Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches

Size: px
Start display at page:

Download "Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches"

Transcription

1 SP Method 4912 Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches

2 page 2 (17) Copyright This test method is copyrighted by SP. Neither a printed nor electronic copy of the test method should be altered in any way. All SP s test methods and all copyrights, ownerships and rights regarding those test methods shall remain the sole and exclusive property of SP.

3 page 3 (17) SP method 4912 Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches Table of contents 1 Scope Disclaimer Field of application Tolerances Method of test Principle Test apparatus Test fires Test scenarios Fire suppression system Measurements Test procedure System rating criteria Rating of suppression performance Requirements for a passed test Explanatory example of the Rating system Test report Appendix Test apparatus Object locations Framework Apertures Doors and walls Fan Test apparatus mockup components Thermocouples... 7

4 page 4 (17) 5 Propane burner Obstructions Obstruction Obstruction 2 and Obstruction Fire trays Orientation of fire trays Appendix Test protocol Test Test Test Test Test Test Test Test Test Test Test Test fire coordinates Appendix 3 Report sheet... 1

5 page 5 (17) 1 Scope The test method described in this document is intended to test and rate suppression performance and limitations of fire suppression systems installed in engine compartments of buses and coaches. Since this test method only examines the suppression performance, and not detection capability or the quality, reliability or durability of the system components, the tests described in this method should be supplemented with other tests. 1 This method assesses the fire suppression performance of fire suppression systems under mock-up operational conditions. For this purpose, several different types of fires are ignited and stabilised inside an enclosure with typical bus engine compartment characteristics before the fire suppression system is activated. After the fire suppression system has been activated and completely discharged, the system is evaluated based on its ability to extinguish various test fires. In order to ensure the reproducibility of the test and facilitate its adoption in different laboratories, the method utilizes a standardised test apparatus. 1.1 Disclaimer The results relate to the performance of third party suppression systems against a variety of tests based on some of the operating conditions and fire hazards thought to be associated with transit bus / coach engine bays. The testing is designed to provide some information about the fire suppression performance of the product as part of a risk assessment for real applications but is not intended to be the sole criterion for assessing the potential fire hazard protection of the product in use. It is up to the fire protection system provider in collaboration with the bus / coach supplier or owner to carry out a full risk assessment for and of each vehicle application and accept full responsibility for the overall performance of the installed suppression system. SP takes no responsibility for how a tested system performs in a real engine compartment fire. Users of this test method should observe the following warning: Safety warning in order that suitable precautions may be taken to safeguard health, the attention of all engaged in fire tests is drawn to the possibility that toxic or harmful gases may be evolved during combustion of the test fires as well as by activating the suppression system. The potential heat released from the test fires should be considered before the test starts and measures must be taken to avoid any risk of explosion or uncontrolled fire development. 1 Component testing requirements are included in Certification rules regarding Fire suppression systems in engine compartments of buses and coaches SPCR 183. The tests of detection performance are to be developed.

6 page 6 (17) 2 Field of application The test method is applicable to suppression systems intended for diesel fueled bus and coach engine compartments having a gross volume between 2 m 3 6 m 3. Within this range of engine compartment size, the suppression systems can be scaled on the basis of the test result 2. 3 Tolerances Following tolerances shall be followed: ±5 seconds for time values ± m for dimensions < 0.1 m (does not apply to the test fire dimensions) ±5 % or those explicitly stated otherwise 4 Method of test 4.1 Principle Within the test method, 13 different tests intended to provide information about the tested system are included. All tests need not to be performed, only the tests required to obtain different certificates and approvals, for example the P-mark according to SPCR 183. Feasible tests: a) Fire suppression tests (Test 1 Test 11) b) Minimum operating temperature fire test c) Fire test without test apparatus floor 4.2 Test apparatus A test apparatus is to be constructed according to sketches and instructions in Appendix Test fires The test fires in Table 1 are to be used in the 11 different test scenarios as described in Appendix 2. Diesel oil (commercial fuel oil or light diesel oil), heptane (C 7 H 16 ) and engine oil (Statoil MaxWay 15W-40 or equivalent) shall be used as test fuels. 2 Scaling model is to be found in the certification rules SPCR 183

7 page 7 (17) Table 1 Test fires Test fire Description Test fire fuel #1 Pool fire 0.3 m 0.3 m Diesel oil and heptane #2 Pool fire 0.3 m 0.3 m and 2 Fibreboards Diesel oil and heptane #3 Pool fire 0.2 m 0.3 m Diesel oil and heptane #4 Pool fire Ø 0.15 m Diesel oil and heptane Approximate peak HRR 60 kw 110 kw 40 kw 7 kw #5 Pool fire 0.2 m 0.3 m and Class A-fire Diesel oil and heptane 50 kw #6 Fibreboard 0.2 m 0.3 m Diesel oil and heptane 35 kw #7 Spray fire (4.5 bar, 0.73 kg/min ±10%) #8 Spray fire (4.5 bar, 0.19 kg/min ±10%) #9 Dripping oil fire (40 droplets/min ±10) Diesel oil Diesel oil Engine oil 520 kw 140 kw 5 kw Pool fires Three different types of trays are applied in Table 1: square, rectangular and circular. Detailed descriptions of these trays are given in Table 2. Table 2 Specification of pool fire trays Dimensions Rim height Nominal thickness Used for test fire 0.3 m 0.3 m 0.07 m 1.5 mm #1, #2, 0.2 m 0.3 m 0.07 m 2 mm #3, #5 Ø 0.15 m 0.1 m 1.5 mm #4

8 page 8 (17) 0.2 m 0.3 m m 2 mm #6 The amount of water, diesel and heptane (±10 %) used in the tests should be in accordance with Table 3. Table 3 Amount of fuel used in pool fire trays Dimensions Water Diesel Heptane Used for test fire 0.3 m 0.3 m 1.0 l 0.5 l 0.2 l #1, #2, 0.2 m 0.3 m 0.5 l 0.5 l 0.2 l #3 Ø 0.15 m 0.2 l 0.2 l 0.1 l #4 0.2 m 0.3 m 0.5 l 0.6 l 0.3 l #5 0.2 m 0.3 m l # Fibreboards Test fire #2 consists of a heptane pool and two diesel soaked fibreboards with a dry density of 3.5 kg/m 2. The dimensions of the fibreboards shall be 12 mm 290 mm 190 mm. The fibreboards shall consist of at least 90 % raw material from wood. The moisture content in the boards before they are soaked in diesel oil shall not exceed 7 %. The fibreboards shall be completely immersed in diesel oil for at least 10 minutes prior to the test and mounted vertically in the pool fire tray not more than 10 minutes before the start of the test. Test fire #6 consists of one diesel soaked fibreboard (as described above). The fibreboard shall be completely immersed in diesel oil for at least 10 minutes prior to the test and placed horizontally in the pool fire tray not more than 10 minutes before the start of the test Class A-fire Test fire #5 consists of a Class A wood crib fire ignited by a heptane pool fire. The fire tray is specified in Table 2. The wood crib shall be placed on steel supports 20 mm (±5 mm) above the fuel surface in the fire tray. The wood crib shall not be in direct contact with the fuel. The wood crib shall consist of five layers of wood pieces. Every layer includes eight pieces of pine wood having the dimensions of 10 mm 10 mm and a length of 100 mm. Six of these pieces aligned in parallel with a mutual distance of 8 mm (±2 mm) form the top of the layer. The two remaining pieces aligned perpendicularly to the previous and with a mutual distance of 60 mm form the bottom of the layer. The overall dimensions of every layer of the crib are thus 100 mm 100 mm 20 mm. Since the wood crib includes five layers, the overall dimensions of the wood crib are 100 mm 100 mm 100 mm. After the wood crib is assembled, it shall be conditioned at a temperature of 105 C (±5 C) for not less than 16 hours. The moisture content shall not exceed 5% prior to the fire test.

9 page 9 (17) Minimum operating temperature fire test Minimum operating temperature fire test is any high fire load test (i.e. Test 1, Test 5 or Test 8) performed with extinguishing agent and propellant gas vessel cooled to either the lowest operating temperature as stated by the manufacturer or lowest temperature announced by the manufacturer as desired to test the system for Fire testing without test apparatus floor Fire suppression system may be regarded as tested without test apparatus floor either: a) After repeating the most severe high fire load test performed with passed result without changing the suppression system configuration. b) After performing all fire tests with a suppression system configuration designed for fire test without apparatus floor Spray fires and dripping oil fire Test fire #7, #8 consist of diesel oil spray fires while Test fire #9 consists of a dripping oil fire (by hot surface ignition). For the test fire #7 shall be used 120 full cone spray nozzle. For test fire #8 shall be used 80 axial flow hollow cone spray nozzle. The spray nozzle for test fire #9 shall be Danfoss 0.60X80H or equivalent.

10 page 10 (17) 4.4 Test scenarios Table 4 shows the different tests scenario categories. The test scenarios are explained in detail in Appendix 2. Table 4 Test scenarios Test Air Test scenario category flow rate 1 0 m³/s High fire load test 2 0 m³/s Low fire load test 3 0 m³/s Hidden fire test m³/s Class A-fire test m³/s High fire load test m³/s Low fire load test m³/s Hidden fire test 8 3 m³/s High fire load test 9 3 m³/s Low fire load test 10 3 m³/s Hidden fire test 11 0 m³/s Re-ignition test 4.5 Fire suppression system To obtain the minimum discharge rate condition, an extinguishing system is to be assembled using its maximum piping limitations with respect to the number of fittings and size and length of pipe. The cylinder is to be filled to its rated capacity and the cylinder or gas cartridge pressurized with the expellant gas to the normal operating pressure (see for further information) Nozzle positioning Nozzle positioning in the tests shall be done by the system manufacturer or supplier. The nozzles may only be positioned inside the test apparatus, at two different areas: 1) In the ceiling and at the rear wall. Nozzles positioned in the ceiling must be positioned so that the nozzle outlet is 0.75 m or more above floor level, and outside Obstruction 1. Nozzles positioned at the rear wall must be positioned so that the nozzle outlet is within 0.35 m of the rear wall (y 1.15 m) and 0.45 m or more above floor level, see Figure 1 and 2. 2) Inside the rear box (referred to as Obstruction 4) in the rear side of the test apparatus. Nozzles should be located in the ceiling of the box, so that the nozzle outlet is 0.29 m or more above floor level, see Figure 2.

11 page 11 (17) Figure 1 Nozzle positioning seen from the front side of test apparatus Figure 2 Nozzle positioning seen from the rear side of test apparatus

12 page 12 (17) 4.6 Measurements The system setup and configuration shall be observed and documented prior to the test (e. g. amount of suppression agent and propellant gas, system pressure, number, type and location of nozzles, length of pipes and number of fittings). If possible, the system pressure drop and suppression agent flow rate should be measured during the test. Temperature shall be measured during the re-ignition tests at locations specified in Appendix 1. Additional thermocouples are not required, but may be used at the discretion of the test facility to obtain more information from the testing. 4.7 Test procedure The tests can be performed in an arbitrary sequence. For certain suppression system configuration, a single test (e.g. Test 1) is considered as failed after two unsuccessful attempts and as passed either after success at first attempt or success at two of three attempts in a case when first of these attempts fails Practical conduct of a test The fire trays are to be filled with diesel and heptane on a base of water according to Table 3. If fibreboards are to be used as a fire source, the fibreboards shall be soaked in diesel oil, prior to the test, according to instructions in Section A pre-burn time based on the information in Appendix 2 is required. The pre-burn time is measured beginning from the time the first fire is ignited. All pool fires in the test scenario shall be ignited within the allowed time for ignition, according to Appendix 2, using a suitable ignition source. A fan is used in some of the test scenarios to obtain a specific air flow rate into the test apparatus. The fan shall remain active until the test is complete, i.e. until it is determined whether the test is passed or failed in accordance with the performance requirements in Section 5.2. A diesel spray is used in some of the test scenarios. The diesel spray shall be activated 10 seconds prior to activation of the suppression system. The diesel spray shall remain active until the test is complete, i.e. until it is clarified if the test is passed or failed in accordance with the performance requirements in Section 5.2. In test for re-ignition, the exhaust manifold mockup tube is pre-heated with a burner prior to the test. Pressurized air may be added to the flame for better combustion. The tube shall be heated from the inner side until the temperature of Tc2 > 600 C, Tc1 > 570 C and Tc5, Tc6 & Tc7 > 520 C (see Figure 9 in Appendix 1). Tc2 > Tc1 > Tc5, Tc6, Tc7 shall be strictly observed. When the predefined temperatures are reached the pre-heating procedure stops (time 00:00). After 30 seconds the engine oil starts dripping (time 00:30). The dripping

13 page 13 (17) frequency shall be 40 droplets/min ± 10 droplets and give rise to a sustained flame on the tube before the suppression system activation which occurs at a time of 00:45. The oil shall continue to drip on to the tube until re-ignition occurs. The test shall stop 5 minutes after extinction of the flames if no re-ignition occurs Test-to-test system modification restrictions Suppression system modifications between the tests are allowed without need of repeating all previously passed tests as long as they comply with the following rules: It is not allowed to change location of an existing nozzle Number of nozzles can be increased at most by 10 % when compared to the lowest number of nozzles used during any of the fire tests. An increase is irreversible i.e. no subsequent decrease of number of nozzles is allowed. Pipe section outside the test apparatus can be shortened. The amount of agent can be increased at most by 20 %. For systems where filling ratio is definable and is changed while making use of this rule, it must be proved that this modification do not decrease the extinguishing performance of the system, by repeating the highest passed high fire load test and the minimum operating temperature test. Pressure can be increased if it not alters the performance of nozzles too much which may be assessed by comparing discharge pattern from a nozzle before and after increasing pressure. Increasing pressure impose need of re-doing the re-ignition test. The highest number of nozzles, the shortest distance between the most remote nozzle and the extinguishing agent vessel, the highest amount of agent and the highest pressure used, will be reported as parameters of the tested system for which tests according to SP Method 4912 has been accomplished. Introduction of further modifications impose need of repeating all previously passed test. 5 System rating criteria 5.1 Rating of suppression performance The tested suppression system will be rated based on the performance measured according to the five categories below: 1) High fire load 2) Low fire load 3) Class A-fire 4) Hidden fire

14 page 14 (17) 5) Hot surface re-ignition A numeric rating is based on the results from the first four categories which thus give rise to four partial ratings which are summed into a total rating. With some exceptions, every passed test gives one point. The results from minimum operating temperature test and hot surface re-ignition test has no effect on this numeric rating and are reported separately. Rating for category 1 4: detailed information on how many points can be gathered for different configuration of tests from different categories can be found in the tables below. It should be especially emphasized, that in Category 2, the tests can be either performed one by one, or in merged mode by which it is meant conducting a the most severe of tests of interests (with respect to air flow rate) supplemented by test fires from the other tests. Regarding Category 4, a hierarchic rating approach is used. This means that Tests 3, Test 7 and Test 10 are considered as same basic scenario with severity increasing in this order, due to increasing air flow rate. Thus, by passing Test 10 one obtains automatically points for passing Tests 7 and Test 3 etc. Ten different tests make it possible to achieve ten points in total and the highest rating is written as: = 10 of 10. Rating for category 5: If no re-ignition occurs during the 5 minutes of test, the test result is: No re-ignition. If re-ignition occurs, the test is repeated (i.e. run twice in total) and the result reported is the shortest time to re-ignition of those two values. To facilitate the understanding of the rating system, a working example is given in Section Category 1 High fire load Rating 1+x+x+x 2+x+x+x 3+x+x+x Criteria Passing Test 1 Passing Test 1 and Test 5 Passing Test 1, Test 5 and Test 8 or passing Test 1, Test 8 and Test 10.

15 page 15 (17) Category 2 Low fire load Rating x+1+x+x x+2+x+x x+3+x+x Criteria Passing Test 2 Passing Test 2 and Test 6 separately or merged (i.e. passing Test 6 supplemented with test fires from Test 2 not originally present in Test 6) Passing Test 2, Test 6 and Test 9 separately or merged (i.e. passing Test 9 supplemented with test fires from Test 2 and Test 6 not originally present in Test 9) Category 3 Class A-fire Rating x+x+1+x Criteria Passing Test Category 4 Hidden fire Rating x+x+x+1 x+x+x+2 x+x+x+3 Criteria Passing Test 3 Passing Test 7 Passing Test Category 5 Hot surface re-ignition protection The result of Test 11 is the time from the extinction of the flames to the time of re-ignition. 5.2 Requirements for a passed test The pool fires (#1, #3, #4), fire sources with fibreboards (#2, #6), pool fire & class A-fire (#5) and sprays (#7, #8) shall be fully extinguished either not later than 1 min after activation or upon the end of discharge of the suppression system. The sprays (#7, #8) are shut off when considered as extinguished. The class A-fires shall not reignite within five minutes after activation. Other test fires shall not re-ignite upon opening of the test apparatus. Visible flames are considered as re-ignition. Glowing is acceptable for the class A-fire and test fires with fibreboards.

16 page 16 (17) 5.3 Explanatory example of the Rating system After conducting fire test, a suppression system might have achieved the following results: Test Air Test scenario category Result flow rate 1 0 m³/s High fire load test Pass 2 0 m³/s Low fire load test Pass 3 0 m³/s Hidden fire test Fail m³/s m³/s m³/s m³/s Class A-fire test High fire load test Low fire load test Hidden fire test Pass Pass Pass Fail 8 3 m³/s High fire load test Pass 9 3 m³/s Low fire load test Pass 10 3 m³/s Hidden fire test Fail 11 0 m³/s Hot surface re-ignition 1:05 minutes 11 (repeated) 0 m³/s Hot surface re-ignition 1:15 minutes The suppression system has now obtained 7 points divided into the following categories, and 1:05 minutes of hot surface re-ignition protection: High fire load Low fire load Class A-fire Hidden fire Hot surface reignition test test test test protection :05 minutes The total rating is written as below. Moreover, it contains information on which fire test was performed additionally in minimum operating temperature mode and passed. Fire suppression performance: = 7 of 10 Re-ignition protection: 1:05 min Minimum operating temperature test passed (-30 C): Test 1

17 page 17 (17) 6 Test report The test report shall as a minimum include the following information: Name and address of the testing laboratory Date and identification number of the test report Name and address of the customer Date of test Name or other identification marks of the tested product Detailed drawing of the test set-up Description of the tested product: o Drawing(s) or pictures of the tested product o Description o Specification of included material Total amount of suppression agent and propellant gas Number and types of used nozzles Identification of the test equipment and used instruments Deviations from the test method, if any Photos from the tests Test results Date and signature

18 Appendix 1 page 1(12) Appendix 1 1 Test apparatus The test apparatus is to be made of steel plate. The thickness of the steel plate shall be in accordance with Table 1. Figure 1 shows the test apparatus from the front side and figure 2 from the rear side. Note that the front side of the test apparatus simulates the rear side of a real engine compartment. z y O x Figure 3 Coordinate system for the position of objects in test apparatus (view from the front side)

19 Appendix 1 page 2(12) Figure 4 Test apparatus seen from the rear side Table 5 Test apparatus objects Object Fan cylinder Obstructions Exhaust manifold mockup Engine mockup Muffler mockup Exhaust pipe Connection pipe Walls, ceiling and floor Plate thickness mm mm 8 mm 2 3 mm 2 3 mm 2 3 mm 2 3 mm 1.5 mm 5 mm 1.1 Object locations All objects in the test apparatus are positioned according to coordinates in meters with origin as marked (O) in Figure 3. The coordinates of the objects refer to the origin of the particular object i.e. left-front-bottom corner or an imaginary left-front bottom corner 3 for cylindrical objects. In Table 6 can be found coordinates of the objects in the test apparatus. Table 6 Coordinates of objects Object Coordinates Fan cylinder (-0.60, 0.40, 0.10) Obstruction 1 (0.0, 0.26, 0.0) Obstruction 2 (0.26, 0.05, 0.02) 3 I.e. properly expressed: left-front-bottom corner (as seen from the front of the test apparatus) of an rectangular cuboid in which the cylindrical object is thought to be inscribed in.

20 Appendix 1 page 3(12) Exhaust manifold mockup (0.76, 0.05, 0.47) Engine mockup (0.87, 0.05, 0.04) Obstruction 3 (1.44, 0.05, 0.02) Obstruction 4 (0.82, 1.2, 0.00) Muffler mockup (2.00, 0.28, 0.23) 1.2 Framework The framework of the test apparatus shall be constructed according to Figure 5. The sizes of the beams are 0.05 m 0.05 m and 0.10 m 0.05 m respectively. Figure 5 Framework for the test apparatus 1.3 Apertures In addition to the opening for the fan, the test apparatus includes six apertures, according to Figure 6. Note that all objects inside the test apparatus are hidden in

21 Appendix 1 page 4(12) Figure 6 in order to more clearly show the apertures. The dimensions and positions of the apertures are according to the coordinates in Table 7. The positions are given by referring to two diagonally opposite corners as all openings are rectangular in shape. However as opening D1 is slightly obstructed by Obstruction 4 giving rise to a nonrectangular aperture, the corresponding coordinates describe the two rectangles of which this aperture can be thought to consist of. Figure 6 Apertures in the test apparatus

22 Appendix 1 page 5(12) Table 7 Coordinates of Apertures in the test apparatus Aperture Coordinates (x, y, z x, y, z) Area of aperture A1 0.03, 0.00, , 0.00, m 2 A2 1.22, 0.00, , 0.00, m 2 B 2.40, 0.50, , 1.30, m 2 C 0.85, 1.50, , 1.50, m 2 D1 2.00, 0.05, , 0.73, m 2 D2 2.00, 0.78, , 1.20, , 1.20, , 1.45, m 2 Total area of apertures: 0.95 m Doors and walls The front and rear side of the test apparatus shall be provided with doors. The front doors shall include windows enabling observation of the progress in extinguishment during the tests. The remaining framework shall be covered with walls, ceiling and floor of steel sheet as specified in Table 5. Walls and ceiling or parts of them may be in the form of closable hatches. The doors and hatches are to be mounted on the outside of the framework in such way that no parts extend to the interior of the test apparatus defined as: 0 m < x < 2.4 m; 0 < y < 1.5 m; 0 < z < 1.25 (if y < 0.5 m) and 0 < z < 0.95 m (if y > 0.5 m). 4 The coordinates takes account for the fact that the opening D2 which is in size identical with D1 is somewhat covered by Obstruction 4 thus restricting the aperture.

23 Appendix 1 page 6(12) 2 Fan An axial fan with a diameter of 0.71 m (+0.00 m, m) shall be mounted on the left side of the fan cylinder. The cylinder shall have an inner diameter of 0.71 m and a length of 0.6 m. The fan shall produce a certain air flow rate through the cylinder according to the test protocol in Appendix 2. A frequency converter may be used to adjust the fan speed. For tests with no fan a concealing plate with the same diameter as the fan opening may be positioned instead in the opening at a distance not closer than 0.05 m from the fan opening. Figure 7 Fan cylinder 3 Test apparatus mockup components The dimensions of the engine mockup are 1.00 m 0.65 m 0.50 m. The dimensions of the Muffler mockup are Ø0.40 m 0.80 m. The muffler and the engine mockup shall be hollowed. The Exhaust manifold mockup tube shall have the inner dimensions of Ø0.080 m 0.90 m. It shall be connected to the centre of the Muffler mockup (as seen in Figure 8) through a connection pipe with an external diameter of 0.08 m, running at a y = 1.40 m. Another pipe with an external diameter of 0.08 m shall also be used to carry the exhaust gases vertically up and out from the Muffler mockup. It shall be connected to the centre of the Muffler mockup front side and run at a y = 0.12 m, see Figure 8. The whole exhaust gas system from the propane burner inlet to the exhaust gas outlet should be relatively smoke tight.

24 Appendix 1 page 7(12) Figure 8 The exhaust system to be pre-heated for the re-ignition test. 4 Thermocouples Seven thermocouples (Tc) shall be mounted on the Exhaust manifold mockup pipe, drilled 2 mm into the tube from the outside. The location of the thermocouples shall be in accordance with Figure 9 and 10. Tc1 Tc4 shall be located on top of the tube and Tc5 Tc7 around the tube, on the same distance from the tube opening as Tc2.

25 Appendix 1 page 8(12) Figure 9 Thermocouples on the exhaust manifold mockup Figure 10 Thermocouples on the exhaust manifold mockup 5 Propane burner The propane burner used to pre warm the exhaust system shall be chosen as to fulfill the requirements on achieved temperatures specified in section Obstructions 6.1 Obstruction 1 Obstruction 1 has the dimensions of 0.23 m 0.90 m 0.84 m, as shown in Figure 11.

26 Appendix 1 page 9(12) Figure 11 Obstruction Obstruction 2 and 3 Obstructions 2 and 3 consist of tubes as shown in Figure 12. The horizontal obstructions tubes are closed and hollow, with an outer diameter of 0.08 m and a length of 0.48 m. The vertical tubes are hollow and open in the bottom, with an outer diameter of 0.08 m and a length of 0.23 m. The open distance between every tube (both horizontal and vertical) is 0.02 m. The distance between the open bottom of the vertical tubes and apparatus floor is 0.02 m. The distance between top of the vertical tubes and the horizontal tubes is 0.03 m. The first horizontal tube layer from the bottom forms a storey which is 0.36 m above the apparatus floor level. Figure 12 Obstruction 2 and 3

27 Appendix 1 page 10(12) 6.3 Obstruction 4 Obstruction 4 is a box measuring 1.25 m 0.30 m 0.39 m. It can be seen in Figure 13 as seen from the same (rear) side as shown in Figure 4. Obstruction 4 includes two apertures. The first, on the right short side (0.24 m x 0.30) is open to the interior of the test apparatus, while the other on the rear long side (0.39 m x 0.33 m) is in conjunction with the test apparatus Aperture C, thus being an opening to the outside (see Figure 13). Figure 13 Obstruction 4 7 Fire trays 7.1 Orientation of fire trays The square fire trays with fibreboards and the rectangular fire trays shall have transverse orientation (in relation to the forced air flow), except the Category 4 (Hidden fires) tests. Figures 14 and 15 show the longitudinal and transverse orientations of the pool trays with fibreboards. Figure 16 show the transverse orientation of the rectangular pool tray (longitudinal orientation does not occur). Diesel spray nozzles are positioned to spray parallel to the long edge of the test apparatus, in the direction of the arrow according to the test protocol in Appendix 2.

28 Appendix 1 page 11(12) Figure 14 Longitudinal orientation of the pool trays with fibreboards Figure 15 Transverse orientation of the pool trays with fibreboards

29 Appendix 1 page 12(12) Figure 16 Transverse orientation of the rectangular pool tray 7.2 Test fire obstruction Test fire #2 in Test 3, Test 7 and Test 10 is concealed from the top and from the rear side with a steel roof obstruction according to Figure 17. Figure 17 Test fire concealed from the top and from the rear side

30 Appendix 2 page 1(18) Appendix 2 Test scenarios with visualization and description of test fire placements as well as test procedure are found in section 1. In section 2 are found coordinates of all test fires. 1 Test protocol 1.1 Test 1 Figure 18 Test 1 Figure 19 Test 1 (seen from rear side) SP Sveriges Tekniska Forskningsinstitut

31 Appendix 2 page 2(18) Test fires: Test fire (from Table 1) Description Placement Position denotation (order as x,y,z) #8 Spray fire (4.5 bar, 0.19 Obstruction 3 right spray fire kg/min) #3 Pool fire 0.2 m 0.3 m Engine central-rear-top mockup #4 Pool fire Ø 0.15 m Obstruction 4 central-rearmostbottom #3 Pool fire 0.2 m 0.3 m Obstruction 3 right-central-upper #2 Pool fire 0.3 m 0.3 m Obstruction 3 right-rear-upper and 2 Fibreboards #3 Pool fire 0.2 m 0.3 m Obstruction 3 right-front-bottom Fan: The fan is not used. Test procedure: Time Action 00:00 Start measuring time 01:20 Ignite pool fires (within 20 seconds) 01:50 Start diesel spray 02:00 Activate suppression system

32 Appendix 2 page 3(18) 1.2 Test 2 Figure 20 Test 2 Figure 21 Test 2 (seen from rear side)

33 Appendix 2 page 4(18) Test fires: Test fire (Table 1) Description Placement Position denotation (order as x,y,z) #4 Pool fire Ø 0.15 m Corner left-front-bottom corner #4 Pool fire Ø 0.15 m Corner left-rear-bottom corner #4 Pool fire Ø 0.15 m Obstruction 4 central-rearmost-bottom #4 Pool fire Ø 0.15 m Obstruction 3 right-central-bottom #4 Pool fire Ø 0.15 m Obstruction 3 right-rear-bottom Fan: The fan is not used. Test procedure: Time Action 00:00 Start measuring time 01:00 Ignite pool fires (within 10 seconds) 02:00 Activate suppression system

34 Appendix 2 page 5(18) 1.3 Test 3 Figure 22 Test 3 Test fires used: Test fire (Table 1) Description Placement Position denotation (order as x,y,z) #2 Pool fire 0.3 m 0.3 m Obstruction 2 left-central-bottom and 2 Fibreboards (Concealed; Figure 17) #2 Pool fire 0.3 m 0.3 m Obstruction 3 right-central-bottom and 2 Fibreboards (Concealed; Figure 17) #4 Pool fire Ø 0.15 m Corner right-front-top corner Fan: The fan is not used. Test procedure: Time Action 00:00 Start measuring time 01:20 Ignite pool fires (within 15 seconds) 02:00 Activate suppression system

35 Appendix 2 page 6(18) 1.4 Test 4 Figure 23 Test 4 Figure 24 Test 4 (seen from rear side)

36 Appendix 2 page 7(18) Test fires: Test fire (Table 1) Description Placement Position denotation (order as x,y,z) #5 Pool fire 0.2 m 0.3 m and Obstruction 2 left-front-upper Class A-fire #5 Pool fire 0.2 m 0.3 m and Obstruction 3 right-front-bottom Class A-fire #5 Pool fire 0.2 m 0.3 m and Class A-fire Obstruction 4 right-rearmost-bottom Fan: Fan: 0.5 m 3 /s Test procedure: Time Action 00:00 Start measuring time 01:00 Ignite pool fire (within 10 seconds) 03:00 Start fan 04:00 Activate suppression system 09:00 End of test if no re-ignition

37 Appendix 2 page 8(18) 1.5 Test 5 Figure 25 Test 5 Test fires: Test fire (Table 1) Description Placement Position denotation (order as x,y,z) Obstruction 2 left spray fire kg/min) #7 Spray fire (4.5 bar, 0.73 #1 Pool fire 0.2 m 0.3 m Obstruction 2 left-central-upper #2 Pool fire 0.3 m 0.3 m Obstruction 2 left-rear-upper and 2 Fibreboards #1 Pool fire 0.3 m 0.3 m Obstruction 2 left-front-bottom #1 Pool fire 0.3 m 0.3 m Obstruction 3 right-front-bottom Fan: The fan is producing an air flow of 1.5 m 3 /s Test procedure: Time Action 00:00 Start measuring time 01:00 Ignite pool fires (within 20 seconds) 01:30 Engage the fan 01:50 Start diesel spray 02:00 Activate suppression system

38 Appendix 2 page 9(18) 1.6 Test 6 Figure 26 Test 6 Figure 27 Test 6 (seen from front side)

39 Appendix 2 page 10(18) Test fires: Test fire (Table 1) Description Placement Position denotation (order as x,y,z) #4 Pool fire Ø 0.15 m Corner left-front-bottom corner #3 Pool fire 0.3 m 0.2 m Obstruction 2 left-central-bottom #4 Pool fire Ø 0.15 m Obstruction 2* left-rearmost-bottom #4 Pool fire Ø 0.15 m Obstruction 4 central-rearmostbottom #4 Pool fire Ø 0.15 m Obstruction 3 right-central-bottom * Actually just outside the rear wall of Obstruction 2 Fan: The fan is producing an air flow of 1.5 m 3 /s Test procedure: Time Action 00:00 Start measuring time 01:00 Ignite pool fires (within 30 seconds) 01:30 Engage the fan 02:00 Activate suppression system

40 Appendix 2 page 11(18) 1.7 Test 7 Figure 28 Test 7 Test fires: Test fire (Table 1) Description Placement Position denotation (order as x,y,z) #4 Pool fire Ø 0.15 m Corner left-front-top corner #2 Pool fire 0.3 m 0.3 m Obstruction 2 left-central-bottom and 2 Fibreboards (Concealed; Figure 17) #2 Pool fire 0.3 m 0.3 m and 2 Fibreboards (Concealed; Figure 17) Obstruction 3 right-central-bottom Fan: The fan is producing an air flow of 1.5 m 3 /s Test procedure: Time Action 00:00 Start measuring time 01:20 Ignite pool fires (within 15 seconds) 01:30 Engage the fan 02:00 Activate suppression system

41 Appendix 2 page 12(18) 1.8 Test 8 Figure 29 Test 8 Test fires: Test fire (Table 1) Description Placement Position denotation (order as x,y,z) #7 Spray fire (4.5 bar, 0.73 Obstruction 2 left spray fire kg/min) #2 Pool fire 0.3 m 0.3 m Obstruction 2 left-front-upper and 2 Fibreboards #1 Pool fire 0.3 m 0.3 m Obstruction 2 left-central-upper #1 Pool fire 0.3 m 0.3 m Obstruction 2 left-rear-bottom #1 Pool fire 0.3 m 0.3 m Obstruction 3 right-central-bottom Fan: The fan is producing an air flow of 3.0 m 3 /s Test procedure: Time Action 00:00 Start measuring time 01:00 Ignite pool fires (within 20 seconds) 01:30 Engage the fan 01:50 Start diesel spray 02:00 Activate suppression system

42 Appendix 2 page 13(18) 1.9 Test 9 Figure 30 Test 9 Figure 31 Test 9 (seen from rear side)

43 Appendix 2 page 14(18) Test fires: Test fire (from Table 1) Description Placement Position denotation (order as x,y,z) #4 Pool fire Ø 0.15 m Corner left-front-bottom corner #3 Pool fire 0.3 m 0.2 m Obstruction 2 left-central-bottom #4 Pool fire Ø 0.15 m Corner left-rear-bottom corner #6 Fibreboard 0.2 m 0.3 Engine mockup central-central-top m #4 Pool fire Ø 0.15 m Obstruction 4 central-rearmostbottom #4 Pool fire Ø 0.15 m Obstruction 3 right-rear-bottom Fan: The fan is producing an air flow of 3.0 m 3 /s Test procedure: Time Action 00:00 Start measuring time 01:00 Ignite pool fires (within 30 seconds) 01:30 Engage the fan 02:00 Activate suppression system

44 Appendix 2 page 15(18) 1.10 Test 10 Figure 32 Test 10 Test fires: Test fire (Table 1) Description Placement Position denotation (order as x,y,z) #4 Pool fire Ø 0.15 m Corner left-front-top corner #2 Pool fire 0.3 m 0.3 m Obstruction 2 left-central-bottom and 2 Fibreboards (Concealed; Figure 17) #2 Pool fire 0.3 m 0.3 m and 2 Fibreboards (Concealed; Figure 17) Obstruction 3 right-central-bottom Fan: The fan is producing an air flow of 3.0 m 3 /s Test procedure: Time Action 00:00 Start measuring time 01:20 Ignite pool fires (within 15 seconds) 01:30 Engage the fan 02:00 Activate suppression system

45 Appendix 2 page 16(18) 1.11 Test 11 Test fires: Figure 33 Test 11 Test fire: Test fire Description (Table 1) #9 Dripping oil fire (40 droplets/min) Placement See Table 12 Fan: The fan is not used. Test procedure: Time Action -15:00 ±5 min Start of pre-heating the tube and measuring the temperature t(t=600 C)=0:00 End of pre-heating the tube 00:30 Start of dripping oil 00:45 Activate suppression system t ext. Extinction of the flames t ext. + 05:00 End of test if no re-ignition

46 Appendix 2 page 17(18) 2 Test fire coordinates Coordinates corresponding to the test fire placement denotations used in Appendix 1-1 are summarized in Table 8 Table 12. Table 8 Test fire placement in Obstruction 2 and Obstruction 3 Applies to placement inside: OBSTRUCTION 2 (left pipe obstruction module) OBSTRUCTION 3 (right pipe obstruction module) Test fire Description Corresponding coordinate x-wise placement denotation LEFT RIGHT #1, #2, #3, #5 Pool fires with trays 0.3 m 0.3 m and 0.2 m x 0.3 m 0.37 m 1.54 m #4 Pool fire Ø 0.15 m 0.45 m* 1.62 m Applies to placement inside: OBSTRUCTION 2 and OBSTRUCTION 3 y-wise placement denotation REAR CENTRAL FRONT #1, #2 Pool fires with trays 0.3 m 0.3 m 0.77 m 0.47 m #3, #5 Pool fires with trays 0.2 m 0.3 m m 0.13 m/0.23 m** #4 Pool fire Ø 0.15 m 0.92 m z-wise placement denotation UPPER BOTTOM #1, #2, #3, #4, #5 Pool fires with trays 0.3 m 0.3 m, 0.2 m x 0.3 m and Ø 0.15 m 0.36 m 0.00 m * Applies to #4 test fire in left-rearmost-bottom location in Test 6 which is actually just outside Obstruction 2 and not inside. ** Applies to Test 5 Table 9 Test fire placement on the Engine mockup Applies to placement on: ENGINE MOCKUP x-wise placement denotation CENTRAL #3, #6 Test fires with trays 0.2 m 0.3 m 0.97 m y-wise placement denotation CENTRAL REAR #3 Pool fire with tray 0.2 m 0.3 m m #6 Fibreboard 0.2 m x 0.3 m 0.45 m - z-wise placement denotation TOP #3, #6 Test fires with trays 0.2 m 0.3 m 0.70 m

47 Appendix 2 page 18(18) Table 10 Test fire placement in Obstruction 4 Applies to placement inside: OBSTRUCTION 4 (rear box) Test fire Description Corresponding coordinate x-wise placement denotation CENTRAL RIGHT #4 Pool fire Ø 0.15 m 0.97 m - #5 Pool fire & Class-A 0.2 m x 0.3 m m y-wise placement denotation REARMOST #4 Pool fire Ø 0.15 m 1.28 m #5 Pool fire & Class-A 0.2 m x 0.3 m 1.25 m z-wise placement denotation BOTTOM #4, #5 Pool fire Ø 0.15 m and Pool fire & Class m A 0.2 m x 0.3 m Table 11 Test fire placement in the corners Applies to placement in: CORNERS Test fire Description Location denotation and corresponding coordinates x-wise placement denotation LEFT RIGHT #4 Pool fire Ø 0.15 m 0.02 m 2.23 m y-wise placement denotation REARMOST FRONT #4 Pool fire Ø 0.15 m 1.20 m* 0.08 m z-wise placement denotation TOP BOTTOM #4 Pool fire Ø 0.15 m 0.92 m 0.00 m * Applies also to #4 test fire in left-rearmost-bottom location in Test 6 in vicinity of Obstruction 2 Table 12 Test fire placement of test fires using nozzles Applies to placement of: NOZZLE OUTLETS (SPRAY & DRIPPING OIL TESTS) Test fire Description Location denotation and corresponding coordinates (x, y, z) #7 Spray fire LEFT SPRAY FIRE (4.5 bar, 0.73 kg/min) 0.37 m 0.70 m 0.46 m #8 Spray fire RIGHT SPRAY FIRE (4.5 bar, 0.19 kg/min) 1.47 m 0.73 m 0.46 m #9 Dripping oil fire DRIPPING OIL FIRE 0.82 m 0.28 m 1.22 m

48 Appendix 3 page 1(1) Appendix 3 Report sheet Manufacturer: Approval test/ Pre-test no.: SP4912 Test: /Customized Suppression system name: Extinguishing agent: Date: Time: Number & type of nozzles: Test PASSED Test FAILED Extinguishing agent volume/mass: Pressurized vessel pressure: Extinguishing agent vessel volume: Extinguishing agent consumption: Position of extinguished (X) and not extinguished ( ) fires: Deviation from/description of test scenario (if customized): Suppression system modification from previous test: Observations: Signature: SP Sveriges Tekniska Forskningsinstitut

Proposal for amendments to UN Regulation No. 107 (Buses and coaches).

Proposal for amendments to UN Regulation No. 107 (Buses and coaches). Submitted by the expert from Sweden Informal document GRSG-105-08 (105 th GRSG, 8 11 October 2013 agenda item 2(a)) Proposal for amendments to UN Regulation No. 107 (Buses and coaches). The text reproduced

More information

Economic and Social Council

Economic and Social Council United Nations Economic and Social Council ECE/TRANS/WP.29/GRSG/2014/6 Distr.: General 20 February 2014 Original: English Economic Commission for Europe Inland Transport Committee World Forum for Harmonization

More information

Fire Detection and Alarm System (FDAS) & Fire Detection and Suppression Systems (FDSS) for Buses - Requirements

Fire Detection and Alarm System (FDAS) & Fire Detection and Suppression Systems (FDSS) for Buses - Requirements AUTOMOTIVE INDUSTRY STANDARD Fire Detection and Alarm System (FDAS) & Fire Detection and Suppression Systems (FDSS) for Buses - Requirements PRINTED BY THE AUTOMOTIVE RESEARCH ASSOCIATION OF INDIA P.B.

More information

Finalized Draft AUTOMOTIVE INDUSTRY STANDARD ARAI

Finalized Draft AUTOMOTIVE INDUSTRY STANDARD ARAI Finalized Draft AUTOMOTIVE INDUSTRY STANDARD Fire Detection and Alarm System (FDAS) & Fire Detection and Suppression Systems (FDSS) for Buses - Requirements ARAI Date of hosting on website: 12 th Last

More information

SP METHOD 5320 Issue No: Test method for fire detection systems installed in engine compartments of heavy vehicles

SP METHOD 5320 Issue No: Test method for fire detection systems installed in engine compartments of heavy vehicles SP METHOD 5320 Test method for fire detection systems installed in engine compartments of heavy vehicles Page 1(17) Copyright This test method is copyrighted by SP. Neither a printed nor electronic copy

More information

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety

More information

Finalized Draft AUTOMOTIVE INDUSTRY STANDARD

Finalized Draft AUTOMOTIVE INDUSTRY STANDARD Finalized Draft AUTOMOTIVE INDUSTRY STANDARD FIRE DETECTION AND ALARM SYSTEM (FDAS) & FIRE DETECTION AND SUPPRESSION SYSTEMS (FDSS) FOR BUSES OF TYPE III (AIS 052) - REQUIREMENTS ARAI Page 1 of 46 CHECK

More information

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1007 26 June 2001 GUIDELINES FOR THE

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 IMO E Ref.: T4/4.01 MSC.1/Circ.1272 4 June 2008 GUIDELINES FOR THE APPROVAL OF FIXED WATER-BASED

More information

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE The Protection of Machinery Spaces by means of the Local Application of Water Mist Dr. Tim R. Nichols CPhys FIFireE 2017 Johnson Controls. All rights reserved. Tyco Fire Products LP is a subsidiary of

More information

SPCR 183. RISE Research Institutes of Sweden AB Certification SPCR

SPCR 183. RISE Research Institutes of Sweden AB Certification SPCR SPCR 183 ignature_1 Certification rules for Fire suppression systems in engine compartments of buses and coaches RISE Research Institutes of Sweden AB Certification SPCR 183 2017-09-08 2 Preface Products

More information

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments Jason Huczek a, Marc Janssens a, Kentaro Onaka b, Stephen Turner c a SwRI, 6220 Culebra Road, San

More information

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES E 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: +44 (0)20 7735 7611 Fax: +44 (0)20 7587 3210 7 December 2018 REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR

More information

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G Ref. T4/4.01 IMO E MSC/Circ.914 4 June 1999 GUIDELINES FOR THE APPROVAL

More information

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen

Gerd Koffmane, Henrik Hoff, AP Sensing GmbH, Böblingen Linear Heat Series Under Test: Extensive fire tests prove Distributed Temperature Sensing (DTS) enables fast and reliable control of fire protection systems in road and rail tunnels Gerd Koffmane, Henrik

More information

RESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO

RESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO MSC 84/24/Add.2 RESOLUTION MSC.265(84) OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization

More information

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c 1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire

More information

FIRE CONTAINMENT AND CONTROL SYSTEMS

FIRE CONTAINMENT AND CONTROL SYSTEMS FIRE CONTAINMENT AND CONTROL SYSTEMS III INTERNATIONAL CONFERENCE MODERN TRENDS OF FIRE PROTECTION IN ROLLING STOCK WARSAW 2016-05-18 AUTHORS: SERGE MÉTRAL (SNCF) CONVENOR OF CEN TC256 WG1 GUILLAUME CRAVEUR

More information

BUS ENGINE COMPARTMENT FIRE PROTECTION SYSTEM FIREPRO TEST REPORT PEER REVIEW

BUS ENGINE COMPARTMENT FIRE PROTECTION SYSTEM FIREPRO TEST REPORT PEER REVIEW & e. INDUSTRIAL LOSS CONTROL & eng Analisi e Controllo dei Rischi Industriali HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE & ENGINEERING BUS ENGINE COMPARTMENT FIRE PROTECTION SYSTEM FIREPRO TEST REPORT

More information

Test Report: ICL/H18/9039 Rev 1

Test Report: ICL/H18/9039 Rev 1 Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk

More information

Heat and Smoke Release of a Ceiling-Installed Speaker

Heat and Smoke Release of a Ceiling-Installed Speaker WFCi Project #12051 Heat and Smoke Release of a Ceiling-Installed Speaker Indicative testing conducted in accordance with the test methodology described in UL 2043, Fire test for heat and visible smoke

More information

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SECTION FM-200 FIRE SUPPRESSION SYSTEM SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to

More information

The Loss prevention Council. Phase 1 report

The Loss prevention Council. Phase 1 report Phase 1 report Title: Investigation of the suitability of the Actual Delivered Density Apparatus (ADD) for the performance evaluation of standard sprinklers as described in Insurance Services project proposal

More information

Copy of article submitted to Fire Safety Engineering for publication January/February 2009

Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Copy of article submitted to Fire Safety Engineering for publication January/February 2009 Metal faced sandwich panels with plastic foam cores - a challenge to fire safety by Gordon Cooke Confusion, misleading

More information

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles Peter Stahl Wagner Schweiz AG, Wallisellen, Switzerland Abstract Fire detection system and firefighting solutions are getting a

More information

Laboratory fire experiments with a 1/3 train carriage mockup

Laboratory fire experiments with a 1/3 train carriage mockup SP Technical Research Institute of Sweden Laboratory fire experiments with a 1/3 train carriage mockup Alexander Claesson, Anders Lönnermark, Haukur Ingason, Johan Lindström, Ying Zhen Li and Mia Kumm

More information

Watermist Fire Protection of Plant Rooms

Watermist Fire Protection of Plant Rooms Guidance Note Watermist Fire Protection of Plant Rooms SCOPE This document sets out the requirements for protection of plant rooms with watermist systems and should be read in conjunction with BS8489-1.

More information

CERTIFICATION BULLETIN

CERTIFICATION BULLETIN ULC Subject C80.1 ULC G 5.2 ULC CCF February 14, 2012 CERTIFICATION BULLETIN 2012-01 Second Edition of ULC/ORD-C80.1 NMETALLIC TANKS FOR OIL-BURNER FUELS AND OTHER COMBUSTIBLE LIQUIDS Members of the Council

More information

An experimental study of the impact of tunnel suppression on tunnel ventilation

An experimental study of the impact of tunnel suppression on tunnel ventilation An experimental study of the impact of tunnel suppression on tunnel ventilation Yoon J. Ko and George Hadjisophocleous Civil and Environmental Engineering, Carleton University 1125 Colonel By Drive, Ottawa,

More information

Contact person Date Reference Page Richard Johansson P (2) Fire Research

Contact person Date Reference Page Richard Johansson P (2) Fire Research issued by an Accredited Testing Laboratory Contact person Richard Johansson 215-8-13 5P4413 1 (2) Fire Research +46 1 516 56 75 richard.johansson@sp.se 12 ISO/IEC 1725 Sklejka-Pisz Paged S.A Ul. kwiatowa

More information

The Science Behind Water Mist Protection of Typical Building Hazards

The Science Behind Water Mist Protection of Typical Building Hazards The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested

More information

ISO INTERNATIONAL STANDARD. Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source

ISO INTERNATIONAL STANDARD. Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source INTERNATIONAL STANDARD ISO 9239-1 Third edition 2010-06-15 Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source Essais de réaction au feu des

More information

Contact person Date Reference Page Alen Rakovic P (19) Fire Research

Contact person Date Reference Page Alen Rakovic P (19) Fire Research Contact person Alen Rakovic 2015-08-28 5P05551 1 (19) Fire Research +46 10 516 51 37 Alen.Rakovic@sp.se PcP. Durk Sverige AB Ruskvädersgatan 3B 418 34 Göteborg Fire Testing of fire protection gratings

More information

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM - 157 - SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM Kratzmeir S. FOGTEC Fire Protection, Research & Development, Germany Keywords: Fire Protection, Fire suppression,

More information

Fire Protection for Printing Machines with High Pressure Water Mist

Fire Protection for Printing Machines with High Pressure Water Mist Fire Protection for Printing Machines with High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Case Study PRINOVIS Printing Company - PRINOVIS is Europe s

More information

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The

More information

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage RESEARCH TECHNICAL REPORT SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale

More information

CO 2 Fire Extinguishing Systems

CO 2 Fire Extinguishing Systems Guidelines for Fire Extinguishing Systems Planning and Installation Content 0 Foreword... 10 0.1 Application of the VdS guidelines... 10 1 General... 10 1.1 Scope... 10 1.2 Aims... 11 1.3 Description...

More information

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS INTERNATIONAL MARITIME ORGANIZATION E IMO ASSEMBLY 23rd session Agenda item 17 A 23/Res.951 25 February 2004 Original: ENGLISH Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED

More information

FM Approvals & Water Mist Systems. Paul Bardsley Engineer, FM Approvals

FM Approvals & Water Mist Systems. Paul Bardsley Engineer, FM Approvals FM Approvals & Water Mist Systems Paul Bardsley Engineer, FM Approvals Presentation Outline Introduction to FM Global Introduction to FM Approvals FM 5560 - Water Mist Systems Who are FM Global? The largest

More information

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008 Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,

More information

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E. Benefiting Government, Industry and the Public Through Innovative Science and Technology Barry L. Badders, Jr. P.E. 7 December 2011 Part 1 Non-Combustibility Test Part 3 Test for A, B,, and F Class Divisions

More information

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS

FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS - 203 - FINDINGS FROM FIRE TESTS IN TUNNEL CONSTRUCTIONS WITH VENTILATION SYSTEMS AND FIXED FIRE SUPPRESSION SYSTEMS Hofer R., IBS Institute for Technical Fire Protection and Safety Research, Linz / Austria

More information

Large-scale fire test for interior materials of the Korean high speed train

Large-scale fire test for interior materials of the Korean high speed train Copyright 2012 Tech Science Press SL, vol.7, no.1, pp.13-18, 2012 Large-scale fire test for interior materials of the Korean high speed train W.H. Park 1, D.H. Lee 1, W.S. Jung 1 Abstract: A large-scale

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 11925-2 Third edition 2010-11-01 Reaction to fire tests Ignitability of products subjected to direct impingement of flame Part 2: Single-flame source test Essais de réaction

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center IR Energy Habanero HAB-M50 Gas Patio Heater Test Report Application of ASTM Standard Test Method FF2644-07 September 2014 Prepared by: Elan Frantz Trey Young Fisher-Nickel,

More information

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? Plumis White Paper April 2017 How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015? As with the introduction of every new formal product category through

More information

User Manual. 110 Cup (55 Cup Raw) Gas Rice Cooker. Model: 177GRCLP, 177GRCNAT 12/2018. Please read and keep these instructions. Indoor use only.

User Manual. 110 Cup (55 Cup Raw) Gas Rice Cooker. Model: 177GRCLP, 177GRCNAT 12/2018. Please read and keep these instructions. Indoor use only. 110 Cup (55 Cup Raw) Gas Rice Cooker Intertek 5010781 Conforms to ANSI STD Z83.11-2016 Model: 177GRCLP, 177GRCNAT 12/2018 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors or liquids

More information

Essentials of Fire Fighting 6 th Edition Firefighter I

Essentials of Fire Fighting 6 th Edition Firefighter I 1 Essentials of Fire Fighting 6 th Edition Firefighter I Chapter 5 Fire Behavior Replace with manual graphic on slide master Learning Objective 1 2 Explain the science of fire as it relates to energy,

More information

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number Indicative hoarding fire experiment Prepared for: London Fire Brigade 21 May 2014 Client report number 292366 1 Hoarding fire demonstration Prepared on behalf of BRE Fire and Security by Name Dr Sung-Han

More information

2. References EN 13829:2001. Thermal performance of buildings. Determination of air permeability of buildings. Fan pressurization method.

2. References EN 13829:2001. Thermal performance of buildings. Determination of air permeability of buildings. Fan pressurization method. 1. Purpose Assessment of potential on site airtightness of vapour control layer systems using accessory components. 2. References EN 13829:2001. Thermal performance of buildings. Determination of air permeability

More information

Ships and marine technology Fireextinguishing. of galley cooking equipment

Ships and marine technology Fireextinguishing. of galley cooking equipment INTERNATIONAL STANDARD ISO 15371 Third edition 2015-11-15 Ships and marine technology Fireextinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d extinction

More information

The first tunnel fire. Benefits of fire

The first tunnel fire. Benefits of fire Benefits of fire suppression Quantifying the effects of suppression on energy release. This article by Fathi Tarada, managing director of fire safety, risk management, ventilation and CFD consultant Mosen

More information

U.S. Coast Guard Research and Development Center 1082 Shennecossett Road, Groton, CT

U.S. Coast Guard Research and Development Center 1082 Shennecossett Road, Groton, CT U.S. Coast Guard Research and Development Center 182 Shennecossett Road, Groton, CT 634-648 Report No. CG-D-7-4 AN EVALUATION OF TOTAL FLOODING HIGH EXPANSION FOAM FIRE SUPPRESSION SYSTEMS FOR MACHINERY

More information

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor

More information

Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist

Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist Dipl.-Ing. Rüdiger Kopp FOGTEC Fire Protection ruediger.kopp@fogtec.com 1 Water Mist for Transformer Fire Protection

More information

The products covered by the Regulation can be classified as follows:

The products covered by the Regulation can be classified as follows: Table of Contents 1. Purpose of the guidelines and disclaimer... 3 1.1. The Regulation... 3 2. Scope... 3 3. Product environmental impacts... 4 4. State of play of legislation... 4 4.1. History of the

More information

Installation Manual EF5000 AUS & NZ

Installation Manual EF5000 AUS & NZ Installation Manual EF5000 AUS & NZ This manual is ONLY for fires with a serial No. from 80600 to 80999. Important: The appliance shall be installed in accordance with; Local gas fitting regulations Municipal

More information

Chapter 17, Initiating Devices

Chapter 17, Initiating Devices Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.

More information

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A. International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.800(19) Magnus Arvidson SP Fire Research SP Technical Research Institute

More information

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER , Volume 9, Number 1, p.38-58, 2007 ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER C.W. Leung and W.K. Chow Department of Building Services Engineering, The Hong Kong

More information

First Revision No. 6-NFPA [ Section No. 2.2 ]

First Revision No. 6-NFPA [ Section No. 2.2 ] Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon

More information

TUNPROTEC. Active Tunnel Fire Protection

TUNPROTEC. Active Tunnel Fire Protection VID FIre KIll TUNPROTEC Active Tunnel Fire Protection 9 An Active Tunnel Fire General The tunnel structures are very valuable. Infrastructure tunnels, such as train tunnels and road tunnels represent very

More information

ISO INTERNATIONAL STANDARD. Determination of the resistance to jet fires of passive fire protection materials Part 1: General requirements

ISO INTERNATIONAL STANDARD. Determination of the resistance to jet fires of passive fire protection materials Part 1: General requirements INTERNATIONAL STANDARD ISO 22899-1 First edition 2007-12-01 Determination of the resistance to jet fires of passive fire protection materials Part 1: General requirements Détermination de la résistance

More information

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE Application of BS 8489 to the Protection of Generator Enclosures IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE Agenda Generator Enclosure Characteristics Generator Fire Characteristics Machinery

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT ISO/TR 15657 First edition 2013-06-15 Fire resistance tests Guidelines for computational structural fire design Essais de résistance au feu Lignes directrices sur la conception statistique

More information

Examination of Performance of Water Mist Fire Suppression Systems under Ventilation Conditions

Examination of Performance of Water Mist Fire Suppression Systems under Ventilation Conditions Examination of Performance of Water Mist Fire Suppression Systems under Ventilation Conditions ZHIGANG LIU,* ANDREW K. KIM AND JOSEPH Z. SU Fire Risk Management, Institute for Research in Construction,

More information

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist Andrew Kim and George Crampton Fire Research Program, National Research Council of Canada 1200 Montreal Road, Ottawa, Ontario,

More information

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6 1. Purpose This policy sets forth requirements for preventing and detecting fires, sounding an alarm, and suppressing fires. Fire protection

More information

Fire Spread in Large Industrial Premises and Warehouses

Fire Spread in Large Industrial Premises and Warehouses Anders Lönnermark, Haukur Ingason Fire Spread in Large Industrial Premises and Warehouses BRANDFORSK project 63-21 SP Swedish National Testing and Research Institute SP Fire Technology SP REPORT 25:21

More information

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

ZONE MODEL VERIFICATION BY ELECTRIC HEATER , Volume 6, Number 4, p.284-290, 2004 ZONE MODEL VERIFICATION BY ELECTRIC HEATER Y.T. Chan Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Selecting

More information

Commission Working Document on possible Ecodesign Requirements for domestic ovens, hobs and range hoods

Commission Working Document on possible Ecodesign Requirements for domestic ovens, hobs and range hoods Commission Working Document on possible Ecodesign Requirements for domestic ovens, hobs and range hoods (1) Under Directive 2009/125/EC ecodesign requirements should be set by the Commission for energy-related

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

HOT AIR GENERATOR WITH GAS BURNER NA11.45 A GGS. Installation Operation Commissioning Maintenance

HOT AIR GENERATOR WITH GAS BURNER NA11.45 A GGS. Installation Operation Commissioning Maintenance Installation Operation Commissioning Maintenance HOT AIR GENERATOR WITH GAS BURNER GGS NA11.45 A 06-2011 04-2011 CONTENTS 1. DESCRIPTION OF THE UNIT 2. INSTALLATION & CONNECTION 3. COMMISSIONING 4. CARE

More information

ISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment

ISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment INTERNATIONAL STANDARD ISO 15371 Second edition 2009-03-15 Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d'extinction

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL HOT WATER HEATING BOILERS DOMESTIC WATER HEATERS 150,000-300,000 Btu/hr MODELS EB-EWU-02 IMPORTANT INSTALLER - AFFIX INSTALLATION MANUAL ADJACENT TO THE BOILER CONSUMER - RETAIN

More information

Ventilation Effects on Fire Patterns during Post Flashover Burning

Ventilation Effects on Fire Patterns during Post Flashover Burning Ventilation Effects on Fire Patterns during Post Flashover Burning By Matthew Obach, M.A.Sc., EIT, CFEI In order to determine the origin of a fire, fire investigators analyze fire patterns that remain

More information

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 Response-Time Comparisons of Ionization and Photoelectric/Heat Detectors 1. Introduction Despite

More information

MINIMUM PERFORMANCE REQUIREMENT FOR AIR FORCE FLIGHTLINE FIRE EXTINGUISHERS:

MINIMUM PERFORMANCE REQUIREMENT FOR AIR FORCE FLIGHTLINE FIRE EXTINGUISHERS: AFRL-ML-TY-TR-02-4540 MINIMUM PERFORMANCE REQUIREMENT FOR AIR FORCE FLIGHTLINE FIRE EXTINGUISHERS: EXTINGUISHING PERFORMANCE AGAINST 3-DIMENSIONAL AND HIDDEN FIRES MAY 2002 Approved for Public Release;

More information

INSTALLATION GUIDE Dual Fuel Ranges

INSTALLATION GUIDE Dual Fuel Ranges INSTALLATION GUIDE Dual Fuel Ranges Contents Wolf Dual Fuel Ranges......................... 3 Safety Instructions............................ 4 Dual Fuel Range Specifications.................. 5 Dual Fuel

More information

The requirements of BS Watermist Fire System standard and how to demonstrate compliance

The requirements of BS Watermist Fire System standard and how to demonstrate compliance The requirements of BS8489-1 Watermist Fire System standard and how to demonstrate compliance Bob Whiteley C. Eng.; F.I.Mech.E.; M.I.Fire E.; B.Tech(Hons) Chair: BSI Watermist Working Group Overview What

More information

Fire protection on chemical manufacturing sites

Fire protection on chemical manufacturing sites CFPA-E No 18:2008 Fire protection on chemical manufacturing sites FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation

More information

IMO INTERPRETATIONS OF FIRE PROTECTION-RELATED PROVISIONS OF THE HSC CODE

IMO INTERPRETATIONS OF FIRE PROTECTION-RELATED PROVISIONS OF THE HSC CODE INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 0171-735 7611 Fax: 0171-587 3210 Telex: 23588 IMOLDN G Ref. T4/4.01 IMO E MSC/Circ.911 4 June 1999 INTERPRETATIONS OF FIRE

More information

Emergency shutdown systems. Procedures for bypassing ESD s

Emergency shutdown systems. Procedures for bypassing ESD s HYDROCARBON PROCESS SAFETY 2 - ELEMENT 3 - UNIT IOG1 Emergency shutdown systems Emergency shutdown systems (ESD s) are intended to minimise the consequences of emergency situations, for example, the uncontrolled

More information

ISO/TS TECHNICAL SPECIFICATION. Fire detection and alarm systems Part 9: Test fires for fire detectors

ISO/TS TECHNICAL SPECIFICATION. Fire detection and alarm systems Part 9: Test fires for fire detectors TECHNICAL SPECIFICATION ISO/TS 7240-9 First edition 2006-01-01 Fire detection and alarm systems Part 9: Test fires for fire detectors Systèmes de détection et d'alarme d'incendie Partie 9: Essais sur foyers

More information

White Paper. The Victaulic Vortex Fire Suppression System Fire Suppression for Electrical and Electronic Applications

White Paper. The Victaulic Vortex Fire Suppression System Fire Suppression for Electrical and Electronic Applications White Paper The Victaulic Vortex Fire Suppression System Fire Suppression for Electrical and Electronic Applications Matthew Puzio, Senior Project Engineer, Fluid Control Technology, Victaulic updated

More information

DNVGL-CP-0401 Edition February 2016

DNVGL-CP-0401 Edition February 2016 CLASS PROGRAMME Type approval DNVGL-CP-0401 Edition February 2016 The electronic pdf version of this document, available free of charge from http://www.dnvgl.com, is the officially binding version. FOREWORD

More information

MOBILE FOOD SERVICE EQUIPMENT FIELD APPROVAL SUBMISSION INFORMATION

MOBILE FOOD SERVICE EQUIPMENT FIELD APPROVAL SUBMISSION INFORMATION Page: 1 of 5 The following will outline the information and material required to process the Field Approval of Mobile Food Service Equipment (MFSE). 1. Type of MFSE. See Page 2. 2. Equipment Identification

More information

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves. Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves Report No: 172158 Prepared for: Lindab Ventilation AB SE 26982 Båstad Järnvägsgatan

More information

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System 1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering

More information

Shell-and-Tube Heat Exchanger (Four Passes) - Optional

Shell-and-Tube Heat Exchanger (Four Passes) - Optional Exercise 2-4 Shell-and-Tube Exchanger (Four Passes) - Optional EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the design and particularities of the four-pass shell

More information

CEPE guidance to a quality control fire test regime for intumescent coatings Date of issue: 24 May 2011

CEPE guidance to a quality control fire test regime for intumescent coatings Date of issue: 24 May 2011 CEPE guidance to a quality control fire test regime for intumescent coatings Date of issue: 24 May 2011 This Guide was drawn up by a CEPE Committee based on the best knowledge currently available. The

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless

More information

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition

More information

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC)

ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) ASSESSING THE FIRE PERFORMANCE OF ELECTRIC CABLES (FIPEC) P. Van Hees and J. Axelsson, SP Sweden, S. J. Grayson and A. M. Green, Interscience Communications UK, H Breulet, ISSeP Belgium and U Vercellotti,

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Annex 2, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Section 1 Application 1 The following new sentence is added to the end of paragraph 1.2:

More information

Rubber and plastics hoses Method of test for flammability

Rubber and plastics hoses Method of test for flammability INTERNATIONAL STANDARD ISO 8030 Third edition 2014-07-15 Rubber and plastics hoses Method of test for flammability Tuyaux en caoutchouc et en plastique Méthode d essai d inflammabilité Reference number

More information

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005 Deutsche Akkreditierungsstelle GmbH Annex to the Accreditation Certificate D-PL-11035-03-00 according to DIN EN ISO/IEC 17025:2005 Period of validity: 25.10.2017 to 24.10.2022 Holder of certificate: DMT

More information

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES FIRE PROTECTIO FOR O-STORAGE OCCUPACIES WITH HIGH CEILIG CLEARACES SOOIL AM, ATOIO BRAGA, HSIAG-CHEG KUG, and JOA M. A. TROUP FM Global Research, 1151 Boston-Providence Turnpike, orwood, Massachusetts

More information