1 Kramer RAS Removal Edison Team Members: Bill Z. Zhang, Protection Engineering Haroun Idris, Electric System Planning Presentation to RASRS November 14, 2018
2 Objective APPROVAL TO remove SCE s Kramer RAS (SOB-209) 2 Southern California Edison
3 Objective Introduction/Background Purpose and operating principles Protection design requirements 3 Southern California Edison
4 Kramer RAS The existing Kramer RAS (SOB-209) is designed to prevent thermal overload and system instability under loss of the Kramer-Inyokern- Randsburg No kv line. The appropriate generation resource is armed or disarmed based on the status of the Inyo phase shifter (PS) and the total power flow on the Kramer-Inyokern-Randsburg No. 1 & No kv lines metered at Kramer substation Line Flow (Inyo PS not In Service) Line Flow (Inyo PS In Service) Arming Requirement 150 MW 160 MW Arm Calgen or McGen (retired) 200 MW 210 MW Arm remaining generator As of December 1, 2014, ACE Cogeneration Company retired its McGen facility with a total capacity of 108 MW 4 Southern California Edison
5 Kramer RAS Map Inyokern Sub Randsburg Sub Kramer Sub 5 Southern California Edison
6 Kramer/Bishop RAS Area Diagram To Dixie Valley (NVE) Bishop Creek Units 2-4 Morgan 55 KV (LDWP) Inyo Haiwee (LDWP) Coso Control Oxbow Mt. Tom 55 KV Calgen 55 KV BISHOP RAS AREA BLM West Downs BLM East Navy 2 McGen (Retired) Inyokern Searles KRAMER RAS AREA Randsburg Mogen (Retired) Sungen LSP Borax Edwards Southbase Holgate Rocket Test Kramer 6 Southern California Edison Legend (#) 500 kv line 230 kv line 115 kv line Non-SCE owned lines (any color line) No. of lines (any color line) Phase Shifter
7 Interface Line Flow (MW) Kramer RAS Review The maximum total path flow on the Kramer-Inyokern-Randsburg No. 1 & No kv lines trended for 2016 is 107 MW, 2015 is 92 MW, and 179 MW for The downward trend from 2014 can be attributed to the generation retirement at McGen (108 MW) Inyokern-Randsburg-Kramer Path 115 kv HOURS 2014 DATA 2015 DATA 2016 Data 7 Southern California Edison
8 Kramer RAS Review (cont.) A 2017 study case was developed with maximum flows on Kramer- Inyokern-Randsburg No. 1 and No kv lines Under off peak load conditions Max. generation on-line in North of Inyokern area With and without Inyo phase shifter in-service Maximum total path flow achieved on Kramer-Inyokern-Randsburg No. 1 and No kv lines was: 115 MW with Inyo PS in-service 120 MW with Inyo PS NOT in-service Total path flow greater than 120 MW on the path is difficult to achieve with existing generation and the retirement of 108 MW at McGen facility. The Kramer RAS is not required at current generation levels and is not triggered at the maximum achievable path flow of 120 MW with the P1 contingency of the Kramer-Inyokern-Randsburg No kv line. The existing Kramer RAS describes the current procedure used to curtail and maintain Inyokern/Bishop area generation as a mitigation for a forced/scheduled outage of either Kramer-Inyokern-Randsburg No. 1 or No kv transmission lines 8 Southern California Edison
9 Conclusion Because the Kramer RAS is obsolete due to the retirement of the 108 MW McGen project and also not WECC compliant, SCE believes it should be retired. In the event future generation(s) materializes in the area and/or a reliability project reconfigures the system topology in the area which could result in increased flow on the Kramer-Inyokern-Randsburg lines, a new WECC-compliant RAS will be proposed to address potential overloads and/or dynamic instability. 9 Southern California Edison
10 Protection relays to be removed Substation No. of Relays Relay Type Designation Comments Kramer: 3 ASEA RXIL Undercurrent Relays: Monitors Inyokern 115kV Line Monitors Lugo No kV Line Monitors Lugo No kV Line 4 RFL-6745-RX 1B 5B 5C 5D Receive from: Inyokern Lugo 1AA & 2AA Lugo (Kramer No. 1 Line) Lugo (Kramer No. 1 Line) 5 RFL-6745-TX/RX 5 RFL-Logic Devices 2A 2B 4A 4B 4C 3F 3H 3J 3K 3L Transmit/Receive To: Coolwater CT31 Coolwater CT 32 Coolwater CT 41 Coolwater CT 42 McGen Test Logic Alarm Test Alarm Test Trip Matrix Arming Sw. Interface 10 Southern California Edison
11 Protection relays to be removed (cont d) Lugo: 3 ASEA RXIL Undercurrent Relays: Monitors 1AA (BDD Ckt) Monitors 1AA (T60 Ckt) Monitors 2AA (BDD Ckt) 3 ASEA RXIL Undercurrent Relays: Monitors 2AA (T60 Ckt) Monitors Kramer No kV Line Monitors Kramer No kV Line Inyokern: 3 RFL-6745-TX Transmit to Kramer: 1AA and 2AA Status Kramer No kV Line Status Kramer No kV Line Status 1 RFL Device 85T-1 Auto Test (Not in Service) 1 ASEA RXIL Undercurrent Relay: Monitors Kramer 115kV Line 1 RFL-6745-TX 85-1 Transmit to Kramer: Kramer 115kV Line Status 1 RFL-6745-RX 85-2 Receive From Kramer: Trip CalGen Signal 1 RFL Device Generator Test (Not in Service) 11 Southern California Edison
12 Protection relays to be removed (cont d) Generators: Coolwater: 4 RFL-6745-RX/TX Receive from Kramer: Trip CT-31 Trip CT-32 Trip CT-41 Trip CT-42 McGen: 1 RFL-6745-RX/TX 85 Receive from Kramer: Trip McGen CalGen No Relays Receives trip directly from Inyokern 12 Southern California Edison
13 Questions 13 Southern California Edison
14 SCE is requesting approval to Remove SCE s Kramer RAS (SOB-209) 14 Southern California Edison
15 Thank You! 15 Southern California Edison
Synchrophasor Technology in Control Centers Clemson University, SC March 12, 2014 Vikram S. Budhraja
Clemson University Power Systems Conference Synchrophasor Technology in Control Centers Clemson University, SC March 12, 2014 Vikram S. Budhraja Outline Synchrophasor Technology Infrastructure Lessons
More informationInnovative Real-Time Contingency Analysis Enhancements for Transmission Operations
Innovative Real-Time Contingency Analysis Enhancements for Transmission Operations Xiaodong Liu Trevor W. Tessin Richard A. Flynn 2016 IEEE PES General Meeting, Boston July 17-21, 2016 Outline Eversource
More informationPOWER SYSTEM INCIDENT REPORT: TRIP OF DOUBLE CIRCUIT MACKAY- COLLINSVILLE TEE - PROSERPINE 132 KV LINES AND STRATHMORE SVC ON 29 DECEMBER 2010
POWER SYSTEM INCIDENT REPORT: TRIP OF DOUBLE CIRCUIT MACKAY- COLLINSVILLE TEE - PROSERPINE 132 KV LINES AND STRATHMORE ON 29 PREPARED BY: Electricity System Operations Planning and Performance FINAL Disclaimer
More informationStandard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance
A. Introduction 1. Title: Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance 2. Number: PRC-005-6 3. Purpose: To document and implement programs for the maintenance of all
More informationStandard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance
Standard PRC-005-5 Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance Standard Development Timeline This section is maintained by the drafting team during the development
More informationThree Terminal 230kV System Protection and Restoration at Calpine s Creed and Goose Haven Energy Centers Suisun City, California
Three Terminal 230kV System Protection and Restoration at Calpine s Creed and Goose Haven Energy Centers Suisun City, California Larry Henriksen POWER Engineers, Inc. Hailey, Idaho Daren Phelps Calpine
More informationWM3000 WIRELESS MODULES
WM3000 WIRELESS MODULES $$:05 $$:07 INSTALLATION INSTRUCTIONS Table of Contents Installation... 3 Mounting Instructions & Connections... 3 Setting the Dip Switches... 4 Setting the Recognition Time...
More informationStandard PRC-005-3(i) Protection System and Automatic Reclosing Maintenance
A. Introduction 1. Title: Protection System and Automatic Reclosing 2. Number: PRC-005-3(i) 3. Purpose: To document and implement programs for the maintenance of all Protection Systems and Automatic Reclosing
More informationInstallation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev
Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1 AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control
More informationNeed for a Bipole III rating of 2300 Mw to transmit Keeyask power.
Need for a Bipole III rating of 2300 Mw to transmit Keeyask power. Introduction Further to the Technical Assessment of the Need for the Bipole III Line, dated 21 November 2014- Dennis Woodford P. Eng.
More informationWhat Utility Analytics means to Exelon
What Utility Analytics means to Exelon Presented by Bart Enright IT Director Smart Grid Initiatives at ComEd Exelon s Analytic Journey Exelon Utilities Overview T&D Grids Data Visualization Data Analytics/Notifications
More informationStandard PRC-005-4(X) Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance
Standard PRC-005-4(X) Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance Standard Development Timeline This section is maintained by the drafting team during the development
More informationDennis Mullen System Operations Manager
Dennis Mullen System Operations Manager EPRI Power Switching Safety and Reliability Conference September 14, 2009 Electric System Control Center (ESCC) Member Companies PSNH Operating Company of NU Retail
More informationStandard PRC-005-3(X) Protection System and Automatic Reclosing Maintenance
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More information1 Descriptions of Function
The Use Case #4 implements integrated management of s 1 Descriptions of Function 1.1 Function Name Date 12-15-2009, Version 1.13 implements integrated management of s 1.2 Function ID L-11.1.4 1.3 Brief
More informationTRANSMISSION ENGINEERING STANDARDS SUBSTATIONS
This standard was reviewed and approved by key managers with final approval by an officer of Oncor Electric Delivery on. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Customer with the Company
More informationOPUCN CUSTOM INCENTIVE RATE PLAN PERFORMANCE REPORT
Page 1 of 6 OPUCN CUSTOM INCENTIVE RATE PLAN 2015-2019 2015-2016 PERFORMANCE REPORT 1. In its 2015 Decision the OEB directed OPUCN report on the following metrics which it proposed for its CIR Plan: (a)
More informationPRC-005. Tips and Updates. February 25th, Jonathan Hayes
PRC-005 Tips and Updates February 25th, 2014 Jonathan Hayes jhayes@spp.org 501.614.3509 NERC Standards Violations 3 Overview PRC-005-1 Current Issues / Best Practices PRC-005-2 Standard Implementation
More information2000 System Disturbances
2000 System Disturbances Review of Selected Electric System Disturbances in North America North American Electric Reliability Council Princeton Forrestal Village 116-390 Village Boulevard Princeton, New
More informationStandard PRC-005-X Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationLineVision TM. Non-Contact Transmission Line Monitoring and Dynamic Line Rating
LineVision TM Non-Contact Transmission Line Monitoring and Dynamic Line Rating Jonathan Marmillo, Business Development M: 484-368-4630 E: jmarmillo@genscape.com www.genscape.com 2017 Genscape Incorporated.
More informationDemand Responsive Lighting Controls
Demand Responsive Lighting Controls California Statewide Utility Codes and Standards Program Josh Rasin Heschong Mahone Group, Inc. Lighting Stakeholder Meeting #3 February 24, 2011 Demand Responsive Lighting
More informationHot Food Holding Cabinets Test for FWE HLC
Design & Engineering Services Hot Food Holding Cabinets Test for Report Prepared by: Design & Engineering Services Customer Service Business Unit Southern California Edison January 4, 2011 Acknowledgements
More informationPower System Protection Part 2 Dr.Prof. Mohammed Tawfeeq. Zones of Protection
84 Power System protection Dr. Mohamad Tawfeeq Zones of protection Zone of protection of a relay is the place or the distance that the relay can protect easily.fig.1 shows an example of protection zones
More informationInstallation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger
Installation Guide for AL400ULM Multi-Output Access Control Power Supply Charger R AL400ULM - Multi-Output Access Control Power Supply/Charger Rev. 072500 Overview: The AL400ULM multi-output access control
More informationFan Coil Unit (FCU) Application Guide
Fan Coil Unit (FCU) Series Room Controllers TABLE OF CONTENTS and SCs Fan coil terminal equipment controllers 2 A5000 - VC3500E5000: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves
More informationInstallation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger
Installation Guide for AL300ULM Multi-Output Access Control Power Supply Charger R AL300ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL300ULM multi-output access control power supply/charger
More informationTransformer On-Line Monitoring
Transformer On-Line Monitoring Rowland James Entergy November 8, 2004 Prologue Why On-Line Monitoring & Diagnostics? Aging and Failure Modes Failure Statistics Current Monitoring & Analysis Methods Why
More informationNational Grid / DG Installation Process Guide per NY SIR / July 2011 ver. 1.0
Distributed Generation Installation Process Guide for Connections to National Grid Distribution Facilities per the New York Standardized Interconnection Requirements Introduction National Grid ( The Company
More informationTo: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations
AGENDA ITEM NO.: 5.D.1 MEETING DATE: 0/4/014 ADMINISTRATIVE REPORT NO.: 014-48 To: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations From: Tito R. Nagrampa
More informationRelay Performance Index for a Sustainable Relay Replacement Program
Relay Performance Index for a Sustainable Relay Replacement Program Aaron Feathers, Abesh Mubaraki, Nai Paz, Anna Nungo Pacific Gas & Electric Company San Francisco, CA Western Protective Relay Conference
More informationTOP R4 Unknown Operating State
TOP-004-2 R4 Unknown Operating State September 30, 2014 Greg Sorenson, PE Senior Compliance Engineer gsorenson.re@spp.org 501.688.1713 Outline Requirement Language Study Outcomes and Limitations Self-Check
More informationRoot Cause Analysis Report Tesoro Golden Eagle Refinery Refinery Power Outage
Summary of Event: The Golden Eagle Refinery (Refinery) experienced a partial electrical outage December 10, 2010 at 10:12 hrs when a transformer at Switching Station #7 failed. A CWS Level 1 report was
More informationMulti-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.
M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @
More informationArc Flash and Selective Coordination
PowerHour webinar series for consulting engineers Experts you trust. Excellence you count on. Arc Flash and Selective Coordination Wednesday June 8 1:00 CDT / 2:00 EDT (1PDH issued by Cummins) Welcome!
More informationGround Fault Protection Improvement Study
Ground Fault Protection Improvement Study Greg Ball DNV KEMA Solar ABCs Stakeholder Meeting July 11, 2013 San Francisco, CA Study Authors 2 Bill Brooks Brooks Engineering Andy Rosenthal New Mexico State
More informationTRANSMISSION ENGINEERING STANDARDS SUBSTATIONS
This standard was reviewed and approved by key managers on September 6, 2011. Officer approval of this revision is not required. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Utility with
More informationTransmission Planning and Siting For Current and Future Needs: A Federal or State Function?
Transmission Planning and Siting For Current and Future Needs: A Federal or State Function? Laurence G. Chaset California Public Utilities Commission National Conference of State Legislatures December
More informationELECTRIC SERVICE RELIABILITY IN PENNSYLVANIA 2008
El e c t r i cse r v i c e Re l i a b i l i t yi n P e n n s y l v a n i a 2008 P e n n s y l v a n i apu b l i cut i l i t yco mmi s s i o n ELECTRIC SERVICE RELIABILITY IN PENNSYLVANIA 2008 Published
More informationHoneywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts
Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS Feature Charts Control Panels FEATURE CHART LYNX Plus (L3000) (Supported Feature) (Not Supported) N/A (Not Applicable) LYNX Touch (L5210)
More informationAPS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES
APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES POWER SUPPLY AND BATTERY CHARGER AC AND DC STATUS INDICATORS ENOUGH POWER TO SUPPORT UP TO 3 MAGLOCKS OR ELECTRIC STRIKES PLUS REQUIRED
More informationSACE PR021/K SIGNALLING UNIT
SACE PR021/K SIGNALLING UNIT 1SDH000559R0002 L3016 1/52 EN CONTENTS 1. GENERAL INFORMATION...4 1.1. FOREWORD...4 1.2. APPLICABLE SCENARIOS...5 2. TECHNICAL SPECIFICATIONS...6 2.1. ELECTRICAL CHARACTERISTICS...6
More informationMulti-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.
M Series Multi-Output Access Control Power Supply Chargers Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 3 amp @ 12VDC or 4 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp
More information4. Applicability: 4.1. Functional Entities: 4.2. Facilities:
Standard PRC-005-2(i) Protection System A. Introduction 1. Title: Protection System 2. Number: PRC-005-2(i) 3. Purpose: To document and implement programs for the maintenance of all Protection Systems
More informationStandard PRC Transmission Relay Loadability
A. Introduction 1. Title: Transmission Relay Loadability 2. Number: PRC-023-2 3. Purpose: Protective relay settings shall not limit transmission loadability; not interfere with system operators ability
More informationSee the table on the following Page for full descriptions of each Pin Type.
8 Pin Comms-22-1 8 Pin Comms Task Format IMPORTANT NOTES: Hardware Compatability. The 8 Pin Comms Task can only be used in Type 2 (CE) Control Module Hardware. 22. Firmware Compatablility. INTRODUCTION.
More informationCITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS.
CITY OF WHITEHORSE SERVICING STANDARDS MANUAL SECTION 2 - CONSTRUCTION DESIGN CRITERIA SUB-SECTION 2.A SCADA STANDARDS Table of Contents 2.A.1 SCADA Standards 2.5-2 2.A.1.1 Generators 2.5-2 2.A.1.2 Building
More informationINTEGRATION OF DEMAND RESPONSE INTO TITLE 20 FOR HOT FOOD HOLDING CABINETS
Design & Engineering Services INTEGRATION OF DEMAND RESPONSE INTO TITLE 20 FOR HOT FOOD HOLDING CABINETS Phase1: Demand Response Potential DR 09.05.07 Report Prepared by: Design & Engineering Services
More informationElectrical Safety Through Design. Mersen EP formerly Ferraz Shawmut
Electrical Safety Through Design Mersen EP formerly Ferraz Shawmut Agenda Who is Mersen? Selective Coordination Code Requirements Coordination Made Easy Mitigating Arc Flash Energy on Transformer Secondary
More informationStandard PRC Protection System Misoperation Identification and Correction
Standard PRC-004-4 Protection System Misoperation Identification and Correction Standard Development Timeline This section is maintained by the drafting team during the development of the standard and
More informationA REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. i Protection & Control. b^n Telecontrol.
A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical ^ Q ^pfi;sslo4rq Mechanical Civil R LE GD SiG ira rte, E pv/a-07 ^^ O i Protection & Control ^ Gi + 0'''' Transmission & Distribution
More informationMicrogrid Fault Protection Based on Symmetrical and Differential Current Components
Microgrid Fault Protection Based on Symmetrical and Differential Current Components Prepared for Public Interest Energy Research California Energy Commission Prepared by Hassan Nikkhajoei and Robert H.
More information600 Range Dialer Installation Manual. Version 1.0
600 Range Dialer Installation Manual Version 1.0 The information contained is supplied without liability for any errors or omissions. No part may be reproduced or used except as authorised by contract
More information4. Applicability: 4.1. Functional Entities: 4.2. Facilities: 5. Effective Date: See Implementation Plan
Standard PRC-005-2 Protection System Maintenance A. Introduction 1. Title: Protection System Maintenance 2. Number: PRC-005-2 3. Purpose: To document and implement programs for the maintenance of all Protection
More informationMT-374B/364B Operation User s Guide. The Anti-Sweat Energy Saving Controller user s manual
MT-374B/364B Operation User s Guide Parker Hannifin Canada Micro Thermo Technologies TM 12855 Brault Street Mirabel, QC J7J 0C4 Office phone 450-668-3033 Introduction The Anti-Sweat Energy Saving Controller
More informationTRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE
TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE TRACENET TM GENESIS APPLICATION OVERVIEW Control and monitoring systems can play an essential role in heat tracing applications which
More informationStandard PRC Protection System and Automatic Reclosing Maintenance. Standard Development Roadmap
Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:
More informationLong-Range Barrier Sensors
Troubleshooting: Receiver LED never turns ON and the buzzer never sounds Buzzer does not sound if the sensor is triggered Receiver LED is ON and the buzzer sounds all the time Test the power and ground
More informationFCD-wire Contents. List of Figures
FCD-wire Contents FCD-X21 Configuration 1 Introduction... 1 2 Opening the FCD Application... 1 3 FCD Window... 2 4 FCD LEDs... 3 5 Configuration Operations... 4 FCD Info...4 FCD System Info...5 FCD Interface
More information1SPP Notification to Construct
May 23, 2013 1SPP Notification to Construct Mr. Philip Crissup Oklahoma Gas and Electric Co. P.O. Box 321, M/C 903 Oklahoma City, OK 73101 RE: Notification to Construct Approved ITP10 Network Upgrades
More informationDepartment of Planning and Community Development
DEPARTMENT OF PLANNING AND COMMUNITY DEVELOPMENT 1010 10 TH Street, Suite 3400, Modesto, CA 95354 Phone: 209.525.6330 Fax: 209.525.5911 August 1, 2011 MEMO TO: FROM: Agricultural Advisory Board Department
More informationSETTING UP A VIRTUAL KEYPAD WITH A DSC POWERSERIES ALARM SYSTEM
DN1902-0909 SETTING UP A VIRTUAL KEYPAD WITH A DSC POWERSERIES ALARM SYSTEM The purpose of this application note is to configure the EntraPass system to interface with the DSC PowerSeries tm alarm systems
More informationCMD420 / CMD421 Series
3 T M CMD420 / CMD421 Series Digital Current Relay (Overcurrent and Undercurrent) For Three-Phase AC Systems Technical Bulletin NAE1032810 / 06.2016 CMD420 / CMD421 Digital overcurrent and undercurrent
More informationSIMULCAST ALARM SYSTEM
Mobile Communications SIMULCAST ALARM SYSTEM TABLE OF CONTENTS ALARM SHELF 19D902821G1................. LBI-38496 COMPUTER SHELF 19D438294G2............... LBI-38497 TUA1/TEST UNIT........................
More informationReal-Time Root Cause Analysis for Complex Technical Systems
Real-Time Root Cause Analysis for Complex Technical Systems Jan Eric Larsson, Joseph DeBor IEEE HPRCT Monterey, CA, August 29 th 2007 Handling Alarm Cascades Root cause analysis: find the initiating events
More informationDemandAire. amaximize Energy Efficiency aincreased Kitchen Comfort acustomizable Systems. Demand Control Kitchen Ventilation System
Demand Control Kitchen Ventilation System Standard 0. Compliant 08 Listed amaximize Energy Efficiency aincreased Kitchen Comfort acustomizable Systems www.streivor.com Standard and Code Requirements for
More informationUNIVERSITY OF NEVADA, LAS VEGAS
UNIVERSITY OF NEVADA, LAS VEGAS NORTH LAS VEGAS LAND OPPORTUNITY North Campus Background Information November 2009 Regional Context 6 7 18 Small Arms Range Site Context Guiding Principles You cannot depend
More informationwireless. web-based. worthy of the name RACO.
wireless. web-based. worthy of the name RACO. reliable monitoring unequalled accessibility on-demand reporting wireless, web-based alarm detection and notification system from RACO designed specifically
More informationLeaside to Main Infrastructure Refurbishment Project
N6667_Leaside to Main Panels Feb 2016_Clarington Panels 16-02-01 3:22 PM Page 1 Leaside to Main Infrastructure Refurbishment Project Strengthening the transmission system in your neighbourhood N6667_Leaside
More informationEARTH LEAKAGE RELAY. User Manual - Issue 1.0
Earth Leakage Relay www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters EARTH
More informationACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs
ACM8 Series UL Listed Sub-Assembly Access Power Controllers Installation Guide Models Include: ACM8 - Eight (8) Fuse Protected Outputs ACM8CB - Eight (8) PTC Protected Outputs Rev. 042811 More than just
More informationChexit, RCM and DE5300
Launch Presentation Chexit, RCM and DE5300 July 2015 Overview Chexit Overview Designed for controlled egress applications Meets both life safety and security & NFPA 101 for "Special Locking Arrangement"
More informationImprovements in Transmission Control Center Alarm Management Practices
Improvements in Transmission Control Center Alarm Management Practices Navin Bhatt, Mahendra Patel, Bill Hollifield, Andrew Hunter 2017 CIGRE Grid of the Future Symposium Cleveland, Ohio, U.S.A. 22-25
More information4. Applicability: 4.1. Functional Entities: 4.2. Facilities: 5. Effective Date: See Implementation Plan
Standard PRC-005-2 Protection System Maintenance A. Introduction 1. Title: Protection System Maintenance 2. Number: PRC-005-2 3. Purpose: To document and implement programs for the maintenance of all Protection
More informationAIS750 Series Alarm Annunciator User Manual (Ver. 2.3 / JUNE. 2014)
AIS750 Series Alarm Annunciator User Manual (Ver 23 / JUNE 2014) 3-350 John Street, Thornhill, tario L3T 5W6 Phone: 289 597 APEX (2739) Fax: 289 597 2200 Toll Free: 1 866 776 2943 Email: mail@annunciatorca
More information5. How and Why the Blackout Began in Ohio
5. How and Why the Blackout Began in Ohio Summary This chapter explains the major events electrical, computer, and human that occurred as the blackout evolved on August 14, 2003, and identifies the causes
More informationAUTO SWITCH ALARM PS1 PS2 CH2 MANUAL REMOTE HISTORY ALARM ONLINE AUTO MANUAL SELECT SWITCH RESET
Instruction Manual Model 1582-125L 1:1 Switch February 2017, Rev. 0 CH1 HISTORY LINE HISTORY RESET AUTO MANUAL SELECT CH2 HISTORY LINE RESET MANUAL REMOTE AUTO PS1 PS2 MODEL 1582 CROSS TECHNOLOGIES INC.
More informationWireless D.I.Y. Alarm Kit
Wireless D.I.Y. Alarm Kit User Manual December 2010 MAMI 21 Hubert Mathew Road Illiondale 1610 Tel: +27 11 452 4737 Email: sales@mami.co.za page 2/10 General The Wireless DIY kit, is a pre-programmed,
More informationBulletin 1608N MiniDySC Dynamic Sag Corrector
User Manual Bulletin 1608N MiniDySC Dynamic Sag Corrector Single Phase Voltage Sag Correction 2...6 Amps (250...750 VA) Important User Information Solid-state equipment has operational characteristics
More informationSystem 9000TS Event Recorder
Important notes The 9000TS System described herein operates on a logic voltage of VDC and as standard +VDC is used for the field contact supply voltage. External power supplies using higher voltage ac/dc
More informationCOMMUNITY DEVELOPMENT SERVICES PLANNING AND BUILDING DEPARTMENT PLACERVILLE OFFICE:
COMMUNITY DEVELOPMENT SERVICES PLANNING AND BUILDING DEPARTMENT http://www.edcgov.us/devservices/ PLACERVILLE OFFICE: LAKE TAHOE OFFICE: 2850 Fair Lane Court, Placerville, CA 95667 924 B Emerald Bay Rd.
More informationACM4 Series UL Listed Sub-Assembly Access Power Controllers
ACM4 Series UL Listed Sub-Assembly Access Power Controllers Installation Guide Models Include: ACM4 - Four (4) Fuse Protected Outputs ACM4CB - Four (4) PTC Protected Outputs Rev. 051311 More than just
More informationDepartment of Planning and Community Development
DEPARTMENT OF PLANNING AND COMMUNITY DEVELOPMENT 1010 10 TH Street, Suite 3400, Modesto, CA 95354 Phone: 209.525.6330 Fax: 209.525.5911 August 1, 2011 MEMO TO: FROM: Agricultural Advisory Board Department
More informationNY LCC Data Specification
NY LCC Data Specification Purpose: This specification is prepared for and by Central Hudson Gas & Electric Corporation, Consolidated Edison Company of New York, Inc.; Long Island Power Authority; Niagara
More informationCOUNTY OF INYO COUNTY COMMERCIAL CANNABIS PERMITTING OFFICE
COUNTY OF INYO COUNTY COMMERCIAL CANNABIS PERMITTING OFFICE 207 WEST SOUTH STREET BISHOP, CA 93514 760.873.7860 NOTICE OF AVAILABLE COMMERCIAL CANNABIS BUSINESS LICENSE(S) AND REQUEST FOR APPLICATIONS
More informationLA5579 Wireless Siren Operation Manual
LA5579 Wireless Siren Operation Manual Introduction The Wireless Siren is based on advanced wireless technology using in home automation system, between the Wireless Siren and Control Panel communicated
More informationBurglar Alarm System 12: 30. Fri 03rd March. Partial Armed Disarmed. Technical Manual 03_
Burglar Alarm System B2 1 2 3 4 5 6 7 8 9 10 12: 30 Fri 03rd March Partial Armed Disarmed Technical Manual 03_09-24848601 1 2 CONTENTS 1- GENERAL SETTING INFORMATION Page 5 Introduction... 6 General Information
More informationPRODUCT CATALOGUE. Cape Town 18 Darter Road Blue Water Estate Kommetjie. Gauteng 245 Louis Botha Avenue Orchards Johannesburg
PRODUCT CATALOGUE Cape Town 18 Darter Road Blue Water Estate Kommetjie Luke Fowles - 076 161 8124 luke@providenttech.co.za Frank Fowles - 082 445 1541 frank@providenttech.co.za www.providenttech.co.za
More informationStandard PRC Protection System Misoperation Identification and Correction
Standard PRC-004-3 Protection System Misoperation Identification and Correction A. Introduction 1. Title: Protection System Misoperation Identification and Correction 2. Number: PRC-004-3 3. Purpose: Identify
More informationHTC-915-CONT. Heat-Trace Control system
Heat-Trace Control system Product overview The Raychem HTC-915 system is a compact, full-featured microprocessor-based single-point heat-trace controller. The HTC-915-CONT provides control and monitoring
More informationCommissioning the Fire Suppression System for 500/230 kv Transformers of EGAT s Nongchok Substation
Commissioning the Fire Suppression System for 500/230 kv Transformers of EGAT s Nongchok Substation S. Chaipitak, Electricity Generating Authority of Thailand, +6624362432, Chaipitak.som@egat.co.th ABSTRACT
More informationIF-L/RF Protection Switch
Instruction Manual Model 1582-1152 IF-L/RF Protection Switch August 2014, Rev. 0 CH1 HISTORY ALARM LINE HISTORY RESET AUTO MANUAL SELECT CH2 HISTORY ALARM LINE RESET MANUAL REMOTE AUTO ALARM PS1 PS2 MODEL
More informationinstallation & operation manual
installation & operation manual TABLE OF CONTENTS INTRODUCTION... 2 FEATURES... 2 PROGRAMMING CONTACT ID... 3 INSTALLATION... 3 OPENING THE HAWK COVER... 3 POWER SUPPLY... 5 CHECK AC... 5 DRY CONTACTS
More informationWIRELESS TEMPERATURE & HUMIDITY STATION INSTRUCTION MANUAL
WIRELESS TEMPERATURE & HUMIDITY STATION INSTRUCTION MANUAL MODEL: S82967 DC: 071118 FIND MANUALS, FAQS, AND MORE UNDER THE SUPPORT TAB HERE: www.lacrossetechnology.com/s82967 TABLE OF CONTENTS 3. Power
More informationThe system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.
FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001
More informationINSTALLATIONSANVISNING INSTALLATION MANUAL INSTALLATIONS ANLEITUNG. LD-64 Profibus
LD-64 Profibus INSTALLATISANVISNING INSTALLATI MANUAL INSTALLATIS ANLEITUNG Galvanic Isolation 6073-2031 Transient Protection Balanced Transmission CE Approved Westermo Teleindustri AB 2001 REV. B Fiberoptiskt
More informationType 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B
PRODUCT BULLETIN SB 8001B Type 8001 ALARM ANNUNCIATOR TYPE8001 FEATURES 16 or 32 alarm points per flush mount enclosure Displays are backlit with long life LEDs and engraved to suit Dimmer controls built
More informationCampus Infrastructure Overlay Land Use Designation
Appendix G LRDP Amendment 3 Campus Infrastructure Overlay Land Use Designation Introduction The West Campus Solar Farm Project will provide sustainable and renewable energy to serve the UCR campus. The
More informationBARREN RIDGE RENEWABLE TRANSMISSION PROJECT
August 2011 BARREN RIDGE RENEWABLE TRANSMISSION PROJECT Visual Resources Technical Report PROJECT NUMBER: 115244 PROJECT CONTACT: GINA FEGLER EMAIL: gina.fegler@powereng.com PHONE: 208-288-6281 Draft Visual
More informationFire control panel detect 3004 plus and accessories
Fire control panel detect 3004 and accessories The modular fire alarm panel detect 3004 is the basic version of a broad product portfolio of the system detect 3000. Up to 20 fire control panels can be
More information