Engineered for flexibility and performance

Size: px
Start display at page:

Download "Engineered for flexibility and performance"

Transcription

1 Enfinity Large Vertical Water Source Heat Pumps with R-410A Refrigerant Vertical Models LVC Standard Range & LVW Geothermal Range Unit Sizes (6 to 25 Tons) R-410A Refrigerant Catalog Engineered for flexibility and performance

2 The information in this manual supersedes and replaces previous catalogues with regards to Daikin Water Source Heat Pump products. Illustrations cover the general appearance of Daikin products at the time of publication and Daikin reserves the right to make changes in design and construction at anytime without notice. The following are trademarks or registered trademarks of their respective companies: LonTalk from Echelon Corporation, BACnet from ASHRAE, Protocol Selectability, and MicroTech II from Daikin. Page 2 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

3 Contents Introduction... 4 Large Vertical Water Source Heat Pumps... 4 Models LVC & LVW, Sizes (6 to 25 Tons)... 4 Nomenclature... 4 LVC & LVW Features and Options... 5 Refrigeration System... 6 Thermal Expansion Valve... 6 Fan Section... 6 Factory Installed Options... 6 Control Features... 7 Control Choices And Added Functionality... 7 MicroTech III Controller... 8 MicroTech III Operating Features... 8 I/O Expansion Module... 9 MicroTech III Controller with LonWorks or BACnet Communication Module MicroTech III LonWorks Communication Module MicroTech III BACnet Communication Module MicroTech III Controller with Communication Modules Features Applications Unit Location Fan Deck Arrangements Vibration Isolators Ductwork and Attenuation Typical Cooling and Heating Refrigeration Cycles Dual Compressors Systems Boiler / Tower Applications: ARI 320 / ISO Open Loop Well Water Applications: ARI 325 / ISO Closed Loop Geothermal Applications: ARI 330/ISO ISO Performance Data Capacity Data Size 2300 SCFM Size 2300 SCFM (continued) Size 3000 SCFM Size 3000 SCFM (continued) Size 4000 SCFM Size 4000 SCFM (continued) Size 00 SCFM Size 00 SCFM (continued) Size SCFM Size SCFM (continued) Size 96 SCFM Size 96 SCFM Electrical Data Operating Limits Additional information for initial start-up only Correction Factors Airflow Correction Factors Antifreeze Correction Factors Physical Data Performance Curves Dimensional Data LVC/LVW Top Discharge LVC/LVW Top Discharge LVC/LVW Top Discharge LVC/LVW Top Discharge LVC/LVW Top Discharge LVC/LVW Top Discharge LVC/LVW Top Horizontal Discharge 072, 096, LVC/LVW Top Horizontal Discharge 1, 215, Accessories Optional 2" Filter Rack & Return Air Duct Collar Supply and Return Water Hoses Condensate Hose Kit Combination Balancing and Shutoff (Ball) Valves Motorized Valve Field Installed Controls Multiple Unit Control Panel (MUCP) Programmable Electronic Thermostat Non-Programmable, Auto or Manual Changeover Thermostat Optional Remote Sensor MicroTech III Water Source Heat Pump Wall Sensors.46 Optional Water Source Heat Pump Room Wall Sensors Wiring Programmable Electronic Thermostat Wiring Non-Programmable, Auto or Manual Changeover Wiring Optional Remote Sensor Wiring Typical Wiring Diagrams MicroTech III Controller with I/O Expansion Module & Communication Module /230, 4, 5--3 (1.5 hp or less) MicroTech III Controller with I/O Expansion Module & Communication Module /230, 4, 5--3 (greater than 1.5 hp) MicroTech III Controller with I/O Expansion Module & Communication Module /230, 4, 5--3 Unit Size Engineering Specifications Catalog Daikin Large Vertical Water Source Heat Pumps Page 3 of 56

4 Introduction Large Vertical Water Source Heat Pumps Models LVC & LVW, Sizes (6 to 25 Tons) Model LVC (Standard Range: 55 F to 110 F) Model LVW (Geothermal Range: 30 F to 110 F) Large Vertical Water Source Heat Pump units are easily located in equipment rooms or floor-by-floor installations. They can be applied to all building types where it is advantageous to extend the water source heat pump concept to larger or core areas. Each heat pump is factory assembled and run tested for reliability. Service is accomplished through multiple front, back and side access panels. Access is available to all serviceable components. Each unit ships on a wooden skid and covered with plastic to facilitate moving with a fork truck. Two unique frame sizes make up our 6- through 25-ton product line - each with a consistent shape for easy layout of the ductwork, water piping, condensate piping and electrical connections. Units are constructed of heavy gauge G- galvanized steel. The interiors of all framework and panels are covered with 1/2" thick, 1½ lb. dual-density fiberglass insulation. Standard 1" filters are supported by factory-mounted brackets for side removal in either direction. Electrical components are located in the lower section, adjacent to the compressor(s). Knockouts are provided on both sides of the unit to facilitate main power and low voltage wiring through separate holes. Each unit is rated to accept time delay fuses for branch circuit overcurrent protection. Each unit is listed with CETL. The control box is accessible through the compressor section access panel. The control box houses the major operating electrical controls, including the control circuit board(s), transformer, compressor contactor(s), fan contactor(s) and terminal block. Each component is accessible for service or replacement. The standard control for all large capacity units is the MicroTech III controller. The unit controller receives its power from the VA control transformer. A LonWorks or BACnet communication module is available as a selectable option. Nomenclature W LVC B L Y S Y Y F Product Category W = WSHP Product Identifier LVC = Large Vertical - Standard Range LVW = Large Vertical - Geothermal Design Series 1 = A Design 4 = D Design 2 = B Design 5 = E Design 3 = C Design Nominal Capacity 072 = 72,000 BTU/h 096 = 96,000 BTU/h 120 = 120,000 BTU/h 1 = 1,000 BTU/h 215 = 215,000 BTU/h 290 = 290,000 BTU/h Controls B = MicroTech III A = DDC Less Board Network Module Option L = LonWorks Module B = BACnet Module Y = None Voltage D = F = 208/ H = K = 4--3 L = 5--3 N = Reserved Y = None Reserved Y = None Condensate Overflow S = Standard Overflow Sensor Current Sensing Y = None Note: For illustration purposes only. Not all options available with all models. Please consult Daikin Sales Representative for specific availability. Page 4 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

5 LVC & LVW Features and Options MicroTech III Controller I/O Expansion Module LonWorks Communication Module BACnet Communication Module 1 Cabinet - Heavy gauge G- galvanized steel. 2 Insulation - All interior framework and panels are lined with 1/2" thick, 1½ lb. dual-density fiberglass insulation. Optional (IAQ) closed-cell foam insulation. 3 Filter - Standard 1" factory-installed filter rack with 1" throwaway filter. Optional 2" filter rack with duct collar for field -installation. 4 Refrigerant Circuit - All units have a dual refrigerant circuit with scroll compressors, thermal expansion valve, coaxial heat exchanger, finned tube airside coil and reversing valve. 5 Compressor Vibration Isolators - Standard feature for all units, reduces vibration sound levels during compressor operation. 6 Schrader Connections - Four Schrader valves are located inside the end access panel one on the low side and one on the high side of the refrigeration circuit for charging and servicing. All valves are 7/16" SAE fittings. 7 MicroTech III Controllers Designed for flexibility, the control board is used in standalone applications in conjunction with the I/O expansion module for control of the second refrigerant circuit. A separate LonWorks or BACnet communication module can be easily snapped onto the board to allow communication with a building automation system. The control system accomodates the use of a two-stage heat/two-stage cool 7-day programmable or nonprogrammable wall-mounted thermostat, offered as a field-installed option. Electrical - The control enclosure includes fan relay, compressor relays, 24-volt control transformer, reversing valve solenoid coil, lockout circuits and control circuit board. 8 LED Annunciator External LED status lights display fault conditions to provide easy troubleshooting and diagnosis, visible without removing access panel. 9 External Pipe Connections Supply and return pipe connections located outside the cabinet make pipe connections easy without removing access panels. Safety Controls (Not Shown) - Low and high refrigerant pressure switches and low refrigerant suction temperature (freezestat) sensor. Catalog Daikin Large Vertical Water Source Heat Pumps Page 5 of 56

6 LVC & LVW Features & Options Large vertical water source heat pump units are easily located in small equipment rooms or floor-by-floor installations. They can be applied to all building types where it is advantageous to extend the water source heat pump concept to larger or core areas. Each heat pump is factory assembled and run tested for reliability. Service is accomplished through multiple front, back and side access panels. Access is available to all serviceable components. Each unit ships on a wooden skid and covered with plastic to facilitate moving with a fork truck. Two unique frame sizes make up our 6- through 25-ton product line - each with a consistent shape for easy layout of the ductwork, water piping, condensate piping and electrical connections. Units are constructed of G- galvanized steel. The interiors of all framework and panels are covered with 1/2" thick, 1½ lb. dual-density fiberglass insulation. Closed-cell foam (IAQ) insulation is available as a selectable option, suitable for fiberglass-free applications. Multiple 1" filters are supported by factory-mounted brackets for side removal in either direction. Electrical components are located in the lower section, adjacent to the compressor(s). Knockouts are provided on both sides of the unit to facilitate main power and low voltage wiring through separate holes. Each unit is rated to accept time delay fuses for branch circuit overcurrent protection. Each unit is listed with CETL and CE. The control box is accessible through the compressor section access panel. The control box houses the major operating electrical controls, including the control circuit board(s), transformer, compressor contactor(s), fan contactor(s) and terminal block. Each component is accessible for service or replacement. Figure 1: Front View with Access Panel Removed The reversing valve is energized in the heating mode and will fail-safe to the cooling mode, which is the predominant mode of operation. Both heat exchanger components incorporate advancedheat transfer technologies. The coaxial heat exhanger has a copper inner tube and steel outer tube. The large face area coil has copper tubes and aluminum fins. Geothermal units include coil and piping insulation to protect against condensation in low temperature applications. Safety controls on each refrigerant circuit include a suction line temperature sensor, low refrigerant pressure and high pressure switches to lock out compressor operation at extreme conditions. The safety controls can only be reset from the main disconnect switch to prevent unauthorized reset. Each circuit has high and low side refrigerant service valves for refrigerant circuit diagnostics and charging. Thermal Expansion Valve Units include a Thermal Expansion Valve (TXV) for refrigerant metering. The TXV allows the unit to operate at optimum efficiency with fluid temperatures ranging from 25 F to 110 F, and entering air temperatures ranging from 40 F to 90 F. The TXV precisely meters the exact amount of refrigerant flow through the system to meet the load and deliver rated heating and cooling capacity. Fan Section The fan section includes a belt-driven fan assembly, multiple DWDI forward curved fan wheels, solid fan shaft, steel ball bearings, three phase fan motor, adjustable motor sheave, adjustable motor base, fan pulley and insulated divider panel between the compressor section. Unit sizes 072 through 120 have two fan assemblies and unit sizes 1 through 290 have three fan assemblies. The fan motor is always located at the piping end. Figure 2: Belt-Driven Fan Assembly Compartment Refrigeration System All Large Vertical unit sizes have dual independent circuits. Each circuit includes a scroll compressor, reversing valve, water to- refrigerant coaxial heat exchanger, expansion valve, airside coil, and safety controls. The compressor is located adjacent to the compressor access panel and isolated from a bottom panel with rubber isolators. Factory Installed Options Optional high static fan motors are available on each unit size to handle increased CFM and static pressure applications. Page 6 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

7 Control Features Control Choices And Added Functionality The control enclosure houses the major operating electrical controls including the MicroTech III controller and I/O expansion module, control transformer, compressor relays and fan relay. Each component is easily accessed for service or replacement. Three unique control choices are offered with the Micro- Tech III control system: Standalone operation using a MicroTech III controller and I/O expansion module MicroTech III controller and I/O expansion module with a LonWorks communication module MicroTech III controller and I/O expansion module with a BACnet communication module Each option features direct quick-connect wiring to all unit-controlled components for clean wiring inside the control box. Each control circuit board receives power from a VA transformer. Table 1: Control Options Control Description Application Protocol MicroTech III (Standalone) Unit Controller with I/O Expansion Module The MicroTech III controller is a standalone microprocessor-based control board conveniently located in the unit control enclosure for easy accessibility. The board is designed to provide thermostat control of a Water Source Heat Pump using a two-stage wall thermostat. The unit controller provides unit-wide control of the WSHP and control of the first refrigerant circuit. The I/O Expansion Module is an extension of the Microtech III controller and provides control of the second refrigerant circuit. External LED status lights display fault conditions to provide easy troubleshooting and diagnosis of the second circuit. Each unit controller is factory programmed, wired, and tested for complete control of single zone, standalone operation of your Daikin Water Source Heat Pump. Allows for: Control of second refrigeration circuit. Unit-mounted or wall-mounted thermostat Wall-mounted thermostat or sensor LonWorks Communication Module The MicroTech III control system accepts a plug-in LonWorks communication module to provide network communications and added functionality to easily integrate with an existing BAS. The communication module can be factory- or field-installed and is tested with all logic required to monitor and control the unit. Designed to be linked with a centralized building automation system (BAS) through a LonWorks communications network for centralized scheduling and management of multiple heat pumps. LonM ark 3. 4 certified BACnet Communication Module The MicroTech III controller accepts a plug-in BACnet commu nication module to provide network communications and added functionality to easily integrate with an existing BAS. The communication module can be factory- or field-installed and is tested with all logic required to monitor and control the unit. Designed to be linked with a centralized building automation system (BAS) through a BACnet communications network for centralized scheduling and management of multiple heat pumps. BACnet MS/TP Catalog Daikin Large Vertical Water Source Heat Pumps Page 7 of 56

8 Control Features MicroTech III Controller The MicroTech III Controller is a microprocessor-based control board conveniently located in the unit control box for easy access through a removable access panel. The standalone unit controller is a hard wired interface and provides all the necessary field connections. The board can be wired for 24-volt AC output to the wall thermostat by using terminals R & C. An LED annunciator is located on the front of the unit chassis to allow quick check of the unit operating status. MicroTech III Operating Features Assumes cycle fan operation-not continuous fan operation: Start-up The unit will not operate until all the inputs and safety controls are checked for normal conditions. Cooling mode On a call for cooling from the wall thermostat, the controller will energize the fan relay and stage compressors to satisfy the space temperature setpoint. When the load is satisfied, the controller will disable the compressor and fan. Heating Mode On a call for heating from the wall thermostat, the controller will enable the fan, energize circuit one reversing valve and circuit 1 compressor to satisfy the space heating setpoint. If the space temperature setpoint is not satisfield, circuit two reversing valve and circuit 2 compressor will be energized and run until the heating setpoint at the thermostat is satisfied. Random Start Power-up Delay Timer In the event of a building power outage, this feature prevents multiple units from starting simultaneously upon building power restoration. Unoccupied Mode A simple grounded signal between terminals U and C (no power source required), puts the unit into the unoccupied mode for night setback operation. Interstaging Timer A default value of 5 minutes between staging of compressors, this feature minimizes short cycling of compressors and improves comfort. Override Mode A switch on the deluxe automatic changeover thermostat can be activated during the unoccupied mode to put the unit back into the occupied mode for two hours for after-hours heating or cooling. Motorized Valve/Pump Restart The IV/PR (H8) terminals on the The MicroTech III unit controller are used to energize (open) a motorized valve or start a water pump to get water circulating prior to starting the compressor on call for heating or cooling. The IV/ PR (H8) terminal may be daisy chained between a maximum of 200 units. Brownout Protection The MicroTech III unit controller measures the input voltage and will suspend compressor and fan operation if the voltage falls below % of the unit nameplate rated value. A unique LED status is generated. Unit Shutdown A simple grounded signal puts the unit into the shutdown mode. Compressor and fan operations are suspended. A unique LED status is generated. Condensate Overflow Protection The MicroTech III controller incorporates a liquid sensor at the top of the drain pan. Upon sensing water flow, cooling operation is suspended. A unique LED status is generated. Remote Reset of Automatic Lockouts The Remote Reset feature provides the means to remotely reset automatic lockouts generated by high-pressure and/ or low-temperature faults. When the MicroTech III controller is in automatic lockout due to one of these faults, and the cause of the fault condition has been alleviated, energizing the O-terminal for 10 seconds or more will force the control board to clear the lockout. A unit power cycle can also be used to clear an automatic lockout if the conditions causing the fault have been alleviated. Intelligent Reset The Fault Retry feature helps to minimize nuisance trips of automatic lockouts caused by high-pressure and/or low-temperature faults. This feature clears faults the first two times they occur within a 24-hour period and triggers an automatic lockout on the 3rd fault. The retry count is reset to zero every 24 hours. Equipment Protection Control The MicroTech III controller receives separate input signals from the refrigerant high-pressure switch and the low suction line temperature sensor. In a high-pressure situation, compressor operation is suspended. In a low temperature situation, the unit goes into a defrost cycle where the unit is put into cooling operation for seconds until the coaxial heat exchanger is free of ice. Each switch generates its own unique LED status. Page 8 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

9 Control Features Note: Most unit fault conditions are the result of operating the equipment outside the unit specifications. Table 2: MicroTech III Controller LED & Fault Outputs Status LED s Thermostat Alarm Mode / Fault Light Yellow Green Red Output-Terminal A Occupied, Bypass, Standby, or Tenant Off On Off Energized Override Unoccupied On On Off Energized Condensate Overflow On Off Off De-energized High Pressure 1 Fault Off Off Flash De-energized Low Pressure 1 Fault Off Off On De-energized Low Temperature 1 Fault Flash Off Off De-energized Brownout Off Flash Off De-energized Emergency Shutdown Off Flash Off De-energized Room/Return Air or Low Temp Sensor 1 Failure Flash Flash On De-energized Service Test Mode Enabled 1 Serial EEPROM Corrupted Network Offline Received Flash Flash Flash De-energized On On On De-energized Off Off Off De-energized Note: 1 Compressor relay/compressor terminal is labeled COMP, switched line of the same electric input as any of the L1 terminals. I/O Expansion Module Table 3: I/O Expansion Module LED & Fault Mode / Fault Invalid Configuration Jumper Setting Base Board Communication Fail Status LED's Yellow Green Red Thermostat Alarm Light Output Terminal A Flash Flash Off De-energized Off Flash Flash N/A High Pressure #2 Fault Off Off Flash De-energized Low Pressure #2 Fault Off Off On De-energized Low Suction Temp #2 Fault Flash Off Off De-energized Sensor Failures Low Suction Low Suction Temp #2, Flash Flash On De-energized 1 EWT (w/ Boilerless EH only) 2 Service Test Mode Enabled Flash Flash Flash De-energized Unoccupied Mode On On Off Energized Occupied, Bypass, Standby, or Tenant Off On Off Energized Override Modes Normal Operation Off On Off De-energized Note: Mode / Faults are listed in order of priority. 1 Boilerless electric heat only 2 Alarm/fault LED indications take precedence over service test mode LED indication. The controller shall use service test mode if the service test mode jumper is installed, even if the LED s indicate an alarm/fault. Figure 3: I/O Expansion Module Configuration Jumper Terminals The I/O Expansion Module is factory-installed for control of the second refrigeration circuit. The I/O Expansion Module has an independent LED annunciator to identify operational fault conditions for the electric heater. Jumper Terminals JP1 shorted in units with 2 compressors JP1 through JP8 not used with 2 circuit units. Catalog Daikin Large Vertical Water Source Heat Pumps Page 9 of 56

10 Control Features MicroTech III Controller with LonWorks or BACnet Communication Module Each Enfinity Large Vertical and Horizontal Water Source Heat Pump can be equipped with a LonWorks or BACnet communication module. The LonWorks module is Lon- Mark 3.4 certified and designed to communicate over a LonWorks communications network to a Building Automation System (BAS). The BACnet module is designed to communicate over a BACnet MS/TP communications network to a building automation system. Both controllers are microprocessor-based and can be factory or field-installed. The control modules are programmed and tested with all the logic required to monitor and control the unit. Optional wall sensors may be used with the communication modules to provide limited local control of the Horizontal Water Source Heat Pump. The MicroTech III controller monitors water and air temperatures and passes information to the communication module. The module communicates with the BAS, to provide network control of the Water Source Heat Pump. MicroTech III LonWorks Communication Module The LonWorkss communication module is designed for units that are integrated into a LonWorks communication network for centralized scheduling and management of multiple heat pumps. MicroTech III Controller with Communication Modules Features The MicroTech III Controller with LonWorks or BACnet Communication Module orchestrates the following unit operations: Enable heating and cooling to maintain space temperature setpoint based on a room sensor setting Enable fan and compressor operation Monitors all equipment protection controls Monitors room and discharge air temperatures Monitors leaving water temperature Relays status of all vital unit functions An amber, on-board status LED indicates the status of the MicroTech III LonWorks or BACnet module. The MicroTech III unit controller with communication module includes: Return Air Temperature sensor (RAT) (field-installed) Discharge Air Temperature sensor (DAT) (field-installed) Leaving Water Temperature sensor (LWT) CAUTION When an optional wall-mounted room temperature sensor is connected to the unit controller, the Return Air Temperature (RAT) sensor must not be installed. A wall-mounted room temperature sensor and the return air temperature sensor must not be connected simultaneously or the unit will not operate properly. The communication modules provide network access to setpoints for operational control MicroTech III BACnet Communication Module Designed to be linked with a centralized building automation system (BAS) through a BACnet communications network for centralized scheduling and management of multiple heat pumps. Available Wall Sensors Include: Room sensor Room sensor with LED status and tenant override button Temperature sensor with LED status, timed-override button, and ±3 F setpoint adjustment Room sensor with LED status, timed-override button, 55 to 90 F setpoint adjustment Page 10 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

11 Applications Unit Location Large Vertical Water Source Heat Pump units are easily located in equipment rooms or floor-by-floor installations. They can be applied to all building types where it is advantageous to extend the water source heat pump concept to larger or core areas. Locate the unit in an area that allows for easy removal of the filter and access panels, and has enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connections. The main control panel is located in the center front of the unit. The fan discharge is top front, and the fan motor is always located at the piping end. Unit sides opposite the control panel and opposite the piping side may be up against walls and still allow for service and maintenance through the remaining access panels. Figure 5: Fan Deck Arrangements Figure 4: Service Clearances Side B Fan Motor Side A 24" (610 mm) Piping Location 24" (610 mm) Control Box Location The contractor should make sure that access has been provided including clearance for 2" (51 mm) thick filter brackets, duct collars and fittings at water and electrical connections. Allow adequate room around the unit for a condensate trap. The unit can be installed free standing in an equipment room. Generally, the unit is located in a separate room with the non-ducted return air facing the return air intake. Alternatively, the unit can have a ducted return air. It is recommended that the unit be located on vibration isolators to reduce any vibration (see Figure 6 on page 12). Rear (or Top) Discharge Right-Hand Piping (Upblast-Rear) Front (or Top) Discharge Right-Hand Piping (Upblast-Front) Fan Motor Front (or Top) Discharge Left-Hand Piping (Upblast-Front) IMPORTANT 1. A 24" (610 mm) minimum clearance is required on the return air, control box and piping sides. However, a 36" (914 mm) clearance allows for easier serviceability. 2. A 12" (305 mm) minimum clearance is required on Side A to gain access to panel to remove locking collar for shaft removal. 3. A 6" (152 mm) clearance is required on Side B to remove screws holding top panel. 4. Top clearance is required for fan shaft removal. 5. Some codes dictate a " (1524 mm) clearance above the control box which could be violated with a ducted return. Check your local codes. Fan Deck Arrangements Six fan discharge arrangements and two piping arrangements are available. With the return air side defined as the front of the unit, the water piping connections may be right-hand (side) or left-hand. All units have a single supply and return water connection with a copper FPT type fitting that protrudes through the unit casing for easy connection. The condensate connection is also a copper FPT type and is located on both sides of the unit. The unused connection is plugged. Rear (or Top) Discharge Left-Hand Piping (Upblast & Rear) Straight Horizontal Discharge Left-Hand Piping (Top-Horizontal Discharge) Straight Horizontal Discharge Right-Hand Piping (Top-Horizontal Discharge) Notes: 1. The hand of unit is determined by looking at the return air (filter) side. The piping and electrical connections are always made on the hand side of the unit. The return air (filter) side is considered the front of the unit. 2. The fan motor is always located at the piping/ electrical connection (hand) side of the unit. Catalog Daikin Large Vertical Water Source Heat Pumps Page 11 of 56

12 Applications Vibration Isolators For minimum sound and vibration transmission, it is recommended that the unit be mounted on vibration isolators. Holes are provided in the bottom panel to facilitate connection of isolators (see Figure 6 & Figure 7 for hole locations). Isolators supplied by the manufacturer are the type shown in Figure 6. Four white isolators are used for single compressor units and six green isolators are used for dual compressor units. The holes in the bottom of the unit allow for a 3 8" (10 mm) bolt to be secured to the isolator. Figure 6: Vibration Isolator Dimensions 2⅝" (61 mm) 7/16" (11 mm) 3/8" (10 mm) TAP 4½" (114 mm) 5½" (140 mm) 2½" (64 mm) Figure 7: Vibration Isolators Locations - Single Compressor Unit 3" (76 mm) A A 7 /16" (11 mm) 28 5 /32" (5 mm) (4) 7 /16" (11 mm) holes 2" (51 mm) Section A-A 1 /4" (6 mm) 3" (76 mm) 3" (76 mm) 3" (76 mm) /32" (1390 mm) Figure 8: Vibration Isolators Locations - Dual Compressor Unit 2" (51 mm) 30 1 /8" (765 mm) (6) 3 /8" (19 mm) holes 2" (51 mm) 3 1 /4" (83 mm) 3 1 /4" (83 mm) (1021 mm) 3 /8" (2042 mm) 40 3 /16" Page 12 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

13 Applications Ductwork and Attenuation Discharge ductwork is normally used with these conditioners. Return air ductwork may also be required but will require field installation of a return air duct collar. All ductwork should conform to industry standards of good practice as described in ASHRAE Systems Guide. The discharge duct system will normally consist of a flexible connector, a transition piece to the final duct size, a short run of duct, an elbow without vanes and a trunk duct tee d into branch ducts with discharge diffusers. Transformation duct must not have angles totalling more than 30 degrees or severe loss of air performance can result. All units have multiple fan outlets. The preferred method for minimum static pressure loss would be individual ducts at each outlet connected to a larger main duct downstream (Figure 9). For minimum noise transmission, the metal duct material should be internally lined with acoustic fibrous insulation. The ductwork should be laid out so that there is no line of sight between the conditioner discharge and the distribution diffusers. Return air ducts can be brought in adjacent to the return air of the conditioner. Typically, the equipment room becomes the common return air plenum. Do not insert sheetmetal screws directly into the unit cabinet for connection of supply or return air ductwork, especially return air ductwork which can hit the drain pan or the air coil. Notes: 1. Transformations to supply duct have maximum slope of 1" to 7". 2. Square elbows with double thickness vanes may be substituted. 3. Do not install ducts so that the air flow is counter to fan rotation. If necessary, turn fan deck assembly and motor. 4. Transformations and units shall be adequately supported so no weight is on the flexible connection. Figure 9: Suggested Supply Ducting per ASHRAE and SMACNA Publications Flexible Connector Note 2 Note 1 Note 1 Note 2 Note 1 Note 2 Flexible Connector Flexible Connector Fan Rotation (See Note 3) Fan Rotation (See Note 3) Fan Rotation (See Note 3) Transformation Duct Flexible Connector Note 2 Main Duct Branch Duct Fan Rotation (See Note 3) Distribution Diffuser Trunk Duct Catalog Daikin Large Vertical Water Source Heat Pumps Page 13 of 56

14 Applications Typical Cooling and Heating Refrigeration Cycles Dual Compressors Note: Typical temperature readings are at full load conditions at ISO for boiler-tower applications. Figure 10: Cooling Refrigeration Cycle When the wall thermostat calls for COOLING, the reversing valve (de-energized) directs the flow of the refrigerant, a hot gas, from the compressor to the water-to-refrigerant heat exchanger (coaxial heat exchanger). There, the heat is removed by the water, and the hot gas condenses to become a liquid. The liquid then flows through a thermal expansion valve to the air-to-refrigerant heat exchanger coil (evaporator). The liquid then evaporates and becomes a gas, at the same time absorbing heat and cooling the air passing over the surfaces of the coil. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle. Figure 11: Heating Refrigeration Cycle When the wall thermostat calls for HEATING, the reversing valve (energized) directs the flow of the refrigerant, a hot gas, from the compressor to the air-to-refrigerant heat exchanger coil (condenser). There, the heat is removed by the air passing over the surfaces of the coil and the hot gas condenses and becomes a liquid. The liquid then flows through a thermal expansion valve to the water-to-refrigerant heat exchanger (evaporator). The liquid then evaporates and becomes a gas, at the same time absorbing heat and cooling the water. The refrigerant then flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle. Page 14 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

15 Applications Systems Water source heat pump systems are one of the most efficient, environmentally friendly systems available for heating and cooling buildings. High-efficiency, self contained units (sizes 7,000 btuh to 290,000 btuh) can be placed in virtually any location within a building. Each unit responds only to the heating or cooling load of the individual zone it serves. This permits an excellent comfort level for occupants, better control of energy use for building owners and lower seasonal operating costs. The Air-Conditioning Refrigeration Institute (ARI) and the International Standards Organization (ISO) publish standards so that water source heat pumps are rated for specific applications. The ARI/ISO loop options shown in this catalog are typical water source heat pump loop choices available in today s market. These systems offer benefits ranging from low cost installation to the highest energy efficiency available in the market today. Boiler / Tower Applications: ARI 320 / ISO A Boiler/Tower application uses a simple two-pipe water circulating system that adds heat, removes heat or transfers rejected heat to other units throughout the building. The water temperature for heating is generally maintained between 65ºF ºF and is usually provided by a natural gas or electric boiler located in a mechanical room. The condensing water temperature, during cooling months, is maintained between ºF and 95ºF and requires the use of a cooling tower to dissipate waste heat. Cooling towers can be located on the roof, or inside or adjacent to the building. This application can be the lowest cost of the loop options available. Note: ASHRAE 90.1 standards require that circulating pumps over 10 HP will require use of variable frequency drive equipment and pipe insulation to be used whenever water temperatures are below degrees and above 105 degrees. See ASHRAE 90.1 Standards for details. Figure 12: Boiler/Tower Application Open Loop Well Water Applications: ARI 325 / ISO Open Loop well water systems use ground water to remove or add heat to the interior water loop. The key benefit of an open loop system is the constant water temperature, usually 50ºF to ºF, which provides efficient operation at a low first cost. Most commercial designers incorporate a heat exchanger to isolate the building loop from the well water. Using heat exchangers can reduce maintenance issues while still allowing the transfer of heat from unit to unit as with the Boiler/Tower System. A successful design provides an ample amount of groundwater (approximately 2 GPM per ton) and adequate provisions for discharging water back to the aquifer or surface. Open Loop applications are commonly used in coastal areas where soil characteristics allow reinjection wells to return the water back to the aquifer. Note that some states have requirements on the depths of return water reinjection wells, and such wells must be approved by the United States Environmental Protection Agency. Also, bad water quality can increase problems with heat exchanger scaling. Suspended solids can erode the heat exchanger. Strainers can be used to contain suspended solids. Figure 13: Open Loop Well Application Catalog Daikin Large Vertical Water Source Heat Pumps Page 15 of 56

16 Applications Closed Loop Geothermal Applications: ARI 330/ISO Vertical Closed Loop applications are installed by drilling vertical bore holes into the earth and inserting a plastic polyethylene supply/return pipe into the holes. The vertical wells are connected in parallel reverse return fashion to allow the water from the building to circulate evenly throughout the borefield. The circulating fluid dissipates heat to the ground in a similar manner as a tower and adds heat back to the loop like a boiler. If properly designed, the loop field can maintain the loop temperatures necessary to condition the building without the use of a boiler or a tower. Loop temperatures usually range from 37ºF to 95ºF in Northern climates. Southern applications can see temperatures ranging from 40ºF to 100ºF. The number of bore holes and their depth should be determined by using commercial software that is specifically designed for vertical geothermal applications. Typical bore depths of a vertical loop range from 150 to 400 feet and generally require about 250 feet of surface area per ton of cooling. Figure 14: Vertical Loop Application Figure 15: Horizontal Loop Application A Surface Water or Lake closed loop system is a geothermal loop that is directly installed in a lake or body of water that is near the building. In many cases, the body of water is constructed on the building site to meet drainage or aesthetic requirements. Surface loops use bundled polyethylene coils that are connected in the same manner as a vertical or horizontal loop using a parallel reverse return design. The size and the depth of the lake is critical. Commercial design services should be used to certify that a given body of water is sufficient to withstand the building loads. Loop temperatures usually range from 35ºF to 90ºF and prove to be the best cooling performer and lowest cost loop option of the three geothermal loops. Some applications may not be good candidates due to public access or debris problems from flooding. Figure 16: Surface Water Loop Application A closed loop Horizontal geothermal application is similar to a vertical loop application with the exception that the loops are installed in trenches approximately 5 feet below the ground surface. The piping may be installed using a four-pipe or six-pipe design and could require 1,500 to 2,000 square feet of surface area per ton of cooling. Loop temperatures for a commercial application can range from 35ºF to 95ºF in Northern climates. Southern climates can see temperatures ranging from 40ºF to 100ºF. Horizontal loops are generally not applied in urban areas because land use and costs can be prohibitive. New advances in installation procedures have improved the assembly time of horizontal loops while keeping the first cost lower than a vertical loop. Page 16 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

17 ISO Performance Data Table 4: Water Loop Airflow Waterflow Cooling Heating Unit Size Voltage CFM L/S GPM L/S Btuh Watts EER COP Btuh Watts COP Table 5: Ground Loop Airflow Waterflow Cooling Heating Unit Size Voltage CFM L/S GPM L/S Btuh Watts EER COP Btuh Watts COP Catalog Daikin Large Vertical Water Source Heat Pumps Page 17 of 56

18 ISO Performance Data Table 6: Ground Source Airflow Waterflow Cooling Heating Unit Size Voltage CFM L/S GPM L/S Btuh Watts EER COP Btuh Watts COP NA NA NA = Not Available Page 18 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

19 Catalog Daikin Large Vertical Water Source Heat Pumps Page 19 of 56 EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Capacity Data Size 2300 SCFM

20 Capacity Data Size 2300 SCFM (continued) EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Notes: 1. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. 2. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 3. See performance correction tables for operating conditions other than those listed above. 4. Interpolation is permissible; extrapolation is not. 5. For performance data outside the EAT listed, refer to the Daikin Selection Tools selection program 6. Tables do not reflect fan or pump power corrections for AHRI/ISO conditions. EWT ( F) = Entering Water Temperature GPM = Water flow rate in Gallons Per Minute WPD (ft. of Water) = Water Pressure Drop EAT ( F), Cooling = Entering Air Temperature, Dry Bulb-Wet Bulb EAT ( F), Heating = Entering Air Temperature, Dry Bulb-Wet Bulb Total (Btu/hr) = Total Cooling/Heating Capacity Sensible (Btu/hr) = Sensible Cooling Capacity Power Input (kw) = Total Power Input to unit THR (Btu/hr) = Total Heat of Rejection EER = Energy Efficiency Ratio THA (Btu/hr) = Total Heat of Absorption LAT ( F) = Leaving Air Temperature COP = Coefficient of Performance Page 20 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

21 Catalog Daikin Large Vertical Water Source Heat Pumps Page 21 of 56 EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Cooling Capacity Data Size 3000 SCFM Operation Not Recommended

22 Capacity Data Size 3000 SCFM (continued) EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Notes: 1. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. 2. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 3. See performance correction tables for operating conditions other than those listed above. 4. Interpolation is permissible; extrapolation is not. 5. For performance data outside the EAT listed, refer to the Daikin Selection Tools selection program 6. Tables do not reflect fan or pump power corrections for AHRI/ISO conditions. EWT ( F) = Entering Water Temperature GPM = Water flow rate in Gallons Per Minute WPD (ft. of Water) = Water Pressure Drop EAT ( F), Cooling = Entering Air Temperature, Dry Bulb-Wet Bulb EAT ( F), Heating = Entering Air Temperature, Dry Bulb-Wet Bulb Total (Btu/hr) = Total Cooling/Heating Capacity Sensible (Btu/hr) = Sensible Cooling Capacity Power Input (kw) = Total Power Input to unit THR (Btu/hr) = Total Heat of Rejection EER = Energy Efficiency Ratio THA (Btu/hr) = Total Heat of Absorption LAT ( F) = Leaving Air Temperature COP = Coefficient of Performance Page 22 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

23 Catalog Daikin Large Vertical Water Source Heat Pumps Page 23 of 56 EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Capacity Data Size 4000 SCFM

24 Capacity Data Size 4000 SCFM (continued) EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Notes: 1. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. 2. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 3. See performance correction tables for operating conditions other than those listed above. 4. Interpolation is permissible; extrapolation is not. 5. For performance data outside the EAT listed, refer to the Daikin Selection Tools selection program 6. Tables do not reflect fan or pump power corrections for AHRI/ISO conditions. EWT ( F) = Entering Water Temperature GPM = Water flow rate in Gallons Per Minute WPD (ft. of Water) = Water Pressure Drop EAT ( F), Cooling = Entering Air Temperature, Dry Bulb-Wet Bulb EAT ( F), Heating = Entering Air Temperature, Dry Bulb-Wet Bulb Total (Btu/hr) = Total Cooling/Heating Capacity Sensible (Btu/hr) = Sensible Cooling Capacity Power Input (kw) = Total Power Input to unit THR (Btu/hr) = Total Heat of Rejection EER = Energy Efficiency Ratio THA (Btu/hr) = Total Heat of Absorption LAT ( F) = Leaving Air Temperature COP = Coefficient of Performance Page 24 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

25 Catalog Daikin Large Vertical Water Source Heat Pumps Page 25 of 56 EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Capacity Data Size 00 SCFM

26 Capacity Data Size 00 SCFM (continued) EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Notes: 1. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. 2. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 3. See performance correction tables for operating conditions other than those listed above. 4. Interpolation is permissible; extrapolation is not. 5. For performance data outside the EAT listed, refer to the Daikin Selection Tools selection program 6. Tables do not reflect fan or pump power corrections for AHRI/ISO conditions. EWT ( F) = Entering Water Temperature GPM = Water flow rate in Gallons Per Minute WPD (ft. of Water) = Water Pressure Drop EAT ( F), Cooling = Entering Air Temperature, Dry Bulb-Wet Bulb EAT ( F), Heating = Entering Air Temperature, Dry Bulb-Wet Bulb Total (Btu/hr) = Total Cooling/Heating Capacity Sensible (Btu/hr) = Sensible Cooling Capacity Power Input (kw) = Total Power Input to unit THR (Btu/hr) = Total Heat of Rejection EER = Energy Efficiency Ratio THA (Btu/hr) = Total Heat of Absorption LAT ( F) = Leaving Air Temperature COP = Coefficient of Performance Page 26 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

27 Catalog Daikin Large Vertical Water Source Heat Pumps Page 27 of 56 EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Capacity Data Size SCFM

28 Capacity Data Size SCFM (continued) EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Notes: 1. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. 2. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 3. See performance correction tables for operating conditions other than those listed above. 4. Interpolation is permissible; extrapolation is not. 5. For performance data outside the EAT listed, refer to the Daikin Selection Tools selection program 6. Tables do not reflect fan or pump power corrections for AHRI/ISO conditions. EWT ( F) = Entering Water Temperature GPM = Water flow rate in Gallons Per Minute WPD (ft. of Water) = Water Pressure Drop EAT ( F), Cooling = Entering Air Temperature, Dry Bulb-Wet Bulb EAT ( F), Heating = Entering Air Temperature, Dry Bulb-Wet Bulb Total (Btu/hr) = Total Cooling/Heating Capacity Sensible (Btu/hr) = Sensible Cooling Capacity Power Input (kw) = Total Power Input to unit THR (Btu/hr) = Total Heat of Rejection EER = Energy Efficiency Ratio THA (Btu/hr) = Total Heat of Absorption LAT ( F) = Leaving Air Temperature COP = Coefficient of Performance Page 28 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

29 Catalog Daikin Large Vertical Water Source Heat Pumps Page 29 of 56 EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Capacity Data Size 96 SCFM

30 Capacity Data Size 96 SCFM EWT GPM WPD Cooling Heating EA (DB/WB) TOT SEN kw EER THR EA (DB) TOT kw COP THA Operation Not Recommended Notes: 1. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution. 2. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 3. See performance correction tables for operating conditions other than those listed above. 4. Interpolation is permissible; extrapolation is not. 5. For performance data outside the EAT listed, refer to the Daikin Selection Tools selection program 6. Tables do not reflect fan or pump power corrections for AHRI/ISO conditions. EWT ( F) = Entering Water Temperature GPM = Water flow rate in Gallons Per Minute WPD (ft. of Water) = Water Pressure Drop EAT ( F), Cooling = Entering Air Temperature, Dry Bulb-Wet Bulb EAT ( F), Heating = Entering Air Temperature, Dry Bulb-Wet Bulb Total (Btu/hr) = Total Cooling/Heating Capacity Sensible (Btu/hr) = Sensible Cooling Capacity Power Input (kw) = Total Power Input to unit THR (Btu/hr) = Total Heat of Rejection EER = Energy Efficiency Ratio THA (Btu/hr) = Total Heat of Absorption LAT ( F) = Leaving Air Temperature COP = Coefficient of Performance Page 30 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

31 Catalog Daikin Large Vertical Water Source Heat Pumps Page 31 of 56 Unit Size Voltage/Hz/Phase Fan Compressor 1 Compressor 2 Fan Motor Total Unit Minimum Min. Circuit Maximum Motor (HP) RLA LRA RLA LRA FLA FLA Voltage Amps Fuse Size Electrical Data Table 7: Large Vertical Unit

32 Operating Limits Table 8: Air Limits - F (English units) Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating Min. Ambient Air 50ºF 50ºF 40ºF 40ºF Normal Ambient Air ºF ºF ºF ºF Max Ambient Air 100ºF ºF 100ºF ºF Min. Entering Air 1,2 50ºF 50ºF 50ºF 40ºF Normal Entering Air db/wb /ºF ºF /ºF ºF Max Entering Air db/wb 1,2 100/83ºF ºF 100/83ºF ºF Table 9: Air Limits - C (SI units) Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating Min. Ambient Air 10ºC 10ºC 5ºC 5ºC Normal Ambient Air 27ºC 21ºC 27ºC 21ºC Max Ambient Air 38ºC 29ºC 38ºC 29ºC Min. Entering Air 1,2 10ºC 10ºC 10ºC 5ºC Normal Entering Air db/wb 27/19ºC 21ºC 27/19ºC 21ºC Max Entering Air db/wb 1,2 38/28ºC 27ºC 38/28ºC 27ºC Table 10: Water - F (English units) Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating Min. Entering Water 1,2 55ºF 55ºF 30ºF 20ºF Normal Entering Water ºF ºF 77ºF 40ºF Max Entering Water 110ºF 90ºF 110ºF 90ºF Table 11: Water - C (SI units) Standard Range Geothermal Range Units Units Cooling Heating Cooling Heating Min. Entering Water 1,2 13ºC 13ºC -1ºC -6ºC Normal Entering Water 29ºC 21ºC 25ºC 4ºC Max Entering Water 43ºC 32ºC 43ºC 32ºC Notes: 1. At AHRI flow rate 2. Maximum and minimum values may not be combined. If one value is at maximum, the other two conditions may not exceed the normal condition for standard units. Extended range units may combine any two maximum conditions, but not more than two, with all other conditions being normal conditions. Environment This equipment is designed for indoor installation only. Sheltered locations such as attics, garages, etc., generally will not provide sufficient protection against extremes in temperature and/or humidity, and equipment performance, reliability, and service life may be adversely affected. Power supply A voltage variation of +/-10% of nameplate voltage is acceptable. Three-phase system imbalance shall not exceed 2%. Additional information for initial start-up only Standard range units: Units are designed to start in an ambient of 50ºF (10ºC), with entering air at 50ºF (10ºC), with entering water at ºF (21ºC), with both air and water at the flow rates used in the ISO rating test, for initial start-up in winter. Note: This is not a normal or continuous operating condition. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature. Geothermal range units: Geothermal range heat pump conditioners are designed to start in an ambient of 40ºF (5ºC), with entering air at 40ºF (5ºC), with entering water at 40ºF (5ºC), with both air and water at the flow rates used in the ISO rating test, for initial start-up in winter. Note: This is not a normal or continuous operating condition. It is assumed that such a start-up is for the purpose of bringing the building space up to occupancy temperature. Page 32 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

33 Airflow Correction Factors Table 12: Airflow Correction Factors Total Cooling Capacity Sensible Cooling Capacity kw - Cooling Total Heat of Rejection Total Heating Capacity kw - Heating Total Heat of Absorption Correction Factors Percent of Nominal Airflow Total Cooling Capacity Sensible Cooling Capacity kw - Cooling Total Heat of Rejection Total Heating Capacity kw - Heating Total Heat of Absorption Percent of Nominal Airflow Total Cooling Capacity Sensible Cooling Capacity kw - Cooling Total Heat of Rejection Total Heating Capacity kw - Heating Total Heat of Absorption Percent of Nominal Airflow Antifreeze Correction Factors Table 13: Ethylene Glycol 10% 20% 30% 40% 50% Cooling Capacity Heating Capacity Pressure Drop Table 14: Propylene Glycol 10% 20% 30% 40% 50% Cooling Capacity Heating Capacity Pressure Drop Table 15: Methanol 10% 20% 30% 40% 50% Cooling Capacity Heating Capacity Pressure Drop Table 16: Ethanol 10% 20% 30% 40% 50% Cooling Capacity Heating Capacity Pressure Drop Catalog Daikin Large Vertical Water Source Heat Pumps Page 33 of 56

34 Physical Data Table 17: Large Vertical Size Unit Size Fan Wheel - D x W (In.) (2) 13 3 /16" 12 5 /8" (2) 13 3 /16" 12 5 /8" (2) 13 3 /16" 12 5 /8" (3) 13 3 /16" 12 5 /8" (3) 13 3 /16" 12 5 /8" (3) 13 3 /16" 12 5 /8" Fan Motor Horsepower Standard Static High Static Coil Face Area (Sq. Ft.) Coil Rows Refrigerant Charge (Oz.) Compressor Compressor Filter, (Qty.) Size (In.) (4) 16" 25 1" (4) 16" 25 1" (4) 16" 25 1" (6) 20" 25 1" (6) 20" 25 1" (6) 20" 25 1" Water Connections, Female NPT 1 1 /4" FPT 1 1 /4" FPT 1 1 /4" FPT 1 1 /2" FPT 1 1 /2" FPT 1 1 /2" FPT Condensate Connections, Female NPT 1" 1" 1" 1 1 /4" 1 1 /4" 1 1 /4" Weight, Operating (Lbs.) Weight, Shipping (Lbs.) Page 34 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

35 Performance Curves Figure 17: Large Vertical Size 072, 096 (Includes allowance for dry coil and filter) EXTERNAL STATIC PRESSURE (INCHES OF WATER) RPM 0 RPM 1000 RPM 1200 RPM 11 2 HP 2 HP 1400 RPM 0 0 1,000 2,000 3,000 4,000 5,000 6,000 CFM Note: For wet coil face velocity (cfm coil face area, sq. ft.). Add the following static to the external static pressure for the corresponding face velocity: 300 fpm =.20"; 400 fpm =.31"; 500 fpm =.44". Re-enter table at the increased external static pressure to determine final cfm. Motor and Drive Selections: Unit Size 072 Unit Size hp: RPM 1.5 hp: 7-9 RPM Do Not Select 2 hp: RPM 2 hp: RPM Figure 18: Large Vertical Size 120 (Includes allowance for dry coil and filter) EXTERNAL STATIC PRESSURE (INCHES OF WATER) RPM 1000 RPM 1200 RPM 1400 RPM 0 1,000 2,000 3,000 4,000 5,000 6,000 CFM Note: For wet coil face velocity (cfm coil face area, sq. ft.). Add the following static to the external static pressure for the corresponding face velocity: 300 fpm =.27"; 400 fpm =.41"; 500 fpm =.58". Re-enter table at the increased external static pressure to determine final cfm. Motor and Drive Selections: Unit Size hp: RPM Do Not Select 3 hp: RPM 2 HP 3 HP Catalog Daikin Large Vertical Water Source Heat Pumps Page 35 of 56

36 Performance Curves Figure 19: Large Vertical Size 1, 215 EXTERNAL STATIC PRESSURE (INCHES OF WATER) RPM 0 RPM 1000 RPM 1200 RPM 1400 RPM 0 0 2,000 4,000 6,000 8,000 10,000 12,000 CFM Note: For wet coil face velocity (cfm coil face area, sq. ft.). Add the following static to the external static pressure for the corresponding face velocity: 300 fpm =.20"; 400 fpm =.31"; 500 fpm =.44". Re-enter table at the increased external static pressure to determine final cfm. Motor and Drive Selections: Unit Size 1 Unit Size hp: RPM 3 hp: RPM Do Not Select 5 hp: RPM 5 hp: 9-11 RPM 3 HP 5 HP Table 18: Large Vertical Size 290 EXTERNAL STATIC PRESSURE (INCHES OF WATER) RPM 1000 RPM 1200 RPM 1400 RPM 0 0 2,000 4,000 6,000 8,000 10,000 12,000 CFM Note: For wet coil face velocity (cfm coil face area, sq. ft.). Add the following static to the external static pressure for the corresponding face velocity: 300 fpm =.27"; 400 fpm =.41"; 500 fpm =.58". Re-enter table at the increased external static pressure to determine final cfm. Motor and Drive Selections: Unit Size hp: RPM Do Not Select 10 hp: RPM 2 HP 10 HP Page 36 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

37 Dimensional Data LVC/LVW Top Discharge 072 Figure 20: Large Vertical Size 072 Front View Left Hand Piping Right Hand Piping Overall Unit Dimensions: 54⅝" W 55¾" H 28" D Electrical Knockouts LVC/LVW Top Discharge 096 Figure 21: Large Vertical Size 096 Left Hand Piping Front View Right Hand Piping Overall Unit Dimensions: 54⅝" W 55¾" H 28" D Electrical Knockouts Catalog Daikin Large Vertical Water Source Heat Pumps Page 37 of 56

38 Dimensional Data LVC/LVW Top Discharge 120 Figure 22: Large Vertical Size 120 Front View Left Hand Piping Right Hand Piping Overall Unit Dimensions: 54⅝" W 55¾" H 28" D Electrical Knockouts LVC/LVW Top Discharge 1 Figure 23: Large Vertical Size 1 Left Hand Piping Front View Right Hand Piping Overall Unit Dimensions: -3/8" W " H 30" D Overall Filter Rack Dimensions: 74-1/4" W 40-1/16"H Page 38 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

39 LVC/LVW Top Discharge 215 Figure 24: Large Vertical Size 215 Left Hand Piping Front View Dimensional Data Right Hand Piping Overall Unit Dimensions: -3/8" W " H 30" D Overall Filter Rack Dimensions: 74-1/4" W 40-1/16"H LVC/LVW Top Discharge 290 Figure 25: Large Vertical Size 290 Left Hand Piping Front View Right Hand Piping Overall Unit Dimensions: -3/8" W " H 30" D Overall Filter Rack Dimensions: 74-1/4" W 40-1/16"H Catalog Daikin Large Vertical Water Source Heat Pumps Page 39 of 56

40 Dimensional Data LVC/LVW Top Horizontal Discharge 072, 096, 120 Figure 26: LVC/LVW Top Horizontal Discharge Opening Sizes 072, 096, 120 LVC/LVW Top Horizontal Discharge 1, 215, 290 Figure 27: LVC/LVW Top Horizontal Discharge Opening Sizes 1, 215, 290 Page 40 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

41 Accessories Optional 2" Filter Rack & Return Air Duct Collar The optional 2" filter rack and duct collar accepts 2" (51 mm) thick filters for side removal. It replaces the existing 1" (25 mm) filter rack and duct collar. The optional 2" return air duct collar kit is used to facilitate connection of return air duct to the unit. A duct collar kit can be used in conjunction with the standard 1" thick filter rack or the optional 2" filter rack. Figure 28: 2" Return Air Filter Rack Figure 30: 2" Return Air Duct Collar and Filter Rack Dimensions Unit Sizes " 74 1 /16" 38 3 /16" *2⅛" Figure 29: 2" Return Air Duct Collar and Filter Rack Dimensions Unit Sizes /16" 6" 30⅞" Catalog Daikin Large Vertical Water Source Heat Pumps Page 41 of 56

42 Accessories Figure 31: Optional Return Air Duct Collar & 2" Filter Rack Components Sizes Top Duct Collar Chassis Center Support Side Flanges Top Filter Rack Filters Center Filter Racks Door End Duct Collar Side Figure 32: Optional Return Air Duct Collar & 2" Filter Rack Components Sizes Center Supports Top Duct Collar Chassis Top Filter Rack Center Filter Racks Duct Collar Center Support Door End Duct Collar Side Page 42 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

43 Accessories Supply and Return Water Hoses Available as fire rated construction in 2 or 3 foot (610 mm or 914 mm) lengths. Fire rated hoses have a synthetic polymer core with an outer rated covering of stainless steel. Fittings are steel. Assembly is fire rated and tested according to UL 94 with a VO rating and ASTM 84. Each hose has MPT connections. Hoses have a swivel connection at one end and are available in 1¼" (32 mm) to match the FPT fittings on unit sizes 072 through 120. Unit sizes 1 through 290 have 1½" (38 mm) FPT fittings. Figure 33: Supply and Return Water Hoses Combination Balancing and Shutoff (Ball) Valves Constructed of brass and rated at 400 psig (28 kpa) maximum working pressure. Valves have a built-in adjustable memory stop to eliminate rebalancing. Valves have FPT connections on both ends for connection to the water hose and to the field piping. Figure 35: Shut off Ball Valve Hose Specifications Inner Tube: Fire retardant TRP (Thermosplastic Rubber) tested to UL- 94 with V-O rating. Outer Braid: Stainless steel wire (ANSI 302/304) Temperature range: 40 F to 200 F Condensate Hose Kit Available as a long clear plastic hose with the necessary clamps and a MPT hose fitting for connection to the FPT field piping. Figure 34: Condensate Hose Kit Catalog Daikin Large Vertical Water Source Heat Pumps Page 43 of 56

44 Accessories Motorized Valve Used in variable pumping type applications, the valve actuator is wired and typically piped in the return water line. The 2-way motorized water valve kit includes the valve body, actuator and wire harness. The 24VAC valve actuator must be wired directly to terminal block H8 on the Micro- Tech III controller. The valve will only energize on a call for heating or cooling. The 1-1/4" valve is rated for 300 psig (2068 kpa and the 1-1/2" valve is rated for 150 psig (1034 kpa). Figure 36: 2-Way Motorized Valve The Multiple Unit Control Panel (MUCP) is an accessory used when up to 3-units are controlled from a single thermostat. The MUCP must be field-installed in a remote location, typically close to the units and convenient for service access. A maximum of 2 boards may be used together if up to 6-units must be connected and controlled from a single thermostat. Figure 38: Multiple Unit Control Panel Ciruit Board Field Installed Controls A multiple unit control panel allows a single thermostat to control up to three units in parallel. Multiple Unit Control Panel (MUCP) Figure 37: Multiple Unit Control Panel and Board The multiple unit control board provides the components necessary to protect the MicroTech III unit controller from electrical damage that may occur when using standard offthe-shelf relays. This version of the board uses VAC relays and should not be used in combination with any other accessories or equipment that require VDC connections to the G, W1, or Y1 terminals. These easy-to-operate comfort command centers bring you a complete range of deluxe features. Features that enable you to match temperature programming to your application, provide added convenience, and help save energy and money. All packed into an extra rugged, highly reliable design that will look and perform like new for years to come. Page 44 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

45 Accessories Programmable Electronic Thermostat Two-Stage Heat/Two-Stage Cool, 7-Day Programmable Figure 39: Daikin Part No (1-Pk, White with Wall Plate) Non-Programmable, Auto or Manual Changeover Thermostat Two Stage Heat/Two Stage Cool, Night Setback Override Figure 40: Daikin Part No (1-Pk, White with Wall Plate) Features Hardwired Programmable and configurable Simpleset TM feature enables easy copying of one day's programming for the entire week Title 24 compliant/no batteries required Relay Ouputs (minimum voltage drop in thermostat) Clear, backlit display makes it easy to see time, temperature, and setpoint even in the dark Ideally suited for: Light commercial/residential (new construction/replacement) Lockout feature prevents unwanted tampering Optional remote temperature sensor available (see page 59) Specifications Electrical Rating: 24 VAC (18 to 30 VAC/VDC) 1 amp maximum per terminal 4 amp maximum total load Easy access terminal block Temperature Control Ranges: 45ºF to 90ºF (7ºC to 32ºC), Accuracy: ± 1ºF (± 0.5ºC) System Configurations: Two-stage heat/two-stage cool Terminations: R, C, W1, Y1, W2, Y2, G, S1, S2 Features Hardwired Two-stage heat / two-stage cool systems Backlit display Field temperature calibration Status indicator light Relay outputs (minimum voltage drop in thermostat) Night set-back override (used when unit is wired through a time clock on the U-terminal) Optional remote temperature sensor available (see "Optional Remote Sensor" on page 46) Specifications Electrical Rating: 24 VAC (18 to 30 VAC/VDC) 1 amp maximum per terminal 4 amp maximum total load Easy access terminal block Temperature Control Ranges: 45ºF to 90ºF (7ºC to 32ºC), Accuracy: ± 1ºF (± 0.5ºC) System Configurations: Two-stage heat / two-stage cool Timing: Backlight Operation: 13 seconds after mode change or button press Terminations: +R, -C, W1, Y1, W2, Y2, G, O, S1, S2 Catalog Daikin Large Vertical Water Source Heat Pumps Page 45 of 56

46 Accessories Optional Remote Sensor Figure 41: Part No Used with Thermostat(s) & The fast, easy solution for temperature sensing problems. For tamper prone areas Poor airflow areas Troubled applications Foam gasket prevents drafts through wall opening Mounts to standard 2" x 4" outlet box 2¾"W x 4½"H MicroTech III Water Source Heat Pump Wall Sensors (Kit P/N , , ) Room temperature sensors provide electronic sensing of room temperatures at wall locations. All sensor models feature a thermistor (10kΩ), a green LED for unit status and tenant override button. Setpoint adjustment potentiometer, heat and fan mode switches are optional features. Feature Tenant Override Button Sensor Kit Part Numbers Yes Yes Yes SPT Adj. Pot No Yes Yes Status LED Yes Yes Yes Fan and Mode Switches No 1 Yes 2 Yes Notes: 1 55º to 95 F (13º to 35ºC) 2-3º to +3ºF (-1.5º to +1.5ºC) Figure 43: MicroTech III Wall Sensor Details 3." 0 to 10 K ohm Potentiometer Figure 42: Room Temperature Sensors Status LED (Green) Fan Control Slide Switch Mode Control Slide Switch 4.59" Tenant Override Momentary Push Button Switch Sensor Sensor Not Shown Sensor Page 46 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

47 Accessories Optional Water Source Heat Pump Room Wall Sensors Wiring Figure 44: Temperature Sensor Wiring to MicroTech III Unit Controller (Kit Part No.s , ) Temperature Sensor Terminals Programmable Electronic Thermostat Wiring Two-Stage Heat/Two-Stage Cool, 7-Day Programmable Figure 46: (Part No ) MicroTech III Unit Control Board Low Voltage Terminal Strip (Circuit 1) 24VAC Common Tenant Override Fan TB2 C O G Thermostat Terminals - C + R MicroTech III Unit Controller TB1 Terminals Cool 1 Cool 2 Heat 1 Heat 2 Alarm Output 24VAC Y1 Y2 W1 W2 A R W1 Y1 W2 Y2 G Figure 45: Temperature Sensor Wiring to MicroTech III Unit Controller ( ) Temperature Sensor Terminals Notes: Includes Thermostat and Wall Plate. Non-Programmable, Auto or Manual Changeover Wiring Two Stage Heat/Two Stage Cool, Night Setback and Override Feature Figure 47: (Part No ) MicroTech III Unit Control Board Low Voltage Terminal Strip (Circuit 1) 24VAC Common Tenant Override Fan TB2 C O G Thermostat Terminals - C + R MicroTech III Unit Controller TB1 Terminals Cool 1 Cool 2 Heat 1 Heat 2 Alarm Output 24VAC Y1 Y2 W1 W2 A R W1 Y1 W2 Y2 G O Override (Optional) Note: An additional conductor is required between "O" terminals for the override feature to work. Catalog Daikin Large Vertical Water Source Heat Pumps Page 47 of 56

48 Accessories Optional Remote Sensor Wiring Used with Thermostat(s) or Figure 48: Part No Thermostat Remote Sensor S1 S2 S1 S2 Cut R12 from circuit board Wire 1 Wire 2 Page 48 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

49 Typical Wiring Diagrams MicroTech III Controller with I/O Expansion Module & Communication Module 208/230, 4, 5--3 (1.5 hp or less) Drawing No MicroTech III Control Board JP1 Open (Normal) Shorted (Test Mode) JP2 Shorted Open (Std Range) JP3 Shorted (Geothermal Range) JP4 Spare JP5 Open JP6 Open JP7 Spare JP8 Spare JP1 Shorted JP2 Open JP3 Open JP4 Open JP5 Open JP6 Open JP7 Spare JP8 Spare I/O Expansion Module Legend Item Description CC1 Circuit 1 Compressor Contactor CC2 Circuit 2 Compressor Contactor CM1 Circuit 1 Compressor CM2 Circuit 2 Compressor COS Condensate Overflow Sensor HP Circuit 1 High Pressure Switch HP2 Circuit 2 High Pressure Switch IOEXP I/O Expansion Board / Harness LED1 LED Annunciator / Harness LED2 LED Annunciator / Harness *RAT Return Air Temp Sensor *LWT Leaving Water Temp Sensor LP Circuit 1 Low Pressure Switch LP2 Circuit 2 Low Pressure Switch SLTS Circuit 1 Suction Line Temp Sensor SLTS2 Circuit 2 Suction Line Temp Sensor R1 Fan Motor Starter RV Circuit 1 Reversing Valve Solenoid RV2 Circuit 2 Reversing Valve Solenoid TB1 Power Terminal Block X1 VA Transformer *DAT Discharge Air Temp Sensor *EWT Entering Water Temp Sensor Notes: 1. Run/Prg Jumper to be in Run position for normal operation * Optional with Communication Module Catalog Daikin Large Vertical Water Source Heat Pumps Page 49 of 56

50 Typical Wiring Diagrams MicroTech III Controller with I/O Expansion Module & Communication Module 208/230, 4, 5--3 (greater than 1.5 hp) Drawing No MicroTech III Control Board JP1 Open (Normal) Shorted (Test Mode) JP2 Shorted Open (Std Range) JP3 Shorted (Geothermal Range) JP4 Spare JP5 Open JP6 Open JP7 Spare JP8 Spare JP1 Shorted JP2 Open JP3 Open JP4 Open JP5 Open JP6 Open JP7 Spare JP8 Spare I/O Expansion Module Legend Item Description CC1 Circuit 1 Compressor Contactor CC2 Circuit 2 Compressor Contactor CM1 Circuit 1 Compressor CM2 Circuit 2 Compressor COS Condensate Overflow Sensor HP Circuit 1 High Pressure Switch HP2 Circuit 2 High Pressure Switch IOEXP I/O Expansion Board / Harness LED1 LED Annunciator / Harness LED2 LED Annunciator / Harness *RAT Return Air Temp Sensor *LWT Leaving Water Temp Sensor LP Circuit 1 Low Pressure Switch LP2 Circuit 2 Low Pressure Switch SLTS Circuit 1 Suction Line Temp Sensor SLTS2 Circuit 2 Suction Line Temp Sensor R1 Fan Motor Starter RV Circuit 1 Reversing Valve Solenoid RV2 Circuit 2 Reversing Valve Solenoid TB1 Power Terminal Block X1 VA Transformer *DAT Discharge Air Temp Sensor *EWT Entering Water Temp Sensor Notes: 1. Run/Prg Jumper to be in Run position for normal operation * Optional with Communication Module Page 50 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

51 Typical Wiring Diagrams MicroTech III Controller with I/O Expansion Module & Communication Module 208/230, 4, 5--3 Unit Size 290 Drawing No MicroTech III Control Board JP1 Open (Normal) Shorted (Test Mode) JP2 Shorted Open (Std Range) JP3 Shorted (Geothermal Range) JP4 Spare JP5 Open JP6 Open JP7 Spare JP8 Spare JP1 Shorted JP2 Open JP3 Open JP4 Open JP5 Open JP6 Open JP7 Spare JP8 Spare I/O Expansion Module Legend Item Description CC1 Circuit 1 Compressor Contactor CC2 Circuit 2 Compressor Contactor CM1 Circuit 1 Compressor CM2 Circuit 2 Compressor COS Condensate Overflow Sensor HP Circuit 1 High Pressure Switch HP2 Circuit 2 High Pressure Switch IOEXP I/O Expansion Board / Harness LED1 LED Annunciator / Harness LED2 LED Annunciator / Harness *RAT Return Air Temp Sensor *LWT Leaving Water Temp Sensor LP Circuit 1 Low Pressure Switch LP2 Circuit 2 Low Pressure Switch SLTS Circuit 1 Suction Line Temp Sensor SLTS2 Circuit 2 Suction Line Temp Sensor R1 Fan Motor Starter RV Circuit 1 Reversing Valve Solenoid RV2 Circuit 2 Reversing Valve Solenoid TB1 Power Terminal Block X1 VA Transformer *DAT Discharge Air Temp Sensor *EWT Entering Water Temp Sensor Notes: 1. Run/Prg Jumper to be in Run position for normal operation * Optional with Communication Module Catalog Daikin Large Vertical Water Source Heat Pumps Page 51 of 56

52 Engineering Specifications General Contractor shall furnish and install Water Source Heat Pumps as indicated on plans. Each unit shall be CETL Listed. Units less than 135,000 Btu/hr. total cooling capacity shall be ISO rated per Standard Each unit shall be fully run tested at the factory. Each unit shall be shipped on a wooden skid and covered with plastic. Casing and Cabinet The casing shall be constructed of heavy-gauge G- galvanized steel corner posts and steel panel construction with heavy gauge steel base pan. The base pan shall have holes to accept field installation of rubber or spring isolators. The interior shall be lined with 1/2" thick, 1½ lb. density glass fiber. Multiple panels on front, back and sides shall provide access to compressor, control box, fan motor and fan assembly. Unit shall have a galvanized steel painted drain pan with a drain connection extending through the unit casing. Insulated drain pan shall act as a divider panel between the compressor and fan sections. Units shall have as standard a factory installed 1" thick filter brackets for side filter removal. Unit shall have multiple 1" thick throwaway filters. Cabinets shall have knockouts for entrance of line voltage and low voltage control wiring. Supply return water and condensate connections shall be copper FPT fittings and protrude through the casing. R-410A Refrigerant Circuit Units shall be dual circuit design containing scroll compressors, electronic expansion valve, water-to-refrigerant coaxial heat exchanger, reversing valve, finned tube heat exchanger, and safety controls. Non-ozone depleting R-410A refrigerant must be used. Compressor(s) shall be scroll type with thermal overload protection and external rubber vibration isolation mounts. Air coil shall be aluminum fins bonded to copper tubes. The coaxial heat exchanger shall be copper inner tube and steel outer tube with a U.L. Listing and a 400 psig water side rating and a 450 psig refrigerant side rating. Optional Cupro-nickel Coax coil for geothermal units. High and low side service valves shall be provided on each refrigerant circuit for measuring and charging of the refrigerant circuit. Safety controls shall include a low suction temperature (freezestat), high refrigerant pressure and low refrigerant pressure switches. Units shall be capable of being reset only by interrupting the power supply to the unit and not from the wall thermostat. Unit shall be capable of starting in an ambient of 40º F with entering water at 55º F standard range, 20º F extended range, with both air and water flow rates at the ISO rating conditions. Electrical A control enclosure shall be located within the unit and shall contain controls for compressor(s), reversing valves(s) and fan motor operation. A terminal block shall facilitate main power wiring connection. A VA transformer shall supply the low voltage control circuit. Unit shall be nameplated to accept time delay fuses for branch overcurrent protection of the power conductors. Unit control system shall provide one or two stage cooling and heating as required by the setpoints of the wall thermostat. The unit shall be capable of providing an output signal to a unit-mounted LED annunciator to indicate a fault condition. The control system shall be microprocessor based and provide the following: Stand-alone operation LonWorks communication capabilities (Must be LonMark 3.4 certified) BACnet communication capabilities (BACnet MS/TP Network) Fan and Motor Assembly Units shall have a belt driven centrifugal fan. The fan housing shall protrude through the cabinet to facilitate field duct connection. Page 52 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

53 Engineering Specifications Solid-State Control System MicroTech III Control System - Unit shall have a microprocessor- based control system. The unit control logic shall provide heating and cooling operation as required by the wall thermostat set point. The control system shall provide the following for stand-alone operation: 1. The use of standard non-programmable or programmable wall thermostats. 2. Fan operation simultaneous with the compressor (fan interlock) regardless of thermostat logic. 3. Time delay compressor operation. 4. Compressor short cycle protection of a minimum of three minutes before restart is possible. 5. Random unit start-up after coming off on unoccupied mode. 6. Single grounded wire connection for activation of the unoccupied or unit shutdown modes. 7. Night setback temperature setpoint input signal from the wall thermostat. 8. Override signal from wall thermostat to override unoccupied mode for 2 hours. 9. Brownout protection to suspend unit operation if the supply voltage drops below % of normal. 10. Condensate overflow protection to suspend cooling operation in an event of a full drain pan. 11. Suspended compressor operation upon activation of the refrigerant pressure switch(es). 12. Cooling operation activated for seconds upon activation of the low suction temperature sensor - defrost cycle. 13. Method of defeating compressor, reversing valve and fan time delays for fast service diagnostics. 14. Remote reset - Provides means to remotely reset automatic lock-outs generated by high/low pressure faults and/or low temperature faults. 15. Fault Retry clears faults the 1st two times they occur within a 24-hour period and triggers automatic lock-out on 3rd fault. MicroTech III Control with I/O Expansion Module I/O Expansion Module connects directly to the main MicroTech III controller to provide control of the second refrigeration circuit. MicroTech III Control with LonWorks Communication Module Unit shall have a microprocessor-based control system. The unit control logic shall communicate over a LonMark communications network. The unit controller is factory programmed [LonMark 3.4 certified Application Code the current standard for new applications] and tested with all the logic required to monitor and control heating and cooling operation. The controller sets the unit mode of operation, monitors water and air temperatures, and can communicate fault conditions via a LonMark communications network. Units with the MicroTech III and LonWorks communication module include return air, discharge air and leaving water temperature sensors. Space temperature sensor options include a set-point adjustment, tenant override button, and the capability of substituting the return air sensor with a wall-mounted room sensor. Microtech III Control w/ BACnet Communication Module Unit shall have a microprocessor-based control system. The unit control logic shall communicate over a BACnet communications network. The BACnet communication module shall incorporate an Atmel ARM7 Thumb series MCU and be capable of supporting a full MSTP BACnet implementation. The microprocessor shall also support SPI compatible communications with the MCU of the Microtech III controller. The physical interface to a BACnet BAS network shall be through an industry standard RS-4 transceiver capable of existing on an RS-4 network of up to 64 nodes. The unit controller is factory programmed and tested with all the logic required to monitor and control heating and cooling operation. The controller sets the unit mode of operation, monitors water and air temperatures, and can communicate fault conditions via a BACnet communications network. Units outfitted with Microtech III and BACnet Communication modules include return air, discharge air and leaving water temperature sensors. Space temperature sensor options include a set-point adjustment, tenant override button, and the capability of substituting the return air sensor with a wall-mounted room temperature sensor. Each communicating unit controller performs the following unit operations: Enable heating and cooling to maintain space temperature set point at the room sensor Enable fan and compressor operation Monitor all safety controls Monitor discharge and return air temperature Monitor leaving water temperature Relay status of all vital unit functions Support optional control outputs Unit mounted LED annunciators aid in diagnosing unit operation by indicating the water source heat pump operating mode Catalog Daikin Large Vertical Water Source Heat Pumps Page 53 of 56

54 Engineering Specifications and alarm conditions. If there are no current alarm conditions, a green LED on the annunciator board will indicate normal unit operating mode. If an alarm condition exists, the Microtech III controller will send the fault condition to the LED annunciator, which will assist in troubleshooting the unit. LED Annunciator shall be visible without removing access panel. Heat pumps with the MicroTech III Controller with a LonWorks Communication Module is designed to be linked with a centralized Building Automation System (BAS) through a LonMark communications network for centralized scheduling and management of multiple heat pumps. Wall-mounted room sensors are available to control the heating and cooling operation of each MicroTech III Water Source Heat Pump. Available room sensors include: Room Sensor with timed override button and LED; Room temperature sensor with timed-override button and set point adjustment (55 to 95 deg F); Room sensor with timed-override button and set point adjustment (-3 to +3 deg F); Room sensor (no options, sensor only). Warranty An optional 4-year extended compressor warranty covers the compressor for 5 years from the date at which the unit ships from the factory. An optional 4-year extended refrigeration circuit warranty covers the entire refrigeration circuit and related components for 5 years. Field Installed Accessories Wall Thermostat Options Programmable Electronic Thermostat Two-stage heat/two-stage cool, 7-day programmable. Subbase shall have system "Mode/Prog" and fan "Auto/On" switches. Thermostat shall have the option of an Optional Remote Sensor. Non-programmable, auto or manual changeover Two-stage heat/two-stage cool, night setback override. Subbase shall have system "Cool/Off/Heat/Auto" and fan "Auto/On switches. Thermostat shall have the option of an Optional Remote Sensor. Wall Temperature Sensor Options: Wall Sensor with timed-override button. Wall Sensor with timed-override button and set point adjustment (55 to 95 deg F), fan mode switch (auto/on), operational mode button (Heat/Cool/Auto) and status LED to display fault condition. Wall Sensor with timed-override button and set point adjustment (-3 to +3 deg F), fan mode switch (auto/on), operational mode button (Heat/Cool/Auto) and status LED to display fault condition. Hose Kits: Two fire-rated flexible hoses with ASTM ratings of Flame Spread 25, Fuel Contribution 25 and Smoke Density 50 for connection to unit and field piping. Hose shall be covered with stainless steel braiding to prevent damage. Valve Options: Combination water balancing and shutoff valve with adjustable memory stop. Optional 2-way, Normally Open (N.O.) or Normally Closed (N.C.) motorized water valves. Page 54 of 56 Daikin Large Vertical Water Source Heat Pumps Catalog

55

56 Daikin Water Source Heat Pumps A Complete Line of Quality Products, Flexible Configurations Stacking Units 3/4 to 3 Ton Large Vertical Units 6 to 25 Ton & Horizontal Units 6 to 10 Ton Rooftop Units 3 to 35 Ton Water to Water Source Heat Pump Units 3 to 35 Ton Console Units 3/4 to 1 1 /2 Ton Enfinity Vertical & Horizontal Units 1/2 to 6 Ton SmartSource Vertical & Horizontal Units 2 to 6 Ton Daikin Training and Development Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at and click on training, or call and ask for the Training Department. Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Representative for warranty details. Refer to Form Y. To find your local Daikin Representative, go to Aftermarket Services To find your local parts office, visit or call 0-37PARTS ( ). To find your local service office, visit or call This document contains the most current product information as of this printing. For the most up-to-date product information, please go to Products manufactured in an ISO Certified Facility Daikin Applied (0) CAT (10/13)

Catalog Enfinity Large Horizontal Water Source Heat Pumps with R-410A Refrigerant

Catalog Enfinity Large Horizontal Water Source Heat Pumps with R-410A Refrigerant Catalog 1112-4 Enfinity Large Horizontal Water Source Heat Pumps with R-410A Refrigerant Horizontal Models CCH Standard Range & CCW Geothermal Range Unit Sizes 072 120 (6 to 10 Tons) R-410A Refrigerant

More information

Enfinity Horizontal Ceiling Catalog Water Source Heat Pumps

Enfinity Horizontal Ceiling Catalog Water Source Heat Pumps Enfinity Horizontal Ceiling Catalog 1108-3 Water Source Heat Pumps Model CCH Standard Range Model CCW Geothermal Range Unit Sizes 007 070 (1/2 to 6 Tons) R-410A Refrigerant Engineered for flexibility and

More information

McQuay Horizontal Water Source Heat Pump 1/2 to 6 Ton

McQuay Horizontal Water Source Heat Pump 1/2 to 6 Ton Catalog 1102-1 McQuay Horizontal Water Source Heat Pump 1/2 to 6 Ton Models CRH & CRW Ceiling Concealed Unit Sizes 007 070 (R-22 Refrigerant) Table of Contents Product Model Nomenclature... 1 Introduction...

More information

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW Operation & Maintenance Manual OM 931-6 Group: WSHP Part Number: 910157590 Date: September 2014 MicroTech III Unit Controller for Water Source Heat Pump Units Used with Enfinity Models CCH/CCW, VFC/VFW,

More information

Enfinity Console Water Source Heat Pumps 1/2 to 1½ Ton

Enfinity Console Water Source Heat Pumps 1/2 to 1½ Ton Enfinity Console Water Source Heat Pumps 1/2 to 1½ Ton R-410A Models MHC Standard Range & MHW Extended Range Unit Sizes 007-018 Catalog 1104-11 Contents Model Nomenclature... 3 AHRI Performance Data....

More information

Enfinity Large Vertical Water Source Heat Pumps with R-410A Refrigerant

Enfinity Large Vertical Water Source Heat Pumps with R-410A Refrigerant Installation & Maintenance Data IM 1059-2 Group: WSHP Part Number: 669479102 Date: November 2011 Enfinity Large Vertical Water Source Heat Pumps with R-410A Refrigerant Vertical Models LVC Standard Range

More information

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps Operation and Maintenance Manual OM 239 Group: WSHP Document PN: 906530 Date: July 205 MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps Large Capacity

More information

Catalog McQuay Enfinity Horizontal & Vertical Water Source Heat Pumps

Catalog McQuay Enfinity Horizontal & Vertical Water Source Heat Pumps Catalog 1100-3 McQuay Enfinity Horizontal & Vertical Water Source Heat Pumps Ceiling Concealed, Vertical Floor Standard and Extended Range Unit Sizes 1/2 to 5 Tons Table of Contents Enfinity Product Model

More information

McQuay Enfinity TM. Horizontal & Vertical Water Source Heat Pump 1/2 to 5 Ton. Catalog

McQuay Enfinity TM. Horizontal & Vertical Water Source Heat Pump 1/2 to 5 Ton. Catalog Catalog 1100-5 McQuay Enfinity TM Horizontal & Vertical Water Source Heat Pump 1/2 to 5 Ton Model CCH & CCW Ceiling Concealed Size 019 060 Model FCV & FCW Vertical Floor Size 007 060 Table of Contents

More information

Enfinity Vertical Water Source Heat Pumps Catalog

Enfinity Vertical Water Source Heat Pumps Catalog Enfinity Vertical Water Source Heat Pumps Catalog 11033 Floor Model VFC & VFW Unit Sizes 007 0 (1/2 to 6 Tons) R410A Refrigerant Engineered for flexibility and performance Contents Model Nomenclature...3

More information

Product Data. Single-Package Horizontally Mounted Water Source Heat Pumps with Electronic

Product Data. Single-Package Horizontally Mounted Water Source Heat Pumps with Electronic Product Data Aquazone 0RHE006-060 Water Source Heat Pumps Horizontal Unit 0 Hz, CE Mark R-407C 1.to13.7NominalkW(Cooling) 1.8 to 16. 8 Nominal kw (Heating) TM Copyright 2004 Carrier Corporation Single-Package

More information

Installation and Maintenance Manual OM

Installation and Maintenance Manual OM Installation and Maintenance Manual OM 1149-3 Group: WSHP Document PN: 910208203 Date: April 2017 MicroTech III SmartSource Unit Controller with I/O Expansion Module for Single and Two Stage Water Source

More information

Enfinity Vertical Water Source Heat Pumps

Enfinity Vertical Water Source Heat Pumps Installation & Maintenance Data IM 930-3 Group: WSHP Part Number: 668996503 Date: November 2011 Enfinity Vertical Water Source Heat Pumps Model VFC Standard Range & VFW Geothermal Unit Sizes 007 070 /

More information

Enfinity Large Horizontal Water Source Heat Pumps with R-410A Refrigerant

Enfinity Large Horizontal Water Source Heat Pumps with R-410A Refrigerant Installation & Maintenance Data IM 1060-2 Group: WSHP Part Number: 669479202 Date: November 2011 Enfinity Large Horizontal Water Source Heat Pumps with R-410A Refrigerant Horizontal Models CCH Standard

More information

Catalog SmartSource Compact Vertical Water Source Heat Pumps. Model GCV - Vertical Unit Sizes (1/2 thru 6 tons)

Catalog SmartSource Compact Vertical Water Source Heat Pumps. Model GCV - Vertical Unit Sizes (1/2 thru 6 tons) Catalog 1116-8 SmartSource Compact Vertical Water Source Heat Pumps Model GCV - Vertical Unit Sizes 007 070 (1/2 thru 6 tons) Contents Model Nomenclature... 3 AHRI Performance Data.... 4 Compact model

More information

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical ENGINEERING GUIDE Water-Cooled Self-Contained Units C-Series, Vertical TABLE OF CONTENTS Introduction...2 Product Overview...3 Nomenclature...4 General Data...5 Cooling Performance Data....6 Evaporator

More information

EP Model. EP Model Water Source Heat Pump. ½ to 6 Ton

EP Model. EP Model Water Source Heat Pump. ½ to 6 Ton EP Water Source Heat Pump ½ to 6 Ton Industry-leading single-stage efficiencies, standard features, and a variety of options - providing energy efficient solutions to accommodate your building requirements.

More information

McQuay Enfinity Horizontal Water Source Heat Pumps R-410A Refrigerant

McQuay Enfinity Horizontal Water Source Heat Pumps R-410A Refrigerant Installation & Maintenance Data IM 1049-1 Group: WSHP Part Number: 910108372 Date: March 2010 McQuay Enfinity Horizontal Water Source Heat Pumps R-410A Refrigerant Model CCH, CCW Unit Sizes 007 070 2010

More information

Reinventing Energy Efficiency

Reinventing Energy Efficiency Commercial WATER2AIR EC LARGE SERIES Reinventing Energy Efficiency www.fhp-mfg.com Environmental stewardship is a core philosophy for FHP Manufacturing from design to production to the reduction in our

More information

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts GTIP60 ISO GT Series, Inch Pounds 60 Hz GT010070 (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts Rev: 903 Rev 1 Revisions: 31103 Changed HZ dwg to field convertible 5902 changed Unit

More information

AAF. Water Source Heat Pump Ceiling Mounted. CCW Vintage E. Last Manufactured: Replacement Parts List No Revision D 08/2016

AAF. Water Source Heat Pump Ceiling Mounted. CCW Vintage E. Last Manufactured: Replacement Parts List No Revision D 08/2016 Replacement Parts List No. 057117300 Revision D 08/2016 AAF Water Source Heat Pump Ceiling Mounted CCW 019-060 Vintage E Last Manufactured: 1999 To find your Daikin Applied parts distributor, call 1-800-377-2787

More information

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer Technical Development Program PRESENTED BY: COMMERCIAL HVAC SYSTEMS Water Source Heat Pump Systems Ray Chow Sales Engineer TDP Updates Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section

More information

GUIDE SPECIFICATIONS AQUARIUS ii

GUIDE SPECIFICATIONS AQUARIUS ii Catalog (AP Technical Data Sheet) GUIDE SPECIFICATIONS AQUARIUS ii AP Series Two Stage R-410A GENERAL Units shall be performance certified to ISO standard 13256-1 for Water Loop Heat Pump, Ground Water

More information

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled FORM 145.05-EG1 (1004) VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU 10 105 Ton Water-Cooled Table of Contents FORM 145.05-EG1 (0804) Features and Benefits.....................................................

More information

SKYPAK II, 3 Ton Series, gives you a

SKYPAK II, 3 Ton Series, gives you a SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall

More information

SpaceKeeper Console (SKC)

SpaceKeeper Console (SKC) SpaceKeeper Console (SKC) With finished cabinet or custom enclosure SKC 008-015 ¾ - 1¼ tons 12 W x 25¼ H x 48 L CGC-09 SpaceKeeper Console R410A MODEL NO. SKC _ 008 010 012 015 Net Cooling Capacity - Rated

More information

VertiCool Aurora Engineering Guide

VertiCool Aurora Engineering Guide Engineering Guide Effective August 2016 Air-Cooled, Water-Cooled and Water Source Heat Pump Contents Product Features... 3 Options... 4 Physical Data...5-6 Air-Cooled Performance Data (a) (b) (c)...7-8

More information

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE CAS Product Specifications Single stage cooling capacity control on all models with Micro channel

More information

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons Product Data OMNIZONE 50BRN,BZN006-024 Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems 5 to 20 Nominal Tons The 50BRN,BZN water-cooled and remote air-cooled indoor, self-contained units

More information

Catalog SmartSource Two-Stage Horizontal & Vertical Water Source Heat Pumps

Catalog SmartSource Two-Stage Horizontal & Vertical Water Source Heat Pumps SmartSource Two-Stage Horizontal & Vertical Water Source Heat Pumps GTH - Horizontal Ceiling GTV - Vertical Floor Unit Sizes 026 072 R-410A Refrigerant Catalog 1114-8 Contents Model Nomenclature... 4

More information

Greensource Residential Water Source Heat Pumps. Simply Smart. i Series: SV Model. boschheatingandcooling.com

Greensource Residential Water Source Heat Pumps. Simply Smart. i Series: SV Model. boschheatingandcooling.com Greensource Residential Water Source Heat Pumps i Series: SV Model Simply Smart The i Series SV Model is a cost-effective single stage water source heat pump that is designed for commercial retrofit and

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Compact, Self-Contained unit that offer low installation cost plus dependable performance. 0 Compact, Self-Contained unit that offer low installation cost plus dependable performance. From carrier s excellence in engineering come a new, compact of single package horizontal and vertical water

More information

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN 20-131.001 Page 1 Copyright 2017 Unico Inc. TABLE OF CONTENTS APPLICATIONS... 3 CABINET CONSTRUCTION... 3 FEATURES AND CONTROLS... 3 DIMENSIONAL

More information

Product Data. Features/Benefits. AQUAZONE 50PCH,PCV Compact Water Source Heat Pumps with PURON Refrigerant (R-410A) 50 Hz

Product Data. Features/Benefits. AQUAZONE 50PCH,PCV Compact Water Source Heat Pumps with PURON Refrigerant (R-410A) 50 Hz Product Data AQUAZONE 50PCH,PCV009-060 Compact Water Source Heat Pumps with PURON Refrigerant (R-410A) 50 Hz 2.1 to 15.0 Nominal kw Single-package horizontally and vertically mounted water source heat

More information

MODULE-AIRE VERTICAL PACKAGE UNITS MB SERIES MB SERIES. Energy Wise HVAC Equipment

MODULE-AIRE VERTICAL PACKAGE UNITS MB SERIES MB SERIES. Energy Wise HVAC Equipment Energy Wise HVAC Equipment FHP MANUFACTURING 601 N.W. 65th Court Fort Lauderdale, FL 33309 (954) 776-5471 (800) 776-5529 Fax www.fhp-mfg.com VERTICAL PACKAGE UNITS MODULE-AIRE FHP brings to the market

More information

SKYPAK II, 3 Ton Series, gives you a

SKYPAK II, 3 Ton Series, gives you a SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall

More information

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps Product Data OMNIZONE 50BV020-064 Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps 18 to 60 Nominal Tons omnizonebwlogo 50BVC,E,J,K,Q020-034 SINGLE PIECE OMNIZONE

More information

Product Data. Features/Benefits Carrier s Aquazone WSHPs are an efficient, compact alternative for all boiler/tower and retrofit applications

Product Data. Features/Benefits Carrier s Aquazone WSHPs are an efficient, compact alternative for all boiler/tower and retrofit applications Product Data Aquazone 50PCH, PCV, PCD007-070 Compact Water Source Heat Pumps with Puron Refrigerant (R-410A) 1 / 2 to 6 Nominal Tons TM Single-package horizontally and vertically mounted water source heat

More information

Console Water Source Heat Pumps

Console Water Source Heat Pumps Installation & Maintenance Data IM 985-2 Group: WSHP Part Number: 669479302 Date: November 2011 Console Water Source Heat Pumps R-410A Models MHC Standard Range & MHW Geothermal Range Flat Top & Slope

More information

Console Water Source Heat Pumps

Console Water Source Heat Pumps Installation & Maintenance Data IM 985 Group: WSHP Part Number: 107225604 Date: April 2009 Console Water Source Heat Pumps R-410A Models MHC Standard Range & MHW Geothermal Range Flat Top & Slope Top Unit

More information

DXair Pool Dehumidifiers

DXair Pool Dehumidifiers DXair Pool Dehumidifiers LV Series / to 6 Ton G-60 Galvanized The option-rich DXair LV Series pool dehumidifier has one of the smallest cabinets in the industry, making it a great choice for replacement

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

McQuay. Large Vertical Water Source Heat Pump. LGP, LHP, LWP Vintage C. Last Manufactured: 1994

McQuay. Large Vertical Water Source Heat Pump. LGP, LHP, LWP Vintage C. Last Manufactured: 1994 Replacement Parts List 0570900 Revision F 09/06 McQuay Large Vertical Water Source Heat Pump LGP, LHP, LWP 07-7 Vintage C Last Manufactured: 994 To find your Daikin Applied parts distributor, call -800-77-787

More information

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION WATER-SOURCE UNITARY HEAT PUMPS SECTION 23 81 46 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

MC SERIES. Optional reverse cycle heating Takes full advantage of building diversity

MC SERIES. Optional reverse cycle heating Takes full advantage of building diversity FHP brings to the market a first in R-410A large capacity modular reverse cycle units. The many features and energy efficiency of the MC Series make them the ideal choice for either new construction or

More information

AVAILABLE WITH ENERGY SAVING ECM MOTOR

AVAILABLE WITH ENERGY SAVING ECM MOTOR WATER SOURCE HEAT PUMP WSHC/WSHX HORIZONTAL Water Source Heat Pumps 3/4 thru 5 Tons HIGHLY EFFICIENT HIGH PERFORMANCE QUIET OPERATION STANDARD FEATURES 100% Factory run tested. All units operate with environmentally

More information

Product Data. AQUAZONE 50HQP Large Capacity Horizontal Water Source Heat Pumps with PURON Refrigerant (R-410A) 6 to 10 Nominal Tons

Product Data. AQUAZONE 50HQP Large Capacity Horizontal Water Source Heat Pumps with PURON Refrigerant (R-410A) 6 to 10 Nominal Tons Product Data AQUAZONE 50HQP072-120 Large Capacity Horizontal Water Source Heat Pumps with PURON Refrigerant (R-410A) 6 to 10 Nominal Tons TM Single-package horizontally mounted water source heat pumps

More information

Water-Cooled Self-Contained Units

Water-Cooled Self-Contained Units CATALOG FORM SK145.15-EG1 (1017) Water-Cooled Self-Contained Units C-Series, Vertical Nomenclature WATER-COOLED SELF-CONTAINED UNIT 1, 2 3 4, 5, 6 7 8 9 10 11 12 13 14 15 16 17 CS V 180 B 2 M 1 V A A A

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS RH-24-HAC-P-1L-C-SDE*F Horizontal Single Stage R410a Model Size 24 Reversing (Heating AND Cooling) 208/230-1-60VAC Liquid to Air Geothermal Heat Pumps Maritime Geothermal Ltd.

More information

technical guide Water-Cooled Self-Contained Units

technical guide Water-Cooled Self-Contained Units technical guide Water-Cooled Self-Contained Units C-Series, Vertical Technical Guide: YK145.00-EG3 (710) TABLE OF CONTENTS Water-Cooled Self-Contained Units Introduction...............................................................................

More information

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data July 28, 2008 Page 1 1 of 3 PROJECT: TAG: Gross Cooling Capacity [Btuh]: 37,800* Design CFM: 1,200 Seasonal

More information

GUIDE SPECIFICATIONS AQUARIUS ii

GUIDE SPECIFICATIONS AQUARIUS ii Catalog (AP Technical Data Sheet) GUIDE SPECIFICATIONS AQUARIUS ii AP Series Two Stage R-410A GENERAL Units shall be performance certified to ISO standard 13256-1 for Water Loop Pump, Ground Water Pump

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS RH-12-HAC-P-1L-C-SDE*F Horizontal Single Stage R410a Model Size 12 Reversing (Heating AND Cooling) 208/230-1-60VAC Liquid to Air Geothermal Heat Pumps Maritime Geothermal Ltd.

More information

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers GUIDE SPECIFICATIONS WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers WW024-072 Reverse Cycle Chillers / Low Temperature Boilers GENERAL Units shall be Underwriter Laboratories (UL) listed

More information

McQuay. Vertical Water Source Heat Pump. FCV, FCG, FCW 036, 042 Vintage A. Last Manufactured: 1993

McQuay. Vertical Water Source Heat Pump. FCV, FCG, FCW 036, 042 Vintage A. Last Manufactured: 1993 Replacement Parts List No. 055237600 Revision D 08/2017 McQuay Vertical Water Source Heat Pump FCV, FCG, FCW 036, 042 Vintage A Last Manufactured: 1993 To find your Daikin Applied parts distributor, call

More information

VariCool VAV Engineering Guide

VariCool VAV Engineering Guide Engineering Guide Effective September 2017 Water-Cooled and Chilled Water, Variable Air Volume Contents Product Features... 3 UNIT FEATURES... 3 Product Features... 4 Marvel Plus Microprocessor Control

More information

McQuay Enfinity (R-410A) and Standard (R-22) Horizontal Water Source Heat Pumps

McQuay Enfinity (R-410A) and Standard (R-22) Horizontal Water Source Heat Pumps Installation & Maintenance Data IM 742-4 Group: WSHP Part Number: 106586605 McQuay Enfinity (R-410A) and Standard (R-22) Horizontal Water Source Heat Pumps Model CRH, CRW Unit Sizes 007 070 / R-22 Refrigerant

More information

McQuay. Ceiling Concealed Horizontal Water Source Heat Pump. CCH, CCG, CCW 048, 060 Vintage A. Last Manufactured: 1995

McQuay. Ceiling Concealed Horizontal Water Source Heat Pump. CCH, CCG, CCW 048, 060 Vintage A. Last Manufactured: 1995 Replacement Parts List No. 055236000 Revision B 06/2015 McQuay Ceiling Concealed Horizontal Water Source Heat Pump CCH, CCG, CCW 048, 060 Vintage A Last Manufactured: 1995 To find your Daikin Applied parts

More information

CA Model Water Source Heat Pump

CA Model Water Source Heat Pump CA Model Water Source Heat Pump ¾ to ½ ton boschheatingandcooling.com andcoo i g.c om The CA console provides high performing heating and cooling in a compact size when space and access is at a premium.

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

SPECIFICATION CATALOG. Console 0.75 to 1.5 Tons. Geothermal/Water Source Heat Pump

SPECIFICATION CATALOG. Console 0.75 to 1.5 Tons. Geothermal/Water Source Heat Pump SPECIFICATION CATALOG Console 0.75 to 1.5 Tons Geothermal/Water Source Heat Pump Table of Contents Model Nomenclature.............................................................. 4 AHRI Data......................................................................

More information

C13-Series Engineering Guide

C13-Series Engineering Guide Engineering Guide Effective January 2018 Horizontal Air-Cooled, Water-Cooled, Chilled Water and Heat Pump Contents Product Features............................... 3 Product Options................................

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz Product Data 50HS Single-Package Heat Pump Units 50 Hz Nominal: 7 to 18 kw (2 to 5 Tons) Single-Package Heat Pump for Manufactured Housing/Residential and Light Commercial use. Features/Benefits One-piece

More information

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS* TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS K*ES120 10 NOMINAL TONS EER 8.5 DESCRIPTION These completely assembled dual circuit evaporator blower units include a well-insulated cabinet, a DX cooling

More information

EP Model Water Source Heat Pump

EP Model Water Source Heat Pump EP Model Water Source Heat Pump ½ to Ton Equipped with added standard features, a stronger, quieter cabinet and improved durability along with a variety of options providing additional energy efficient

More information

Rev. 2/13

Rev. 2/13 Rev. 2/13 2 EC Series Table of Contents MODEL NOMENCLATURE...3 FHP MANUFACTURING...3 ADVANTAGES OF FHP s TECHNOLOGY...3 LARGE EC SERIES MODELS 072 360...3 FEATURES...3 Cabinet...3 Quiet Operation...4 Serviceability...4

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

water to water heat pumps

water to water heat pumps AQUARIUS WW SERIES water to water heat pumps O ur Aquarius WW Series water-cooled modular reverse cycle chillers are designed to meet all your replacement or new construction chiller requirements. Specifically

More information

Specifications and Performance

Specifications and Performance R45C/H Packaged Terminal Air Conditioner (PTAC) Packaged Terminal Heat Pump (PTHP) Straight Cooling Nominal Capacities 9,000 12,000 15,000 18,000 Btuh The Right Fit for Comfort 2.6 3.5 4.4 5.3 kw Heat

More information

Daikin. Enfinity Console Water Source Heat Pump. WMHC, WMHW 015, 018 Design 2. Replacement Parts List No New 11/2017

Daikin. Enfinity Console Water Source Heat Pump. WMHC, WMHW 015, 018 Design 2. Replacement Parts List No New 11/2017 Replacement Parts List No. 700053300 New 11/2017 Daikin Enfinity Console Water Source Heat Pump WMHC, WMHW 015, 018 Design 2 To find your Daikin Applied parts distributor, call 1-800-377-2787 or visit

More information

LM Split Systems Water Source Heat Pump

LM Split Systems Water Source Heat Pump LM Split Systems Water Source Heat Pump 2 to ton boschheatingandcooling.com and coo g.c om 1 The fully featured LM Split Systems include a standard two-stage scroll compressor and an ECM (Electronically

More information

Greensource iseries Water Source Heat Pumps. SV Model. Made in Florida boschheatingandcooling.com

Greensource iseries Water Source Heat Pumps. SV Model. Made in Florida boschheatingandcooling.com boschheatingandcooling.com 1 Greensource iseries Water Source Heat Pumps SV Model Made in Florida boschheatingandcooling.com 1 Replacement Water Source Heat Pump About the Bosch Group The Bosch Group has

More information

Product Data. Fig. 1 - Unit 50VR -A

Product Data. Fig. 1 - Unit 50VR -A 50VR---A Performancet 15 SEER 2---Stage Packaged Heat Pump tem with PuronR (R---410A) Refrigerant Single and Three Phase 2to5NominalTons(Sizes24---60) Product Data Fig. 1 - Unit 50VR -A A09033 Single-Packaged

More information

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be

More information

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System PART 1 SYSTEM DESCRIPTION 1.1 The HVAC system is based on the CGC HYBRID Hydronic Heat Pump System. 1.2 The system will automatically

More information

SECTION AIR-SOURCE UNITARY HEAT PUMPS

SECTION AIR-SOURCE UNITARY HEAT PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 81 43 AIR-SOURCE UNITARY HEAT PUMPS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System

More information

LV Split Systems Water Source Heat Pump

LV Split Systems Water Source Heat Pump LV Split Systems Water Source Heat Pump 1½ to ton boschheatingandcooling.com and coolin g.c om 1 The option-rich LV Split Systems offer lower operating costs, space-saving flexibility and quiet comfort,

More information

McQuay. Enfinity Vertical Water Source Heat Pump. WFCV, WFCW Design 1. Replacement Parts List No Revision D 03/2018

McQuay. Enfinity Vertical Water Source Heat Pump. WFCV, WFCW Design 1. Replacement Parts List No Revision D 03/2018 Replacement Parts List No. 70006800 Revision D 03/208 McQuay Enfinity Vertical Water Source Heat Pump WFCV, WFCW 007-02 Design To find your Daikin Applied parts distributor, call -800-377-2787 or visit

More information

Daikin McQuay. Enfinity Console Water Source Heat Pump. WMHC, WMHW 007, 009, 012 Design 1. Replacement Parts List No Revision M 11/2017

Daikin McQuay. Enfinity Console Water Source Heat Pump. WMHC, WMHW 007, 009, 012 Design 1. Replacement Parts List No Revision M 11/2017 Replacement Parts List No. 700013000 Revision M 11/2017 Daikin McQuay Enfinity Console Water Source Heat Pump WMHC, WMHW 007, 009, 012 Design 1 To find your Daikin Applied parts distributor, call 1-800-377-2787

More information

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the operation of reverse-cycle refrigeration (heat pumps) Explain

More information

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/ 1 of 3 Cooling Capacity [Btuh] 24,800 * Condensing Unit SEER: 13.0 ** Condensing Unit CFM: 1,600 Condenser Fan No./Type: 1/CENTRIFUGAL Diameter x Width [in]: 10x10 Drive: Adjustable Belt Motor HP: 0.5

More information

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons Product Data 50HS Single-Package Heat Pumps 1 1 2 to 5 Nominal Tons Single-Package Heat Pump for Manufactured Housing/Residential and Light Commercial use. Features/Benefits One-piece heat pumps with optional

More information

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons 560.20-TG1Y (388) EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons Each circuit includes a fully hermetic compressor with a crankcase

More information

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump VertiCool CLASSIC Engineering Guide Effective March 2018 Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump Contents Product Features... 3 UNIT FEATURES... 3 OPTIONS:... 3 Physical Data...

More information

SPECIFICATION CATALOG. Commercial 7 to 25 Tons. Geothermal/Water Source Heat Pump

SPECIFICATION CATALOG. Commercial 7 to 25 Tons. Geothermal/Water Source Heat Pump SPECIFICATION CATALOG Commercial 7 to 25 Tons Geothermal/Water Source Heat Pump Table of Contents The Envision Series... 2-6 Inside the Envision Series.... 7-8 Envision Controls.... 9-14 Envision Application

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

Specifications and Performance

Specifications and Performance R35C/H Packaged Terminal Air Conditioner (PTAC) Packaged Terminal Heat Pump (PTHP) Straight Cooling Nominal Capacities 9,000 12,000 15,000 18,000 Btuh 2.6 3.5 4.4 5.3 kw Heat Pump Nominal Capacities 9,000

More information

RoofPak Applied Rooftop Systems

RoofPak Applied Rooftop Systems RoofPak Applied Rooftop Systems RoofPak Applied Rooftop Systems Design flexibility, energy efficiency, system performance and reliability make Daikin RoofPak applied rooftop systems the ideal solution

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ) Technical Guide SUNLINE 2000 SPLIT-SYSTEM EVAPORATOR BLOWER K4EU180 15 NOMINAL TONS (WORLD 50 HZ) DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper

More information

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307 DESCRIPTION Technical Guide CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) This 20 ton evaporator blower is designed with two distinct modules to provide maximum application

More information

Genesis Compact (GC) Series Submittal Data

Genesis Compact (GC) Series Submittal Data SERIES: HZ: UNIT OF MEAS: LANGUAGE: GC - R22 50 SI ENGLISH Genesis Compact (GC) Series Submittal Data Models GCH/V 018B - 060B 50Hz - R22 English Language/SI Units REVISION: 03/13/03 ** MODEL DECODER GC

More information

Advance Release September 2009

Advance Release September 2009 Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*

More information

INSTALLATION MB SERIES MANUAL TABLE OF CONTENTS MB SERIES ( INSTALLATION ) UNIT DESCRIPTION. FHP MB series are available in two models: VH CABINET:

INSTALLATION MB SERIES MANUAL TABLE OF CONTENTS MB SERIES ( INSTALLATION ) UNIT DESCRIPTION. FHP MB series are available in two models: VH CABINET: MB SERIES ( INSTALLATION ) INSTALLATION MANUAL MB SERIES TABLE OF CONTENTS Unit Description...1 Installation...2 General...2 Safety Considerations...2 Moving and Storage...3 Location...3 Acoustical Considerations...3

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

15 SEER, PACKAGE AIR CONDITIONING UNITS, 2-5 TONS Single Phase, 208/230 V, 60 Hz COOLING

15 SEER, PACKAGE AIR CONDITIONING UNITS, 2-5 TONS Single Phase, 208/230 V, 60 Hz COOLING SOUND REFRIGERANT ENVIRONMENTALLY PAN5 Product Specifications 15 SEER, PACKAGE AIR CONDITIONING UNITS, 2-5 TONS Single Phase, 208/230 V, 60 Hz REFRIGERATION CIRCUIT Environmentally sound R--410A refrigerant

More information

FCC Fan-Coil Units High-Performance, Vertical

FCC Fan-Coil Units High-Performance, Vertical FCC Fan-Coil s High-Performance, Vertical Model FCC construction features Piping and supply-duct connections are from top of unit, eliminating the need for side or back access Right or left-hand configurations

More information