SPECIFICATIONS Annual Fire Pump Testing and Inspection Department of Technology, Management and Budget Managed Facilities - Statewide

Size: px
Start display at page:

Download "SPECIFICATIONS Annual Fire Pump Testing and Inspection Department of Technology, Management and Budget Managed Facilities - Statewide"

Transcription

1 SPECIFICATIONS Annual Fire Pump Testing and Inspection Department of Technology, Management and Budget Managed Facilities - Statewide PURPOSE This RFP is to establish a three year quote for service to provide annual test and inspection service for fire pumps per the following specifications and inventory list. Service shall be performed in accordance with currently adopted local and national codes including, but not limited to, NFPA 25. WORKING CONDITIONS All work shall be done in accordance with all regulations governing the Department of Technology, Management and Budget (DTMB), where the work is to be performed, and with the minimum possible interference of the daily working activities of DTMB. Materials, tools, etc., shall be confined so as not to unduly encumber the premises. WORKING HOURS Testing services shall be performed between the hours of 7:00AM and 5:00PM, Monday through Friday, except State holidays, or at the discretion of DTMB Office of Infrastructure Protection Safety Services Supervisor. Quarterly meetings may be held at the discretion of the Office of Infrastructure Protection Safety Services Supervisor to review contract compliance. TEST AND INSPECTION PROCEDURES Annual testing shall be performed in accordance with currently adopted local and national codes including, but not limited to, NFPA 25. Contractor shall schedule service with Office of Infrastructure Protection Safety Services Supervisor, or designee, ten (10) days in advance. Testing will be completed one building at a time. TESTING REQUIREMENTS Contractor shall coordinate with the Office of Infrastructure Protection Safety Services Supervisor, or designee, the removal of the fire alarm control panel from service prior to arrival. Contractor shall notify DTMB Central Control and the local Fire Department prior to testing. Upon completion of testing, contractor shall notify DTMB Central Control and the local fire department that the pump is back in service. Contractor shall coordinate with DTMB Office of Infrastructure Protection Safety Services Supervisor, or designee, the placement of the fire alarm control panel back into service prior to departure.

2 I. Motor Driven Pumps II. REPORTS - Drop pressure and record start and stop pressures of jockey pump - Operate jockey pump stop push button and record findings - Operate jockey pump start push button and record findings - Open jockey pump disconnecting means and ensure that all power is disconnected - Drop pressure and record start and stop pressures of Fire Pump - Run fire pump for a minimum of 30 minutes - Check and record motor voltage and amperage ( each phase leg ) - Check relief valve for setting and flow - Observe for excess noise, vibration etc. and record deficiencies - Check bearings for excessive vibration or excessive heat - Record suction and discharge pressures at Churn - Record suction and discharge pressures at 100 % of rated capacity - Record suction and discharge pressures at 150 % of rated capacity - Operate fire pump control panels stop pushbutton and record findings - Operate fire pump control panel start pushbutton and record findings - Open disconnecting means and ensure that all power is disconnected - Check fire pump packing for proper leakage - Drop pressure to ensure jockey pump will start and stop before fire pump is energized - When testing complete place back into automatic service - Place fire alarm control panel back in service Diesel Pumps - Clean battery terminals - Record fuel level - Grease fire pump coupling - Record specific gravity of battery - Report on condition of belts and hoses - Change engine oil and filter(s) - Change engine cooling solution and record temperature rating - Replace fuel filter - Clean or replace air filter - Check / drain water separator - Clean water strainers if applicable - Verify operation of cooling water solenoid if applicable - Report on condition of engine exhaust system - Report on fuel line condition - Ensure engine starts on EACH Battery - Ensure engine starts with manual start button - Ensure engine starts with drop in water pressure and record the starting pressure - Record engine running temperature - Record engine running oil pressure if available 1. All devices will be marked up on building prints for scheduled services. A comprehensive evaluation of system shall be prepared by contractor. The evaluation shall include contractor recommendations and price of labor and materials. 2. Test results along with a list of deficiencies shall be recorded during each service and shall be provided within 15 days of service.

3 3. A detailed price quote will be provided to repair the deficiencies identified during testing. A copy of all reports shall be provided to: DTMB Office of Infrastructure Protection Safety Services Supervisor 615 West Allegan Street EMERGENCY SERVICE Contractor shall respond within four (4) hours of requests for emergency service. A separate purchase order shall be issued for all emergency and non-emergency service calls. SITE VISIT An optional site visit may be arranged at the bidder s request. If a site visit is desired please contact the following person to make arrangements. Brenda Sprunger, Analyst DTMB-Financial Services Phone: sprungerb1@michigan.gov QUESTIONS Questions concerning this RFP must be submitted through Buy4Michigan ( no later than 3:00pm on July 24, 2013: Answers to questions will be prepared and posted under the bid number at: PAYMENT Invoices shall be submitted within 30 days after completion of service and receipt of test report. Invoice shall include building name and purchase order number. Invoices shall be for actual service provided. Invoices shall be sent to: DTMB Financial Services Accounts Payable Cass, 2 nd Floor 320 S. Walnut St DTMB-Accounts-Payable@michigan.gov Bidders Qualification NFPA 25 (Water-Based Fire Protection Systems) - These tasks shall be performed by personnel who have developed competence through training and experience.

4 PRICING SHEET Must be completed and included with proposal. The State is seeking quotes for three (3) years Bidder shall provide two separate costs: one for completing the work during normal business hours (Monday through Friday, 7:00AM - 5:00PM, except State holidays) and one for completing the work after normal business hours (Monday through Friday, 5:01PM - 6:59AM, Saturday & Sunday, 7:00AM - 5:00PM) CAPITOL COMPLEX (LANSING, MI) Address Year 1 Through 9/30/14 Year 2 Through 9/30/15 Year 3 Through 9/30/16 Allegan Ramp (2 pumps) Constitution Hall Grand Tower Hall of Justice John A. Hannah Lewis Cass Lottery Michigan State Police Headquarters Michigan Library & Historical Center Ottawa Romney State Laboratory 530 W. Allegan 525 W. Allegan 235 S. Grand 925 W. Ottawa 100 S. Pine 320 S. Walnut 101 E. Hillsdale 333 S. Grand 702 W. Kalamazoo 100 S. Pine 111 S. Capitol 3350 N. Martin Luther King Jr.

5 SECONDARY COMPLEX (DIMONDALE, MI) Address Year 1 Through 9/30/14 Year 2 Through 9/30/15 Year 3 Through 9/30/16 Michigan State Police Training Academy Operations Center Secretary of State 7426 N. Canal 7285 Parsons 7064 Crowner OUTSTATE BUILDINGS Address Year 1 Through 9/30/14 Year 2 Through 9/30/15 Year 3 Through 9/30/16 Flint State Office 125 E. Union Flint, MI Grand Rapids State Office Jackson State Office Jerome T. Hart State Office (Saginaw) 350 Ottawa, NW Grand Rapids, MI 301 E. Louis B. Glick Highway Jackson, MI 411 E. Genesee Saginaw, MI

6 Total Annual Year 1 Through 9/30/14 Total Annual Year 2 Through 9/30/15 Total Annual Year 3 Through 9/30/16 Total Annual Bidder shall provide quote for hourly labor rate for additional services. For quotational purposes only the State is not obligated to purchase any additional services. Labor Rate Year 1 Year 2 Year 3 Monday thru Friday 7:00 AM to 5:00PM $ /HR $ /HR $ /HR Monday thru Friday 5:01PM to 6:59AM $ /HR $ /HR $ /HR Weekends and Holidays $ HR $ /HR $ /HR

7 FIRE PUMP INVENTORY SHEET CAPITOL COMPLEX (LANSING, MI) Allegan Ramp Address Pump Make Pump Model 530 W. Allegan N. Pump Room - Peerless S. Pump Room - Peerless 6AF16 6AF16 Constitution Hall Grand Tower Hall of Justice John A. Hannah Lewis Cass Lottery Michigan State Police Headquarters Michigan Library & Historical Center Ottawa Romney State Laboratory 525 W. Allegan 235 S. Grand 925 W. Ottawa 100 S. Pine 320 S. Walnut 101 E. Hillsdale 333 S. Grand 702 W. Kalamazoo 100 S. Pine 111 S. Capitol 3350 N. Martin Luther King Jr. 8X6MIH ITT A-C X6MI ITT A-C 8000 Peerless 6AF16 Allis Chalmers X6MI ITT A-C 8000 ITT A-C 8X8X17F SECONDARY COMPLEX (DIMONDALE, MI) Address Pump Make Pump Model Michigan State Police Training Academy 7426 N. Canal Allis Chalmers Operations Center 7285 Parsons Peerless 5AEF14 (Diesel) Secretary of State 7064 Crowner ITT 1580

8 OUTSTATE BUILDINGS Flint State Office 125 E. Union Flint, MI Allis Chalmers KSJF Grand Rapids State Office 350 Ottawa, NW Grand Rapids, MI Peerless 6AF16 Jackson State Office Jerome T. Hart State Office (Saginaw) 301 E. Louis B. Glick Highway Jackson, MI 411 E. Genesee Saginaw, MI Peerless 8X6MJ 4ABF10

1. Delete BID FORM in its entirety and replace with the BID FORM attached to this Addendum.

1. Delete BID FORM in its entirety and replace with the BID FORM attached to this Addendum. ADDENDUM NO. 2 TO THE BIDDING DOCUMENTS Solicitation Number 2016-13 Fire Alarm, Sprinkler & BFP Inspections and Repairs Saint Clair County MidAmerica Saint Louis Airport DATE: November 30, 2016 BIDS CLOSE:

More information

COUNTY OF ROCKLAND Department of General Services Purchasing Division

COUNTY OF ROCKLAND Department of General Services Purchasing Division Department of General Services Purchasing Division Title: Contract Period: Fire Extinguishers and Suppression Systems-Inspection, Testing, Maintenance, Repair and Recharging 3/1/18 through 2/28/19 with

More information

This addendum responds to initial questions submitted by vendors. A1. Batteries are to be invoiced separately under the cost plus.

This addendum responds to initial questions submitted by vendors. A1. Batteries are to be invoiced separately under the cost plus. 5761 Keyo Building Orono, ME 04469-5761 Main:207-581-2712 ldd/tdy:207-973-3262 www.maine.edu REQUEST FOR PROPOSALS #030-17 University of Southern Maine Scheduled Testing, Inspection & Cleaning of Life

More information

SPECIFICATIONS FOR TENDER # SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH

SPECIFICATIONS FOR TENDER # SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH SPECIFICATIONS FOR TENDER #0371-0739 SUPPLY OF A FIRE ALARM SYSTEMS SERVICE AGREEMENT FOR WESTERN HEALTH CLOSING DATE: 8 June 2007 CLOSING TIME: 11:00 AM (Newfoundland Time) Invitation to Tender for a

More information

"This is only the scope of work for the project. For more information, interested parties should contact Procurement at

This is only the scope of work for the project. For more information, interested parties should contact Procurement at "This is only the scope of work for the project. For more information, interested parties should contact Procurement at purchasing@stpgov.org to ensure receipt of a full bid package, to be listed as a

More information

ELEVATOR RESCUE PROCEDURE

ELEVATOR RESCUE PROCEDURE ELEVATOR RESCUE PROCEDURE Office of Environmental Health & Safety December 2013 Table of Contents I. Purpose:... 3 II. Scope:... 3 III. Responsibility:... 3 IV. Types of Emergencies:... 3 V. Definitions:...

More information

"This is only the scope of work for the project. For more information, interested parties should contact Procurement at

This is only the scope of work for the project. For more information, interested parties should contact Procurement at "This is only the scope of work for the project. For more information, interested parties should contact Procurement at purchasing@stpgov.org to ensure receipt of a full bid package, to be listed as a

More information

Majis Industrial Services SAOC TENDER NO. MISCP/09/2014

Majis Industrial Services SAOC TENDER NO. MISCP/09/2014 Majis Industrial Services SAOC TENDER NO. MISCP/09/2014 Expression of Interest for Performance-based Operation and Maintenance (O&M) Services for the 20 MLD Majis Seawater Desalination Plant in Sohar,

More information

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website. 4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level II Content Outline The candidate for NICET certification at Level II in the Inspection and Testing of Water- Based

More information

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL SECTION 21 30 00 FIRE PROTECTION PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00,

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 3 Page 1 of 6 I. PURPOSE This procedure establishes guidelines for the weekly or monthly inspection and testing of all fire pumps within the University of Rochester by representatives of

More information

Mr. Burke presented the Airport and Boeing s badging process and public safety issues as outlined in the attached meeting agenda.

Mr. Burke presented the Airport and Boeing s badging process and public safety issues as outlined in the attached meeting agenda. MIDAMERICA ST. LOUIS AIRPORT TO: ISSUED BY: All Plan Holders and Meeting Attendees (Meeting Roster Attached) MidAmerica St. Louis Airport Dept. of Engineering & Planning DATE: November 22, 2016 Re: Summary

More information

REQUEST FOR PROPOSAL No Fire Extinguishers, Fire Suppression, Fire Alarms, Emergency Lighting & Sprinkler Systems Maintenance

REQUEST FOR PROPOSAL No Fire Extinguishers, Fire Suppression, Fire Alarms, Emergency Lighting & Sprinkler Systems Maintenance PURCHASING DEPARTMENT REQUEST FOR PROPOSAL No. 1895 Fire s, Fire Suppression, Fire s, Emergency Lighting & Sprinkler Systems Maintenance Addendum No. 1 July 7, 2017 This addendum shall be read in conjunction

More information

REQUEST FOR PROPOSALS CLEANING SERVICES

REQUEST FOR PROPOSALS CLEANING SERVICES REQUEST FOR PROPOSALS CLEANING SERVICES Jeffrey Gray City Manager City of Jonesville 265 E. Chicago Street Jonesville, MI 49250 manager@jonesville.org (517) 849-2104 Overview The City of Jonesville is

More information

March 27, ADDENDA No. 1. VARIOUS FIRE SERVICES Richland County, Ohio

March 27, ADDENDA No. 1. VARIOUS FIRE SERVICES Richland County, Ohio March 27, 2019 ADDENDA No. 1 Subject: Richland County, Ohio Enclosed herewith is a copy of Addenda No. 1 for the subject project. This material will be included in the final agreement and will become a

More information

PROGRAMMABLE ENERGY SAVING TIMER. ASAP Timers, LLC Multi-Family Timer Model A-1. User Manual

PROGRAMMABLE ENERGY SAVING TIMER. ASAP Timers, LLC Multi-Family Timer Model A-1. User Manual PROGRAMMABLE ENERGY SAVING TIMER ASAP Timers, LLC Multi-Family Timer Model A-1 User Manual Table of Contents Product Information...1 Normal Operation...2 Display and Touch points...2 Peak Electricity Demand

More information

Annual Fire Systems and Backflow Preventers Testing

Annual Fire Systems and Backflow Preventers Testing Facilities Management Request for Qualifications Annual Fire Systems and Backflow Preventers Testing At Various Facilities Proposals Due: 2:30 PM, Tuesday May 15, 2018 Deliver to: Attn: Sara Winger, Purchasing

More information

STATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC RACCOON CREEK STATE PARK (BEAVER COUNTY)

STATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC RACCOON CREEK STATE PARK (BEAVER COUNTY) STATEMENT OF WORK ELECTRICAL REPAIR / MAINTENANCE BUILDING PROJECT FDC-213-100797 RACCOON CREEK STATE PARK (BEAVER COUNTY) I. SCOPE OF WORK: The Commonwealth of Pennsylvania, Department of Conservation

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

REQUEST FOR PROPOSAL. Grounds Maintenance

REQUEST FOR PROPOSAL. Grounds Maintenance REQUEST FOR PROPOSAL Grounds Maintenance March 1, 2019 Invitation Syracuse City invites contractors to submit a bid to perform grounds maintenance of Syracuse City Hall, Police Station, and Museum. Bid

More information

marta 2424 Piedmont Rd. N.E. Atlanta, GA

marta 2424 Piedmont Rd. N.E. Atlanta, GA marta 2424 Piedmont Rd. N.E. Atlanta, GA 30324-3330 404-848-5000, February 20, 2013 TO ALL PLANHOLDERS SUBJECT: ADDENDUM NUMBER 1 PREVENTIVE MAINTENANCE AND REPAIR SERVICES FOR BUS FIRE SUPPRESSION AND

More information

Cohoes Housing Authority 100 Manor Sites Cohoes, NY P: F:

Cohoes Housing Authority 100 Manor Sites Cohoes, NY P: F: Cohoes Housing Authority 100 Manor Sites Cohoes, NY 12047 P: 518-235-4500 F: Authority wide Landscaping Improvements The Cohoes Housing Authority of the City of Cohoes, New York is receiving proposals

More information

Request for Bid Proposal For Repair of Sprinkler Systems Iowa Veterans Home Marshalltown, Iowa

Request for Bid Proposal For Repair of Sprinkler Systems Iowa Veterans Home Marshalltown, Iowa The is seeking a service provider to correct the deficiencies of the fire sprinkler system as identified during a standard inspection. Deficiencies will be corrected per NFPA 25 in the buildings located

More information

Request for Proposal

Request for Proposal Request for Proposal Intent: The State of New Jersey Department of Environmental Protection Division of Parks and Forestry, Forest Service (NJFS) has been awarded a grant under the federal American Recovery

More information

Request for Proposal

Request for Proposal Request for Proposal Intent: The State of New Jersey Department of Environmental Protection Division of Parks and Forestry, Forest Service (NJFS) has been awarded a grant under the federal American Recovery

More information

Sheetz Inc. Fire Protection Service Guidelines

Sheetz Inc. Fire Protection Service Guidelines Sheetz Inc. Fire Protection Service Guidelines Overview The following are guidelines for Sheetz Fire Protection Services for the 2016/2018 contract year. Each key area is listed below with the appropriate

More information

This addendum responds to initial questions submitted by vendors.

This addendum responds to initial questions submitted by vendors. 5761 Keyo Building Orono, ME 04469-5761 Main:207-581-2712 ldd/tdy:207-973-3262 www.maine.edu REQUEST FOR PROPOSALS #125-2017 Mechanical & HVAC Preventative Maintenance, Inspection & Repair Services for

More information

TEXAS DEPARTMENT OF TRANSPORTATION PORTABLE FIRE EXTINGUISHER SERVICES ANNUAL INSPECTION MAINTENANCE, REPAIR, AND RECHARGING

TEXAS DEPARTMENT OF TRANSPORTATION PORTABLE FIRE EXTINGUISHER SERVICES ANNUAL INSPECTION MAINTENANCE, REPAIR, AND RECHARGING TEXAS DEPARTMENT OF TRANSPORTATION SPECIFICATION NO. * PORTABLE FIRE EXTINGUISHER SERVICES ANNUAL INSPECTION MAINTENANCE, REPAIR, AND RECHARGING PUBLICATION This specification is a product of the Texas

More information

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING.

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING. SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING Table of Contents Section Title Page 1 Introduction 2 2 Proposed Schedule 2 3 Instructions

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 23 05 93 - TESTING, ADJUSTMENT AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Austin Independent School District Police Department Policy and Procedure Manual

Austin Independent School District Police Department Policy and Procedure Manual Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for

More information

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SMALL WORKS PROJECT REQUEST FOR SEALED BIDS

SMALL WORKS PROJECT REQUEST FOR SEALED BIDS SMALL WORKS PROJECT REQUEST FOR SEALED BIDS PIERCE COUNTY FIRE PROTECTION DISTRICT #22 18421 OLD BUCKLEY HIGHWAY BONNEY LAKE, WA 98391 (253) 863-1800 (253) 863-1848 (FAX) Date Bid Requested: 5/24/2012

More information

S T A T E O F F L O R I D A D E P A R T M E N T O F J U V E N I L E J U S T I C E BUREAU OF MONITORING AND QUALITY IMPROVEMENT PROGRAM REPORT FOR

S T A T E O F F L O R I D A D E P A R T M E N T O F J U V E N I L E J U S T I C E BUREAU OF MONITORING AND QUALITY IMPROVEMENT PROGRAM REPORT FOR S T A T E O F F L O R I D A D E P A R T M E N T O F J U V E N I L E J U S T I C E BUREAU OF MONITORING AND QUALITY IMPROVEMENT PROGRAM REPORT FOR BI, Inc. - Electronic Monitoring (Contract Provider ) 6265

More information

YTD. IT Manager Smith attended the quarterly ESO Oversight Committee meeting on Monday, October 29 th in Bellevue.

YTD. IT Manager Smith attended the quarterly ESO Oversight Committee meeting on Monday, October 29 th in Bellevue. 2ADMINISTRATOR S 2018 WEEKLY REPORT # 2018-44 October 29 th November 4 th, 2018 CALLS FOR SERVICE This Week 2018 YTD YTD Change Fire 3 365-1.9% Aid 206 8483 4% Other 55 2330-8.2% Total 264 11178 1% Last

More information

System Test Report CLEAN AGENT

System Test Report CLEAN AGENT City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information

More information

Authorized individuals to be notified. Include two (2) persons with access to the premises to allow emergency access.

Authorized individuals to be notified. Include two (2) persons with access to the premises to allow emergency access. Registration of Private Alarm Systems Town of Lincoln Date: $25.00 Registration $10.00 Renewal Address of Alarmed Property: Phone # of Alarmed Property: Owner s Name: Owner s Home Address: Owner s Home

More information

The following is a list of civic buildings and properties that may be appropriate for filming:

The following is a list of civic buildings and properties that may be appropriate for filming: Civic Properties The following is a list of civic buildings and properties that may be appropriate for filming: BUILDING Vancouver Centennial Museum Vancouver Maritime Museum St. Rock Shelter Planetarium

More information

Regional Office: Agra Padam Business Park, Ground Floor, Sector 12 A, Avas Vikas Sikandara Yojna, Agra 282007 Phone: 0562 2600481, Fax: 0562 2600582 E-mail: ro.agra@syndicatebank.co.in -------------------------------------------------------------------------------------------------------------------------------

More information

District Heat Montpelier. Customer Training

District Heat Montpelier. Customer Training District Heat Montpelier Customer Training 1 Welcome & Overview of Training Introductions District Heat Montpelier Overview In Building Components On Going Maintenance and Best Practices Optimizing Performance

More information

(3) Chart. The following chart illustrates the above hours: TABLE INSET:

(3) Chart. The following chart illustrates the above hours: TABLE INSET: The City of Fort Myers, Florida CDD/BUSINESS TAX 1825 Hendry Street Suite 101 Fort Myers, Florida 33901 (239)321-7990 BUSINESS TAX RECIEPT APPLICATION INFORMATION SHEET FOR NIGHTCLUBS To obtain a City

More information

PLP - TERMS AND CONDITIONS Philadelphia Gas Works Residential Parts & Labor Plan Contract

PLP - TERMS AND CONDITIONS Philadelphia Gas Works Residential Parts & Labor Plan Contract PLP - TERMS Residential Parts & Labor Plan Contract TERMS This Residential Parts & Labor Plan Contract (this Plan ) is available to customers of the ( PGW ) who have natural gas house heaters, gas water

More information

BIRCH RUN TOWNSHIP SAGINAW COUNTY, MICHIGAN ORDINANCE NO ALARM SYSTEM ORDINANCE AMENDMENT

BIRCH RUN TOWNSHIP SAGINAW COUNTY, MICHIGAN ORDINANCE NO ALARM SYSTEM ORDINANCE AMENDMENT BIRCH RUN TOWNSHIP SAGINAW COUNTY, MICHIGAN ORDINANCE NO. 2017-01 ALARM SYSTEM ORDINANCE AMENDMENT ADOPTED: April 18, 2017 PUBLISHED: April 26, 2017 EFFECTIVE: May 26, 2017 An Ordinance to amend Sections

More information

LIVINGSTON COUNTY BOARD PROPERTY COMMITTEE MINUTES OF OCTOBER 1, 2018

LIVINGSTON COUNTY BOARD PROPERTY COMMITTEE MINUTES OF OCTOBER 1, 2018 LIVINGSTON COUNTY BOARD PROPERTY COMMITTEE MINUTES OF OCTOBER 1, 2018 Committee Chair Mike Ingles called the meeting to order at 6:00 p.m. in the committee meeting room in the Historic Livingston County

More information

COUNTY OF ROCKLAND Department of General Services Purchasing Division

COUNTY OF ROCKLAND Department of General Services Purchasing Division COUNTY OF ROCKLAND Department of General Services Purchasing Division Title: Contract Period: Alarm System Inspection, Testing, Maintenance and Repair- Fire Alarm Systems, September 6, 2017 through September

More information

Invitation to Bid WATER HEATER HHS & WHH

Invitation to Bid WATER HEATER HHS & WHH Invitation to Bid WATER HEATER HHS & WHH Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066 for WATER

More information

MANUAL OF PROCEDURE. Keys and Access Control (Standard and Electronic)

MANUAL OF PROCEDURE. Keys and Access Control (Standard and Electronic) MANUAL OF PROCEDURE PROCEDURE NUMBER: 1411 PAGE 1 of 6 PROCEDURE TITLE: STATUTORY REFERENCE: BASED ON POLICY: Keys and Access Control (Standard and Electronic) Florida Statutes 1001.64, 1013.37, and 934.03;

More information

Brunswick-Glynn County Joint Water & Sewer Commission

Brunswick-Glynn County Joint Water & Sewer Commission Brunswick-Glynn County Joint Water & Sewer Commission INVITATION FOR BIDS DATE: 18 August 2015 PROJECT: Academy Creek Sludge Dryer Repairs 1.0 PROJECT DESCRIPTION The Brunswick-Glynn Joint Water & Sewer

More information

S T A T E O F F L O R I D A D E P A R T M E N T O F J U V E N I L E J U S T I C E BUREAU OF MONITORING AND QUALITY IMPROVEMENT PROGRAM REPORT FOR

S T A T E O F F L O R I D A D E P A R T M E N T O F J U V E N I L E J U S T I C E BUREAU OF MONITORING AND QUALITY IMPROVEMENT PROGRAM REPORT FOR S T A T E O F F L O R I D A D E P A R T M E N T O F J U V E N I L E J U S T I C E BUREAU OF MONITORING AND QUALITY IMPROVEMENT PROGRAM REPORT FOR 3M Electronic Monitoring (Contract Provider) 1838 Gunn

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES SECTION 21 30 00 FIRE PUMPS GENERAL This standard provides general requirements of The University of South Alabama in Mobile Alabama for fire pumps. This document is not intended to serve as a guide specification.

More information

NEW RESIDENT CHECKLIST

NEW RESIDENT CHECKLIST NEW RESIDENT CHECKLIST Welcome to Matteson! Our community has so much to offer. Beyond its many amenities, our community has a strong hometown appeal that will make you proud of living in Matteson. Your

More information

PROCEDURE: FURNITURE, ART, & DÉCOR STANDARDS & REQUESTS

PROCEDURE: FURNITURE, ART, & DÉCOR STANDARDS & REQUESTS Office of Planning, Design, and Construction 2500 North State Street Jackson, Mississippi 39216-4505 Phone (601) 984-1410 Date: July 7, 2017 PROCEDURE: FURNITURE, ART, & DÉCOR STANDARDS & REQUESTS 1.1

More information

SarasotaCountySchools.net

SarasotaCountySchools.net July 18, 2017 Materials Management Purchasing Department 101Old Venice Road, Osprey, FL 34229 Phone 941-486-2183 Fax 941-486-2188 SarasotaySchools.net MEMORANDUM TO: FROM: TITLE: Members of the School

More information

Urban Gardener Certification Program Application & Agreement 2013

Urban Gardener Certification Program Application & Agreement 2013 Urban Gardener Certification Program Application & Agreement 2013 Thank you for your interest in the Hunter Park GardenHouse Urban Gardener Certification Program! Here you will find a description of the

More information

11 CONTRACT AWARD FOR SECURITY SERVICES

11 CONTRACT AWARD FOR SECURITY SERVICES 11 CONTRACT AWARD FOR SECURITY SERVICES The Finance and Administration Committee recommends the adoption of the recommendations contained in the following report dated November 3, 2011, from the Commissioner

More information

USD 480 Auxiliary Services Department Robert Burkey, Director

USD 480 Auxiliary Services Department Robert Burkey, Director USD 480 Auxiliary Services Department Robert Burkey, Director Maintenance, Buildings & Grounds Custodial/Warehouse Tim Hickert, Supervisor Misael Garcia, Supervisor Phone: (620) 604-1070 Phone: (620) 604-2494

More information

PLEASE NOTE! This plan must include: setback dimensions, gas meter location, any obstructions, well and septic

PLEASE NOTE! This plan must include: setback dimensions, gas meter location, any obstructions, well and septic PLEASE NOTE! Your application for gas service cannot be processed without a copy of your site or plot plan that clearly shows the location of your new home on your lot. This plan must include: setback

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

Housing & Residence Life - Building Emergency Evacuation Plan

Housing & Residence Life - Building Emergency Evacuation Plan 9201 University City Blvd, Charlotte, NC 28223-0001 t/ 704.687.1111 f/ 704.687.5302 http://safety.uncc.edu/ Housing & Residence Life - Building Emergency Evacuation Plan This plan establishes fire and

More information

STEP 1: SELECT A NITROGEN GENERATOR STEP 2: SELECT A VENT STEP 3: SELECT MONITORING EQUIPMENT STEP 4: CONTACT ECS

STEP 1: SELECT A NITROGEN GENERATOR STEP 2: SELECT A VENT STEP 3: SELECT MONITORING EQUIPMENT STEP 4: CONTACT ECS STEP 1: SELECT A NITROGEN GENERATOR To ensure the nitrogen generator is adequately sized, the following information is required: The total cumulative size of all dry/preaction sprinkler systems The size

More information

YTD. Administrator Robertson attended the Auburn Area Chamber of Commerce meeting on Tuesday, July 17 th in Auburn.

YTD. Administrator Robertson attended the Auburn Area Chamber of Commerce meeting on Tuesday, July 17 th in Auburn. ADMINISTRATOR S WEEKLY REPORT # 2018-29 July 16 th 22 nd, 2018 CALLS FOR SERVICE This Week 2018 YTD YTD Change Fire 19 244 14.6% Aid 182 5633 3.6% Other 63 1495-7.9% Total 264 7372 1.3% Last Week: Administrator

More information

201 High Street Farmville, Virginia June 4, 2007 at 2:00 p.m. local time

201 High Street Farmville, Virginia June 4, 2007 at 2:00 p.m. local time May 23, 2007 ADDENDUM 1 TO ALL BIDDERS: Reference: 214-07- Inspection Fire Alarms Dated: May 10, 2007 Commodity: Fire Alarm Maintenance & Inspection Delivery To: Longwood University 201 High Street Farmville,

More information

SUMTER COUNTY BOARD OF COMMISSIONERS EXECUTIVE SUMMARY

SUMTER COUNTY BOARD OF COMMISSIONERS EXECUTIVE SUMMARY SUMTER COUNTY BOARD OF COMMISSIONERS EXECUTIVE SUMMARY SUBJECT: Renewal of contract with VSC Fire & Security for RFP 011-0-2014/CRM Sumter County Fire Prevention Services (Staff recommends approval). REQUESTED

More information

Highway 417 Expansion East

Highway 417 Expansion East Highway 417 Expansion East Nicholas Street to Ottawa Road 174 GWP 4091-07-00 & GWP 4320-06-00 Outline Project Overview Highway 417 Widening Bridge Rapid Replacements Traffic & Incident Management Project

More information

Plant Operations Cleaning and Sanitation Audits.

Plant Operations Cleaning and Sanitation Audits. Plant Operations Cleaning and Sanitation Audits http://plantoperations.dadeschools.net/ DISTRICT-WIDE SCHOOLS Cleaning & Sanitation Audit (4 years) Overall Scores % Fail % Pass 90% 63% 37% 54% 46% 45%

More information

Memo. Fire Department Members, Municipal Representatives, First Responders and Emergency Services Personnel

Memo. Fire Department Members, Municipal Representatives, First Responders and Emergency Services Personnel Government of Newfoundland and Labrador Fire and Emergency Services Memo Date: February 19, 2018 To: Fire Department Members, Municipal Representatives, First Responders and Emergency Services Personnel

More information

Florida Department of Transportation

Florida Department of Transportation Page 1 of 7 RICK SCOTT GOVERNOR Florida Department of Transportation 1109 S. Marion Avenue Lake City, Florida 32025 ANANTH PRASAD SECRETARY September 27, 2011 To: Proposal Holders Addendum No: 1, E2Q23,

More information

STATEMENT OF WORK I. SCOPE OF WORK:

STATEMENT OF WORK I. SCOPE OF WORK: STATEMENT OF WORK Purchase and Installation of Diesel Standby Generator Set and Service Entrance Rated Automatic Transfer Switch for Sewage Treatment Plant Nockamixon State Park (Bucks County) I. SCOPE

More information

SECTION SECURITY TESTING AND COMMISSIONING

SECTION SECURITY TESTING AND COMMISSIONING SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,

More information

Lead Remediation/Abatement at Forest Blvd., Hugo, MN

Lead Remediation/Abatement at Forest Blvd., Hugo, MN Request for Bids for Lead Remediation/Abatement at 14383 Forest Blvd., Hugo, MN This Request for Bids ( RFB ) is for the services of a qualified and licensed contractor to provide remediation/abatement

More information

YTD. The monthly Safety Committee meeting was held on Monday, July 2 nd at GSA Station 35.

YTD. The monthly Safety Committee meeting was held on Monday, July 2 nd at GSA Station 35. ADMINISTRATOR S WEEKLY REPORT # 2018-27 July 2 nd 8 th, 2018 CALLS FOR SERVICE This Week 2018 YTD YTD Change Fire 44 211 23.4% Aid 200 5229 3.7% Other 81 1372-7.7% Total 325 6812 1.7 % Last Week: The monthly

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

BANK OF BARODA BARODA CORPORATE CENTRE MUMBAI

BANK OF BARODA BARODA CORPORATE CENTRE MUMBAI BANK OF BARODA BARODA CORPORATE CENTRE MUMBAI TENDER NOTICE FOR ANNUAL MAINTENANCE CONTRACT AND REFILLING OF FIRE EXTINGUISHERS AT BANK OF BARODA CORPORATE OFFICE BUILDINGS IN MUMBAI NAME OF WORK: Bank

More information

DESCRIPTION OF WORK. The bidder shall provide adequate proof of licensure and insurance.

DESCRIPTION OF WORK. The bidder shall provide adequate proof of licensure and insurance. BID DOCUMENTS: SCOPE: 1. Description of Work 2. Advertisement of Bids 3. Furniture Specification 4. Request for Approval of Substitution 5. Bid Tabulation Sheet DESCRIPTION OF WORK A. This project shall

More information

Request for Proposal

Request for Proposal Request for Proposal 10 th Street Corridor Master Plan Department of Planning and Zoning 500 Quartermaster Court Suite 200 Jeffersonville, IN 47130 April 18, 2017 For further information contact: Chad

More information

BID/RFP TITLE: Water-Based Fire Protection Systems Inspection, Maintenance and Services Contract

BID/RFP TITLE: Water-Based Fire Protection Systems Inspection, Maintenance and Services Contract The School Board of Miami-Dade County, Florida SCHOOL BOARD ADMINISTRATION BUILDING Bureau of Procurement and Materials Management 1450 N.E. 2 nd Avenue, Room 352 Miami, Fl. 33132 Direct All Inquiries

More information

REQUEST FOR PROPOSALS FOR THE PROVISION OF PREVENTIVE MAINTENANCE ON FACILITY HVAC SYSTEMS FOR SKOKIE PUBLIC LIBRARY

REQUEST FOR PROPOSALS FOR THE PROVISION OF PREVENTIVE MAINTENANCE ON FACILITY HVAC SYSTEMS FOR SKOKIE PUBLIC LIBRARY REQUEST FOR PROPOSALS FOR THE PROVISION OF PREVENTIVE MAINTENANCE ON FACILITY HVAC SYSTEMS FOR SKOKIE PUBLIC LIBRARY Skokie Public Library is requesting proposals for a contract for the provision of preventive

More information

City of La Puente REQUEST FOR PROPOSAL ADDENDUM NO. 1

City of La Puente REQUEST FOR PROPOSAL ADDENDUM NO. 1 City of La Puente REQUEST FOR PROPOSAL ADDENDUM NO. 1 BID TITLE: Facility Access Control and Security System REQUESTING DEPARTMENT: Development Services RELEASE DATE: July 12, 2016 DUE DATE: August 4,

More information

SECTION INSPECTION AND TESTING OF WORK

SECTION INSPECTION AND TESTING OF WORK SECTION 01455 PART I - GENERAL 1.01 SECTION INCLUDES A. Project Inspections and Procedures B. Scheduling Inspectors Notification requirements 1.02 RELATED SECTIONS A. Section 01310 COORDINATION B. Section

More information

The attached information details the bids, purchases and/or services being recommended as follows:

The attached information details the bids, purchases and/or services being recommended as follows: MEMORANDUM TO: Paul Soma, Superintendent FROM: Christine Thomas-Hill, Executive Director of Finance/Operations DATE: March 4, 2016 RE: APPROVAL OF BIDS, PURCHASES AND/OR SERVICES The attached information

More information

ARTICLE II FALSE ALARMS

ARTICLE II FALSE ALARMS ARTICLE II FALSE ALARMS History: Adopted by the Board of Supervisors of Center Township as Ordinance No. 2013-02-01, February 13, 2013. 5-201. General The Center Township Board of Supervisors finds that

More information

CURRICULUM VITAE L. EARLE GRAHAM

CURRICULUM VITAE L. EARLE GRAHAM CURRICULUM VITAE L. EARLE GRAHAM CSC Principal Consultant 25851 Avatar Lane Laguna Niguel, CA 92677 Telephone: (949) 364-0870 EDUCATION Bachelor of Arts, Public Service Management, University of Redlands

More information

MEMORANDUM. Pat Black, CPPB, Director of Materials Management APPROVAL TO AWARD BID #7095 FOR PLUMBING SERVICES TIME AND MATERIALS

MEMORANDUM. Pat Black, CPPB, Director of Materials Management APPROVAL TO AWARD BID #7095 FOR PLUMBING SERVICES TIME AND MATERIALS ENC. March 20, 2007 THE SCHOOL BOARD OF SARASOTA COUNTY, FLORIDA MATERIALS MANAGEMENT DEPARTMENT 101 OLD VENICE ROAD OSPREY, FLORIDA 34229 TELEPHONE (941) 486-2183 FAX (941) 486-2188 MEMORANDUM TO: FROM:

More information

Fire Safety Account Financial Report for Fiscal Year 2018

Fire Safety Account Financial Report for Fiscal Year 2018 This document is made available electronically by the Minnesota Legislative Reference Library as part of an ongoing digital archiving project. http://www.leg.state.mn.us/lrl/lrl.asp Minnesota Department

More information

ALLIED FIRE & SAFETY EQUIPMENT CO.,INC.

ALLIED FIRE & SAFETY EQUIPMENT CO.,INC. BID RESULTS CK09MERCER2014-17 FIRE EXTINGUISERS, FIRE ALARM SYSTEMS, FIRE SUPPRESSION AND SPRINKLER SYSTEMS, DIESEL AND ELECTRIC PUMP PREVENTIVE MAINTENANCE SERVICE AND REPAIR FOR A PERIOD OF TWO (2) YEARS

More information

RFP REQUEST FOR PROPOSALS CITY OF PORTSMOUTH, NH. DESIGN ENGINEERING SERVICES North Mill Pond Trail and Greenway

RFP REQUEST FOR PROPOSALS CITY OF PORTSMOUTH, NH. DESIGN ENGINEERING SERVICES North Mill Pond Trail and Greenway RFP 61-18 REQUEST FOR PROPOSALS CITY OF PORTSMOUTH, NH DESIGN ENGINEERING SERVICES North Mill Pond Trail and Greenway Sealed Requests for Proposals, plainly marked RFP 61-18 Design Engineering Services

More information

ADMINISTRATOR S WEEKLY REPORT # September 12 th through 18 th, 2011

ADMINISTRATOR S WEEKLY REPORT # September 12 th through 18 th, 2011 ADMINISTRATOR S WEEKLY REPORT # 2011-38 September 12 th through 18 th, 2011 CALLS FOR SERVICE % This Week 2011 YTD Change Fire 11 248 25.9% Aid 138 5,025 3.4% Other 35 1,290-14.3% Total 184 6,563 0.% Last

More information

Campus Wide Fire Alarm Repairs

Campus Wide Fire Alarm Repairs BID # 15-24 Campus Wide Fire Alarm Repairs SECTION "C" TECHNICAL SPECIFICATIONS OWNER Board of Trustees Middlesex County College 2600 Woodbridge Avenue P.O. Box 3050 Edison, New Jersey 08818-3050 PREPARED

More information

Energy Upgrade California Home Upgrade Offered by The Energy Network

Energy Upgrade California Home Upgrade Offered by The Energy Network Energy Upgrade California Home Upgrade Offered by The Energy Network Who is The Energy Network? Local government organization Created by the California Public Utilities Commission Provides resources and

More information

Urban Gardener Certification Program Application & Agreement 2015

Urban Gardener Certification Program Application & Agreement 2015 Urban Gardener Certification Program Application & Agreement 2015 Thank you for your interest in the Hunter Park GardenHouse Urban Gardener Certification Program! Here you will find a description of the

More information

ACCOUNTS RECEIVABLE CLERK

ACCOUNTS RECEIVABLE CLERK ACCOUNTS RECEIVABLE CLERK Compiles and maintains accounts receivable records by performing the following duties: Conducts collection calls Collects and sorts cash billings. Addresses customer inquiries

More information

CENTRAL GEORGIA TECHNICAL COLLEGE. Maintenance, Custodial & Operation Plan Facilities & Equipment

CENTRAL GEORGIA TECHNICAL COLLEGE. Maintenance, Custodial & Operation Plan Facilities & Equipment CENTRAL GEORGIA TECHNICAL COLLEGE Maintenance, Custodial & Operation Plan Facilities & Equipment Central Georgia Technical College Maintenance, Custodial and Operation Plan In order that Central Georgia

More information

* Electricity and Energy Conservation Opportunities

* Electricity and Energy Conservation Opportunities * Electricity and Energy Conservation Opportunities * Scott Wishart * Energy Analyst * BPI Analyst & Envelope Professional * Energy Insight, Inc. * (218) 355-2218 (office) * sw@energyinsightinc.com * HOW

More information

Vibra LITE 8 CONGRATULATIONS!

Vibra LITE 8 CONGRATULATIONS! Vibra LITE 8 CONGRATULATIONS! You have selected a quality timepiece that will assist you in remembering tasks, managing your time and keeping focused. Perfect for reminders for medication and medical conditions,

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Request for Qualifications For Administration of the 2016 Summer Sprout Program

Request for Qualifications For Administration of the 2016 Summer Sprout Program Page 1 of 6 Request for Qualifications For Administration of the 2016 Summer Sprout Program Requested by: City of Cleveland, Department of Community Development 601 Lakeside Avenue, room 320 Cleveland,

More information

Planning Committee 04/02/2015 Schedule Item 6. Smith Farm Estate, Old Bridge Close, Northolt, UB5 6UA.

Planning Committee 04/02/2015 Schedule Item 6. Smith Farm Estate, Old Bridge Close, Northolt, UB5 6UA. Planning Committee 04/02/2015 Schedule Item 6 Ref: Address: Ward: Proposal: PP/2014/5145 Smith Farm Estate, Old Bridge Close, Northolt, UB5 6UA. Greenford Broadway Installation of sports pitch, reconstruction

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

4/18/2017. *2012 edition of NFPA 99 has gone through a major overhaul. *This document is now a Code.

4/18/2017. *2012 edition of NFPA 99 has gone through a major overhaul. *This document is now a Code. Carsten Lunde, ASSE 6050 Instructor April 20, 2017 Carsten s Yearly Analysis, Inc. Any opinions expressed verbally by the speaker before you and all text in this presentation should be considered the speakers

More information