AS 2419 OVERVIEW OF PROPOSED CHANGES. Gary Nenadovich Director G N Consulting

Size: px
Start display at page:

Download "AS 2419 OVERVIEW OF PROPOSED CHANGES. Gary Nenadovich Director G N Consulting"

Transcription

1 AS 2419 OVERVIEW OF PROPOSED CHANGES Gary Nenadovich Director G N Consulting

2 Disclaimer FPA Australia's policy is one of continuous improvement, details of products, procedures or methods described within this document are subject to change without notice. All information provided here is believed to be correct at the time of publication. Every effort has been made to ensure the accuracy of information which is provided in good faith nothing contained herein is intended to incorporate any representation or warranty, either express or implied or to form the basis of any legal relations between the parties hereto, additional to or in lieu of such as may be applicable to a contract of sale or purchase. This presentation is so provided solely on the basis that users will be responsible for making their own assessment of the matters discussed herein and are advised to verify all relevant representations, statements and information. FPA Australia, its directors, employees and agents do not accept any liability for any injury, loss or damage incurred by use of or reliance on the information.

3 Objectives 1. Generate public comment in response to DR AS Provide an overview of changes proposed in DR AS Outline process for providing feedback via FPA Australia 4. Provide an update regarding AS 2941 & AS Discuss insurance considerations in relation to fire hydrant systems 6. Provide an update on AS logbooks and FPAS 7. Facilitate questions and answers

4 DR AS Status FP009 commenced a complete rewrite of the standard in This draft is proposed to replace AS Public comment period commenced on 29 January Public comment period closes on 2 April Standards Australia is anticipating completion of public comment and ballot voting by FP009 in time to have a new version of AS adopted as a primary reference document in the 2015 BCA. FPA Australia is seeking members comments by 15 March 2014.

5 DR AS Status NCC BCA Volume One 2013 Public Comment Draft NCC BCA Volume One 2015 NCC BCA Volume One 2015 AS Published Draft considered for adoption by ABCB AS XX Time Now Target Standards Committee FP009 Developing Draft Assessment of Draft and PIA by ABCB DR AS Public Comment Consideration of Public Comment by FP009 Standards Committee Ballot Publication Deemed-to-Satisfy Requirement of BCA Volume One Good Practice where the BCA is not required Could inform an Alternative Solution

6 Ideal Situation NCC BCA Volume One Primary Reference Standards AS 2118 Suite AS Secondary Reference Standards AS AS

7 DR AS Objective The objective of the new AS is to specify minimum requirements for the design, installation and commissioning of fire hydrant systems which a) will augment the efficient extinguishment of fire within the boundaries of the site; b) can be utilized to minimize fire spread within or between one property or building and another; c) can be used by trained fire-fighting personnel; and d) Have inlet an outlet connections suitable for use with the local fire brigade s firefighting equipment.

8 DR AS Objective The objective of this edition is to incorporate changes that reflect current best practice, and to restructure, refine and expand the content o the Standard to clarify the intent of the normative provisions. This has resulted in an increase in the number of informative appendices.

9

10 DR AS Key Changes The changes in this revision include the following: (i) (ii) A restructure of the document and content to make it easier to use and to improve its readability. Inclusion of informative appendices to clarify the intent of section(s) and clause(s). (iii) New technologies and industry best practices to enable competitive and cost-effective design and water conservation. (iv) previous Section 8, Pipework and valves split into two sections. (v) Acknowledgement of the life safety benefits of installed sprinkler systems.

11 DR AS Key Changes - Foreword There is now an acknowledgement in the foreword of DR AS that: Fire hydrant systems need to be designed, installed and commissioned by a person who have acquired through training, qualification, experience, or a combination of these, the knowledge and skill enabling them to correctly perform the required tasks. This is aligned with FPA Australia s development of the national Fire Protection Accreditation Scheme (FPAS) and proposed design, installation and certify classes to complement the already launched test and inspect class of accreditation.

12 DR AS Key Changes Section 1 Definitions The new standard includes 30 additional definitions to assist practitioners and approval agencies. Some examples include: Awning Balcony Break tank Block plan Boost Cabinet Classification Façade Fire brigade Fire hydrant attack/feed Fire load Fire main Floor area Flow, downstream Flow, Upstream Large Isolated Building Pressure, boost Pressure test (hydrostatic) Private water mains Pumpset Pumpset, fire hydrant Pumpset, jockey Pumpset, relay Reticulated water supply Room Roof Suction connection Water agency Water supply, infill Water supply, primary Water supply, supplementary

13 DR AS Key Changes Section 2 System Performance & Design No fire brigade booster assembly installed External Feed hydrant pressure and flow requirements apply Fire brigade booster assembly installed - External Attack hydrant pressure and flow requirements apply + Additional pressure and flow capacity when boosted Internal Attack hydrant pressure and flow different requirements

14 DR AS Key Changes Section 2 System Performance & Design Clause Multiple firefighting systems Where an additional firefighting system, other than hose reels (e.g. wallwetting sprinklers, automatic fire sprinklers) draw from the same water source or uses common pipework, the water source shall provide for the simultaneous operation of the systems. This aligns with FPA Australia Technical Advisory Note TAN-01.

15 DR AS Key Changes Section 2 System Performance & Design Clause 2.3 Hydraulic Design parameters Residual pressure at each fire hydrant shall not be less than that specified in Tables 2.6, 2.7, 2.8, 2.9 or 2.10 No reference to 95% performance of residual pressure available to property as per AS Information in relation to this is now in the Informative Appendix T.

16 DR AS Key Changes Section 2 System Performance & Design Clause 2.3 Hydraulic Design parameters Number of fire hydrants required to discharge simultaneously. New Table 2.1 provides basis for determining the number of hydrants required to flow according to the number of fire compartment and building classifications. Risk rationale applied.

17 DR AS Key Changes Section 2 System Performance & Design Clause 2.3 Hydraulic Design parameters Number of fire hydrants required to discharge simultaneously. AS included 1 Table (Table 2.1). Now multiple tables are proposed. New Table 2.2 Class 2 to 9 Buildings (excluding class 7a open deck carparks). Table now divided into: Non-sprinkler-protected buildings Sprinkler-protected buildings: <25m in effective height Sprinkler-protected buildings: >25m in effective height

18 Number of fire hydrants required to discharge simultaneously. Table 2.3 Class 7b or 8 buildings

19 Number of fire hydrants required to discharge simultaneously. Table 2.4 Class 7a Open deck carparks

20 Number of fire hydrants required to discharge simultaneously. Table 2.5 Open Yards

21 DR AS Key Changes Section 2 System Performance & Design Clause 2.3 Hydraulic Design parameters Hydrant Pressure and Flow No significant change to expected pressure and flows however, confusing Tables 2.2 and 2.3 from AS now scrapped in favour of 5 separate tables as follows: Table 2.6 Feed hydrant performance Table 2.7 Attack hydrant performance Table 2.8 Fire brigade boosted performance Table 2.9 Fixed on-site fire hydrant pumps Table 2.10 Relay Pump(s)

22

23

24

25

26

27 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause 3.1 General It is now nominated that location of fire hydrants must provide coverage to all portions of the building that are considered to be part of the floor area of the building as defined by the National Construction Code series and, where required, all parts of an open yard(s). It is now noted that: Note 2. Fire hydrants may be above ground, with outlets suitable for connection of a fire hose, or in ground, with connection suitable for attachment of a fire brigade standpipe to which the fire hose may be connected.

28 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause Classification of hydrants as external now includes consideration of the following parameters: Being external to enclosing walls Podium areas In relation to a building with no enclosing walls, in an area not covered by the roof Awnings, roof overhang or similar with effective depths of 3m

29 DR AS Key Changes Section 3 Hydrant location & other related provisions

30 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause A hydrant is now classified as internal if: It is within an area enclosed by walls or on a roof that is not considered to be a podium Where there are no enclosing walls but under a roof Under an awning, balcony or horizontal floor projection

31 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause Classification of feed, attack and attack/feed fire hydrants Considerations for classification of hydrants as feed, attack or attack/feed Is a fire brigade booster assembly installed? If a fire brigade booster assembly is installed, is the fire hydrant located downstream of the fire brigade booster assembly? Is the hydrant within 20m or 10m of hardstand? What pressure and flow will be achieved? Attack/feed is a new classification only applicable when hydrants are part of a system where they may be used by the fire brigade as attack or feed hydrants. Internal fire hydrants are attack fire hydrants.

32 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause Hardstand Hardstand areas and vehicular approaches are proposed to meet certain criteria including: Ability to withstand static and dynamic loads applied by attending fire brigade pumping appliance(s) All weather surface Sized for access and effective positioning of fire brigade pumping appliance(s) Accommodate appropriate gradients for sloping sites for fire brigade pumping appliance(s)

33 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause 3.4 Location Clause 3.5 External Hydrants Located to provide coverage allowed to: One level below-ground and maximum 4 storeys above ground when attached to an external hydrant or fire brigade pumping appliance. Or One level below-ground, ground and one extra storey or mezzanine if internal hydrants are also required to achieve coverage.

34 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause Street Hydrants Expected to meet the requirements for external hydrants But Where a booster is installed, street hydrants not able to be used for total or partial coverage Not more than 2 street hydrants can be used for coverage Signage indicated street hydrant location is required

35 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause Protection of fire hydrants Sprinklered building no requirements. In non-sprinklered buildings, external hydrants: In or on the external wall of the building 90/90/90 separating construction 2m either side, 3m above Within 3.5m of the external wall 90/90/90 separating construction 2m either side, 3m above. Can be part of the building or freestanding independent structure Greater than 3.5m and less than 10m 90/90/90 separating construction 1m either side provided a minimum of 3m width is achieved and 2m above

36 DR AS Key Changes Section 3 Hydrant location & other related provisions

37 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause 3.6 Internal fire hydrants To be located in every required fire isolated exit not covered by external hydrants as permitted by the Standard. For required non-fire isolated exits internal hydrants are required to be within 4m of the exit However fire hydrant outlets need not be located adjacent to each required non-fireisolated exit, provided coverage can be achieved by fire hydrants located elsewhere. Mid landing locations ok as long as not more than half a flight of stairs above the FFL.

38 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause 3.11 Method of Measurement and Hose Lay Limitations New section. Confirms route to be measured must be direct but along expected paths of travel Where fire hose coverage requires ascending or descending a ramp or stair, the distance shall be measured along the path of travel followed by the stairway or ramp. For a stairway, the path shall be taken as a line along the nosing so the treads at the outer perimeter of the stair enclosure. For a ramp, the path shall be taken along the outer perimeter of the ramp. Distance from the building is a distance from the edge of the building including awning, roof or horizontal projection subject to depth. Fire hydrant locations serving a car park shall be determined with all car parking spaces empty.

39 DR AS Key Changes Section 3 Hydrant location & other related provisions Clause 3.11 Method of Measurement and Hose Lay Limitations Revolving doors not permitted to be used as an access point to the building for coverage Storage racking, shelving, internal walls, partitions, doors, fixed seating or any other fixed obstruction that restrict normal fire hose coverage throughout the building shall be measured around the obstructions. Where a fire brigade pumping appliance is to be used, for measuring purposes in determining coverage, the appliance shall: Be on hardstand Not <10m from the building Not under a roof or projection Be positioned in a single location

40 DR AS Key Changes Section 4 Water Sources & Supplies Clause Adequacy of water sources Where a river, reservoir, lake, dam, seawater or bore is used as a water source, evidence of the reliability and suitability of the water source shall be provided. Clause Water for use Recycled water acceptable subject to it being determined to be suitable for human contact. Clause 4.2 Water supplies Minimum 4 hours supply required for the required performance of the hydrant system or if also serving other firefighting systems, supply for simultaneous operation for the required durations of each system.

41 DR AS Key Changes Section 4 Water Sources & Supplies Clause Metering Where a water meter is installed the meter shall- (a) (b) be installed on a bypass such as around a backflow prevention device; or be installed in-line, provided the meter- (i) does not limit flow, including in the event of meter failure; (ii) does not include a strainer; and (iii) has the same nominal bore as the fire service. The hydraulic effect of the meter and associated pipework and fittings shall be included in flow and pressure calculations of the fire hydrant system design.

42 DR AS Key Changes Section 5 Water Storage Tanks Clause 5.2 Tank Construction On-site tanks shall be constructed from concrete or steel. Concrete tanks AS/NZS 1170 loading, AS3735 Concrete Steel tanks AS2304 Clause Tank fill time Multiple tank refill times to 50% capacity depending on tank capacity. Clause Increased signage requirements such as PRIMARY WATER SUPPLY and FIRE HYDRANT TANK

43 DR AS Key Changes Section 6 Pumpsets Requirements regarding relay pumps now in this section instead of fire brigade booster sec. Clause 6.2 When a pumpset is required When a primary water supply is unable to provide unassisted pressures required Relay pumps required when a building has an effective height >50m. Jockey / pressure maintenance pump required when any pressure-responsive device used for initiating the automatic starting of an on-site pumpset is installed. Different duty flow and pressures to be determined depending on number of pumps and relay pumps.

44 DR AS Key Changes Section 6 Pumpsets Clause 6.4 Fire Hydrant Pumpset(s) Configuration Minor changes to number and type of pumps allowed based on reliability and emergency power connection. Clause More comprehensive requirements in relation to: Relay pumps Inflow water supply pumpset(s) Fixed on-site pumpset(s) in parallel or in series with the fire brigade booster assembly Pump control Pump room or enclosure

45 DR AS Key Changes Section 7 Fire Brigade Booster Assembly Clause 7.1 General A fire brigade booster assembly shall (b) be located in a cabinet in accordance with the requirements of Section 10. (d) Incorporate fire hydrant valves and fire brigade booster connections that comply with the requirements of AS and AS respectively. Clause External alarm indication The location of the fire brigade booster shall be indicated by a red strobe light, which is activated by an alarm signal from a fire panel that serves: Any installed automatic smoke detection and alarm system or sprinkler system

46 DR AS Key Changes Section 7 Fire Brigade Booster Assembly Clause Accessibility, clearance and protection Booster must not be <3m from the vent terminal construction of the gas assembly or gas measurement system serve a gas assembly or gas measurement system. (Note these are defined by AS/NZS ) A clear area free of obstruction is required immediately in front of the booster cabinet 1500mm in front, 250mm either side. Clause 7.4 Types of fire brigade booster assemblies H pattern In-line I pattern Tank model Tank suction

47 Types of Fire Brigade Booster Assemblies H Pattern

48 Types of Fire Brigade Booster Assemblies H Pattern

49 Types of Fire Brigade Booster Assemblies I Pattern

50 DR AS Key Changes Section 7 Fire Brigade Booster Assembly Clause Number of boost inlet connections required Not less than two fire brigade booster inlet connections shall be provided for each fire brigade booster assembly. The number of fire brigade booster inlet connections required to be provided at a fire brigade booster assembly that only serves a fire hydrant system shall be determined as follows: Number of fire brigade booster inlets required = Hydrant system demand (L/s) 10 (L/s) If a fire hydrant and sprinkler system are served Number of fire brigade booster inlets required = Hydrant system demand (L/s) 10(L/s) + Sprinkler demand (L/s) 10(L/s)

51 DR AS Key Changes Section 7 Fire Brigade Booster Assembly Clause Non-sprinkler-protected buildings Specific requirements to protect the fire brigade booster assembly depending on proximity to building. Clause Sprinkler-protected buildings No requirement to protect the fire brigade booster assembly.

52 DR AS Key Changes Section 8 Pipework Design & Installation Previous Section 8 now split into 2 sections, i.e. Section 8 and Section 9. Clause Large isolated buildings not greater than 25 m Ring mains now required to be external to the building (where possible). New Clauses including: Clause 8.9 System Monitoring Valve monitoring now required for buildings greater than 25 m Clause 8.12 High Rise Design Criteria (should avoid the need for Alt. Solutions) Down feed (cascade systems) and Up feed (bottom up) systems allowed

53 DR AS Key Changes Section 9 Pipes, valves & fittings Pipe, valves and fittings specifications can be found here New Clause Plastic Pipe Joints Revised clauses including: Clause 9.7 Pipe Marking Previous 2 methods combined to 5 required and 5 optional criteria; and Clause 9.8 Corrosion Protection Recognises internal corrosion.

54 DR AS Key Changes Section 10 Ancillary Equipment Signage, cabinets and enclosures, pressure gauges and block plan requirements can be found here New Clause 10.2 Cabinets, Enclosures and Recesses Cabinets are now required to house fire brigade booster assemblies Clause 10.3 Signage Previous information expanded and contained under this one clause Clause Pressure gauge schedule A permanent chart showing pressure settings for all gauges at the F.B. booster assembly

55 DR AS Key Changes Section 11 Commissioning A more comprehensive description of system testing can be found here which includes reference to 2 Normative Appendices Q and S and 1 Informative Appendix R. New Clause 11.2 Hydrostatic testing of non-booster systems New Clause 11.3 Hydrostatic testing of boosted systems New Clause 11.4 Dynamic flow testing New Table 11.1 lists minimum mandatory testing in accordance with Normative Appendix Q and S

56 DR AS Appendicies

57 DR AS Appendicies

58 DR AS Appendicies

59 DR AS Appendicies

60 DR AS Appendicies

61 DR AS Appendicies

62 DR AS Appendicies

63 DR AS Appendicies

64 Thank you! For info about GN Consulting please visit our website:

Developments in Australian Standard AS (Emergency Lighting)

Developments in Australian Standard AS (Emergency Lighting) Developments in Australian Standard AS2293.2 (Emergency Lighting) Russell Porteous Chief Executive Officer, Firewize Australian Standards Committee LG-007 Disclaimer Firewize policy is one of continuous

More information

SCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY

SCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY SCHEDULE Essential s taken from Schedule 9 of the Building Regulations 2006 43 PART 1 BUILDING FIRE INTEGRITY 1 Building elements required to satisfy prescribed fire-resistance levels 2 Materials and assemblies

More information

Draft FPA Australia Technical Specification for Public Comment FPAA101D DRAFT

Draft FPA Australia Technical Specification for Public Comment FPAA101D DRAFT Draft FPA Australia Technical Specification for Public Comment FPAA101D These preliminary pages provide information on the background to this Technical Specification, the system it covers and the context

More information

Australian Standard. Fire hydrant installations. Part 1: System design, installation and commissioning AS

Australian Standard. Fire hydrant installations. Part 1: System design, installation and commissioning AS AS 2419.1 1994 (Incorporating Amendment Nos 1 and 2) AS 2419.1 1994 Australian Standard Fire hydrant installations Part 1: System design, installation and commissioning This Australian Standard was prepared

More information

Draft FPA Australia Technical Specification for Public Comment FPAA101H DRAFT

Draft FPA Australia Technical Specification for Public Comment FPAA101H DRAFT Draft FPA Australia Technical Specification for Public Comment FPAA101H These preliminary pages provide information on the background to this Technical Specification, the system it covers and the context

More information

Baseline Data Required for AS

Baseline Data Required for AS Baseline Data Required for AS 1851-2012 Name: Brett Dundules Position: Technical Officer Organisation Fire Protection Association Australia Introduction Brief History of AS 1851-2012 Introduction of Baseline

More information

Fire Sprinkler Systems Seminar. AS Public Comment Draft Forum

Fire Sprinkler Systems Seminar. AS Public Comment Draft Forum Fire Sprinkler Systems Seminar AS2118.1 Public Comment Draft Forum Welcome Chris Wyborn / Scott Williams / Matthew Wright FPA Australia Fire Sprinkler Systems Seminar 1. Development of the new standard

More information

Australian Standard. Fixed fire protection installations Pumpset systems AS AS 2941

Australian Standard. Fixed fire protection installations Pumpset systems AS AS 2941 AS 2941 2002 AS 2941 Australian Standard Fixed fire protection installations Pumpset systems This Australian Standard was prepared by Committee FP-008, Fire Service Pumps. It was approved on behalf of

More information

Alarm Signalling Equipment: Connection Requirements (Victoria) TAN 06. Technical Advisory Note. Version 1 October 2018

Alarm Signalling Equipment: Connection Requirements (Victoria) TAN 06. Technical Advisory Note. Version 1 October 2018 TAN 06 Alarm Signalling Equipment: Connection Requirements (Victoria) Version 1 October 2018 1 1 Purpose statement The purpose of this is to provide advice concerning the legislative requirements for the

More information

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006)

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) 1. INTRODUCTION 1.1 Essential Safety Measures Defined Essential Safety Measures (previously called essential services) are

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

Fire Protection, Inspection and Testing Qualifications Forums. Jeremy Rose (Artibus Innovation) Chris Wyborn (FPA Australia)

Fire Protection, Inspection and Testing Qualifications Forums. Jeremy Rose (Artibus Innovation) Chris Wyborn (FPA Australia) Fire Protection, Inspection and Testing Qualifications Forums Presenters: Jeremy Rose (Artibus Innovation) Chris Wyborn (FPA Australia) Welcome Agenda New arrangements for training package development

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

NZS 4517:2010. New Zealand Standard. Fire sprinkler systems for houses. Superseding NZS 4517:2002 NZS 4517:2010

NZS 4517:2010. New Zealand Standard. Fire sprinkler systems for houses. Superseding NZS 4517:2002 NZS 4517:2010 New Zealand Standard Fire sprinkler systems for houses Superseding NZS 4517:2002 NZS 4517:2010 NZS 4517:2010 COMMITTEE REPRESENTATION This Standard was prepared under the supervision of the P 4517 Committee,

More information

Fire protection documentation. CFPA-E Guideline No 13:2015 F

Fire protection documentation. CFPA-E Guideline No 13:2015 F Fire protection documentation CFPA-E Guideline No 13:2015 F FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation in the

More information

Fire Protection Accreditation Scheme (FPAS)

Fire Protection Accreditation Scheme (FPAS) Fire Protection Scheme (FPAS) A voluntary accreditation scheme for the fire protection industry covering inspect and test activities Information Guide December 2013 Fire Protection Association Australia

More information

Australian Standard. Emergency escape lighting and exit signs for buildings. Part 1: System design, installation and operation AS 2293.

Australian Standard. Emergency escape lighting and exit signs for buildings. Part 1: System design, installation and operation AS 2293. AS 2293.1 2005 AS 2293.1 2005 Australian Standard Emergency escape lighting and exit signs for buildings Part 1: System design, installation and operation This Australian Standard was prepared by Committee

More information

BUILDING CODE ACCESS CONSULTING ESSENTIAL SERVICES

BUILDING CODE ACCESS CONSULTING ESSENTIAL SERVICES Essential Safety Measures - Fire & Smoke Control of Mechanical Services Antony Rickards Building Compliance BUILDING CODE ACCESS CONSULTING ESSENTIAL SERVICES Essential Safety Measures What we will cover.

More information

Information Bulletin

Information Bulletin Consideration of emergency response in Alternative Solutions Version 1 Approved for release May 2015 1.0 Purpose statement The purpose of this document is to increase awareness and consideration of the

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Australian Standard. Components for the protection of openings in fire-resistant walls. Part 1: Fire-resistant doorsets AS AS 1905.

Australian Standard. Components for the protection of openings in fire-resistant walls. Part 1: Fire-resistant doorsets AS AS 1905. AS 1905.1 2005 AS 1905.1 2005 Australian Standard Components for the protection of openings in fire-resistant walls Part 1: Fire-resistant doorsets This Australian Standard was prepared by Committee FP-019,

More information

AS 1851:2012 The Use and Adoption of the New Standard The impacts and challenges for the fire protection and property management industries.

AS 1851:2012 The Use and Adoption of the New Standard The impacts and challenges for the fire protection and property management industries. AS 1851:2012 The Use and Adoption of the New Standard The impacts and challenges for the fire protection and property management industries. Development of the new Standard Chris Wyborn Senior Technical

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

Module 9: Ontario Building Code Fire Fighting Provisions

Module 9: Ontario Building Code Fire Fighting Provisions Ontario Building Code (OBC) 1. Sprinklers 2. Standpipes 3. Fire Alarms 4. Entrances Ontario Building Code (OBC) 1. Sprinklers 2. Standpipes 3. Fire Alarms 4. Entrances 1. Sprinklers i) Sprinkler Systems

More information

Fire Protection Coffee Break Training May 2016

Fire Protection Coffee Break Training May 2016 Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers

More information

Client Advisory Note June 2015:

Client Advisory Note June 2015: Client Advisory Note June 2015: Topics: 1. Substantially revised Fire Alarm and Smoke Control Standards for proposed adoption in NCC Volume One BCA 2016; 2. Independent review of Building Professionals

More information

AS/NZS 3190:2011 AS/NZS

AS/NZS 3190:2011 AS/NZS AS/NZS 3190:2016 Australian/New Zealand Standard Approval and test specification Residual current devices (currentoperated earth-leakage devices) Superseding AS/NZS 3190:2011 AS/NZS 3190:2016 AS/NZS 3190:2016

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Checklist For Building Inspection & Fire Safety

Checklist For Building Inspection & Fire Safety INSPECTION CHECKLIST Date of Inspection: Location/Address: Weather Condition: Inspector: AFTER COMPLETING YOUR INSPECTION, TRANSFER YOUR CONCERNS/OBSERVATIONS TO THIS AREA Facility: Name: Staff Contact:

More information

SUP 14: Floor laying. Unified procedures for use within NHS Scotland

SUP 14: Floor laying. Unified procedures for use within NHS Scotland Unified procedures for use within NHS Scotland May 2015 Contents page Acknowledgements... 3 1. Introduction... 4 1.6 Control of Contractors... 4 2. Procedure... 5 2.1 Checklists... 5 2.4 Records... 5 Appendix...

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 69 PRESIDENT SEPTEMBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report: 69

More information

SNZ PAS 4509:2008. Fire Protection Association New Zealand Inc Nigel Robinson. Insurance Brokers Association of New Zealand Inc Peter Hughes

SNZ PAS 4509:2008. Fire Protection Association New Zealand Inc Nigel Robinson. Insurance Brokers Association of New Zealand Inc Peter Hughes Committee representation This Code of Practice was prepared under the supervision of the P 4509 Committee the Standards Council established under the Standards Act 1988. The committee consisted of representatives

More information

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

AS/NZS :2015. Plumbing and drainage AS/NZS :2015. Part 4: Heated water services. Australian/New Zealand Standard

AS/NZS :2015. Plumbing and drainage AS/NZS :2015. Part 4: Heated water services. Australian/New Zealand Standard AS/NZS 3500.4:2015 Incorporating Amendment No. 1 Australian/New Zealand Standard Plumbing and drainage Part 4: Heated water services Superseding AS/NZS 3500.4:2003 AS/NZS 3500.4:2015 AS/NZS 3500.4:2015

More information

Australian Standard. Water mist fire protection systems System design, installation and commissioning AS

Australian Standard. Water mist fire protection systems System design, installation and commissioning AS AS 4587 1999 Australian Standard Water mist fire protection systems System design, installation and commissioning This Australian Standard was prepared by Committee FP/12, Aqueous Fire Protection Systems.

More information

COMPLYING DEVELOPMENT CERTIFICATE APPLICATION Made under the Environmental Planning and Assessment Act 1979 Sections 85, 85A

COMPLYING DEVELOPMENT CERTIFICATE APPLICATION Made under the Environmental Planning and Assessment Act 1979 Sections 85, 85A COMPLYING DEVELOPMENT CERTIFICATE APPLICATION Made under the Environmental Planning and Assessment Act 1979 Sections 85, 85A IDENTIFICATION OF BUILDING Address Lot, DP/MPS etc Suburb or town Post Code

More information

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,

More information

Fire Management Guide

Fire Management Guide Fire Management Guide Meeting day to day fire management obligations in WA requires reference to Health and Safety legislation, the Building Code of Australia, and multiple Australian Standards. This guide

More information

ISO INTERNATIONAL STANDARD. Testing of valves Fire type-testing requirements. Essais des appareils de robinetterie Exigences de l'essai au feu

ISO INTERNATIONAL STANDARD. Testing of valves Fire type-testing requirements. Essais des appareils de robinetterie Exigences de l'essai au feu INTERNATIONAL STANDARD ISO 10497 Third edition 2010-02-15 Testing of valves Fire type-testing requirements Essais des appareils de robinetterie Exigences de l'essai au feu Reference number ISO 10497:2010(E)

More information

Scope of Section 2. AS vs. Application Issues. Schedules & Log- Contents. Books

Scope of Section 2. AS vs. Application Issues. Schedules & Log- Contents. Books Contents Scope of Section 2 Application Issues AS 1851-1997 vs 2005 Schedules & Log- Books Scope of AS1851 Section 2 Review and rewrite of all sprinkler maintenance activities AS 1851.3 1997 becomes General

More information

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT Factory Name: 4 YOU CLOTHING LTD 367/1 Senpara Parbata, Mirpur-10, Dhaka Dhaka Dhaka Bangladesh 27 May 2014 The Alliance for Bangladesh Worker Safety Page 1/20

More information

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.0 GENERAL: Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.1 PURPOSE -The intent of this guideline is to provide the requirements for the protection

More information

Firefighting operations on automatic sprinklers systems F5-06 GD

Firefighting operations on automatic sprinklers systems F5-06 GD DESIGNER S GUIDE Firefighting operations on automatic sprinklers systems F5-06 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position on design

More information

FIRE PREVENTION AND PROTECTION*

FIRE PREVENTION AND PROTECTION* Chapter 30 (Replaced old ordinance September10, 2012) FIRE PREVENTION AND PROTECTION* * Cross References: Buildings and building regulations, ch. 14; environment, ch. 26; manufactured homes and trailers,

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

CERTIFICATION SAFETY & BEYOND

CERTIFICATION SAFETY & BEYOND CERTIFICATION SAFETY & BEYOND Ferhun Emeksiz & R.M ( Max) Bradbury Client Manager & Fire Products Program Manager Global-Mark Pty Ltd Content Product Certification Understanding the framework Fundamental

More information

Australian Standard. Security screen doors and security window grilles AS AS 5039

Australian Standard. Security screen doors and security window grilles AS AS 5039 AS 5039 2003 AS 5039 Australian Standard Security screen doors and security window grilles This Australian Standard was prepared by Committee CS-023, Security Screen Doors and Security Window Grilles.

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 1841.1:2007 AS/NZS 1841.1:2007 Australian/New Zealand Standard Portable fire extinguishers Part 1: General requirements AS/NZS 1841.1:2007 This Joint Australian/New Zealand Standard was prepared

More information

NZS 4510:2008 Incorporating Amendment No. 1. New Zealand Standard. Fire hydrant systems for buildings. Superseding NZS 4510:1998 NZS 4510:2008

NZS 4510:2008 Incorporating Amendment No. 1. New Zealand Standard. Fire hydrant systems for buildings. Superseding NZS 4510:1998 NZS 4510:2008 New Zealand Standard Fire hydrant systems for buildings Superseding NZS 4510:1998 NZS 4510:2008 Incorporating Amendment No. 1 NZS 4510:2008 Committee Representation This Standard was prepared under the

More information

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014 NFPA 13 2016 Edition NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s Committees created the First Draft at meetings between July 2013 and December 2013 Balloting ended in early 2014 First Draft decisions

More information

AS AS Australian Standard. Installation of fire hose reels. This is a free 6 page sample. Access the full version online.

AS AS Australian Standard. Installation of fire hose reels. This is a free 6 page sample. Access the full version online. AS 2441 2005 AS 2441 2005 Australian Standard Installation of fire hose reels This Australian Standard was prepared by Committee FP-007, Fire Hose Reels. It was approved on behalf of the Council of Standards

More information

The requirements of BS Watermist Fire System standard and how to demonstrate compliance

The requirements of BS Watermist Fire System standard and how to demonstrate compliance The requirements of BS8489-1 Watermist Fire System standard and how to demonstrate compliance Bob Whiteley C. Eng.; F.I.Mech.E.; M.I.Fire E.; B.Tech(Hons) Chair: BSI Watermist Working Group Overview What

More information

FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA

FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA 93 FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA INTRODUCTION 94 Legal requirements for the protection of firefighters Requirements of Building Act Fire Prevention Act Technical Guidelines OIB

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 3500.4:2003 (Incorporating Amendment Nos 1 and 2) AS/NZS 3500.4:2003 Australian/New Zealand Standard Plumbing and drainage Part 4: Heated water services AS/NZS 3500.4:2003 This Joint Australian/New

More information

Annual Essential Safety Measures Report. 29 Bay Sample Street Port Melbourne VIC 3207

Annual Essential Safety Measures Report. 29 Bay Sample Street Port Melbourne VIC 3207 Annual Essential Safety Measures Report 29 Bay Sample Street Port Melbourne VIC 3207 30+ Years Experience In Reporting Services Our Quality Reports Make Roscon The Number #1 Choice We conduct onsite audits

More information

ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND SHELTER FIRST EDITION APRIL 2015

ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND SHELTER FIRST EDITION APRIL 2015 ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND SHELTER FIRST EDITION APRIL 2015 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner. Neither whole

More information

Essential Services and Inspection Guide Checklist

Essential Services and Inspection Guide Checklist Essential Services and Inspection Guide Checklist Foreword The provision of protection measures within buildings is essential to promote the safety of occupants and paramount for effective operation of

More information

Management Practices: Fire Protection Impairments November 2015

Management Practices: Fire Protection Impairments November 2015 RiskTopics Management Practices: Fire Protection Impairments November 2015 When business capital is invested in fire protection, it is difficult to explain any fire protection outage that allows a fire

More information

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS AS 4214 2002 (Incorporating Amendment No. 1) AS 4214 2002 Australian Standard Gaseous fire extinguishing systems This Australian Standard was prepared by Committee FP-011, Gaseous Fire Protection. It was

More information

Fire Collars for Floor Wastes Understanding BCA Compliance Options

Fire Collars for Floor Wastes Understanding BCA Compliance Options Fire Collars for Floor Wastes Understanding BCA Compliance Options February 2005 Introduction There has been a great deal of discussion in recent times regarding fire testing requirements for fire collars

More information

Use this guide to assist you when completing the Evacuation scheme application form.

Use this guide to assist you when completing the Evacuation scheme application form. Guide EVACUATION SCHEME APPLICATION ABOUT THIS GUIDE Use this guide to assist you when completing the Evacuation scheme application form. CONTENTS Before you start completing your application Section 1

More information

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT BUILDING ASSESSMENT REPORT FIRE FOR 75 Fox Street Building OCTOBER 2014 Report for Department of Infrastructure Development Fire Services Preliminary Report:

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 1850:2009 AS/NZS 1850:2009 Australian/New Zealand Standard Portable fire extinguishers Classification, rating and performance testing AS/NZS 1850:2009 This Joint Australian/New Zealand Standard

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved;

More information

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD DESIGNER S GUIDE Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 2293.2:1995 Australian/New Zealand Standard Emergency evacuation lighting for buildings AS/NZS 2293.2:1995 This Joint Australian/New Zealand Standard was prepared by Joint Technical Committee LG/7,

More information

Queensland Building Plan (Licensing Reform) FPA Australia Submission

Queensland Building Plan (Licensing Reform) FPA Australia Submission Queensland Building Plan (Licensing Reform) FPA Australia Submission Table of contents 1.0 Executive Summary... 2 2.0 About FPA Australia... 3 3.0 Introduction... 6 4.0 Background... 6 5.0 Fire Occupational

More information

Certification of Thermographers

Certification of Thermographers CFPA-E No 3:2011 F Certification of Thermographers CFPA-E -GUIDELINES FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation

More information

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY. STATE OF LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BOULEVARD, BATON ROUGE, LA 70806 800-256-5452 225-925-4920

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE

More information

SMALL LOT DESIGN STANDARDS. An Illustrated Working Draft for Test Implementation

SMALL LOT DESIGN STANDARDS. An Illustrated Working Draft for Test Implementation SMALL LOT DESIGN STANDARDS An Illustrated Working Draft for Test Implementation SMALL LOT DESIGN STANDARDS ILLUSTRATED WORKING FOR TEST IMPLEMENTATION OVERVIEW SMALL LOT CODE AMENDMENT & POLICY UPDATE

More information

Application Form. Qualified Accreditation

Application Form. Qualified Accreditation Inspect and Test Application Form Qualified Accreditation Application Process Important Note: Please ensure you have read the Qualified Accreditation FACT SHEET available on: http://www.fpaa.com.au/fpas/factsheets-application-forms

More information

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670.

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670. AS 1670.1 2004 (Incorporating Amendment No. 1) AS 1670.1 2004 Australian Standard Fire detection, warning, control and intercom systems System design, installation and commissioning Part 1: Fire This Australian

More information

Australian Standard. Fire detection, warning, control and intercom systems Control and indicating equipment. Part 1: Fire

Australian Standard. Fire detection, warning, control and intercom systems Control and indicating equipment. Part 1: Fire AS 4428.1 1998 (Incorporating Amendment No. 1) AS 4428.1 Australian Standard Fire detection, warning, control and intercom systems Control and Part 1: Fire This Australian Standard was prepared by Committee

More information

Code for Design of Clean Room

Code for Design of Clean Room Translated English of Chinese Standard: GB50073-2013 www.chinesestandard.net Sales@ChineseStandard.net GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA UDC P GB 50073-2013 Code for Design of Clean

More information

Automatic Sprinkler Systems Care and Maintenance

Automatic Sprinkler Systems Care and Maintenance 0-0.0 January 2012 Country of Origin: United Kingdom Automatic Sprinkler Systems Care and Maintenance Introduction...1 Weekly Inspection and Tests...2 Monthly Inspection and Tests...3 Service and Maintenance

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 3760:2003 (Incorporating Amendment No. 1) AS/NZS 3760:2003 Australian/New Zealand Standard In-service safety inspection and testing of electrical equipment AS/NZS 3760:2003 This Joint Australian/New

More information

CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES

CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES EMERGENCY MANAGEMENT DESIGN GUIDELINES 000331 Details of revisions Level Details Date Initial 1 Document created from 20150513NewBuildsAndRedevelopments.docx

More information

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011 The Code of Practice for Fire Safety in Buildings 2011 The FS Code comprises 7 parts and 1 annex: Part A Introduction Part B

More information

Practice Advisory 18: Fire safety design for tall buildings

Practice Advisory 18: Fire safety design for tall buildings Practice Advisory 18: Fire safety design for tall buildings It s important that reliable and resilient fire design features are used in the design of tall buildings. This advisory highlights the specific

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:

More information

Occupational Health & Safety Practitioner. Reading BUILDING FIRE SAFETY

Occupational Health & Safety Practitioner. Reading BUILDING FIRE SAFETY Occupational Health & Safety Practitioner Reading BUILDING FIRE SAFETY January 2009 Contents OVERVIEW...1 SECTION 1: INTRODUCTION...2 SECTION 2: BUILDING CLASSIFICATIONS...4 SECTION 3: PASSIVE AND ACTIVE

More information

Australian Fire Association

Australian Fire Association Australian Fire Association MODEL NSW COMPETENT FIRE SAFETY PRACTITIONER ACCREDITATION SCHEME The NSW Government has introduced new fire safety regulations designed to strengthen the state s building regulation

More information

PRIVATE FIRE SERVICE INSTALLATION PACKET

PRIVATE FIRE SERVICE INSTALLATION PACKET PRIVATE FIRE SERVICE INSTALLATION PACKET The 2017 Edition supersedes all previous versions for Private Fire Service Installation To Whom It May Concern: SUBJECT: PRIVATE FIRE SERVICE INSTALLATION Illinois

More information

Checklist For Life Safety

Checklist For Life Safety INSPECTION CHECKLIST Date of Inspection: Location/Address: Weather Condition: Inspector: AFTER COMPLETING YOUR INSPECTION, TRANSFER YOUR CONCERNS/OBSERVATIONS TO THIS AREA Facility: Name: Staff Contact:

More information

Firefighting operations emergency vehicle access guide F5-02 GD

Firefighting operations emergency vehicle access guide F5-02 GD DESIGNERS GUIDE Firefighting operations emergency vehicle access guide F5-02 GD Introduction Scope Context Use this guidance document to ensure that Fire and Emergency New Zealand fire appliances can access

More information

Newport City Council Bettws High School Fire Fighting Performance Specification CONTRACT C1

Newport City Council Bettws High School Fire Fighting Performance Specification CONTRACT C1 Fire Fighting Performance Specification CONTRACT C1 Fire Fighting Performance Specification August 2008 4 Pierhead Street, Capital Waterside, CF10 4QP Tel +44 2920 473727 Fax +44 2920 472277 This report

More information

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex:

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex: The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex: Mr. Junkers Lam Senior Building Surveyor of Buildings Department (9 Sept 2013) Part A Introduction Part B Means

More information

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE ASSESSMENT REPORT (FAR) INITIAL FIRE ASSESSMENT REPORT (FAR) Factory SQ Station, Plot # 221-223, Jamirdia, Valuka, Mymensingh Mymensingh 17 Jun 2014 The Alliance for Bangladesh Worker Safety Page 1/17 Factory 17 Jun 2014 Introduction

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES SECTION 21 30 00 FIRE PUMPS GENERAL This standard provides general requirements of The University of South Alabama in Mobile Alabama for fire pumps. This document is not intended to serve as a guide specification.

More information

UNCONTROLLED IF PRINTED. Issued with the authority of the Chief Commissioner and General Manager of Scouts Australia NSW

UNCONTROLLED IF PRINTED. Issued with the authority of the Chief Commissioner and General Manager of Scouts Australia NSW PROCEDURE Emergency preparedness Issued with the authority of the Chief Commissioner and General Manager of Chief Commissioner signature Chief Executive Officer signature Sponsor Head of Risk Document

More information

MEDIUM-DENSITY HOUSING # 7. Fire safety

MEDIUM-DENSITY HOUSING # 7. Fire safety BRANZ FACTS MEDIUM-DENSITY HOUSING # 7 Fire safety Moving from low-density to medium-density housing (MDH) involves people living in closer proximity. This has a number of implications for fire safety

More information

Firefighting operations on fire control centres F5-09 GD

Firefighting operations on fire control centres F5-09 GD DESIGNER S GUIDE Firefighting operations on fire control centres F5-09 GD Introduction Purpose Scope The purpose of this guideline is to provide a consistent Fire and Emergency New Zealand position on

More information

PLANNING INSTITUTE OF AUSTRALIA, NSW DIVISION SUBMISSION ON THE NSW DRAFT HOUSING CODE AND NSW DRAFT COMMERCIAL CODE

PLANNING INSTITUTE OF AUSTRALIA, NSW DIVISION SUBMISSION ON THE NSW DRAFT HOUSING CODE AND NSW DRAFT COMMERCIAL CODE PLANNING INSTITUTE OF AUSTRALIA, NSW DIVISION SUBMISSION ON THE NSW DRAFT HOUSING CODE AND NSW DRAFT COMMERCIAL CODE This Submission provides detailed comment on draft Codes following feedback from PIA

More information

Fire Service Considerations A Primer for Building and System Designers. Society of Fire Protection Engineers Fire Service Committee

Fire Service Considerations A Primer for Building and System Designers. Society of Fire Protection Engineers Fire Service Committee Fire Service Considerations A Primer for Building and System Designers Society of Fire Protection Engineers Fire Service Committee Version 1 October 15, 2012 Target Audience Any of these designers without

More information