asimplex 4020 Fire Alarm System Contractor Installation Instructions Technical Manuals Online! -

Size: px
Start display at page:

Download "asimplex 4020 Fire Alarm System Contractor Installation Instructions Technical Manuals Online! -"

Transcription

1 asimplex 4020 Fire Alarm System Contractor Installation Instructions Simplex Time Recorder Co FA ( ) All specifications and other information shown were current as of publication and are subject to change without notice Ed 1 95

2 NOTICE FIRST TIME INSTALLERS OF SIMPLEX 4020 FIRE ALARM PANELS AFTER READING THE INFORMATION CONTAINED IN THIS MANUAL, CALL YOUR LOCAL SIMPLEX REPRESENTATIVE BEFORE PROCEEDING TO CONNECT FIELD WIRING! NOTICE FOR POWER-LIMITED SYSTEMS: THE 4020 PANEL HAS INTERNAL BARRIERS TO PREVENT CONTACT BETWEEN POWER-LIMITED AND NON-POWER-LIMITED CONDUCTORS THE AREA IN THE RIGHT AND BOTTOM OF THE PANEL IS RESERVED FOR NON-POWER-LIMITED WIRING DO NOT APPLY AC OR BAlTERY POWER TO THE 4020 SYSTEM (UNLESS IN THE PRESENCE OF A SIMPLEX TECHNICAL REPRESENTATIVE) I

3 TABLE OF CONTENTS PAGE Introduction 1 Supplied Documentation 1 Installation Procedure 1 Inventory the Delivered Equipment l Install the Back Box 2 Mount the Electronics Into the Back Box 2 Install and Tag All System Wiring 2 Install the Peripheral Devices and EOL Resistors 3 MAPNET II@ Address Chart 4 Check and Terminate All Field Wiring 5 Neatly Dress the Panel Wiring 7 Install the Retainer 7 Install the Panel Door 7 Install the Door Bumpers 7 Ground the Door to the Back Box 7 Close and Lock the Panel Door 7 Call Simplex 7 FIGURES FIGURE PAGE Panel Layout 2 2 Location of DIP Switches on Sensor Base 4 3 Device Address Label 4 4 Field Wiring Terminal Locations 5 5 Internal Routing of Power-Limited and Non-Power-Limited Wiring 6 6 Acceptable Zone and Signal Circuit Meter Readings 7 i

4

5 CONTRACTOR INSTALLATION INSTRUCTIONS > I : i r:y 2 a * : : * IMPORTANT * IMPORTANT * IMPORTANT * * -:, : :I :: 1x I - =dc, 1NA CLEAN, DRY, AND SAFE PLACE UNTIL NEEDED _ _ *****************it** _ / ;I) *( SYSTEM IS BEING INSTALLED INTRODUCTION This publication provides a logical sequence of procedures to follow when installing a 4020 system Throughout this publication, you are often referred to the documentation listed below In such cases, notes describing use of the documents will generally follow immediately Supplied Documentation The envelope that contained this publication also contains the following documents: 4020 Fire Alarm Back Box - Installation Instructions (FA ) Field Wiring Diagram, 4020 (84 l-842) l Wiring diagrams for specific devices are included with the devices 4020 Fire Alarm - Operating Instructions (FA ) Except for the last publication, all of the above documents are required for system installation Note: If you are unfamiliar with fire alarm system wiring, you can order a publication entitled How to Wire a Building for a Fire Alarm System (Pub No FA ) from Simplex INSTALLATION PROCEDURE Note: If possible, proceed through the installation process in the sequence that follows 1 Inventory the delivered equipment Note: In addition to the envelope that contained this publication, supplied 4020 material includes an envelope containing installation hardware l When you are required to use installation hardware during a system installation procedure, that fact is noted at the start of the procedure

6 2 Install the back box l See accompanying document entitled 4020 Fire Alarm Back Box lnsfallation Instructions Note the restrictions for routing of Power-Limited Wiring (see Figure 1) Note: The installation hardware envelope contains the panel keys 3 Mount the electronics into the back box l See Figure 1 for panel layout l Connect the ground (green) wire from the CPU bay to a grounding screw on the back box l Per article 250 of the National Electrical Code, a dedicated equipment ground conductor must connect to the other grounding screw (consult NEC Table 250 for conductor size) CPU BAY z \ GROUNDING SCREWS CPU/EXPANSION BAY- INTERCONNECTION PLUG EXPANSION BAY - NON-POWER-LIMITED FIELD WIRING E IN SHADED AREA POWER-LIMITED FIELD WIRING ONLY IN NON-SHADED AREA Figure Panel Layout 4 Using the SYSTEM POINT SUMMARY (supplied by your local Simplex Rep) and the appropriate pages in the enclosed 4020 Field Wiring Diagram, connect terminals and tag all system wiring General Notes A The index for the 4020 Field Wiring Diagram is found on the document s first page B The 4020 Field Wiring Diagram includes pages titled 4020 Precautions for Wiring C At both ends of each circuit, tag wires with I/O terminal number or MAPNET@ channel number and polarity (if polarity applies) l For example, I/O 4+ and I/O 4- D T-tapping is permitted only for Style 4 (formerly Class B) MAPNET II@ circuits 2

7 rev: 1 SYSTEM POINT SUMMARY Page 4 15:36:30, FRI, 06-MAR-92 POINT SUMMARY System Point Summary (ascending by zone name): ZONE Point Zone Name Custom Label Tw= 101 CENTER HALLWAY 102 NORTH HALLWAY 103 SOUTH HALLWAY 104 ALL SIGNALS Ml-l PRINCIPALS OFFICE Ml-2 CAFETORIUM Ml-3 KITCHEN M;-37 JANITORS CLOSET PULL PULL PULL SSIG SMOKE SMOKE HEAT HEAT Device PNIS Tn=e Code - ADRDET ADRDET MBZAM MBZAM Note: Land zone 101 on terminal block I/O 1; land zone 102 on terminal block I/O 2; etc 5 Install the peripheral devices and EOL resistors Note 1: The installation hardware envelope contains the required resistors l 33K resistors are color coded orange, orange, red (and have a gold tolerance band); 1 OK resistors are color coded brown, black, orange (and also have a gold tolerance band) l Resistors other than those described above will be used by the Simplex Rep during installation checkout Note 2: Except for devices that connect to MAPNET II@ channels (devices named Ml -1, M2-15, etc), wire peripherals in accordance with the appropriate 4020 Field Wiring Diagram ( ) l Wire a MAPNET II@ device in accordance with the diagram that accompanies the device THEN SET THE DEVICE S ADDRESS SWITCHES (see Figure 2 on page 4) Note 3: A MAPNET II@ device s address is represented by the final digit(s) in the zone s name Examples: The device that connects to a zone named Ml -2 must have its switches set to address 2; the device that connects to a zone named Ml -117 must have its switches set to address 117 l See page 4 for a complete listing of MAPNET II@ addresses Note 4: Use a small screwdriver or ball point pen to set device address switches Note 5: After setting the device address, mark the device s address label to agree with the address switches (see Figure 3 on page 4) 3

8 DIP SWITCHES 0 = OFF n = ON Address Label (Marked for Address 5) Figure 2 Location of DIP Switches on Sensor Base Figure 3 Device Address Label MAPNET II@ Address Chart Note 1: Address zero (all switches turned OFF) is not a valid address Note 2: Switch number 8 is never turned ON SWl-1 SW,-2 SW,-3 SW14 SW14 SW,-5 SW,-7 SW,-8 ON OFF OFF OFF OFF OFF OFF OFF = ADDRESS 1

9 6 Check and terminate ail field wiring (see Figure 4 for terminal locations) a Check each circuit for voltages, shorts, or opens as follows: 1 With the meter set on 3OOVAC, read the voltage across the circuit Meter must read 0 volts 2 With the meter set on 60 VDC, read the voltage across the circuit again (this time in both directions) Meter must read 0 volts 3 With the meter set on OHMS x 10 and its (+) and (-) leads connected to the circuit s (+) and (-) wires, respectively, check resistance l Readings must compare favorably with those shown in Figure 6 (see page 7) Note: if reading indicates an open in a circuit that includes a smoke detector, make sure the detector head(s) are properly mounted and seated l Circuits always read open (infinity) if detector power is absent and separately-powered devices (four-wire smoke detectors) are involved b Connect the wires to their terminals in accordance with the SYSTEM POINT SUMMARY and the appropriate field wiring diagrams c For Power-Limited systems, you must not route Power-Limited field wiring in the shaded areas of Figures 4 (see Figure 5 for routing information) INPUT POWER TERMINALS (REMOVE COVER FOR ACCESS) DooR GRoUND MAPNET CHANNEL 1 INPUT POWER GROUND COMM, CITY, TEL \ (Ml-1 THRU M-127) (120124j VAC) \ THRU l/o12 I/O 17 THhJ I/O 20 I I/O 13 THRU I/O 16 I I/O 21 THRU I/O 24 I/O 1 THRU I/O 4 MAPNET@ CHANNEL 2 W-1 THRU M2-127) Figure 4 Field Wiring Terminal Locations 5

10 d Use Figure 5 as a reference when routing field wiring inside a 4020 panel for Power-Limited Systems Use the top left and left-side knockouts for Power-Limited wiring only The right-side knockouts are reserved for Non-Power-Limited wiring Use additional knockouts when needed CONDUIT ENTRANCE FOR POWER-LIMITED WIRING / CONDUIT ENTRANCE FOR NON-POWER- LIMITED WIRING NON-POWER-LIMITED POWER-LIMITED WIRING SEE NOTES 2 & 3 c TIE WRAP / /WIRING TIE POINT I 1 SEE NOTE 3 TERMlNATlON Figure 5 internal Routing of Power-Limited and Non-Power-Limited Wiring Notes: 1 Non-power limited field wiring (AC power, Battery Wiring, City Connection) must be installed and routed in the shaded area only 2 Power limited field wiring (all connections in the unshaded area except the city) must be installed and routed as shown 3 Keep slack to a minimum inside the enclosure Using tie wraps (supplied), neatly dress and bundle the wiring together Anchor power-limited wiring to the tie points 4 Tie the wiring located between the bays to the internal wiring troughs (if applicable) 5 When switching power through relay contacts, power for these circuits must be provided by the system power supply that is listed for Fire Protective Signaling use

11 CIRCUIT TYPE METER READING Style B Style D Style Y Style Z (formerly Class B) Initiating Device (Zone) Circuit From zone + to zone - (each zone) From zone + to ground From zone -to ground (formerly Class A) initiating Device (Zone) Circuit From zone + to zone - (each zone) From zone + to ground From zone -to ground From zone + to + A From zone - to - A (formerly Class B) Notification Appliance Circuit (each signal circuit) From + to ground From -to ground Resistance across circuit In one direction In opposite direction (formerly Class A) Notification Appliance Circuit (each signal circuit) From + to ground From -to ground From + to + A From-to-A Resistance across circuit In one direction In opposite direction 33K ohms Less than 50 ohms Less than 50 ohms 1 OK ohms Less than 200 ohms Less than 50 ohms Less than 50 ohms Less than 200 ohms Shielding (twisted shielded pair wiring) From OV to ground From OV COMMON to ground MAPNET ii@ Loops (ZAMs, and IAMs) From MAPNET@ + to ground From MAPNET@ -to ground Style D (formerly Class A) Monitor ZAMs (6wire detectors) More than 50K ohms More than 50K ohms More than 50K ohms 7 Neatly dress the panel wiring 8 install the retainer 9 install the panel door Figure 6 Acceptable Zone and Signal Circuit Meter Readings 10 Using the two adhesive disks and the two rubber bumpers (from the hardware envelope), affix the bumpers to upper and lower left-hand corners of the door 11 Using the green wire from the hardware envelope, ground the upper right-hand corner of the door to the back box 12 Close and lock the panel door 13 Call your local Simplex Branch Office (listed in the yellow pages) to check out, test, and program the system * l l DO NOTAPPLY AC OR BATTERY POWER TO THE SYSTEM l * * 7

12

13

14 BeSimplex Simplex Plaza l Gardner, Massachusetts USA FA ( ) 1

/5121/5122 TrueAlert Power Supply Installation Instructions

/5121/5122 TrueAlert Power Supply Installation Instructions 4100-5120/5121/5122 TrueAlert Power Supply Installation Instructions Introduction This publication provides an overview of the features, specifications, and capabilities of the TrueAlert power supplies

More information

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately

More information

Multi-Application Peripherals and Accessories

Multi-Application Peripherals and Accessories ON UL, ULC Listed FM Approved MultiApplication Peripherals and Accessories Communicating Devices Communications Individually Addressable Devices FEATURES Individually addressable communications over a

More information

ANNUNCIATOR FIXED MODULE

ANNUNCIATOR FIXED MODULE 12 Clintonville Road Northford, CT 06472 Phone: 203-484-7161 Fax: 203-484-7118 THE ANNUNCIATOR FIXED MODULE Installation Manual for the AFM-16ATF and AFM-32AF Annunciator Modules Document # 15970 3/27/95

More information

Addressable IDNet Isolator Installation Instructions

Addressable IDNet Isolator Installation Instructions 4090-9116 Addressable IDNet Isolator Installation Instructions Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS - Follow the instructions in this installation manual. These instructions must be followed

More information

, -9686, -9688, -9755, Duct Detector/Sensor Installation Instructions

, -9686, -9688, -9755, Duct Detector/Sensor Installation Instructions 574-776 Rev. C 4098-9685, -9686, -9688, -9755, -9756 Duct Detector/Sensor Installation Instructions Blank Page Cautions and Warnings DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking

More information

PSN-1000 & PSN 1000(E) Installation Manual

PSN-1000 & PSN 1000(E) Installation Manual PSN-1000 & PSN 1000(E) Installation Manual Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 Technical Support: (866) 956-1211 Fax: (314) 595-6999 www.pottersignal.com

More information

AU MX Digital Loop Card Installation Instructions

AU MX Digital Loop Card Installation Instructions 4100-6077AU MX Digital Loop Card Installation Instructions Cautions and Warnings READ AND SAVE THESE INSTRUCTIONS - Follow the instructions in this installation manual. These instructions must be followed

More information

Rev. A. Technical Manuals Online! -

Rev. A. Technical Manuals Online! - Q 574-039 Rev. A DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent, immediately

More information

5000 INSTALLATION GUIDE

5000 INSTALLATION GUIDE 5000 INSTALLATION GUIDE Table of Contents Section Page No 1. INTRODUCTION... 3 2. WARNINGS AND CAUTIONS... 3 3. UNPACKING... 3 4. INSTALLATION... 4 5. CONTROL PANEL - REMOVING ITEMS BEFORE MOUNTING...

More information

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL G1000 AND H1000 SERIES ANNUNCIATORS

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL G1000 AND H1000 SERIES ANNUNCIATORS DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL G1000 AND H1000 SERIES ANNUNCIATORS SEEKIRK, INC. 2420 Scioto Harper Dr. Columbus, OH 43204 Tel: (614) 278-9200 FAX: (614) 278-9257 email: seekirk@seekirk.com

More information

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117 Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel Revision E 61117 CAUTION: (Read This First) This panel has been designed to make it nearly bullet proof to mistakes made when wiring

More information

Public Safety DAS Annunciator Panel

Public Safety DAS Annunciator Panel Public Safety DAS Annunciator Panel 120 VAC Models: 1221-A, 1221-B, 1221-C Revision D 91117 48 VDC Models: 1221-A-48, 1221-B-48, 1221-C-48 24 VDC Models: 1221A-24, 1221-B-24, 1221-C-24 CAUTION: (Read This

More information

Multiplex Eight Input Remote Modules

Multiplex Eight Input Remote Modules Multiplex Eight Input Remote Modules 1.0 Introduction These instructions cover the installation of the D7042/D7042B Eight Input Remote Modules in a fire system supervised by an FPD-7024 Fire Alarm Control

More information

Cimco Series 21. Series 21 - Specifications INDEX. Description. Operational Specification 2

Cimco Series 21. Series 21 - Specifications INDEX. Description. Operational Specification 2 Series 21 - Specifications INDEX Description Page Operational Specification 2 Analog Operational Specification - Communications Options 3 Digital Operational Specification - Communications Options 4 Hardware

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal3FD - 12VDC @ 4.6 amp or 24VDC @ 5.2 amp. - Sixteen (16) PTC protected power-limited outputs.

More information

SP-1000X. Panic Device Power Controller Installation Guide. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev TM SP-1000X Panic Device Power Controller Installation Guide Rev. 120213 Overview: SP-1000X will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed to handle the high current

More information

AL600ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide AL600ULADA NAC Power Extender Installation Guide Rev. 122000 AL600ULADA - NAC Power Extender Overview: The Altronix AL600ULADA is an extremely cost effective 6.5 amp voltage regulated remote power supply/battery

More information

Fire Alarm System Accessories

Fire Alarm System Accessories Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer

More information

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep. 140 58th St. Brooklyn, NY Power Supply/Chargers Installation Guide Models Include: eflow4n/eflow4nx - 4 amp @ 12VDC or 24VDC eflow4n8/eflow4nx8 eflow4n8d/eflow4nx8d - 4 amp @ 12VDC or 24VDC - 4 amp @ 12VDC

More information

Annunciator Modules. for Fire Lite Fire Alarm Control Panels. Document # /30/95 Revision:

Annunciator Modules. for Fire Lite Fire Alarm Control Panels. Document # /30/95 Revision: 12 Clintonville Road Northford, CT 06472 203-484-7161 FAX: 203-484-7118 Annunciator Modules for Fire Lite Fire Alarm Control Panels Document # 15390 3/30/95 Revision: P/N 15390:C ECN 95-210 C Installation

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 031703 Overview: The Altronix AL802ULADA is an extremely cost effective 8 amp voltage regulated

More information

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500 Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA

More information

Booster Power Supply Manual

Booster Power Supply Manual Supply Manual DEVELOPED BY COPYRIGHT NOTICE General Signal Building Systems Corporation 6411 Parkland Drive Sarasota, FL 34243 (941) 739-4300 Copyright 1999 General Signal Building Systems Corporation

More information

Rev. B. TrueAlert Addressable Controller Application Manual

Rev. B. TrueAlert Addressable Controller Application Manual 574-996 Rev. B TrueAlert Addressable Controller Application Manual This page intentionally blank Copyrights and Trademarks Copyright 000 Simplex Time Recorder Company, Westminster, MA 044-000. All rights

More information

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment. LED Driver Module Installation Guide 1.0 Notice These instructions are for installing Radionics LED Driver Module in a fire alarm system controlled by Radionics D8024 or D10024 Fire Alarm Control Panels

More information

Installation Guide for models:

Installation Guide for models: 140 58th St. Brooklyn, NY Access Power Controllers with Power Supplies Installation Guide for models: Maximal11F - Power Supply 1: 12VDC @ 3.3 amp or 24VDC @ 3.6 amp. - Power Supply 2: 12VDC @ 3.3 amp

More information

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

LDM Series Lamp Driver Modules For Graphic Annunciation and Control 12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and

More information

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL RELEASE DEVICES MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL The LiftMaster Fire Control (LM21-AFC) Release Device/Control Panel is UL/CUL listed normally energized fail-safe device incorporating

More information

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk

More information

TrueAlert Addressable Notification Appliances

TrueAlert Addressable Notification Appliances Fire Control ** IS NORMAL ** :0:pm Mon 9-Feb-9 SY S TE M AC SUPERVISORY TROUB LE SILENCED SUPV TROUBLE SILENCE RESET CONTROL DISC ON NEC T POW ER + V ZONE P WR + 0V ZONE P WR - +IDNE T IDC + - IDNE T IDC

More information

Addressable NAC Output Module D327A

Addressable NAC Output Module D327A Installation Instructions Notice Addressable NAC Output Module D327A These instructions cover the installation of the D327A Addressable NAC Output Module in an analog system controlled by a Bosch D8024,

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

General Routing Interface

General Routing Interface General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.

More information

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT

SPEC SHEET. Simple Expansion Solutions ZONE EXPANSION MODULES: SINGLE AND MULTIPLE POINT SPEC SHEET Simple Expansion Solutions Expand your DMP panel options with a wide array of expansion modules. Add supervised Class B burglary zones. Connect non-powered burglary or fire type devices for

More information

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION Fire Safety Installation Instructions Model SMB- Main Control Board OPERATION The SIEMENS Model SMB- board in each MXL-IQ System controls operations and monitors input device identity, network communication,

More information

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01 PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Warnings and Notices WARNING - To reduce the risk of fire or electric shock, do not expose this product

More information

Series. Access Power Controllers. Installation Guide

Series. Access Power Controllers. Installation Guide Series Access Power Controllers Installation Guide Models Include: Maxim11 - Power Supply 1: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Power Supply 2: 12VDC @ 3.5 amp or 24VDC @ 2.7 amp. - Sixteen (16) fuse

More information

AL800ULADA. NAC Power Extender. Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide AL800ULADA NAC Power Extender Installation Guide Rev. 122000 AL800ULADA - NAC Power Extender Overview: The Altronix AL800ULADA is an extremely cost effective 8 amp voltage regulated remote power supply/battery

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

F220-B6PS/M. Installation Guide. Addressable Detector Bases

F220-B6PS/M. Installation Guide. Addressable Detector Bases F220-B6PS/M EN Installation Guide Addressable Detector Bases F220-B6PS/M Installation Guide 1.0 Overview 1.0 Overview These instructions cover the installation of the B6PS/M Addressable Detector Bases

More information

Security CCTV System Construction Checklist

Security CCTV System Construction Checklist Security CCTV System Construction Checklist Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.

More information

Cold Deck Canopy and Shelf Lights and Retrofit Kit

Cold Deck Canopy and Shelf Lights and Retrofit Kit PAGE 1 OF 8 General Information Cold Deck LED lighting systems are intended for use inside of commercial refrigerated display merchandisers for food zone, splash zone, and non-food zones only. Cold Deck

More information

20 Light Remote Annunciator

20 Light Remote Annunciator Light Remote Annunciator Owner s Manual Surface Mount Flush Mount 94-95- Standard Annunciator 94-, 94-95-, 95-4- 4- Annunciator w/remote Relay Panel 4-, 4-4-, 4-49-, 49-49-, 49- Time Multiplexed Annunciator

More information

/9308 External Battery Chargers Installation Instructions

/9308 External Battery Chargers Installation Instructions 4081-9306/9308 External Battery Chargers Installation Instructions Introduction This publication describes the installation procedure for an External Battery Charger used with the 4100U or 4100ES System.

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101

More information

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001 SLATE Base Module R8001A1001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform can

More information

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX Page 1 of 10 Model 10807800 January 2014 ACCURATE ELECTRONICS INC PO BOX 1654 97075-1654 8687 SW HALL BLVD 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 WWW.ACCURATE.ORG Practice Section 10807800

More information

Certificate of Conformity Certificate num. Registration date Version Valid until

Certificate of Conformity Certificate num. Registration date Version Valid until CSIRO Verification Services Highett, Victoria, Australia +61 (0)3 9252 6000 http://www.activfire.gov.au/ Page 1 of 7 Product designation Simplex, Model 4100U/4100U-S1/4100ES/4100ES-S1, fire indicator panel

More information

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL Firefly II Multi Voltage RELEASE DEVICES Firefly II & IIB-MV INSTALLATION MANUAL GENERAL DESCRIPTION: S/N The The Cookson Company Firefly II-MV time delay release devices are designed for use on rolling

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

NT DUAL CHANNEL DISPLAY. User Guide

NT DUAL CHANNEL DISPLAY. User Guide NT DUAL CHANNEL DISPLAY User Guide Table of Contents Introduction... 2 Input Signals... 2 Output Signals... 2 User Programmable Features... 2 Installation... 3 Mechanical Installation... 3 Dimensional

More information

SAFEPATH SP40/2 D10 D35 AMP P/N P/N Installation, Testing, TONE SW Operation, and W4 Maintenance D54 SHORT

SAFEPATH SP40/2 D10 D35 AMP P/N P/N Installation, Testing, TONE SW Operation, and W4 Maintenance D54 SHORT W1 U8 AC N L SAFEPATH4 F2 IN BAT 24V TB7 TB1 AC TBL STB D11GRN YEL RED F1 D13 D14 AC SW1 SW2 RECORD D34 1 2 3 4 SP40/2 D9 D22 DV D10 D35 BAT MIC W2 ON D37 STB SHORT D39 STB OPEN 1 2 3 R SW3 1 2 3 4 TEL

More information

MANUAL RESET ALARM RELEASE

MANUAL RESET ALARM RELEASE Fire Door Release MODEL AR-D2 MANUAL RESET ALARM RELEASE INSTRUCTION MANUAL AR-D2 GENERAL INFORMATION 1. Review all installation instructions, procedures, cautions and warnings contained within this manual

More information

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone: Cookson Company 1901 South Litchfield Road Goodyear, AZ 85338 Phone: 800-294-4358 www.cooksondoor.com O W N E R S M A N U A L MODEL FIREFLY III EXTENDED PERFORMANCE RELEASE DEVICE TABLE OF CONTENTS INTRODUCTION

More information

MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL RELEASE DEVICES GENERAL DESCRIPTION MODEL B2 INSTALLATION MANUAL S/N: The B2 Series Time Delay Release Devices are UL Listed, Canadian Listed, and CSFM Listed for use on rolling doors, single-slide and

More information

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE SAFE A N D SECURE Cornell 100 Elmwood Ave. Crestwood Industrial Park Mountaintop, PA 18707 Tel 800.233.8366 Fax 800.526.0841 Email: cornell@cornelliron.com O W N E R S M A N U A L M O D E L F I R E G A

More information

Event Detection System (EDS)

Event Detection System (EDS) WaveGrid Event Detection System (EDS) Installation, Operations and Maintenance Guide Control Module Revision 6.0 June 24 th, 2016 Sensor Module I Functional Description The Event Detection System (EDS)

More information

FireNET Fire Alarm Control Panel Installation Manual

FireNET Fire Alarm Control Panel Installation Manual FireNET L@titude Fire Alarm Control Panel Installation Manual Page 2 Contents Contents Contents 3 Glossary 9 Compliance Information 11 Section 1: Introduction 12 Technical Support 12 Return Material Authorization

More information

Remote NAC Power Supply D7038

Remote NAC Power Supply D7038 Operation and Installation Guide Remote NAC Power Supply D7038 D7038 REMOTE NAC POWER SUPPLY Page 2 2005 Bosch Security Systems Contents Contents 1.0 Overview...5 1.1 Module Control...5 1.1.1 Option Bus

More information

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC.

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC. Model I TS-12 1 INSTALLATION lnstrljctlons Y K FIRE BURGLARY lnstrumentsrn INC. 50 Engineers Road, Hauppauge, N.Y. 11788 516-582-6j61 800-645-5430 DO WHAT THEY DON T.......................................................................................

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow6na8d - 4A @ 12VDC or 24VDC - Eight (8) PTC Outputs eflow102na8d - 10A @ 12VDC - Eight

More information

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev RPSMLR2 RPSMLR2BB Panic Device Power Controller Installation Guide LISTED Rev. 102715 Overview: RPSMLR2BB, RPSMLR2 will operate up to two (2) 24VDC panic hardware devices simultaneously. It is designed

More information

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

SOLID STATE SECURITIES, INC. THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL S S S S S S LISTED L * PATENT PENDING S S 90 OLID TATE ECURITIES, INC SOLID STATE FAIL-SAFE UNIT U 99Y9 RESET RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep. Power Supply/Chargers Installation Guide Models Include: eflow4na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow6na8-4a @ 12VDC or 24VDC - Eight (8) Fused Outputs eflow102na8-10a @ 12VDC - Eight

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE Cookson 100 Elmwood Avenue Crestwood Industrial Park Mountaintop, PA 18707 Phone: 800-233-8366 Fax: 800-526-0841 CornellCookson.com O W N E R S M A N U A L M O D E L S F I R E G A R D M C F I R E G A R

More information

Z-20 Fire Control Panels

Z-20 Fire Control Panels MANUAL RELEASE SYSTEM ABORT PUSH AND HOLD - I D N E T I N + + ID N E T I N - RE D NAC+ N A C - BLK C O ILS U P E R V IS IO NM O D U L E ( 2A M P )2 0 8 1-9 0 4 6 IN S T A L L A T IO NIN S T R U C T IO

More information

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL THE GAMEWELL COMPANY PN: 71981 60 PLEASANT STREET ISSUE A ASHLAND, MA 01721 3/22/2001 This page intentionally blank ii

More information

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION: RELEASE DEVICES MADE IN THE U.S.A. RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION: S/N: The "WPS" World Power Series, Time Delay Release

More information

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL AH1000, BH1000, AND EH1000 SERIES ANNUNCIATORS

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL AH1000, BH1000, AND EH1000 SERIES ANNUNCIATORS DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL AH1000, BH1000, AND EH1000 SERIES ANNUNCIATORS SEEKIRK, INC. 2420 Scioto Harper Dr. Columbus, OH 43204 Tel: (614) 278-9200 FAX: (614) 278-9257

More information

CP CP

CP CP CP-8161-333 CP-8161-433 Electronic Programmable Controller Six Stage, Dual Setpoint General Instructions APPLICATION Electronic six stage programmable controller with proportional output for heating, cooling

More information

OPERATION / INSTALLATION

OPERATION / INSTALLATION OPERATION / INSTALLATION & PROGRAMMING MANUAL AFP-2800 LCD-80 Fire Alarm Panel Revision 1.01 November 16, 2004 NSW (Head Office) 7 Columbia Court Norwest Business Park Baulkham Hills NSW 2153 Ph: (02)

More information

IDNet and MAPNET II Addressable Devices

IDNet and MAPNET II Addressable Devices Devices Compatible with 4008, 4010, 4010ES, 4100U, & 4100ES IDNet Communications, & MAPNET II Communications Model Description Model Description Listings 4090-9101 Class B IDC ZAM 4098-9791 Sensor Base,

More information

Operation and Maintenance Manual

Operation and Maintenance Manual (FKER Series) Repeater Panel (FKER, FKER, FKER8) Operation and Maintenance Manual Man-9EL Issue June Index Section Page. Introduction.... Safety and mounting.... Technical specification.... Control panel

More information

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 GENERAL DESCRIPTION SERIAL NUMBER The Cookson Company FIREFLY II PLUS Time Delay Release

More information

Print Specification. Publication. Instructions. Specific requirements. General requirements

Print Specification. Publication. Instructions. Specific requirements. General requirements Print Specification Publication GSA-CC1 Single Input Signal Module Installation Sheet P/N P-047550-1802-EN REV 04 ISS 23JUN15 Instructions This page is the print specification for the publication. It is

More information

ROOM VALET Installation and Wiring Guide PARTS I, II, and III

ROOM VALET Installation and Wiring Guide PARTS I, II, and III ROOM VALET Installation and Wiring Guide PARTS I, II, and III and Owner s Manual 1 ROOM VALET Visual Alerting System For The Hard of Hearing and Deaf Installation and Wiring Guide Contents Section I Room

More information

Macurco DVP-120 / DVP-120M Detection and Ventilation Control Panel User Instructions

Macurco DVP-120 / DVP-120M Detection and Ventilation Control Panel User Instructions Macurco DVP-120 / DVP-120M Detection and Ventilation Control Panel User Instructions IMPORTANT: Keep these User Instructions for reference. TABLE OF CONTENTS 1 Introduction 4 1.1 DVP-120 General Information

More information

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) AL802ULADA NAC Power Extender Installation Guide (See Application Guide for additional information) Rev. 042010 Agency Listings: UL Listed Control Units for Fire Protective Signaling Systems (UL 864).

More information

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations: F1! 44487023 These instructions cover the following parts: PS902 Power Supply Installation Instructions! DANGER: To avoid risk of electric shock, turn off AC power before installing or servicing PS902

More information

The ACM-8R Annunciator Control Module

The ACM-8R Annunciator Control Module 12 Clintonville Road Northford, CT 06472 203-484-7161 FAX: 203-484-7118 The Annunciator Control Module For the System 500, System 5000, AFP-200, AM2020, AFP1010 and SFP-1024 Fire Alarm Control Panels Document

More information

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL Document No...G108WO1.DOC Serial No... Issue Date...17 th SEPTEMBER 1999 Software Version...1.4 APPROVED TO: NZS 4512:1997 AS/NZS 3548:1992 Fire Alarm

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS II 1400-3 ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS Features: For use with doors or groups of doors that must interlock with each other to regulate control of accessing one area from another,

More information

/ XPS Interconnection Diagrams

/ XPS Interconnection Diagrams 4100-5153/4100-5154 XPS Interconnection Diagrams Introduction This publication provides interconnection diagrams for 4100-5153 (120 VAC) and 4100-5154 (220/240 VAC) 13 A Expansion Power Supplies (XPS).

More information

FIRE STROBE 2000 INSTALLATION INSTRUCTIONS

FIRE STROBE 2000 INSTALLATION INSTRUCTIONS FIRE STROBE 2000 INSTALLATION INSTRUCTIONS I. SITE INSPECTION FOR INSTALLATION A.P.I voice: (858) 292-1561 web: http:// www.firestrobe.com 1. Carefully inspect the area where the Fire Strobe 2000 will

More information

D A R A - 4. Data Aire Relay Auto-Changeover

D A R A - 4. Data Aire Relay Auto-Changeover D A R A - 4 Data Aire Relay Auto-Changeover WARNING: If adding the DARA-4 panel to existing units that did not include a DARA-4 panel when originally purchased it will be necessary to add a relay or relays.

More information

Notification Appliance Circuit Module

Notification Appliance Circuit Module Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance

More information

Installation and Operation Manual Low Power (LP) DC Power System

Installation and Operation Manual Low Power (LP) DC Power System Installation and Operation Manual Low Power (LP) DC Power System LPS Power Enclosure LPB Battery Enclosure 2051259 R3 Information in this document is subject to change without notice and does not represent

More information

Installation Instructions

Installation Instructions 50ZPB, C, 50ZHB, C, PA3Z ---A, PH3Z ---A, PA4Z, PH4Z, PAJ4,PHJ4,WJA4,WJH4 SMALL PACKAGED PRODUCTS (SPP) Accessory Electric Heaters 5---20 kw For 14 SEER, R---410A Manufactured Home Installation Instructions

More information

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com LiftMaster 300 Windsor Drive Oak Brook, IL 60523 LiftMaster.com O W N E R S M A N U A L MODELS LM21AFCB LM21AFCBVB B ADVANCE FIRE CONTROL RELEASE DEVICE FM APPROVED TABLE OF CONTENTS INTRODUCTION General

More information

MODELS ASHP, ASHH, ASUP, and ASUH

MODELS ASHP, ASHH, ASUP, and ASUH 2562229A REV. A 1210 Printed in U.S.A. MODELS ASHP, ASHH, ASUP, and ASUH INSTALLATION AND SERVICE INSTRUCTIONS blank page INSTALLATION AND SERVICE INSTRUCTIONS FOR MODELS ASHP, ASHH, ASUP, AND ASUH SAFETY

More information

Cold Deck FIT. Canopy and Shelf Lights and Retrofit Kit. Installation Guide for General Information. Tools and Accessories Recommended

Cold Deck FIT. Canopy and Shelf Lights and Retrofit Kit. Installation Guide for General Information. Tools and Accessories Recommended General Information Cold Deck FIT LED lighting systems are intended for use inside of commercial refrigerated display merchandisers for food zone, splash zone, and non-food zones only. Cold Deck FIT LED

More information

Rack Mount Series Installation Guide

Rack Mount Series Installation Guide Rack Mount Series Installation Guide Models Include: Maximal1RHV Maximal1RV - 12VDC @ 4 amp or 24VDC @ 3 amp. - 12VDC @ 4 amp or 24VDC @ 3 amp. - Eight (8) Fuse Protected Outputs. - Sixteen (16) Fuse Protected

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44

More information

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL S S S S S S OLID TATE ECURITIES, INC S S 90 SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED 99Y9 RESET U L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information