CASE STUDIES OF HIGH HUMIDITY PROBLEMS IN HOT AND HUMID CLIMATES IN THE UNITED STATES

Size: px
Start display at page:

Download "CASE STUDIES OF HIGH HUMIDITY PROBLEMS IN HOT AND HUMID CLIMATES IN THE UNITED STATES"

Transcription

1 CASE STUDIES OF HIGH HUMIDITY PROBLEMS IN HOT AND HUMID CLIMATES IN THE UNITED STATES D Turner *, P.E., Ph.D., S Deng, P.E., GH Wei, P.E. and D Claridge, P.E., Ph.D. Energy Systems Laboratory, Texas A&M University System, College Station, Texas ABSTRACT Maintenance of acceptable indoor air quality is a challenging problem in the hot and humid areas of the world. High humidity or the intrusion of water into the building can result in mold growth for a number of reasons, including poor building design, bad mechanical systems, poor construction, maintenance problems, or improper building occupant behavior. The Energy Systems Laboratory at Texas A&M University, College Station, Texas, has developed a process called Continuous Commissioning 1, (CC) 1, which improves building energy efficiency through optimization of the HVAC and controls systems. In the process of commissioning different buildings we have encountered many different mold problems, some of which have been so severe that the occupants had to be removed from the building. This paper discusses some of those problems encountered, the resolution of the problem (if found) and groups the case studies into design problems, poor maintenance, construction issues, retrofit applications, and tenant behavior. In many instances where poor indoor quality conditions exist, it is not a single problem that is found; rather it is a combination of several problems. Specific examples are given from our experiences. INTRODUCTION Over the last fifteen years it has become apparent that moisture and humidity control problems exist in buildings. The causes of these problems can be complex and involve many aspects of building design, construction and maintenance (Harriman 2001). Improper humidity control inside a building can lead to occupant discomfort, people feeling sick, building deterioration, and the development of mold, mildew or odors. At Texas A&M University the Energy Systems Laboratory has been called upon to solve many humidity problems. The group has worked on all types of buildings including dormitories, office buildings, laboratories, hospitals, and auditoriums. Several of the buildings have experienced the existence of not only high levels of humidity but also mold. Mold in buildings is a serious problem since previous studies indicate that it can lead to or aggravate health problems including headaches, breathing difficulties, allergic reactions, and aggravation of asthma systems (United States Environmental Protection Agency, 2001). Many of the problems leading to mold and inadequate humidity control can easily be identified and prevented. The problems will be divided into five categories, and examples will be given in each category. Since most of these buildings had experienced some type of mold growth it is also important to understand what mold is (how it acts) and most importantly how it can be prevented or eliminated. MOLD Over the last fifteen to twenty years, as building ventilation standards have changed, there has been a growing concern for mold and mold prevention. Monetary problems due to mold clean up, worker s compensation, and building restorations have become a major concern for the HVAC industry. In order to control and eliminate mold one must first know some basics about mold. Mold is a fungus. It is all over the world and it is crucial to the earth s ecosystem since it breaks down trees and other natural wastes. Mold is microscopic in size and travels through the air. Its survival is directly dependent on humidity, temperature, and limited exposure to ultraviolet light. As a result, different species of mold live in temperature ranges from just above freezing to just below the boiling point of water depending on the ideal conditions for growth of that particular mold species. In a particular place and building there could be * Corresponding author wdt5451@esl.tamu.edu 1 Continuous Commissioning and CC are registered trademarks of the Texas Engineering Experiment Station (TEES), the Texas A&M University System, College Station, Texas. 1438

2 hundreds of different species of mold. When temperature and humidity conditions change, one species of mold dies, but it may be quickly replaced or outgrown by the best suited species to take its place (Harriman, 2001; United States Environmental Protection Agency, 2001). Since mold travels through the air and most buildings do not have direct sunlight, the best way to prevent its development is to maintain adequate relative humidity levels inside a building. Penicillin mold, for example, starts to grow when relative humidity levels rise around the area of seventy-eight percent (Harriman, 2001), at which it thrives on surfaces with condensation present. Once mold has grown and can be easily identified with the human eye, it has already grown a protective layer called mycelium. This protective layer allows the surface in which the mold is growing to be kept moist. Due to this protective layer, mold is very difficult, if not impossible, to completely remove from a building once it is present. When mold is treated by ultraviolet light or toxic chemicals such as bleach, only the top layer of the mold is usually killed. If the original spore is unaffected, it will continue to live on the surface in a dormant state. Once there is additional moisture present, the mold will again reproduce and develop (Harriman, 2001; United States Environmental Protection Agency, 2001). CAUSES OF HUMIDITY PROBLEMS Humidity control has been a major concern in areas that experience warm temperature and high humidity. Excess humidity not only causes discomfort for the building s occupants but it also allows for the growth of mold in these buildings. ASHRAE standard number 62 states that an office environment should have a relative humidity in the range of 30 to 60% (ASHRAE, 1989). There are many causes for lack of humidity control in buildings. Most of these causes can be avoided if a concerted effort is made to control the relative humidity inside a building. Some of these causes can be prevented before the building is built by having adequate and proper design of the HVAC system and proper construction techniques. Other ways to prevent the lack of humidity control are proper building retrofit and proper maintenance. This paper will focus on five major categories of causes for humidity problems in buildings: Design, Construction, Retrofit Applications, Maintenance Issues, and Tenant Behavior. Category 1: HVAC Design The first of these categories, the one in which an engineer has the most control over, is HVAC design. A building should be designed properly to provide a comfortable environment for its occupants to work or live. The building should be installed with proper type of equipment to supply adequate cooling or heating. It is also crucial for a building to have a positive differential pressure to the outside atmosphere. If the building pressure is negative, the engineer will have no control as to what type of air will be drawn into the building making it impossible to control the humidity level. A paper (Chen, et al, 2004) summarizes the results of 31 case studies of buildings which have high humidity/mold problems. Approximately one-third of the problem buildings were found to have poor HVAC design. Another important factor in HVAC design is the building s location. It is necessary to take into account the position of the building with respect to wind direction, speed, and outside air humidity content. The engineer should try to minimize any direct openings to the outside to control infiltration. Case Study: Lecture Hall, University Campus A lecture hall had experienced high relative humidity levels, and mold was starting to grow on the surfaces of walls, tables, and chairs. Measurements in the room indicated temperatures near the comfortable range of F but relative humidity levels near 80%. (Chen, et al. 2000) A single-zone air handling draw-through unit configuration served the lecture hall. Of all the air handling systems, the single-zone air handling system is perhaps the simplest and most common type of system. The unit is controlled to respond to the room conditions as indicated by a room thermostat. No reheat coil was designed for this system, so dehumidified primary air or recirculated room air could not be reheated. The original design data of the AHU and the measured air condition data both indicate that the cooling capacity and supply airflow volume was adequate for the sensible load, but not the latent load. The single-zone AHU 1439

3 system with no reheat capacity originally chosen was not adequate for the space due to the lack of humidity control. Different geographic locations have different ratios of latent load to sensible load and different AHU types have different advantages. The ratio of latent load to sensible load should be considered as a criterion to design the HVAC system and select equipment for different climates (Harriman, Plager and Kosar, 1999). The engineering solution to this problem is to retrofit the AHU with a reheat capability to maintain proper humidity control. Category 2: Construction Sometimes the way a building was designed or planned is not the way it was ultimately built. Such problems can be seen in many buildings throughout Texas and elsewhere. In (Chen, et al, 2002) 37 percent of the case study buildings with humidity problems were categorized as having a construction problem. Case Studies: #1 Dormitory on College Campus A building on a campus had the distinction of being a building plagued by humidity issues. The ceilings in many of its bathrooms were weeping to the point that water was raining on the occupants. This condensation problem had no obvious cause since room humidity levels were not excessive. Removal of the lighting fixtures in one bathroom revealed that the crawl space above the bathroom was filled with very hot (90 F), very humid (95%) air that was condensing on all the surfaces with temperatures below the air s dew point. The condensate would then leak into the bathrooms below. An examination of the crawl spaces discovered numerous pathways for this humid air through large unsealed holes originally cut for piping. These gaps allowed the humid air to freely migrate from a steam tunnel to the rest of the building. Once the humid air came in contact with a cold surface, it would condense (Chen, et al, 2002). #2 Dormitory on a Military Base Although this was not a severe mold problem, this case study represents how much attention needs to be paid to small details in construction. Mold was growing on the supply air grille to the occupied space. Conditioned air at 55 F was supplied in the duct, but there were small gaps (1/4 to 1/2 ) between the end of the metal duct and the diffuser grille. This small gap allowed hot, moist attic air to come in contact with the cold supply duct and grille, and moisture condensed on the surface of the grille. This led to mold growth. Figures 1 and 2 show the small gaps between the supply duct and the ceiling. Lack of attention to even small construction details can cause problems. Figure 1. Junction of the supply air duct and the ceiling 1440

4 Figure 2. Junction of the supply air duct and the ceiling #3 - Military Hospital After about seven years of operation, severe mold problems were observed in a number of rooms. The mold was first discovered during a renovation when vinyl wallpaper was removed from a wall, and mold was found growing on the underside of the wallpaper. Further investigations showed similar growth in several locations. Energy Systems Lab engineers investigated the humidity and mold areas and found a number of problems. Figure 3. Smoke test showing negatively pressure at an electrical wall plug 1. The building had a lot of cracks in the outside walls. There were many locations where daylight could be seen through the brick walls. 2. Many rooms in the building were negatively pressurized. Figure 3 shows a smoke test at an electrical outlet. 3. Most of the severe mold was occurring on the backside of the vinyl wallpaper, around windows, or around electrical wall plugs, as shown in Figures 4 and 5. Figure 4. Mold behind the vinyl wall. 1441

5 Figure 5. Mold around windows and electrical wall plugs During the subsequent investigation, it was determined that the flow tracking stations on some of the air handling units had failed, and that there was not a correct differential between supply and return air, resulting in some areas of the building having negative pressure with respect to the outside conditions. Further, during windy days, the cracks in the outer walls allowed for greater infiltration of untreated air. With the untreated air and moisture moving into the building, the vinyl wallpaper served as a vapor barrier, and moisture was trapped on the underneath side of the wallpaper. As with the situation with many of the case studies presented herein and summarized in (Chen, et al 2004), the mold growth is not attributable to just a single cause. In this example construction problems related to the exterior wall cracks and the installation of the vinyl wallpaper were major causes of the mold problems. However, the problems were made worse by the negative pressurization caused by the air flow station failures in the air handling units. Category 3: Building Retrofits and Alterations Once a building has been in place for several years changes have to be made to it in order to better fulfill its purpose. For example, a conference room may be changed into new offices, or a classroom may be converted into a computer or server room. There are also advancements in the technology utilized in the office environment. Offices must now have fast and reliable Ethernet connections. There is also the need for additional telephone lines for fax machines and other office equipment. All this wiring has to be distributed throughout the building. In order for this to be done, electrical conduit has to be run through walls and from floor to floor. Often the breaks made in walls and ceilings are not properly sealed. In Chen, et al % of the observed humidity problems were categorized as having been caused by retrofits and alterations. Case Studies: #1 Classroom/Office Building Built in the 1980 s, construction retrofits and alterations occurred to account for the upgraded information technology equipment installed. Ethernet wiring had to be distributed throughout the building, which caused holes to be placed in walls for wiring conduit. These holes were often not sealed correctly, and they allowed for undesired air flow throughout the building. In particular, holes in walls in or near mechanical rooms, which shared a wall with one of the stairwells, allowed humid outside air to be sucked into the stairwell. This was a major factor for the growth of mold in the building. #2 Hospital Mold Problems This case study falls into all five categories, i.e., design, retrofit, construction, maintenance, and occupant behavior. However, since the humidity problems and subsequent mold problems occurred after an energy retrofit, it will be discussed within this category. After an energy retrofit, a geriatric hospital began experiencing some severe mold problems. When engineers from the Energy Systems Lab were asked to investigate the problems, excessively high humidities (> 80%) were found. There was severe mold growth in bathrooms and on many of the hospital walls. While this mold would be bad for any hospital, it was particularly bad for this facility since it largely housed elderly patients, many of whom had severe respiratory problems. 1442

6 The retrofit that had occurred was a chiller replacement, where direct expansion units had been replaced by two small chillers. The chillers supplied chilled water to outside air pre-treatment AHUs and fan coil units. There were several major problems noted in the site analysis: 1. The outside air pre-treatment units were handling nearly twice as much outside air than design, resulting in less dehumidification and discharge air temperatures in the high 60 s. 2. Chilled water supply temperatures ranged from 48 F to 51 F during the site visit. 3. Fan coil units had high discharge air temperatures, F. (Thermostats controlled chilled water valves.) 4. Neither of the chillers had isolation valves. 5. During fall and spring operation, and during summer evenings where only one chiller was used, the supply water to the hospital was blended with the return water through the off chiller. 6. The high chilled water temperatures could not dehumidify adequately during low load, high humidity conditions. 7. There were numerous unsealed penetrations in the building which allowed infiltration of untreated outside air (also caused from prior retrofits and poor maintenance). 8. The air distribution system was poor. To complicate matters even further, a decision was made by facility administrators to open all the outside air vents fully open to allow more fresh air into the building. This occupant behavior decision exacerbated the problem because too much outside air was already being admitted into the building. This case study presents an example of how bad an IAQ problem can be when there is a poor design, construction problems, maintenance issues, improper retrofit application, and bad decisions by occupants/administration. Fortunately, there was a successful ending to the story. The mold/mildew was cleaned and mitigated, isolation valves were installed on each of the chillers, and the chillers were programmed to supply 44 F water to the hospital. A Testing, Adjusting, and Balancing (TAB) firm was hired to balance the air distribution system, including bringing in the proper amount of outside air. Facility maintenance staff and the contractor worked to seal as many of the building penetrations as they could. The building was restored to an acceptable living environment. Category 4: Poor Maintenance One of the main causes of mold within buildings is poor maintenance. In many institutions, where there are a large number of buildings to maintain, regular scheduled maintenance is often delayed in order to fix new and last-minute complaints from building occupants. As a result, problems that could have been prevented begin to accumulate. In some instances problems will not be fixed until complaint calls are made to the maintenance office (Chen, et al, 2000; Chen, et al, 2004). In the Chen, et al paper, which analyzes some 31 case histories, there were some maintenance issues in 95% of the cases. This is by far the category with the highest cause for lack of humidity control and also the easiest to prevent. Case Study #1 - Dormitory Humidity Problems This dormitory had high levels of humidity inside bathrooms and bedrooms. Relative humidity levels reached the 80 percent mark and residents constantly complained about comfort. Upon careful inspection of the building, it was discovered that all the outside air grilles were partially or completely obstructed, effectively forcing the units to circulate only inside air. Exhaust fans operated continuously. As a result, the building was being operated very negative and untreated air was entering through doors, windows, and any available cracks. This problem could have easily been corrected by proper maintenance and inspection of HVAC equipment. Case Study #2 Dormitory on Campus This dorm s humidity problems could have very easily been prevented. During inspection, it was noticed that the two outside air AHUs designed to dry out the outside air and provide the building with positive pressure were off-line due to component failures. It was further noticed that the coiling coils were still active, flowing chilled water. Even with the air handling units off, air flow was detected through the units due to the negative pressure in the building. Simultaneously, untreated air was infiltrating through doors and cracks of the building. Once the hot, humid air came in contact with the cool ductwork fed by the off-line AHUs, it condensed and dripped onto the hallway below. 1443

7 Humidity control problems could easily have been prevented with proper air handling unit maintenance and inspection. Once one of the components was not working properly it should have been replaced, and the humidity problem could have been avoided. The fact that both outside air AHUs were not working points to improper maintenance. Category 5: Tenant Behavior It is important that tenants be educated to understand how their behavior impacts the HVAC system and indoor air quality. With so many buildings now being built with central HVAC systems, many windows are not operable and, therefore, cannot be opened by the occupants. However, some buildings have operable windows, and these are sometimes opened to allow fresh air into the building. There are also instances when building occupants will leave outside doors open or forget to close large delivery doors in conditioned storage areas. Wind effects will cause a positively pressurized building to become negative under high-wind conditions, but this is a transient effect. Even though buildings may be positively pressurized by the HVAC system, the systems are not designed to handle long periods of time with windows or door open. Occupants should be educated to keep windows and doors closed, especially during periods of potentially high humidity. Case Study: Military Hospital Energy Systems Laboratory engineers made a site visit to a major military hospital which was experiencing severe comfort problems. Like several of the case studies previously discussed, this case study is not just related to tenant behavior. The indoor humidity problems were caused by a poor retrofit design, poor maintenance, not enough chilled water being supplied, and tenant behavior. The occupants were sensing both high temperature (77-80 F) and high humidities (65-80%) and were naturally uncomfortable. To get some improved comfort, they were opening their windows (and sometimes leaving them open), which allowed a large, direct path of untreated air into the facility. Their behavior only made the IAQ conditions within the facility even worse. CONCLUSION Causes for lack of humidity control and the development of mold come from many different sources. They are related to every stage of a building s life from the original design to construction to retrofits to poor maintenance to uneducated tenant behavior. The existence of mold in a building is a serious concern and should be treated immediately. The easiest way to deal with the mold problem is to prevent it by having a properly designed building HVAC system and to keep it performing adequately with proper maintenance. Once mold has been identified in the building, it should be treated, the cause of the high humidity eliminated if possible, and steps should be taken to see that future problems will not reoccur. REFERENCES 1. ASHRAE, ANSI/ASHRAE , Ventilation for Acceptable Indoor Air Quality. Atlanta: American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. 2. Chen, Hui, Homer L. Bruner, Song Deng, Claridge, D. E. and Turner, Dan, 2002, Eliminating Humidity and Condensation Problems in University Dormitories Case Study, International Conference for Enhanced Building Operations, Dallas, Texas, October 15-17, Chen, Hui, Song Deng, Homer L. Bruner, Claridge, D. E., 2000, Control of Humidity with Single-Duct, Single-Zone, Constant Air Volume System A Case Study. The Proceedings of the Twelfth Symposium on Improving Building Systems in Hot and Humid Climates, San Antonio, Texas, May 15-17, 2000, pp Chen, Hui, Song Deng, Homer Bruner, and Jerry Garcia, Roots of Mold Problems and Humidity Control Measures in Institutional Buildings with Pre-Existing Mold Condition. Proceedings of Fourteenth Symposium on Improving Building Systems in Hot and Humid Climates, May 17-20, 2004, pp Harriman, L., Brundrett, G., Kittler, R., Humidity Control Design Guide for Commercial and Institutional Buildings, ASHRAE 2001, pp Harriman, III., L. G., Plager, Dean and Kosar, Douglas, 1999 Dehumidification and Cooling Loads from Ventilation Air, Journal of Energy Engineering, Vol. 96, No. 6, pp United States Environmental Protection Agency, Mold Remediation in Schools and Commercial Buildings, diation.pdf.march

Computing Services Center

Computing Services Center Continuous Commissioning Report for the Computing Services Center Building #516 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Civil Engineering Building

Civil Engineering Building Continuous Commissioning Report For the Civil Engineering Building Building 492 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Physical Plant Complex

Physical Plant Complex Continuous Commissioning Report For the Physical Plant Complex Building #1156 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-05 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Galveston (TAMU-G) Galveston, Texas Submitted to Texas A&M University

More information

Raised Access Floor - (AE Breadth Area)

Raised Access Floor - (AE Breadth Area) Raised Access Floor - (AE Breadth Area) Currently, the Plaza has a raised access flooring system on both the 7 th and 8 th floors. The 8 th floor is designed with an independent HVAC system utilizing an

More information

Comfort and health-indoor air quality

Comfort and health-indoor air quality Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental

More information

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Continuous Commissioning: A Valuable Partner to Retrofit Projects Continuous Commissioning: A Valuable Partner to Retrofit Projects Yeqiao Zhu Aamer Athar Kenneth Banks Ph.D. PE, CEM PE, CEM Energy Systems Laboratory Sempra Energy Solutions Sempra Energy Solutions Charles

More information

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner ESL-TR-99/12-09 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University at Commerce (TAMU-Commerce) Commerce, Texas Submitted to Texas

More information

Energy problems in small apartment buildings

Energy problems in small apartment buildings Energy problems in small apartment buildings Uneven heating and drafts, window condensation, complaints about odors and burned out lamps these are common problems in four-unit to eight-unit apartment buildings.

More information

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort

More information

The Temperature and Relative Humidity Control in Cushing Library

The Temperature and Relative Humidity Control in Cushing Library The Temperature and Relative Humidity Control in Cushing Library Chenggang Liu Research Associate Song Deng Assistant Director Homer L. Bruner, Jr., CEM Mechanical Systems Specialist Utilities Office of

More information

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS Chaoqin Zhai 1, Xiaohong

More information

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1 Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9

More information

Song Deng, P.E. Assistant Director Energy Systems Laboratory Texas A&M University College Station, TX

Song Deng, P.E. Assistant Director Energy Systems Laboratory Texas A&M University College Station, TX Room Temperature ontrol during Season Switchover with Single Duct Variable Air Volume System without Reheat henggang Liu Research Associate Song Deng, P.E. Assistant Director Homer L. Bruner, Jr., EM Mechanical

More information

Managing HVAC in High Performance Buildings

Managing HVAC in High Performance Buildings Managing HVAC in High Performance Buildings Ultra-Aire is one of five brands manufactured in Madison, WI under Therma-Stor, LLC. Our company, established in 1977, is considered the pioneer of whole-house

More information

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001 This HAP e-help provides a high-level overview of induction beams, how they work and how to model them in HAP 4.8 (and later versions). The first half of the article explains how induction beams work.

More information

The Art of Building Science

The Art of Building Science The Art of Building Science What is Building Science? Building Science seeks to apply the scientific fundamentals of building dynamics to the functional relationships between the house s components and

More information

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems about your house CE 28 k Assessing the Comfort and Safety of Your Home s Mechanical Systems The heating, ventilating and air conditioning (HVAC) systems are a vital part of every home. These mechanical

More information

Effect of Moisture on Building Systems!

Effect of Moisture on Building Systems! Effect of Moisture on Building Systems! There is always some moisture in the air around us. An indoor relative humidity of about 50% is usually considered a healthy level because it is comfortable for

More information

2006 Building Science Press All rights of reproduction in any form reserved.

2006 Building Science Press All rights of reproduction in any form reserved. building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Building Science Digest 110 HVAC in Multifamily Buildings 2006-10-24 by Joseph Lstiburek Abstract: Are

More information

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President Humidity Control Design Tips R. Mark Nunnelly, PE, CxA, LEED AP President AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects

More information

Mold/Moisture Control Case Study

Mold/Moisture Control Case Study Mold/Moisture Control Case Study Presented by Boggarm S. Setty, P.E., FASHRAE Setty & Associates, Ltd. www.clima2005.ch Clima 2005 Lausanne Solothurnstrasse 13 CH-3322 Schönbühl Switzerland th 8 REHVA

More information

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge ESL-TR-99/12-04 Report of Energy Efficiency Study and Metering/Utilities Profile for Electricity Deregulation at the Texas A&M University-Corpus Christi (TAMU-CC) Corpus Christi, Texas Submitted to Texas

More information

Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation

Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation Author:John Vavrin, PE Presenter: Dale Herron US Army Corps of Engineers Engineer Research

More information

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available. PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN September 30, 2015 PBA Project No. 2015.0140.00 PETER BASSO ASSOCIATES INC. CONSULTING ENGINEERS 5145 LIVERNOIS ROAD,

More information

C R A W L SPACE V E N T I L A T I O N C O M M O N PROBLEMS AND HOW YOU CAN FIX THEM

C R A W L SPACE V E N T I L A T I O N C O M M O N PROBLEMS AND HOW YOU CAN FIX THEM C R A W L SPACE V E N T I L A T I O N 1 0 1 C O M M O N PROBLEMS AND HOW YOU CAN FIX THEM C O M M O N P R O B L E M S 1 Crawl spaces tend to have high humidity, bad smells and poor air quality CRAWL SPACE

More information

Continuous Commissioning Report

Continuous Commissioning Report Continuous Commissioning Report for the Bush Academic Facility (Bldg. 1607) Submitted to: Office of Energy Management Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Unit with Enhanced Humidity Control Motorized Bypass Damper Temperature and Humidity Controller Reheat Control Elastomeric Foam Insulation High Efficiency,

More information

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China Humidity Control Systems for Civil Buildings in Hot Summer and Cold Winter Zone in China Xiaoping Yu Doctoral Candidate Chongqing University of Science & Technology Chongqing, China, 400042 xiaoyup@163.com

More information

Moisture Movement. By Ben Gromicko

Moisture Movement. By Ben Gromicko By Ben Gromicko It is important to study moisture in a course that is about inspecting insulation, because wet insulation does not work well. Also, insulation is an important part of the building envelope

More information

IAQ Building Education and Assessment Model (I-BEAM)

IAQ Building Education and Assessment Model (I-BEAM) Heating, Ventilation, and Airconditioning (HVAC) Text Modules IBEAM IAQ in L... http://www.epa.gov/iaq/largebldgs/ibeam/text/hvac.html Page 1 of 6 10/21/08 IAQ in Large Buildings http://www.epa.gov/iaq/largebldgs/ibeam/text/hvac.html

More information

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation Mingsheng Liu, Ph.D., P.E. Energy Systems Laboratory Texas A&M University College Station, Texas

More information

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for

More information

Harrington Tower Building

Harrington Tower Building Continuous Commissioning Report For the Harrington Tower Building Building #435 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

A Glossary of HVAC Terms

A Glossary of HVAC Terms A Glossary of HVAC Terms Confused by the many terms and acronyms surrounding your indoor comfort system? Don t be! This handy glossary of terms will tell you what you need to know when discussing your

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA CITY OF DANA POINT COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 33282 Golden Lantern, Suite 209 Dana Point, CA 92629 949 248 3594 www.danapoint.org INDOOR AIR QUALITY B011 AIR 2013 CALIFORNIA CODES CODE

More information

Do All DOAS Configurations Provide the Same Benefits?

Do All DOAS Configurations Provide the Same Benefits? TECHNIL FTURE This article was published in ASHE Journal, July 2014. Copyright 2014 ASHE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without

More information

Understanding Ventilation in Hot Humid Climates by Joseph Lstiburek

Understanding Ventilation in Hot Humid Climates by Joseph Lstiburek building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Building Science Digest 107 Understanding Ventilation in Hot Humid Climates 2006-10-26 by Joseph Lstiburek

More information

Ice Arena Mold Contamination By: Todd Bradley C.E.M

Ice Arena Mold Contamination By: Todd Bradley C.E.M Ice Arena Mold Contamination By: Todd Bradley C.E.M Mold or Toxic Mold Syndrome is a hot topic today. Cases of black mold or toxic mold are reported frequently in many public newspapers and in industry

More information

Continuous Commissioning of Commercial Kitchen and Dining Facilities Case Study

Continuous Commissioning of Commercial Kitchen and Dining Facilities Case Study The 7 th International onference for Enhanced Building Operations (IEBO 2007) ontinuous ommissioning of ommercial Kitchen and Dining Facilities ase Study Hui Li, hen Xu, Qiang hen and Song Deng Energy

More information

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline ME 414/514 HVAC Systems Overview Equipment Outline 2-1 The Complete System 2-2 The Air-Conditioning and Distribution System 2-3 Mechanical Equipment Air-handling Equipment Heating Equipment Boilers Furnaces

More information

CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI

CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI A crawl space needs to be ventilated with outside air. Without ventilation there will be growth of

More information

A Brief Guide to Mold, Moisture, And Your Home

A Brief Guide to Mold, Moisture, And Your Home A Brief Guide to Mold, Moisture, And Your Home This guide provides information and guidance for homeowners on how to clean residential mold problems and how to prevent mold growth, and is provided by as

More information

How to Prepare Your Crawl Space for Installation

How to Prepare Your Crawl Space for Installation While you re waiting for your new dehumidifier to arrive, here are a few topics to keep in mind. How to Prepare Your Crawl Space for Installation Prior to installation, be sure to do the following; 1.

More information

"A Brief Guide to Mold, Moisture, and Your Home"

A Brief Guide to Mold, Moisture, and Your Home "A Brief Guide to Mold, Moisture, and Your Home" Mold Basics The key to mold control is moisture control. If mold is a problem in your home, you should clean up the mold promptly and fix the water problem.

More information

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

EADQUARTERS. Technical Report One. Stephanie Kunkel   Mechanical Option EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option

More information

CHAPTER 4. HVAC DELIVERY SYSTEMS

CHAPTER 4. HVAC DELIVERY SYSTEMS CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer

More information

High Efficiency Dehumidification System (HEDS)

High Efficiency Dehumidification System (HEDS) Advanced HVAC Technologies High Efficiency Dehumidification System (HEDS) Scot Duncan, P.E., Jim Meacham, P.E. Conservant Systems, Inc. August 16, 2017 Tampa Convention Center Tampa, Florida Why Was HEDS

More information

Technical Report Three

Technical Report Three Technical Report Three Existing Conditions for Mechanical Systems Contents Executive Summary...2 Building Overview...2 Mechanical Systems Overview...2 Mechanical System...3 Outdoor & Indoor Design Conditions...3

More information

WatchDog 550 Quick Start Guide

WatchDog 550 Quick Start Guide Prepare Crawl Space for Installation Tips for Dehumidifier Installation Operating Instructions Benefits of a Dehumidifier Common Terms Parts Diagram Trouble Shooting Submit Warranty Additional Resources

More information

Active desiccant integration with packaged rooftop HVAC equipment

Active desiccant integration with packaged rooftop HVAC equipment Applied Thermal Engineering 25 (2005) 3138 3148 www.elsevier.com/locate/apthermeng Active desiccant integration with packaged rooftop HVAC equipment James R. Sand a, *, John C. Fischer b a Oak Ridge National

More information

HVAC DISTRIBUTION and DELIVERY SYSTEMS

HVAC DISTRIBUTION and DELIVERY SYSTEMS HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 1) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 REMINDER HVAC = Heating, Ventilating, Air-Conditioning The AC part of HVAC implies a system that

More information

Using Infrared for Residential Energy Surveys

Using Infrared for Residential Energy Surveys Using Infrared for Residential Energy Surveys Dave McCullen Sumter Electric Cooperative Inc. ABSTRACT In the electric industry today, advising consumers on energy conservation has replaced selling energy

More information

Model 1700 Whole-Home Dehumidifier

Model 1700 Whole-Home Dehumidifier Model 1700 Whole-Home Dehumidifier Take control of excess indoor moisture for your family and your home. Your home can have the latest heating and cooling technology, but you and your family can still

More information

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM 551B 581B DuraPac Plus Series Sizes 036-150 3to12 1 / 2 Tons Cancels: New PAD 551B.36.2 10/1/04 CONTENTS Page INTRODUCTION.................................

More information

Healthy Climate Indoor Air Quality Solutions. Solutions that fit your unique needs

Healthy Climate Indoor Air Quality Solutions. Solutions that fit your unique needs i n d o o r a i r q u a l i t y s o l u t i o n s Healthy Climate Indoor Air Quality Solutions Solutions that fit your unique needs Healthy Climate Indoor Air Quality Solutions Custom, whole-home product

More information

LIMITED INDOOR MOLD ASSESSMENT

LIMITED INDOOR MOLD ASSESSMENT LIMITED INDOOR MOLD ASSESSMENT RESIDENTIAL PROPERTY 1022 NORTHWEST 27 TH STREET SAN ANTONIO, TEXAS PREPARED FOR: PREPARED BY: LUCAS OLIVA ARGUS ENVIRONMENTAL SAN ANTONIO HOUSING AUTHORITY 10004 WURZBACH

More information

Supplement A- Improving Forced Air Heating Systems

Supplement A- Improving Forced Air Heating Systems Supplement A Improving Forced Air Heating Systems The Challenge Recent research and testing of new homes in the Pacific Northwest and across the United States shows the importance of a properly installed

More information

Humidity Control in Tropical Climate with Heat Pipes - The GREEN Way

Humidity Control in Tropical Climate with Heat Pipes - The GREEN Way TROPICAL SUBTROPICAL GREEN BUILDING ALLIANCE CONFERENCE 2012 Humidity Control in Tropical Climate with Heat Pipes - The GREEN Way Case Study: Cheras Rehab Hospital, Kuala Lumpur By Mohan Dhingra Managing

More information

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012 HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

Mechanical Systems Thesis Proposal: Calvert Memorial Hospital Prince Frederick, MD Holly Mawritz

Mechanical Systems Thesis Proposal: Calvert Memorial Hospital Prince Frederick, MD Holly Mawritz : Holly Mawritz Senior Thesis Project Proposal Penn State University Department of Architectural Engineering Mechanical Emphasis Faculty Consultant: Dr. Jim Freihaut 12-10-04 Table of Contents: Executive

More information

Improving your home comfort by enhancing the air

Improving your home comfort by enhancing the air i n d o o r a i r q u a l i t y Improving your home comfort by enhancing the air The perfect answer to air quality problems? Healthy Climate Solutions. With fuel and electricity costs on the rise, today

More information

Desiccant Dehumidifier

Desiccant Dehumidifier Since the 1950s Desiccant Dehumidifier Dry Spaces With NO Added Heat BMIL Technologies, LLC 4915 Arendell St., #313 Morehead City, NC 28557 PH 252-727-0994 FAX 252-727-0996 WWW.BMIL.COM Product Description

More information

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

8 5.11: Finned-Tube Coils and Heat Exchangers : Humidifiers and Water Spray Systems : Access for Inspection, Cleaning, and Maintenance

8 5.11: Finned-Tube Coils and Heat Exchangers : Humidifiers and Water Spray Systems : Access for Inspection, Cleaning, and Maintenance Table of Contents 3 Executive Summary 4 Building Overview 5 Mechanical Systems Overview 6 ASHRAE Standard 62.1 2013 Evaluation 6 Section 5: Systems and Equipment 6 5.1: Ventilation Air Distribution 6 5.2:

More information

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

NOVEMBER 2012 THE EUROPEAN EXPERIENCE Radiant-cooling systems have progressed in the last few decades, garnering attention as a comfortable and energy- and material-efficient option. 1 Compared with air radiant-cooling hydronic systems use

More information

IAQ: Re-tuning Commercial Buildings

IAQ: Re-tuning Commercial Buildings IAQ: Re-tuning Commercial Buildings A low-cost path to improved air quality and energy efficiency. B y S c o t t G o r d o n, C M All images courtesy of Johnson Controls Service. 10 RSES Journal FEBRUARY

More information

Green Flag Level Two Survey: Indoor Air Quality Program

Green Flag Level Two Survey: Indoor Air Quality Program Green Flag Level Two Survey: Indoor Air Quality Program You have chosen to work on the Indoor Air Quality (IAQ) program to earn a Green Flag award. Answering these survey questions will take you on a tour

More information

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 2) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Contextual Reminder All-air systems Single zone Terminal reheat Multi-zone Dual-duct VAV Combinations

More information

Application of the VRV Air-Conditioning System Heat Recovery Series in. Interior Zone and Analysis of its Energy Saving

Application of the VRV Air-Conditioning System Heat Recovery Series in. Interior Zone and Analysis of its Energy Saving Application of the VRV Air-Conditioning System Heat Recovery Series in Interior Zone and Analysis of its Energy Saving Qiang Zhang Deying Li Jiandong Zhang Master Student Professor Engineer Key Laboratory

More information

Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems

Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems Guanghua Wei, P.E. Joe Martinez Tom Minihan Assistant Research Engineer Research Engineering Associate Graduate Student Tim Brundidge

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma Objectives and Requirements For the Creative and Performing Arts High School (CAPA), the main objective of the mechanical design is to provide an energy efficient system that is easily maintainable and

More information

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Available online at   Energy Procedia 6 (2011) MEDGREEN 2011-LB Available online at www.sciencedirect.com Energy Procedia 6 (2011) 759 768 MEDGREEN 2011-LB Comparison of two methods of improving dehumidification in air conditioning systems: hybrid system (refrigeration

More information

Mold Awareness & Remediation: A Common Sense Approach

Mold Awareness & Remediation: A Common Sense Approach Mold Awareness & Remediation: A Common Sense Approach About This Session BE INTERACTIVE!! Share ideas. Share challenges. There is more than one right answer! IICRC Institute of Inspection Cleaning & Restoration

More information

Liquid Desiccant Technology Delivers Energy Cost Reductions and Indoor Air Quality Improvements. White Paper

Liquid Desiccant Technology Delivers Energy Cost Reductions and Indoor Air Quality Improvements. White Paper Liquid Desiccant Technology Delivers Energy Cost Reductions and Indoor Air Quality Improvements White Paper Abstract Cooling represents the third leading use of energy and source of carbon emissions in

More information

Redesign of Bennett Hall HVAC System

Redesign of Bennett Hall HVAC System MEE 488 April 18, 2006 Redesign of Bennett Hall HVAC System Greg Andreasen Michael Chicoine Florent Hohxa Jason Jacobe Mechanical Engineering, University of Maine, Orono ME 04473, USA ABSTRACT Our task

More information

about your house Choosing a Dehumidifier

about your house Choosing a Dehumidifier about your house CE 27 Moisture in house air can be a problem when there is either too little or too much. Air that is too dry can cause discomfort, dried and itchy skin and nasal passages, cracked or

More information

WHAT YOU NEED TO KNOW ABOUT MOLD IN YOUR HOME

WHAT YOU NEED TO KNOW ABOUT MOLD IN YOUR HOME WHAT YOU NEED TO KNOW ABOUT MOLD IN YOUR HOME You can be the cleanliest person in the world and still have a mold problem in your home. WHY? Because mold and mold spores are everywhere, both indoors and

More information

Got Mold? Frequently Asked Questions About Mold

Got Mold? Frequently Asked Questions About Mold What are molds? With more than 100,000 species in the world, it is no wonder molds can be found everywhere. Neither animal or plant, molds are microscopic organisms that produce enzymes to digest organic

More information

Tech to Tech May 07 HRV s & ERV s

Tech to Tech May 07 HRV s & ERV s Tech to Tech May 07 HRV s & ERV s Make daily deposits to your box of knowledge, soon it will have many reference cards. --Randal S. Ripley With the cost of energy going up all the time, home owners and

More information

NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS. Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan

NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS. Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan NORTH CENTRAL MICHIGAN COLLEGE PETOSKEY CAMPUS Facilities Conditions Assessment Mechanical And Electrical Petoskey, Michigan PBA Project No. 2014.0137.00 Prepared By: Wayne Kerbelis Terry Cleis September

More information

Ventilation for New Low-Rise Residential Buildings July 20, 2015

Ventilation for New Low-Rise Residential Buildings July 20, 2015 Ventilation for New Low-Rise Residential Buildings July 20, 2015 BSC Standard 01 2015 Building Science Corporation 3 Lan Drive, Suite 102 Westford, MA 01886 www.buildingscience.com Contents 1. PURPOSE...3

More information

WALK-AROUND INSPECTION LIST

WALK-AROUND INSPECTION LIST WALK-AROUND INSPECTION LIST Page 1 of 18 BUILDING DESCRIPTION Location of building in relation to potential sources (industry, landfills, emissions, outside renovations, etc.) Original construction date

More information

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop Energy-Savings Strategies for Rooftop VAV Systems Occupied set-point temperature Unoccupied set-point temperature Rooftop variable-air-volume (VAV) s are used to provide comfort in a wide range of building

More information

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1

More information

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS SUMMARY Ammonia odours were reported in the community close to the time of the incident (Appendix D) and firefighters reported

More information

Displacement Ventilation

Displacement Ventilation Displacement Ventilation Displacement Ventilation Displacement Ventilation vs. Dilution Ventilation Characteristics Design Considerations Layout and Selection Product Overview Casino Case Study Dilution

More information

WatchDog 900c Quick Start Guide

WatchDog 900c Quick Start Guide Prepare Crawl Space for Installation Tips for Dehumidifier Installation Operating Instructions Benefits of a Dehumidifier Common Terms Parts Diagram Trouble Shooting Submit Warranty Additional Resources

More information

Ventilation in Humid Climates: Data from Field Experiments

Ventilation in Humid Climates: Data from Field Experiments Gaylord Texan Resort & Convention Center October 20-23, 2004 - Dallas, Texas Ventilation in Humid Climates: Data from Field Experiments Neil Moyer FSEC Yearly Housing Starts Past 3 Years Source: NAHB x

More information

The Unplanned Impacts On Houses By Powered Attic Ventilators

The Unplanned Impacts On Houses By Powered Attic Ventilators The Unplanned Impacts On Houses By Powered Attic Ventilators John J. Tooley Jr., Natural Florida Retrofit Bruce Eugene Davis, Advanced Energy Corporation Applied Building Science Center 1994 ABSTRACT It

More information

Home WHOLE-HOME COMFORT SOLUTIONS. Bringing balance. Creating comfort.

Home WHOLE-HOME COMFORT SOLUTIONS. Bringing balance. Creating comfort. Home WHOLE-HOME COMFORT SOLUTIONS Bringing balance. Creating comfort. IAQ is important. Every home has its own unique IAQ conditions that can easily fall out of balance. Too much or too little humidity,

More information

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012) Madeira City Schools Madeira, Ohio HVAC Assessment December 2011 (Revised February 2012) Prepared by: CMTA Engineering Consultants, Inc. 10411 Meeting Street Prospect, KY 40059 www.cmtaegrs.com (502) 326-3085

More information

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD ASHRAE Standard 62 Ventilation Report Technical Assignment #1 Prepared By: Holly Mawritz October 6, 2004 Table Of Contents: Executive Summary 2 Assumptions 3 Procedure 4 Sample Calculations 5 System and

More information

Table of Contents. List of Figures and Tables. Executive Summary: 3 ASHRAE Standard 62.1 Section 6 Analysis 7

Table of Contents. List of Figures and Tables. Executive Summary: 3 ASHRAE Standard 62.1 Section 6 Analysis 7 Army Reserve Center Newport, Rhode Island Technical Report One: ASHRAE Standard 62.1 Ventilat tion and Standard 90.1 Energy Design Evaluations October 4, 2010 2 Table of Contents Executive Summary: 3 ASHRAE

More information

LIMITED MICROBIAL & IAQ SURVEY CLOSING REPORT SOUTHEASTERN SCHOOL DISTRICT 02/12/2015

LIMITED MICROBIAL & IAQ SURVEY CLOSING REPORT SOUTHEASTERN SCHOOL DISTRICT 02/12/2015 HOME OFFICE PO Box 326 MT AETNA PA 19544 MEMBERS OF: VOICE 717-933-9475 FAX 717-933-1403 TOLL FREE 877-255-0558 Web Page: proaccorp.com CLOSING REPORT SOUTHEASTERN DISTRICT 02/12/2015 PROJECT LOCATION:

More information

Museum Archive Dehumidification in Hot & Humid Climates

Museum Archive Dehumidification in Hot & Humid Climates Museum Archive Dehumidification in Hot & Humid Climates B. K. Browning, PE Principal Engineer KWR Services Austin, Texas ABSTRACT This paper discusses some of the difficulties found with a desiccant dehumidification

More information

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80 NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80 Carrier Software Systems Carrier Corporation Syracuse, New York rev October 10, 2013 Copyright 2013 Carrier Corporation, All Rights Reserved Page

More information

Brine Generation Study

Brine Generation Study DOE/WIPP 00-2000 Brine Generation Study April 2000 Waste Isolation Pilot Plant Carlsbad, New Mexico Processing and final preparation of this report was performed by the Waste Isolation Pilot Plant Management

More information