1 General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: Two Fire Routing Outputs are provided for differentiation between Call Point (MCP) and Automatic Detector (AFD) Fire Alarm Signals if required. Outputs are monitored for open and short circuit wiring conditions in both the quiescent (off) and active (on) modes with fault conditions indicated on the panel (CIE) display / LED Indicators. Outputs are compatible with a wide range of routing equipment coil impedances (1kΩ to 5kΩ). Simple to install and configure. Circuitry is prepared ready for Confirmation inputs in accordance with the EN54-2:1997 +A1:2006 Clause The operation and functions described in this manual are available from Software Version onwards.

2 Specifications & Ordering: Models, Sales Order Parts: Mxp-032 Mxp-032F General Routing Interface General Routing Interface (fitted) Applications / Limitations: EN54-2 compliant routing interfaces providing monitored outputs to fire alarm and fault routing circuits. Circuits are monitored for open and short circuit conditions in both the normal and active mode in compliance with EN54-2 and BS5839-1: 2002 Clause a. The outputs will drive relay coils with impedances of between 1kΩ and 5kΩ. Compatibility: Can be used with Mx-4200, Mx-4400 and Mx-4800 control panels programmed with Version software (or later) and fitted with base card hardware revision levels 10 ( Mx-4400) and 09 ( Mx- 4200) or later. Compatible with the PC Configuration Tool from version 4.19 or later. Requires installation of the Mxp-031 Peripheral Bus Interface Adaptor card in the panel. Item Output Circuit Specification Fire & Fault Outputs Input Circuit Specification (Future Option) Operating Voltage Panel Loading, standby, AC Mains Fail (fault output off) Panel Loading, quiescent state (fault output on) Panel Loading, ALL inputs and outputs active On-board Indications Specification Details 24VDC Active, 5VDC Monitor 1.0mA monitor mode nominal, 5.0mA 25.0mA active (energised) mode depending on coil impendence, 40.0mA maximum short circuit current 4x Monitored Input EOL 10KΩ, Operating Resistor 470Ω 24V DC [Range 19-28V] from panel Auxiliary Supply Output 43mA 45mA +24mA (1KΩ coil), +5mA (5KΩ coil) 48mA, +72mA (1KΩ coils), +15mA (5KΩ coils) 6x LED Indicators for Outputs Active, Communications and Microprocessor Heartbeat Operating Temperature 0 C to 50 C Approvals EN54-2:1997 +A1:2006 As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice

3 Table of Contents Page 1. INTRODUCTION INSTALLING THE CARD IN THE PANEL... 4 A. MOUNTING THE CARD... 4 B. WIRING... 4 C. EOL JUMPER INSTALLING THE CARD IN AN EXTERNAL ENCLOSURE FIELD WIRING CONNECTIONS... 5 A. OUTPUT WIRING... 5 B. INPUT WIRING CONFIGURATION Introduction Outputs to Routing Equipment Clauses 7.9 and 8.9. The Routing Interface Card provides monitored outputs in accordance with EN54-2 for connection to: - Fire Routing Equipment (Item E) and - Fault Routing Equipment (Item J). Two fire routing outputs are provided. These can be independently programmed with different cause and effect rules. They can, for example, be programmed to signal MCP (Call Point) and AFD (Automatic Fire Detection) conditions respectively. When Fire Routing is disabled at the panel, both outputs are disabled. Also provided for future options is provision for confirmation / fault inputs. Details of these are provided below but are not currently supported by the panel. The panel will indicate activated, disabled and fault conditions for each output using a combination of the LED Indicators (Function 1, 2 & 3 for Fire Alarm Output) and the Alphanumeric Display. The panel will indicate a fault condition if it fails to establish communications (or loses communications) with the General Routing Interface Card. 3

4 J1 EOL SELECT 2. Installing the Card in the Panel a. Mounting the Card J1 EOL SELECT The card is fitted to the chassis using 4x M3 screws. Refer to the diagram opposite. Screws marked * must be securely fixed to provide an earth connection for EMC purposes. * Routing Interface TB4 J1 * M3 Fixing Screws Base Card TB2 Communications TB3 DC SUPPLY b. Wiring Cables are provided for internal connection of a local 24V DC supply and communications connections. Connect the DC Supply from the AUX output (TB2 on the base card) to the connections on TB4 observing polarities (V+ to 24V and 0V to 0V). Mounting Position for the Routing Interface Card A B 24V 0V TB4 Routing Interface Connect the communications cable between TB3 on the Base Card to the connections on TB4 so that 'A' is connected to 'A' and 'B' to 'B'. Route the wiring as shown in the diagram above. TB2 Base Card TB3 To Batteries 0V V+ AUX B A B A c. EOL Jumper OUT IN If the card is mounted in the panel, ensure that the EOL jumper (J1) is set to the OUT position. OUT IN OUT IN If the card is mounted external to the panel and is the last (furthest) unit on the link then set the EOL Jumper (J1) to the IN position. 3. Installing the card in an External Enclosure Alternatively, the card may be mounted in a separate enclosure such as Mxm-044. This may be required if a modem / 8x relay output / sounder splitter card option is installed in the panel. In this case, the enclosure should be located not greater than 10M from the control panel (and must be within the same room) with the wiring run in rigid metal conduit. All wiring should be in 18AWG cable minimum. See above for connections. Communications cable must be twisted-pair type. Use the right hand A+B connections on TB3. Set Jumper J1 as described above. 4

5 4. Field Wiring Connections The Routing Interface can be used to output monitored signals to Fire Alarm Routing Equipment and to Fault Routing Equipment. Each function comprises of an output circuit (and optional confirmation input future option). Each circuit is monitored for open circuit and short circuit wiring conditions in both the activated and quiescent states. The outputs can be connected to a remote relay coil with a resistance of 1KΩ to 5KΩ. A suppression diode must be connected across the coil observe connection polarities. The Fault Output is normally energised during the quiescent condition it will de-energise on any fault or on total loss of power. NB: These circuits are classed as Safety Extra Low Voltage (SELV) circuits. Route away from mains wiring Not Currently Used Power + Data OUT IN OUT IN OUT IN1 IN2 FIRE 1 FIRE 2 FAULT Routing Interface Typical Arrangement a. Output Wiring Connect the output wiring to the + and - terminals. Use cables of appropriate size for the voltage and loading required. All cables should be to the same voltage and insulation specification appropriate to the intended application. Maximum cable impedance = 100Ω. Refer to diagram above for typical arrangement the wiring to the relay coil in the remote equipment. Refer to the specification section for the maximum and minimum compatible coil impedances. If an output is not used connect a 4.7KΩ EOL resistor across the relevant terminals. b. Input Wiring FUTURE OPTION The fire alarm outputs each have an associated input for a confirmation signal to indicate that the output signal has reached the receiving centre. IN1 & IN2 are additional inputs. A 10kΩ E.O.L resistor should be placed across any unused input terminals. 10K ¼W The monitored inputs circuits should be wired as per the diagram opposite. 470R ¼W Volt free contact The 470Ω (operating) resistor and 10kΩ (E.O.L) resistor arrangement should be made adjacent to the switch contacts to ensure that correct fault monitoring of the total circuit (including the wiring) between the input contact and the General Routing Interface unit is maintained. + SWITCH INPUT 'n' 5

6 5. Configuration To configure the panel for monitored fire and fault routing, select the SETUP option from the COMMISSION menus and scroll down to the following display. [Setup] TRACE LOGGING MODE : STANDARD DETECTOR BLINKING : NONE EARTH MONITORING : FIRE/FAULT ROUTING : x More> To enable the operation of the General Routing Interface, press the button to cycle through the options and select the MONITORED option. X MONITORED NOT MONITORED No Fire / Fault Routing Fire / Fault Routing uses the General Routing Interface Card Fire / Fault Routing uses the base card volt-free relay outputs As soon as the MONITORED option is selected, the panel will try to establish communications with the General Routing Interface Card. If connection cannot be established then a fault condition will be indicated. By default, the outputs are configured to use Output Groups 199 (Fire) and 200 (Fault). These can be adjusted or can be assigned to alternative output groups as required for the application. Refer to the Panel Installation and Commissioning Manual for general information on output group programming. 6

7 USER NOTES

8 Doc Number: Revision: 02A Advanced Electronics Ltd Moorland Way, Cramlington, Northumberland, NE23 1WE UK Tel: +44 (0) Fax: +44 (0) Web:

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

Document No Issue 4 product manual

Document No Issue 4 product manual DX Document No. 997-147-000-4 Issue 4 product manual MORLEY-IAS Dimension Series Table of Contents 1 INTRODUCTION... 7 1.1 NOTICE... 7 1.2 MODELS... 7 1.3 WARNINGS AND CAUTIONS... 9 1.4 NATIONAL APPROVALS...

More information

VACIE REFERENCE GUIDE REVISION 1.2.6

VACIE REFERENCE GUIDE REVISION 1.2.6 VACIE REFERENCE GUIDE REVISION 1.2.6 November 2016 INTRODUCTION... 3 SECTION 1... 4 VACIE CONFIGURATION... 4 Communications... 4 Vocia VACIE Devices... 4 Vocia Support devices:... 5 Power Supply and Network

More information

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels Installation and user manual for the FX range of fire panels 1, 2, 4 and 8 zone panels Contents Panel installation 3 Panel connections 3 Wiring connection drawings 4 Panel facilities 6 Installation check

More information

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F II 1400-2 ACSI 1406-04-AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F INSTALLATION Transformer Model BE31763001 by Basler Electric, Transformer Model 2010028 by Galaxy

More information

FEC403EN Installation Manual

FEC403EN Installation Manual FEC403EN Installation Manual P/N 10-4101-501-2FC1-01 ISS 22JAN15 Copyright Trademarks and patents Manufacturer 2015 UTC Fire & Security. All rights reserved. The FEC403EN name and logo are trademarks of

More information

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS QUICK USER GUIDE FOR, 2 & 4 ZONE PANELS INDICATORS COLOUR INDICATION MON FAULT Yellow On when a fault condition has occurred, or if no other fault Led is on, this indicates 24v auxiliary fuse failure.

More information

User Manual. Security Systems Security System L208

User Manual. Security Systems Security System L208 User Manual Security Systems Security System L208 a Contents This hand book is a technical instruction document for the installation, commissioning and operation of the L208 intrusion alarm security system.

More information

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual

NFS Supra / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel. Installation and Operating Manual / VSN-2Plus / ESS-2Plus Conventional Fire Alarm Control Panel Installation and Operating Manual HLSI-MN-025-I v.05 April 2015 Note: This manual is valid for the following control panel models: NFS-Supra

More information

RMS/RPX Reader. User Manual

RMS/RPX Reader. User Manual RMS/RPX Reader User Manual Copyright Disclaimer Trademarks and patents Intended use FCC compliance Copyright 2005, GE Security Inc. All rights reserved. This document may not be copied or otherwise reproduced,

More information

UNC100 Integra Manual

UNC100 Integra Manual UNC100 Integra Manual New Generation Building Security July 30, 2014 V1.2 Copyright Notice Copyright 1995-2014 by All rights reserved Worldwide. Printed in Canada. This publication has been provided pursuant

More information

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)

Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0)

More information

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL Approved Document No. GLT-201-7-1 CONTENTS 1. INTRODUCTION... 1.1 HANDLING THE PCBS... 1.2 USING THIS MANUAL... 1.3 ABOUT THE INFINITY FIRE ALARM CONTROL PANEL

More information

LF-4000 Series Conventional Fire Alarm Control Unit

LF-4000 Series Conventional Fire Alarm Control Unit LF-4000 Series Conventional Fire Alarm Control Unit Features: 1 to 36 Zone Control Panels Control Key Switch Easy Push Button Control Switches Zone Circuit Monitoring for Open and Short Sounder Circuit

More information

Notification Appliance Circuit Module

Notification Appliance Circuit Module Notification Appliance Circuit Module D192G en Installation guide Notification Appliance Circuit Module Notices en 3 1 Notices These instructions cover the installation of the D192G Notification Appliance

More information

MMF Six Zone Interface Module

MMF Six Zone Interface Module Installation and Maintenance Instructions I56-900-005 MMF-0-6 Six Zone Interface Module SPECIFICATIONS Normal Operating Voltage: 5- VDC Stand-By Current: ma Alarm Current: 40 ma (assumes all six LEDs solid

More information

C-Bus Four Channel Analogue Output Unit Installation Instructions

C-Bus Four Channel Analogue Output Unit Installation Instructions C-Bus Four Channel Analogue Output Unit Installation Instructions 5504AMP Series REGISTERED PATENT Table of Contents Section... Page 1.0 Product Range...3 2.0 Description...3 3.0 Capabilities...3 4.0 Wiring

More information

KFP-AF Series Fire Alarm Control Panel Installation Manual

KFP-AF Series Fire Alarm Control Panel Installation Manual KFP-AF Series Fire Alarm Control Panel Installation Manual P/N 501-405103-1-20 REV 2.0 ISS 03MAR11 Copyright Trademarks and patents Manufacturer Version Certification European Union directives Contact

More information

Conventional Fire Detection

Conventional Fire Detection SECTI 4: page 1 Section 4: Conventional Fire Detection Contents System Architecture Control Panel Automatic & Manual Detection Manual Call Points Smoke Detectors Heat Detectors Beam Smoke Detectors Duct

More information

DS7465i. Installation Instructions. Input/Output Module

DS7465i. Installation Instructions. Input/Output Module DS7465i EN Installation Instructions Input/Output Module DS7465i Installation Instructions.0 Introduction EN 2.0 Introduction The DS7465i Input/Output Module operates with compatible multiplex systems.

More information

EN54 & ISO Zone Conventional Fire Control Panel

EN54 & ISO Zone Conventional Fire Control Panel EN54 & ISO 7240 2-8 Zone Conventional Fire Control Panel Installation, Commissioning & Configuration Manual.0 For use with Zircon EN 2-8 Fire Control Panels The following markings are used either on the

More information

Control Panel Engineering and Commissioning Instructions

Control Panel Engineering and Commissioning Instructions Twinflex - V3 Fire Detection & Alarm System Control Panel Engineering and Commissioning Instructions (TO BE RETAINED BY THE COMMISSIONING ENGINEER) 26-0338 Issue 9 Fike s policy is one of continual improvement

More information

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009 Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual Man-1048 Issue 05 October 2009 CONTENTS Contents... Page Safety & Installation...2 Installation - continued...3

More information

Specification/ Data Sheet

Specification/ Data Sheet Specification/ Data Sheet TRITON RP Agent Release Control Panel FEATURES Agent Release Control Panel designed specifically for suppression release operation with: Four initiating device circuits (IDCs)

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

Control Panel. D9412GV4/D7412GV4 v2.00. en UL Installation Instructions

Control Panel. D9412GV4/D7412GV4 v2.00. en UL Installation Instructions Control Panel D9412GV4/D7412GV4 v2.00 en UL Installation Instructions Control Panel Table of Contents en 3 Table of contents 1 Introduction 4 1.1 About documentation 4 1.2 Determine Bosch Security Systems,

More information

Document No Issue 4 user manual

Document No Issue 4 user manual DX Document No. 996-148-000-4 Issue 4 user manual Dimension Series Table of Contents 1 INTRODUCTION... 5 1.1 NOTICE... 5 1.2 MODELS... 5 1.3 WARNINGS AND CAUTIONS... 7 1.4 NATIONAL APPROVALS... 7 1.5 EN54

More information

EN54 & ISO Zone Conventional Fire Control Panel

EN54 & ISO Zone Conventional Fire Control Panel EN & ISO 0 - Zone Conventional Fire Control Panel Installation, Commissioning & Configuration Manual 99-9-000-, Issue.0 For use with NFS - and FLS - Fire Control Panels The following markings are used

More information

Easy Series ICP-EZM2. System Reference Guide

Easy Series ICP-EZM2. System Reference Guide Easy Series ICP-EZM2 en System Reference Guide Easy Series Table of Contents en 3 Table of Contents 1 Overview 6 1.1 Installation Workflow 6 1.2 System Components and Wiring 6 1.3 Phone Menus 10 1.3.1

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

Vega Devices.

Vega Devices. Vega Devices This document lists the Argus Vega devices that are compatible with the Panels. It also highlights any specific requirements and technical information. Range of Fire Alarm Control The operation

More information

Operating Instructions

Operating Instructions Operating Instructions System 57 5701 CONTROL SYSTEM OPERATING INSTRUCTIONS Helping to make a safer world Ensure that you read and understand these instructions BEFORE operating the equipment. Please pay

More information

CONVENTIONAL >FIRE DETECTION C400 SYSTEM FIRE DETECTION

CONVENTIONAL >FIRE DETECTION C400 SYSTEM FIRE DETECTION FIRE DETECTION >FIRE DETECTION CONVENTIONAL C400 SYSTEM FIRE DETECTION EFFICIENT AND MODULAR Elkron fire detection systems protect your business and grow with it Elkron's conventional fire detection range

More information

Zone Terminal, 2-fold, FM MT/U , GH Q R0111

Zone Terminal, 2-fold, FM MT/U , GH Q R0111 , GH Q631 0060 R0111 SK 0001 B 01 The zone terminal is used for the monitored connection of detectors from security techlogy on the EIB. The device is installed in conventional switch boxes (Ø 55 mm).

More information

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels R 12 Clintonville Road, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118 Instruction Manual for the MS-4012/4024 and CMS-4012/4024 Fire Alarm Control Panels Document 15586 5/11/93 Revision:

More information

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS GENERAL INFORMATION Please read these instructions and keep them in a safe place. These instructions must

More information

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16 TraceTek TTSIM-1A TraceTek Sensor Interface Module with Relay Installation/OPERATION Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and

More information

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

LDM Series Lamp Driver Modules For Graphic Annunciation and Control 12 Clintonville Road Northford, CT 06472 (203) 484-7161 FAX: (203) 484-7118 LDM Series Lamp Driver Modules For Graphic Annunciation and Control Used with the System 500, System 5000, AM2020/AFP1010 and

More information

FMR Installation Instructions. Addressable Fire System Controller

FMR Installation Instructions. Addressable Fire System Controller FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3

More information

21-light Remote Annunciator. Owner s Manual

21-light Remote Annunciator. Owner s Manual 21-light Remote Annunciator Owner s Manual Annunciator Description... Inside Font Cover Detailed Specifications... 1 Environmental Specifications... 1 Power Supply Requirements... 1 Communication With

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

Planning Elevator Relay Groups Programming Millenium for Windows Software

Planning Elevator Relay Groups Programming Millenium for Windows Software Installation Booklet: Elevator Control Unit (ECU) Introduction The Elevator Control Unit (ECU) is an option in the Millenium for Windows systems. Once you add an elevator in the software, each elevator

More information

Installation & Operation Manual

Installation & Operation Manual 519_D Radiant Thermostat 519 03/13 Zoning Replaces: New Installation & Operation Manual Introduction The Radiant Thermostat 519 accurately controls the room and/or floor temperature for a hydronic heating

More information

Construction Products Regulation (CPR) Update. Graham Simons Technical Manager, FIA

Construction Products Regulation (CPR) Update. Graham Simons Technical Manager, FIA Construction Products Regulation (CPR) Update Graham Simons Technical Manager, FIA What are we talking about? Construction Products Regulation 305/2011 EU (CPR) Replaced Construction Products Directive

More information

PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL

PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL PREMIER EX8 INSTALLATION MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 & EN54 PARTS 2 & 4 INSTALLATION MANUAL Approved Document No: GLT.MAN-124 INDEX Extinguishing

More information

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual BS-316 Gas detection control panel up to 16 inputs Installation operation manual Page 1 from 21 Contents 1 Operation instructions--------------------------------------------------------------------------------------------------------------------3

More information

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1. Data Sheet Ref: 90501085 WD-CS Water leak detection cable Technical Overview The WD-CS range of cable sensors are typically used to detect water leaks usually under floors, and are used in conjunction

More information

Fire control panels FC726 FC726-XA

Fire control panels FC726 FC726-XA Fire control panels FC726 FC726-XA Modular, pre-confectioned, microprocessor-controlled fire control panel for up to max. 1512 device addresses Integrated, user-friendly operating unit Detection and automatic

More information

Installation Manual RINS1211-4

Installation Manual RINS1211-4 Installation Manual 2x 2x RINS1211- Contents Page System Overview Technical Specification 5 Overview 6 The Control Panel 6 The Printed Circuit Board The Tamper Spring and Connections 8 Connections 9 Transformer

More information

Radiant Thermostat 519

Radiant Thermostat 519 106103_dl_02 Radiant Thermostat 519 Installation & Operation Manual Introduction The Radiant Thermostat 519 accurately controls the room and/or floor temperature for a hydronic heating zone using Pulse

More information

Reflective Optical Beam Smoke Detector User Guide

Reflective Optical Beam Smoke Detector User Guide Reflective Optical Beam Smoke Detector User Guide 1. Installation IMPORTANT NOTE: The infrared beam path MUST be kept clear of obstructions at all times! Failure to comply may result in the system initiating

More information

DC1192 Input /Output module

DC1192 Input /Output module DC1192 Input /Output module Interactive, AnalogPLUS/SynoLOOP, collective/synoline600 AlgoRex Synova In-/output module suitable for collective fire detection system as detection line coupler interactive

More information

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

DUAL MONITORED INPUT/OUTPUT UNIT BN-305 DUAL MONITORED INPUT/OUTPUT UNIT BN-30 Interactive fire detection systems Product Datasheet Features Interactive For interfacing and controlling external units to Autronica s interactive fire detection

More information

Environmental Monitoring & Control Units Types MCU 3 & 4 Installation and Hardware

Environmental Monitoring & Control Units Types MCU 3 & 4 Installation and Hardware Environmental Monitoring & Control Units Types MCU 3 & 4 Installation and Hardware Supplied by Analox Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK T: +44 (0)1642 711400

More information

DI601AM Outdoor PIR/AM Detector Installation Sheet

DI601AM Outdoor PIR/AM Detector Installation Sheet DI601AM Outdoor PIR/AM Detector Installation Sheet EN DE ES FR IT NL PL PT SV Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 TOP Figure 8 Figure 9 TOP Long range 30m section Short/ medium

More information

Unity DAU Voice Alarm System

Unity DAU Voice Alarm System Unity DAU Voice Alarm System User Manual & Log Book Site Name Address Contractor Commissioned Introduction Voice Alarm (VA) systems are the quickest way to evacuate the public & staff from a building.

More information

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) T M 1 isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) Technical Bulletin NAE1012372 / 03.2015 isopv

More information

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC. M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @

More information

LaserFOCUS VLF-250 Engineering Specification

LaserFOCUS VLF-250 Engineering Specification Vision Fire & Security LaserFOCUS VLF-250 Engineering Specification May 2004 Part Number 20296 LaserFOCUS VESDA 2 VESDA LaserFOCUS Contents Scope...4 Description...4 General...4 Approvals...4 Codes, Standards

More information

CW9000 Wireless Fire System. Installation Manual

CW9000 Wireless Fire System. Installation Manual CW9000 Wireless Fire System Installation Manual CONTENTS 1 PROJECT PROCESS...4 1.1 PLANNING...4 1.2 SITE SURVEY...4 1.3 EQUIPMENT INSTALLATION...4 1.4 COMMISSIONING / CONFIGURATION...4 2 SYSTEM INSTALLATION...5

More information

Electric Release Panel Wiring Tips

Electric Release Panel Wiring Tips R IPS CARBO STEEL PIPE FIRE PROTECTIO PRODUCTS Electric Release Panel Wiring Tips 30.4 VICTAULIC IS A ISO 900 CERTIFIED COMPAY Model PDRP-00 Releasing Panels are compact single enclosure units containing

More information

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing

Control Panels. Control Panels for Commercial Applications. Control panels provide the central processing Control Panels Control Panels for Commercial Applications Control panels provide the central processing and logic for an integrated system. In a typical system, there are four major functions: inputs,

More information

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual Part Number P84748 Assembly Number A84749 Revision C Revision A Copyright 2006 Printed in U.S.A. All rights reserved.

More information

F220-B6PS/M. Installation Guide. Addressable Detector Bases

F220-B6PS/M. Installation Guide. Addressable Detector Bases F220-B6PS/M EN Installation Guide Addressable Detector Bases F220-B6PS/M Installation Guide 1.0 Overview 1.0 Overview These instructions cover the installation of the B6PS/M Addressable Detector Bases

More information

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for

More information

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...

More information

FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL

FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL FireNET Series - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL The FireNET 427 control panel is an analog addressable fire alarm panel containing 2 or 4 SLC loops with each loop supporting 27 devices of

More information

AutroFlame X33AF. Addendum. Multi-spectrum IR flame detector. Protecting life, environment and property...

AutroFlame X33AF. Addendum. Multi-spectrum IR flame detector. Protecting life, environment and property... AutroFlame X33AF Multi-spectrum IR flame detector Addendum Protecting life, environment and property... 116-P-X33AFADDENDUM/YGB, DEC P/N 95-8624, 2007-11-12 COPYRIGHT This publication, or parts thereof,

More information

INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM. Features

INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM. Features INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM Description Mircom s FleX-Net TM Series Network Fire Alarm Control Panels offer modular components to meet a wide variety of applications. Designed for peerto-peer

More information

Microphones VIGIL VIGIL. Unitouch. combined data sheets LEADING THE WAY TO SAFETY

Microphones VIGIL VIGIL. Unitouch. combined data sheets LEADING THE WAY TO SAFETY VIGIL Microphones VIGIL Unitouch combined data sheets LEADING THE WAY TO SAFETY Emergency Fire Microphone Certified to BSEN54 BFM400 is a range of fully monitored emergency fire microphones that provide

More information

Sita200plus. 200detectors. Single loop analogue addressable System

Sita200plus. 200detectors. Single loop analogue addressable System Single loop analogue addressable System Fast short circuit isolator in every device 15 combinations of smoke & heat detection modes Loop length up to 2km long with spurs INTELLIGENT FIRE TECHNOLOGY A D

More information

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand

5U Compact System. Installation Manual V1.0. Manufactured by Enatel Ltd. 321 Tuam Street PO Box Christchurch New Zealand 5U Compact System Installation Manual V1.0 Manufactured by Enatel Ltd. 321 Tuam Street PO Box 22-333 Christchurch New Zealand Phone +64-3-366-4550 Fax +64-3-366-0884 Email sales@enatel.net www.enatel.net

More information

Commercial Series TriTech Motion Detector. Reference Guide

Commercial Series TriTech Motion Detector. Reference Guide Commercial Series riech Motion Detector en Reference Guide Commercial Series riech Motion Detector able of contents en 3 able of contents 1 Safety 4 Introduction 5.1 About documentation 5. Bosch Security

More information

Installation Instructions Model HZM

Installation Instructions Model HZM Installation Instructions Model Remote Conventional Zone Module INTRODUCTION The Model from is an intelligent device that connects a single zone of conventional devices to a DLC (FireFinder-XLS System)

More information

User manual. ABB i-bus EIB. Zone Terminal MT/S Intelligent Installation System ABB STOTZ-KONTAKT

User manual. ABB i-bus EIB. Zone Terminal MT/S Intelligent Installation System ABB STOTZ-KONTAKT User manual ABB i-bus EIB Zone Terminal MT/S 4.12.1 Intelligent Installation System ABB STOTZ-KONTAKT 2 Contents Page 1 Device configuration..................................... 4 1.1 Introduction..........................................

More information

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual

MS-2410BC. Conventional Fire Alarm Control Panel. Programming, Installation, Maintenance and Operating Instruction Manual 24 Viceroy Road Unit #6 & 7 Concord, Ontario L4K2L9 Phone (905) 660-7210 FAX: (905) 660-7204 MS-2410BC Conventional Fire Alarm Control Panel Programming, Installation, Maintenance and Operating Instruction

More information

HTC-915-CONT. Heat-Trace Control system

HTC-915-CONT. Heat-Trace Control system Heat-Trace Control system Product overview The Raychem HTC-915 system is a compact, full-featured microprocessor-based single-point heat-trace controller. The HTC-915-CONT provides control and monitoring

More information

M550 and M600. Installation Instructions

M550 and M600. Installation Instructions M550 and M600 Installation Instructions Cooper Security Limited 2005-2006 Every effort has been made to ensure that the contents of this book are correct. However, neither the authors nor Cooper Security

More information

R-Series Remote Annunciators and Expanders Installation and Operation Guide

R-Series Remote Annunciators and Expanders Installation and Operation Guide R-Series Remote Annunciators and Expanders Installation and Operation Guide P/N 3100969-EN REV 05 ISS 06MAY13 Copyright Trademarks and patents Manufacturer Version FCC compliance Contact information 2013

More information

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE The Door Switch 11772 Westline Industrial Drive St. Louis, Mo 63146 (877) 998-5625 www.thedoorswitch.com Patent No. RE42,991 and RE44,039 CONTROL PANEL TRANSFORMER (SUPPLIED WITH CONTROL PANEL) NOTIFICATION

More information

Fire control panel detect 3004 plus and accessories

Fire control panel detect 3004 plus and accessories Fire control panel detect 3004 and accessories The modular fire alarm panel detect 3004 is the basic version of a broad product portfolio of the system detect 3000. Up to 20 fire control panels can be

More information

Pioneer-R16 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual Pioneer-R16 Gas Monitor Operator s Manual Edition 7/2/97 RKI INSTRUMENTS, INC RKI Instruments, Inc. 33248 Central Ave, Union City, CA 94587 (510) 441-5656 Chapter 1: Description About the Pioneer-R16 Gas

More information

Installation Manual Premier 412/816/832. Issue 10

Installation Manual Premier 412/816/832. Issue 10 Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the

More information

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel ACC-25/50ZST Zoned System Voice with Telephone Evacuation Control Panel General The AUDIO COMMAND CENTER 25/50 Zone System with FireFighters Telephone (ACC-25/50ZST) is a state-of-the-art Emergency Voice

More information

Operating Manual. KD780 Gas and CO detection control panel. 1. Target group. 2. Warnings. 2.1 General warnings

Operating Manual. KD780 Gas and CO detection control panel. 1. Target group. 2. Warnings. 2.1 General warnings Operating Manual KD780 Gas and CO detection control panel 1. Target group The target group of this manual are qualified personnel of the gas safety and regulating technology, skilled personnel or the persons

More information

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX

ACCURATE ELECTRONICS INC PO BOX SW HALL BLVD BEAVERTON OR USA FAX Page 1 of 10 Model 10807800 January 2014 ACCURATE ELECTRONICS INC PO BOX 1654 97075-1654 8687 SW HALL BLVD 97008 BEAVERTON OR USA 503.641.0118 FAX 503.646.3903 WWW.ACCURATE.ORG Practice Section 10807800

More information

December Scorpio. Fire Control Panel. Installation, Operation & Maintenance Manual. P/N UL Listing File No. S2422.

December Scorpio. Fire Control Panel. Installation, Operation & Maintenance Manual. P/N UL Listing File No. S2422. December 2001 Scorpio TM Fire Control Panel Installation, Operation & Maintenance Manual P/N 06-235793-001 UL Listing File No. S2422 Fire Systems SAFETY SUMMARY Installation Precautions Adherence to the

More information

SOFTWARE VERSION 2.20 CONTROL PANEL RESET:

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: -961112-0002 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3

More information

VA301C CONTROLLER WITH BACnet OPTION

VA301C CONTROLLER WITH BACnet OPTION ORDERING INFORMATION VA301C Controller VA301C-DLC VA301C-DLC-BIP Gas detection controller with data logging, display and plastic housing. Gas detection controller with data logging and display, BACnet/IP

More information

Installation Instructions Model SSD-C-REM

Installation Instructions Model SSD-C-REM Installation Instructions Model SSD-C-REM Remote System Status Display with Control ON ALARM SUPERVISORY SECURITY TROUBLE AUDIBLES SILENCED INTRODUCTION The SIEMENS Model SSD-C-REM is an optional FireFinder

More information

Operating Instructions MEW01349 Revision -

Operating Instructions MEW01349 Revision - Operating Instructions MEW01349 Revision - Fire Alarm System EBL512 G3 V1.1.x Author: Jan Pettersson Date of issue: 2011-02-18 Date of rev: This page has deliberately been left blank. Table of contents

More information

BA334D Intrinsically safe Externally powered pulse input field mounting rate totaliser Issue 13

BA334D Intrinsically safe Externally powered pulse input field mounting rate totaliser Issue 13 TR Automatyka Sp. z o. o. Tel. (+48 022) 886 10 16 www.trautomatyka.pl ul. Lechicka 14 ; 02-156 Warszawa Fax. (+48 022) 846 50 37 biuro@trautomatyka.pl BA334D Intrinsically safe Externally powered pulse

More information

Addressable Loop Modules

Addressable Loop Modules Addressable Loop s Introduction FC10MIM The FC10MIM Mini Input module is designed to monitor fire contacts, such as extinguishing system control, ventilation control, fire door control etc. The module

More information

4-Channel Contact Closure Fiber Link Card System

4-Channel Contact Closure Fiber Link Card System USER GUIDE RLH Industries, Inc. The leader in rugged fiber optic technology. U-020 2017A-0330 4-Channel Contact Closure Fiber Link Card System SYSTEM INSTALLATION INFORMATION Description The 4 Channel

More information

DigiAir QUICK GUIDE & INSTRUCTION MANUAL

DigiAir QUICK GUIDE & INSTRUCTION MANUAL DigiAir QUICK GUIDE & INSTRUCTION MANUAL The most trusted brand in Alarm Signalling www.csldual.com @CSLDualCom CSL DualCom Limited Figure 1 - DigiAir Yellow Comms LED Red Fault LED Yellow Service LED

More information

3226 Trunk Port FXO Doorphone

3226 Trunk Port FXO Doorphone 3226 Trunk Port FXO Doorphone Installation and User Guide Algo Communication Products Ltd., Burnaby, BC Canada V5J 5L2 www.algosolutions.com - 1 - Document #: 90-00040F Important Safety Notice The 3226

More information

Electro-Detectors Page 2. Revision History. EDA-Z Installation and Operation Manual

Electro-Detectors Page 2. Revision History. EDA-Z Installation and Operation Manual EDA-Z1000 Radio Fire Alarm System Operation and Installation Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2TP UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk

More information

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel Synova TM Commissioning in no time thanks to automatic address allocation Auto-addressing makes setting dip switches unnecessary Automatic

More information