in Building Drips and Sediment Traps Outlets Fittings and Piping Manual Gas Shutoff Valves Systems Containing Gas-Air Mixtures Outside the Flammable Range Systems Containing Flammable Gas-Air Mixtures Electrical Bonding and Grounding Pipe Sizing Methods Equipment Connections to Building Piping LP-Gas Facilities and Piping Pressure Testing and Inspection Part II Fuel Supply: Manufactured/Mobile Home Parks and Recreational Vehicle Parks Single and Multiple Manufactured Homesite Fuel Supply Systems Manufactured Home Community LP-Gas Supply Systems Manufactured Home Accessory Building Fuel Supply Systems Community Building Fuel Supply Systems in Manufactured Home Communities Recreational Vehicle Park Fuel Gas Equipment and Installations Analysis: This change is to correlate the UMC and NFPA 54, National Fuel Gas Code. NFPA 54 is nationally recognized and an applied standard. By including a reference to NFPA 54 within the UMC, the result is to ease comparison of the two documents. These are three important areas that changed: Fuel gas piping systems are limited to 5 psi, the specific prohibition against liquefied petroleum appliances in a pit or basement was removed, and CSST fuel piping systems were added to the code. Chapter 14 No change Chapter 15 No change Section Scope. Stationary fuel cell power plants shall be tested in accordance with ANSI Z21.83, American National Standard/Canadian Gas Association Standard for Fuel Cell Power Plants, and shall be installed in accordance with NFPA 853, Standard for the Installation of Stationary Fuel Cell Power Plants and the manufacturer s installation instructions. Analysis: This is a new chapter, which references ANSI Z (Standard for Fuel Cell Power Plants)

23 Chapter 17 Chapter 16 of the 2000 UMC has been moved to Chapter 17 in the 2003 UMC. In Part I, only UMC Standards No. 2-2, 6-2, and 6-5 have been retained. The remaining standards were deleted. In Part II, the standards are listed by product category and promulgating agency. Analysis: The format of the standards was completely redone by the Standards Task Group to be more user friendly. Appendix A, Standard No. 6-2 See Section 506.2, 602.1, and of the Uniform Mechanical Code Analysis: Two additional sections reference Standard No. 6-2 in the 2003 UMC. Appendix B All language from Appendix B, Chapter 15 has been deleted and replaced with extracted language from NFPA 54, Chapter 11. Analysis: This change is to correlate the UMC and NFPA 54, National Fuel Gas Code. NFPA 54 is nationally recognized and an applied standard. By including a reference to NFPA 54 within the UMC, the result is to ease comparison of the two documents. Appendix C All language from Appendix C has been moved into the body of code in the 2003 version. Chapter 16 in Appendix B of the 2000 UMC has been moved into Appendix C of the 2003 UMC. Analysis: Reformatting of the 2003 UMC to be more user friendly.

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

UNIFORM MECHANICAL CODE

UNIFORM MECHANICAL CODE INDEX Note: Content and section numbers will be updated before publishing. 2009 International Association of Plumbing and Mechanical Officials. All rights reserved. The copyright in this index is separate

More information

CHAPTER 5: EXHAUST SYSTEMS

CHAPTER 5: EXHAUST SYSTEMS MOTORS, FANS AND FILTERS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION SECTIONS 23.20.100 Local Amendments To The International Mechanical Code, 2000 Edition 23.20.202 Definitions 23.20.301.14

More information

2012 International Mechanical Code Significant Changes. About the Significant Changes

2012 International Mechanical Code Significant Changes. About the Significant Changes Significant Changes to the International Mechanical Code and the International Fuel Gas Code With Louisiana Amendments Copyright Materials This presentation is protected by US and International Copyright

More information

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Ohio Administrative Code Rule Number OMC Section IMC origin Reason for proposed 4101:2-2-01 Air, Makeup 2015 Modified definition Air,

More information

Inspection Checklist Mechanical Rough in

Inspection Checklist Mechanical Rough in Property Owner Name: Property Address: Permit Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans are on site and

More information

Chapter FUEL GAS CODE*

Chapter FUEL GAS CODE* Chapter 19.09 FUEL GAS CODE* * Editors Note: Serial No. 2004-31, 1, adopted Oct. 11, 2004 amended Title 19 in its entirety to read as herein set out. See the editor's note at Tit. 19 and also the Code

More information

Analysis of Changes for the 6 th Edition (2017) Florida Codes

Analysis of Changes for the 6 th Edition (2017) Florida Codes Analysis of Changes for the 6 th Edition (2017) Florida Codes Changes to the Florida Building Code, Mechanical This Analysis of Changes for the 6 th Edition (2017) of the Florida Codes is intended to provide

More information

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

2012 INTERNATIONAL FUEL GAS CODE VENTS

2012 INTERNATIONAL FUEL GAS CODE VENTS 2012 INTERNATIONAL FUEL GAS CODE SECTION 502 (IFGC) VENTS 502.1 General. All vents, except as provided in Section 503.7, shall be listed and labeled. Type B and BW vents shall be tested in accordance with

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION Sections 23.20.100 Local amendments to the International Mechanical Code, 2012 Edition.... 2 23.20.101.2 Scope.... 2 23.20.103-110

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code 2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code Welcome! Shawn Strausbaugh Director PMG Technical Resources ICC Government Relations sstrausbaugh@iccsafe.org

More information

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT

CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT CHAPTER 9 SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL BURNING EQUIPMENT SECTION 901 GENERAL 901.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FUEL GAS CODE 2009 EDITION.

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FUEL GAS CODE 2009 EDITION. CHAPTER 23.110 LOCAL AMENDMENTS TO THE INTERNATIONAL FUEL GAS CODE 2009 EDITION. 23.110.100 Local amendments to the International Fuel Gas Code, 2009 Edition. 23.110.101.2 Scope. 23.110.103 23.110.110.

More information

NC Mechanical Code. Land Use and Environmental Service Agency (Code Enforcement) Table of Contents

NC Mechanical Code. Land Use and Environmental Service Agency (Code Enforcement) Table of Contents Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Exhaust Systems Chapter 7 Combustion Air Chapter 9 Specific Appliances Chapter 11 Refrigeration Chapter 13 Fuel Oil Piping POLICY Table

More information

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Changes to the Florida Building Code, Fuel-Gas This Analysis of Changes for the 5 th Edition (2014) of the Florida Codes is intended

More information

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard

More information

UNIFORM MECHANICAL CODE SIGNIFICANT CHANGE COMPARISON STUDY

UNIFORM MECHANICAL CODE SIGNIFICANT CHANGE COMPARISON STUDY CHAPTER 1 ADMINISTRATION CHAPTER 1 SCOPE AND ADMINISTRATION 101.3.1.1 Conflicts Between Codes. New 101.3.3 Appendices. New 102.6 Existing Buildings. New 110.1 General. New 115.6.1 Corrections. New 117.0

More information

Notable Changes in the Mechanical Codes

Notable Changes in the Mechanical Codes Notable Changes in the Mechanical Codes July 2004 The following are some of the changes between the 1997 Uniform Mechanical Code and the 2003 International Mechanical Code(M) and the 2003 International

More information

TABLE OF CONTENTS. Part I Administrative... 1

TABLE OF CONTENTS. Part I Administrative... 1 Part I Administrative............................ 1 CHAPTER 1 Deleted Part II Definitions.............................. 3 CHAPTER 2 DEFINITIONS.................... 3 R201 General..................................

More information

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. 1.1.1.1 (B), (C), & (D)

More information

2015 MECHANICAL CODE REQUIREMENTS

2015 MECHANICAL CODE REQUIREMENTS 2015 MECHANICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Mechanical requirements for residential buildings per

More information

Item # 1 Comment Seq # 1 UMC 2012 (Chapters 1 15): Chair, UMC Correlation Task Group (Manual of Style)

Item # 1 Comment Seq # 1 UMC 2012 (Chapters 1 15): Chair, UMC Correlation Task Group (Manual of Style) Item # 1 Comment Seq # 1 UMC 2012 (Chapters 1 15): SUBMITTER: Martin Cooper Chair, UMC Correlation Task Group (Manual of Style) RECoMMEndaTIon: The following is recommended by the Correlation Task Group

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter except as otherwise

More information

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev This fact sheet provides an overview of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. These revisions are published

More information

Inspection Checklist Residential Mechanical Rough In July 2016

Inspection Checklist Residential Mechanical Rough In July 2016 Inspection Checklist Residential Mechanical Rough In July 2016 This Inspection Checklist reflects code requirements of the 2015 International Residential Code (IRC), the 2015 Uniform Plumbing Code (UPC),

More information

Inspection Checklist Mechanical Final

Inspection Checklist Mechanical Final Property Owner Name: Property Address: Property Parcel Number: Inspectors Name: Review Date: Permits and Plans 1. Job address is posted in a visible location. (R319.1) 2. Permit and approved plans, and

More information

TABLE OF CONTENTS. Part I Administrative

TABLE OF CONTENTS. Part I Administrative Part I Administrative.......................... 1-1 CHAPTER 1 SCOPE AND ADMINISTRATION. 1-1 R101 General............................. 1-1 R102 Applicability......................... 1-2 R103 (Not adopted)........................

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION CHAPTER 23.20 LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2006 EDITION Sections 23.20.100 Local amendments to the International Mechanical Code, 2006 Edition... 2 23.20.101.2 Scope... 2 23.20.303.4

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply

More information

1 Exam Prep Florida Building Code-Mechanical Tabs and Highlights

1 Exam Prep Florida Building Code-Mechanical Tabs and Highlights 1 Exam Prep Florida Building Code-Mechanical Tabs and s These 1 Exam Prep Tabs are based on Florida Building Code-Mechanical, 2014. Each 1 Exam Prep tabs sheet has five rows of tabs. Start with the first

More information

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717) City of York Qdot Engineering 101 S. George St 116 E Gas Ave York, PA 17405 York, PA 17405 (717) 849-2329 (717) 744-8315 INSPECTION CHECKLIST Residential Mechanical 2009 Codes This checklist is intended

More information

CHIMNEYS AND VENTS CHAPTER 8

CHIMNEYS AND VENTS CHAPTER 8 CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SECTION 1801 GENERAL 1801.1 Scope. Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

CHAPTER 8 CHIMNEYS AND VENTS

CHAPTER 8 CHIMNEYS AND VENTS CHAPTER 8 CHIMNEYS AND VENTS SECTION 801 GENERAL 801.1 Scope. This chapter shall govern the installation, maintenance, repair and approval of factory-built chimneys, chimney liners, vents and connectors.

More information

Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended (amended sections listed below)

Adopting Agency BSC SFM. Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended (amended sections listed below) CALIFORNIA MECANICAL CODE MATRIX ADOPTION TABLE CAPTER CIMNEY AND VENTS Adopting Agency BSC SFM CD DSA OSPD 1 1/AC AC SS SS/CC 1 4 Adopt Entire Chapter X X X X X X X X X X Adopt Entire Chapter as amended

More information

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents Table of Contents Chapter 1 Administration Chapter 2 Definitions Chapter 3 General Regulations Chapter 4 Ventilation. Chapter 5 Exhaust Systems Chapter 6 Duct Systems Chapter 7 Combustion Air Chapter 8

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 CHAPTER 6 DUCT SYSTEMS SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION FGC 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment

More information

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION 601 GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and equipment

More information

IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND

IFGC-2012 AMENDED IFGC-2015 IFGC-2018 CHAPTER 1 SCOPE AND CHAPTER 1 SCOPE AND CHAPTER 1 SCOPE AND ADMINISTRATION ADMINISTRATION 301.1.2 LP-Gas installations. Whenever there is a conflict between this code and NFPA 54 and B+NFOA 58 as adopted by the Nevada LP-Gas

More information

Standard for tests for flammability of plastic materials for parts in devices and appliances

Standard for tests for flammability of plastic materials for parts in devices and appliances IAS Accreditation Number TL-212 Company Name Address 3933 U.S. Route 11 Cortland, NY 13045 Contact Name Terence J. O'Beirne, Quality Manager Telephone (607)758-6316 Effective Date of Scope September 25,

More information

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...

More information

ARTICLE 25. FUEL GAS CODE

ARTICLE 25. FUEL GAS CODE ARTICLE 25. Rule 1. Indiana Fuel Gas Code, 2003 Edition (Repealed) (Repealed by Fire Prevention and Building Safety Commission; filed Mar 18, 2008, 2:32 p.m.: 20080423-IR-675070479FRA, eff 90 days after

More information

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee Gil Rossmiller In the construction industry for over 30 years ICC IRC Plumbing & Mechanical Code Development Committee ICC- IECC Commercial Energy Code Development Committee Building Official Parker, Colorado

More information

UMC 2012 ( ): Item # 38

UMC 2012 ( ): Item # 38 UMC 2012 (504.3.1): Item # 38 Steve Taylor Taylor Engineering 504.3.1 Moisture Exhaust Ducts. Moisture exhaust ducts shall terminate on the outside of the building and shall be equipped with a back-draft

More information

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents Table of Contents Chapter 1 Administration Chapter 2 Definitions Chapter 3 General Regulations Chapter 4 Ventilation. Chapter 5 Exhaust Systems Chapter 6 Duct Systems Chapter 7 Combustion Air Chapter 8

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

TABLE OF CONTENTS Board of Appeals General Limitations of Authority... 6 Table Mechanical Permit Fees...

TABLE OF CONTENTS Board of Appeals General Limitations of Authority... 6 Table Mechanical Permit Fees... TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION............. 1 101.0 General....................... 1 101.1 Title.......................... 1 101.2 Scope........................ 1 101.3 Purpose......................

More information

Ventilation for New Low-Rise Residential Buildings July 20, 2015

Ventilation for New Low-Rise Residential Buildings July 20, 2015 Ventilation for New Low-Rise Residential Buildings July 20, 2015 BSC Standard 01 2015 Building Science Corporation 3 Lan Drive, Suite 102 Westford, MA 01886 www.buildingscience.com Contents 1. PURPOSE...3

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

This standard shall prescribe provisions based on minimum requirements for safety to life and property.

This standard shall prescribe provisions based on minimum requirements for safety to life and property. NFPA STANDARDS DEVELOPMENT SITE FIRST DRAFT REPORT Closing Date: February 22, 2013 NOTE: All Public Comment must be received by 5:00 pm EST/EDST on the published Closing Date. NFPA 90B, Standard for the

More information

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ] Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard and shall be considered

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

SECTION DUCTWORK

SECTION DUCTWORK PART 1 GENERAL 1.1 REFERENCES SECTION 23 31 00 DUCTWORK A. ASHRAE - Handbook, Duct Design B. ASHRAE - Handbook, Duct Construction C. ASTM A90/A90M - Standard Test Method for Weight (Mass) of Coating on

More information

CHANGES TO THE TEXT OF THE 2010 CODE BOOKS

CHANGES TO THE TEXT OF THE 2010 CODE BOOKS The State Uniform Fire Prevention and Building Code (the Uniform Code) includes the publications that are incorporated by reference in Parts 1220 to 1227 of Title 19 of the New York Codes, Rules and Regulations

More information

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Solvent Extraction Plants

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE

More information

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS 1 Ventilation and Exhaust 2 Seminar Introduction Seminar addresses key concepts

More information

CHAPTER 1 ADMINISTRATION SECTION 101 (IFGC) GENERAL

CHAPTER 1 ADMINISTRATION SECTION 101 (IFGC) GENERAL CHAPTER 1 ADMINISTRATION SECTION 101 (IFGC) GENERAL 101.1 Title. These regulations shall be known as the North Carolina Fuel Gas Code as adopted by the North Carolina Building Code Council on March 11,

More information

Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition

Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition Errata ANSI Z223.1 National Fuel Gas Code 2015 Edition Reference: Various Errata Z223.1-2015-1 Issue Date: 3/10/16 National Fuel Gas Code user: The American Gas Association (AGA) notes the following errors

More information

NFPA 54 UPDATE. Paul Cabot American Gas Association

NFPA 54 UPDATE. Paul Cabot American Gas Association NFPA 54 UPDATE Paul Cabot American Gas Association PRESENTATION TOPICS Summary Listing Schedule Revisions Definitions/General Piping Appliances and Appliance Installation Venting 2015 Edition Revision

More information

2012 International Fuel Gas Code Design, Installation and Inspection Principles

2012 International Fuel Gas Code Design, Installation and Inspection Principles Overview 2012 International Fuel Gas Code Design, Installation and Inspection Principles Based on the 2012 International Fuel Gas Code Administration Definitions General regulations Gas piping installations

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION 601 (IFGC) GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and

More information

Level I Chapter 1 Worksheet

Level I Chapter 1 Worksheet Chapter 1 Worksheet 1. When the present code requires certain safety to life requirements for existing buildings, those requirements shall. a. be void b. apply c. be approved d. be grand-fathered 2. The

More information

For the Florida Building Commission And the Fire Code Advisory Council

For the Florida Building Commission And the Fire Code Advisory Council Life-Safety Modifications Mechanical and Existing Building Compared to the 2012 Changes of the International Building Code and National Fire Protection Association- 101 For the Florida Building Commission

More information

Wausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records

Wausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records VIOLATION Code AISLES/EXITS NFPA 1-14.13.2.1 NFPA 1-14.4.1 NFPA 1-14.4.2.1 NFPA 101-7.10.9 Violation Codes Description Aisles and Exits Emergency Lighting Working Required emergency lighting systems shall

More information

CHAPTER 17 STANDARDS STANDARDS Broadway, New York, NY 10018,

CHAPTER 17 STANDARDS STANDARDS Broadway, New York, NY 10018, STANDARDS Chapter 17, Part II CHAPTER 17 STANDARDS 1701.0 Scope Part I of this chapter covers standards that are hereby declared to be part of this code. Part II of this chapter lists standards which relate

More information

Appendices. Provisions in the appendices shall not apply unless specifically adopted or referenced in this code.

Appendices. Provisions in the appendices shall not apply unless specifically adopted or referenced in this code. CHAPTER 1 ADMINISTRATION SECTION 101 GENERAL 101.1 Title. These regulations shall be known as the North Carolina Mechanical Code as adopted by the North Carolina Building Code Council on March 11, 2008,

More information

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS Presented to: Presented by: Sargon Ishaya, PE www.pragmaticprofessionalengineers.com Introduction Today s Agenda Overview Review

More information

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES CHAPTER 18 SEMICONDUCTOR FABRICATION FACILITIES SECTION FC 1801 GENERAL 1801.1 Scope. This chapter shall govern the design, installation, operation and maintenance of semiconductor fabrication facilities

More information

Fundamentals of the 2012 International Mechanical Code

Fundamentals of the 2012 International Mechanical Code Fundamentals of the 2012 International Mechanical Code Brent Ursenbach Salt Lake County PDS 385-468-6694 bursenbach@slco.org bursenbach@yahoo.com 2 IMC 101.2 Scope This code shall regulate the design,

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

CHAPTER 10 STEAM AND HOT WATER BOILERS

CHAPTER 10 STEAM AND HOT WATER BOILERS CHAPTER 10 STEAM AND HOT WATER BOILERS 1001.0 Purpose. The purpose of this chapter is to establish and provide minimum standards for the protection of public welfare, health, safety, and property by regulating

More information

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. PIPING Various Brass REVISED

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]

Public Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ] 8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR7040 SAF-MER (36.1.1.4) 36.1.1.4 The provisions of this chapter shall apply to life safety requirements for all new mercantile buildings. Specific requirements shall apply to suboccupancy groups,

More information

2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments

2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments 2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments Based on the International Residential Code (IRC ) GR PPN 1208 Course Approval # 12085 Description This seminar reviews and

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Technical Policy Title: Plant Processing and Extraction

More information

C O D E S & A M M E N D M E N T S

C O D E S & A M M E N D M E N T S SEVIER COUNTY UTILITY DISTRICT SEPTEMBER 2, 2014 Sevier County Utility District has adopted the 2009 International Fuel Gas Code for gas inspections. The following pages contain frequently used codes and

More information

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building

More information

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments: Second Revision No. 3-NFPA 31-2015 [ Section No. 10.5.1 ] 10.5.1* Oil burners, other than oil stoves with integral tanks, shall be provided with some means for manually stopping the flow of oil to the

More information

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur.

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur. First Revision No. 1-NFPA 501-2015 [ Section No. 5.3.1.3 ] 5.3.1.3 The following conditions shall be met when an interior finish material is tested using the test protocol of NFPA 286, Standard Methods

More information

Laboratories and Hazardous Materials. Company Overview

Laboratories and Hazardous Materials. Company Overview Laboratories and Hazardous Materials Don E. Contois, P.E. Sam Sinapi Company Overview R.W. Sullivan Engineering (RWS) was established in 1945 and currently has 95 employees. RWS is a full service engineering

More information

ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL

ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL LINE ITEM # ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL LINE ITEM DETAIL Labor Material FURNACE COMPONENTS 1 Furnish & Install Sight-Impaired Thermostat For Heating and Cooling

More information

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM 1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,

More information

Comparative Matrix A Comparison of the NFPA 96 and ICC Standards and Codes with regard to Commercial Kitchen Systems

Comparative Matrix A Comparison of the NFPA 96 and ICC Standards and Codes with regard to Commercial Kitchen Systems Comparative Matrix A Comparison of the NFPA 96 and ICC Standards and Codes with regard to Commercial Kitchen Systems Matrix 2008 First Edition Comparative Matrix 2008 Phil Ackland First Edition 1 This

More information

TABLE OF CONTENTS Limitations of Authority...6 Table Swimming Pool, Spa, and Hot Tub Permit Fees...7

TABLE OF CONTENTS Limitations of Authority...6 Table Swimming Pool, Spa, and Hot Tub Permit Fees...7 TABLE OF CONTENTS CHAPTER 1 ADMINISTRATION..............1 101.0 General.......................1 101.1 Title..........................1 101.2 Scope........................1 101.3 Purpose......................1

More information