DO WE HAVE TO TEAR IT OFF?

Size: px
Start display at page:

Download "DO WE HAVE TO TEAR IT OFF?"

Transcription

1 DO WE HAVE TO TEAR IT OFF? Dr. Jonathan Barnett, FIEAust CPEng NER FSFPE PE Technical Director RED Fire Engineers

2

3 WHAT CAN GO WRONG

4

5

6

7

8

9

10

11

12

13 3.1 m x 3.1 m 3 m x 3 m Continuous to top of building 4.8 m x 4.8 m

14

15

16 THE FIRE

17

18

19

20 COST IMPACT FIRE

21 LOCATION EAST DOCKLANDS

22 LOCATION EAST DOCKLANDS

23 LACROSSE DOCKLANDS La Trobe Street, Melbourne 25 Nov Occupants 23 storeys $15,000, fire fighters involved

24 COST $6.5M (fire damage) 26 sprinkler heads operated, which along with water from hose streams resulted in $700,000 damage $8.6M (cladding) Replace non-fire damaged cladding $1M lost rent and cost of emergency accommodation Insurance premium increase of $130,000 since 2014

25 FACADE Case 1: Cladding is [part of] the exterior wall Case 2: Cladding is an attachment

26 WHAT IS AN ATTACHMENT? An adjunct or supplementary device

27 CASE 1: CLADDING IS PART OF THE EXTERNAL WALL If you remove the cladding, do you still have a complete wall? Does it look like a wall? Does it have the characteristics of an external wall? Keeps the weather out Protects the building from a nearby fire

28 IS IT AN ATTACHMENT? Back of interior plasterboard Remnant of ACP

29 IS IT COMBUSTIBLE? It does not pass AS1530.1

30 CASE 1: CLADDING IS PART OF THE EXTERNAL WALL For DtS product must be non-combustible as deemed or as tested to AS1530.1:1994 (Spec C (a)) Failure: Any flaming Furnace T > 50 C Specimen T > 50 C 750 C

31 IS IT ALLOWED? Certificate of compliance such as a Codemark? No Performance Solution (Alternative Solution) by a fire engineer? Not at time of construction

32 MBS ACTION Emergency Order Fire-affected apartments were cordoned off with fire rated construction Essential safety measures were repaired and re-activated and tested for compliance The MFB was placed on heightened alert to allow for quicker response. The architectural-decorative panels which were unsecured were removed.

33 NEXT STEP The damaged apartments were repaired The cladding on that section of the building was replaced with Vitracore G2 Meets AS through testing of component parts

34 MBS ACTION Building notice to remove and replace non-compliant external cladding. Notice to all 470 owners

35 RESPONSE Four entities representing the various Owners Corporations appealed the order to the Building Appeals Board.

36 THE BUILDING APPEALS BOARD Independent statutory body est. under the 1993 building act or the Building Regulations 2006 (The board dates back to Federation) Hears Modifications, Appeals, Disputes

37 LACROSSE AND THE BAB The owners Appealed the MBS Building orders to remove the ACP not involved in the fire and to replace it with one compliant with the requirements of the BCA Combustibility Structural stability Weatherproofing LU Simon requested and became a party to the appeals

38 LU SIMON S ROLE LU Simon was the builder should not be held responsible for the fire and subsequent damage because the blaze was caused by careless disposal of a cigarette and spread as a result of materials stored on the balcony. Cladding like the Alucobest brand used on the Lacrosse tower had been used across Australia for at least 40 years (From The Age, 26 Dec 2016).

39 LU SIMON S APPROACH Initially proposed banning of use of balconies for storage and a management in use plan to control over crowding (From The Age, 23 Mar 2016). For the appeal proposed wall wetting sprinklers and balcony sprinklers

40 AS Drencher system to provide protection to a building that is exposed to an external fire source Based on work in the 70s at the Experimental Building Station, Department of Housing and Construction, Australia for protection of glazing.

41 TYCO WS WINDOW SPRINKLER

42 USE ON CLADDING If the fire ignites the inside of the cladding where the fire will be shielded from an external water spray, the sprinkler s effectiveness is unknown. A small fire, starting down low, might be one example of such a fire A larger fire where the plume is blown away from the sprinkler head for a while, allowing ignition of the cladding is another such fire

43 EFFECTIVENESS Small fire might be worse than large fire Wind can allow ignition of cladding before sprinkler activation Fires from the inside will impact the cladding before external sprinkler activation

44 WHAT DID THE BAB FIND? There were no identified legal errors with the building orders, nor were the orders contrary to the building act The expert witnesses for all sides agreed that the ACT was combustible and did not meet the DtS requirements of the BCA

45 WHAT DID THE BAB FIND? LU Simon s alternative solution was supposed to address CP2 and CP4 CP2: to buildings, within buildings, to exits, to SOUs CP4: Resist fire and and maintain tenable conditions for escape LU Simon said the external sprinklers would comply with CP2 and CP4 and was at least equivalent to DtS

46 LARGE SCALE DEMONSTRATION BS8414 apparatus (Similar to AS5113) This large crib fire has a very small incipient stage, thus doesn t address the issue of a small fire igniting the cladding before sprinkler activation Lack of wind during the demonstration fire

47 LARGE SCALE DEMONSTRATION Didn t test fire from inside wall cavity to the outside Didn t test the ease of ignition of old or damaged ACP Lack of multiple tests, thus only a demonstration The heads used were not listed for such use anywhere in the world

48 LARGE SCALE DEMONSTRATION The MFB pointed out that during AS5113 development, sprinklers were discussed and rejected due to uncertainties

49 LACK OF COLLABORATION The BAB criticized LU Simon for not inviting all parties to witness the tests. From LU Simon s attorney: had that test not achieved the outcome that [it] achieved, it is likely that we would not have put forward the alternative solution of this matter before board

50 OVERALL ASSESSMENT Reliability of external sprinkler system is questionable as building s water supply has been downgraded from Grade 1 to Grade 2 Existing sprinkler system may not be as robust as no FRL between SOUs and between floors. (Lack of penetration seals) Lack of effective management in use plan (maintenance of sprinklers and ACP)

51 FINAL OUTCOME BAB refused to agree to the appeal.

52 Thank you JONATHAN BARNETT M: E:

Lessons Learned from the FaçadeFiasco. Dr. Jonathan Barnett Technical Director, RED Fire Engineers

Lessons Learned from the FaçadeFiasco. Dr. Jonathan Barnett Technical Director, RED Fire Engineers Lessons Learned from the FaçadeFiasco Dr. Jonathan Barnett Technical Director, RED Fire Engineers How did we arrive at the fac ade compliance problem and who is responsible? Who should cover rectification

More information

Post Incident Analysis Report

Post Incident Analysis Report Fire Safety Post Incident Analysis Report Reducing the incidence and impact of fire in the community MFB Burnley Complex 450 Burnley Street Richmond VIC 3121 Lacrosse Docklands 673-675 La Trobe Street,

More information

Fire Curtains and Radiation Attenuation

Fire Curtains and Radiation Attenuation The National Construction Code (NCC) provides a Deemed-to-Satisfy (DtS) method for fire barriers. This method generally requires these barriers to provide a specific fire resistance level (FRL) based on

More information

Design and Construction of South Asia s Tallest Tower Lotus Tower

Design and Construction of South Asia s Tallest Tower Lotus Tower Design and Construction of South Asia s Tallest Tower Lotus Tower Priyan Mendis, Professor of Civil Engineering, Director of ARC Center for Prefab Housing, University of Melbourne Contents Introduction

More information

MEDIUM-DENSITY HOUSING # 7. Fire safety

MEDIUM-DENSITY HOUSING # 7. Fire safety BRANZ FACTS MEDIUM-DENSITY HOUSING # 7 Fire safety Moving from low-density to medium-density housing (MDH) involves people living in closer proximity. This has a number of implications for fire safety

More information

FACADES AND FIRE The Essential Elements

FACADES AND FIRE The Essential Elements FACADES AND FIRE The Essential Elements Andy Dean BSc (Hons), MCIOB, FSFE Head of Façade Engineering WSP Middle East Manama, Bahrain, Jun 2014 Reaction to fire versus fire resistance LEARNING OBJECTIVES

More information

Fire safety and high rise student accommodation

Fire safety and high rise student accommodation Fire safety and high rise student accommodation This practical leaflet aims to explain the following: the Grenfell Tower fire the potential implications for students living in highrise halls what students

More information

Extreme Fires!

Extreme Fires! Extreme Fires! Is History Repeating Itself? 1971 - Airlie House Conference International Conference On Fire Safety In High-rise Buildings Evacuation impractical protect in place Limit fuel load prohibit

More information

FIRE RESCUE NSW RESEARCH PROJECT FOR SPRINKLERS IN BUILDINGS UNDER 25 METRES IN HEIGHT

FIRE RESCUE NSW RESEARCH PROJECT FOR SPRINKLERS IN BUILDINGS UNDER 25 METRES IN HEIGHT FIRE RESCUE NSW RESEARCH PROJECT FOR SPRINKLERS IN BUILDINGS UNDER 25 METRES IN HEIGHT John Clampett & Morgan Cook (Churchill Fellow 2012) Consultant & Team Leader Fire Research John Clampett Consulting

More information

CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation

CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation Speaker: Dr. L. K. Sze, Lipmann Technical Director of Date: 23 January, 2018 Disclaimer:

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

Fire Collars for Floor Wastes Understanding BCA Compliance Options

Fire Collars for Floor Wastes Understanding BCA Compliance Options Fire Collars for Floor Wastes Understanding BCA Compliance Options February 2005 Introduction There has been a great deal of discussion in recent times regarding fire testing requirements for fire collars

More information

Emergency Evacuation. Made Simple. EVACUATION STRATEGIES - PROBLEMS & SOLUTIONS EXPLAINED Alan Oliver

Emergency Evacuation. Made Simple. EVACUATION STRATEGIES - PROBLEMS & SOLUTIONS EXPLAINED Alan Oliver Emergency Evacuation. Made Simple EVACUATION STRATEGIES - PROBLEMS & SOLUTIONS EXPLAINED Alan Oliver TagEvac is the trusted, proven and safe way to manage evacuation of your building. Using intuitive information

More information

Cladding Screening Test Result

Cladding Screening Test Result Cladding Screening Test Result Submitting body Building address L&Q, One Kings Hall Mews, SE13 5JQ Flats 1-18, Burnell House, E20 1GY Organisation type: Contact details for test result Location of where

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the

More information

FIRE AND SECURITY CONSULTING SERVICES

FIRE AND SECURITY CONSULTING SERVICES FIRE AND SECURITY CONSULTING SERVICES http://fscs-techtalk.com 17 McKenna Court NOOSAVILLE QUEENSLAND, 4566 AUSTRALIA Phone: +61 (0)7 5455 5148, Mobile: 0409 399 190, Email: rafoster@bigpond.net.au MISCELLANEOUS

More information

Alarm Signalling Equipment: Connection Requirements (Victoria) TAN 06. Technical Advisory Note. Version 1 October 2018

Alarm Signalling Equipment: Connection Requirements (Victoria) TAN 06. Technical Advisory Note. Version 1 October 2018 TAN 06 Alarm Signalling Equipment: Connection Requirements (Victoria) Version 1 October 2018 1 1 Purpose statement The purpose of this is to provide advice concerning the legislative requirements for the

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot # 33-36 Sector # 07, Chittagong Chittagong Chittagong 08 Jun 2014 The Alliance for Worker Safety Page 1/18 08 Jun 2014 Introduction to the Report

More information

Mid Rise Timber Framing. Click here to start

Mid Rise Timber Framing. Click here to start Mid Rise Timber Framing Click here to start Mid Rise Construction - What s changed? Recent changes to the building code mean that you can now build up to 25m in height using timber. (termed mid-rise construction

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Mogorkhal, Chowrasta, National University, Gazipur Gazipur Dhaka 09 May 2016 The Alliance for Worker Safety Page 1/13 09 May 2016 Introduction to the

More information

SCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY

SCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY SCHEDULE Essential s taken from Schedule 9 of the Building Regulations 2006 43 PART 1 BUILDING FIRE INTEGRITY 1 Building elements required to satisfy prescribed fire-resistance levels 2 Materials and assemblies

More information

Appendix A: US Fire Statistics Tables

Appendix A: US Fire Statistics Tables Appendix A: US Fire Statistics Tables The following US fire statistics have been provided by Marty Ahrens and John R. Hall Jr. of the Fire Analysis and Research Division, National Fire Protection Association.

More information

What are the Concerns and How Can we Mitigate

What are the Concerns and How Can we Mitigate What are the Concerns and How Can we Mitigate Len Garis, Fire Chief City of Surrey, Adjunct Professor - School of Criminology and Criminal Justice & Associate to the Centre for Social Research University

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and

More information

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number Indicative hoarding fire experiment Prepared for: London Fire Brigade 21 May 2014 Client report number 292366 1 Hoarding fire demonstration Prepared on behalf of BRE Fire and Security by Name Dr Sung-Han

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Nayabari, Kanchpur, Sonargaon, Narayanganj. Sonargaon Dhaka 14 Nov 2013 The Alliance for Worker Safety Page 1/15 Factory 14 Nov 2013 Introduction to the

More information

The Melbourne Airport Precinct Fire Safety Strategy

The Melbourne Airport Precinct Fire Safety Strategy The Melbourne Airport Precinct Fire Safety Strategy Fire Safety Strategy Page 2 of 69 This document defines and informs the outcomes for fire safety within the Melbourne Airport Precinct. It addresses

More information

#5 Proposed Revisions to the Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies, Subject AC179-1011-R1 (RB/MB) John D. Nicholas Representing Background Relevant to AC179 18 Years in the Building

More information

Understanding Passive Fire Protection

Understanding Passive Fire Protection ASFP Response to Hackitt Report/Scottish Regulatory Review What is Passive Fire Protection and why is it important? Niall Rowan Chief Executive Officer Association for Specialist Fire Protection Contents

More information

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard SOCIAL ACCOUNTABILITY ACCREDITATION SERVICES To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard Background: After an

More information

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012 SAFETY CODES COUNCIL #1000, 10665 Jasper Avenue N.W., Edmonton, Alberta, Canada, T5J 389 Tel: 780-413-0099 I 1-888-413-0099 Fax: 780-424-5134 I 1-888-424-5134 www.safetycodes.ab.ca COUNCIL ORDER No. 0015423

More information

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006)

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) 1. INTRODUCTION 1.1 Essential Safety Measures Defined Essential Safety Measures (previously called essential services) are

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory 94/95 (OLD) 46 NEW (Ground To 5th), BLOCK C TONGI INDUSTRIAL AREA,, TONGI, GAZIPUR, GAZIPUR, 0, BD GAZIPUR Dhaka Bangladesh 11 Apr 2014 The Alliance for Bangladesh

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Assessor: 28 S.S. Tower, Vogra, Joydebpur, Gazipur Joydebpur, Gazipur Dhaka Uttaron The Alliance for Worker Safety Page 1/17 12 Apr 2015 Introduction to the Report The following

More information

Museum Towers EVACUATION PROCEDURE IN CASE OF FIRE

Museum Towers EVACUATION PROCEDURE IN CASE OF FIRE Museum Towers SP 40414 267-277 Castlereagh Street, Sydney, NSW 2000 Ph: 9267 1832 Fax: 9267 9485 Email: info@museumtowers.com.au Web: www.museumtowers.com.au EVACUATION PROCEDURE IN CASE OF FIRE Fire prevention

More information

WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS

WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS 1 WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS TABLE 4.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF ASSEMBLIES Construction

More information

Chapter Nursing Homes

Chapter Nursing Homes Chapter 16.01 Nursing Homes Section 1. Licensing. No nursing, convalescent or old age home, as defined in Section 2 of this ordinance, shall be operated except under a license from the City Council of

More information

Summerland leisure centre, Isle of Man, August 1973

Summerland leisure centre, Isle of Man, August 1973 Summerland leisure centre, Isle of Man, August 1973 At 20.00 on 2nd August 1973 fire started outside this leisure centre building and spread into the interior, especially the amusements area. Of the estimated

More information

CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES

CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES EMERGENCY MANAGEMENT DESIGN GUIDELINES 000331 Details of revisions Level Details Date Initial 1 Document created from 20150513NewBuildsAndRedevelopments.docx

More information

Learning from incidents IFE AGM and Conference 2014 Intelligent Engineering Reducing Risk 25 th and 26 th June 2014 Stratford on Avon

Learning from incidents IFE AGM and Conference 2014 Intelligent Engineering Reducing Risk 25 th and 26 th June 2014 Stratford on Avon Learning from incidents IFE AGM and Conference 2014 Intelligent Engineering Reducing Risk 25 th and 26 th June 2014 Stratford on Avon Martin Shipp Technical Development Director, Fire Safety BRE Part of

More information

COMPLYING DEVELOPMENT CERTIFICATE APPLICATION Made under the Environmental Planning and Assessment Act 1979 Sections 85, 85A

COMPLYING DEVELOPMENT CERTIFICATE APPLICATION Made under the Environmental Planning and Assessment Act 1979 Sections 85, 85A COMPLYING DEVELOPMENT CERTIFICATE APPLICATION Made under the Environmental Planning and Assessment Act 1979 Sections 85, 85A IDENTIFICATION OF BUILDING Address Lot, DP/MPS etc Suburb or town Post Code

More information

COMPLYING DEVELOPMENT CERTIFICATE APPLICATION FORM

COMPLYING DEVELOPMENT CERTIFICATE APPLICATION FORM COMPLYING DEVELOPMENT CERTIFICATE APPLICATION FORM Under the Environmental Planning and Assessment Act 1979/ Environmental Planning and Assessment Regulation 2000 SUBJECT LAND Lot: Section: DP/SP: APPLICANT/S

More information

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary

More information

8.1. Fire and Heritage. The maintenance series. Information sheet. Guidelines on Fire Safety in Heritage Buildings

8.1. Fire and Heritage. The maintenance series. Information sheet. Guidelines on Fire Safety in Heritage Buildings The maintenance series Information sheet 8.1 Fire and Heritage Destruction of the Prince of Wales Theatre by fire on 3 October 1860. It was situated at the corner of King and Castlereagh Streets, Sydney.

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT B.K. Bari, Taltoli, Mirzapur Bazar, Gazipur Sadar Gazipur Gazipur Dhaka The Alliance for Worker Safety Page 1/11 Introduction to the Report The following report

More information

Fire Engineering in the UK

Fire Engineering in the UK COST Action C26 Urban Habitat Constructions Under Catastrophic Events Malta, 23-25 October 2008 Fire Engineering in the UK A Fire Officer s Perspective Steve Beckley Chief Fire Officers Association and

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory 214 Baiozid Bostami Road Nasirabad Industrial Area Chittagong 04 Sep 2016 The Alliance for Bangladesh Worker Safety Page 1/11 Factory 04 Sep 2016 Introduction to

More information

FIRE/SMOKE BARRIER FUNDAMENTALS

FIRE/SMOKE BARRIER FUNDAMENTALS FIRE/SMOKE BARRIER FUNDAMENTALS William E. Koffel, P.E., FSFPE President Koffel Associates, Inc. www.koffel.com wkoffel@koffel.com Expertly Engineering Safety From Fire OBJECTIVE Identify the different

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 03-31-929 Application No. 2003-38 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.1.13.7.(1)

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

June 2017 (Updated 18 January 2018) Fire Safety Policy. Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited

June 2017 (Updated 18 January 2018) Fire Safety Policy. Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited June 2017 (Updated 18 January 2018) Fire Safety Policy Peter Webb, Project Manager Compliance First Choice Homes Oldham Limited Trusted provider of quality homes, excellent landlord and support services,

More information

Canadian Wood Council Fire and Safety Risks Posed by Wood Frame Residential Construction Professor / Fire Chief Len Garis July 15, 2015

Canadian Wood Council Fire and Safety Risks Posed by Wood Frame Residential Construction Professor / Fire Chief Len Garis July 15, 2015 Canadian Wood Council Fire and Safety Risks Posed by Wood Frame Residential Construction Professor / Fire Chief Len Garis July 15, 2015 Credit(s) earned on completion of this course will be reported to

More information

Kensington Aldridge Academy, London W10

Kensington Aldridge Academy, London W10 Kensington Aldridge Academy, London W10 Fire Safety Review Job Number: 1103 June 2018 FIRE SAFETY REVIEW CONTENTS EXECUTIVE SUMMARY 1.0 INTRODUCTION 2.0 FIRE SAFETY REQUIREMENTS 3.0 EXTERNAL WALL SPECIFICATION

More information

Page 1 of 4 FIRE REPORT - STRUCTURE Emergency Management BC / Office of the Fire Commissioner INCIDENT NUMBER: DDE 2014 06 17 05 03. Location of Incident: 4283 ARTHUR DR DELTA BC # of Occupants (At time

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 2 New Eskaton Road, Mogbazar, Dhaka Dhaka Dhaka Bangladesh 15 Jun 2013 The Alliance for Bangladesh Worker Safety Page 1/10 Factory Name: 15 Jun 2013

More information

Smoke Alarm Legislation

Smoke Alarm Legislation THE REQUIREMENT FOR SMOKE ALARMS Is it law for residential properties to have mains powered smoke alarms installed? The Building Regulations 2012 require owners to install compliant mains powered smoke

More information

Assistance in Case of Accidents with Ammonia

Assistance in Case of Accidents with Ammonia Assistance in Case of Accidents with Ammonia 1. Possible Causes Regular inspections of the relevant safety features in an ammonia refrigeration plant are part of complying with the (legal) requirements,

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction

More information

FIRESTOP INSPECTION. Dr. Selina LIN. Technical Manager August 01, FS Inspection 1

FIRESTOP INSPECTION. Dr. Selina LIN. Technical Manager August 01, FS Inspection 1 FIRESTOP INSPECTION Dr. Selina LIN Technical Manager August 01, 2017 FS Inspection 1 HILTI IN FIGURES Operations in more than 120 countries 23,385 employees (at the end of 2015) 120 nationalities in the

More information

Copyright 2018 American Wood Council 1

Copyright 2018 American Wood Council 1 Fire Tests in Support of Tall Mass Timber Buildings DES603 Sam Francis Senior Director, National Programs American Wood Council Jason Smart, P.E. Manager, Engineering Technology American Wood Council The

More information

5 Key Stages to Risk Assessment

5 Key Stages to Risk Assessment 5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT 171-181, Baizid Bostami Road Nasirabad I/A, Chittagong Chittagong The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Vill: Golora, Post: Kaitta P.S. Saturia, Manikgonj Manikgonj, Dhaka The Alliance for Bangladesh Worker Safety Page 1/14 Introduction to the Report The following

More information

Gothenburg dance hall, Sweden, 1998

Gothenburg dance hall, Sweden, 1998 Gothenburg dance hall, Sweden, 1998 The fire occurred on 28 October 1998 in a crowded dance hall in Gothenburg. 63 people died, 120 were injured and about 60 were rescued by the fire brigade. The hall

More information

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex:

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex: The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex: Mr. Junkers Lam Senior Building Surveyor of Buildings Department (9 Sept 2013) Part A Introduction Part B Means

More information

Annual Essential Safety Measures Report. 29 Bay Sample Street Port Melbourne VIC 3207

Annual Essential Safety Measures Report. 29 Bay Sample Street Port Melbourne VIC 3207 Annual Essential Safety Measures Report 29 Bay Sample Street Port Melbourne VIC 3207 30+ Years Experience In Reporting Services Our Quality Reports Make Roscon The Number #1 Choice We conduct onsite audits

More information

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 The Code of Practice for Fire Safety in Buildings 2011 The FS Code comprises 7 parts and 1 annex: Part A Introduction Part B

More information

[NOTE: Proposed additions to existing code language are highlighted in yellow.]

[NOTE: Proposed additions to existing code language are highlighted in yellow.] PROPOSED AMENDMENTS TO THE 2015 INTERNATIONAL RESIDENTIAL CODE AS ADOPTED BY LARIMER COUNTY FOR VACATION HOMES, LARGE VACATION HOMES AND SMALL HOTELS WITHIN THE ESTES VALLEY PLANNING AREA [NOTE: Proposed

More information

Tampa, FL Fire Cause Classification Task Group Tue, 14 April 2011

Tampa, FL Fire Cause Classification Task Group Tue, 14 April 2011 Fire Cause Classification Tampa, FL Tue, 12 April 2011 Proposals: CP2 - Chapter 19 (New 19 is a portion of old 19) CP3 - Chapter 20 (New 20 is the remainder of old 19) CP4-2 definitions in Chapter 3, as

More information

REFERENCES: ESSENTIALS OF FIRE FIGHTING, FOURTH EDITION, IFSTA ===============================================================

REFERENCES: ESSENTIALS OF FIRE FIGHTING, FOURTH EDITION, IFSTA =============================================================== TOPIC: REINVENTING FIRE PREVENTION LEVEL OF INSTRUCTION: TIME REQUIRED: TWO HOURS INSTRUCTOR GUIDE MATERIALS: APPROPRIATE AUDIO-VISUAL MATERIALS REFERENCES: ESSENTIALS OF FIRE FIGHTING, FOURTH EDITION,

More information

IFS Fiber Module Installation & Operation Instructions

IFS Fiber Module Installation & Operation Instructions DT00 DT00-R DT0 DT0-R IFS Fiber Module Installation & Operation Instructions DR00 DR00-R DR00 DR00-R P/N 0 REV B ISS 0AUG DT00 CONTACT WHEN ON CHANNEL CONTACT TRANSMITTER ifs International Fiber Systems

More information

Fire protection documentation. CFPA-E Guideline No 13:2015 F

Fire protection documentation. CFPA-E Guideline No 13:2015 F Fire protection documentation CFPA-E Guideline No 13:2015 F FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation in the

More information

Sprinklers in Wood-Frame Construction:

Sprinklers in Wood-Frame Construction: Sprinklers in Wood-Frame Construction: What Architects and Engineers Need to Know Presented by: Brian D. Kuhn Jr., P.E. (MA, CA, DC, 6 others), LEED Green Associate Please add relevant logo here Disclaimer:

More information

Sprinkler Systems and Fire Outcomes in Multi-Level Residential Buildings

Sprinkler Systems and Fire Outcomes in Multi-Level Residential Buildings Sprinkler Systems and Fire Outcomes in Multi-Level Residential Buildings Fire Chief Len Garis and Dr. Joseph Clare January 2012 Executive Summary 1. This paper summarizes the findings from an evaluation

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

Design Guidelines Fire Safety in New and Refurbished Buildings

Design Guidelines Fire Safety in New and Refurbished Buildings Design Guidelines Fire Safety in New and Refurbished Buildings Introduction All major new or refurbishment projects must comply with the Technical Standards (Scotland) Regulations as a matter of course.

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No. 74, Block -K, Rupnagar Ind. Area, Secti, Dhaka Dhaka Dhaka The Alliance for Worker Safety Page 1/8 Introduction to the Report The following report

More information

New Approaches to Design for Fire Safety

New Approaches to Design for Fire Safety New Approaches to Design for Fire Safety Tuesday, 20 th July 2010 Allister Smith UK Property Risk Manager Aviva Insurance Peter Wilkinson Associate Director Fire Protection Association Overview Financial

More information

Fire safety systems. Behaviour of fires

Fire safety systems. Behaviour of fires Fire safety systems The objective of the BCA Housing Provisions (Volume 2) with respect to Class 1 buildings (residential) and fire, is to safeguard occupants from illness or injury, to avoid the spread

More information

Fire protection of cantilevered external steel balconies in multistorey flats - a case study.

Fire protection of cantilevered external steel balconies in multistorey flats - a case study. Fire protection of cantilevered external steel balconies in multistorey flats - a case study. A presentation prepared for April 2015 meeting of the `Steel in Fire Forum, Institution of Structural Engineers,

More information

Mechanical Smoke Extract Shaft Systems

Mechanical Smoke Extract Shaft Systems Mechanical Smoke Extract Shaft Systems Presented by Mechanical Smoke Extract Shaft Systems Why Choose Crossflow? Crossflow is a family run company with over 45 years technical expertise. We are a solutions

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Nishchintapur, Ashulia DEPZ road, Zirabo, Savar Savar Dhaka 08 May 2014 The Alliance for Worker Safety Page 1/8 08 May 2014 Introduction to the Report The following

More information

FIRES IN BUILDING & CONSTRUCTIONS

FIRES IN BUILDING & CONSTRUCTIONS FIRES IN BUILDING & CONSTRUCTIONS By: ZEESHAN BARI AIM OF THE PRESENTATION inform how FIRE spreads in p onstructions and Buildings. OBJECTIVES After this Presentation you should be able to: Understand

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Mouza Chandra, Shafipur, Kaliakoir, Gazipur Gazipur Dhaka 24 Mar 2014 The Alliance for Worker Safety Page 1/12 24 Mar 2014 Introduction to the Report The following

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

DEALING WITH FIRE SAFETY

DEALING WITH FIRE SAFETY DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the

More information

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415 ASSESSMENT REVIEW Review of Assessment Report WFRA C91415 Fire resistance performance of steel electrical wall boxes mounted in plasterboard partitions with modified mounting arrangements, box design and

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Plot No -246-249, Adamjee EPZ, Siddhirganj, Narayanganj Narayanganj 17 Jul 2016 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jul 2016 Introduction

More information

Chapter 101 OPEN FIRES

Chapter 101 OPEN FIRES Chapter 101 OPEN FIRES 101.1. Definitions: 101.2. General Prohibition Against Open Burning: 101.3. Permitted Fires: 101.4. Authorized Locations: 101.5. Materials: 101.6. Time: 101.7. Prohibition Against

More information

Welcome to the. Firestop Seminar. Hilti Technical and Engineering Support

Welcome to the. Firestop Seminar.  Hilti Technical and Engineering Support Welcome to the Firestop Seminar www.hilti.co.uk/technical Hilti Technical and Engineering Support 1 Agenda 1. Passive Fire Protection a) The Importance of Firestop b) What are the Regulations c) Test Criteria

More information

Occupational Health & Safety Practitioner. Reading BUILDING FIRE SAFETY

Occupational Health & Safety Practitioner. Reading BUILDING FIRE SAFETY Occupational Health & Safety Practitioner Reading BUILDING FIRE SAFETY January 2009 Contents OVERVIEW...1 SECTION 1: INTRODUCTION...2 SECTION 2: BUILDING CLASSIFICATIONS...4 SECTION 3: PASSIVE AND ACTIVE

More information

CERTIFICATION SAFETY & BEYOND

CERTIFICATION SAFETY & BEYOND CERTIFICATION SAFETY & BEYOND Ferhun Emeksiz & R.M ( Max) Bradbury Client Manager & Fire Products Program Manager Global-Mark Pty Ltd Content Product Certification Understanding the framework Fundamental

More information

FIBERSHIELD V FIREIRE CURTAINSURTAINS (COMPACT FLEXIBLE AUTOMATIC FIRE BARRIERS)

FIBERSHIELD V FIREIRE CURTAINSURTAINS (COMPACT FLEXIBLE AUTOMATIC FIRE BARRIERS) FIREIRE CURTAINSURTAINS Approved for use for 30m wide x 10m drop in accordance with AS1530.4 and AS1905.2 KEY FEATURES Fire tested in accordance with AS1530.4 (Up to 2 hours) GENERAL Fibershield automatic

More information

Home Fires Are Common, Deadly and Preventable

Home Fires Are Common, Deadly and Preventable Home Fires Are Common, Deadly and Preventable Fire safety probably isn t high on the list of concerns for buyers when they purchase a home. But the statistics indicate that it should be. According to the

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment George Wright House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General

More information

Life Safety - Means of Egress/Exits NFPA 101

Life Safety - Means of Egress/Exits NFPA 101 Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all

More information

FIRE PREVENTION STRATEGY FOR BUILDINGS IN CONSTRUCTION. Fire Department, Taipei City Government, Taipei, Taiwan, ROC 2

FIRE PREVENTION STRATEGY FOR BUILDINGS IN CONSTRUCTION. Fire Department, Taipei City Government, Taipei, Taiwan, ROC 2 FIRE PREVENTION STRATEGY FOR BUILDINGS IN CONSTRUCTION Chun-Shing Yeh 1, Ban-Jwu Shih 2 and Chuan-Wei Wu 2 1 Fire Department, Taipei City Government, Taipei, Taiwan, ROC 2 Associate Professor, Department

More information

FIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES LEADING THE WAY IN FIRE PROTECTION

FIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES   LEADING THE WAY IN FIRE PROTECTION FIREMASTER ACTIVE FIRE CURTAIN BARRIER ASSEMBLIES WWW.COOPERSFIRE.COM.AU LEADING THE WAY IN FIRE PROTECTION DESIGN SOLUTIONS THAT WORK FOR YOU Active Fire Curtain Barrier Assemblies comprise technologically

More information