Fire Systems Maintenance and Fire Detection Systems. Dwayne Smith Fire Protection Engineer

Size: px
Start display at page:

Download "Fire Systems Maintenance and Fire Detection Systems. Dwayne Smith Fire Protection Engineer"

Transcription

1 Fire Systems Maintenance and Fire Detection Systems Dwayne Smith Fire Protection Engineer

2 Introduction Overview of Regulatory Framework Act, Regulations and Codes Fire Protection Maintenance AS Tips and Tricks for maintenance FAQ Fire Detection System Design AS Unwanted alarm mitigation EWIS and Evacuation strategies

3 AS Current revision released in December 2012

4 Regulatory Framework QLD Building Act QLD Building Regulations QLD Development Code National Construction Code Series (BCA) Design Standards (e.g AS1670) Maintenance Standards - AS1851

5 Obligations Not required to comply with current design standards. Installation standards apply. Required to comply with the current maintenance standards.

6 Critical Defect? AS1851 now defines the level of a defect

7 Test Frequencies

8 Interface Testing Historically not captured very well, and in some cases not established at all Requires the testing of the interfaces between services, i.e smoke exhaust, stair press etc. Not intended as a commissioning test or retest.

9 Hospital Interface Testing Application of interface testing in a hospital can involve a significant number of services. Mechanical (stair press, smoke exhaust) Door releases Make up air Security BMS Public Address Gas shut off solenoids Pneumatic Tube

10 Testing Regimes It is often difficult to find records of testing other than weekly or monthly. 6 monthly, annual or more are rare. Instances in the past of significant sites in QLD with hydrant pipework which had not been hydrostatically or boost tested for 30 years. (5 yearly requirement). Another instance of a building which had a sprinkler system with no water in it for around 50 years. Annual testing would have picked this up.

11 Common Failures Underground pipework can deteriorate over time. Type B copper and Firelite were popular in the 1980 s, may not meet current requirements. Depending on water hardness, pipework may calcify an internal build up of calcium restricting flow. Water authorities are turning down water pressures in street mains to conserve water. From this, some systems no longer meet their requirements.

12 Internal conditions

13 Tips Consider an investigation into the underground pipework quality, and have it tested. Note, it may contain asbestos! Make sure you have a good clear block plan for sprinklers, detection and hydrants. Make sure that everything is labelled and corresponds with the block plan. Consider access safety to maintenance staff and QFRS is applicable, even though AS1851 doesn t mention it. Consider ESD initiatives hydrant and sprinkler test water can be captured and reused on site While we would recommend compliance with current standards, don t feel pressured into spending big money if you don t need to.

14 AS1670 Standard for fire detection and alarm systems (or is it?) AS1668, the standard for smoke control also applies. In hospitals, AS (EWIS) is applicable as well. National Construction Code series drives the requirements for AS1670 detection.

15 National Construction Code Class 9a hospitals require full smoke detection to AS1670 regardless of height or size. The rise in storeys of a building drives the AS1668 fan control requirements. As an aside, sprinklers are required in any building greater than 25m in effective height, and may be provided in lieu of zone smoke control in a building with a rise in storeys of 3 or more. A full Emergency Warning and Intercommunication System (EWIS) is required for any hospital over 2 storeys or a floor area of more than 1000m 2

16 Detector Types Typical hospital detection types: Smoke Photoelectric or Ionisation type Heat fixed temperature or rate of rise Aspirated (Vesda) for critical areas such as server rooms, or where access is limited Fire Sprinklers Other detection devices covered by AS1670: Infrared Beam detection Linear Heat detection cable Other detection? Video smoke detection

17 System Types Two main types Addressable or Conventional In addressable systems, each detector has a unique address where it can be pinpointed by the FIP In conventional systems detectors are grouped into zones, identifies on the FIP as a zone rather than a detector. Conventional is generally being replaced with addressable.

18 General Intent of AS1670 Fire detection throughout the building every room, switchboards, lift shafts, risers. Additional fire detection is required in air handling units, stair press fans and the like Alarm tones are to be audible throughout

19 Specific Case Operating Theatre No special requirements under AS1670. A situation occurred in a hospital in New Zealand where a fire occurred in a plant room serving the theatre. Smoke was picked up by the Air Conditioning and dumped on top of the patient. As the smoke was cooled by the air, it didnt set off any detection in the room. There was no detection in the ventilation system. Patient had to be relocated mid operation once a manual alarm was raised.

20 Unwanted Alarm Mitigation Unwanted alarms are a nuisance to both the occupants and the fire brigade it ties up valuable resources. Smoke detectors can be triggered by dust, steam, or even invisible products of combustion. Areas in which false alarms are predicted (e.g kitchens) another detection device can be used instead of smoke detection usually a heat detector. The NCC considers a sprinkler to be the equivalent of a heat detector as they operate the same. In areas outside of patient care, it is possible to just delete a smoke detector altogether but note you lose the addressability function.

21 Emergency Warning and Intercommunication Systems Evacuation strategies in hospitals are a top priority due to the difficulty of mobilising patients. An EWIS allows full customisation of the system to maximise occupant discharge. This can be arranged such that alert and evacuate tones cascade radially occupants in the adjacent compartment are preparing to evacuate while the compartment of fire origin is evacuating. Warden intercommunication points, strobe lights, mimic panels and break glass alarms are also provided. Additional flexibility is afforded in the NCC for a reduction in alarm tone sound levels to suit the trauma of the patients.

22 Evacuation Strategy - Ipswich

23 Summary AS1670 drives the locations of detection and spacing requirements for full coverage. All of the building must be protected. Determines the requirements for detection type NCC permits the substitution of detectors to mitigate unwanted alarms AS drives system requirements for a full EWIS to allow for orderly evacuation.

2004 AUSTRALIAN STANDARDS UPDATE

2004 AUSTRALIAN STANDARDS UPDATE 2004 AUSTRALIAN STANDARDS UPDATE PREPARED by Peter Parsons Chairman of SAI FP-002 Chairman of ISO TC 21/SC 3 TSP Strategic Product Management Kjell Jawerth Chairman FPA Aust. TC/2 Member SAI FP-002 TSP

More information

FIRE AND EVACUATION PLAN

FIRE AND EVACUATION PLAN FIRE AND EVACUATION PLAN For The Body Corporate for PROMINENCE 13-21 Bombery Street Cannon Hill QLD 4170 Community Titles Scheme 48433 Complied By: Date of inspection: 28/6/2017 Inspector name: Scott Thomson

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

Building Consent Application Compliance Schedule Information

Building Consent Application Compliance Schedule Information Private Bag 9023 Whangarei 0148 New Zealand T: 09 430 4200 0800 WDC INFO 0800 932 463 F: 09 438 7632 W: www.wdc.govt.nz E: mailroom@wdc.govt.nz Building Consent Application Compliance Schedule Information

More information

4 August Islington Fire Protection Transpower NZ Limited

4 August Islington Fire Protection Transpower NZ Limited 4 August 2011 Islington Fire Protection Contents 1. Introduction...1 General Approach...2 2. General Notes...3 3. Description of Building Areas...4 Use, Layout, Fire Load, Criticality and Division...4

More information

AS Fire detection, warning, control and intercom systems System design, installation and commissioning. Presented by: DAVID ISAAC

AS Fire detection, warning, control and intercom systems System design, installation and commissioning. Presented by: DAVID ISAAC AS 1670.1 2015 Fire detection, warning, control and intercom systems System design, installation and commissioning Presented by: DAVID ISAAC Presentation Content NEW SECTION 7 RELOCATION OF SMOKE DETECTION,

More information

SAQCC FIRE D&GS TRAINING SUB COMMITTEE COURSE CURRICULUM

SAQCC FIRE D&GS TRAINING SUB COMMITTEE COURSE CURRICULUM SAQCC FIRE D&GS TRAINING SUB COMMITTEE COURSE CURRICULUM COURSE ORIGINATOR Fire Detection Principles Nichola Allan DATE 23rd August 2013 Amendment 1 5th October 2013 Technical changes - Issued Amendment

More information

Certification Assessment Instrument and Guidelines

Certification Assessment Instrument and Guidelines Certification Instrument Full compliance with BCA 96 will ensure passing 19 for Section 1 Do not need 100 to pass 1 SECTION 1 SAFETY (25 POINTS) Residential Fire Sprinkler System Not required to pass Section

More information

Baseline Data Required for AS

Baseline Data Required for AS Baseline Data Required for AS 1851-2012 Name: Brett Dundules Position: Technical Officer Organisation Fire Protection Association Australia Introduction Brief History of AS 1851-2012 Introduction of Baseline

More information

SCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY

SCHEDULE. Essential Safety Measures taken from Schedule 9 of the Building Regulations PART 1 BUILDING FIRE INTEGRITY SCHEDULE Essential s taken from Schedule 9 of the Building Regulations 2006 43 PART 1 BUILDING FIRE INTEGRITY 1 Building elements required to satisfy prescribed fire-resistance levels 2 Materials and assemblies

More information

St. Vincent s Health System Page 1 of 6

St. Vincent s Health System Page 1 of 6 St. Vincent s Health System Page 1 of 6 TITLE: Fire Plan Code Red FACILITY: St. Vincent s East FUNCTION: ORIGINATING DEPT: HOSPITAL SHARED POLICY? EFFECTIVE DATE: _X Yes No DOCUMENT NUMBER: 801 ORIGINATION

More information

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD Fire alarm and emergency power SPRINKLER HEAD 1 Alert signal Alarm signal Fire detector Heat detector Smoke detector Smoke alarm 1. Detector locations 1. Fire detector locations (3.2.4.11) 2. Smoke detector

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

Detection, and Suppression Systems

Detection, and Suppression Systems Fire Detection, Protection, ti and Suppression Systems Objectives (1 of 5) Explain why all fire fighters should have a basic understanding of fire protection systems. Describe the basic components and

More information

BUILDING CODE ACCESS CONSULTING ESSENTIAL SERVICES

BUILDING CODE ACCESS CONSULTING ESSENTIAL SERVICES Essential Safety Measures - Fire & Smoke Control of Mechanical Services Antony Rickards Building Compliance BUILDING CODE ACCESS CONSULTING ESSENTIAL SERVICES Essential Safety Measures What we will cover.

More information

Smoke Alarm User s Manual

Smoke Alarm User s Manual V-MUL-007-D(A0) Smoke Alarm User s Manual Please read and save this manual PHOTOELECTRIC SMOKE ALARM( HUSH FEATURE) MODEL: VST-S588H Class II Apparatus Photoelectric smoke alarms are generally more effective

More information

Scope of Section 2. AS vs. Application Issues. Schedules & Log- Contents. Books

Scope of Section 2. AS vs. Application Issues. Schedules & Log- Contents. Books Contents Scope of Section 2 Application Issues AS 1851-1997 vs 2005 Schedules & Log- Books Scope of AS1851 Section 2 Review and rewrite of all sprinkler maintenance activities AS 1851.3 1997 becomes General

More information

Approved Document for New Zealand Building Code Warning Systems Clause F7 Third Edition

Approved Document for New Zealand Building Code Warning Systems Clause F7 Third Edition Approved Document for New Zealand Building Code Warning Systems Clause F7 Third Edition Prepared by the Building Industry Authority This Approved Document is prepared by the Building Industry Authority,

More information

Fire safety procedure

Fire safety procedure Fire safety procedure Review date: October 2020 Responsible (s): Health and Safety Applicable to Staff: Accessible to Students: Accessible to general public: (including clients) Yes Yes Yes 1 Contents

More information

FIRE SAFETY POLICY Page 1 of 15 Reviewed: October 2017

FIRE SAFETY POLICY Page 1 of 15 Reviewed: October 2017 Page 1 of 15 Policy Applies to: All Mercy staff Compliance by the occupants of Marinoto Clinic, Mercy Care East, Allied Health personal, credentialed specialists, patients and visitors will be facilitated

More information

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

NFPA 101 Code Update from 2012 Edition to the 2015 Edition NFPA 101 Code Update from 2012 Edition to the 2015 Edition Presented by: Gary Furdell AHCA Fire Protection Specialist 1 2 2012 Update to 2015 Chapter 18 New Health Care Occupancies 4 18.1.3.2 Atrium walls

More information

Firefighting operations on fire control centres F5-09 GD

Firefighting operations on fire control centres F5-09 GD DESIGNER S GUIDE Firefighting operations on fire control centres F5-09 GD Introduction Purpose Scope The purpose of this guideline is to provide a consistent Fire and Emergency New Zealand position on

More information

FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA

FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA 93 FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA INTRODUCTION 94 Legal requirements for the protection of firefighters Requirements of Building Act Fire Prevention Act Technical Guidelines OIB

More information

Firefighting operations on fire alarm panels F5-04 GD

Firefighting operations on fire alarm panels F5-04 GD DESIGNER S GUIDE Firefighting operations on fire alarm panels F5-04 GD Introduction Alarm system devices Alarm system types A fire alarm system consists of one or more devices and/or control mechanisms

More information

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles

More information

Code of Practice for the Management of Overhead Corridor Ducts in the Main Building.

Code of Practice for the Management of Overhead Corridor Ducts in the Main Building. Issue Status: Issue No. Date Issued Comments 1. 14/08/2013 DRAFT 2. 15/08/2013 UPDATED FOLLOWING MEETING (15/08/13) 3. 19/08/2013 UPDATED TO INCORPORATE EMAIL COMMENTS (16/08/13) 4. 24/09/2013 ACCESS OF

More information

Innovative protection that combines power and flexibility

Innovative protection that combines power and flexibility Innovative protection that combines power and flexibility Desigo Fire Safety Modular outpaces industry standards and includes cutting-edge detection and communication capabilities usa.siemens.com/desigo-fs-modular

More information

Draft FPA Australia Technical Specification for Public Comment FPAA101H DRAFT

Draft FPA Australia Technical Specification for Public Comment FPAA101H DRAFT Draft FPA Australia Technical Specification for Public Comment FPAA101H These preliminary pages provide information on the background to this Technical Specification, the system it covers and the context

More information

Maintenance of Fire Systems

Maintenance of Fire Systems Maintenance of Fire Systems Duty Holder Facilities Manager Responsible Person By John Briggs All Fire Facilities, equipment, systems and devices are required by law to be subject to a suitable system of

More information

Purpose of Emergency Response Program Emergency Response Team / Leader Evacuation Procedures Building Life Safety System Virtual Evacuation Building

Purpose of Emergency Response Program Emergency Response Team / Leader Evacuation Procedures Building Life Safety System Virtual Evacuation Building Purpose of Emergency Response Program Emergency Response Team / Leader Evacuation Procedures Building Life Safety System Virtual Evacuation Building Tour Questions and Answers To prepare designated office

More information

Workplace Guidelines

Workplace Guidelines Occupational Health & Safety Life Saving Victoria Workplace Guidelines A Basic Introduction to Guidelines in Lifesaving Clubs for: Emergency Evacuation Plans & Procedures Hot Work & Welding Electrical

More information

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE

More information

Compliance Document for New Zealand Building Code Clause F7 Warning Systems Third edition

Compliance Document for New Zealand Building Code Clause F7 Warning Systems Third edition Compliance Document for New Zealand Building Code Clause F7 Warning Systems Third edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building

More information

HART XL High Sensitivity Smoke Detection

HART XL High Sensitivity Smoke Detection High Sensitivity Smoke Detection The Hart XL High Sensitivity Smoke Detection system (HSSD) is an aspirating fire detection system designed to give very early indication of an incipient fire condition.

More information

Releasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.

Releasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd. Releasing Systems Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd. Releasing Systems What is a releasing system? System designed to detect a fire Causes release of an extinguishing system in

More information

University of London

University of London University of London Senate House and Stewart House Fire safety arrangements Contents 1. Introduction p.2 2. Fire Risk Assessment documentation p.2 3. Action to be taken by a person discovering a fire

More information

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006)

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) 1. INTRODUCTION 1.1 Essential Safety Measures Defined Essential Safety Measures (previously called essential services) are

More information

p. vi, References p. v, Contents p. 7, References pp. 7-8, References p. 5, Contents p. 7, References p. 9, Definitions p. 13, 1.2.

p. vi, References p. v, Contents p. 7, References pp. 7-8, References p. 5, Contents p. 7, References p. 9, Definitions p. 13, 1.2. Compliance Document for New Zealand Building Code Clause F7 Warning Systems Third Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building

More information

Advanced Fire Alarm Systems Training Program Outline (5 Day)

Advanced Fire Alarm Systems Training Program Outline (5 Day) Advanced Fire Alarm Systems Training Program Outline (5 Day) Day 1 Prescriptive and Performance-Based Design Understand the methodology in accessing the threat of fire within a structure. Know the difference

More information

Martin Huber 26September 2017 F&G SOLUTIONS FOR THE PROCESS INDUSTRY

Martin Huber 26September 2017 F&G SOLUTIONS FOR THE PROCESS INDUSTRY Martin Huber 26September 2017 F&G SOLUTIONS FOR THE PROCESS INDUSTRY Agenda 1 Challenges in the Process Industry International codes and standards F&G in an industrial Facility Honeywell s industrial F&G

More information

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670.

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670. AS 1670.1 2004 (Incorporating Amendment No. 1) AS 1670.1 2004 Australian Standard Fire detection, warning, control and intercom systems System design, installation and commissioning Part 1: Fire This Australian

More information

POLICY. Code Announcement means an announcement (e.g. page or strobe light, verbal notification) to commence a Fire Drill without an audible alarm.

POLICY. Code Announcement means an announcement (e.g. page or strobe light, verbal notification) to commence a Fire Drill without an audible alarm. POLICY Number: 7311-95-001 Title: Fire Drill Policy Authorization [ ] President and CEO [ X] Vice President, Finance and Corporate Services Source: Director, Enterprise Risk Management Cross Index: Date

More information

Loss Prevention Standards

Loss Prevention Standards Introduction Fire compartmentation is an essential part of an effective fire safety design of a building. The primary objective of fire compartmentation or passive fire protection is to prevent a building

More information

Following are the systems proposed as per NBC & Local Fire Authority:

Following are the systems proposed as per NBC & Local Fire Authority: 1. OBJECTIVES AND STRATEGIES OF THE FIRE PROTECTION DESIGN This report describes the design parameters, system requirements of fire protection system for mixed occupancy (Assembly + Business) building

More information

Scope. Warning sounders except specific requirements. Intercom Systems for Emergency Purposes. Sound Systems for Emergency Purposes

Scope. Warning sounders except specific requirements. Intercom Systems for Emergency Purposes. Sound Systems for Emergency Purposes Scope Section 6 covers all Control and Indicating Equipment including Local Alarm systems. Section 6 also covers all detectors and input/output devices, including Occupant Warning sounders except specific

More information

FIRE SAFETY 2013 ANNUAL REPORT. Author: Senior Fire Safety Advisor Contact Details for further information: Frank Barrett

FIRE SAFETY 2013 ANNUAL REPORT. Author: Senior Fire Safety Advisor Contact Details for further information: Frank Barrett AGENDA ITEM 4.1 FIRE SAFETY 2013 ANNUAL REPORT Executive Lead: Director of Planning Author: Senior Fire Safety Advisor Contact Details for further information: Frank Barrett 02920742292 SITUATION This

More information

FIRE PLAN. In order to assure the safety of patients, visitors and staff, a standard response to fire or the potential of fire is required.

FIRE PLAN. In order to assure the safety of patients, visitors and staff, a standard response to fire or the potential of fire is required. FIRE PLAN PURPOSE In order to assure the safety of patients, visitors and staff, a standard response to fire or the potential of fire is required. This fire plan sets out the standard response for all

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES

CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES CURTIN UNIVERSITY PROJECT DELIVERY GUIDELINES FIRE SERVICES TECHNICAL REQUIREMENTS 000330 Details of revisions Level Details Date Initial 1 Document created via PDG process from 000222 Knowledge - Fire

More information

Safety Engineering. Fire Protection Systems and Life Safety Systems

Safety Engineering. Fire Protection Systems and Life Safety Systems Safety Engineering Fire Protection Systems and Life Safety Systems Introduction 2 A key aspect of fire protection is to identify a developing fire emergency in a timely manner, and to alert the building's

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information Charles M. LeMaistre PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

Sprinkler Permit Applications

Sprinkler Permit Applications REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations

More information

Establishing the Risk Basis of Building Size Limits

Establishing the Risk Basis of Building Size Limits Establishing the Risk Basis of Building Size Limits A look at the history of development of our building codes and safety opportunities to facilitate wood design initiatives. Presented on January 27, 2015

More information

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617)

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617) Unwanted Fire Alarms Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA 02169-7471 (617) 984-7463 mahrens@nfpa.org Unwanted fire alarms, however they are defined, are a problem

More information

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites

More information

EC 5.10 FIRE PREVENTION MANAGEMENT

EC 5.10 FIRE PREVENTION MANAGEMENT EC 5.10 FIRE PREVENTION MANAGEMENT The organization manages fire safety risks. 1 The organization develops and maintains a written management plan describing the processes it implements to effectively

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

Client Advisory Note June 2015:

Client Advisory Note June 2015: Client Advisory Note June 2015: Topics: 1. Substantially revised Fire Alarm and Smoke Control Standards for proposed adoption in NCC Volume One BCA 2016; 2. Independent review of Building Professionals

More information

3.1 Introduction. 3.1 Introduction

3.1 Introduction. 3.1 Introduction DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G and Element Z for technical

More information

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey.

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey. Documentation required by the Hospital Accreditation program Life Safety (LS) and selected Environment of Care (EC) standards is presented in the following pages. These documents will be reviewed by the

More information

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!

More information

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Contents Contents 1. INTRODUCTION... 3 1.1 Purpose...3 1.2 Definitions....3 Premises Management...

More information

Plan Review Check List Fire Alarm System

Plan Review Check List Fire Alarm System Plan Review Check List Fire Alarm System EXCELSIOR FIRE DISTRICT 241OO SMITHTOWN ROAD SHOREWOOD, MN 55331 Alarm system must be installed according to NFPA 72, 2010 Edition, National Fire Alarm and Signaling

More information

technical specification smoke venting systems

technical specification smoke venting systems technical specification smoke venting systems An Introduction to FDS FDS sets the standards the rest of the industry follows Providing a complete service for all of your smoke ventilation system needs.

More information

Firefighting operations on automatic sprinklers systems F5-06 GD

Firefighting operations on automatic sprinklers systems F5-06 GD DESIGNER S GUIDE Firefighting operations on automatic sprinklers systems F5-06 GD Introduction When to use Scope Use this chapter to provide a consistent Fire and Emergency New Zealand position on design

More information

EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL

EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL EN54 Part 23 Made Easy CPD PRESENTED BY SIMON ADAMS GENT BY HONEYWELL EN54 Part 23 Intent Standardise output levels from Visual Alarm Devices Improve designs & safety through ensuring enough light is generated

More information

MX4428. Addressable Fire Alarm System. Features. Advantages & Options

MX4428. Addressable Fire Alarm System. Features. Advantages & Options MX4428 Addressable Fire Alarm System Features // Supports MX Series devices including the 850 Series Generation 6 Multi-Sensor analogue addressable detector range // SMARTSENSE and MX FASTLOGIC (fuzzy

More information

Terminal & Building Emergency Evacuation Induction

Terminal & Building Emergency Evacuation Induction The following 20 questions are multiple choice questions. You are asked to circle the answer you believe is correct. Please ensure your name and contact details as below are completed. By signing this

More information

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett

Fire Protection System and Life Safety Evaluation of Building X. Anthony W. Sublett Fire Protection System and Life Safety Evaluation of Building X Presented by Anthony W. Sublett Culminating Project Master of Science in Fire Protection Engineering California Polytechnic State University

More information

AS 2419 OVERVIEW OF PROPOSED CHANGES. Gary Nenadovich Director G N Consulting

AS 2419 OVERVIEW OF PROPOSED CHANGES. Gary Nenadovich Director G N Consulting AS 2419 OVERVIEW OF PROPOSED CHANGES Gary Nenadovich Director G N Consulting Disclaimer FPA Australia's policy is one of continuous improvement, details of products, procedures or methods described within

More information

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7 AGENDA: Life Safety Code Referenced Publications Overview Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99

More information

COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE

COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE 100130 Description The first part of the course presents the requirements for fire alarm systems. It describes the buildings

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Carr House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General description

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL GK FIRE & SECURITY LTD, UNIT 1 GREBE RD, PRIORSWOOD IND EST, TAUNTON, TA2 8PZ

FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL GK FIRE & SECURITY LTD, UNIT 1 GREBE RD, PRIORSWOOD IND EST, TAUNTON, TA2 8PZ BS5839-1 : 2013 FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL Forward It is recommended that this logbook be maintained by a relevant member of the premises management, to ensure that every entry

More information

RMS-I-DE-01 Smoke Detector

RMS-I-DE-01 Smoke Detector RMS-I-DE-01 Smoke Detector 2012 CONTEG, spol. s r.o. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted or stored in any retrieval system of any nature,

More information

Smoke Alarm User Manual

Smoke Alarm User Manual Smoke Alarm User Manual Model number: GS528A Ref:ST528A Thank you for purchasing our smoke alarm. Please take a few minutes to read the user s manual thoroughly and familiarize yourself and your family

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

Fire safety systems. Behaviour of fires

Fire safety systems. Behaviour of fires Fire safety systems The objective of the BCA Housing Provisions (Volume 2) with respect to Class 1 buildings (residential) and fire, is to safeguard occupants from illness or injury, to avoid the spread

More information

False Alarm Management. Graham Simons FIA Technical Manager

False Alarm Management. Graham Simons FIA Technical Manager False Alarm Management Graham Simons FIA Technical Manager False Alarm Management Smoke alarms and smoke detectors sensitive to airborne particles and may not discriminate smoke & dust False alarms are

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Practice Advisory 18: Fire safety design for tall buildings

Practice Advisory 18: Fire safety design for tall buildings Practice Advisory 18: Fire safety design for tall buildings It s important that reliable and resilient fire design features are used in the design of tall buildings. This advisory highlights the specific

More information

Fire Safety Policy & Fire Safety Management System Version October 2013 Emergency Evacuation Procedures

Fire Safety Policy & Fire Safety Management System Version October 2013 Emergency Evacuation Procedures Emergency Evacuation Procedures Contents 1. Raising the fire alarm 2. Schedule of patient evacuation 3. Designated fire officer roles 3.1 The Fire Team Leader 3.2 Security personnel 3.3 Shift Technicians

More information

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata)

2012 International Building Code Errata (Portions of text and tables not shown are unaffected by the errata) [F]TABLE 903.2.11.6 ADDITIONAL REQUIRED SUPPRESSION SYSTEMS SECTION SUBJECT 402.10 402.5 Covered and open mall buildings (Portions of table not show remain unchanged) 2012 International Building Code SEVENTH

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

Draft FPA Australia Technical Specification for Public Comment FPAA101D DRAFT

Draft FPA Australia Technical Specification for Public Comment FPAA101D DRAFT Draft FPA Australia Technical Specification for Public Comment FPAA101D These preliminary pages provide information on the background to this Technical Specification, the system it covers and the context

More information

KING S HOUSE SCHOOL FIRE RISK MANAGEMENT POLICY & PROCEDURES

KING S HOUSE SCHOOL FIRE RISK MANAGEMENT POLICY & PROCEDURES Member of staff responsible : Headmaster Date of policy review : June 2018 Date of next review : June 2019 Approved by Governors : June 2018 KING S HOUSE SCHOOL FIRE RISK MANAGEMENT POLICY & PROCEDURES

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

HART XL High Sensitivity Smoke Detection

HART XL High Sensitivity Smoke Detection High Sensitivity Smoke Detection Hart XL High Sensitivity Smoke Detection (HSSD) TM is a smoke detection system that is simple to install, commission, service and use yet remains brilliantly capable in

More information

Hi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety

Hi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety Hi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety manager. As the appointed fire safety manager for a premise,

More information

Clofield Limited. Product Data Sheets. Paging System. Care Call. Preventative monitoring for homecare... Wireless alerting system for Carers

Clofield Limited. Product Data Sheets. Paging System. Care Call. Preventative monitoring for homecare... Wireless alerting system for Carers Preventative monitoring for homecare... Wireless alerting system for Carers Care TM Call Clofield Limited Care Call Paging System Product s Pager CCP3A-2217-EU Care Call Pager Unit Lightweight & discreet,

More information

and Aspirating Smoke Detection

and Aspirating Smoke Detection An Introduction to and Aspirating Smoke Detection 1 An Intro to FAAST and Aspirating Smoke Detection Agenda System Sensor Overview Aspirating Smoke Detection Overview of FAAST Devices Installations of

More information

Some information I have read tells me to evacuate immediately in case of fire. Fire In Your Residential Building. To Go?? To Stay??

Some information I have read tells me to evacuate immediately in case of fire. Fire In Your Residential Building. To Go?? To Stay?? Fire In Your Residential Building To Go?? or To Stay?? Your safety depends on the right decision. Your fire safety is your responsibility! If you live in an apartment or condominium, your safety also depends

More information

Chapter 5. Energy Conservation & Fire Safety

Chapter 5. Energy Conservation & Fire Safety Chapter 5 Energy Conservation & Fire Safety For internal circulation of BSNL only Page 1 Introduction: ENERGY CONSERVATION The ever-increasing cost of energy (i.e. Electrical power & diesel) has contributed

More information