1 SUPPLEMENT 7 The Application of Performance- Based Design Concepts for Fire and Life Safety Milosh Puchovsky, P.E. James Quiter, P.E. Editor s Note: This supplement provides a brief overview regarding the application of performance-based design approaches for fire and life safety. Specific examples regarding egress, occupant loading, structural fire protection, smoke management, and sprinkler protection are addressed. Milosh Puchovsky, P.E., is a principal fire protection engineer with NFPA, where he oversees NFPA s projects on Performance-Based Codes and Fire Risk. He also serves as staff liaison to a number of technical committee projects, including those responsible for NFPA s Building Construction and Safety Code and Life Safety Code. Milosh also oversees NFPA s High-Rise Building Safety Advisory Committee. Jim Quiter, P.E., is a principal of Arup and the leader of Arup Consulting in the United States. He is also chair of the Safety to Life Technical Correlating Committee and a member of the NFPA 5000 Technical Correlating Committee, as well as Chair of the NFPA High- Rise Building Safety Advisory Committee. Jim is a registered professional engineer in several states. The application of performance-based design concepts has been permitted by various codes and standards through equivalency or alternative means of protection provisions. Initially, the overall concept was to allow for the use of alternative approaches or technologies in meeting the intent of the code. As such, equivalency concepts were pursued where the code did not specifically address a given situation, or where priority was given to a design concept that called for a building arrangement or feature that was not in strict compliance with the prescriptive provisions of the code. While the equivalency approach has been implemented for decades, no guidance or established approach existed that would aid the designer or the enforcing authority in making appropriate decisions about the equivalent means of protection. Over the past several years, a more formalized approach to the equivalency concept has been developed. This approach is often referred to as performance-based design. Both the Society of Fire Protection Engineers (SFPE) and NFPA have developed guidance documents in this regard. 1,2 As noted in Chapters 4 and 5 of the Life Safety Code, performance-based design is now specifically addressed and permitted by NFPA 101 as well as NFPA 5000, Building Construction and Safety Code. 3 The application of performance-based design for fire safety should include a risk analysis to identify the types of fires to be considered. This is an important step, as the threat to occupants by fire needs to be identified and quantified if an appropriate fire safety solution is to be developed. Traditional building regulations do not identify the fire hazard against 1207

2 1208 Supplement 7 The Application of Performance-Based Design Concepts for Fire and Life Safety which the standard protects. In most cases, building regulations prescribe a solution to some unidentified or vague fire situation. Performance-based design provides a more flexible approach, allowing greater design freedom while specifically addressing fire and life safety concerns of a specific building project. When properly applied, it provides a more informed approach so that life safety risks can be more carefully addressed. Performancebased design also typically involves the use of computer fire models or other fire engineering calculation methodologies, such as timed egress studies, to help assess if the proposed fire safety solutions meet the fire safety goals under the conditions specified. Although performance-based design can be applied to any building project, it is most effective for complex and unusual structures, particularly those that do not fit well within the guidelines of prescriptive building regulations. Examples include convention centers, shopping malls, airport terminals, transportation centers, and buildings with unenclosed vertical openings, all of which pose challenges with regard to egress, spread of fire and smoke, and detection and suppression. Museums and historic structures also benefit from performance-based design because the designers of these buildings must balance aesthetics and historic preservation with fire safety concerns, and building regulations do not usually address property protection or historic preservation. For similar reasons, industrial facilities with hazardous or sensitive processes and contents also benefit from performance-based design. EGRESS FROM AN OBSERVATION TOWER In developing the fire and life safety program for a building such as an observation tower with a large population and amusement rides, numerous issues need to be addressed. The tower rises over 900 ft (274 m) above grade, with eight occupied levels and two amusement rides in the pod or upper portion of the tower. At the base of the tower is a casino building. Occupied floors of the pod include two levels of observation deck, a restaurant, a meeting room level, wedding chapels, and a bar level. The top level functions as an amusement level, containing a roller coaster and space shot ride. Exhibit S7.1 illustrates level 6 of the pod, which functions primarily as a restaurant. Exhibit S7.2 illustrates level 8 of the pod, which functions as the lower observation level. Exhibit S7.3 illustrates level 1 of the pod, which serves as one of two refuge areas. The most obvious concern is providing for emergency egress, considering that the lowest occupied floor is 795 ft (242 m) above grade. In accordance with applicable regulations, some floors of the structure could include an occupant load in excess of 500 people. Strict adherence to the Life Safety Code requires three remote exit stairs leading from the top of the tower to the base of the building. The physical area of the supporting structure is not large enough to provide remotely located stairs in accordance with the Code, and the height of the building makes the use of stairs as a means of egress somewhat impractical. An alternative approach based on performancebased design concepts was necessary to develop a workable egress strategy. Exit Program The primary evacuation method for this building is the use of typical exit stairs for the occupied floors, discharging to areas of refuge on the lowest two floors of the pod. In other words, from floors 3 through 10 of the pod, three sets of exit stairs are provided, each enclosed in 2-hour fire-resistant construction, just as would be found in most other buildings. However, these stairs discharge to an area of refuge at the lowest two levels of the pod, which is still 750 ft (230 m) above grade. These two areas of refuge are used for no other purpose, and consist entirely of noncombustible construction. Rather than rely on mechanical systems to maintain the areas of refuge free of smoke in the event of a fire, the two floors are open to the surrounding exterior environment so that natural ventilation occurs. Since the two areas are below the occupied levels, it is unlikely that a fire in an occupied level would spread to the areas of refuge. Additionally, all the floors including the areas of refuge are provided with sprinkler, standpipe, and alarm systems, further reducing the likelihood of downward fire spread. (Detectors are located on all floors other than the open refuge floors.) From the area of refuge, a single stair leads down through the shaft of the tower to grade. The primary evacuation route from the area of refuge involves the elevators. These elevators have two levels and travel at a speed of up to 1,800 ft/min. They can discharge either within the main casino or at two specially designed discharge levels at the roof of the base building. These discharge levels are enclosed in 2-hour fire-resistant construction from the roof to grade and are separated from all other areas by 2-hour fireresistant construction. Special Elevator Shaft Protection To increase the reliability of the elevators and the safety of the elevator car occupants, special protection 2006 Life Safety Code Handbook

3 Egress from an Observation Tower 1209 Exhibit S7.1 Observation tower, pod level Elevator lobbies are on a separate smoke control zone to maintain pressurization with relation to adjacent spaces. Therefore, smoke in an adjoining area will not spread into an elevator lobby. 4. Openings into the elevators are slightly raised from the remainder of the floor, preventing water flow on a floor level from spilling into the elevator hoistway. 5. Because the areas of refuge are at the two lowest floor levels of the pod, the elevators will not need to travel past a fire floor. Elevators will travel only between the areas of refuge and the base building. Areas of refuge for disabled persons are provided within the enclosed pressurized stairwells at each level. 6. Elevator shafts are vented to the outside at the top, and the vents are separate from the machine rooms. In addition, the machine rooms form sepahas been provided. The tower design was undertaken during the same time period in which the National Institute of Standards and Technology (NIST) was initiating studies on the use of elevators for building evacuation. Many of the recommendations developed by NIST have been incorporated as design concepts for the tower. The concepts include the following: 1. Elevators open into 2-hour fire-resistance-rated elevator lobbies on all floors, at both the top and the bottom of the building. 2. There are four elevators that travel through the shaft from the base to the top. Two independent elevator machine rooms serve these elevators. The elevator machine rooms are separated by 2-hour fire-resistant construction and have a 4-in. curb installed between them so that water flow in one machine room will not affect the other. Life Safety Code Handbook 2006

4 1210 Supplement 7 The Application of Performance-Based Design Concepts for Fire and Life Safety Exhibit S7.2 Observation tower, pod level 8. rate smoke control zones, and air-conditioning for the machine rooms is on emergency power. 7. All four elevators are on emergency power. The emergency power riser is in a separate dedicated 2-hour shaft. 8. Only three of the elevators are assumed to be available for evacuation purposes. The fourth elevator is dedicated for use by the fire department. Stairs In addition to the elevator evacuation, a single stair leads down through the tower and discharges to grade. The stair enclosure is pressurized and remains independent of the base building. Enlarged stair landings at predetermined levels allow occupants to stop and rest as they descend through the building. In addition, the three stairs in the pod of the building are enclosed in 2-hour fire-resistant construction and pressurized. Each of these stairs has areas of evacuation assistance, with communication capability to the central control room. Occupant Load Determination With a building of this type, it is important to understand and control the occupant load. Three methods were used to determine occupant load. Once the three calculations were performed, the lowest occupant load calculated was used as the limiting factor for the building. Areas of Refuge. Building codes and the Life Safety Code typically allow holding areas or areas of refuge for horizontal exits. Where those holding areas are used, the codes require a minimum of 3 ft 2 (0.28 m 2 ) per person. Therefore, one of the limiting factors for this building was the size of the areas of refuge. De Life Safety Code Handbook

5 Egress from an Observation Tower 1211 Exhibit S7.3 Observation tower, pod level 1. termining their maximum holding capacity provides a factor of safety for several reasons, as follows: 1. The area of stairs leading to the areas of refuge was not included in the holding area. These stairs would significantly increase the number of people that could be safely accommodated within an area separated from the fire by 2-hour construction. 2. The calculations assume that no occupants are leaving the building via elevator or stair. Instead, they assume that all occupants are contained within the areas of refuge. 3. The evacuation scenario is to evacuate the floor of origin, the floor above, and the floor below. Therefore, only a portion of the building would be simultaneously evacuated. However, the occupant load of the entire building is limited by the size of the area of refuge. Code Calculations. The second means of determining the occupant load of the building was based on code calculations. The expected occupant load, based on the applicable building code, was calculated for each floor of the building. The load was then totaled for the entire building, and this occupant load was used as a limiting factor for the number of people in the building. Evacuation Capacity. The third determining factor was the capacity of the elevators to evacuate occupants. The speed of evacuation was based on calculation methods for elevator evacuation contained in Life Safety Code Handbook 2006

6 1212 Supplement 7 The Application of Performance-Based Design Concepts for Fire and Life Safety NIST studies. For this project, it was concluded that a 1-hour time frame was reasonable to fully evacuate the areas of refuge. This 1-hour time frame was based on three of the four elevators being used for evacuation, with the fourth dedicated solely to fire department use. The 1-hour calculation also ignores the availability of the stair leading down through the shaft. Therefore, by this calculation, all occupants are expected to leave via the three elevators. It should be noted that operational considerations require the occupant load to be further limited if one of the elevators is out of service for repair. Once these three methods of calculation were completed, an occupant load of approximately 2600 people was developed as the expected load of the building. This was the load factor around which the remainder of the building was designed. To ensure that this load factor is not exceeded, the building owner has instituted an occupant counting system that keeps track of the number of people entering and leaving the tower. Therefore, the load of the building will not exceed the calculated occupant load. A key aspect of the egress program is crowd management during an incident. The tower staff have been trained to direct people to the nearest stair and areas of refuge. Other staff have been trained to respond immediately to the area of refuge and to direct people to either the stair or the elevator queue. Railings are provided to help establish queues at the elevators. Signage and floor path markings are also evident to help guide people arriving in the refuge area. Other Features The evacuation system was not designed as a standalone system. The fire protection features for the project were specifically designed to rapidly detect and control a fire, to control smoke generated by likely fires, and to ensure that a backup electric power system was available. The building is completely protected with automatic sprinklers. Sprinkler densities exceed those required by the codes. The sprinkler system was calculated to provide a very high density for the first four sprinklers operating, plus ordinary hazard density for the most remote 1500 ft 2. Water supply is from two pumps at street level, which pump up to the pod. There is on-site water storage within the pod and two additional pumps sized for sprinkler plus standpipe demand in the pod. With these pumps and on-site water storage, redundant water supply is available. The building is fully protected with automatic smoke detectors, except that kitchens contain heat detection. The smoke detectors are on an addressable system, with alarm verification to reduce the number of unwanted alarms. Manual fire alarm boxes are also provided in the facility. To reduce unwanted alarms, the boxes have been placed within the stairways. The alarms report to the main central control room for the casino, as well as to two auxiliary control rooms. One of the auxiliary control rooms is located at the base of the tower; the second is located within the area of refuge at elevation 750 ft (230 m). The control room within the area of refuge is accessed directly from the fire fighters elevator. Communication and information flow from the three control rooms is identical. The fire alarm system is a Class A system, with separate risers running up through the shaft. The risers are separated by 2-hour fire-resistant construction. Emergency power is sized to accommodate all portions of the fire protection system, including the fire pumps, fire alarm system, all elevators, smoke control, and necessary lighting. The emergency power riser is routed through a separate 2-hour shaft up through the tower, in order to prevent a single event from impacting the primary and emergency power. The building is provided with an automatic smoke control system. Upon actuation of an alarm, the floor of origin and any floors open to it go to full exhaust while adjoining floors are pressurized. In addition, the elevator lobbies for all floors are pressurized, as is the stair leading down through the shaft of the tower. Exhaust from the smoke control system is ducted to discharge above the ride level at the top of the tower, in order to eliminate reintroduction of smoke into the building. The observation tower required a fire protection approach that departs from the typical building code approach to a building. Use of stairs as the sole evacuation method was not feasible or reasonable. Requiring all of the occupants to utilize stairs would result in an unsafe condition for many of the expected occupants of this building. A more reasonable method was to provide an area where people could be staged until evacuated and a reliable means to perform that evacuation. In this example, the performance-based design approach was shown to provide protection in accordance with the overall intent of the building codes, while departing significantly from the detailed prescribed code requirements. SPRINKLER PLACEMENT IN AN ART GALLERY The design concept for the upper floor of an art gallery called for a unique roof/ceiling structure con Life Safety Code Handbook

7 Sprinkler Placement in an Art Gallery 1213 Section 1 1 Section 2 2 Exhibit S7.4 Plan view of ceiling arrangement. Section A A 15 ft 6 in. 4 ft 0 in. 38 ft 1¹ ₂ in. 3 ft 10 in. sisting of a grid of approximately 800 skylight pockets. NFPA 13, Standard for the Installation of Sprinkler Systems, 4 does not address the ceiling arrangement, and a fire engineering analysis was necessary to address the relevant fire safety concerns and develop appropriate sprinkler positioning and spacing criteria. The ceiling/roof structure consisted of a grid of circular skylight pockets extending approximately 60 in. (1500 mm) from their base to their peak. The opening to the skylight pocket was approximately 42 in. (1070 mm) in diameter. The separation between adjacent skylight pockets was approximately 14 in. (360 mm), with the supporting members approximately 48 in. (1200 mm) apart. The ceiling height (to the base of the skylight pockets) was approximately 216 in. (5490 mm) from the floor below. A rendering of a section of the ceiling/roof arrangement is shown in Exhibits S7.4 and S7.5. Because of the depth, area, and arrangement of the skylight pockets, the specific rules of NFPA 13 concerning sprinkler positioning were not directly applicable and did not adequately address the relevant fire and life safety concerns. Locating sprinklers in each pocket was undesirable in terms of both functionality and aesthetics. Locating sprinklers in the pockets would place them farther away from the floor where a potential fire was expected to occur, prolonging the time to sprinkler activation. Once activated, the sprinklers would not be able to develop their proper spray pattern if positioned in the skylight pocket; the result would be a column of water discharged from each skylight pocket. Also, locating sprinklers in alternating pockets would result in an unacceptable delay in sprinkler activation unless the fire was located directly below a skylight with a sprinkler. Section A-A 3 ft 10 in. 38 ft 1 ¹ ₂ in. Exhibit S7.5 Section view of ceiling/roof arrangement. 17 ft 9¹ ₂ in. Locating sprinklers in the supporting grid at the base of the pockets appeared to offer the best option. However, because of the depth of the pockets, the sprinklers would be positioned more than the distance permitted by NFPA 13 from the top of the skylight pocket. In this case, proper sprinkler spacing needed to be determined. Fire engineering employing computer fire models offered an effective means of analyzing how sprinklers would perform under the skylights. During a fire, the skylight pockets, because of their depth and number, would serve as heat reservoirs and have an impact on sprinkler activation. How much of an impact would be a function of numerous factors including the design fire, fire dynamics, ceiling and room geometry, and sprinkler type, spacing, and positioning. It is important to note that NFPA 13 only provides information on how to install sprinklers; it provides no information or criteria for how soon after the start Life Safety Code Handbook 2006

8 1214 Supplement 7 The Application of Performance-Based Design Concepts for Fire and Life Safety of a fire the sprinklers are to activate. It is understood, however, that sprinklers need to activate during the early stages of fire development to be effective in controlling the fire. Computational fluid dynamics (CFD) was applied to help understand the performance expected from an NFPA 13 specified system, to quantify the associated delay caused by the skylight pockets, and to help determine appropriate sprinkler spacing and positioning to achieve the intent of NFPA 13. In this regard, design fires representative of the fuel load in the gallery were quantified, and acceptable sprinkler activation performance criteria were determined. Sprinkler positioning and spacing appropriate to meet the activation criteria for the design fires were identified. Exhibit S7.6 illustrates one scenario modeled and analyzed using Fire Dynamics Simulator, a CFD computer fire model developed and maintained by NIST. The overall approach was to establish design fires representative of the types of fires expected in the gallery space. Various ceiling/roof arrangements permitted by NFPA 13 were then evaluated, using CFD computer models for the specified design fires, to determine sprinkler activation times. These activation times were established as acceptance criteria. Various sprinkler spacing configurations under the roof structure proposed for the upper gallery were evaluated to determine those that would result in a time to sprinkler activation that was less than that established as the acceptance criteria. The analysis established sprinkler activation time criteria for ceiling arrangements addressed by NFPA 13. Three cases (smooth, flat ceiling; ceiling channels; and ceiling grid) were evaluated for the types of fires expected in the gallery. The maximum sprinkler spacing and maximum distance between the sprinkler deflector and ceiling were evaluated to determine acceptance criteria. The engineering analysis included several factors that allowed a degree of conservatism to account for uncertainties in both the analysis and the forthcoming installation process and allowed some flexibility in potential future modification of the design concept. These factors included the following: 1. Using ceiling heights less than that proposed for the upper gallery in the determination of acceptable criteria as allowed by NFPA 13. This created shorter sprinkler activation times. 2. Spacing ceiling members closer than the maximum permitted by NFPA 13 in the determination of acceptable criteria. This created shorter sprinkler activation time. 3. Establishing a design fire with higher rates of heat release than those for the types of combustibles Exhibit S7.6 CFD analysis of sprinkler activation Life Safety Code Handbook

9 Life Safety for a Botanical Garden Project 1215 typically expected in the gallery. This flexibility allowed for contents that might be present in the gallery for special exhibits and functions. The analysis of the gallery roof structure indicated that a sprinkler spacing arrangement could be developed that would result in a sprinkler activation time shorter than that derived from NFPA 13. A performance-based approach was used to develop a means of protection equivalent to that prescribed by NFPA 13. STRUCTURAL FIRE PROTECTION FOR A STUDENT CENTER One of the design objectives for a university student center project was to create an open and uncluttered feel for the atrium. The intent was to use exposed slender structural steel elements to support the glazed façade, the circulation ramps, and the roof. According to the applicable building regulations, the structural elements in the atrium needed to have a certain fire resistance rating. Conventional methods of achieving such a rating such as cladding or coating the structural members with a cementitious material or intumescent paint would have been effective but would have diminished the desired architectural effect and negatively affected overall project functionality. A performance-based design approach was developed as an equivalent means of meeting the building code requirements. A code analysis was conducted, and a fire strategy outlining the approach to resolve the relevant issues was prepared. The concerns of the associated stakeholders, including the local enforcing authorities, were identified and articulated, as were the design fires and criteria for determining acceptance of the alternative design. Risk analysis principles were used to determine the likely fire hazards expected in the atrium space. Design fires were developed to quantify the relative size, duration, and characteristics of the fires anticipated. At the same time, the failure criteria in terms of fire resistance of the structural steel members proposed were also determined. It was agreed that the alternative design would need to withstand the impact of the design fires for a minimum time period of hourly fire resistance rating specified by the building code. The performance of the structural steel members when exposed to the specified design fires was evaluated through the use of modeling and with the collaboration of structural engineers. The analysis included the effect of the structural member composition, as well as the means and spacing of structural supports and the methods of fastening. The analysis indicated that the structural elements could withstand the respective fire loads represented by the design fires for the time period associated with the code-prescribed fire resistance rating. To account for a degree of uncertainty and to provide for a factor of safety, it was proposed that the spacing of the structural members supporting the walkways and roof structure be decreased from what was initially specified, resulting in some redundancy of the structural support system. The effect of this arrangement was that, should a given structural member prematurely fail, there was a reduced likelihood that the entire structure would fail. Thus, it was demonstrated that the conventional fire resistance rating of the structural elements could be achieved through other means, and that an equivalent means of protection could be provided for the anticipated design fires. A timed egress study was also undertaken to verify that occupants could evacuate from this space before the building structure suffered any negative effects from the fire. An approach based entirely on prescribed code requirements does not specifically consider building performance or occupant response under expected fire conditions. Building codes consider classes of buildings generically and do not address specific fire hazards, unique building features, and occupant characteristics. As a result, code-prescribed solutions can provide for excessive fire protection in some instances and inadequate protection in others. With a performance-based approach, the architects in the university student center project were able to implement their design vision while adequately addressing applicable fire safety concerns. LIFE SAFETY FOR A BOTANICAL GARDEN PROJECT The design of a botanical garden project consisting of multiple floor levels carved into the surrounding hillside presented unusual challenges for fire and life safety. The project entailed a freestanding structure reaching 180 ft (55 m) at its highest points and covered an overall area of 5.4 acres (21,853 m 2 ). From the outset, it was clear that a prescriptive code approach would be of limited value for the project. The applicable building regulations classified the structure as an assembly occupancy, but if the project had been designed to fit the requirements of the prescriptive code, the design team would have been faced with trying to make the building conform to requirements derived from safety measures intended for theaters, arenas, and other more conventional Life Safety Code Handbook 2006

10 1216 Supplement 7 The Application of Performance-Based Design Concepts for Fire and Life Safety public buildings. The relevance of the prescriptive requirements was clearly limited for the project there was no rule book to follow. Early on in the design project, it was proposed that fire and life safety provisions be developed through performance-based design. This was discussed and agreed upon with the client and the local building and fire authorities. The fire hazards in a building like this are very different from those typically encountered in conventional buildings. The vegetation clearly constituted a fire load, potentially an extremely large one, so the potential for a forest fire-type scenario was discussed. The team carried out a qualitative hazard analysis of the risk in terms of frequency and consequences of a vegetation fire in the structure, but this showed such a fire to be of sufficiently low probability that it was an impractical design parameter. The examination of fire loading, therefore, turned to items other than the vegetation. Throughout the structure, huts are provided as information points for visitors. The huts are built of timber, with thatched roofs, and also have electrical power. Scenarios involving a fire in a hut were therefore developed as the basis for the fire safety design. Because large visitor populations were anticipated, safe and efficient evacuation was a key concern in developing the fire strategy. The circulation (and, hence, evacuation) routes are far from conventional, as visitors walk around the botanical gardens on winding pathways linked to exits around the perimeter. Also, because the structure cuts into the hillside, pathway elevations vary considerably. A major challenge was to address the scale of the building, reflected in the length of the travel routes. If travel distance requirements of the building regulations were to be met, escape from the upper parts of the structure would require tunnels cut through the side of the hill. Such tunnels would probably need to have been pressurized, as they would have been at the upper levels of the project near potential smoke layers. Other options were needed. The fire engineers proposed that evacuation be based on the time period necessary to egress the building rather than strictly on the distance to be traveled. The approach was to demonstrate that occupants could egress the facility prior to the onset of untenable conditions. The majority of the exits were located on the lower grades of the project, so, in the event of a fire, the occupants would travel to lowerlevel exits rather than use exits at the top of the botanical garden. Lower-level exits were also preferred as they encouraged the population to move away from the upper levels, where smoke would accumulate. While this route would result in evacuation distances of up to 450 ft (137 m), these distances were demonstrated to be acceptable due to the overall low level of hazard and large size of the space. To verify the proposed strategy, combined smoke and evacuation calculations using computer models were undertaken. Based on the design fires, this allowed for a dynamic fire and smoke spread analysis of the actual geometry of the space. The timed egress study also considered various scenarios, such as the effect of blocked exits. Due to the structure s unique geometry, conventional smoke modeling software packages which assume rectangular box-type enclosures were unsuitable for calculating the rate of smoke fill. Project-specific calculations were therefore developed that allowed for the geometry of botanical garden spaces, using a three-dimensional model of the structure. From the model, it was possible to accurately determine the cross-sectional plan area of the project at various heights, and hence assess smoke filling rates using design fire scenarios agreed upon with the local authorities. The egress modeling showed that the project could be evacuated in 5 to 6 minutes, while the smoke modeling indicated that a smoke layer would not descend to levels where it would impede evacuation for 15 to 25 minutes (depending on the fire scenario). The team concluded that the escape distances could be safely extended and evacuation conditions would be acceptable under the conservative scenarios studied. Many fire safety systems conventionally associated with public assembly spaces were unsuitable. Detection methods including optical and aspirated smoke detection were found to be ineffective, due to the potential for smoke stratification to delay detection at high levels and plants obscuring optical detection sight lines. Although the associated structures are essentially low fire hazard spaces, the fire safety strategy had to be developed from a common-sense, first principles point of view. The recognition that there was little relevant guidance for the project, and that adherence to conventional codes would result in unnecessary, costly, and ineffective measures, unlocked the design process. Close collaboration with the architect, enforcement officials, and other engineering disciplines allowed each team member to fully participate in developing the design and clearly understand the thought process and reasoning behind the proposed strategy. The result is a simple, robust, and cost Life Safety Code Handbook

11 Cultural Preservation of a Historic Building 1217 effective strategy that provides a high level of fire safety for the botanical garden s occupants. CULTURAL PRESERVATION OF A HISTORIC BUILDING For historic structures, performance-based design concepts often offer the most viable and effective solution for meeting both fire safety needs and cultural preservation goals. One such project was a designated landmark building consisting of cast iron and decorative masonry construction with ornate public and ceremonial spaces centered around an open atrium. The building was originally constructed in the mid-1800s to operate as a courthouse. It consisted of approximately 150,000 ft 2 (14,000 m 2 ) over several floors. The proposed design concept for the courthouse building called for a comprehensive, governmentfunded restoration and rehabilitation program to prepare the building for adaptive reuse as a multifunctional public and cultural facility with exhibition space, offices, and a restaurant. The design concept for the project called for the preservation of a number of areas and building features, including the open atrium, the ornate original wood doors, and numerous cast iron columns. Although building code requirements are relaxed somewhat for specific features of historic structures, imposing the applicable prescriptive requirements on the project would have affected the overall historic authenticity and compromised the functionality and significance of the public spaces and unique architectural features. Therefore, the overall fire strategy was to identify and meet the intent of the applicable building regulations regarding life safety, while minimizing the aesthetic and visual impact of new construction and maintaining the open environment and original design features to the greatest degree possible. During the early stages of the development of the fire strategy, it became obvious that a conventional, prescriptive code-based approach would have forced a dramatic change to the proposed design concept and that an alternative approach could provide for a more effective and robust level of fire and life safety. In most code-mandated prescriptive designs, the various fire safety features and systems are addressed independently of one another. The performancebased concept calls for an integrated approach of fire and life safety systems. Such an approach is especially pertinent to existing and historic building projects because it can result in less intrusive fire and life safety systems and features while meeting the required level of safety. In historic landmark buildings, this integrated approach typically results in improved building functionality and more cost-effective fire protection systems. One of the major fire and life safety challenges in this courthouse building pertained to the compartmentation of building spaces. Building regulations require compartmentation to help prevent the horizontal and vertical spread of fire through the building. The existing building construction did not provide for the rated fire separations required by building regulations. Many doors were of original heavy wood construction with decorative wood and glass features and did not meet current fire protection ratings. It was proposed that the atrium remain open to multiple floors, existing non-rated shafts be reused as mechanical shafts, and certain building areas be open to each other through open stairways. In developing an appropriate strategy, the aim was to assess the inherent fire protection qualities of existing building features (such as substantially constructed walls and high ceilings), to take advantage of the inherent degree of fire protection, and to supplement it with certain new active systems where necessary. The overall approach was to identify the fire loads (design fires) to be considered and then demonstrate through fire engineering that sufficient fire safety could be provided for the time period intended by the building regulations. In some cases, it was determined that the prescribed fire resistance rating would be needed; for other situations, a performance-based solution was developed. In general, a fire that starts in the non-public areas is to be controlled so that it does not develop and grow to a point where it could threaten occupants in public spaces. Therefore, it was proposed that nonpublic areas the attic and basement, mechanical spaces, and kitchens be separated from public spaces by fire-rated construction. Additionally, areas traditionally constituting a higher fire hazard, such as electrical switch gear rooms, mechanical rooms, and storage areas, were also constructed to form separate compartments. As most of these spaces were non-public spaces, the new construction had a limited impact on the aesthetic features of the building. In addition to compartmentation, other fire and life safety issues were identified and addressed through a performance-based approach. Issues regarding smoke management, egress, structural fire resistance, active systems, and fire-fighting facilities were addressed in a comprehensive manner. The overall fire safety solution integrated existing features with new systems and construction so that the Life Safety Code Handbook 2006

12 1218 Supplement 7 The Application of Performance-Based Design Concepts for Fire and Life Safety level of safety provided by the building code was satisfied, while preserving the historic value of the building to the extent possible. CLOSING REMARKS While considered by some a relatively new approach, performance-based design has been practiced for many years through the equivalency option in many codes and standards. The past several years have seen the development of a more formalized approach for practicing performance-based design, as well as the revision of codes and standards that specifically address performance-based design approaches. Even so, where a performance-based design is pursued, it usually involves a variance by the local building official or regulating body. However, the development of guidelines and definitions of applicable terms serves to better facilitate the discussion between designers and enforcers and allow for better-informed decisions. This supplement has provided a brief overview of the types of projects in which performance-based design has been successfully applied and accepted by the authorities having jurisdiction. Even though performance-based design is gaining more acceptance, the prescriptive code is likely to remain the first means of developing a fire safety strategy for a building. Enforcing authorities have a greater comfort level with the prescriptive rules that are, in essence, the law. As such, code reviews and interpretations are often the first step in developing the fire safety design process. For certain projects or for specific aspects of projects, the prescriptive code does not adequately address a given situation or would be incompatible with the developer s or architect s design vision. In other cases, a more cost-effective alternative would result in the same level of protection as that required by the prescriptive building code. In such cases, performance-based design concepts can be used to develop solutions that address specific issues while complementing the requirements prescribed by traditional building and fire codes. REFERENCES 1. The SFPE Engineering Guide to Performance-Based Fire Protection Analysis and Design, Society of Fire Protection Engineers, Bethesda, MD, Performance Based Primer for Codes and Standards Preparation, National Fire Protection Association, Quincy, MA, NFPA 5000, Building Construction and Safety Code, 2006 edition, National Fire Protection Association, Quincy, MA. 4. NFPA 13, Standard for the Installation of Sprinkler Systems, 2002 edition, National Fire Protection Association, Quincy, MA Life Safety Code Handbook

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P-02-07 THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS March, 2007 Society of Fire Protection Engineers - 1 - Position

More information

Considerations in the Design of Smoke Management Systems for Atriums

Considerations in the Design of Smoke Management Systems for Atriums Construction Technology Update No. 48 Considerations in the Design of Smoke Management Systems for Atriums by G.D. Lougheed This Update discusses the use of an engineered approach to the design of smoke

More information

Fire Protection Coffee Break Training May 2016

Fire Protection Coffee Break Training May 2016 Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers

More information

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE Human Factors - Egress Analysis for High Hazard Occupancies Presented by: Michael J. Klemenz, PE, SFPE Group H Other SFPE presenters today discussed issues relevant to Group H This presentation addresses

More information

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Mandatory Fire Safety Instruction NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS Reference A: Reference B: Approved Document B

More information

Tunnel Fire Dynamics and Evacuation Simulations

Tunnel Fire Dynamics and Evacuation Simulations Tunnel Fire Dynamics and Evacuation Simulations James Priest, PhD & James Niehoff DGS-SEE Seminar on Fire Protection for Physics Research Facilities 7 & 8 October 2015 Introduction (Background) Presentation

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

Statue of Liberty: A Risk Analysis

Statue of Liberty: A Risk Analysis Statue of Liberty: A Risk Analysis Bruce Campbell, FSFPE VP DOE Services National Park Service Agenda Overview of Project Scope Evaluation Steps Task 1 Code Analysis Task 2 Fire Modeling Task 3 Egress

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

1. Revise , from what was done by Second Revision SR-95 (Annual 2014 revision cycle NFPA 101 Second Draft), to read as follows:

1. Revise , from what was done by Second Revision SR-95 (Annual 2014 revision cycle NFPA 101 Second Draft), to read as follows: NFPA 101 -Proposed 2015 Edition Life Safety Code TIA Log No. 1130 Reference: 12.4.1, 13.4.1, A.12.4.1, and A.13.4.1 Comment Closing Date: April 18, 2014 Submitter: Jeffrey Tubbs, Arup and Michael DiMascio,

More information

technical specification smoke venting systems

technical specification smoke venting systems technical specification smoke venting systems An Introduction to FDS FDS sets the standards the rest of the industry follows Providing a complete service for all of your smoke ventilation system needs.

More information

Fire protection documentation. CFPA-E Guideline No 13:2015 F

Fire protection documentation. CFPA-E Guideline No 13:2015 F Fire protection documentation CFPA-E Guideline No 13:2015 F FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation in the

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

Chapter 17, Initiating Devices

Chapter 17, Initiating Devices Chapter 17, Initiating Devices Summary. Chapter 17 was Chapter 5 in NFPA 72-2007. The term authority having jurisdiction is replaced in some sections by the term other governing laws, codes, or standards.

More information

rpsa FIRE PROTECTION ENGINEERS

rpsa FIRE PROTECTION ENGINEERS FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator

More information

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN

SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN , Volume 4, Number 2, p.73-83, 2003 SMOKE MANAGEMENT AND EGRESS ANALYSIS OF A SPORTS ARENA USING THE PERFORMANCE-BASED DESIGN K.H. Yang and C.S. Yang Mechanical Engineering Department, National Sun Yat-Sen

More information

Life Safety - Means of Egress/Exits NFPA 101

Life Safety - Means of Egress/Exits NFPA 101 Life Safety - Means of Egress/Exits NFPA 101 Properly designed exits provide a safe path of escape from a fire or other emergency environment. The means of egress (exits) should be arranged to permit all

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title

More information

Selecting appropriate egress strategies

Selecting appropriate egress strategies Selecting appropriate egress strategies The selection of an appropriate egress strategy requires a good understing of the building its occupants, the protection measures in place, the expected emergency

More information

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN Presented by Ian Levine June, 2016 Photo courtesy of Google Maps PRESENTATION OVERVIEW BUILDING

More information

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c Table 1015.1 EXIT ACCESS TRAVEL DISTANCE a WITHOUT SPRINKLER WITH SPRINKLER OCCUPANCY SYSTEM SYSTEM A, E, F-1, I-1, M, 200 250 b,d R, S-1 B 200 300 c F-2, S-2, U 300 400 c No Change to Other Entries in

More information

IBC Committee Responsibility Matrix January 2017

IBC Committee Responsibility Matrix January 2017 IBC Committee Responsibility Matrix January 2017 Chapter 1 ADMIN same Chapter 3 High-Hazard Group H 307.1 same IFC same Uses Other Than Group H 307.1.1 same IFC same Hazardoss Materials 307.1.2 307.2 IFC

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

National Fire Protection Association 1 Batterymarch Park Quincy, MA USA

National Fire Protection Association 1 Batterymarch Park Quincy, MA USA REVISION 1.0 21 JANUARY 2000 National Fire Protection Association, 1999 National Fire Protection Association 1 Batterymarch Park Quincy, MA 02269-9101 USA Preface This primer has been developed by the

More information

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect

M E M O R A N D U M. All Licensed Assisted Living Facilities. Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect M E M O R A N D U M To: From: Approved: All Licensed Assisted Living Facilities Felicia Cooper, Deputy State Fire Marshal Administrator Don Zeringue, Chief Architect Henry Fry, Deputy Assistant Secretary

More information

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD DESIGNER S GUIDE Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 909 SMOKE CONTROL SYSTEMS 909.1 Scope and purpose. This section applies to mechanical or passive smoke control systems when they are required for new buildings or portions thereof by provisions

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications Smoke shafts - an overview Scope of this guide Smoke shaft is the common term for

More information

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs 1 ABSTRACT Noureddine Benichou and Ahmed H. Kashef * Institute for Research in Construction National Research Council of Canada

More information

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

DEALING WITH FIRE SAFETY

DEALING WITH FIRE SAFETY DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

MD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia

MD-DC-VA Automatic Fire Alarm Association, Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia , Inc. Interfacing Fire Alarm, Sprinkler and Elevator Systems In Maryland, DC and Virginia Presented by: Andrew Roe, SET Alarm Tech Solutions, LLC Scope: The Purpose of Elevator Controls History of Elevator

More information

By: Russell Bainbridge March 18th, 2016 FPE 596

By: Russell Bainbridge March 18th, 2016 FPE 596 By: Russell Bainbridge March 18th, 2016 FPE 596 Egress Analysis and Design California Polytechnic State University's Engineering IV building Fire Detection, Alarm and Communication Systems A warehouse

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

Firefighting operations on automatic sprinklers systems F5-06 GD

Firefighting operations on automatic sprinklers systems F5-06 GD DESIGNER S GUIDE Firefighting operations on automatic sprinklers systems F5-06 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position on design

More information

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION Mid-Rise Workshop, Coast Plaza Inn, Calgary, Feb. 4 th, 2016 Outline Overview of risks Regulations Changes to 2015 NFC for mid-rise

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS SUMMARY Ammonia odours were reported in the community close to the time of the incident (Appendix D) and firefighters reported

More information

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title:

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title: ctbuh.org/papers Title: Authors: Subjects: Keywords: Fire Engineering the Tallest Building in the Historic City of Manchester, UK Dean McGrail, Associate Director, WSP Group Simon Lay, Technical Director,

More information

Interfacing Fire Alarm, Sprinkler and Elevator Systems

Interfacing Fire Alarm, Sprinkler and Elevator Systems 1 Interfacing Fire Alarm, Sprinkler and Elevator Systems Rodger Reiswig, SET Director, Industry Relations SimplexGrinnell November 17, 2010 Interfacing to Elevators 2 ASME A17.1 Safety Code for Elevators

More information

Narrative Reports As Regulated by 780 CMR, Section 903.0

Narrative Reports As Regulated by 780 CMR, Section 903.0 EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes 2012 International Fire Code Significant Changes Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Koffel Associates, Inc. www.koffel.com Expertly Engineering Safety From

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the

More information

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS WHITE PLAINS SMOKE CONTROL CODE a. Application of Code. PART 1. GENERAL REQUIREMENTS The following uniform standards and procedures shall apply to the design, installation and testing of new smoke purge

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter ((shall)) apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

Unit 2 Fire Safety (Zone 2)

Unit 2 Fire Safety (Zone 2) IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 2) Examiner Report March 2017 Introduction 21% of the candidates that sat the examination attained a pass. Candidates did not

More information

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19 PART 3 Building and Equipment Design Features Chapters 5 through 19 Chapter 5 Fire Service Features No changes addressed Chapter 6 Building Services and Systems Chapter 7 Fire-Resistance-Rated Construction

More information

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com

More information

HAWAII ADMINISTRATIVE RULES DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS DIVISION OF OCCUPATIONAL SAFETY AND HEALTH GENERAL INDUSTRY STANDARDS

HAWAII ADMINISTRATIVE RULES DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS DIVISION OF OCCUPATIONAL SAFETY AND HEALTH GENERAL INDUSTRY STANDARDS HAWAII ADMINISTRATIVE RULES TITLE 12 DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS SUBTITLE 8 DIVISION OF OCCUPATIONAL SAFETY AND HEALTH PART 2 GENERAL INDUSTRY STANDARDS CHAPTER 71.1 EXIT ROUTES, EMERGENCY

More information

Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia

Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall. Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia Application of the New Italian Fire Safety Code (D.M. 3 agosto 2015) to Case Study 3 Mall Enrico Danzi Luca Fiorentini Luca Marmo Vincenzo Puccia A Challenging Application for the New Italian Fire Code

More information

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS Part 3 BUILDING CODE MYTHS & INTERPRETATIONS November 18, 2016 Frank Durante, RBO Building Inspector District of Mission Phone 604 820 3729 Wendy Morrison, AScT, BCQ GHL CONSULTANTS LTD Fire Science and

More information

Agency for Health Care Administration

Agency for Health Care Administration Page 1 of 92 ST - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag These guidelines are meant solely to provide guidance to surveyors in the survey process. ST - K0100 - General Requirements

More information

4.1.3 LAND USE CATEGORIES

4.1.3 LAND USE CATEGORIES 4.1.3 LAND USE CATEGORIES a. City Center District The City Center District incorporates the existing character and mix of uses in downtown Belmont to encourage redevelopment and new development in keeping

More information

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007 BUILDING CODE OF THE CITY OF NEW YORK New York City Department of Buildings 4 June 2007 Fatma Amer, PE, Deputy Commissioner, Technical Affairs James Colgate, RA, Executive Architect John Lee, RA Keith

More information

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Fire Science and Technorogy Vol.24 No.4(2005) 165-178 165 Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings Jun-ichi Yamaguchi 1, Takeyoshi Tanaka 2 1 Technical Research

More information

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)

More information

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD

The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD The Swedish National Board of Housing, Building and Planning s general recommendations on the analytical design of a building s fire protection, BBRAD BFS 2011:27 with amendments up to BFS 2013:12 The

More information

The Physical Environment Portal: Module 5, LS Leadership

The Physical Environment Portal: Module 5, LS Leadership The Physical Environment Portal: Module 5, LS.02.01.10 - Leadership Fire Safety: Background Fire safety impacts both the lives of the occupants and the physical structures. In the early 1900 s many buildings

More information

Emergency Ventilation System Design - Preliminary Report Shishir Gupta

Emergency Ventilation System Design - Preliminary Report Shishir Gupta Emergency Ventilation System Design - Preliminary Report Shishir Gupta (shishir@mechartes.com), Abstract The existing stations and tunnels of Metro Railway, Kolkata are not equipped with effective emergency

More information

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device

More information

For the Florida Building Commission And the Fire Code Advisory Council

For the Florida Building Commission And the Fire Code Advisory Council Life-Safety Modifications Mechanical and Existing Building Compared to the 2012 Changes of the International Building Code and National Fire Protection Association- 101 For the Florida Building Commission

More information

ICC CODE CORNER 2015 International Fire Code

ICC CODE CORNER 2015 International Fire Code PART II GENERAL SAFETY PROVISIONS CHAPTER 4 EMERGENCY PLANNING AND PREPAREDNESS SECTION 401 GENERAL 401.1 Scope. Reporting of emergencies, coordination with emergency response forces, emergency plans and

More information

Chapter Nursing Homes

Chapter Nursing Homes Chapter 16.01 Nursing Homes Section 1. Licensing. No nursing, convalescent or old age home, as defined in Section 2 of this ordinance, shall be operated except under a license from the City Council of

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES [B] APPENDIX SR GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES The provisions contained in this appendix are adopted by the Building Codes Division of the State of Oregon SECTION SR101

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 910 SMOKE AND HEAT VENTS 910.1 General. Where required by this code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains shall conform to the requirements

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical self-closing device

More information

SELF PRESERVATION SOCIETY By Jim Creak

SELF PRESERVATION SOCIETY By Jim Creak SELF PRESERVATION SOCIETY By Editor of the Means of Escape Magazine and Chairman of The Health & Safety Signs Association. w w w. m e a n s - of- e s c a p e. c o m Agenda Regulatory Reform Fire Safety

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition Copyright National Fire Protection Association 2013. All rights reserved. This copy is solely for your personal, noncommercial use in connection with participation in the NFPA Standards Development Process.

More information

Module 7. Control of Smoke & Highlights of Code Requirements

Module 7. Control of Smoke & Highlights of Code Requirements Module 7 Control of Smoke & Highlights of Code Requirements 1 Module 7 Overview This module will cover: 1. The requirements of smoke control in the Ohio Building Code Section 909 2. The differences between

More information

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST TENANT IMPROVEMENTS Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;

More information

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard SOCIAL ACCOUNTABILITY ACCREDITATION SERVICES To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard Background: After an

More information

COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE

COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE 100126 The course is organized into three bands. Band A covers HVACrelated building components and other types

More information

Practice Advisory 18: Fire safety design for tall buildings

Practice Advisory 18: Fire safety design for tall buildings Practice Advisory 18: Fire safety design for tall buildings It s important that reliable and resilient fire design features are used in the design of tall buildings. This advisory highlights the specific

More information

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS Mandatory Fire Safety Instruction Reference A: Reference B: NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS Approved Document B Fire Safety

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Section No. Subject Page No. 1 Authority and Purpose 10-1 2 Definitions

More information

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites

More information

Fire evacuation drill

Fire evacuation drill European guideline (handbook) Fire evacuation drill (draft document) Ver: 2010-06-02 Prepared by Aleš Jug, Slovenia Related guideline: CFPA E: 19_2009 Fire safety engineering concerning evacuation from

More information

DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES

DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES NOTE: Each proposed Denver amendment to the International Codes must be justified. In order to be considered, the amendment proposal must address climate,

More information

FORMULATION OF FIRE SAFETY REQUIREMENTS FOR NEW RAILWAY INFRASTRUCTURES

FORMULATION OF FIRE SAFETY REQUIREMENTS FOR NEW RAILWAY INFRASTRUCTURES FORMULATION OF FIRE SAFETY REQUIREMENTS FOR NEW RAILWAY INFRASTRUCTURES Ir Law Chi Keung, Peter Hong Kong Fire Services Department, Railway Development Strategy Division, 2/F Tung Lo Wan Fire Station,

More information