Investigation report. Radiation resistance of fire detectors under the influence of radioactive gamma radiation
|
|
- Henry Roberts
- 6 years ago
- Views:
Transcription
1 Radiation resistance of fire detectors under the influence of radioactive gamma radiation Page 1 ST FIR/PRM1
2
3 Contents 1. Introduction Fire detectors tested Trial description Trial design Energy distribution and volumetric heat generation rate of -radiation Execution of the trials Trial results Discussion of results Basics Evaluation and conclusions Operating time as influenced by -radiation Appendix
4 1. Introduction Reliability and safety requirements are particularly important for early recognition of fires in nuclear systems. Here automatic fire detectors are also used in areas in which they are subjected to radioactive radiation. The type and dosage levels of radiation at the location of the detector can lead to changes in the response of the fire detector as well as damage to individual components. Taking into account the location factors in each case, the results of these investigations have a significant impact on the selection of fire detector types and their operating time when developing new fire detector systems and with regard to maintenance measures for existing systems. The present investigation shows how the sensitivity and the quiescent value of various MAGIC.SENS fire detectors are influenced by varying degrees of gamma radiation at different dose rates. 2. Fire detectors tested Fire detectors with GLT- and LSN-technology, and with optical, thermal and chemical sensors were tested. Trial 1 Detector designation Type Sensors OT 300 GLT optical + thermal OT 400 LSN optical + thermal OTC 410 LSN optical + thermal + chemical Trial 2 Detector designation Type Sensors OT 300 GLT optical + thermal OT 400 LSN optical + thermal OTC 410 LSN optical + thermal + chemical 4
5 3. Trial description 3.1. Trial design The trials were performed in the tank system at the technical facility of the Jülich Research Centre. Here medium burn up fuel assemblies positioned vertically in storage capsules, are used for specific gamma radiation as required. Supervision of sample containers in radiation tank The fire detectors were lowered into the radiation tank in a sample container with a diameter of 330 mm, and were positioned between the fuel assemblies and supplied and checked via pipelines. The surrounding medium consisted of air at a temperature of C. Sample containers 5
6 3.2. Energy distribution and volumetric heat generation rate of -radiation In order for the quality of the gamma radiation to be evaluated, the energy distribution and volumetric heat generation rate were determined for medium burn up fuel assemblies (55%). Figure 1 shows the volumetric heat generation rate and the photon energy averaged with the volumetric heat generation rate across the entire energy range as a function of the decay time. The emission rate (photons/sec) decreases erratically during the first two weeks. The next phase over a period of 16 months is characterised by an average negative slope. Thereafter, the trend is relatively flat, attributable to the gamma activity in durable fission products. The average energy of the gamma radiation decreases rapidly during the first three months. After that the trend is almost constant at an average energy of 0.6 MeV. Emission rate in s 1 1.0E E E+15 Volumetric heat generation rate: photons per s Energy in MeV 1.0E+14 Average energy of gamma radiation E Time in months Fig. 1: Volumetric heat generation rate and average energy in gamma radiation of burnt up fuel assembly depending on the decay time Figure 2 illustrates the energy distribution in gamma radiation with different decay times. Accordingly, after only two weeks, no high energy photons (> 3,5 MeV) are emitted. As the decay time increases, so the energy spectrum shifts towards lower energies due to the remission of high energy gamma radiation. This results in a slight decrease in average energy in the -photons (Fig. 1). The fire detectors were exposed to an energy spectrum of MeV during the trials. On average, the quantum energy amounted to 0.7 MeV. The absorbed dose was measured using an ionisation chamber with direct display. The neutron field is negligibly low, which means that no activation takes place. After radiation the probes can easily be handled. 6
7 Emission rate in s 1 1.0E E E E E E+07 Gamma radiation spectrum at discharge after 2 weeks after 2 months after 3 months after 3 years 1.0E Energy in MeV Fig. 2: Energy distribution in gamma radiation of burnt up fuel assembly (55% burn up) 3.3. Execution of the trials In trial 1, all fire detectors were exposed to gamma radiation with an average absorbed dose rate of 25 Gy/hr for a period of 20 hrs 35 min. The cumulative absorbed dose amounted to 515 Gy. The second trial was executed at an average absorbed dose rate of 15 Gy/hr. A cumulative absorbed dose of 105 Gy was achieved for all LSN-fire detectors over an exposure time of 7 hrs. The GLT-fire detectors remained in the radiation tank for 17 hrs. The cumulative absorbed dose amounted to 255 Gy. The sensitivity of all detectors was measured in an aerosol channel in accordance with EN 54-7 before and after radiation. Sensitivity measurement of the chemical sensors in the OTC 410-detectors was carried out using a test gas concentration of 30 ppm carbon monoxide (CO). In addition to measuring the sensitivity, the quiescent value of the optical component was recorded for all LSN-detectors. One component of the detectors was in operation during radiation (test mode). 7
8 3.4. Trial results The measurement results are recorded in tables 1 6. During exposure to radiation the noise in the optical component increases marginally (from approx. +/ 2 digits to approx. +/ 5 digits). The quiescent value is higher after exposure to radiation, but far below the limit value that would trigger a contamination warning. In trial 1, the first fire detector was defective after a radiation duration of 5 hrs ( cumulative absorbed dose of 125 Gy). In total, defects occurred in 2 of 6 OT 300-detectors, 4 of 6 OT 400-detectors and 1 of 6 OTC 410-detectors. The failure in the OT 300-detectors was caused by defective operation amplifiers. The detectors were unable to produce an optical alarm, but could still produce a temperature alarm. The LSN- chip was defective on each of the four affected OT 400-detectors. The FET-transistors could be switched, although the LSN-chips were no longer responding. In the case of the defective OTC 410-detector, the current consumption of the EEPROM increased and the alarm -LED lit up. In trial 2 (cumulative absorbed dose of 255 Gy or 105 Gy), no defects were recorded in the OT 300 and the OT 400-detectors. A higher current consumption occurred in two of the six OTC 410-detectors in the EEPROM ( 200 A). Where the detectors were started with a higher current, they became functional again. The first defect occurred after a radiation duration of 5 hrs ( cumulative absorbed dose of 75 Gy). In summary, the results of the second trial show that defects occurred in 0 of 6 OT 300-detectors, 0 of 6 OT 400-detectors and 2 of 6 OTC 410-detectors. The sensitivity of the optical sensor increases by approximately 5 to 20% as a result of the radiation. The sensitivity of the chemical sensor increases slightly (approximately 7%) for an absorbed dose of 515 Gy and on average remains unchanged for an absorbed dose of 105 Gy. 8
9 MAGIC.SENS OT 300 Trial 1: Average dose rate: 25 Gy/hr Duration of radiation 20 hrs 35 min Cumulative dose: 525 Gy Serial number before radiation after radiation Serial number Sensitivity of O part in db/m Sensitivity of O part in db/m Error/comment OP defect/t alarm intact OP defect/t alarm intact Trial 2: Average dose rate: 15 Gy/hr Duration of radiation 17 hrs Cumulative dose: 255 Gy Serial number before radiation after radiation Sensitivity of O part in db/m Sensitivity of O part in db/m Error/comment
10 MAGIC.SENS OT 400 Trial 1: Average dose rate: 25 Gy/hr Duration of radiation 20 hrs 35 min Cumulative dose: 525 Gy Serial number before radiation after radiation Quiescent value Sensitivity of 0 part in db/m Quiescent value Sensitivity of 0 part in db/m Error/comment LSN chip defective * LSN chip defective * LSN chip defective * LSN chip defective Trial 2: Average dose rate: 15 Gy/hr Duration of radiation 7 hrs Cumulative dose: 105 Gy Serial number Quiescent value before radiation after radiation Sensitivity Quiescent value of 0 part in db/m Sensitivity Error/comment of 0 part in db/m * * * * Detectors were operational (test mode) during radiation. 10
11 MAGIC.SENS OTC 410 Trial 1: Average dose rate: 25 Gy/hr Duration of radiation 20 hrs 35 min Cumulative dose: 525 Gy before radiation after radiation Serial number Quiescent Sensitivity Sensitivity Quiescent Sensitivity value of 0 part in db/m of C part in db/m value of 0 part in db/m Sensitivity of C part in db/m Error/ Comment * EEPROM defective * Trial 2: Average dose rate: 25 Gy/hr Duration of radiation 7 hrs Cumulative dose: 105 Gy before radiation after radiation Serial number Quiescent Sensitivity Sensitivity Quiescent Sensitivity Sensitivity Error/ value of 0 part in db/m of C part in db/m value of 0 part in db/m of C part in db/m Comment * EEPROM defective * EEPROM defective * Detectors were operational (test mode) during radiation. 11
12 4. Discussion of results 4.1. Basics In principle, the question may be asked as to whether the trials performed with a gamma radiation source meet the conditions of use in nuclear systems and to what extent statements regarding the effect on electronic devices are representative. In scientific discussions and trials the types of radiation relevant for electronic devices are limited to gamma radiation and neutron radiation. Neutron radiation occurs only in containment with a direct view of the reactor, without reflections, and only during reactor operation. In the utility rooms, which are in the majority, only gamma radiation is available. The safety regulations of the KTA ( Kern-Technischer Ausschuss Nuclear Safety Standards Commission) and the IEEE (USA) standard prescribe only gamma radiation for testing devices Evaluation and conclusions The trials showed that gamma radiation can damage the ICs over a longer period of time. In particular, these were the LSN-chip with an absorbed dose of more than 125 Gy and the EEPROM in the OTC 410 with an absorbed dose of more than 75 Gy. Due to their construction, the GLT-fire detectors (OT 300) were significantly less sensitive to radiation. Because defects were also not found in the temperature component of the OT 300 detector for a cumulative absorbed rate of 515 Gy in trial 1, it can be concluded that the T 300 GLT-detector (thermal sensor) is suitable for areas of high radiation (up to 515 Gy). No defects were detected for a cumulative dose of 255 Gy in OT 300-detectors. OT 400- detectors also showed themselves to be resistant to radiation of 105 Gy. This result can be assumed for O 400 and T 400-detectors due to the similarity in construction. In all fire detectors tested, sensitivity either remained the same or increased Operating time as influenced by -radiation Using the results from different absorbed dose rates (trial 1 and trial 2), an estimate of the expected lifespan in known conditions for use can be made. For this, the type, dose rate and cumulative dose of radiation present at the detector location must be known. According to radiation protection regulations, the absorbed dose rate in the controlled zone of nuclear systems is between 7.5 Sv/hr and 3 msv/hr. 12
13 The results of the trials enable an estimate to be made of the operating time in which no malfunctions are to be expected in controlled zones. This is based on the maximum radiation exposure, which is also the limit value for identifying restricted areas: For OT 400: t E = D V D E = 105 Gy 3 mgy/hr = 35,000 hrs = 4 years D V 255 Gy For OT 300: t E = = = 85,000 hrs = 9.7 years D E 3 mgy/hr with t E operating time D V absorbed dose from trial 2 (no defects) D E expected absorbed dose rate at installation location In containment, the maximum ion dose is around 70 na/kg and the absorbed dose in the range of approx. 10 mgy. An operating time can also be estimated for this area: For OT 300: t E = D V = D E 255 Gy 10 mgy/hr = 25,500 hrs = 2.9 years 5. Appendix Radiological values Values Unit Relation Old unit Energy W ev (electron volt) 1 ev = 1.602x10 19 J Activity A Bq (Becquerel) 1 Bq = 1 sec 1 1 Ci (Curie) = 37x10 9 Bq Absorbed dose D Absorbed dose rate D Ion dose J Gy (Gray) 1 Gy = 1 J/kg 1 rd (Rad) = 0.01 Gy Gy/sec, Gy/hr C/kg (Coulomb/kg) Equivalentdose Sv (Sievert) 1 Sv = 1 Gy D e (for -radiation) 1 C/kg = 1 As/kg 1 R (Röntgen) = mc/kg 1 rem = 0.01 Sv 13
14 Bosch Sicherheitssysteme GmbH Robert Koch Str Ottobrunn, Germany Telephone +49 (0) Fax +49 (0) sicherheitssysteme.de info.service@de.bosch.com
HEALTH AND SAFETY PROGRAM 406 IONIZING/NONIONIZING RADIATION PROTECTION
Page 1 of 11 1.0 PURPOSE Axiall, Plaquemine Complex, maintains various sources of ionizing and nonionizing radiation throughout the complex. Ionizing radiation sources include density gauges and PMI Analyzers.
More informationBL 200 Strobes. Page F.01U A1.en/ 6/2/2004 ST / PMF1 / zab
PRODUCT INFORMATION BL 200 Strobes Page 1 601- F.01U.000.862 A1.en/ 6/2/2004 ST / PMF1 / zab Table of Contents 1. Product Description............................... 2 2. Features.........................................
More informationRadiation Alert Frisker INTERNATIONAL
Radiation Alert Frisker INTERNATIONAL S.E. International, Inc. P.O. Box 39, 436 Farm Rd. Summertown, TN 38483 USA 1.800.293.5759 931.964.3561 Fax: 1.931.964.3564 www.seintl.com radiationinfo@seintl.com
More informationUser s Manual. Electronic Personal Dosimeter (For Gamma(X)-ray) NRF30. Fuji Electric Co., Ltd. TN514629i 1/31
User s Manual Electronic Personal Dosimeter (For Gamma(X)-ray) NRF30 Fuji Electric Co., Ltd. TN514629i 1/31 Introduction Thank you for purchasing the Electronic Personal Dosimeter NRF30 (Hereinafter described
More informationTable of Contents. 1. Mounting Tips... 2
Table of Contents 1. Mounting Tips............................................. 2 1.1. Connections and DIP switch settings................................... 3 1.2. Mounting the Fireray 50/100RV........................................
More informationEnvironmental Radiation Monitoring System
Environmental Radiation Monitoring System Toshihiro Takagi Osamu Kimura Atsushi Minagoshi 1. Introduction In order to ascertain conditions near the perimeter of a supervised area at a nuclear power plant
More informationPortable Survey Instruments NISP-RP-01
NUCLEAR INDUSTRY STANDARD PROCESS Radiological Protection NISP-RP-01 This is an industry document for standardizing radiation protection processes used by supplemental radiation protection technicians.
More informationPRODUCT INFORMATION. GLT - Non-Automatic Fire Detector Series 120
PROUCT INFORMATION PI-34.51 GLT - Non-Automatic Fire etector Series 10 FMC-10-KM-G-R / FMC-10-KM-H-R FMC-10-KM-G-B / FMC-10-KM-H-B / FMC-10-KM-G-Y FMC-10-EST-G-B Page 1 BL-F.01U.066.178 A3.en / 14.03.008
More informationEVALUATION OF A NEUTRON-PHOTON SHIELD FOR TRANSURANIC (TRU) WASTE CONTAINERS
EVALUATION OF A NEUTRON-PHOTON SHIELD FOR TRANSURANIC (TRU) WASTE CONTAINERS M. Gallegos, R. Ruby, E. J. Sullivan, R. J. Wishau Los Alamos National Laboratory ABSTRACT The Los Alamos National Laboratory
More informationNUCLEAR INDUSTRY STANDARD PROCESS Radiological Protection. Level 3 Information Use
NUCLEAR INDUSTRY STANDARD PROCESS Radiological Protection Level 3 Information Use NISP-RP-001 Industry Approval Date: September 14, 2018 This is an industry document for standardizing radiation protection
More informationRadiation Monitoring System RMS
Radiation Monitoring System RMS VF RMS radiation monitoring system is a modular and standardized system for the radiological monitoring. Variety of radiation monitors, display and alarm units can be connected
More informationCharacterising the smoke produced from modern materials and evaluating smoke detectors
www.bre.co.uk Briefing Paper Characterising the smoke produced from modern materials and evaluating smoke detectors Raman Chagger 01 Contents Abstract 02 Introduction 02 Background 03 The current test
More informationNEXT GENERATION DRINKING WATER RADIATION SAFETY MONITOR
FEATURES: WORLD S ONLY PAG-LEVEL WATER MONITOR MEASURES AT OR BELOW EPA/DHS PAG LEVELS Protective Action Guideline Levels and Military Drinking Water Limits REAL TIME, IN-LINE, CONTINUOUS DETECTS ALPHAS,
More informationA Continuous Air Monitoring Sampler for 125 I - RIS-125
A Continuous Air Monitoring Sampler for 125 I - RIS-125 S.Levinson, I.Belaish, T.Kravchik, U.German, O.Pelled, Y. Laichter, Y.Mazor, U.Wengrowicz, E.Dolev, H.Assido, D.Tirosh Nuclear Research Center Negev,
More informationA comparison of emerging gamma detector technologies for airborne. radiation monitoring
A comparison of emerging gamma detector technologies for airborne ANSRI Dublin 2016 11-13 May radiation monitoring Steven Bell Contents Airborne radioactivity MetroERM Gamma spectrometers Experimental
More informationA bright alpha numeric display and the simplified keypad (three buttons) allow the operation even under harsh conditions.
Personal Alpha/Beta Continuous Air Monitor (CAM) The pocamon (personal online continuous air monitor) monitors continuously the breathing air to detect airborne radioactive aerosols (LLRD). Typical application
More informationRadiation Monitoring Systems
Radiation Monitoring Systems Certificate No. 3250 Contents A guide to Southern Scientific radiation monitoring systems Area Gamma & Interlock Systems (page 3) AGM3 AUTOMESS 6150 Contamination Monitors
More information50(394) IEC. ore content meter ore sorting equipment overvoltage (of a Geiger-Müller county tube)...
INDEX A (absorbed) dose ratemeter... 394-11-17 absorption band (of a scintillator)... 394-18-08 acceptance test... 394-20-09 accident monitor... 394-12-27 activator... 394-10-08 actuated equipment... 394-14-05
More informationThermo Scientific Aerosol Monitor FHT 58 S Technical Specification ZT-221E
Thermo Scientific Aerosol Monitor FHT 58 S Technical Specification ZT-221E Thermo Fisher Scientific Messtechnik GmbH Frauenauracher Straße 96 91056 Erlangen Germany www.thermo.com info.rmp.erlangen@thermofisher.com
More informationMaximize safety and productivity. Thermo Scientific Nuclear Power Radiation Detection and Monitoring Solutions
Maximize safety and productivity Thermo Scientific Nuclear Power Radiation Detection and Monitoring Solutions Monitoring solutions to optimize safety, efficiency and compliance Our years of expertise and
More informationHEALTH AND SAFETY MANUAL
HEALTH AND SAFETY MANUAL Title: Ionizing Radiation Approved by: Greg Savoy Rev. 3/1/13 1.0 Purpose The purpose of this safety policy is to establish guidelines for the protection and safety of Compay employees
More informationTHE REPUBLIC OF UGANDA ATOMIC ENERGY ACT, 2008 SCHEDULE 1 FORM 2A
ATOMIC ENERGY COUNCIL P.O.BOX 7044 KAMPALA Regulation 15 ATOMIC ENERGY FORM 2A (AEF 2A) THE REPUBLIC OF UGANDA ATOMIC ENERGY ACT, 2008 SCHEDULE 1 FORM 2A APPLICATION FOR AUTHORIZATION TO POSSESS AND USE
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 62401 Edition 2.0 2017-12 Radiation protection instrumentation Alarming personal radiation devices (PRDs) for the detection of illicit trafficking of radioactive material INTERNATIONAL
More informationIdentify the following features and specifications for the ESP1
LEARNING OBJECTIVES: 2.17.01 List the factors which affect an RCT's selection of a portable contamination monitoring instrument, and identify appropriate instruments for contamination monitoring. (Also
More informationAmerican Nuclear Society (ANS)
What s New... American Nuclear Society (ANS) Project Initiation Notification System (PINS) ANS Standards Before work on a draft can begin, a Project Initiation Notification System (PINS) form must be approved
More informationFiber Optic Cable Qualification Update
Fiber Optic Cable Qualification Update EQTM 2018 Eric Rasmussen RSCC Wire and Cable LLC Eric.rasmussen@r-scc.com Terry Price Ontario Power Generation Terry.price@opg.com 1 Darlington Nuclear Generating
More informationReal-Time Remote Monitoring System Utilizing New Electronic Personal Dosimeter
Real-Time Remote Monitoring System Utilizing New Electronic Personal Dosimeter NAKASHIMA, Sadao * MAEKAWA, Osamu * ABE, Shigeru * A B S T R A C T Conventional radiation exposure management methods included
More informationMaximizing safety and productivity. Nuclear Power Radiation Detection and Monitoring Solutions
Maximizing safety and productivity Nuclear Power Radiation Detection and Monitoring Solutions Growing portfolio You can depend on Thermo Scientific radiation detection and monitoring solutions to optimize
More informationCOMPANY PROFILE. DETECTION & MEASUREMENT OF IONIZING RADIATIONS RADIOLOGICAL MONITORING SYSTEMS HEALTH AND ENVIRONMENTAL SAFETY
monitoring for safety COMPANY PROFILE DETECTION & MEASUREMENT OF IONIZING RADIATIONS RADIOLOGICAL MONITORING SYSTEMS ENVIRONMENTAL MONITORING HEALTH AND ENVIRONMENTAL SAFETY www.rtsinstruments.com 2 monitoring
More informationSeismic Countermeasures for Environmental Radiation Monitoring System
Seismic Countermeasures for Environmental Radiation Monitoring System Osamu Maekawa Takeshi Miyairi Teruo Ebato ABSTRACT Environmental radiation monitoring system continually measures and monitors the
More informationCo-60 irradiator for therapy level calibrations at SSDLs
SPECIFICATION Co-60 irradiator for therapy level calibrations at SSDLs Prepared by: Igor Gomola, Technical Officer for TC Project ISR6021 Date: 2014-Aug-04, Rev.08 Page 1 1. Scope and Background This document
More informationTABLE OF CONTENTS. Section Title Page 1.0 SUMMARY TEST SPECIMEN Materials and Construction TEST PROGRAM 4
TABLE OF CONTENTS Section Title Page 1.0 SUMMARY 1 2.0 TEST SPECIMEN 2 2.1 Materials and Construction 2 3.0 TEST PROGRAM 4 3.1 Test Sequence 4 3.2 Functional Test Procedures 5 3.3 Specimen Preconditioning
More informationTable of Contents. Section Title Page 1.0 SUMMARY TEST SPECIMEN Materials and Construction 3.0 TEST PROGRAM 2
EDR-5210 01/07/92 Table of Contents Section Title Page 1.0 SUMMARY 1 2.0 TEST SPECIMEN 2 3.0 2.1 Materials and Construction 3.0 TEST PROGRAM 2 3.1 Test Sequence 3.2 Functional Test Procedures 3.3 Specimen
More informationRadiation Control and Monitoring System on the HTTR
Radiation Control and Monitoring System on the HTTR Y. Minowa, T. Nakazawa, H. Kikuchi, T. Nomura and N. Sato Japan Atomic Energy Research Institute Oarai Research Establishment, Oarai-machi, Ibaraki-ken
More informationHEAT REMOVAL TESTS FOR THE HIGH PERFORMANCE VAULT STORAGE SYSTEM OF SPENT NUCLEAR FUEL
HEAT REMOVAL TESTS FOR THE HIGH PERFORMANCE VAULT STORAGE SYSTEM OF SPENT NUCLEAR FUEL M. Oda*, M. Shimizu*, N. Kumagai*, H. Kanai**, M. Tanabe** *Nuclear Fuel Cycle Group, Power & Industrial Systems R&D
More informationNCRP REPORT No. 165National Council RESPONDING TO A RADIOLOGICAL OR NUCLEAR TERRORISM INCIDENT: A GUIDE FOR DECISION MAKERS
NCRP REPORT No. 165National Council RESPONDING TO A RADIOLOGICAL OR NUCLEAR TERRORISM INCIDENT: A GUIDE FOR DECISION MAKERS Appendix B Public Information Statements B.1 In the Event of a Radiological Dispersal
More informationBattery-operated, hand-held alarm and measuring instruments for radiation protection
Battery-operated, hand-held alarm and measuring instruments for radiation protection The GRAETZ alarm dosemeter ED150 warns the task force when the defined radiation dose for the operation is reached.
More informationPORTABLE ISOTOPE IDENTIFIER Search Tool / Sample Counting System
FEATURES: HIGH GAMMA SENSITIVITY MULTI-CHANNEL ANALYZER (MCA) WORKS WITH VARIETY OF PROBES RADIONUCLIDE LIBRARY TAILORED TO CUSTOMER REQUEST SIMULTANEOUSLY MEASURES ; DISPLAYS; ALARMS 1-3 SEPARATE DETECTORS
More informationSeries 65 Product Guide MAN 3036
Series 65 Product Guide MAN 3036 TABLE OF CONTENTS Page No. 1 Ionisation Smoke Detector... 1 1.1 Operating Principles:... 1 1.2 Product Codes... 2 1.3 Integrating Version:... 2 1.4 Options:... 2 1.5 Safety
More informationOperating instruction
Operating instruction FP102 / FP104 / FP106-2SO Conventional Fire Panels with 2 Sounder Outputs This document is only intended for customers of our fire panels and must not be copied or transfered to a
More informationApplication Note. Application Note for BAYEX
Application Note Application Note for BAYEX Preface This application note provides the user a more detailed description of the Bayesian statistical methodology available in Version 8.05 and above, of the
More informationFAP-420/FAH-420 Automatic Fire Detectors LSN improved version. Product Information
FAP-420/FAH-420 Automatic Fire Detectors LSN improved version en Product Information FAP-420/FAH-420 Table of Contents en 3 Table of Contents 1 Product Description 5 2 System Overview 6 2.1 Configuration
More informationRadon Detection Specialists, Inc.
Commercial Radon Survey Report Client: Community Consolidated School District 181 Site Address: Prospect School 130 N Prospect Clarendon Hills, IL 60514 Survey Date: April 23, 2012 to April 25, 2012 Initial
More informationFundamentals is subdivided into Sources of Radiation, Biological Effects, Mathematics, Chemistry, Physics, and Units and Terminology.
NRRPT Exam Review Class - an intensive 5-day class designed to prepare the candidate to successfully pass the NRRPT Exam. The course concentrates on the basic tools the candidate needs to successfully
More informationEffect of Contamination on the Sensitivity of Optical Scatter Smoke Sensors
Effect of Contamination on the Sensitivity of Optical Scatter Smoke Sensors Stephen Ellwood AW Technology Ltd, Earl Shilton, Leicestershire, United Kingdom Abstract A review on the limits to the compensation
More informationDosimeters/Survey meters
Dosimeters/Survey meters 40 Gracechurch Str., EC3V OBT, London, United Kingdom (24 Hour Customer Line) 0044 208 720 6926 RAD-ION (RI-02) Especially designed for the Detection of Pulsed (Golden Engineering)
More informationRadon Detection Specialists, Inc.
Commercial Radon Survey Report Client: Community Consolidated School District 181 Site Address: Walker School 120 S Walker Clarendon Hills, IL 60514 Survey Date: April 25, 2012 to April 27, 2012 Initial
More informationLARGE VOLUME HEMISPHERICAL NUCLEAR RADIATION DETECTOR CZT/500(S)
LARGE VOLUME HEMISPHERICAL NUCLEAR RADIATION DETECTOR CZT/500(S) Ganibu Dambis 26, P.O.Box 33 Riga, LV-1005, LATVIA Tel. (+371)6738-3947 Fax:(+371)6738-2620 office@bsi.lv www.bsi.lv CONTENTS INTRODUCTION...
More informationInjection with front ends open at the ESRF
Injection with front ends open at the ESRF P. Berkvens, P. Colomp and F. Bidault European Synchrotron Radiation Facility Abstract The ESRF is planning to introduce, beginning of 23, a new mode of operation
More informationPerformance Requirements for Monitoring Pulsed, Mixed Radiation Fields Around High-Energy Accelerators
Performance Requirements for Monitoring Pulsed, Mixed Radiation Fields Around High-Energy Accelerators D. Forkel-Wirth Wirth, S. Mayer, H.G. Menzel, A. Muller, T. Otto, M. Pangallo, D. Perrin, M. Rettig,
More informationNuclear Associates
Nuclear Associates 05-575 MiniMonitor III Multipurpose X and Gamma Ray Survey Meter Operators Manual February 2005 Manual No. 05-575-1 Rev. 2 2004, 2005 Fluke Corporation, All rights reserved. Printed
More informationRadioactivity dosimeter RD01. User's Manual
Radioactivity dosimeter RD01 User's Manual 2011 Contents Introduction 2 Technical specifications 4 How does RD01 work? 5 How to use RD01? 7 Power 10 How to carry out measures correctly? 11 Warranty 12
More informationQualification Testing of Nuclear High Voltage Splice (NHVS) Title Pages: 49. Report Number: EDR-5391 Rev. 0 06/15/05. Approved by: Signature: Date:
Energy Report EDR-5391 Qualification Testing of Nuclear High Voltage Splice (NHVS) Title Pages: 49 Qualification Testing of Nuclear High Voltage Splice (NHVS) Enclosures: Report Number: Date: EDR-5391
More informationRadon Detection Specialists, Inc. Love the Lungs You re With
630-325-4443 800-244-4242 kws@radonresults.com Commercial Radon Survey Report Client: Pleasantdale School District 107 8100 School Street La Grange, Illinois 60525 Survey Date: August 27, 2014 to August
More informationRadon Detection Specialists, Inc.
Commercial Radon Survey Report Client: Community Consolidated School District 181 Site Address: Monroe School 210 N Madison Hinsdale, IL 60521 Survey Date: May 7, 2012 to May 9, 2012 Initial Test RDS-R-002
More informationThe Modular System for Radioactivity Measurements FH 40 G/GL FHT 6020
Earphones The Modular System for Radioactivity Measurements For the connection to the separate earphone output. This enables the simultaneous operation of external FH 40 G probes and earphone. For the
More informationThe Modular System for Radioactivity Measurements FH 40 G/GL FHT 6020
The Modular System for Radioactivity Measurements FH 40 G/GL Digital Survey Meter FHT 6020 Display Unit Rugged and reliable Versatile multipurpose meter and area monitor Data logging Internal detector
More informationRadon Detection Specialists, Inc.
Commercial Survey Report Client: Community Consolidated School District 181 Site Address: Elm School 6010 S Elm St Hinsdale, IL 60521 Survey Date: April 9, 2012 to April 11, 2012 Initial Test RDS-R-002
More informationDated 15-Dec-2000; J. Schilz, subject to change
product data infrared sources preliminary! Infrared source 5 V, 115 ma, 3.17 mm diameter Features: - Incandescent infrared source up to 4.4 µm, - high reliability, - stable output, - short time constant.
More informationRAM GAM-1C Gamma Survey Meter TYPE TEST
Sunday, September 11, 2016 RAM GAM-1C Gamma Survey Meter TYPE TEST Compliance for ANSI N42.17A - 2003 American National Standard for Performance Specifications for Health Physics Instrumentation Portable
More informationCURRENT INDOOR RADON SITUATION IN LITHUANIA
CURRENT INDOOR RADON SITUATION IN LITHUANIA Rima Ladygienė, PhD Radiation Protection Centre LEGISLATION National policy on radon is based on the appropriate recommendations of International Commission
More informationRadon Detection Specialists, Inc.
Commercial Radon Survey Report Client: Community Consolidated School District 181 Site Address: The Lane School 500 N Elm St Hinsdale, IL 60521 Survey Date: April 17, 2012 to April 19, 2012 Initial Test
More informationHIGHLY SENSITIVE FOR NUCLEAR POWER PLANTS Real-Time Continuous Water Monitor
FEATURES: HIGHLY SENSITIVE FOR NUCLEAR POWER PLANTS WORLD S ONLY PAG-LEVEL WATER MONITOR MEASURES AT OR BELOW EPA/DHS PAG LEVELS (EPA s PROTECTIVE ACTION GUIDELINE LEVELS) REAL TIME, IN-LINE, CONTINUOUS
More informationCertificate of Completion
Love the Lungs You re With 630-325-4443 800-244-4242 Certificate of Completion Every parent or guardian is notified that this facility has performed radon measurements to ensure the health and safety of
More informationRadon Survey Summary Report
GWASANAETHAU IECHYD A DIOGELWCH - HEALTH AND SAFETY SERVICES ADRODDIAD REPORT Radon Survey Summary Report September 2010 Gwasanaethau Iechyd a Diogelwch Health and Safety Services, Penbre, Lon y Coleg.
More informationSurface Contamination Monitor. Operation Manual
Surface Contamination Monitor Operation Manual 1996, 2005, 2013, 2014, 2015 IMI-International Medcom, Inc. All rights reserved. Contents 1 Introduction...1 How the IMI Inspector Alert Detects Radiation...
More informationDetecting Radiation. Protection through Detection. February Animations in this training work best in Windows XP
Saudi Arabia : info_ksa@magusintl.com U.A.E : info_uae@magusintl.com Detecting Radiation Animations in this training work best in Windows XP February 2006 Why Detect Radiation Today? Medicine Imaging Cancer
More informationMolekule Produces No Ozone or Other Secondary Pollutants, and Actually Reduces Ozone in the Air.
Cover Sheet Molekule Produces No Ozone or Other Secondary Pollutants, and Actually Reduces Ozone in the Air. PURPOSE: Some earlier generation air purifiers, have been shown to release ozone or secondary
More informationRemote Gamma Imaging of High Dose Environments
Remote Gamma Imaging of High Dose Environments Paul Griffiths Copyright BIL Solutions Ltd 2006. The copyright in this document is wholly vested in BIL Solutions Ltd who reserve all intellectual property
More informationProducts & Solutions for Military Customers
Products & Solutions for Military Customers NUCLEAR MEASUREMENT SOLUTIONS FOR SAFETY, SECURITY & THE ENVIRONMENT U.S. Army photo by Sgt. 1st Class Adelita Mead WWW.CANBERRA.COM Products and Solutions for
More informationIBL 637 Cesium-137γ-ray machine 2016
IBL 637 Cesium-37γ-ray machine 206 Page of 2. Equipment identification IBL 637 Cesium-37γ-ray machine UMCG building 325 room 325.0549A 2. Goal The Cesium-37γ-ray machine is to be used by authorized researchers
More informationFlame Safeguards LFE10. Building Technologies HVAC Products
7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication
More informationUV - flame detector KLC 10 for oil -, gas- and dual fuel burners for intermittent burner operations
KLC 10 Technical information UV - flame detector KLC 10 for oil -, gas- and dual fuel burners for intermittent burner operations Description The KLC 10 is a compact UV flame detector, which has been developed
More informationSIEMENS ULTRAMAT 6 IR CARBON MONOXIDE ANALYZER METHOD VALIDATION FOR TESTING CARBON MONOXIDE IN NITROGEN, NF
2015 SIEMENS ULTRAMAT 6 IR CARBON MONOXIDE ANALYZER METHOD VALIDATION FOR TESTING CARBON MONOXIDE IN NITROGEN, NF FINAL APPROVAL REVISION #: 0 ISSUE DATE: December 4, 2015 PAGE: 1 of 13 This Methods
More informationUnderstanding total measurement uncertainty in power meters and detectors
Understanding total measurement uncertainty in power meters and detectors Jay Jeong, MKS Instruments. Inc. INTRODUCTION It is important that users of calibrated power meters and detectors understand and
More informationPortable Alpha/Beta Continuous Online Air Monitor (CAM)
Aer 5000 Desktop Portable Alpha/Beta Continuous Online Air Monitor (CAM) The Aer5200 monitors the ambient air continuously to detect airborne radioactive aerosols (LLRD). Typical application fields are
More informationRadiation Alert Area Monitor
Radiation Alert Area Monitor S.E. International, Inc. P.O. Box 39, 436 Farm Rd. Summertown, TN 38483 USA 1.800.293.5759 931.964.3561 Fax: 1.931.964.3564 www.seintl.com radiationinfo@seintl.com Contents
More informationFAP-420/FAH-420 Automatic Fire Detectors LSN improved version
Fire Alarm Systems FAP-420/FAH-420 Automatic Fire Detectors LSN improved version FAP-420/FAH-420 Automatic Fire Detectors LSN improved version ombination of optical, thermal and chemical sensors with intelligent
More informationASTM E Standard Practice for Radiological Response. ASTM E Standard Practice for Radiological Response
ASTM E2601-08 Standard Practice for Radiological Response Presentation Format Standard is for guidance to support local AHJ plan development Utilize several scenarios to present and discuss concepts in
More informationCertificate of Completion
Love the Lungs You re With 630-325-4443 800-244-4242 Certificate of Completion Every parent or guardian is notified that this facility has performed radon measurements to ensure the health and safety of
More informationUsers Manual. LAURUS Systems, Inc. - Ph: Fax:
Users Manual LAURUS Systems, Inc. - Ph: 410-465-5558 - Fax: 410-465-5257 - www.laurussystems.com Introduction The rad-d is a security and inspection system that detects emissions from radioactive material.
More informationNuclear Products Requalification Testing Phase 2. Title Pages: 113. Report Number: EDR-5389 Rev. 0 12/10/2004. Approved by: Signature: Date:
Energy Report EDR-5389 Nuclear Products Requalification Testing Phase 2 Title Pages: 113 Nuclear Products Requalification Testing Phase 2 Enclosures: Report Number: Date: EDR-5389 Rev. 0 12/10/2004 Prepared
More informationAPES- Environmental Effects of Radiation Laboratory Activity. Purpose: To see the effect of the seed irradiation on germination and plant growth
APES- Environmental Effects of Radiation Laboratory Activity Purpose: To see the effect of the seed irradiation on germination and plant growth Background: The irradiation of seeds may cause a sudden and
More informationA FIRST RESPONDERS GUIDE TO PURCHASING RADIATION PAGERS
EML-624 A FIRST RESPONDERS GUIDE TO PURCHASING RADIATION PAGERS FOR HOMELAND SECURITY PURPOSES Paul Bailey Environmental Measurements Laboratory U.S. Department of Homeland Security 201 Varick Street,
More informationPhoto Beam 5000/3000 Series Heater. en Installation Guide
Photo Beam 5000/3000 Series Heater en Installation Guide Photo Beam 5000/3000 Series Heater Table of Contents en 3 Table of contents 1 Introduction 4 1.1 About documentation 4 2 General description 5
More informationRelevant Radon properties
Relevant Radon properties Radon is a natural gas and has a half life of 3.8 days. This means that if a box was full of radon gas, half of it would have decayed into something else after 3.8 days. It has
More informationSECTION 1: STARTING 1.1 UNPACKING AND INSPECTION
SECTION 1: STARTING 1.1 UNPACKING AND INSPECTION Upon receipt of the laser system, inspect the shipping containers for gross external damage. Unpack the unit and inspect for internal damage. If any damage
More informationDepartment of State Health Services
Page I of 10 Pursuant to the Texas Radiation Control Act and Texas (Agency) regulations on radiation, and in reliance on statements and representations heretofore made by the licensee, a license is hereby
More informationFlame Safeguards LFE10. Building Technologies HVAC Products
7 71 Flame Safeguards LAE LFE Flame safeguards for burners with intermittent operation The LAE is used for the supervision and indication of oil flames The LFE is used for the supervision and indication
More informationCertificate of Completion
Love the Lungs You re With 630-325-4443 800-244-4242 Certificate of Completion Every parent or guardian is notified that this facility has performed radon measurements to ensure the health and safety of
More informationRadon and Thoron Measurements at Special Underground Circumstances
Radon and Thoron Measurements at Special Underground Circumstances Tibor Kovács a*, Norbert Kávási b, Csaba Németh c, János Somlai a, Tamás Vigh d, Gábor Szeiler a, and Shinji Tokonami e, Hiroyuki Takahashi
More informationMODEL 3216 ROOF MOISTURE GAUGE
Instruction Manual MODEL 3216 ROOF MOISTURE GAUGE Troxler Electronic Laboratories, Inc. 3008 Cornwallis Rd. P.O. Box 12057 Research Triangle Park, NC 27709 Phone: 1.877.TROXLER Outside the USA: +1.919.549.8661
More informationSettings and Maintenance of the CombinAir
Atmos CombinAir Settings and Maintenance of the CombinAir Issue 13.8.10 Operation and commissioning: The control unit on the front of the CombinAir is used to adjust the settings during commissioning.
More informationSERIES 65 ENGINEERING PRODUCT GUIDE
SERIES 65 ENGINEERING PRODUCT GUIDE Wide voltage conventional detectors Series 65 incorporates well-proven sensing technologies, including an IC based on that used in XP95 analogue addressable detectors.
More informationConsultation Draft. Issue 2. Good Practice Guide No. 29. The Examination, Testing and Calibration of Installed Radiation Protection Instruments
Good Practice Guide No. 29 The Examination, Testing and Calibration of Installed Radiation Protection Instruments Peter Burgess, Lynsey Keightley, Clare Lee, Max Pottinger, Mike Renouf, David Williams.
More informationTrials of Vexo inhibitor in domestic central. heating systems
Trials of Vexo inhibitor in domestic central heating systems by Rayner Mayer d25.03.2013 Executive summary A new type of inhibitor has been formulated by VEXO International to improve the efficiency of
More informationBeam Loss Position Monitoring with Optical Fibres at DELTA
Beam Loss Position Monitoring with Optical Fibres at DELTA Frank Rüdiger M. Körfer (DESY) W. Göttmann (HMI Berlin) G. Schmidt (DELTA) K. Wille (DELTA) 24. June 2008 Frank Rüdiger 1 Table of Content 1.
More informationOral Syringe Product Stability &
Oral Syringe Product Stability & Print Durability Comparison The Comar Oral Syringe dispenser design has proven to be the most stable product for ease of use and legibility when exposed to a series of
More informationSVG 2 and Probes. Innovation with Integrity. The new Generation of Semiconductor Radiation Meters and Handheld Radiation Detection Probes
SVG 2 and Probes The new Generation of Semiconductor Radiation Meters and Handheld Radiation Detection Probes Innovation with Integrity Defence CBRNE General Specification Alarm thresholds for the dose
More informationEnergy and Angular Responses of the Criticality Accident Alarm System Using Current-mode-operated Scintillation Detector
Energy and Angular Responses of the Criticality Accident Alarm System Using Current-mode-operated Scintillation Detector N. Tsujimura 1, T. Yoshida 1 and S. Mikami 1 1 Japan Nuclear Cycle Development Institute,
More information