Reducing cooling energy by system innovation Yi Jiang Operating agency of EBC Annex 59 Building energy Research center Tsinghua University
|
|
- Patience Parrish
- 6 years ago
- Views:
Transcription
1 IEA Annex 59 Low temperature heating & high temperature cooling Reducing cooling energy by system innovation Yi Jiang Operating agency of EBC Annex 59 Building energy Research center Tsinghua University
2 Where is the energy lost through cooling? Indoor chilled water chiller cooling water cooling tower outdoor 40 Condensing Temperature 35 Cooling water ΔT 7 T in, ω in AHU Outdoor air Outdoor wet bulb temperature Indoor temperature ΔT 6 ΔT 5 T e Thro T c Evap Cond Com Cooling tower Temperature / o C 20 ΔT 1 Air in FCU 15 ΔT 2 Chilled water 10 ΔT 3 5 Evaporation Temperature ΔT Q 0.75 Q Heat q /W ΔT 2
3 Where is the energy lost through cooling? The real demand for space cooling is just raising the heat Q for 3K from 25 indoor to 28 outdoor, the required work is 3Q [WK] However the chiller does lift up the heat Q from 5 at the evaporator to 40 at the condenser, the actual work is 35Q [WK], as many as 11 times! The additional 32Q have been paid for completing the heat transfer process as well as heat flux mixed with different temperature during the heat transportation process from indoor to outdoor The other reason is that dehumidification required. To make moisture condensation, low temperature below dew point as the cooling source is needed 3
4 An Innovation of space cooling system Separate humidity control from temperature control: THIC An independent air system added to remove latent heat for humidity control Temperature can then be controlled by a high temperature cooling source (eg. 15 to 20 ) to remove sensible heat only As sensible heat normally takes more than 70% of the total heat load, high efficiency cooling source can be used to remove sensible heat Underground water or underground heat exchanger if ground temperature is below 15 Evaporate cooling can also provide cooling source if the dew point outdoor is below 15 COP for compression chiller can be achieved at 9 ~ 10 comparing with 5~6 at normal state Reduce the temperature difference between indoor space and cooling source so to raise required cooling source temperatures as high as possible Reduce the power of fans and pumps by improvement of the heat delivering system 4
5 An Innovation of space cooling system Separate humidity control from temperature control (THIC) Humidity control as well as indoor air quality: Dried outdoor air Temperature control: High temperature cooling source (or low temperature heating source in winter) Air-conditioning devices Terminal Indoor environment Humidity control subsystem Outdoor air processor Dry air Displacement vent Personalized vent. Control indoor humidity and CO2 Temperature control subsystem Summer: Cooling source Winter: Heat resource 16~19 C 16 Radiant panel Dry FCU Control indoor temperature Operating principle of the THIC air-conditioning system * Liu XH, Jiang Y, et al. Temperature and Humidity independent Control (THIC) of Airconditioning System. Berlin: Springer Press,
6 Sensible heat removal for Temp. control In more than 40% of cooling applications in the world the outdoor dew point is below 15. Moisture can be removed by air exchange with outdoor. Space cooling is just to remove sensible heat To raise the cooling source temperature for high efficiency cooling, the key approach is to reduce the Δt during heat delivering process Avoid the mixing loss of heat collection process at indoor terminals Avoid Δt loss of heat exchange process Avoid the mixing loss of heat fluxes with different temperature 6
7 Terminal handling process Task: collecting heat and moisture from sources Indoor terminal Indoor state T in, ω in T Heat sources T in Mixing process Solar radiation Supply air Transfer Indoor heat sources and moisture sources Supply water Avoid mixing loss of heat collection process at indoor terminals! Q Q 7
8 Terminal handling process Heat sources with different temperatures 平板电视 flat-panel tv Heat sources temp. varying in the range of 26~40ºC, or even higher message sign Significant mixing loss from heat sources to indoor air 8
9 Direct solar radiation 35 QsTs Inner surface (Ts) Temperature / o C QsTs Indoor air (Ta) Indoor air Supply air Chilled water QsTr Radiant floor surface (Tr) Floor surface Chilled water QsTr Heat flux W/m 2 9
10 Terminal handling process > Simplify heat transfer process from heat sources to chilled water 35 Radiant floor Jet ventilation 30 Temperature / o C Heat flux W/m Heat sources Radiant floor surface Chilled water Heat sources Indoor air Supply air Chilled water 10
11 Terminal handling process > Reducing indoor mixing loss > Decrease temperature gradient in space > Avoid fluid mixture of high temperature with low temperature System I Floor radiantion Floor convection System II Floor heat conduction Envelope convection Mixture Entransy dissipation En Φ (W o C/m 2 ) Air-water convection 11
12 Terminal handling process Jet ventilation Radiant floor ~5m Jet supply air ~20m ~2m Displacement supply air ~20m Radiant floor Radiant floor Displacement ventilation Temperature / o C Mixture Entransy Dissipation Convective Entransy Dissipation Convective Entransy Dissipation Envelope Indoor air Heat flux W/m 2 Supply air Chilled water Temperature / o C Radiant Entransy Dissipation Conductive Entransy Dissipation Heat flux W/m 2 Convective Entransy Dissipation Mixture Entransy Dissipation Convective Entransy Dissipation Envelope Indoor air Displacement air Radiant floor Chilled water 12
13 Terminal handling process Entransy dissipation comparison > Total entransy dissipation of System II (2411 (W ºC)/m 2 )) is less than that of System I (3413 (W ºC)/m 2 )) > Reduced entransy dissipation (1002 (W ºC)/m 2 )) by system II equals to rising 6.3ºC of chilled water temperature. System I Floor radiantion Floor convection System II Floor heat conduction Envelope convection Mixture Air-water convection Entransy dissipation En Φ (W o C/m 2 ) 13
14 Terminals with low mixing loss Radiant panels, radiant floor, TABs Radiant 放射パネル Panel Ceiling 高さ height:2.8m : Measuring Point:1.5m 200 間隔で計測 above floor Indoor 空調室内機 Unit Floor 床面 Embedded radiant systems: a) Floor, b) Ceiling, c) Wall, d) TABS 14
15 Application Terminal 3 of Xi an airport Area: 258,000m 2, with a maximum height of 36.5m Coming into service since May 2012 The first terminal adopting radiant cooling/heating in China Radiant cooling, displacement ventilation, liquid desiccant 15
16 AC system (summer) Large space area Stratified air conditioning in summer Natural ventilation zone ~ 20m 顶部排风 ( 排出高温高湿空气 ) Infiltration 渗风 Dry air 分布式送风末端 Conditioned temp., low hum. zone Displacement ventilation 2 m 建筑开口 Entrance 辐射地板 Radiant floor with high temp water 16
17 Terminal handling process 121m Air 17m West Wall m 17m East Wall 17m 12m m 12m 7.4m m 7.4m 2.8m Displacement vent m Displacement vent m 1.7m 1.1m m 1.1m 2m 1.7m 1.1m Measured temperatures 17
18 Application Radiant floor for cooling (without solar) Temperature ) floor surface (no seat) floor surface (under seat) dew point Cooling capacity (W/m 2 ) :00 11:00 12:00 13:00 14:00 Time 15:00 16: :00 11:00 12:00 13:00 Time 14:00 15:00 16:00 Temperatures Cooling capacity (20~40W/m 2 ) 18
19 Application Radiant floor for cooling (with solar) Solar radiation on floor: High intensity, transient process 200 C B A Solar radiation density (W/m 2 ) Point A 11min Point B 24min Point C 31min Time (p.m.) Floor surface temperature ( C) Point A Point C Point B Point D (under chair) Cooling capacity (W/m 2 ) Point A Point C Point B Point D (under chair) Time Time Cooling capacity could be higher than 100W/m2 with direct solar radiation 19
20 Application Power consumption Significant energy conservation benefits T2 T2: T3 20
21 Application Radiant terminal in a solar house (Denmark) Embedded pipes 21
22 Application Radiant terminal in a solar house (Denmark) 35 Floor cooling Heat flux [W/m 2 ] Operative temperature and external air temperature during the cooling season 0 Cooling capacity 22
23 Avoid Δt loss of heat exchange process Direct connection of the cooling source with indoor terminals Enlarge the heat transfer ability and adjust the flow rates at both sides so to ensure the Δt uniformed along the heat exchange process T h,in T h,in T h,out T h,out T T h,in T T h,in T h,out T c,out T c,out T h,out T c,out T c,out T c,in T c,in T c,in x T c,in Unmatched flow rates Q 23
24 Avoid Δt loss of heat exchange process 4~5 K temperature difference for water circulation On-off control for each indoor terminal (radiative) to obtain near linear control performance Careful design of the water piping system to avoid large pump power consumed Remove most of control valves and other resistance device in water loops except on-off control valve Pressure drop: 10~15 m H 2 O for total water loop circulation On-off control 24
25 Case study Evaporative cooling as cooling source Outlet water temperature 15~19 to remove sensible heat Tsp Exhaust air C 4 M 2 Inlet air O 1 A A 1 Inlet air O Cold water User heat exchanger 3 T Key parts: countercurrent air cooler/packing tower Design idea: matched flow rates and parameters 25
26 Case study Evaporative cooling as cooling source Installed in Shihezi Kai Rui Building, now four years wellrunning. Shihezi outdoor design air state: dry bulb 32.8, wet bulb Designed water out temperature 18.5, cooling Energy output 120kW. 26
27 Case study Evaporative cooling as cooling source Temperature( ) Inlet dry bulb tempeature( ) Inlet wet bulb temperautre( ) Out water temperature ( ) Inlet dew point temperature( ) 19:40 19:40 12:50 18:40 12:10 20:10 13:00 17:40 12:20 17:00 21:40 19:00 23:40 16:50 22:00 22:40 15:20 10:10 14:50 9:50 14:30 19:10 10:40 15:20 20:00 10:10 14:50 19:30 13:00 20:40 15:20 20:00 10:30 15:10 19:50 14:10 18:50 23:30 Out water Temperature lower than inlet Wet Bulb Temperature. Tested COP (sensible heat removed/power of fan and pump) higher than
28 Case study Evaporative cooling as cooling source Applications in the dry region (Xinjiang province, China) Shihezi Kai Rui Building Aksu People s Hospital Xinjiang Chinese Medicine Hospital Xinjiang Medical University Hospital Xinjiang air force hospital Office building of Xinjiang medicine hospital Changji medicine hospital Xinjiang international exhibition center 28
29 Suitable region for evaporative cooling Climate condition: dew point 15 System requirement: Low Δt loss terminals with on-off control Large water circulation with minimal pressure drop Division: Outdoor Humidity Ratio: 12g/kg West China West U.S. 29
30 Suitable region for evaporative cooling Climate condition: dew point 15 North Europe Outdoor Humidity Ratio (g/kg) 30
31 Efficient dehumidification process For moist region: humidity control is part of the task in space cooling Weak point of dehumidification by condensation: Require the cooling source below dew point Reheat, or mix with higher temperature environment 60 温度 T / o C 转轮除湿 S Reheating 冷凝除湿 溶液除湿 R Conventional desiccant wheel O O R S 含湿量 ω /(kg/kg) New approaches for dehumidification are required! 31
32 Efficient dehumidification process New approaches for dehumidification Liquid desiccant dehumidification Two-stage total heat recovery Exhaust air Return air Condenser Fresh air Supply air Evaporator Throttle Compressor Multi-stage process for dehumidification, matched parameters 32
33 Efficient dehumidification process New approaches for dehumidification Liquid desiccant dehumidification Close to the iso-relative humidity line instead of isenthalpic line 33
34 Efficient dehumidification process New approaches for dehumidification Liquid desiccant dehumidification Fresh air t ( C) Fresh air d (g/kg) Supply air t ( C) Supply air d (g/kg) Return air t ( C) Return air d (g/kg) Exhaust air t ( C) Exhaust air d (g/kg) Cooling Dehumidify Deep Dehumidify Total Heat Recovery Humidify COP %
35 Efficient dehumidification process New approaches for dehumidification Solid desiccant dehumidification (DESICA, Japan) 排风 EA FA 新风 回风 RA compressor 压缩机 送风 SA Heat pump utilized for internal cooling in dehumidification 35
36 Efficient dehumidification process New approaches for dehumidification Solid desiccant dehumidification (DESICA, Japan) Return exhausted air air Supply Supplied air air Fresh Outdoor air air heat exchangers glued with silica-gel Return return air air % A typical process EA Exhaust exhausted air air Supply supplied air air after a period: Four-way valve changes direction Air valves change direction Outdoor fresh air heat exchangers air glued with silica-gel Return return air air T ( ) SA RA 40% 60% 80% 100% ω(g/kg) FA Close to the iso-relative humidity line instead of isenthalpic line COP is as high as
37 Application Liquid desiccant Temperature and Humidity Independent control system Cooling tower FCU & radiant panel Return air 4 th floor Supplied air Outdoor air processor Exhaust air Outdoor air 3 rd floor Cooling water pump 2 nd floor 1 st floor 17ºC Outdoor air processor Chiller Chilled water pump 37
38 Application Liquid desiccant Cooling capacity /kw Energy consump /kw COP Outdoor air process OAHU Fan Chiller Chilled water pump Chilled water process Cooling water pump Cooling tower Fan Coil Unit Entire system (OAHU=4.6) 3.7 (Chiller=8.5)
39 Application Liquid desiccant Power consumption /kwh 105,000 90,000 75,000 60,000 45,000 30,000 15,000 0 Apr May Jun Jul Aug Sep Oct Annual power consumption: 32kWh/(m 2 AC area) Common building in Shenzhen: ~50kWh/(m 2 AC area) Energy saving: ~30% 39
40 Application DESICA Office building in Japan DESICA for humidity control and VRF for temp. control 40
41 Application DESICA Office building in Japan DESICA for humidity control and VRF for temp. control 41
42 Application DESICA DESICA for humidity control and VRF for temp. control Conventional System THIC System -47.4% Ventilation Fan HP Desiccant Compressor Ventilation Standby Power Requirement Inner Unit of VRF Outer Unit of VRF Conventional System THIC System Average Dayly Energy Consumption(kWh/m2 day) Set temperature is % Average Daily Energy Consumption(kWh/m2 day) Set temperature is 26 VRF Standby Power Requirement Ventilation Fan HP Desiccant Compressor Ventilation Standby Power Requirement Inner Unit of VRF Outer Unit of VRF VRF Standby Power Requirement 42
43 THIC applications in China Dry area: Indirect evap. cooling Wet area: Dehumidification solution THIC applications in China: Over 10 million m 2 buildings since
44 How much energy can be saved? Office building in dry climate Conventional system for cooling: electricity used 50 kwh/ m2, Total cooling: 100 kwh/ m2, COP=2, fans: 17kWh/ m2, pumps: 11kWh/ m2, chiller:22kwh/ m2 Evaporate cooling with the innovative system: electricity used 23kWh/ m2, 54% saved Total cooling 100 kwh/ m2, COP=5, fans:8kwh/ m2, pumps: 15kWh/ m2 Office building in moist region Conventional HVAC system for cooling: electricity used 65kWh/ m2 Total cooling:130 kwh/ m2,cop=2, fans:22kwh/ m2, pumps:14kwh/ m2, chiller:29kwh/ m2 THIC system: electricity used 44kWh/ m2, 32% saved Total cooling:130kwh/ m2, dehumidifier with fan: 14kWh/ m2, pumps:15kwh/ m2, chiller:15kwh/ m2 Latent heat:35kwh/ m2,copl=2.5, sensible heat:95kwh/ m2,cops=3.2 44
45 Conclusion Huge potential saving in space cooling technology! Dry regions, ~40% of current cooling applications Direct/indirect evaporative cooling instead of mechanical chillers System should be well designed both for indoor terminal and heat delivering to adapt high temperature cooling More than 50% energy can be saved! Moist regions: east China and US, Japan, south India Humidity should be treated independently with temperature Desiccant humidity control techniques should be applied for dehumidification Sensible heat should be removed with high temperature cooling source About 30% saving can be achieved! 45
46 46 IEA EBC Annex 59 High Temperature Cooling & Low Temperature Heating In Buildings ( )
47 This presentation is the summary of EBC Annex 59: High temperature cooling & low temperature heating in buildings 47
48 For more information:
49 Reducing ΔEn in HV&AC system 2. Coupled Temp. & Humid. control Conventional system: coupled control of indoor Temp. & Humid. ~7ºC chilled water is required for cooling & dehumidification 40 Condensing temperature 40 Condensing temperature 35 Cooling water ΔT 4 35 Cooling water Temperature / o C Outdoor wet bulb temperature Indoor temperature Air in FCU Chilled water Evaporating temperature ΔT 5 ΔT 6 ΔT 1 ΔT 2 ΔT 3 ΔT CHP Temperature / o C Outdoor wet bulb temperature Indoor temperature Air in FCU Chilled water Evaporating temperature ΔEn is significantly reduced for Temp. control in the improved system ΔT CH, high T Q 0.75 Q Q 0.75 Q Heat /W Heat /W Conventional system THIC system (for Temp. control) Adopting other approaches for Humid. control 49
50 Application in buildings Data center Return air 测试机架 Racks Conventional system Rack Q T chip T out Temperature Entransy dissipation of rack cooling process T in Air flow T return Entransy dissipation of air mixing process T supply T coldsource HEX Q Tex Outdoor Environment Entransy dissipation of heat exchanging process Entransy dissipation of heat flow into outdoor environment Q Heat 50
51 Application in buildings Data center Internal cooled new system Chilled water out LHP 2 Liquid pipe 2 Steam pipe 2 Rack exhaust air (Room temperature) LHP 1 Chilled water in Rack temp distribution Room temp LHP2 Server intake air Server 1 Server 2 Server exhaust air Temp LHP 1 Server N Steam pipe 1 Liquid pipe 1 Rack intake air (Room temperature) 51
52 Former CRAC Compressor power kw Fan power kw Server power kw EER Indoor air temp Evaporative temp Supply/ Return air temp Rack inlet/exhaust air temp Outdoor air dry/wet bulb temp January 2nd /24 24/33 6 / 0.2 May 7th /25 24/33 22 /13 August 10th /25 25/34 29 /19 Current distributed cooling Cooling tower kw Chiller 1 power kw Chiller 2 power kw Pump power kw Rack fan kw Server power kw Former:rack exhaust T=indoor T +9 Current:rack exhaust T indoor T EER Indoor air temp Supply/Ret urn water temp Rack inlet/exhaust air temp January 2nd / /24.2 May 7th / /25.3 August 10th / /
53 Former CRAC Compressor power kw Fan power kw Server power kw EER Indoor air temp Evaporative temp Supply/ Return air temp Rack inlet/exhaust air temp Outdoor air dry/wet bulb temp January 2nd /24 24/33 6 / 0.2 May 7th /25 24/33 22 /13 August 10th /25 25/34 29 /19 EER:Increased from 2.6 to 5.7 PUE: Decreased from 1.6 to 1.35 Current distributed cooling Cooling tower kw Chiller 1 power kw Chiller 2 power kw Pump power kw Rack fan kw Server power kw EER Indoor air temp Supply/Ret urn water temp Rack inlet/exhaust air temp January 2nd / /24.2 May 7th / /25.3 August 10th / /
Zero Internal Heating/Cooling Load Air-Conditioning system
Zero Internal Heating/Cooling Load Air-Conditioning system Study on Indoor Thermal Environment of an Office Room with the Liquid Cooling Air-conditioning System Li Wang (University of Tokyo, Japan) (leowang19861986@gmail.com)
More informationIntegrated Building Environmental Design Case Study: Beijing Parkview Green
Integrated Building Environmental Design Case Study: Beijing Parkview Green The 7th International Energy Agency Annex 44 Forum 24 October 2007 Dr Raymond Yau Director Ove Arup & Partners Hong Kong Ltd.
More informationInternational Forum on Energy, Environment Science and Materials (IFEESM 2015)
The Comparison and Analysis of Humidity Environment between Floor and Ceiling Radiant Cooling Systems that Combined with Displacement Ventilation Kai SUN 1 a *, Chuan-hui ZHOU 1 1 College of Urban Construction,
More informationFAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney
FAST AND ROBUST BUILDING SIMULATION SOFTWARE Chilled Beam Performance: 1 Shelly Street, Sydney 3D Model Creation 1 Shelley Street, Sydney 3D Model Creation 1 Shelley Street, Sydney Daylight Analysis 1
More informationIntegrated Building Environmental Design. Beijing Parkview Green. 10 May 2008
Integrated Building Environmental Design Beijing Parkview Green 10 May 2008 Developer : Beijing Chyau Fwu Properties Co., Ltd. Architect : Integrated Design Associates Engineering Consultant : Ove Arup
More informationHigh-Temperature Cooling & Low-Temperature Heating AC System Evaluation of energy saving in an office in Tokyo
High-Temperature Cooling & Low-Temperature Heating AC System Evaluation of energy saving in an office in Tokyo Katsuhiro URANO (*), Akio SUMITA (**) (*) 2-2-7, Kitakyuhoji, Yao-shi, Osaka, 581-0071, Japan
More informationState of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney
Frenger Radiant chilled beam performance at 3D Model Creation Daylight Analysis Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled
More informationChilled Ceilings / Beams Working Principles & Applications
5 th International Conference on Energy Sustainable Energy Polices and Technologies 15-17 October 2014 Chilled Ceilings / Beams Working Principles & Applications Francis W H Yik ATAL Building Services
More informationAppendices. Appendix A: Moisture Load Calculation. A.1 Moisture Generated by Occupants
Appendices Appendix A: Moisture Load Calculation Indoor moisture is mainly from moisture generated by occupants and moisture evaporated from open water surface, plant transpiration, and infiltration moisture
More informationTemperature and Humidity Individual Controll HVAC System with the New Desiccant Device DESICA-
Temperature and Humidity Individual Controll HVAC System with the New Desiccant Device DESICA- Tadafumi Nishimura tadafumi.nishimura@daikin.co.jp DAIKIN INDUSTRIES, LTD. Osaka, Japan November. 11, 2014
More informationK.F. Fong *, C.K. Lee, T.T. Chow
Investigation on radiative load ratio of chilled beams on performances of solar hybrid adsorption refrigeration system for radiant cooling in subtropical city K.F. Fong *, C.K. Lee, T.T. Chow Building
More informationKawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto
Kawasaki centrifugal chiller using water as a refrigerant Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto Contents 1. Introduction of MiZTURBO 2. Study of CO 2 emissions
More informationOpen Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System
Send Orders for Reprints to reprints@benthamscience.ae The Open Electrical & Electronic Engineering Journal, 215, 9, 7-14 7 Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning
More informationMechanical System Redesign. Dedicated Outdoor Air System. Design Criteria
Mechanical System Redesign Dedicated Outdoor Air System Design Criteria The outdoor air conditions used were for Philadelphia, Pennsylvania IAP at a 0.4% occurrence. The supply air conditions were developed
More informationSIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA
Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS Chaoqin Zhai 1, Xiaohong
More informationSIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY
SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY Xiaoyun Xie, Yidan Tang, Xiaoqin Yi, Shuanqiang Liu,Yi Jiang Department of Building Science and Technology,
More informationSession: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island
Session: HVAC 101 HVAC 101 Steve Sain Sain Engineering Associates, Inc. August 9, 2016 Rhode Island Convention Center Providence, Rhode Island Why? 2 Acknowledgements 3 Disclaimer I m gonna shoot down
More informationHumidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China
Humidity Control Systems for Civil Buildings in Hot Summer and Cold Winter Zone in China Xiaoping Yu Doctoral Candidate Chongqing University of Science & Technology Chongqing, China, 400042 xiaoyup@163.com
More informationHeat pump and energy recovery systems
SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air
More informationLATEST HEAT PUMP TECHNOLOGIES IN JAPAN. Waseda University Kiyoshi Saito
LATEST HEAT PUMP TECHNOLOGIES IN JAPAN Kiyoshi Saito IEA Heat Pump Conference 217 INTRODUCTION In Japan, since great effort to improve performance of heat pump system has been made, still new technologies
More informationEnergy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for
More information2. CURRICULUM. Sl. No.
. CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration
More informationFeasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System
Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang
More informationDehumidification: Energy Efficiency Comparisons
Fourth Annual Energy Management Workshop Cocoa, Florida February 10-11, 2003 Dehumidification: Energy Efficiency Comparisons Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting,
More informationAdaptibility Analysis of nzeb and Passivhaus in Mixture Climates of China
Adaptibility Analysis of nzeb and Passivhaus in Mixture Climates of China Vice President of CCHVAC Ph.D. & Prof. Xu Zhang, Director, Institute of HVAC Eng., Tongji University, Shanghai, PRC Contents The
More informationCHAPTER 4. HVAC DELIVERY SYSTEMS
CHAPTER 4. HVAC DELIVERY SYSTEMS 4.1 Introduction 4.2 Centralized System versus Individual System 4.3 Heat Transfer Fluids 4.4 CAV versus VAV Systems 4.5 Common Systems for Heating and Cooling 4.6 Economizer
More informationEVALUATION OF HEAT REJECTION STRATEGIES FOR LIQUID DESICCANT AIR-CONDITIONING SYSTEMS
EVALUATION OF HEAT REJECTION STRATEGIES FOR LIQUID DESICCANT AIR-CONDITIONING SYSTEMS by Danial Salimizad A thesis submitted to the Department of Mechanical and Materials Engineering in conformity with
More informationRESEARCH ON NATURAL REFRIGERANTS IN JAPAN. WASEDA UNIVERSITY Kiyoshi SAITO
RESEARCH ON NAURAL REFRIGERANS IN JAPAN WASEDA UNIVERSIY Kiyoshi SAIO INRODUCION In Japan, we have the highest level technologies for natural refrigerant use in the world. CO2 Residential heat pump water
More informationseasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former
A study on reducing the energy demand of a liquid desiccant dehumidifier with a radiant panel system Tae Ha Leigh, 1 Dae Uk Shin, 1 Goo Sang Joe, 1 Min Gi Kim, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim 2,*
More informationINSTITUTE FOR ENVIRONMENTAL RESEARCH & SUSTAINABLE DEVELOPMENT NATIONAL OBSERVATORY OF ATHENS (NOA)
1 SOLAR COOLING An Overview of European Applications & Design Guidelines Costas Balaras, Ph.D. Member ASHRAE, Mechanical Engineer, Research Director GRoup Energy Conservation (GR.E.C.) INSTITUTE FOR ENVIRONMENTAL
More informationSOLAR COOLING TECHNOLOGIES
SOLAR COOLING TECHNOLOGIES S. SRINIVASA MURTHY Professor of Refrigeration & Clean Energy Technologies Energy Efficiency Summit 2010 Chennai Trade Centre, Chennai Department of Mechanical Engineering Indian
More informationComparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area
Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area MMS DEZFOULI, SOHIF MAT, K.SOPIAN Solar Energy Research Institute (SERI, Universiti
More informationDynamic performance of a novel dew point air conditioning for the UK buildings
*Corresponding author: xudongzhao@nottingham. ac.uk Dynamic performance of a novel dew point air conditioning for the UK buildings... Xudong Zhao *, Zhiyin Duan, Changhong Zhan and Saffa B. Riffat School
More informationA New Dedicated Outdoor Air System with Exhaust Air heat recovery
12 th IEA HEAT PUMP Conference Paper number O1.2.4 A New Dedicated Outdoor Air System with Exhaust Air heat recovery GREATLAB Zi-Yang Zhang, Xiang Cao, Zhi Yang, Liang-Liang Shao, Chun-Lu Zhang, Yue Yu
More informationHVAC 101. The Basics of Heating, Ventilation and Air Conditioning
HVAC 101 The Basics of Heating, Ventilation and Air Conditioning HVAC Heating, Ventilation and Air Conditioning Provides comfort for people Allows humans to exist under adverse conditions. Comfort Comfort
More informationRecent Advances in Energy, Environment and Economic Development
Experimental Investigation of Solar Hybrid Desiccant Cooling System in Hot and Humid Weather of Malaysia MM SALEHI DEZFOULI, Z HASHIM, MH RUSLAN, B BAKHTYAR, K SOPIAN, A ZAHARIM, S MAT, A RACHMAN, Solar
More informationPreliminary Findings on the Performance of a New Residential Solar Desiccant Air-Conditioner
Preliminary Findings on the Performance of a New Residential Solar Desiccant Air-Conditioner Daniel Rowe 1, Stephen White 1, Mark Goldsworthy 1, Thorsten Spillmann 1, Roger Reece 1, Darren Rossington 1,
More informationReview of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386
Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386 Xiaojie LIN 1, Yunho HWANG 1, Reinhard RADERMACHER 1, Saikee OH 2 1 Center for Environmental
More informationEfficient energy recovery in AHU. DOHA, Qatar Timo Schreck Enventus AB, Sweden
Efficient energy recovery in AHU DOHA, Qatar 11.04.2010 Timo Schreck Enventus AB, Sweden Main principles for cooling and dehumidification process in AHU 1. With cooling coil and reheater 2. Energy recovery
More informationTemperature. In the HVAC area, we talk about two kinds of temperatures.
HEATING and COOLING HEATING and COOLING PSYCHROMETRIC CHART Temperature In the HVAC area, we talk about two kinds of temperatures. One is called dry bulb (DB) temperature, a fancy name for the reading
More informationAalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols. Publication date: 2016
Downloaded from vbn.aau.dk on: marts 27, 2019 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress volume 3 Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's
More informationPerformance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy
Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy F. Zhang 1, Y. Yin 1,2* and X. Zhang 1,2 1 School of Energy and Environment Southeast University,
More informationMSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)
MSP WRAP-ARUND MULTIPLE SMALL PLATE DEHUMIDIFICATIN TECHNLGY VS. CNVENTINAL DEHUMIDIFICATIN IN DEDICATED UTDR AIR SYSTEMS (DAS) ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++
More informationEnergy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings
- 1 - Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings Mamoru Hamada, Living Environment Systems Laboratory, Mitsubishi Electric Co., Kamakura, Kanagawa, Japan Naomichi
More informations. Properties for R134a are as follows : Saturated R-134a Superheated R-134a
CHAPTER 9 REFRIGERATION & AIR-CONDITIONING YEAR 2012 ONE MARK Common Data For Q. 1 and Q.2 A refrigerator operates between 120 kpa and 800 kpa in an ideal vapour compression cycle with R-134a as the refrigerant.
More informationS.A. Klein and G.F. Nellis Cambridge University Press, 2011
12.A-1 A mixture of helium and water vapor is flowing through a pipe at T= 90 C and P = 150 kpa. The mole fraction of helium is y He = 0.80. a.) What is the relative humidity of the mixture? b.) What is
More informationDevelopment of compact air heat pump inverter module chiller Air heat pump chiller DT-R(4 units)
Development of compact air heat pump inverter module chiller Air heat pump chiller DT-R(4 units) Takuya ITO Mitsubishi Electric Corporation 1 Biography Belonging The Air-conditioning & Refrigeration systems
More informationReducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling
Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling Aleksandra Cichoń,*, Anna Pacak, Demis Pandelidis, and Sergey Anisimov Department of
More informationThe Energy Consumption Investigation of the Hotel Central. Air-conditioning System and the Research of Energy Saving Measures
Advanced Materials Research Online: 2013-06-27 ISSN: 1662-8985, Vols. 712-715, pp 1614-1618 doi:10.4028/www.scientific.net/amr.712-715.1614 2013 Trans Tech Publications, Switzerland The Energy Consumption
More informationExperimental Research of Air Source Heat Pump Frosting and Defrosting in a. Double Stage-Coupling Heat Pump
Experimental Research of Air Source Heat Pump Frosting and Defrosting in a Double Stage-Coupling Heat Pump Zhiyi Wang Jiansheng Gu Zehua Lu Senior Engineer Engineer Associate Engineer Zhejiang Dun an School
More informationAR/IA/UP 241 Lecture 5: Psychrometrics
Faculty of Architecture and Planning Thammasat University AR/IA/UP 241 Lecture 5: Psychrometrics Author: Asst. Prof. Chalermwat Tantasavasdi 1. Definition of Psychrometric Chart The word psychrometry is
More informationFeasibility study on an energy-saving desiccant wheel system with CO 2 heat pump
IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump To cite this article: Yefeng Liu et al 2018 IOP
More informationReCooler Heat-Pump Energy efficient cooling unit for eq Air Handling Unit
ReCooler Heat-Pump Energy efficient cooling unit for eq Air Handling Unit 28 May 2013 Agenda Introduction to Fläkt Woods Our Product Solution Technical Features Benefits Fläkt Woods Index We save energy!
More informationNew PHE applications in construction & HVAC.
New PHE applications in construction & HVAC Static head isolation Static Head isolation A temperature gradient present in different levels Different sizing of AHU / FCU required Reduces pressure head in
More informationExperimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant
Proceedings of the World Congress on Momentum, Heat and Mass Transfer (MHMT 16) Prague, Czech Republic April 4 5, 216 Paper No. ENFHT 111 DOI: 1.11159/enfht16.111 Experimental Investigation of a Multi
More informationAvailable online at Energy Procedia 6 (2011) MEDGREEN 2011-LB
Available online at www.sciencedirect.com Energy Procedia 6 (2011) 759 768 MEDGREEN 2011-LB Comparison of two methods of improving dehumidification in air conditioning systems: hybrid system (refrigeration
More informationAHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency
Application Note 24 AHRI 920 Performance Rating and Comparisons I NTRODUCTION In 2015, the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) introduced a performance rating for dedicated outside
More information4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)
4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao
More informationMunters Heat Exchangers
Munters Heat Exchangers Brad Perdew Applications Engineer 8/27/12 DOAS Configurations Cheryl Hughes Regional Sales Manager October 11, 2016 cheryl.hughes@munters.com Munters DOAS Configurations Presentation
More informationArticle Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms
Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms Min Suk Jo, Jang Hoon Shin, Won Jun Kim and Jae Weon Jeong * Department of Architectural
More informationAvailable online at ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 7 (215 ) 418 426 International Conference on Solar Heating and Cooling for Buildings and Industry, SHC 214 Theoretical analysis and
More informationCOMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS
- 1 - COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS W. Mittelbach, Managing Director, SorTech AG, Weinbergweg 23, 06120 Halle, Germany T. Büttner, Head of R&D / production, SorTech AG,
More informationAIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University
AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort
More informationPhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi
PhEn-602 Pharmaceutical Facility Design Notes #7 J. Manfredi 1 HVAC Design and the Psychrometric Chart 2 HVAC Considerations Pharmaceutical Facility Design Process 1. SPACE REQUIREMENTS Temperature Humidity
More informationHigh Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO
High Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO 2012 1 Learning Objectives for this Session Get acquainted with typical systems used in the
More information7. MECHANICAL SYSTEM DESIGN
7. MECHANICAL SYSTEM DESIGN The second primary topic of this thesis is to investigate the application of a dedicated outdoor air system (DOAS) to the SLCC. The stated goals for this thesis of improved
More informationContinuous Commissioning: A Valuable Partner to Retrofit Projects
Continuous Commissioning: A Valuable Partner to Retrofit Projects Yeqiao Zhu Aamer Athar Kenneth Banks Ph.D. PE, CEM PE, CEM Energy Systems Laboratory Sempra Energy Solutions Sempra Energy Solutions Charles
More informationResearch on Waste Heat Recovery System for Residential Gas Engine-Driven Heat Pump
Exhaust Research on Waste Heat Recovery System for Residential Gas Engine-Driven Heat Pump Takeshi YOKOYAMA, TECHNOLOGY DEVELOPMENT DEPT, TOKYO GAS CO., LTD, 3-3-, MINAMISENJU, ARAKAWAKU, TOKYO, JAPAN
More informationAdsorption Chillers Energysmart Green Cooling
Adsorption Chillers Energysmart Green Cooling New Partners in innovation Leaders in Dehumidification... Worldwide Power Partner Inc USA www.bryair.com Recover Low Grade Process Waste Heat For Energy Smart
More informationINTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012
HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationShuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan
INDOOR CLIMATE DESIGN BASED ON FEEDBACK CONTROL OF HVAC COUPLED SIMULATION OF CONVECTON, RADIATION, AND HVAC CONTROL FOR ATTAINING GIVEN OPERATIVE TEMPERATURE Shuzo Murakami, Shinsuke Kato, and Taeyeon
More informationHumidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President
Humidity Control Design Tips R. Mark Nunnelly, PE, CxA, LEED AP President AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects
More informationAND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University
Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University 2 Objectives Differentiate between dry air and atmospheric air. Define and calculate
More informationAnnual environmental performance evaluation of light and heat in daylight harvesting systems using Radiance and NewHASP
Annual environmental performance evaluation of light and heat in daylight harvesting systems using Radiance and NewHASP 2017 International Radiance Workshop August 22 24 Portland, Oregon Chikako Ohki and
More informationOptimisation of cooling coil performance during operation stage for improved humidity control
Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 741 Optimisation of cooling coil performance during operation stage for improved humidity control S.C. Sekhar * and L.T. Tan National
More informationEnergyPlus Testing with Global Energy Balance Test
Table of Contents Table of Contents Plus Testing with Global Balance Test 1 Test Objectives and Overview 1.1 Test Type: Comparative 1.2 Test Suite: Plus Global Balance Test Description 1.2.1 Base Case
More information27/11/2015. How does a greenhouse work: humidity. Energiezuinig ontvochtigen. Climate control, humidity
Energiezuinig ontvochtigen How does a greenhouse work: humidity Masterclass 26 november 2 HAS Den Bosch BOGO project Klimaat en energie: nieuwe low input teeltsystem in de tuinbouw F. Kempkes en S. Hemming,
More informationThe Ed Roberts Campus Berkeley, CA
The Ed Roberts Campus Berkeley, CA Anderson Clemenceau Mechanical Option Penn State A.E. Senior Thesis April 14, 2015 Leddy Maytum Stacy Architects, Photo by Tim Griffith ASHRAE Climate Zone 3C 99.6% Heating
More informationAPPLICATION GUIDE BEAMS
BEAMS There is an increasing need for energy efficient air conditioning systems as energy codes become more stringent. Chilled beam systems are one such alternate to traditional all air conditioning systems.
More informationComfort and health-indoor air quality
Comfort and health-indoor air quality 1 The human body has a complicated regulating system to maintain the human body temperature constant most of the time, which is 98.6 F (36.9 C) regardless of the environmental
More informationModule 1: Introduction to Radiant Cooling. Pierre Jaboyedoff
Module 1: Introduction to Radiant Cooling Pierre Jaboyedoff Module 1: Introduction to Radiant Cooling Heat Transfer Basics Human Body Heat Exchange Radiant Cooling Basics Radiant Cooling Suitability? Radiant
More informationOxyvap Evaporative Cooling Applications
Oxyvap Evaporative Cooling Applications Oxycom Fresh Air BV March 9th, 2015 Abstract This paper shows two highly efficient applications of the Oxyvap direct evaporative cooling technology, developed by
More informationR4 Ventures LLC White Paper
R4 Ventures LLC White Paper Preliminary Temperature Performance Evaluation of New Cooling Technologies consisting of the Multistage Evaporative Cooling System (MECS) for Phoenix, AZ; Newark, DE; Houston,
More informationHigh Performance Buildings and Occupant comfort
Nicolaus Copernicus High Performance Buildings and Occupant comfort The Earth moves, in two ways. It rotates on an axis (period = 1 day). It revolves around the sun (period = 1 year). Peter Simmonds, Ph.D.,
More informationAvailable online at ScienceDirect. Energy Procedia 52 (2014 ) Vishal Vadabhat, Rangan Banerjee
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 52 (214 ) 541 551 213 International Conference on Alternative Energy in Developing Countries and Emerging Economies Modeling of Demand
More informationDesign Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System
Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,
More informationEarthWise System Seminar
EarthWise System Seminar Tim Gasper, P.E. Solutions Engineer Brady-Trane Services, Inc. EarthWise Systems? Energy Efficiency Emissions Buildings use 39% of the Primary Energy Consumed in the United States
More informationA study of radiant cooling for a room with daytime application in tropical climate
International Journal of Smart Grid and Clean Energy A study of radiant cooling for a room with daytime application in tropical climate Satinee Wongkee, Surapong Chirarattananon, Pipat Chaiwiwatworakul
More informationHeat Pumps and Public Swimming Pools, a Perfect Match
TOPICAL ARTICLE Heat Pumps and Public Swimming Pools, a Perfect Match M. Zuliani, P. Pattijn - Belgium Public swimming pools have a very high energy consumption, due to high demands of heating and climatisation
More informationSIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I
SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road 517583 AUTONOMOUS QUESTION BANK (DESCRIPTIVE) Subject with Code : Refrigeration and Air Conditioning (16ME8806) Course & Branch:
More informationb.) Technical Information:
Section VI- Strategies a.) Summary: It is important for new construction designers to consider the heating, ventilation, and air conditioning needs within a building. There are many different systems,
More informationSolar Air-Conditioning and Refrigeration - Introduction
- Introduction Hans-Martin Henning Fraunhofer-Institut für Solare Energiesysteme ISE, Freiburg/Germany Workshop April 25, 2007 Aix-les-Bains, FRANCE slide 1 Overview Introduction Technologies Status, Examples
More informationModular Active. Chilled. Beams
Modular Active Chilled Beams How Twa MAC Beams Work Primary air (100% outside air) is dehumidified to between 50-57 F dew point and is used to: control the latent requirements of the space, provide fresh
More informationEnergy Recovery with Cooling and Heating Model ERCH
Energy Recovery with Cooling and Heating Model ERCH 100% Outdoor Air System Dedicated Outdoor Air System 1,000-10,000 cfm 1.75 in. wg External Static Pressure Indirect Gas, Hot Water, Electric Heating,
More informationWhite Paper Dehumidification in Humid Climates - A Theoretical Case Study
White Paper Dehumidification in Humid Climates - A Theoretical Case Study This white paper provides details of a theoretical comparison of operating costs associated with mechanical dehumidification systems
More informationH EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative
A U.S. Environmental Protection Agency survey released in 2007 concluded that IT data centers consumed 61 billion kw of electricity at a total cost of $4.5 billion in 2006. As energy costs continue to
More informationState of the Art of HVAC Technology in Europe and America
Downloaded from orbit.dtu.dk on: Oct 27, 2018 State of the Art of HVAC Technology in Europe and America Olesen, Bjarne W.; Kazanci, Ongun Berk Published in: Proceedings of the World Engineering Conference
More informationOptimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic Algorithm
International Journal of ChemTech Research CODEN (USA): IJCRGG ISSN: 0974-4290 Vol.7, No.01, pp 400-407, 2014-2015 Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic
More informationEnhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning
More informationChapter 10. Passive Cooling Contents
Chapter 10. Passive Cooling Contents 10.1 Introduction to Cooling 10.2 Historical and Indigenous Use of Passive Cooling 10.3 Passive Cooling Systems 10.4 Comfort Ventilation VS Night Flush Cooling 10.5
More information