BRAT BRAN INSTALLATION, USER AND MAINTENANCE MANUAL

Size: px
Start display at page:

Download "BRAT BRAN INSTALLATION, USER AND MAINTENANCE MANUAL"

Transcription

1 INSTALLATION, USER AND MAINTENANCE MANUAL EN Air/water chillers and heat pumps with axial-flow fans with and without pump assemblies BRAT BRAN

2 INDEX INDICE U General warnings 3 A Checking and starting up the unit 19 U Waiver of liability 3 A LED and display 20 U Fundamental safety rules 3 I A Displaying alarms 28 I Receiving, handling and installing the 4 product Characteristics 5 Dimensioned drawings 6 Water connections 6 Electrical connections 10 Mains power supply connections 12 Installer connections 12 General technical data 14 U A A A A Peak limiter alarm signals 29 Operating characteristics 30 Shutting down for long periods 32 Routine maintenance 32 Special maintenance 32 Disposal 32 Troubleshooting 33 Useful information 35 U I A Operating limits 16 Pressure drop and pressure head available 17 to system The following symbols are used in some parts of this publication and inside the unit: U User Important Danger high temperatures I Installer Prohibition A Assistance Danger voltage The manufacturer reserves the right to modify the data in this manual without warning. ENVIRONMENTAL INFORMATION: This unit contains fluorinated greenhouse gases covered by the Kyoto Protocol. The maintenance and disposal operations must only be carried out by qualified personnel. 2 BRAT2 - BRAN2 EN

3 GENERAL WARNINGS These appliances have been designed to chill and/or heat water and must be used in applications compatible with their performance characteristics; these appliances are designed for residential or similar applications. Incorrect installation, regulation and maintenance or improper use absolve the manufacturer from all liability, whether contractual or otherwise, for damage to people, animals or things. Only those applications specifically indicated in this list are permitted Read this manual carefully. All work must be carried out by qualified personnel in conformity with legislation in force in the country concerned. The warranty is void if the above instructions are not respected and if the unit is started up for the first time without the presence of personnel authorised by the Company (where specified in the supply contract) who should draw up a start-up report. U The documents supplied with the unit must be consigned to the owner who should keep them carefully for future consultation in the event of maintenance or service. When the items are consigned by the carrier, check that the packaging and the unit are undamaged. If damage or missing components are noted, indicate this on the delivery note. A formal complaint should be sent via fax or registered post to the After Sales Department within eight days from the date of receipt of the items. All repair or maintenance work must be carried out by the Company s Technical Service or qualified personnel following the instructions in this manual. Do not modify or tamper with the appliance as this may create situations of danger; in such cases the manufacturer of the appliance is not liable for any damage caused. WAIVER OF LIABILITY This publication is the sole property of Climaveneta. Any reproduction or disclosure of such is strictly prohibited without the written authorisation of Climaveneta. This document has been prepared with maximum care and attention paid to the content shown. Nonetheless, Climaveneta waives all liability deriving from the use of such document. Read this document carefully. U All work must be performed, components selected and materials used professionally and in complete accordance with the legislation in force in material in the country concerned, and considering the operating conditions and intended uses of the system, by qualified personnel. FUNDAMENTAL SAFETY RULES U When operating equipment involving the use of electricity and water, a number of fundamental safety rules must be observed, namely: The unit must not be used by children or by unfit persons without suitable supervision. Do not touch the unit with bare feet or with wet or damp parts of the body. Never perform any cleaning operations before having disconnected the unit from the mains power supply. Do not modify safety or control devices without authorisation and instructions from the manufacturer. Do not pull, detach or twist the electrical cables coming from the unit, even when disconnected from the mains electricity supply. Do not open doors or panels providing access to the internal parts of the unit without first ensuring that the mains switch is in the off position. Do not introduce pointed objects through the air intake and outlet grills. Do not dispose of, abandon or leave within reach of children packaging materials (cardboard, staples, plastic bags, etc.) as they may represent a hazard. The BRAT/N appliances are supplied without the main switch. Respect safety distances between the unit and other equipment or structures. Guarantee adequate space for access to the unit for maintenance and/or service operations (see the figure on page 5). Power supply: the size of the electrical cables must be adequate for the power of the unit and the power supply voltage must correspond with the value indicated on the respective units. All units must be earthed in conformity with legislation in force in the country concerned. Some terminals in the electrical panel may be powered even after the unit is disconnected. Make sure power is not connected before proceeding. Water connections should be carried out as indicated in the instructions to guarantee correct operation of the unit. Add glycol to the water circuit if the unit is not used during the winter or the circuit is not emptied. Handle the unit with the utmost care (see weight distribution table) to avoid damage. Power supply to the unit must be disconnected using a switch with suitable characteristics, to be supplied and installed by the installer. BRAT2 - BRAN2 EN 3

4 H RECEIVING, HANDLING AND INSTALLING THE PRODUCT The chillers are supplied accompanied by: - installation, user and maintenance manual; - CE declaration; CHOICE OF INSTALLATION SITE Before installing the unit, agree with the customer the site where it will be installed, taking the following points into consideration: Check that the fixing points are adequate to support the weight of the unit; Pay scrupulous respect to safety distances between the unit and other equipment or structures to ensure that air entering the unit and discharged by the fans is free to circulate. HANDLING AND POSITIONING The unit should always be handled by qualified personnel using equipment adequate for the weight of the chiller. Before handling the unit, check the capacity of the lift equipment used, respecting the instructions on the packaging. To move the unit horizontally, make appropriate use of a lift truck or similar, bearing in mind the weight distribution of the unit. To lift the unit, insert tubes long enough to allow positioning of the lifting slings and safety pins in the special feet on the unit. For the sizes of these tubes, see the figures shown in the corresponding section. To avoid the slings damaging the unit, place protection between the slings and the unit. Position the unit in the site indicated by the customer. Place either a layer of rubber (min. thickness 10 mm) or vibration damper feet (optional) between the base and support surface. Fix the unit, making sure it is level and that there is easy access to water and electrical components. If the site is exposed to strong winds, fix the unit adequately using tie rods if necessary. If a heat pump unit is being installed, make sure the condensate is drained using the drain hose supplied as standard. Prevent leaves, branches or snow from accumulating around the unit. These could reduce the efficiency of the unit. The installation, user and maintenance manual is an integral part of the unit and should therefore be read and kept carefully. It is recommended that the packaging should not be removed until the unit is located in the installation site. During transport, the chiller should be kept in a vertical position The weight of the chiller is biased towards the compressor side (side of the packaging with the barcode, see the figure at the foot of the page). Do not dispose of packaging materials in the environment or leave them within reach of children as they may represent a hazard. Barcode (compressor side) L P BRAT(N) : Ø 22mm BRAT(N) : Ø 25mm BRAT2 Dimensions and weight with standard packaging Size 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T 0071T 0091T 0101T 0121T Dimension L mm Dimension P mm Dimension H mm Weight Kg BRAN2 Dimensions and weight with standard packaging Size 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T 0071T 0091T 0101T 0121T Dimension L mm Dimension P mm Dimension H mm Weight Kg BRAT2 Dimensions and weight with wooden crate Size 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T 0071T 0091T 0101T 0121T Dimension L mm Dimension P mm Dimension H mm Weight difference Kg BRAN2 Dimensions and weight with wooden crate Size 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T 0071T 0091T 0101T 0121T Dimension L mm Dimension P mm Dimension H mm Weight difference Kg BRAT2 - BRAN2 EN

5 CHARACTERISTICS The BRAT(N)2 appliances are air-water units operating on R-410A and refrigerant are suitable for outdoor installation. The units are CE marked, as established by the EU directives, including the latest amendments, and the corresponding approximated national legislation. They are factory tested and on site installation is limited to water and electrical connections Electrical panel 2 Control panel 3 Heat exchanger, side 4 Low pressure switch 5 High pressure switch 6 Scroll compressor 7 Filter 8 Thermostatic valve 9 Axial-flow fan 10 Heat exchanger, outdoor side 11 Pump (accessory) 12 Liquid receiver (only BRAN2) 13 Expansion vessel (models WITH HYDRONIC UNIT only) 14 Reversing valve (only BRAN2) BRAT2 - BRAN2 EN 5

6 DIMENSIONED DRAWINGS I C W1 = E = W2 B 900 W4 A W D Dimension 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T 0071T 0091T 0101T 0121T A mm B mm C mm D mm E mm Weight distribution BRAT2 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T 0071T 0091T 0101T 0121T W1 kg W2 kg W3 kg W4 kg Total in operation kg Weight distribution BRAN2 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T 0071T 0091T 0101T 0121T W1 kg W2 kg W3 kg W4 kg Total in operation kg WATER CONNECTIONS The choice and installation of components is the responsibility of the installer who should follow good working practice and current legislation. Construction of a bypass is recommended to enable the pipes to be washed through without having to disconnect the unit (see drain valves). The connection piping should be supported in such a way as to avoid it weighing on the unit. The following devices must be installed on the water circuit: 1. Two pressure gauges with a suitable scale (intake and outlet); 2. Two vibration damper joints (intake and outlet); 3. Two shut off valves (normal in intake and calibrating in outlet); 4. A flow switch on the unit outlet to the system circuit (compulsory). The flow switch must be calibrated by the installer to a value equal to 70% of rated flow. 5. Two thermometers (intake and outlet). 6. An intake filter must be installed as close as possible to the evaporator and positioned to allow easy access for routine maintenance. 500 micron filter mesh. 7. All the pipes must be insulated with suitable material to prevent the formation of condensate and heat loss. The insulating material must be a vapour barrier. Make sure that the control and shut-off devices protrude from the insulation. 8. At the lowest points in the system, install drain valves for easy emptying. 9. At the highest points in the system, install automatic or manual air vent valves. Failure to install the flow switch will mean the heat exchanger is not protected in the event of no flow of liquid. Climaveneta cannot be held liable for any damage to the unit and/or the system following the failure to install these devices or the filter. The correct operation of the components that help ensure the safety of the appliance and the system should be checked regularly. Specifically, this involves cleaning the filters and checking the operation of the flow switches installed. Water flow to the chiller unit must conform to the values shown in the section on General Technical Data. The flow of water must be maintained constant during operation. The water content of the unit must be such as to avoid disturbing operation of the refrigerant circuits. 6 BRAT2 - BRAN2 EN

7 Minimum system water content Size 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T 0071T 0091T 0101T 0121T Minimum water content BRAT2 l Minimum water content BRAN2 l Expansion vessel size Size 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T 0071T 0091T 0101T 0121T Expansion vessel BRAT2 l Expansion vessel BRAN2 l Safety valve calibration Size 0021M-T 0025M-T 0031M-T 0041M-T 0051T 0061T 0071T 0091T 0101T 0121T Safety valve l System water circuit connection diagram, BRAT2 version WITHOUT HYDRONIC KIT FACTORY CONNECTED INSTALLER CONNECTIONS UTILITY RETURN UTILITY OUTLET 1 PRESSURE GAUGE 2 VIBRATION-ISOLATING JOINT 3 SHUT-OFF VALVE 4 CALIBRATING VALVE 5 FLOW SWITCH 6 THERMOMETER 7 CIRCULATOR PUMP 8 SAFETY VALVE 9 EXPANSION VESSEL 10 MESH FILTER 11 FILL/TOP-UP 12 TEMPERATURE PROBE 13 DIFFERENTIAL PRESSURE SWITCH 14 DRAIN/CHEMICAL WASHING VALVE 15 SYSTEM VENT System water circuit connection diagram, BRAT2 version WITH HYDRONIC KIT FACTORY CONNECTED INSTALLER CONNECTIONS UTILITY OUTLET 15 UTILITY RETURN 1 PRESSURE GAUGE 2 VIBRATION-ISOLATING JOINT 3 SHUT-OFF VALVE 4 CALIBRATING VALVE 5 FLOW SWITCH 6 THERMOMETER 7 CIRCULATOR PUMP 8 SAFETY VALVE 9 EXPANSION VESSEL 10 MESH FILTER 11 FILL/TOP-UP 12 TEMPERATURE PROBE 13 DIFFERENTIAL PRESSURE SWITCH 14 DRAIN/CHEMICAL WASHING VALVE 15 SYSTEM VENT System water circuit connection diagram, BRAN2 version WITHOUT HYDRONIC KIT FACTORY CONNECTED INSTALLER CONNECTIONS UTILITY RETURN UTILITY OUTLET 1 PRESSURE GAUGE 2 VIBRATION-ISOLATING JOINT 3 SHUT-OFF VALVE 4 CALIBRATING VALVE 5 FLOW SWITCH 6 THERMOMETER 7 CIRCULATOR PUMP 8 SAFETY VALVE 9 EXPANSION VESSEL 10 MESH FILTER 11 FILL/TOP-UP 12 TEMPERATURE PROBE 13 DIFFERENTIAL PRESSURE SWITCH 14 DRAIN/CHEMICAL WASHING VALVE 15 SYSTEM VENT BRAT2 - BRAN2 EN 7

8 System water circuit connection diagram, BRAN2 version WITH HYDRONIC KIT FACTORY CONNECTED INSTALLER CONNECTIONS UTILITY OUTLET 15 UTILITY RETURN 1 PRESSURE GAUGE 2 VIBRATION-ISOLATING JOINT 3 SHUT-OFF VALVE 4 CALIBRATING VALVE 5 FLOW SWITCH 6 THERMOMETER 7 CIRCULATOR PUMP 8 SAFETY VALVE 9 EXPANSION VESSEL 10 MESH FILTER 11 FILL/TOP-UP 12 TEMPERATURE PROBE 13 DIFFERENTIAL PRESSURE SWITCH 14 DRAIN/CHEMICAL WASHING VALVE 15 SYSTEM VENT The chillers must be provided with a filling/top-up system connected to the return line and a drain cock in the lowest part of the installation. Installations containing antifreeze or covered by specific legislation must be fitted with water circuit disconnectors. The manufacturer is not liable for obstruction, breakage or noise resulting from the failure to install filters or vibration dampers. Particular types of water used for filling or topping up must be treated with appropriate treatment systems. For reference values, see the table. Risk of freezing The unit must be prevented from freezing at outside air temperatures around 0 C. The following are recommended: use suitable percentages of antifreeze (see Ethylene glycol solutions ) protect the piping with heating sheaths, empty the system, making sure no water remains at the lowest points in the circuit or there are closed valves where water may stagnate. It is recommended to use non-toxic food grade antifreeze, compliant with the standards in force in the countries where the unit is used, if domestic hot water production is also featured. The antifreeze used must be corrosion inhibited and compatible with the water circuit components. Ethylene glycol solutions Water and ethylene glycol solutions used as a heat carrier in the place of water reduce the performance of the unit. Multiply the performance figures by the values given in the following table. The heat pumps must be fitted with a filling/top-up system connected to the return line and a drain valve in the lowest part of the system. Systems containing antifreeze or covered by specific legislation must be fitted with low-loss headers. cpf cq cdp Freezing point ( C) Percentage of ethylene glycol by weight 12% 0,985 1,02 1,07 cpf: cooling capacity correction factor cq: flow rate correction factor cdp: pressure drop correction factor 20% 0,98 1,04 1,11 28% 0,974 1,075 1,18 35% 0,97 1,11 1,22 40% 0,965 1,14 1,24 Water quality The water used in the system and domestic hot water circuits must comply with the following characteristics: PH 6-8 Electrical conductivity less than 200 mv/cm (25 C) Chlorine ions less than 50 ppm Sulphuric acid ions less than 50 ppm Total iron less than 0.3 ppm Alkalinity M less than 50 ppm Total hardness less than 50 ppm Sulphur ions none Ammonia ions none Silicon ions less than 30 ppm 8 BRAT2 - BRAN2 EN

9 Fouling factors The performance data given refer to conditions with clean evaporator plates (fouling factor = 1). For different fouling factors, multiply the figures in the performance tables by the coefficient given in the following table. Fouling factors (m 2 C/W) f1 4,4 x ,86 x ,72 x ,96 0,93 f1: capacity correction factor fk1: compressor power input correction factor fx1: total power input correction factor Evaporator fk1-0,99 0,98 fx1-0,99 0,98 SIZE AND POSITIONING OF CONNECTIONS, BRAT2 AND BRAN2 BRAT2 Safety valve BRAN2 Safety valve IN OUT B C OUT B C IN A D A D Dimensions A mm B mm C mm D* mm Water connections in/out, male Ø /4 1 1/4 1 1/4 1 1/4 *D Safety valve connector position, only on the models with hydronic kit Condensate drain In heating mode the unit produces a significant quantity of condensate, which must be suitably drained. Proceed as follows: Connect the unit condensate drain Make sure the drain hose has a incline of at least 2 cm/m, without obstructions or choking. Connect the condensate drain hose to a rainwater drain. Do not connect to the sewage system as odours may be sucked up if the water in the drain trap evaporates. After connecting, check correct drainage of the condensate by pouring water into the pan. If necessary, suitably insulate the condensate drain hose. Condensate drainage must not cause problems to objects or people. If the outside air temperature is less than 0 C, the condensate may freeze. The unit comes with frost protection for the condensate collection basin inside the unit. Use hot wires on the condensate drain hose downstream of the unit to protect against frost. BRAT2 - BRAN2 EN 9

10 FILLING THE SYSTEM - Before filling, check that the system drain valve is closed. - Open all system and terminal air vents. - Open system shut off valves. - Start filling by slowly opening the system water fill cock outside the unit. - When water begins to leak out of the terminal air vent valves, close them and continue filling until the pressure gauge indicates a pressure of 1.5 bar. The system must be filled to a pressure of between 1 and 2 bars. It is recommended that this operation be repeated after the unit has been operating for a number of hours. The pressure of the system should be checked regularly and if it drops below 1 bar, the water content should be topped-up. Check the tightness of the joints. EMPTYING THE SYSTEM - Before emptying, place the mains switch in the off position. - Make sure the system fill/top-up water cock is closed. - Open the drain cock outside the unit and all the system and terminal air vent valves. If the fluid in the circuit contains antifreeze, it should not be allowed to drain freely, as it is pollutant.it should be collected for possible reuse.when draining after heat pump operation, take care as the water may be hot (up to 50 ). ELECTRICAL CONNECTIONS The BRAT2 and BRAN2 leave the factory already wired, and require the installation of a circuit breaker, a lockable mains disconnect switch for the connection to the mains power supply, and the connection of the flow switch to the corresponding terminals. All the above operations must be carried out by qualified personnel in compliance with the legislation in force. For all electrical work, refer to the electrical wiring diagrams in this manual. It is also recommended to check that: - The characteristics of the mains electricity supply are adequate for the power ratings indicated in the electrical specifications below, also bearing in mind the possible use of other equipment at the same time. The devices on the unit must be lockable. An efficient earth connection is obligatory. The manufacturer cannot be held liable for any damage caused by the failure to correctly earth the unit. In the case of three phase units, ensure the phases are connected correctly. Do not use water pipes to earth the unit. Power to the unit must be turned on only after installation work (water and electrical) has been completed. All the electrical connections must be performed by qualified personnel according to the relevant standards in force in the country concerned. Respect instructions for connecting phase, neutral and earth conductors. The power line should be fitted upstream with a suitable device to protect against short-circuits and leakage to earth, isolating the installation from other equipment. Voltage must be within a tolerance of ±10% of the rated power supply voltage for the unit (for three phase units, the unbalance between the phases must not exceed 2%). If these parameters are not respected, contact the electricity supply company.for electrical connections, use double insulation cable in conformity with legislation in force in the country concerned. A circuit breaker and a lockable mains disconnect switch, in compliance with the CEI-EN standards (contact opening of at least 3mm), with adequate switching and residual current protection capacity based on the electrical data table shown below, must be installed as near as possible to the appliance. 10 BRAT2 - BRAN2 EN

11 ELECTRICAL DATA, BRAT2 AND BRAN2 WITHOUT HYDRONIC KIT Size Power supply Maximum values Fuses (5x20T 250V) (V-Ph-Hz) FLA [A] FLI [kw] SA [A] SA LIM [A] FU1 FU2 FU3 FU4 BRAT2 - BRAN N-50 16,6 3,1 61,6 27,6 4A 1,25A 2A - BRAT2 - BRAN N-50 19,6 3,8 82,6 37,6 4A 1,25A 2A - BRAT2 - BRAN N-50 23,6 4,7 97,6 44,6 4A 1,25A 2A - BRAT2 - BRAN N-50 27,6 6,0 131,3 46,3 4A 1,6A 2A - BRAT2 - BRAN N-50 6,1 3,1 32,6 18,6 4A 1,25A 2A - BRAT2 - BRAN N-50 6,6 3,6 35,6 19,6 4A 1,25A 2A - BRAT2 - BRAN N-50 8,6 4,4 48,6 26,6 4A 1,25A 2A - BRAT2 - BRAN N-50 10,6 6,0 65,3 36,3 4A 1,6A 2A - BRAT2 - BRAN N-50 12,4 6,1 65,3 36,3 4A 1,6A 2A - BRAT2 - BRAN N-50 15,6 7,4 75,3 42,3 4A 1,6A 2A - BRAT2 - BRAN N-50 16,8 8,8 102,3 57,3 4A 1,6A 1A 1A BRAT2 - BRAN N-50 18,8 10,0 129,3 71,3 4A 1,6A 1A 1A BRAT2 - BRAN N-50 22,2 11,7 140,9 77,9 4A 3,15A 1A 1A BRAT2 - BRAN N-50 31,6 14,7 141,9 78,9 4A 3,15A 1A 1A F.L.I. Maximum power input F.L.A. Maximum current input S.A. Start-up current S.A. LIM Peak current with peak limiter Maximum values for sizing the protection switches and power supply cables ELECTRICAL DATA, BRAT2 AND BRAN2 WITH HYDRONIC KIT Size Power supply Maximum values Fuses (5x20T 250V) (V-Ph-Hz) FLA [A] FLI [kw] SA [A] SA LIM [A] FU1 FU2 FU3 FU4 BRAT2 - BRAN N-50 17,2 3,1 62,2 28,2 1,25 1,25A 2A - BRAT2 - BRAN N-50 20,2 3,9 83,2 38,2 1,25 1,25A 2A - BRAT2 - BRAN N-50 24,2 4,8 98,2 45,2 1,25 1,25A 2A - BRAT2 - BRAN N-50 28,6 6,1 132,2 47,2 1,25 1,6A 2A - BRAT2 - BRAN N-50 6,7 3,1 33,2 19,2 1,25 1,25A 2A - BRAT2 - BRAN N-50 7,2 3,7 36,2 20,2 1,25 1,25A 2A - BRAT2 - BRAN N-50 9,2 4,5 49,2 27,2 1,25 1,25A 2A - BRAT2 - BRAN N-50 11,6 6,1 66,2 37,2 1,25 1,6A 2A - BRAT2 - BRAN N-50 13,4 6,2 66,2 37,2 1,25 1,6A 2A - BRAT2 - BRAN N-50 16,6 7,5 76,2 43,2 1,25 1,6A 2A - BRAT2 - BRAN N-50 18,1 9,0 103,6 58,6 1,6 1,6A 1A 1A BRAT2 - BRAN N-50 20,1 10,2 130,6 72,6 1,6 1,6A 1A 1A BRAT2 - BRAN N-50 23,5 12,0 142,2 79,2 1,6 3,15A 1A 1A BRAT2 - BRAN N-50 32,9 15,0 143,2 80,2 1,6 3,15A 1A 1A F.L.I. Maximum power input F.L.A. Maximum current input S.A. Start-up current S.A. LIM Peak current with peak limiter Maximum values for sizing the protection switches and power supply cables BRAT2 - BRAN2 EN 11

12 MAINS POWER SUPPLY CONNECTIONS Before connecting the unit to the power supply, makes sure that switch QF1 is open, suitably padlocked and marked. Remove the inspection panel by unscrewing the screws. Use cable gland A for the main electrical power cable and cable gland B for other external cables to be connected by the installer. A B Identify the terminals used for electrical connections on the layout drawing shown in this manual. Make the connections as shown on the wiring diagram enclosed with the product. Replace the covers on the electrical panel and the closing panel. Make sure that all the covers removed to make the electrical connections have been replaced before powering up the unit. Position the main switch QF1 (outside the unit) in the ON position. INSTALLER CONNECTIONS All terminals referred to in the explanations below are to be found on the terminal block inside the electrical panel and described as installer terminals (see the wiring diagram enclosed with the product). REMOTE ON/OFF (SA1) To use a remote on/off device, an external contactor must be connected to installer terminals 14 and 15, setting parameter CL42 to -1 (CL42=-1). For timed operation, connect a daily or weekly timer between terminals 14 and 15. REMOTE ALARM (RD1) For remote display of unit shut-down, an audible or visual alarm warning device can be connected between terminals 12 and 13. Connect the phase to terminal 13 and the alarm signal device between terminal 13 and the neutral (maximum load applicable 500 ma at 24 V). REMOTE COOLING/HEATING CHANGEOVER (SA2) To use a remote cooling/heating changeover device, connect the contact of the device to installer terminals 16 and 17. To activate the device, proceed as follows: - From the HSW15 control panel select parameter CL43 and set it to the value +3 (contact closed = cooling, contact open = heating) or -3 (contact closed = heating, contact open = cooling) COMPRESSOR ON SIGNAL (GN1) For remote display of compressor operating status, an audible or visual alarm warning device can be connected between terminals 10 and 11. Connect the phase to terminal 11 and the signal device between terminal 10 and the neutral. 12 BRAT2 - BRAN2 EN

13 / OUTSIDE AIR PROBE (BT3) (Accessory) The outside air probe allows the system water temperature set point to be compensated during heating or cooling operation. Installation instructions The outside air probe must be installed: outside of the home not in direct sunlight, away from flue gas discharges, air outlets, or doors and windows. on a perimeter wall facing north/north-west at a minimum height of 2.5 metres above the ground or at most half way up the house. H 1 2H min2,5 m N-W N Mounting method: Open the cover of the sensor. Attach a probe to the wall and the correct position as described above. For the electrical connections see Connection diagram. Re-place the cover of the sensor. TECHNICAL DATA Sensing element NTC 10Kohm ± 1% (25 C) Degree of protection IP65 Perm. ambient / carriage temperature -50 C C Measuring range -50 C C Materials PA 15% GK, Colour RAL 9010 BT REMOTE KEYPAD KIT (A5) (Accessory) The remote keypad kit can be used to display all unit functions and access the parameters of the electronic board from a point located at some distance from the unit itself. It consists of a remote control module. To install the kit, proceed as follows: - access the unit s electrical panel after having disconnected the power supply; - connect the remote control module with 3 wires to terminals 22, 23 and 24 on the installer terminal block: - terminal 22 connected to the GND terminal on the module; - terminal 23 connected to the Signal terminal on the module; - terminal 24 connected to the +12V DC terminal on the module; FLOW SWITCH CONNECTION (F3) The system flow switch must be connected to terminals 18 and 19. If this is not connected, the unit will not be able to operate and the controller will display alarm code ER20 (see "Displaying alarms"). BRAT2 - BRAN2 EN 13

14 GENERAL TECHNICAL DATA U BRAT2 without hydronic kit Cooling capacity 1 [kw] 7,71 9,50 11,5 15,0 7,70 9,0 11,64 15,7 17,9 20,5 25,1 28,4 35,1 40,6 Power consumption 1 [kw] 2,18 2,71 3,73 4,44 2,11 2,51 3,49 4,61 4,97 5,87 7,53 9,14 9,95 12,9 EER 1 3,54 3,50 3,09 3,39 3,65 3,58 3,34 3,40 3,61 3,50 3,34 3,11 3,53 3,15 Cooling capacity 2 [kw] 5,74 7,03 8,68 11,4 5,72 7,10 8,76 11,8 13,3 15,6 19,0 21,6 26,6 31,5 Power consumption 2 [kw] 2,10 2,60 3,53 4,16 2,06 2,46 3,24 4,32 4,78 5,38 6,81 8,24 9,08 11,9 EER 2 2,73 2,70 2,46 2,74 2,77 2,89 2,70 2,74 2,79 2,89 2,79 2,62 2,93 2,64 ESEER 1 3,31 3,32 3,06 3,21 3,43 3,57 3,26 3,30 3,18 3,39 3,25 3,08 3,42 3,11 Flow-rate 1 m 3 /h 1,33 1,63 1,98 2,59 1,32 1,55 2,00 2,70 3,09 3,53 4,32 4,89 6,04 6,99 Pressure drop 1 kpa Flow-rate 2 m 3 /h 0,99 1,21 1,49 1,96 0,98 1,22 1,51 2,04 2,29 2,68 3,27 3,71 4,57 5,42 Pressure drop 2 kpa Sound power 4 [dba] Power supply V-N/Ph-Hz 230-1N N-50 No. of compressors No. of circuits Type of compressor Scroll No. of fans Air flow-rate 1 [m 3 /h] No. of system heat exchangers Type of system heat exchanger PLATE System water heat exchanger content l (1) outside air 35 C evaporator water IN/OUT 23/18 C (2) outside air 35 C evaporator water IN/OUT 12/7 C (3) maximum and minimum operating pressure refer to activation of the pressure switches (4) sound power based on measurements performed in accordance with ISO 9614 and Eurovent 8/1 Performance in accordance with EN 14511:2013 BRAT2 with hydronic kit Cooling capacity 1 [kw] 7,76 9,56 11,6 15,1 7,75 9,1 11,70 15,8 18,0 20,7 25,3 28,6 35,3 40,9 Power consumption 1 [kw] 2,10 2,62 3,63 4,30 2,03 2,43 3,38 4,49 4,81 5,73 7,31 8,94 9,67 12,6 EER 1 3,69 3,65 3,20 3,51 3,82 3,73 3,46 3,52 3,74 3,61 3,46 3,20 3,65 3,24 Cooling capacity 2 [kw] 5,77 7,08 8,73 11,5 5,75 7,15 8,81 11,9 13,4 15,7 19,1 21,7 26,8 31,8 Power consumption 2 [kw] 2,05 2,54 3,44 4,09 2,01 2,39 3,16 4,23 4,69 5,27 6,63 8,07 8,87 11,8 EER 2 2,82 2,79 2,54 2,81 2,86 2,99 2,79 2,81 2,86 2,98 2,88 2,69 3,02 2,70 ESEER 1 3,43 3,46 3,16 3,31 3,56 3,73 3,37 3,40 3,29 3,51 3,36 3,17 3,53 3,20 Flow-rate 1 m 3 /h 1,33 1,64 2,00 2,60 1,33 1,56 2,01 2,72 3,10 3,56 4,35 4,92 6,07 7,03 Available pressure head 1 kpa Flow-rate 2 m 3 /h 0,99 1,22 1,50 1,98 0,99 1,23 1,52 2,05 2,30 2,70 3,29 3,73 4,61 5,47 Available pressure head 2 kpa Sound power [dba] Power supply V-N/Ph-Hz 230-1N N-50 No. of compressors No. of circuits Type of compressor Scroll No. of fans Air flow-rate [m 3 /h] No. of system heat exchangers Type of system heat exchanger PLATE System water heat exchanger content l (1) outside air 35 C evaporator water IN/OUT 23/18 C (2) outside air 35 C evaporator water IN/OUT 12/7 C (3) maximum and minimum operating pressure refer to activation of the pressure switches (4) Sound power based on measurements performed in accordance with ISO 9614 and Eurovent 8/1 Performance in accordance with EN 14511: BRAT2 - BRAN2 EN

15 GENERAL TECHNICAL DATA U BRAN2 without hydronic kit Heating capacity 1 [kw] 6,76 8,37 10,5 12,9 6,73 8,3 10,00 13,4 14,8 17,3 21,5 24,7 29,7 35,9 Power consumption 1 [kw] 2,31 2,93 3,57 4,50 2,30 2,78 3,31 4,63 4,79 5,73 6,81 7,84 9,49 11,3 COP 1 2,93 2,86 2,93 2,87 2,93 2,98 3,02 2,89 3,09 3,02 3,16 3,15 3,13 3,17 Cooling capacity 2 [kw] 4,81 5,89 7,29 9,6 4,80 5,99 7,35 10,0 11,1 13,0 15,9 18,4 22,3 27,1 Power consumption 2 [kw] 2,02 2,49 3,36 3,95 1,98 2,36 3,06 4,09 4,53 5,09 6,40 7,80 8,51 11,3 EER 2 2,38 2,37 2,17 2,42 2,43 2,54 2,40 2,43 2,45 2,56 2,49 2,36 2,62 2,39 ESEER 1 2,89 2,92 2,70 2,86 3,00 3,14 2,88 2,94 2,78 3,00 2,89 2,77 3,05 2,83 Flow-rate 1 m 3 /h 1,16 1,44 1,80 2,22 1,16 1,43 1,72 2,30 2,55 2,98 3,70 4,25 5,11 6,17 Pressure drop 1 kpa Flow-rate 2 m 3 /h 0,83 1,01 1,25 1,64 0,83 1,03 1,26 1,71 1,91 2,24 2,74 3,16 3,84 4,66 Pressure drop 2 kpa Sound power 4 [dba] Power supply V-N/Ph-Hz 230-1N N-50 No. of compressors No. of circuits Type of compressor Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll No. of fans Air flow-rate 1 [m 3 /h] No. of system heat exchangers Type of system heat exchanger PLATE System water heat exchanger content l (1) outside air 7 C; condenser water in/out 40/45 C (2) outside air 35 C; evaporator water IN/OUT 12/7 C (3) maximum and minimum operating pressure refer to activation of the pressure switches (4) Sound power based on measurements performed in accordance with ISO 9614 and Eurovent 8/1 Performance in accordance with EN 14511:2013 BRAN2 with hydronic kit Heating capacity 1 [kw] 6,72 8,32 10,4 12,8 6,68 8,2 9,99 13,3 14,8 17,2 21,4 24,5 29,4 35,7 Power consumption 1 [kw] 2,24 2,85 3,47 4,38 2,23 2,70 3,23 4,54 4,68 5,60 6,65 7,61 9,27 11,1 COP 1 3,00 2,92 3,00 2,92 3,00 3,05 3,09 2,93 3,16 3,07 3,22 3,22 3,17 3,22 Cooling capacity 2 [kw] 4,83 5,93 7,33 9,6 4,82 6,03 7,39 10,0 11,2 13,1 16,0 18,5 22,5 27,3 Power consumption 2 [kw] 1,98 2,44 3,29 3,91 1,94 2,31 2,99 4,03 4,46 5,00 6,27 7,64 8,43 11,1 EER 2 2,44 2,43 2,23 2,46 2,49 2,61 2,47 2,48 2,51 2,62 2,55 2,42 2,67 2,45 ESEER 1 2,97 3,02 2,77 2,91 3,07 3,26 2,97 2,99 2,85 3,09 2,97 2,84 3,12 2,89 Flow-rate 1 m 3 /h 1,16 1,43 1,79 2,20 1,15 1,42 1,72 2,29 2,55 2,96 3,68 4,21 5,06 6,14 Available pressure head 1 kpa Flow-rate 2 m 3 /h 0,83 1,02 1,26 1,65 0,83 1,04 1,27 1,72 1,93 2,25 2,75 3,18 3,87 4,70 Available pressure head 2 kpa Sound power [dba] Power supply V-N/Ph-Hz 230-1N N-50 No. of compressors No. of circuits Type of compressor Scroll No. of fans Air flow-rate [m 3 /h] No. of system heat exchangers Type of system heat exchanger PLATE System water heat exchanger content l (1) outside air 7 C; condenser water in/out 40/45 C (2) outside air 35 C; evaporator water IN/OUT 12/7 C (3) maximum and minimum operating pressure refer to activation of the pressure switches (4) Sound power based on measurements performed in accordance with ISO 9614 and Eurovent 8/1 Performance in accordance with EN 14511:2013 BRAT2 - BRAN2 EN 15

16 OPERATING LIMITS U Outside air temperature [ C] COOLING OPERATION WITH WATER-GLYCOL MIX Water outlet temperature at evaporator [ C] Operating range in COOLING Water temperature head min-max= 3-8 K Water circuit pressure min-max= 1-3 bars Max storage temperature= 63 C Maximum percentage of glycol= 40% As standard, the unit is manufactured with operating parameters allowing water produced at the evaporator down to +5 C. If needing to produce water down to -10 C, contact technical service. 60 HEATING Water outlet temperature at condenser [ C] Outside air temperature [ C] Operating range in heating Water temperature head min-max= 4-10 K Water circuit pressure min-max= 1-3 bars Maximum water temperature at system heat exchanger water inlet +50 C Max storage temperature= 63 C Maximum percentage of glycol= 40% 16 BRAT2 - BRAN2 EN

17 PRESSURE DROP AND PRESSURE HEAD AVAILABLE TO SYSTEM U SYSTEM HEAT EXCHANGER PRESSURE DROP, UNIT WITHOUT HYDRONIC KIT Pressure drop [kpa] System heat exchanger pressure drop Water flow-rate [m 3 /h] Pressure drop [kpa] System heat exchanger pressure drop Water flow-rate [m 3 /h] AVAILABLE PRESSURE HEAD, UNIT WITH HYDRONIC KIT Available pressure head [kpa] Available pressure head Water flow-rate [m 3 /h] BRAT2 - BRAN2 EN 17

18 PRESSURE DROP AND PRESSURE HEAD AVAILABLE TO SYSTEM U AVAILABLE PRESSURE HEAD, UNIT WITH HYDRONIC KIT Available pressure head [kpa] Available pressure head Water flow-rate [m 3 /h] Available pressure head [kpa] Available pressure head Water flow-rate [m 3 /h] The pressure head refers to the value available to the system. The pump installed on the unit, if the hydronic kit option is purchased as an accessory, is a circulator pump with built-in inverter, including water pressure transducer and microprocessor to manage the following control modes adjustment: The type of control can be set using the selector on the pump body. As standard, the type of control is set to CON- STANT ΔP. CONSTANT ΔP: the pressure differential between pump suction and discharge is kept constant, pump speed decreases progressively when the terminals close. VARIABLE ΔP: the pressure differential reduces as flowrate decreases, to account for the lower pressure drop along the piping running to the terminals (recommended for long sections of piping) VARIABLE ΔP CONSTANT ΔP (standard setting) 18 BRAT2 - BRAN2 EN

19 CHECKING AND STARTING UP THE UNIT PREPARING FOR FIRST START UP or restarting after shutting down for long periods. The unit must be started up for the first time by the Technical Service. Before starting up the units, make sure that: - All safety conditions have been respected; - The unit is adequately fixed to the surface it rests on; - Clearances have been respected - Water connections have been carried out as indicated in the instruction manual; - The water circuit is filled and vented. - The water valves are open; - Electrical connections have been carried out correctly - Voltage is within a tolerance of 10% of the rated voltage for the unit; - The unit is correctly earthed; - All electrical connections are tight and all water connections have been carried out correctly. The unit must be started up for the first time with standard settings. Set Point values may be modified only after testing has been completed. Before starting up, power up the unit for at least two hours by switching QF1 and QS1 ON (see "wiring diagram" and the control panel in standby) so as to allow the oil in the compressor sump to heat up. STARTING UP FOR THE FIRST TIME (after two hours) ON OFF Before starting the chiller: - Make sure the switch QF1 is in the OFF position. - Make sure the contact of the on/off device SA1 (see the wiring diagram) is open (if featured). - Close the door of the electrical panel. ON - Move the main unit switch QS1 to the ON position. OFF - Move the switch QF1 (outside the unit) to ON. - The icon with the off symbol ( ) lights up on the control panel, indicating power is connected. For the position of internal components, see the diagrams. A ACTIVATING AND DEACTIVATING THE UNIT ON OFF - Move the contact on the on/off device SA1 (if featured) to ON. During this phase, if the following indications appear on the display, follow the instructions: - ER20 check the water flow-rate and the connection of the flow switch. - ER01 (three-phase heat pumps only): check the power supply connection and if necessary reverse two phases. At every change of season, make sure the operating conditions fall within the limits specified. Make sure the current input of the compressor is less than the maximum shown in the table of technical specifications. Make sure the voltage is within the established limits and that, for three phase units, the unbalance between the phases is less than 2%. Check that the cover is closed again following the setting procedure To access the control panel, open the door: - remove the screw 1; - press the points 2 simultaneously and lift the door 3. esc set BRAT2 - BRAN2 EN 19

20 LEDS AND DISPLAY A 1 2 esc set 3 1 STATUS AND OPERATING MODE LEDS 2 VALUE AND UNIT OF MEASURE LEDS Alarm Heating Cooling Standby Clock Degrees centigrade Pressure (Bar) Menu (ABC) Defrost 3 UTILITY LEDS Compressor Fans System pump Frost protection heater system heat exchanger 20 BRAT2 - BRAN2 EN

21 SETTING THE CLOCK The HSW15 controller is fitted with a clock for managing time bands to control specific events. Follow the procedure shown below to set the hours, minutes and date. To set the clock of the unit, starting from the main display, press the set button. Pressing the set button once displays the various directories. Scroll the menu using the UP and DOWN buttons until reaching the directory CL. To enter menu CL press the set button. Once having entered this menu, HOUr will be shown. Select whether to set the time, date or year using the UP and DOWN buttons. Once having decided which value to set, press the [set]** button to enter the corresponding menu. **pressed and held for 3 around seconds. To set the time, date and year simply scroll with the UP and DOWN buttons until the desired value and BRAT2 - BRAN2 EN 21

22 ... press the set button. To exit the clock setting menu press the esc button until returning to the main display. 22 BRAT2 - BRAN2 EN

23 SCHEDULER SETTING The HSW15 controller can manage the unit based o the time and the day of the week. The controller features four time bands in three profiles that can be combined, when programming, with the days of the week. The profile defines the behaviour of the unit over a 24 hour period. Time band management must be enabled by parameter te00 = 1 (te00 = 0 standard setting). Programming example 1) Define the profile for each time band, as shown in the following table. Description Description Profile 1 Profile 2 Profile 3 Hour / Minutes hours 00 (te10=0) / min.00 (te11=0) hours 00 (te38=0) / min.00 (te39=0) te66..te67 Operating mode ON/Standby ON (te12=0) ON (te40=0) te68 TIME BAND 1 Cool set point te13=15 te42=15 te69 Heat set point te14=30 te42=30 te70 DHW set point te15=50 te43=50 te71 Hour / Minutes hours 6 (te17=6) / min.00 (te18=0) hours 7 (te45=6) / min.00 (te46=0) te73..te74 Operating mode ON/Standby ON (te19=0) ON (te47=0) te75 TIME BAND 2 Cool set point te20=12 te48=12 te76 Heat set point te21=33 te49=33 te77 DHW set point te22=45 te50=45 te78 Hour / Minutes hours 9 (te24=9) / min.00 (te25=0) hours 7 (te52=12) / min.00 (te53=0) te80..te81 Operating mode ON/Standby ON (te26=0) ON (te54=0) te82 TIME BAND 3 Cool set point te27=15 te55=12 te83 Heat set point te28=30 te56=33 te84 DHW set point te29=50 te57=45 te85 Hour / Minutes hours 17 (te31=17) / min.00 (te32=0) hours 17 (te59=17) / min.00 (te60=0) te87..te88 Operating mode ON/Standby ON (te33=0) ON (te61=0) te89 TIME BAND 4 Cool set point te34=12 te62=12 te90 Heat set point te35=33 te63=33 te91 DHW set point te36=45 te64=45 te92 Example of profile 1 to be used on opening days Example of profile 2 to be used on closing days 2) Associate one of the three programmed profiles with each day of the week. The days of the week are identified by the parameters te01 to te07; te01 = Monday, te02= Tuesday te07=sunday. Once having displayed the day of the week, te01 to te07, select the value 1, 2 or 3 corresponding to Profile 1, Profile 2 and Profile 3 respectively. Follow the operations shown below to program the profiles and combine them with the day of the week: To access directory te from the main display, press esc and set together. [esc+set]. Pressing these two buttons enters the menu with the list of directories. Use the up and down buttons to scroll to the directory PAr. Press the set button and use the up and down buttons to scroll to the directory te. Press the set button to display the first parameter, te00. Use the up and down buttons to scroll to the other parameters. To set the selected parameter, press the set button and enter the value using the up and down buttons. Confirm the changes by pressing the set button or alternatively cancel by pressing esc. BRAT2 - BRAN2 EN 23

24 SELECTING THE OPERATING MODE There are three different modes: Standby mode (StbY) Cooling mode (COOL) Heating only mode (HEAT) SETTING THE SET POINTS As an example, the Set Point in COOL mode will be changed from 12.0 degrees centigrade to 12.5 degrees centigrade. For example, to switch operation from StbY to COOL. To change the operating mode, press and hold the mode button for at least 2 seconds. To change the set point, starting from the main display, press the set button. Pressing the set button once displays the various directories. Scroll the menu using the up and down buttons until reaching the SP directory. A scroll menu will start flashing with the values StbY (standby) and COOL (cool). Use the up and down buttons to select the desired operating mode. To enter the SP directory press the set button. The unit will automatically return to the main display and the Stby LED, previously on, will now be off and the COOL LED will be on. The active mode will be displayed (COOL). Taking the example of changing the set point for the operating mode. Press the SET button. 24 BRAT2 - BRAN2 EN

25 SETTING THE PARAMETERS Accessing the PASS directory (from the main display, pressing the esc and set buttons together [esc+set] and scrolling to the directory with up / down) and setting the PASS accesses the parameters visible for the password entered. The instrument will display the current set point (in this case 12.0 degrees centigrade). To increase or decrease the value, use the up and down buttons. For example, to change the set point to 12.5 degrees, press the up button until the desired value is displayed. To access the PASS directory from the main display, press esc and set together [esc+set]. Once having reached the desired set point, press the set button. In this way, the instrument will save the value Pressing the two buttons accesses the menu listing the directories. Scroll using the up and down buttons to the PASS directory. To return to the main display, press esc or wait for the menu timeout to expire (15 seconds). To enter the PASS directory press the set button. Then enter the password (installer or manufacturer), press set and exit. Access the parameters to display or change the values. Press the up and down buttons to select the Par submenu. Press the set button to display the desired directory. BRAT2 - BRAN2 EN 25

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB T_SMT_0609_GB 4,9 49,5 kw Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans INDEX SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 CE CONFORMITY... 3 WORKING

More information

INSTALLATION - OPERATION - SERVICE MANUAL TELECOM-RANGE. Split unit HED-HCAT

INSTALLATION - OPERATION - SERVICE MANUAL TELECOM-RANGE. Split unit HED-HCAT INSTALLATION - OPERATION - SERVICE MANUAL TELECOM-RANGE EN Split unit HED-HCAT 0011 0061 INDEX General warnings 4 Fundamental safety rules 4 Identification HED unit 5 Receiving and handling HED unit 5

More information

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION ECO-FRIENDLY REFRIGERANT GAS INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the result of many years

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running Climaveneta Technical Bulletin BRH_0011_0121_201211_EN BRH r HFC R-410A 0011-0121 5,5-35,1 kw Water-cooled liquid chillers (The photo of the unit is indicative and may change depending on the model) Versatile

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available May 2006 10 12 167 - GB - 00 MARKING

More information

ELFOEnergy Duct Inverter

ELFOEnergy Duct Inverter Technical Bulletin BT14E002GB-02(EC1) ELFOEnergy Duct Inverter Air-water ductable liquid chiller for indoor or outdoor installation SERIES WSA-XIN 21-141 Nominal cooling capacity (A35/W7) da 4 a 31 kw

More information

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N E S A RE F R E IG RA N T G TECHNICAL MANUAL -FRIEND Y CONDENSING UNITS FOR OUTDOOR INSTALLATION O L CMA C 2 The manufacturer declines all the responsabilities regarding inaccuracies contained in this manual,

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw CHGV 50 CHGV 64 CHGV 72 CHGV 80 PHRV heat pump model also available November 2007 10 12 167 - GB -

More information

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw TECHNICAL INSTRUCTIONS CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw CHGV 22 CHGV 2 CHGV 32 CHGV 40 PHRV heat pump model also available September 2007 10 12 11 - GB - 02

More information

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation Air-Cooled Liquid Chillers www.eurovent-certification.com www.certiflash.com Quality Management Systems 0RB 008-05 Nominal cooling capacity 8- The new generation of Aquasnap liquid chillers was designed

More information

HYDRONIC RESIDENTIAL

HYDRONIC RESIDENTIAL HYDRONIC RESIDENTIAL Chillers, reversible heat pumps and modular units for small and medium applications. Climaveneta. brand of Mitsubishi Electric Hydronics & IT Cooling Systems, presents the mini chiller

More information

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE TEcHnIcal InsTRucTIons PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE PHRIE 095 PHRIE 1 PHIE 095 PHIE 1 PHRIE 155 PHRIE 157 PHRIE 175 PHRIE 177 PHRIE 195 PHRIE 197 PHRIE 7 PHRIE

More information

CRIMSON & CRIMSON MAX

CRIMSON & CRIMSON MAX High efficiency water/water and geothermal heat pumps 5 114 General High efficiency water/water and geothermal heat pumps. Ideal for heating, cooling and production of domestic hotwater with total or partial

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient PRODUCT SELECTION DATA Easy and fast installation Compact, reliable and efficient Class A variable speed circulator available Air-Cooled Liquid Chillers 0RB 008-015 CARRIER participates in the ECP programme

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

Air-to-water scroll chillers

Air-to-water scroll chillers Air-to-water scroll chillers Model CGA 040 to 115 Cooling capacity: 14-40 kw CG-PRC031B-GB Table of Contents Technical specifications...4 Standard configuration... 4 Hydraulic version... 4 Casing... 4

More information

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB R407C EASY_R Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans 5,2 41,5 kw T_ESY_R_0508_GB EASY_R R407C INDEX WORKING LIMITS... 3 SERIES IDENTIFICATION... 4 MODEL

More information

Water chillers water/water type SIGMA Technical information manual

Water chillers water/water type SIGMA Technical information manual Water chillers water/water type SIGMA Technical information manual 2 INDEX Technical features 1 Versions 3 Accessory versions 4 Technical data 7 Electrical data 11 Cooling capacity 12 Heating capacity

More information

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017 Zeta Rev LN HP 10.2 Configured unit accessories 1PS - One user-side pump with tank LN - Low noise RG - Condensation control with fan speed regulator CSP - Set point compensation depending on external air

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw Multifunction chillers for indoor installation. Cooling Capacity: 22 222 Heating Capacity: 25 236 Scroll compressors EC Plug Fans Plate type heat exchangers EER up to 3,12 COP up to 3,84 ESEER up to 4,01

More information

ELFOEnergy Extended Inverter

ELFOEnergy Extended Inverter Technical Bulletin BT14F009GB-03 ELFOEnergy Extended Inverter AIR-COOLED INVERTER CHILLER FOR OUTDOOR INSTALLATION WSAT-XIN 21-171 RANGE PREMIUM Version Nominal cooling capacity (A35/W7) from 4 to 30 kw

More information

Blue Box Epsilon Echos +

Blue Box Epsilon Echos + Blue Box Epsilon Echos + 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Packaged version in 5 sizes Nominal cooling capacity (A35;W7): 6 26 kw Nominal heating

More information

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers Self-adjusting electronic control Cooling capacity: 35 to 700 kw 410A Cooling Operation DYNACIAT - DYNACIAT POWER

More information

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw

CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw TECHNICAL INSTRUCTIONS CHG AIR COOLED WATER CHILLER WITH CONDENSATION BY HELICOIDAL AIR 8 to 17 kw CHG 1 CHG 1 8. kw. kw.7 kw 1. kw April 7 19 - GB - 2 MARKING This product marked conforms to the essential

More information

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW

PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER 9 to 18 KW TECHNICAL INSTRUCTIONS PHRT HEAT PUMP WITH HYDRAULIC EQUIPMENT AIR / WATER to KW PHRT PHRT PHRT PHRT For terminal units and boiler overhaul applications Heating Cooling PHRT.00 kw -. kw PHRT.0 kw /.0 kw

More information

kw COOLING kw HEATING

kw COOLING kw HEATING Heat pump water/water liquid chillers for indoor installation. Inversion on hydraulic circuit. 394 1505 kw COOLING 477 1976 kw HEATING technicalcatalogue T_FRGSCRWP_0913_GB INDEX GENERAL CHARACTERISTICS...

More information

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS Total heat recovery multi-purpose units LCP Outdoor monobloc air-water unit LCP - kw Heating, cooling, domestic hot water one single system to meet all kinds of needs. Total heat recovery multi-purpose

More information

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA OWNER S MANUAL Vintage Classic HEAT COOL models Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support 888-475-7443 Manufacturing High Quality, High Efficiency Heat Pump

More information

PYXIS U PYXIS U. rcgroupairconditioning

PYXIS U PYXIS U. rcgroupairconditioning Industrial : Packaged air cooled liquid chillers for outdoor installation equipped with scroll compressors and microchannel condensing coils Cooling capacity: 44 284 rcgroupairconditioning MIN FETURES

More information

HYDROCIAT LW R407C. Water cooled chillers USE RANGE

HYDROCIAT LW R407C. Water cooled chillers USE RANGE Screw compressors CIAT dry direct expansion shell and tubes evaporator HPS equipment (High Power System) cooling or heating Heat recovery ENVIRONMENTALLY HFC R407C PROTECTION DE FRIENDLY L'ENVIRONNEMENT

More information

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS Energy saving thanks to a total recovery p Cooling Heating/DHW h Galletti multi-purpose heat pumps are total recovery units used for a simultaneous hot and

More information

Installation and Operation Manual IDRA PLUS DS. Solar Solar storage cylinder. Installation and Operation Manual

Installation and Operation Manual IDRA PLUS DS. Solar Solar storage cylinder. Installation and Operation Manual Installation and Operation Manual IDRA PLUS DS Solar Solar storage cylinder EN Installation and Operation Manual GENERAL INFORMATION This - comprises pages. Rev. manual, Code ENGLISH General information

More information

RMA AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

RMA AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL RMA ECO-FRIENDLY REFRIGERANT GAS AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL Dear Customer, Thank you for having purchased a FERROLI product. It is the

More information

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 46 Above picture is only indicative and is not binding AIR FC The packaged air cooled chillers of RAS Kp series are suitable

More information

Modular Air-cooled Chillers

Modular Air-cooled Chillers Modular Air-cooled Chillers High Seasonal Efficiency (HSE) version Cooling capacity 48-232 kw Trane Flex Series Modular air/water chillers with axial EC fans, inverter driven scroll compressors and microchannel

More information

Galletti Water chillers and heat pumps catalogue

Galletti   Water chillers and heat pumps catalogue Galletti www.galletti.it Water chillers and heat pumps catalogue Table of Contents/SMALL SYSTEMS MPI DC Water chillers and heat pumps with inverter compressor 6 models page 6 MCE MPE Air condensed water

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw COMFORT CHILLERS AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw climaveneta.com COMFORT CHILLERS PERFECT COMFORT AND MAXIMUM EFFICIENCY Air-cooled liquid chiller for outside installation

More information

USER AND MAINTENANCE MANUAL

USER AND MAINTENANCE MANUAL USER AND MAINTENANCE MANUAL Air cooled liquid chillers R410A refrigerant Cooling capacity 2.1 32.2 Tons, scroll and rotary compressors 60 Hz 1 Dear Customer, Thank you for the trust you have placed in

More information

Installation Manual. Instrucciones de instalación y manual de usuario 1

Installation Manual. Instrucciones de instalación y manual de usuario 1 Installation Manual Instrucciones de instalación y manual de usuario 1 Installation instructions and user manual V8 2 INDEX 1 GENERAL SAFETY WARNINGS... 4 2 OPERATING PRINCIPLE... 5 3 TECHNICAL FEATURES...

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

Part 1 General Information... 1 Part 2 Outdoor Unit... 4 Part 3 Installation... 45

Part 1 General Information... 1 Part 2 Outdoor Unit... 4 Part 3 Installation... 45 Contents Part 1 General Information... 1 Part 2 Outdoor Unit... 4 Part 3 Installation... 45 The specifications, designs, and information in this book are subject to change without notice for product improvement.

More information

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata EKS/HE Refrigerant R410A GWP=2.088 Scroll Compressor Shell & Tube exchanger Axial fan Brazed plate heat exchanger MultiScroll Air-cooled liquid chillers High efficiency Solution B - Base I - Integrata

More information

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100 HTD High Temperature Non-Cycling Refrigerated Compressed Air Dryers Operation & Maintenance Manual MODELS HTD 21 thru HTD 100 - TABLE OF CONTENTS - 1.0 GENERAL 2 1.1 How to use this manual 1.2 Symbols

More information

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz EN Technical Catalogue Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: 321-1308 kw 50 Hz EKV/BS business Air cooled water chillers for outdoor installation. Flexibility in the

More information

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw COMFORT HEAT PUMPS AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw climaveneta.com COMFORT HEAT PUMPS PERFECT COMFORT AND MAXIMUM EFFICIENCY Air to water heat pump for outdoor installation,

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

AGEO CALEO. Water-to-water high temperature heat pumps USE RANGE DESCRIPTION. Designed to replace a conventional boiler and produce domestic hot water

AGEO CALEO. Water-to-water high temperature heat pumps USE RANGE DESCRIPTION. Designed to replace a conventional boiler and produce domestic hot water Designed to replace a conventional boiler and produce domestic hot water Heating capacity : 16 to 25 Heating Hydraulic module ENVIRONMENTALLY HFC R4A PROTECTION DE FRIENDLY L'ENVIRONNEMENT USE CIAT is

More information

Air-cooled chillers with single-screw compressor. Installation, operation and maintenance manual D - KIMAC EN. Original Instructions

Air-cooled chillers with single-screw compressor. Installation, operation and maintenance manual D - KIMAC EN. Original Instructions Installation, operation and maintenance manual D - KIMAC00611-09EN Air-cooled chillers with single-screw compressor EWAD650-C17 C-SS EWAD650-C17 C-SL EWAD620-C16 C-SR EWAD760-C19 C-XS EWAD760-C19 C-XL

More information

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS Indoor motor-driven evaporating units LER 0-0 kw Compact and silent machines with remote dissipation into the air Scroll compressor PLUS R-0A R-0A refrigerant Cooling only Split version Electronic expansion

More information

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual u Air-to-Water Reverse Cycle Heat Pumps AQH 40 to 130 40 to 131 kw 45 to 141 kw Engineering Data Manual EDM AQH-W.3GB Date : November 2007 Supersedes : TM AQH-W.2GB/03.04 Specifications The Aqu@Logic air-to-water

More information

AWR-MTD2-XE INSTALLATION - OPERATING - SERVICE MANUAL

AWR-MTD2-XE INSTALLATION - OPERATING - SERVICE MANUAL INSTLLTION - OPERTING - SERVICE MNUL EN Reverse-cycle air/water heat pumps with domestic hot water production, axial-flow fans and water pump assembly WR-MTD-XE 9 INDEX U I U I General warnings 3 Checking

More information

TCHE-THHE TCEE

TCHE-THHE TCEE K11206-GB ed. 6 TCHE-THHE 155 2130 TCEE 155 2130 Q-Flow range Macrosystem 50,2 124,5 kw TCHE-THHE - Water cooled water chillers and heat pumps units with environmentally friendly refrigerant. Range with

More information

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED EQV R-407C WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED Size Cooling Heating [kw] [kw] 5 1,9 2,2 7 2,4 2,5 9 2,6 2,5 15 3,3 3,2 17 3,7 3,7 REPLACE: BT02E008GB-01 The Versatemp EQV units

More information

ELFOEnergy Extended Inverter

ELFOEnergy Extended Inverter Technical Bulletin BT14F008GB-00 ELFOEnergy Extended Inverter Air cooled inverter heat pump for outdoor installation WSAN-XIN 21-171 RANGE PREMIUM Version Nominal heating capacity (A7/W45) from 5 to 32

More information

REMOTE CONTROL FOR CHILLER MYCHILLER

REMOTE CONTROL FOR CHILLER MYCHILLER REMOTE CONTROL FOR CHILLER MYCHILLER GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD... 5 BOARD CONFIGURATION... 7 LIST OF MAIN PARAMETERS... 7 CONFIGURATION OF MAIN

More information

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS RAE 1352 F.K + MV AIR R-407C FC Series RAE... F.K Cooling capacity from 77 to 289 kw - 2 circuits The air cooled chillers of RAE... F.K series, are designed for outdoor installation and are particularly

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 1402 C O K AIR R-407C Series RAE... C K Cooling capacity from 81 to 250 kw - 2 circuits The air cooled chillers of RAE C K series, with centrifugal fans, are designed for indoor installation and are

More information

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES COOLING CAPACITY FROM 76 TO 612 Kw 1 AND 2 COOLING CIRCUITS RAE 1702 F Kc + P2 28 Above picture is only indicative

More information

PRODUCT GUIDE

PRODUCT GUIDE PRODUCT GUIDE 01.2017 Cooling Heating CHAPTER 1 AIRCOOLED LIQUID CHILLERS AND HEAT PUMPS FOR RESIDENTIAL & LIGHT COMMERCIAL APPLICATION Power (kw) Page IACAK/II/WP 101.5 106 0 58 115 A CLASS energy efficiency

More information

Planning guide. Atec.

Planning guide. Atec. www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.

More information

WHE 2.24 / WHE 2.24 FF

WHE 2.24 / WHE 2.24 FF EN Wall-hung gas boilers WHE 2.24 WHE 2.24 FF User Guide 300011777-001-C . Contents 1 Introduction.............................................................................3 1.1 Symbols used...........................................................................................3

More information

PURESTREAM. ACW Air Cooled Fluid Cooler User and Maintenance Manual AMBIENT FLUID COOLER BY FRIULAIR

PURESTREAM. ACW Air Cooled Fluid Cooler User and Maintenance Manual AMBIENT FLUID COOLER BY FRIULAIR PURESTREAM AMBIENT FLUID COOLER BY FRIULAIR ACW Air Cooled Fluid Cooler User and Maintenance Manual Dear Customer, Please read this manual carefully in order to obtain the best performance from our products.in

More information

TCHE-THHE TCEE

TCHE-THHE TCEE K11208-GB ed. 3 TCHE-THHE TCEE Q-Flow range Macrosystem 148,4 262,2 kw TCHE-THHE - Water cooled water chillers and heat pumps units with environmentally friendly refrigerant. Range with hermetic Scroll

More information

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw PROCESS CHILLERS AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw climaveneta.com PROCESS CHILLERS MAXIMUM EFFICIENCY IN EVERY TYPE OF PROCESS APPLICATION Air cooled liquid chiller for outdoor

More information

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA. OWNER S MANUAL Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750 Proudly Made in the USA support@aquacomfort.com 888-475-7443 Manufacturing High Quality, High Efficiency Heat

More information

44,9 202,0 kw. technicalcatalogue

44,9 202,0 kw. technicalcatalogue Packaged air cooled liquid chillers for outdoor installation equipped with scroll compressor and microchannel condensing coils 44,9 202,0 kw technicalcatalogue T_PYXU_0413_GB INDEX EUROVENT CERTIFICATION...

More information

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS RAE 201 C K RAE 482 C K AIR R-407C Series RAE... C K from 19 to 83 kw - 1 and 2 circuits The air cooled chillers of RAE... C K series, with centrifugal fans, are designed for indoor installation and are

More information

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY Easy and fast installation Hydronic module available Compact, reliable and efficient Nominal cooling capacity : 8-40 kw Nominal heating capacity : 17-40 kw 50 410A Cooling or heating USE The air-to-water

More information

Section 1. Information before installation

Section 1. Information before installation 2 3 Section 1. Information before installation 1.1 General delivery conditions All equipment, even carriage and packaging paid, is shipped at the recipient s risk. If damaged caused during transport is

More information

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps.

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps. Air/water cooled chillers and heat pumps 41 303 kw General BETA ECHOS is a range of chillers and ductable air-water heat pumps. Configurations HP: Reversible heat pump LE: For connection to remote evaporator

More information

MPE 4-76 kw. Outdoor monobloc unit. Air chillers and heat pumps MPE PLUS. Efficiency under all operating conditions. 152 galletti.

MPE 4-76 kw. Outdoor monobloc unit. Air chillers and heat pumps MPE PLUS. Efficiency under all operating conditions. 152 galletti. Air chillers and heat pumps MPE Outdoor monobloc unit MPE - kw Efficiency under all operating conditions Rotary compressor PLUS Scroll compressor R-0A R-0A refrigerant Cooling only Cooling / Heating Monobloc

More information

i-kir2 MTD 0011m 0061m INSTALLATION - USER - MAINTENANCE MANUAL

i-kir2 MTD 0011m 0061m INSTALLATION - USER - MAINTENANCE MANUAL INSTLLTION - USER - MINTENNCE MNUL EN i-kir2 MTD reverse-cycle air/water heat pump with DC inverter-driven compressors, domestic hot water production, axial-flow fans and hydronic unit for outdoor installation

More information

Operating instructions Page 14. Refrigerator Read the operating instructions before switching on for the first time

Operating instructions Page 14. Refrigerator Read the operating instructions before switching on for the first time Operating instructions Page 14 Refrigerator Read the operating instructions before switching on for the first time 7085 039-00 LKv 5710 Content Disposal notes... 14 Description of the appliance... 14 Safety

More information

TTV 4500 / TTV 4500 HP / TTV 7000

TTV 4500 / TTV 4500 HP / TTV 7000 TTV 4500 / TTV 4500 HP / TTV 7000 EN OPERATING MANUAL AXIAL FAN TRT-BA-TTV4500-4500HP-7000-TC-003-EN Table of contents The current version of the operating manual can be found at: Notes regarding the operating

More information

Contents. Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79

Contents. Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79 MCAC-TSM-2008-02 Contents Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79 Contents i MCAC-TSM-2008-02 Introduction Introduction Midea Mini Unitary

More information

SWIMMING POOL HEAT PUMP Owners Manual

SWIMMING POOL HEAT PUMP Owners Manual SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 5.6kW 9.5kW and 12.5kW models only. The heat pump unit is sold with a 2 year warranty on all components. Please contact your supplying dealer

More information

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA OWNER S MANUAL Models: AC110, AC125, AC150 made from 2003 through 2010 Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support/ (888) 475-7443 Manufacturing High Quality,

More information

LZT High efficiency air to water heat pumps with E.V.I. compressors

LZT High efficiency air to water heat pumps with E.V.I. compressors High efficiency air to water heat pumps with E.V.I. compressors -20 C +43 C +65 C E.V.I. C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating

More information

KELVIN Clim F497. Kelvin air conditioning

KELVIN Clim F497. Kelvin air conditioning KELVIN Clim F497 Cooling Capacity: 400 ~ 1260 kw Free-Cooling Capacity: 497 ~ 1492 kw Packaged air cooled liquid chillers with free-cooling system in A class energy efficiency for outdoor installation,

More information

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors infolinia: +48 691 262 691-15 C +63 C +43 C E.V.I. HP The series of high efficiency heat pumps has been specifically designed for use with

More information

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB Packaged air cooled liquid chillers for outdoor installation 42 574 kw technicalcatalogue T_EGL_1012_GB INDEX EUROVENT CERTIFICATION... 3 GENERAL CHARACTERISTICS... 3 SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION...

More information

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning : Packaged air cooled liquid chillers with free-cooling system for outdoor installation, equipped with screw compressors and axial fans Cooling Capacity: 314 1343 Free-Cooling Capacity: 308 938 GLYCOL

More information

Water-cooled screw chillers. Installation, Operation and Maintenance Manual D EIMWC EN. Original Instructions

Water-cooled screw chillers. Installation, Operation and Maintenance Manual D EIMWC EN. Original Instructions Installation, Operation and Maintenance Manual D EIMWC00404-14EN Water-cooled screw chillers EWWD 340 C18 I-SS EWWD 360 C12 I-XS EWLD 320 C17 I-SS 50Hz Refrigerant: R-134a Original Instructions Contents

More information

ELFOEnergy SHEEN. Technical Bulletin. Air source inverter heat pump for outdoor installation. WSAN-XSi RANGE HIGH SEASONAL EFFICIENCY

ELFOEnergy SHEEN. Technical Bulletin. Air source inverter heat pump for outdoor installation. WSAN-XSi RANGE HIGH SEASONAL EFFICIENCY Technical Bulletin BT17I022GB-00 ELFOEnergy SHEEN Air source inverter heat pump for outdoor installation WSAN-XSi 10.1 22.2 RANGE Nominal heating capacity (A7/W45) from 23,3 to 61 kw Nominal cooling capacity

More information

LAB 07M LAB 09M LAB 11M

LAB 07M LAB 09M LAB 11M LAB 07M LAB 09M LAB 11M Installation and Operating Instructions Air-to-Water Heat Pump for Outdoor Installation FD 8910 Table of contents 1 Warnings regarding the documentation... EN-3 1.1 Use in compliance

More information

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Modular Standard HP Chiller 1/4 screw compressor with Carel driver Program for pco¹ pco 2 and pcoc Modular Standard HP Chiller 1/4 screw compressor with Carel driver Manual version 1.0 25 September 2003 Program code: FLSTDmMSDE Do we want you to save you time and money?

More information

Aqua Mini Full DC Inverter Unitary Chiller 50Hz. Content

Aqua Mini Full DC Inverter Unitary Chiller 50Hz. Content MCAC-ATSM-2014-09 Content 1. Outdoor units lineup... 2 2. Nomenclature... 3 3.Features... 4 4. Description of main components... 8 5. Specifications... 10 6. Dimensions... 14 7. Piping Diagram... 15 8.

More information

Installation instructions Danfoss heat pump DHP-R

Installation instructions Danfoss heat pump DHP-R Installation instructions Danfoss heat pump DHP-R Table of contents DHP-R 1 Important information........................................................... 5 1.1 Refrigerant...5 1.2 Noise and vibrations...5

More information

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A10

INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A10 Code 00773 04 Edit. 03/0 INSTRUCTION AND MAINTENANCE MANUAL DRYERS A5 - A6 - A7 - A7,5 - A8 - A9 - A0 READ THIS MANUAL CAREFULLY BEFORE CARRYING OUT ANY OPERATIONS ON THE DRYER. Cod. 00773 04 - Edition

More information

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10 Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW Compressors Scroll Serie: Series: Emissione: Issue: SCAEY Catalogo: Leaflet: Sostituisce: Supersedes: DE 88 04/11 12/10 Index

More information

kw. technicalcatalogue

kw. technicalcatalogue Packaged air cooled liquid chillers in A class energy efficiency for outdoor installation equipped with scroll compressor and microchannel condensing coils 108 876 kw technicalcatalogue T_PYXCLA_0413_GB

More information

ELFOEnergy Ground. Technical Bulletin. Water cooled heat pump for indoors installation WSHN-EE RANGE

ELFOEnergy Ground. Technical Bulletin. Water cooled heat pump for indoors installation WSHN-EE RANGE Technical Bulletin BT06C002GB-11 ELFOEnergy Ground Water cooled heat pump for indoors installation WSHN-EE 17-121 RANGE Nominal heating capacity (W10/W45) from 6,68 kw to 38,7 kw Nominal cooling capacity

More information

pyxis cla pyxis cla A-CLASS NEW rcgroupairconditioning

pyxis cla pyxis cla A-CLASS NEW rcgroupairconditioning Industrial PYXIS CL: Packaged air cooled liquid chillers in class energy efficiency for outdoor installation, equipped with scroll compressor and microchannel condensing coils Cooling Capacity: 108 876

More information

1. Information before installation General terms of delivery, storage and transport

1. Information before installation General terms of delivery, storage and transport EN Read this manual carefully before installing, maintaining or repairing this device! The symbol indicates important information that must be taken into account in order to avoid risk of personal injury

More information

GLIDER EVO CLA GLIDER EVO CLA HIGHEFFICIENCY ACLASS. rcgroupairconditioning

GLIDER EVO CLA GLIDER EVO CLA HIGHEFFICIENCY ACLASS. rcgroupairconditioning GLIDER EVO CL GLIDER EVO CL: Packaged air cooled liquid chillers in class energy efficiency for outdoor installation, equipped with screw compressors and axial fans Cooling Capacity: 282 1513 HIGHEFFICIENCY

More information