BS 5839 Part 1 : 2013 Changes. By Don Scott

Size: px
Start display at page:

Download "BS 5839 Part 1 : 2013 Changes. By Don Scott"

Transcription

1 BS 5839 Part 1 : 2013 Changes By Don Scott

2 BS 5839 Part 1 : 2013 This new edition of the CoP is not a full revision but technical and nomenclature changes It could in reality have been classed as A3, however a BS can only be amended twice, so this had to published as a new version It is recognized that a full revision is required and this will follow in due course

3 Reasons for Revision 1. Findings from the Rose Park Fire 2. As a result of the research carried out by BRE regarding high ceiling detection 3. Up-date references to reflect latest versions and new standards 4. To highlight the requirements, use and selection of VAD s

4 Nomenclature Changes Old Terminology care home fire service responsible person New Terminology residential care premises fire and rescue service premises management

5 New Title to Better Reflect Scope and Content BS 5839, Fire detection and fire alarm systems for buildings Part 1: Code of practice for design, installation, commissioning and maintenance of systems in non-domestic premises

6 Normative References BS 9999, Code of practice for fire safety in the design, management and use of Buildings BS EN 54-23:2010, Fire detection and fire alarm systems Part 23: Fire alarm devices Visual alarm devices Code of practice for the Design, Installation, Commissioning and Maintenance of Aspirating Smoke Detector (ASD) Systems, Fire Industry Association, Issue 3 February 2012

7 Clause 3 Terms and Definitions 3.9 coincidence arrangement designed so that an output is obtained only when at least two independent input triggering signals are present at the same time NOTE This is not to be mistaken for double knock, which is a colloquial term often used for an arrangement whereby an output is given only when two successive signals are received from the same device. This definition now aligns with BS6266

8 Clause 3 Terms and Definitions 3.12 competent person person with the relevant current training and experience, and with access to the requisite tools, equipment and information, and capable of carrying out a defined task You need to keep your training up to date to remain competent

9 Clause 3 Terms and Definitions 3.45 premises management persons having day-to-day control of the premises, the fire detection and fire alarm system(s) and implementation of the fire procedures NOTE In large premises, a single person with specialist knowledge is often delegated the responsibility for the fire detection and fire alarm system and associated matters. In small premises, a person with specialist knowledge is unlikely to be present, but responsibility for the fire detection and fire alarm system can still be delegated to a specific person.

10 Reference to premises management Section 7, clause 47; the title has been changed from Responsible Person the Premises Management. This section has been reworded to remove the term Responsible Person but the meaning of 47 remains largely unchanged. Clause 48 Logbook, 48.2 a) has been amended to remove the term Responsible Person but otherwise the meaning of the sub-clause is unchanged. It is worth pointing out that the identity of the persons responsible for the FD&FA system should be recorded in the logbook which is something that is often overlooked.

11 Clause 3 Terms and Definitions 3.58 staff alarm restricted alarm, following the operation of a manual call point or automatic fire detector, given to certain staff in the premises to permit investigation prior to evacuation and/or summoning of the fire and rescue service NOTE The use of staff alarms in response to signals from manual call points is not generally acceptable.

12 Clause 3 Terms and Definitions 3.66 zone plan diagrammatic representation of a building, showing specific topographic information and the division of the building into detection zones

13 Reference to Zone Plan Clause 6; Exchange of information, 6.1 states Experience shows that the responsibility for provision of a zone plan is often ill-defined, leading to the absence of a suitable zone plan when an installation is handed over. It is important that this responsibility is defined at an early stage of the planning of an installation. 6.2c recommends that the installer consult with the designer, the user or purchaser, the supplier of the system and consultants and that during these consultations that the topic of the provision of the zone plan should be settled.

14 Reference to Zone Plan Clause 23 Control and Indicating equipment, 23.1 New paragraph In at least one multiple-fatality fire, it has been determined that some or all of the deaths could have been avoided if a diagrammatic representation of the premises (commonly described as a zone plan) had been provided in close proximity to the CIE. Accordingly, it is important to ensure that a suitable zone plan is provided adjacent to all CIE (including any repeat control and/or indicating equipment), unless the CIE incorporates a suitable display (e.g. an illuminated mimic diagram). The objective is to ensure that those responding to a fire alarm signal (including staff on the premises and firefighters) are given unambiguous information as to the location of a fire.

15 Reference to Zone Plan Clause 23 Control and Indicating equipment, The following recommendations apply to the facilities provided for visual indication of fire signals. e) On or adjacent to indicating equipment, there should be a diagrammatic representation of the building, showing at least the building entrances, the main circulation areas and the division into zones. Where the division into zones is not provided by the display recommended in c) or d), a correctly orientated zone plan of the premises (see 3.66) should be displayed. NOTE 3 In some complex premises, e.g. shopping centres, additional information, such as occupier names, might be of value to those who are unfamiliar with the premises. This could be provided by a supplementary list that, for example, enables a unit number on a zone plan to be related to the occupier name, such as the name of a retailer in a shopping centre. Where such information is provided, it is important that it is kept up-to-date.

16 Reference to Zone Plan Clause 42 Acceptance, 42.2.b) New sub-clause 5 inserted 5) that a suitable diagrammatic representation of the premises is provided close to all CIE [see e)]; 46.2 b) Major non-compliance, new sub-clause 10 10) the absence of a zone plan or other suitable diagrammatic representation of the premises [see e)].

17 Reference to Zone Plan Annex H Model Certificates, (Informative) H.4 Acceptance certificate Tick box:- A suitable zone plan (or other suitable diagrammatic representation) of the premises is provided on or adjacent to all control and indicating equipment. (Delete if not applicable.)

18 7 Variations from the recommendations of this standard 7.2 e) Major non-compliances (see 46.2) that are agreed variations should be clearly recorded in the logbook so that they are readily available for future reference by maintenance companies and any other interested parties. This removes any guess work at a later date as to the reasons for any design or installation variations to the standard.

19 8 Relationship between system Category and areas protected 8.2 f) In a Category L1 or P1 system, automatic fire detectors should be installed in all rooms and areas of the building, but the following rooms or areas need not be protected if they are of low fire risk (see 3.32): 1) toilets, shower rooms and bathrooms; NOTE 7 In some public buildings, such as hospitals and shopping centres, toilets might not be of low fire risk, owing to the potential for arson. 2) stairway lobbies and toilet lobbies 3) small cupboards (typically, less than 1 m2);

20 8 Relationship between system Category and areas protected 8.2 f) Cont. NOTE 8 A riser in which there is a fire-resisting floor and ceiling may be treated as a cupboard. NOTE 9 If detection can be excluded from any room or area in a Category L1 system, it can also be excluded from such rooms or areas in a Category L2, L3 or L4 system. 4) some shallow voids (less than 800 mm in depth) [see 2.2d)].

21 11 System components 11.2 k) CIE should conform to BS EN NOTE 1 BS EN 54-2 contains optional performance characteristics which are not necessarily provided in all CIE, even if third-party certificated against BS EN It needs to be ensured that the CIE provided has appropriate facilities to enable compliance with all the recommendations of this British Standard. Make sure you get one to do what you want it to.

22 12 Monitoring, integrity and reliability of circuits external to control equipment System integrity d) Two simultaneous faults on a manual call point or fire detector circuit should not disable protection within an area greater than m2. NOTE 1 The areas quoted in c) and d) are relatively arbitrary; in the case of c), the recommendation is based on custom and practice in non-addressable fire detection and fire alarm systems over many years. Engineering judgement might determine that, in a given system, minor increases in the areas quoted do not significantly impede the system integrity, but this ought then to be regarded as a variation from the recommendations of this standard.

23 13 Detection zones 13.1 Commentary If a detector is concealed in a relatively inaccessible area (such as a floor or ceiling void), it is normally desirable to provide a remote indication of its operation. In an addressable system, the provision of an individual remote indicator might not be necessary provided that the location of each fire detector is clearly indicated at the CIE Remote indication of detector operation NOTE Remote indicators might be required in a specification for areas such as inaccessible voids or locked rooms. See also 40.2 for the as-fitted drawing.

24 15 Communication with the fire and rescue service 15.1 Commentary Since the objective of a Category L system is evacuation of occupants, rather than protection of property, manual summoning of the fire and rescue service by occupants may, again, suffice. However, if the early attendance of the fire and rescue service is likely to be essential to life safety in the event of fire (e.g. in hospitals), a secondary, automatic means of transmission might be warranted, unless there are adequate arrangements to ensure that there will be no delay at any time in manual summoning of the fire and rescue service by occupants. Automatic transmission of fire alarm signals is also necessary in the case of residential care premises.

25 15 Communication with the fire and rescue service 15.2 e) If the early summoning of the fire and rescue service is considered critical to the safety of occupants (e.g. on the basis of a fire risk assessment), facilities should be provided for automatic transmission of alarm signals to an alarm receiving centre, unless there are reliable arrangements for summoning the fire and rescue service by persons in the building. NOTE 2 In the case of shopping centres and hospitals, compliance with the Technical Handbooks (see

26 15 Communication with the fire and rescue service 15.2 f) In residential care premises, facilities should be provided for automatic transmission of alarm signals to an alarm receiving centre. NOTE 3 In the case of residential care premises, compliance with the Technical Handbooks (see Environment/Building/ Building-standards/publications/pubtech) that support the Building (Scotland) Regulations 2004 [3] necessitates automatic

27 15 Communication with the fire and rescue service 15.2 i) Any alarm receiving centre to which fire alarm signals are relayed should conform to the recommendations of BS NOTE 4 Schemes exist for third-party certification of alarm receiving centres to BS However, transmission of fire alarm signals (as opposed to intruder alarm signals) is not always within the scope of the alarm receiving centre s certification; if reliance is placed on third-party certification, it needs to be

28 16 Audible alarm signals Recommendations applicable to hospitals and residential care premises The following recommendations are applicable. a) Audible alarms in hospitals should conform to the recommendations of the Department of Health publications HTM Part B (in England and Wales) or SHTM 82 (in Scotland). b) Audible alarms in residential care premises should conform to , except that, if the alarm signal is not intended to rouse occupants of some or all rooms from sleep, a)3) does not apply. Any relaxation of a)3) should, however, be subject to the specific agreement of every authority responsible for enforcing fire safety legislation in the premises. NOTE More than one authority may be responsible for enforcing relevant legislation in residential care premises (e.g. the fire authority and the social services department of the local authority).

29 18 Fire alarm warnings for people with impaired Hearing General e) Where tactile devices are provided, control and transmission equipment should comply with the recommendations of Annex C Portable alarm devices j) The system should conform to the recommendations of the following clauses and subclauses of this part of BS a)4) e) e) 27.2g)1) a)5) g) f) 27.2g)2) a)6) m) g)3) a)7) b) e) b) c) 27.2c) Annex C d) d) 27.2d)

30 19 Staged fire alarms Recommendations applicable to staff alarms b) In residential care premises, a staff alarm should not incorporate any delay in summoning of the fire and rescue service when the fire alarm system operates, but there may be a delay in the general alarm signal, provided all staff are made aware of the fire alarm signal [see also 15.2f)].

31 20 Manual call points 20.2 h) h) Manual call points should be fixed at a height of 1.4 m above finished floor level, at easily accessible, wellilluminated and conspicuous positions free from potential obstruction. They should be sited against a contrasting Background to assist in easy recognition. A lower mounting height is acceptable in circumstances where there is a high likelihood that the first person to raise an alarm of fire will be a wheelchair user. NOTE 6 The figure of 1.4 m is arbitrary, but reflects long established custom and practice. A minor difference (e.g. less than 300 mm) in mounting height (e.g. to align with the mounting height of light switches) need not be regarded as significant, nor need it be recorded as a variation. 1.2m stated in AD M

32 21 Types of fire detector and their selection Smoke detectors The final paragraph of Smoke detectors (which is a commentary) which describes video smoke detection has been expanded and slightly reworded. While there is no corresponding recommendations, it does indicate that this technology is now coming of age and will shortly become mainstream.

33 22 Spacing and siting of automatic fire detector 22.9 Recommendations for limits of ceiling height Table 3

34 21 Types of fire detector and their selection Choice of fire detection principle For aspirating systems, specialist application guidance needs to be sought from the manufacturer. The COP has now adopted the terminology used in BS EN to describe high sensitivity class A, enhanced sensitivity class B and standard sensitivity class C.

35 21 Types of fire detector and their selection 21.2 e) In areas in which early detection of a smouldering fire is required, optical smoke detectors, optical beam detectors, aspirating smoke detection systems, carbon monoxide fire detectors or suitable multi-sensor fire detectors should be used.

36 22 Spacing and siting of automatic fire detector In clause 22 Spacing and siting of automatic fire detectors sub clause 22.1 Commentary, aspirating systems are referred to alongside beam detectors as suitable detection types in tall spaces. Where it discusses stratification it suggests that positioning sample holes at different levels might be employed. Also Similarly, as the hot gases and smoke flow horizontally across a ceiling, there is a stagnant boundary layer at the surface of the ceiling; this precludes the sensitive element of a heat or smoke detector from being mounted flush with a ceiling. This restriction does not apply to the sampling points of an aspirating smoke detection system, which may be flushmounted because the sampled air drawn into the sampling hole comes from the main flow outside the boundary layer.

37 22 Spacing and siting of automatic fire detector 22.7 Recommendations for siting of aspirating smoke detection systems a) However, as the detector actually draws samples of air through sampling points (holes in the pipework), 22.3d) does not apply and the sampling points may be flush with a ceiling. Slight re-wording 22.3 d) 25mm from ceiling c) Where an aspirating smoke detection system is used to protect spaces with high ceilings (>25 m) and there is a risk that the smoke could stratify before reaching the ceiling, sampling should be provided at multiple levels using drop-pipe arrangements at the wall and, where practical, within the main space.

38 22 Spacing and siting of automatic fire detector 22.3 i) Where an area contains partitions or storage racks that reach within 300 mm of the ceiling, the partitions or storage racks should be treated as walls that extend to the ceiling (see Figure 9). NOTE 9 Where a rack contains high-value or high-risk materials or where the height of the rack exceeds 8 m, the use of in-rack detection might be considered.

39 22 Spacing and siting of automatic fire detector 22.3 and 22.7 both refer to the FIA Code of Practice for Design, Installation, Commissioning and Maintenance of Aspirating Smoke Detector (ASD) Systems.

40 22 Spacing and siting of automatic fire detector

41 22 Spacing and siting of automatic fire detector 22.5 Recommendations for siting of optical beam smoke detectors d) If optical beam smoke detectors are installed at a distance of more than 600 mm below ceiling level in order to provide supplementary detection of a rising smoke plume within a high space (e.g. an atrium), the width of the area protected on each side of an optical beam should be regarded as 12.5% of the height of the beam above the highest likely seat of fire (see Figure 13). NOTE 1 An optical beam smoke detector may be installed at an angle from the horizontal, pointing down from the ceiling, in order to provide supplementary detection [i.e. in addition to beams located at or near the ceiling, as recommended in 22.3d)] to detect of a stratified smoke layer within a high space.

42 22 Spacing and siting of automatic fire detector 22.9 Recommendations for limits of ceiling height Table 3

43 22 Spacing and siting of automatic fire detector 22.5 Recommendations for siting of optical beam smoke detectors However, the COP gives no advice on Quantity, spacing, mounting height or the angle of the OBSDs.

44 35 Measures to limit false alarms Recommendations for selection and siting of automatic fire detector a) In areas with high levels of dust and dirt which could contaminate detectors and/or lead to unwanted alarm, aspirating smoke detectors may be used which incorporate mechanical filtration of the air samples before they are analysed for the presence of smoke. It should be confirmed that the Filters used for any such detectors are covered under the detectors approval to BS EN Furthermore, consideration should be given to the consequences of blocked filters to the detection capability of the system and a rigorous regular maintenance regime established if needed.

45 35 Measures to limit false alarms Recommendations for selection and siting of automatic fire detector j) Many aspirating smoke detection systems can operate at a level of sensitivity much higher than normal point type smoke detectors. Special consideration should be given to the potential for false alarms when a high sensitivity (Class A) or enhanced sensitivity (Class B) aspirating smoke detection system is proposed, to ensure that an unacceptable rate of unwanted alarms is not likely to result.

46 35 Measures to limit false alarms Recommendations for selection and siting of automatic fire detector NOTE 2 Such systems are often used to provide signals intended to be managed as a pre-alarm warning (to indicate that an alarm condition is approaching) or as a very early warning (to alert staff of abnormal conditions that are worthy of investigation). Such signals might not be suitable (or intended) to be managed as an alarm signal that triggers alarm devices and evacuation of the building. In fact, such pre-alarm warnings or very early warning signals can be used to avoid false alarms and unnecessary evacuations. In some applications in which Class A and/or Class B aspirating smoke detection systems are used, a Class C (normal sensitivity) signal is provided which is managed as an alarm condition.

47

48 35 Measures to limit false alarms d) Staff alarms should conform to NOTE recommends that, in residential care premises, the fire and rescue service is summoned immediately when the fire detection and fire alarm system operates. e) If the fire and rescue service is not summoned immediately at the start of any investigation period associated with a staff alarm, it is essential that they are summoned immediately on expiry of this period, unless it has been determined that the alarm signal is a false alarm. NOTE 2 Reliability in compliance with this recommendation would be aided by a monitored facility for automatic transmission of an alarm signal to an alarm receiving centre on expiry of the investigation period.

49 35 Measures to limit false alarms f) Any arrangements for filtering of automatic summoning of the fire and rescue service by an alarm receiving centre should conform to BS Such filtering should not be applied to signals from fire alarm systems in residential care premises.

50 45 Inspection and servicing 45.1 Routine servicing of a fire detection and fire alarm system does not constitute a fresh review of system design; it is a verification of the functionality and serviceability of the existing system. Accordingly, it will not necessarily be the case that non-compliances with Section 2 of this Standard will be identified at the time of routine servicing; in any case, the maintenance technician might not be aware as to whether an apparent noncompliance is, in fact, simply an agreed variation, particularly if the design certificate is not available. However, at their own prerogative, the maintenance organization may point out aspects of non-compliance with Section 2. Nevertheless, any such advice provided to the user by the maintenance organization cannot be regarded (by users, enforcing authorities or any other party) as an implication that the maintenance technician has identified, or has endeavoured to identify, all such areas of non-compliance, or that there has been any review of the original design.

51 45 Inspection and servicing 45.3 Recommendations for periodic inspection and test of the system d) The battery voltage should be measured with the mains on to check the steady state charge voltage and check it is within the manufacturer s recommendations. New d) The standby battery should be disconnected and full load alarm should be simulated. Old If however the service technician is not in possession of an appropriate test within the manufactures maintenance manual. The FIA would recommend carrying out both the old and the new recommendations as a simple safeguard.

52 45 Inspection and servicing 45.4 Recommendations for inspection and test of the system over a 12 month period o) The cause and effect programme should be confirmed as being correct by activating at least one cause and observing the operation of effects.

53 46 Non-routine attention 46.2 Recommendations for special inspection on appointment of a new servicing organization b) 10) the absence of a zone plan or other suitable diagrammatic representation of the premises [see e)].

54 46 Non-routine attention Recommendation for inspection and test of the system following long periods of disconnection The recommendations for inspection and test of the system over a 12 month period (see 45.4) should be undertaken. NOTE If there is a major change in occupation or use of a building it might be appropriate for the cause and effects of the system to be checked. Delay alarms, filtering, phased evacuation etc.

55 Section 7: User s responsibilities 47 Premises management 47.2 A single, named member of the premises management should be appointed to supervise all matters pertaining to the fire detection and fire alarm system. This person should normally be the keeper of the documentation as described in Clause 40, and should be given sufficient authority to carry out the following duties. i) Ensuring that, where necessary, a suitable zone plan is displayed and is kept up-to-date [see e)]. NOTE 2 It would be of value for the premises management to be aware of the policy of the relevant fire and rescue service with regard to response to calls from the premises and/or any ARC, in the event of operation of the fire detection and fire alarm system.

56 25 Power supplies 25.2 Recommendations for mains power supplies c) To facilitate local isolation during maintenance, suitable means should be provided for double pole isolation of the low voltage supply circuit that serves the power supply and control equipment [see 29.2e)]. NOTE 2 The contractor responsible for supplying the 230 V mains power supply needs to ensure that the particular device used does actually afford isolation. A number of switching devices do not meet the required isolation performance criteria. BS 7671:2008+A1:2011, Table 53.4, details whether a particular device can actually be used for the purpose of isolation. Same note appears in 29.2 e) Electrical safety

57 25 Power supplies 25.2 Recommendations for mains power supplies h) Every isolator, switch and protective device that is capable of disconnecting the mains supply to the fire detection and fire alarm system should be situated in a position inaccessible to unauthorized persons or be protected against unauthorized operation by persons without a special tool. NOTE 4 A special tool may, for example, be a key actuator (sometimes called secret key ) for a mains switch device. This note has been deleted

58 25 Power supplies 25.2 Recommendations for mains power supplies NOTE 4 It is recognized that in such an arrangement the recommendations of Clause 26 in respect of the fire resistance of the mains power supplies cables do not apply.???????

59 26 Cables, wiring and other interconnections 26.1 All references to the use of RCD s and surface mounted cable for the FD&A system and BS 7671 introduced by amendment A2 have been removed

60 27 Radio-linked systems 27.2 Recommendations has been subtly rewritten making it clear that wireless devices, that rely solely on battery power, should have two independent batteries such that if one set (primary) should fail a second would continue to support the device. A number of paragraphs in 27.2 have been deleted and the paragraphs renumbered. These paragraphs described the operation of the equipment and are no longer required as BS

61 Clause 17 Visual alarm signals Basically this Clause remains the same apart from reference to BS EN 54 Part 23 and reference to the new informative annex F Annex F is basically the same as the LPCB CoP 0001

62 22.3 Recommendations for siting of heat and smoke detectors e) Detectors within rooms that open onto escape routes in a Category L3 system should either be sited in accordance with 22.3d) or should be sited on a wall, close to any door that opens onto an escape route. Wall-mounted detectors should be sited such that the top of the detection element is between 150 mm and 300 mm below the ceiling, and the bottom of the detection element is above the level of the door opening.

63 22.3 Recommendations for siting of heat and smoke Detectors e) NOTE 6 Wall mounting may also be adopted in those rooms or areas in which the protection afforded by a Category L2 system reflects only the recommendations for a Category L3 system, in that the purpose is protection of the adjacent escape route (i.e. other than in areas in which detector siting needs to reflect the objective of protecting the occupant of the room of fire origin, as is the case in bedrooms intended for disabled people, or giving warning in areas in which the likelihood of fire is high).

64 16 Audible alarm signals Recommendations applicable to Category M and L systems (other than in hospitals and residential care premises) NOTE 8 An instrument conforming to BS EN , set to slow response and A-weighting, is suitable for measuring the sound pressure level of the alarm signal. BS EN replaced BS EN 60651

65 Conformity versus compliance There a number of instances where the term comply with has been changed to conform to where the clause refers to some part of BS Because BS is a code of practice, and only has recommendations and uses the word should, it is not a hard and fast set of rules that must be complied with; conform is, therefore, more appropriate.

66 Fire Detection and Fire Alarm There are numerous references to fire detection and alarm and fire alarm which have been expanded to read fire detection and fire alarm.

67 CIE The 2008 version had various references to CIE and Control and Indicating equipment. The 2013 version now standardises on CIE.

BS 5839: Part THE CHANGES

BS 5839: Part THE CHANGES BS 5839: Part 1 2013 THE CHANGES INTRODUCTION This document has been created to summarise the main changes that have been made to the BS 5839 Part 1 2013. This data is correct at the time of publication

More information

Guidance Note Guide to the changes in BS

Guidance Note Guide to the changes in BS Guidance Note INTRODUCTION... 3 SCOPE... 4 THE CHANGES START ON THE FRONT PAGE NEW STYLE...5 NEW VERSION... 6 NEW TITLE... 7 NORMATIVE REFERENCES... 8 COINCIDENCE DETECTION... 9 COMPETENT PERSON... 10

More information

BS 5839 Part 6 : 2013 Changes. By Don Scott

BS 5839 Part 6 : 2013 Changes. By Don Scott BS 5839 Part 6 : 2013 Changes By Don Scott BS 5839 Part 6 : 2013 This new edition of the CoP is not a full revision but contains technical changes It is recognized that a full revision is required and

More information

FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation

FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation Guidance Note FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation FIA Guidance on Manual Call Point - Protection False Alarm Mitigation 1. INTRODUCTION... 3 2. BS 5839-1 RECOMMENDATIONS...

More information

FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL GK FIRE & SECURITY LTD, UNIT 1 GREBE RD, PRIORSWOOD IND EST, TAUNTON, TA2 8PZ

FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL GK FIRE & SECURITY LTD, UNIT 1 GREBE RD, PRIORSWOOD IND EST, TAUNTON, TA2 8PZ BS5839-1 : 2013 FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL Forward It is recommended that this logbook be maintained by a relevant member of the premises management, to ensure that every entry

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-26992-0 SOUTH AFRICAN NATIONAL STANDARD Fire detection and alarm systems for buildings System design, installation and servicing Published by SABS Standards Division 1 Dr Lategan Road Groenkloof

More information

SOUTH AFRICAN NATIONAL STANDARD

SOUTH AFRICAN NATIONAL STANDARD ISBN 978-0-626-19281-5 SOUTH AFRICAN NATIONAL STANDARD Fire detection and alarm systems for buildings System design, installation and servicing Published by Standards South Africa 1 dr lategan road groenkloof

More information

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater APPROVED BY: JBJ Precept EN Fire Detection/Alarm Panel & Precept EN Repeater Logbook PAGE 1 of 19 List of Contents 1. FIRE ALARM SYSTEM MAINTENANCE... 3 2. USER RESPONSIBILITIES... 3 2.1. RESPONSIBLE PERSON...

More information

Waking Watch / Common Fire Alarm. Guidance to support a temporary simultaneous evacuation strategy in a purpose-built block of flats

Waking Watch / Common Fire Alarm. Guidance to support a temporary simultaneous evacuation strategy in a purpose-built block of flats Waking Watch / Common Fire Alarm Guidance to support a temporary simultaneous evacuation strategy in a purpose-built block of flats Contents 1. Introduction... 3 2. Definitions... 5 3. Competence... 6

More information

Construction Products Regulation (CPR) Update. Graham Simons Technical Manager, FIA

Construction Products Regulation (CPR) Update. Graham Simons Technical Manager, FIA Construction Products Regulation (CPR) Update Graham Simons Technical Manager, FIA What are we talking about? Construction Products Regulation 305/2011 EU (CPR) Replaced Construction Products Directive

More information

Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems:

Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Compatibility and connectivity assessment of system components Guide to BS EN 54-13:2017 Fire Detection and alarm systems: Compatibility

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS

FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS WM_Winter 05_part1_EW.qxd 17/11/05 6:55 am Page 1 1 IN DWELLINGS By John Ware IN THE UK around 80% of all fire deaths and injuries occur in dwellings, a total of 450 to 500 deaths and 14,000 injuries per

More information

Building Standards Division. Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems

Building Standards Division. Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems Building Standards Division Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems Crown Copyright 2015 Produced by the Buildings Standards Division February 2015 Version

More information

Secretary of State determination under article 36 of the Fire Safety Order

Secretary of State determination under article 36 of the Fire Safety Order Fire and Rescue Service Circular Circular number 48/2009 Date issued 13 August 2009 This circular is For information and consideration Status This circular covers the outcome of a referral to the Secretary

More information

A guide to the changes between BS 8418:2010 and BS 8418:2015

A guide to the changes between BS 8418:2010 and BS 8418:2015 A guide to the changes between BS 8418:2010 and BS 8418:2015 March 2016 For other information please contact: British Security Industry Association t: 0845 389 3889 e: info@bsia.co.uk www.bsia.co.uk Form

More information

Guidance Note. Guidance Document on Best Practice for Fire Detector Testing/Test Equipment

Guidance Note. Guidance Document on Best Practice for Fire Detector Testing/Test Equipment Guidance Note Guidance Document on Best Practice for Fire Detector Testing/Test Equipment Guidance Document on Best Practice for Fire Detector Testing/Test Equipment 1. SCOPE OF THIS DOCUMENT... 3 2. COMPETENCY

More information

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work

Legal Requirements. There is no general legal requirement to install sprinklers. in places of work 01 A sprinkler system is a pipework distribution system charged with water, with a network of heatsensitive sprinkler heads supplied via a tank/reservoir or a water main. If the temperature rises above

More information

NOTTINGHAM CITY HOMES

NOTTINGHAM CITY HOMES APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes

More information

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002 a guide to Fire Alarm Systems Design BS5839 Part1:2002 incorporating Amendment No.2 The Regulatory Reform (Fire Safety) Order (RRO) became law on 1 October 2006 Legally you must comply! What is the RRO?

More information

A Guide To BS Understanding the selection, spacing and siting of detectors

A Guide To BS Understanding the selection, spacing and siting of detectors World Class Leaders in Fire Detection Since 1918 A Guide To BS5839-12017 Understanding the selection, spacing and siting of detectors Welcome to A Guide to BS5839 Part 1 : 2017 from HOCHIKI EUROPE (UK)

More information

Guidance Note FIA Application Guidance on BS :2015

Guidance Note FIA Application Guidance on BS :2015 Guidance Note FIA Application Guidance on BS 7273-4:2015 FIA Application Guidance on BS 7273-4:2015 1. INTRODUCTION... 3 2. OVERVIEW... 3 2.1. WHAT IS A DOOR RELEASE MECHANISM?...3 2.2. WHY INSTALL DOOR

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems BAFE Scheme: SP203-1 Version 5: May 2011 Fire Protection Industry Scheme, Reference SP203 Part 1 For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems British

More information

Charlotte Building, 17 Gresse Street, London W1T 1QL

Charlotte Building, 17 Gresse Street, London W1T 1QL Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of

More information

FIRE SAFETY POLICY. Approval Approved by: University Court Date: March 28 th 2017

FIRE SAFETY POLICY. Approval Approved by: University Court Date: March 28 th 2017 Date: March 2017 Page 1 of 12 FIRE SAFETY POLICY Approval Approved by: University Court Date: March 28 th 2017 Page 1 of 12 Date: March 2017 Page 2 of 12 UNIVERSITY OF ABERDEEN FIRE SAFETY POLICY Contents

More information

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9 Index Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8 Fire Risk Assessments 9 Fire Alarm Systems 10-20 Locations 10 Servicing 11 12 Activations 13 14 Weekly Checks

More information

Guided Learning Hours (GLH) 8 Invigilated Assessment Hours (IA) 2 Total Qualification Time (TQT) 10

Guided Learning Hours (GLH) 8 Invigilated Assessment Hours (IA) 2 Total Qualification Time (TQT) 10 Qualification: Date Completed: 02 Feb 17 Unit: FIA AO Level 3 Fire Detection and Alarm Advanced Installer Development Group: FD&A Development Group Guided Learning Hours (GLH) 8 Invigilated Assessment

More information

Personal Protection Systems (PPS)

Personal Protection Systems (PPS) Personal Protection Systems (PPS) Guidance on the use, deployment and limitations of Personal Protection Watermist Systems in the homes of vulnerable people Prepared for: BRE Global Date: 12.11.2015 Report

More information

Consultant Specification AGILE Wireless Fire Detection System

Consultant Specification AGILE Wireless Fire Detection System Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures 161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments

More information

EMERGENCY EVACUATION PLAN

EMERGENCY EVACUATION PLAN UCL ESTATES & FACILITIES DIVISION Construction Maintenance & Fire Safety UNIVERSITY COLLEGE LONDON EMERGENCY EVACUATION PLAN Regulatory Reform (Fire Safety) Order 2005 Name & Address of Building: Occupying

More information

Fire Safety. A TUC guide for trade union activists

Fire Safety. A TUC guide for trade union activists Fire Safety A TUC guide for trade union activists Contents Section one Introduction 3 Section two The law 4 Section three Fire risk assesment 5 Section four Policies and procedures 6 Section five Enforcement

More information

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation FIRE RISK ASSESSMENT Retirement Housing (Independent Living) Developed in conjunction with Cambridge shire Fire and Rescue Service, Housing and Care 21 s primary authority (v3.november 2016) Regulatory

More information

Code of Practice for Design, Installation, Commissioning & Maintenance of Duct Smoke Detector (DSD) Systems

Code of Practice for Design, Installation, Commissioning & Maintenance of Duct Smoke Detector (DSD) Systems Code of Practice for Design, Installation, Commissioning & Maintenance of Duct Smoke Detector (DSD) Systems Issue 1.0 Page 1 of 35 Fire Industry Association Code of Practice for Design, Installation, Commissioning

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems BAFE Scheme: SP203-1 Version 7.1: January 2019 FIRE SAFETY REGISTER Fire Protection Industry Scheme, Reference SP203-1 For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO)

A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO) 4 PEEL HOUSE,TAUNTON STREET,SHIPLEY,BN18 3NA TEL: 01274 595015 FAX: 01274 580804 EMAIL:sales@rosse-systems.co.uk A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO) THE PURPOSE OF THIS DOCUMENT

More information

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation The purpose

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 7240-19 First edition 2007-08-15 Fire detection and alarm systems Part 19: Design, installation, commissioning and service of sound systems for emergency purposes Systèmes de

More information

fire risk assessment For use by landlords of small premises Premises Address

fire risk assessment For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Northern Ireland HMO Fire Safety Guide

Northern Ireland HMO Fire Safety Guide Northern Ireland HMO Fire Safety Guide 2 February 2018 Contents Equality Statement 5 Houses in Multiple Occupation (HMO) Fire Safety Standards 6 1.0 Introduction 6 2.0 Definition of Houses in Multiple

More information

PREMISES FIRE SAFETY LOGBOOK

PREMISES FIRE SAFETY LOGBOOK 0844 740 3473 PREMISES FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: AN INTRODUCTION TO YOUR LOG BOOK. The Regulatory Reform (Fire Safety) Order 2005 (FSO) requires that the

More information

Fire Risk Assessment Guidance

Fire Risk Assessment Guidance Fire Risk Assessment Guidance This document is a guidance note to accompany the example fire risk assessment template. The example fire risk assessment template has been designed with small to medium domestic

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

RRC SAMPLE MATERIAL MANAGING FIRE SAFETY LEARNING OUTCOMES

RRC SAMPLE MATERIAL MANAGING FIRE SAFETY LEARNING OUTCOMES MANAGING FIRE SAFETY LEARNING OUTCOMES On completion of this element, you should be able to demonstrate understanding of the content by applying what you have learnt to familiar and unfamiliar situations.

More information

Approved Document for New Zealand Building Code Warning Systems Clause F7 Third Edition

Approved Document for New Zealand Building Code Warning Systems Clause F7 Third Edition Approved Document for New Zealand Building Code Warning Systems Clause F7 Third Edition Prepared by the Building Industry Authority This Approved Document is prepared by the Building Industry Authority,

More information

Early Warning Fire Detection Engineering

Early Warning Fire Detection Engineering Early Warning Fire Detection Engineering Conference Presentation Author: Adrian Haenni Senior Project Manager EARL WARNING Objective Nature of an Early Warning System Structured method for a successful

More information

Guidance Note. Fire Alarm Detector Applications and Documentation of the Selection

Guidance Note. Fire Alarm Detector Applications and Documentation of the Selection Guidance Note Fire Alarm Detector Applications and Documentation of the Selection Fire Alarm Detector Applications and Documentation of the Selection INTRODUCTION... 3 FLOW CHART FOR THE SELECTION OF...

More information

NHSScotland Firecode Scottish Fire Practice Note 3 Version 3

NHSScotland Firecode Scottish Fire Practice Note 3 Version 3 NHSScotland Firecode Scottish Fire Practice Note 3 Version 3 Escape bed lifts October 2010 Contents page About this publication...4 1. Introduction...5 2. Definitions...6 3. Considerations that will influence

More information

Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website: EQUALITY ACT 2010

Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website:   EQUALITY ACT 2010 Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0)20 3166 5002 Website: www.fia.uk.com EQUALITY ACT 2010 1. INTRODUCTION This Fact File aims to highlight some

More information

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing) FIRE SAFETY LOG BOOK (Record of Fire Safety Equipment Testing) Fire safety log book MARCH 2013 CONTENTS 1.0 PREMISES SPECIFIC INFORMATION 2.0 FIRE SAFETY EQUIPMENT TESTING 2.1 Escape Routes 2.2 Fire Warning

More information

FIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS

FIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS A GUIDE ON FIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS INTRODUCTION Fire safety in blocks of flats is something that must be taken very seriously. The Local Government Group (LGG) was commissioned to

More information

SELF PRESERVATION SOCIETY By Jim Creak

SELF PRESERVATION SOCIETY By Jim Creak SELF PRESERVATION SOCIETY By Editor of the Means of Escape Magazine and Chairman of The Health & Safety Signs Association. w w w. m e a n s - of- e s c a p e. c o m Agenda Regulatory Reform Fire Safety

More information

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL 3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

Handout Notes Major changes in BS : 2016

Handout Notes Major changes in BS : 2016 Handout Notes Major changes in BS 5266-1: 2016 The contents section now includes Introduction 1 Scope 2 Normative references 3 Terms and definitions 4 Consultation and records 5 Illumination for emergency

More information

Draft FPA Australia Technical Specification for Public Comment FPAA101D DRAFT

Draft FPA Australia Technical Specification for Public Comment FPAA101D DRAFT Draft FPA Australia Technical Specification for Public Comment FPAA101D These preliminary pages provide information on the background to this Technical Specification, the system it covers and the context

More information

NHS Tayside. Fire Safety Policy

NHS Tayside. Fire Safety Policy NHS Tayside Fire Safety Policy Policy Manager Mark Anderson, Head of Property Policy Group Fire Safety Policy Review Group Policy Established Last Updated April 2014 Policy Review Period/Expiry April 2017

More information

FIRE SAFETY LOG BOOK

FIRE SAFETY LOG BOOK FIRE SAFETY LOG BOOK Regulatory Reform (Fire Safety) Order 2005 If you own, manage or operate a business, you will need to comply with fire safety law. The main law is the Regulatory Reform (Fire Safety)

More information

Emergency Lighting: what, when & how? Richard Caple MSc MSLL Lighting Applications Manager

Emergency Lighting: what, when & how? Richard Caple MSc MSLL Lighting Applications Manager Emergency Lighting: what, when & how? Richard Caple MSc MSLL Lighting Applications Manager What is emergency lighting? Legislation and standards Emergency lighting design Emergency lighting testing requirements

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE Summary Guadalupe County requirements for the Permit Issuance and safe operation of a Temporary Special Amusement Occupancy. PURPOSE To

More information

QUALIFICATIONS AND CREDIT FRAMEWORK (QCF) LOGIC CERTIFICATION LIMITED (LCL) QUALIFICATION SPECIFICATION

QUALIFICATIONS AND CREDIT FRAMEWORK (QCF) LOGIC CERTIFICATION LIMITED (LCL) QUALIFICATION SPECIFICATION QUALIFICATIONS AND CREDIT FRAMEWORK (QCF) LOGIC CERTIFICATION LIMITED (LCL) QUALIFICATION SPECIFICATION LEVEL 4 CERTIFICATE IN GAS SAFETY MANAGEMENT IN RESIDENTIAL PREMISES (601/0956/8) 1.0 Area and scope

More information

3.1 Introduction. 3.1 Introduction

3.1 Introduction. 3.1 Introduction DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional

More information

UBS1RF OPTICAL SMOKE ALARM EN 14604:2005/AC:2008 DOP:UBS1RF-001-V1

UBS1RF OPTICAL SMOKE ALARM EN 14604:2005/AC:2008 DOP:UBS1RF-001-V1 U S E R M A N U A L UBS1RF OPTICAL SMOKE ALARM EN 14604:2005/AC:2008 DOP:UBS1RF-001-V1 0359 18 UBS1RF Optical Smoke Alarm OverView This optical smoke alarm is a fire detection and alarm device which gives

More information

FIRE SAFETY POLICY Revised March 2013

FIRE SAFETY POLICY Revised March 2013 FIRE SAFETY POLICY Revised March 2013 CONTENTS Page No 1.0 Statement of Intent 1 2.0 Fire Safety Accountability Structure 2 3.0 Roles and Responsibilities 3 4.0 Fire Safety Management 7 5.0 Fire Risk Assessment

More information

New Fire Safety Order

New Fire Safety Order Voltimum Technical seminar New Fire Safety Order Implications for the Emergency Lighting Systems Presented by Chris Watts Cooper Lighting and Security Chairman of - British Standards CPL 34/9 Code of Practice

More information

A GUIDE TO FIRE DETECTION AND ALARM SYSTEMS

A GUIDE TO FIRE DETECTION AND ALARM SYSTEMS A GUIDE TO FIRE DETECTION AND ALARM SYSTEMS A Fire detection and alarm ( FD+a ) system is what most workplaces and public accessed buildings have in place. The FD+a system has two primary functions and

More information

Fire Safety Logbook. FOLLOW the regulations. MANAGE fire risks. RECORD relevant checks

Fire Safety Logbook.  FOLLOW the regulations. MANAGE fire risks. RECORD relevant checks Fire Safety Logbook www.landlords.org.uk FOLLO the regulations RECORD relevant checks MANAGE fire risks Property Details Property Address: Post Code: Licence Holder/Manager: Contact Details Fire Detection

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: DSFRS Log book Version 1.0 (October 2007)

FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: DSFRS Log book Version 1.0 (October 2007) FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: AN INTRODUCTION TO YOUR LOG BOOK. This Fire Safety Log book has been prepared to assist the responsible person in coordinating

More information

INTRUDER ALARM FOR BUSINESS SECURITY

INTRUDER ALARM FOR BUSINESS SECURITY INTRUDER ALARM FOR BUSINESS SECURITY WELCOME PACK THANK YOU FOR CHOOSING ADT Thank you for choosing us to help protect your business and employees. Please take the time to read your Welcome Pack carefully

More information

p. vi, References p. v, Contents p. 7, References pp. 7-8, References p. 5, Contents p. 7, References p. 9, Definitions p. 13, 1.2.

p. vi, References p. v, Contents p. 7, References pp. 7-8, References p. 5, Contents p. 7, References p. 9, Definitions p. 13, 1.2. Compliance Document for New Zealand Building Code Clause F7 Warning Systems Third Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building

More information

THE LOCAL GOVERNMENT GROUP GUIDE: FIRE SAFETY IN PURPOSE-BUILT BLOCKS OF FLATS

THE LOCAL GOVERNMENT GROUP GUIDE: FIRE SAFETY IN PURPOSE-BUILT BLOCKS OF FLATS DERBY HOMES BOARD 24 NOVEMBER 2011 ITEM C5 THE LOCAL GOVERNMENT GROUP GUIDE: FIRE SAFETY IN PURPOSE-BUILT BLOCKS OF FLATS Report of the Chief Executive 1. SUMMARY This report provides a brief overview

More information

Guidance on Video Smoke Detection Technology (VSD)

Guidance on Video Smoke Detection Technology (VSD) Guidance Note Guidance on Video Smoke Detection Technology (VSD) Guidance on Video Smoke Detection Technology (VSD) SCOPE... 3 INTRODUCTION... 4 WHAT IS VSD?... 5 STANDARDS... 7 GENERAL GUIDANCE ON THE

More information

Fire Safety Management Plan. Qube 90, Whitfield Street, W1T 4EZ. Fire Safety Management Plan & Evacuation Procedures

Fire Safety Management Plan. Qube 90, Whitfield Street, W1T 4EZ. Fire Safety Management Plan & Evacuation Procedures Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting Fire 5. 0 Discovering

More information

False Alarm Management

False Alarm Management False Alarm Management This document is intended only for fire system professionals who are already experienced in the selection and positioning of fire detectors. Whenever you apply any False Alarm Management

More information

FIRE SAFETY LOGBOOK ADDRESS OF PREMISES NOMINATED RESPONSIBLE PERSON

FIRE SAFETY LOGBOOK ADDRESS OF PREMISES NOMINATED RESPONSIBLE PERSON FIRE SAFETY LOGBOOK ADDRESS OF PREMISES NOMINATED RESPONSIBLE PERSON SURESITE LTD. All rights reserved. Not to be reproduced without prior permission 23 AN INTRODUCTION TO YOUR LOG BOOK This fire safety

More information

Consumer unit replacement in domestic and similar premises

Consumer unit replacement in domestic and similar premises Consumer unit replacement in domestic and similar premises 6 Issue 2 The Electrical Safety Council is indebted to the following organisations for their contribution and/or support to the development of

More information

Fire Safety Register

Fire Safety Register Fire Safety Register Introduction 1.1 Section 18(2) of the Fire Services Acts, 1981 and 2003 generally applies to all premises other than a dwelling house occupied as a single private dwelling. This section

More information

False Alarm Management. Graham Simons FIA Technical Manager

False Alarm Management. Graham Simons FIA Technical Manager False Alarm Management Graham Simons FIA Technical Manager False Alarm Management Smoke alarms and smoke detectors sensitive to airborne particles and may not discriminate smoke & dust False alarms are

More information

ISO 6183 INTERNATIONAL STANDARD. Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation

ISO 6183 INTERNATIONAL STANDARD. Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation INTERNATIONAL STANDARD ISO 6183 Second edition 2009-06-15 Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation Équipement de protection contre l'incendie

More information

U S E R M A N U A L UBH1RF HEAT ALARM

U S E R M A N U A L UBH1RF HEAT ALARM U S E R M A N U A L UBH1RF HEAT ALARM OverView This heat alarm is a fire detection and alarm device which gives off an audible and visual warning when the ambient temperature reaches 54 C to 70 C. These

More information

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety

More information

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff

More information

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Contents Contents 1. INTRODUCTION... 3 1.1 Purpose...3 1.2 Definitions....3 Premises Management...

More information

Unit 2 Fire Safety (Zone 2)

Unit 2 Fire Safety (Zone 2) IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 2) Examiner Report March 2017 Introduction 21% of the candidates that sat the examination attained a pass. Candidates did not

More information

Health and Safety Services. Safety Guide 5. Fire drills

Health and Safety Services. Safety Guide 5. Fire drills Health and Safety Services Safety Guide 5 Fire drills Fire drills Contents Summary...iii 1. Scope...1 2. Responsibilities...1 2.1. Duties on managers... 1 2.2. Duties of all building occupants... 1 2.3.

More information

Date Issued: December 14, 2017 Revision: 2.1

Date Issued: December 14, 2017 Revision: 2.1 2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,

More information

Compliance Document for New Zealand Building Code Clause F7 Warning Systems Third edition

Compliance Document for New Zealand Building Code Clause F7 Warning Systems Third edition Compliance Document for New Zealand Building Code Clause F7 Warning Systems Third edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building

More information

AMBASSADOR HOUSE. A guide on. Fire Safety in Purpose Built Blocks of Flats

AMBASSADOR HOUSE. A guide on. Fire Safety in Purpose Built Blocks of Flats AMBASSADOR HOUSE A guide on Fire Safety in Purpose Built Blocks of Flats INTRODUCTION Fire safety in blocks of flats is something that must be taken very seriously. The Local Government Group (LGG) was

More information

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted Fire Risk Assessment Prepared for ABC Car Workshop Assessor: (Assessor s Name) Date of Assessment: 24/07/17 Date of Next Assessment Review: Upon occupation Introduction and Scope This Fire Risk Assessment

More information

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. IF YOU RECEIVED A NOTICE BY MAIL AND YOU DO NOT CURRENTLY HAVE A FIRE ALARM INSTALLED IN YOUR BUILDING, YOU MAY DISREGARD THE NOTICE. Dear Building

More information