Installation Smoke Detector ELQZ , GOLD

Size: px
Start display at page:

Download "Installation Smoke Detector ELQZ , GOLD"

Transcription

1 Installation Smoke Detector ELQZ , GOLD General The ELQZ smoke detector is used for measuring any smoke present in ventilation ducts. It consists of an ionising detector mounted in an adaptor system where both the tube and enclosure are designed for optimum airflow through the detector. The system meets all the fire safety requirements for air velocities between 0.2 m/s and 20 m/s. The smoke detector is used together with a control unit (fitted inside an ELQA equipment cubicle or a separate equipment cubicle for the smoke detection and warning function) for controlling fans, fire and smoke dampers. Operation If any smoke is detected, a red LED on the detector lights up and the detector transmits an alarm signal to the control unit. Any accumulation of impurities in the smoke detector will make it more sensitive and gradually approach its alarm condition. To avoid unnecessary alarms caused by fouling, the detector is equipped with a service alarm (green LED). When lit, this LED indicates that the detector ought to be cleaned. Tecnical details Type of detector Ionising Power supply Power consumption: In-operation Service alarm Smoke alarm Permissible ambient temperature Permissible humidity Inclosure Class Weight 24VDC (from control unit) Max 0,04mA ~ 13mA ~ 48mA -20 C to +50 C Max 99% rh IP54 800g Accessories The ELQZ Mounting bracket should be used for mounting the detector on a circular or insulated duct. Maintenance Whenever the smoke detector becomes fouled, it will be more sensitive and may trip the service alarm. This situation can easily be delayed by vacuum cleaning the detector once a year. Dimensions Venturi tube length 600 mm. (All dimensions in mm) Specifications are subject to alteration without notice. 1

2 GB.ELQZ Installation and Location Install the smoke detector with the airflow direction arrow on its cover pointing in the direction of airflow through the ducting. The detector can be mounted on the side or top of the duct for vertical or horizontal air flow. If the ambient temperature varies radically, for example outdoors or in cold attics, insulate the detector to protect it from the ambient air and prevent the formation of condensation inside the detector housing. To ensure satisfactory smoke detection, the smoke detector should be located at a distance, in the direction of airflow, that is equivalent to at least 3 x the hydraulic diameter of the duct upstream of the nearest source of disturbance in the ducting (see the examples of sources of disturbance below). If it is located downstream of the nearest source of disturbance, its distance from this source should be equivalent to at least 5 x the hydraulic diameter of the ducting. Examples of sources of disturbance FAN SILENCER DAMPER COIL Hydraulic diameter CIRCULAR DUCT BEND MIN 3xdh BRANCH d = D h Ø D RECTANGULAR DUCT d = h 2xHxB H+B H ADAPTER EXTRACT AIR SUPPLY AIR B AIR HANDLING UNIT 2 AIR HANDLING UNIT Specifications are subject to alteration without notice.

3 1 Drill an opening in the duct. 35 mm dia. opening for smoke detector without mounting bracket. 50 mm dia. opening for smoke detector with mounting bracket (see item 10). 2 Do not cut this end! End plug. Measure the ventilation duct. Cut the tube to an appropriate length, if needed. The tube should penetrate 90% of the duct diameter into the duct. Insert the end plug. 3 Lock the tube in position by means of the stop screw. Slip the seal onto the tube. Insert the tube in the bottom of the detector housing. IMPORTANT! The arrow on the plastic cover must point in the same direction as that of the air flowing through the duct. 4 Mount the tube and the detector on the duct. Secure the detector housing at the 3 points indicated by the arrows. Specifications are subject to alteration without notice. 3

4 5 Flow indicator. CAUTION! The indicator doesn't rotate; it rocks. If the indicator doesn't move at all, it is advisable to consider relocating the detector. 6 Insert the block. 7 Electric wiring. If only one smoke detector is connected to the system, install the final resistor (2,2kΩ) in this detector. If several smoke detectors are to be connected to one control unit, wire the final resistor (2,2kΩ) in the last detector in the loop. Fit only one resistor per loop! Connect the electric wiring as shown in the wiring diagram. 4 Specifications are subject to alteration without notice.

5 8 Performance checks. Check that the detector operates correctly. Expose the detector to smoke from a match or a suitable spray for testing smoke detectors. 9 Secure the cover by means of screws. Fit the cover on the detector. Do not drill any holes in the plastic cover for fitting identification plates or the like. Doing so will cause leakage, which will seriously impair detector performance. Specifications are subject to alteration without notice. 5

6 10 ELQZ Mounting bracket for a circular duct or an insulated rectangular duct. The mounting bracket enables the detector to be installed on a duct having a diameter as small as 100 mm. Secure the legs of the Fäst bracket beslagets to the duct. ben på kanalen. Håltagning Opening: Ø 50 mm Ø 50 mm. Beslaget The bracket är lätt att is easy böja/forma to bend/form så att det to passar fit on runda circular eller or plana flat kanaler. duct surfaces. Beslaget The bracket levereras is plant. supplied completely flat. Circular Rund kanal. duct Rubber Gummitätning. seal Rubber Gummitätning. seal Insulated Isolerad plan kanal. rectangular duct FINAL INSPECTION Make sure thatthe arrow on the detector cover points in the direction of airflow. Check that the cover and its gasket seals properly against the base and that nothing is lodged in between them, such as insulation. Check that the plug is properly seated in the test hole. Check that the flow indicator indicates airflow (is rocking). It is advisable to test the performance of the detector in full scale. Fault tracing. The smoke detector indicates a service alarm. The detector has become fouled and needs to be cleaned. This can appropriately be done by vacuum cleaning or by carefully blowing surfaces clean with compressed air. The service alarm may trip sooner than expected if the newly installed ducting hasn t been properly cleaned before the system is commissioned. The smoke detector initiates an alarm when no smoke is present. The smoke detector has been located where condensation can form inside it, such as outdoors, in a cold attic, a kitchen or the like. An alarm is indicated by the control unit only. Measure the resistance of the loop (2,2kΩ) from the control unit. Check that the control unit is OK by wiring the final resistor to the smoke detector output on the control unit. Use a voltmeter to check that 24 V DC with the correct polarity is present in the socket below the detector. 6 Specifications are subject to alteration without notice.

Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT

Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT 1. General The TBLZ-1-72-a optical smoke detector with built-in control unit is used for measuring

More information

Instructions for the BASIC BCRW Fan, Sizes General

Instructions for the BASIC BCRW Fan, Sizes General Instructions for the BASIC BCRW Fan, Sizes 004 027 1. General The BCRW is a direct-driven fan of axi-centrifugal design. This fan offers excellent power efficiency, low, uniform air flow, low sound generation

More information

Installation Instruction Venturi-Air Duct Kit. (Part No. S )

Installation Instruction Venturi-Air Duct Kit. (Part No. S ) Installation Instruction Venturi-Air Duct Kit (Part No. S4-34760) Intended purpose This product is designed for installation on a loop circuit of a Vigilon system. Warning In order to ensure correct and

More information

Instructions. Duct Mount Accessory Q Rev: 11/

Instructions. Duct Mount Accessory Q Rev: 11/ Instructions Duct Mount Accessory Q5016 Rev: 11/16 95-8752 Table of Contents DESCRIPTION...1 FEATURES...1 OPERATION...1 SPECIFICATIONS.... 2 INSTALLATION... 2 Detector Location...2 Tools for Assembly...4

More information

Ionisation single-tube smoke detector for duct mounting

Ionisation single-tube smoke detector for duct mounting Detectors Ionisation single-tube smoke detector for duct mounting 600 mm venturi tube is included., incl. end resistor (not RAC(M)) 9...33 V DC (via ABV control unit). 24 V AC ±15 % for RAC(M) models.

More information

E-PDD Duct Smoke Detector Installation Sheet

E-PDD Duct Smoke Detector Installation Sheet E-PDD Duct Smoke Installation Sheet E-PDD operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from

More information

FX-PDD Duct Smoke Detector Installation Sheet

FX-PDD Duct Smoke Detector Installation Sheet FX-PDD Duct Smoke Detector Installation Sheet Table 2: LEDs LED Power LED Alarm/active LED Off when the detector is in the alarm state. Flashes intermittently when the detector is in the normal state.

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

INSTRUCTIONS. Duct Mount Kit Q900. Description. Operation

INSTRUCTIONS. Duct Mount Kit Q900. Description. Operation INSTRUCTIONS Duct Mount Kit Q900 Description The Detector Electronics Model Q900 Duct Mount Kit is used with the Model PIRECL PointWatch Eclipse IR gas sensor to detect combustible hydrocarbon gases within

More information

TrueAlarm Analog Sensing

TrueAlarm Analog Sensing TrueAlarm Analog Sensing UL, ULC Listed* Addressable Duct Sensor Housings with TrueAlarm Photoelectric Sensor; Available with Multiple Relay Features Compact air duct sensor housing with clear cover to

More information

D2E Duct Smoke Detector

D2E Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS D2E Duct Smoke Detector Specifications Operating Temperature: 20 to 60 C Storage Temperature: 20 to 60 C Humidity: 0% to 93% Relative Humidity Non-condensing Air

More information

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608) FORM ASX-40021 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SM-501 Series Smoke Detectors, Model EXSAC and EXSAD (Ionization), EXSAJ and EXSAK (Photoelectric) Air Specialties Express, 448 S. Main

More information

Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector

Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector NOTICE TO THE INSTALLER This manual provides an overview and the installation instructions for the PAD100-DUCTR module. This module is

More information

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608) FORM ASX-40020 INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS SL-2000 Series Smoke Detectors, Model EXSAA and EXSAB (Ionization), EXSAG and EXSAH (Photoelectric) Air Specialties Express, 448 S. Main

More information

DH500ACDC Intelligent Air Duct Smoke Detector Housing

DH500ACDC Intelligent Air Duct Smoke Detector Housing INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500ACDC Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 Specifications Length: 14.5

More information

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS TEST LOG Detector Identification Information Manufacturer and Serial Date Detector Model: Number: Installed: Description of Detector Location: Test Results and Maintenance Data Date Test Test Maintenance

More information

PRODUCT OVERVIEW SM-501 AT-A-GLANCE

PRODUCT OVERVIEW SM-501 AT-A-GLANCE AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SM-501 SERIES DUCT SMOKE DETECTORS SM-501-N SM-501-P PRODUCT APPLICATION SM-501 Series duct smoke detectors provide early detection

More information

Sintrol Snifter A1+ Manual. Version 1.2.2

Sintrol Snifter A1+ Manual. Version 1.2.2 Sintrol Snifter A1+ Manual Version 1.2.2 Table of Contents 1 INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 3 1.3 How does it work?... 3 2 INSTALLATION... 4 2.1 Selecting the installation location...

More information

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER Installation Instructions Model AD-HR Air Duct Monitoring Housing INTRODUCTION The SIEMENS Model AD-HR is a sampling tube, air duct monitoring housing. When used with a compatible smoke detector, smoke

More information

You in Control PRODUCT OVERVIEW

You in Control PRODUCT OVERVIEW AIR PRODUCTS AND CONTROLS You in Control AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SERIES PLENUM DUCT SMOKE DETECTORS NO-FLOW LOW-FLOW SPECIAL APPLICATION -N -P PRODUCT

More information

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd 1 MJC Mini Cartridge Filters Owners Manual TSOM 556 Date of Issue: 13.07.04 Orgreave Drive, Sheffield South Yorkshire. S13 9NR Tel:0114 254 0600 Fax: 0114 2540250 Email:sales@hodgeclemco.co.uk www.hodgeclemco.co.uk

More information

Electro Controls. Flow WattsIndustries.co.uk

Electro Controls. Flow WattsIndustries.co.uk Electro Controls Flow - 07 WattsIndustries.co.uk FLOW AIR FLOW SWITCHES EAA.. EAA.. detects air flow in ducts to monitor fan operation and switches in the event of flow failure. It is suitable for non-aggressive

More information

DMFPM-2R MULTIFUNCTIONAL

DMFPM-2R MULTIFUNCTIONAL Mounting and operating instructions Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND

More information

SK-Duct Air Duct Smoke Detector

SK-Duct Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3432-001R 12 Clintonville Road Northford, CT 06472 203.484.7161; Fax: 203.484.7118 SK-Duct Air Duct Smoke Detector http://www.silentknight.com Specifications

More information

Installation Instructions for Duct Accessories GOLD/SILVER C/COMPACT

Installation Instructions for Duct Accessories GOLD/SILVER C/COMPACT Installation Instructions for Duct Accessories GOLD/SILVER C/COMPACT 1. Installation, duct accessories 1.1 General These instructions deal with the installation of duct accessories in duct systems. For

More information

Snifter. User Manual. Distributor

Snifter. User Manual. Distributor Snifter User Manual Distributor Version 1.3 08/09/2009 1 Table of Contents 1. INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 3 1.3 How does it work?... 3 2. INSTALLATION... 4 2.1 Selecting the

More information

USER INSTRUCTIONS FOR 0.25 LITRE MINI DEHUMIDIFIER - MODEL NO. DHMD025

USER INSTRUCTIONS FOR 0.25 LITRE MINI DEHUMIDIFIER - MODEL NO. DHMD025 USER INSTRUCTIONS FOR 0.25 LITRE MINI DEHUMIDIFIER - MODEL NO. DHMD025 THANK YOU FOR CHOOSING YOUR NEW DEHUMIDIFIER. BEFORE USING THE UNIT READ THESE INSTRUCTIONS FULLY AND RETAIN THEM FOR FUTURE REFERENCE

More information

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side s Frost detectors for use on the air side QAF63.2-J QAF63.6-J Active capillary tube sensor for acquiring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter VALLOX Product Code: 3158400 L 3158410 R SILENCER (OPTIONAL) INSTRUCTIONS FOR USE AND MAINTENANCE WATER CIRCULATED POST-HEATING UNIT (OPTIONAL) ELECTRIC POST-HEATING UNIT (OPTIONAL)) PREHEATER (OPTIONAL)

More information

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

ZIOU/230 - MAINS IO INSTRUCTION MANUAL Description ZIOU/230 - MAINS IO INSTRUCTION MANUAL The Mains IO Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel

More information

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-1975-004R Before installing detectors, please thoroughly read the NEMA Guide for

More information

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000 SERVICE INSTRUCTIONS FOR Fire Alarm System MINI-2000 Version 1.3 02.04.1998 Jari Ollila Tom Brunberg Oy Esmi Ab Copyright Oy ESMI Ab, 1991... 1998 The copyright to the documentation herein is the property

More information

LZP-2 ZONE CONTROL PANEL

LZP-2 ZONE CONTROL PANEL 2004 Lennox Industries Inc. Dallas, Texas, USA ZONING SYSTEM 504,926M 5/2004 Litho U.S.A. LZP-2 ZONE CONTROL PANEL INSTALLATION INSTRUCTIONS FOR ZONE CONTROL PANELS USED WITH LENNOX HEATING AND COOLING

More information

VFL, VFLPG, VTL and VRA Rectangular electric duct heaters

VFL, VFLPG, VTL and VRA Rectangular electric duct heaters VFL, VFLPG, VTL and VRA Rectangular electric duct heaters VFL, VFLPG, VTL and VRA Rectangular electric duct heaters VEAB rectangular duct heaters are available in ratings of up to 2000 kw and are used

More information

Contents. Technical Description of the Air Handling Unit General, Specification Function, Functional Sections

Contents. Technical Description of the Air Handling Unit General, Specification Function, Functional Sections Room unit Contents Technical Description of the Air Handling Unit General, Specification... 146 Function, Functional Sections... 147 Control System Control Display, Airflow Control... 148 Temperature Control...

More information

DH100ACDCI Ionization Air Duct Smoke Detector

DH100ACDCI Ionization Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),

More information

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installing detectors, please thoroughly read the NEMA Guide for Proper Use

More information

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495

More information

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS Air Duct Smoke Detector with Extended Air Speed Range A Division of Pittway 825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 60-77-6495 The Innovair

More information

l High precision, computer-designed parabolic optical system,. Dual element pyro-electric sensor.

l High precision, computer-designed parabolic optical system,. Dual element pyro-electric sensor. GENERAL INFORMATION: The No. 1852 provides 12 zones of coverage with a range of up to 25 feet (at a typical mounting height of 7-0 ). This model has the following important features: l High precision,

More information

Xenex Conventional Fire Detection & Alarm System

Xenex Conventional Fire Detection & Alarm System SECTI 4: page 1 Section 4: Xenex Conventional Fire Detection & Alarm System SECTI 4: page 3 Xenex system architecture Beam Transmitter Beam Receiver End of Line Call Point Smoke Detector Smoke Detector

More information

MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS

MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS 1. FEATURES The Type N Trap range is particularly suitable for high pressure/high temperature trapping applications

More information

PRODUCT OVERVIEW. SL-2000 AT-A-GLANCE MODEL NUMBER: SL-2000-N 4-Wire Ionization Duct Smoke Detector SL-2000-P 4-Wire Photoelectric Duct Smoke Detector

PRODUCT OVERVIEW. SL-2000 AT-A-GLANCE MODEL NUMBER: SL-2000-N 4-Wire Ionization Duct Smoke Detector SL-2000-P 4-Wire Photoelectric Duct Smoke Detector AIR PRODUCTS AND CONTROLS You in Control AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SERIES DUCT SMOKE DETECTORS -N 4-Wire, Ionization Type -P 4-Wire, Photoelectric Type

More information

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side s Frost detector for use on the air side QAF64.2-J QAF64.6-J With active capillary tube sensing element for acquiring the lowest temperature within a range of 0 15 C With startup function Operating voltage

More information

QFM41.. Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

QFM41.. Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates 1 883 1883P01 1883P02 1859P04 QFM41.. AQF4150 AQF3153 Symaro Duct sensors for relative humidity and temperature with calibration certificates QFM41.. Operating voltage AC 24 V / DC 13.5...35 V Signal output

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

Self-regulating vacuum pumps. Characteristics. Ø max. vacuum air drawn in L2 model nozzle (%) Specifications. Curves: see page 9/27.

Self-regulating vacuum pumps. Characteristics. Ø max. vacuum air drawn in L2 model nozzle (%) Specifications. Curves: see page 9/27. Branch-specific applications (electric vacuum and blow-off control) Description The communication between both elements, electronic vacuum switch and gripping valve control allows the consumption of compressed

More information

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products 1 821 1821P01 Frost sensors for use on the air side Active capillary tube sensor for measuring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10 V Use On

More information

DH400 Air Duct Smoke Detector

DH400 Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS DH400 Air Duct Smoke Detector Before Installing Please thoroughly read System Sensor s Guide for Proper Use of Smoke Detectors in Duct Applications (I56-473-XX),

More information

Air heater/cooler in combination with ground source heat pump

Air heater/cooler in combination with ground source heat pump Swegon CASA Air heater/cooler in combination with ground source heat pump Installation, operation and maintenance instructions for design engineers, installation engineers and service personnel SDHWM_c_EN

More information

INSTALLATION, BALANCING & MAINTENANCE

INSTALLATION, BALANCING & MAINTENANCE FORM 10.2 REV 0510 THERMA-FUSER THERMALLY POWERED VAV DIFFUSER INSTALLATION, BALANCING & MAINTENANCE MODULAR VAV SYSTEMS Models: ST-C VAV cooling only. ST-HC VAV cooling and VAV heating. (See Fig. 1 for

More information

INSTALLATION AND MAINTENANCE

INSTALLATION AND MAINTENANCE INSTALLATION AND MAINTENANCE DH100ACDCIA & DH100ACDCPA Air Duct Smoke Detector Before Installing ULC standard CAN/ULC-S524-M91 Standard For The Installation Of Fire Alarm Systems should be referenced for

More information

S304 and S305 Dust Emission Monitors. User Manual. Distributor

S304 and S305 Dust Emission Monitors. User Manual. Distributor S304 and S305 Dust Emission Monitors User Manual Distributor Version 6.4 30/5/2012 Table of Contents 1. INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 4 1.3 Principle of operation... 4 2. INSTALLATION...

More information

DH100ACDCI Ionization Air Duct Smoke Detector

DH100ACDCI Ionization Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS Ionization Air Duct Smoke Detector Before Installing Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),

More information

You in Control PRODUCT OVERVIEW SM-501 AT-A-GLANCE

You in Control PRODUCT OVERVIEW SM-501 AT-A-GLANCE AIR PRODUCTS AND CONTROLS You in Control AIR PRODUCTS AND CONTROLS INC. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR SM-501 SERIES DUCT SMOKE DETECTORS SM-501-N 4-Wire, Ionization Type SM-501-P 4-Wire,

More information

Accuracy by Design Products for the HVAC Professional

Accuracy by Design Products for the HVAC Professional Accuracy by Design Products for the HVAC Professional Greystone Energy Systems Inc., is one of North America s largest ISO registered manufacturers of HVAC sensors and transducers for Building Automation

More information

CV Circular electric duct heaters

CV Circular electric duct heaters Circular electric duct heaters Circular electric duct heaters VEAB circular electric duct heaters are used for heating the ventilation air supplied to individual rooms and zones, with individually controlled

More information

Model 1750A/ 1770A Dehumidifier Installation Instructions

Model 1750A/ 1770A Dehumidifier Installation Instructions Model 1750A/ 1770A Dehumidifier Installation Instructions Safety Instructions WARNING 1. Improper installation may cause property damage or injury. Installation, service, and maintenance must be performed

More information

Duct Temperature Sensors

Duct Temperature Sensors 1 762 1761P03 1762P01 Mounting flange AQM630 QAM21 Symaro Duct Temperature Sensors QAM2161040 QAM2171040 Active sensors for acquiring the air temperature in air ducts AC 24 V or DC 13535 V Signal output

More information

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Duct smoke housings, 4-wire D341/D341P and D342/D342P Duct smoke housings, 4-wire D341/D341P and D342/D342P en Installation manual Duct smoke housings, 4-wire Notices en 3 1 Notices These instructions cover the installation of the D341/D342 Duct smoke housings

More information

The Silent Range Pure Elegance & Tranquillity. The widest range of ultra quiet silent fans

The Silent Range Pure Elegance & Tranquillity. The widest range of ultra quiet silent fans The Silent Range Pure Elegance & Tranquillity The widest range of ultra quiet silent fans The most advanced SILENT technology delivering the highest extract performance. 1 Your first choice for ventilation

More information

DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories

DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories interactive, AnalogPLUS/SynoLOOP, collective/synoline600 AlgoRex Synova TM Base made of impact and scratch-proof plastic Screw less terminals

More information

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview Overview Modern combustion (or gas) turbine packages typically include an axial compressor, a combustion section and a turbine. Both compressor and turbine sections consist of one or more sets of fixed

More information

Duct and Rough Service Carbon Monoxide Sensor

Duct and Rough Service Carbon Monoxide Sensor Product Identification and Overview Duct and Rough Service Carbon Monoxide Sensor BAPI s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations.

More information

GOLD RX, GOLD RX 12 GOLD RX,

GOLD RX, GOLD RX 12 GOLD RX, Overview GOLD RX Rotary heat exchanger m 3 /h The GOLD RX 12-80 can be split into three sections for transport within the building site. Available total pressure rise, Pa GOLD RX GOLD RX, 04-08 Right-hand

More information

DICTATOR Hold-Open Systems for Hazardous Areas

DICTATOR Hold-Open Systems for Hazardous Areas DICTATOR for Hazardous Areas Products to be used in hazardous areas obviously have to meet special demands. The European ATEX directives (first the EN 94/9/EG and then the directive 2014/34/ EU) brought

More information

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21... Use Type summary Operating voltage AC 24 V or DC 13.5...3 Signal output DC 0...10 V for relative humidity Signal output

More information

Conventional Fire Alarm System 2014 V1.2

Conventional Fire Alarm System 2014 V1.2 Conventional Fire Alarm System 2014 V1.2 Product Overview Control Panel 2 Conventional Fire Panel GST102A 2 zone Fire panel GST104A 4 zone Fire panel GST108A 8 zone Fire panel GST116A 16 zone Fire Panel

More information

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information... 3 2 Safety notes... 3 3 Technical description...4 4 Transport... 6 5

More information

Installation and Maintenance

Installation and Maintenance 1.0 INTRODUCTION MRXBOXAB-ECO-LP1SW (Standard Unit) MRXBOXAB-ECO-LP1-OHSW (Opposite Hand Unit) Mechanical Ventilation Unit with Heat Recovery for Ceiling Void Mounting Installation and Maintenance The

More information

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2 I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications

Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications Data Sheet 907020 Page 1/9 Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications For measuring relative humidity and temperature For versatile climatic applications and ventilation

More information

DH100LP Air Duct Smoke Detector with Extended Air Speed Range

DH100LP Air Duct Smoke Detector with Extended Air Speed Range INSTALLATION AND MAINTENANCE INSTRUCTIONS DH100LP Air Duct Smoke Detector with Extended Air Speed Range 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 The Innovair DH100LP

More information

DUCT SMOKE DETECTORS IQ8

DUCT SMOKE DETECTORS IQ8 Marcin Cichy 11.2017 DUCT SMOKE DETECTORS IQ8 Special fire alarm detectors EN 54-27 duct smoke detectors EN 54-27:2015 Fire detection and fire alarm systems Part 27: Duct smoke detectors New standard introduced

More information

READ AND SAVE THESE INSTALLATION INSTRUCTIONS

READ AND SAVE THESE INSTALLATION INSTRUCTIONS Nomenclature: D F I 0 0 H : Open coil element T: Tubular element F: Finned tubular element I: Slip in type F: Flange type 0: No screen left of the heater 1: Screen left of the heater 0: No screen right

More information

WHHR Midi & Midi Lite

WHHR Midi & Midi Lite WHHR Midi & Midi Lite Residential Whole House Heat Recovery Units with Low Energy EC Motors Optional - Integral LCD Installation, Operating and Maintenance Instructions Image of model with LCD screen Page

More information

Self-regulating vacuum pumps. Characteristics. Ø max. vacuum air drawn in L2 model nozzle (%) Specifications. Curves: see page 9/27.

Self-regulating vacuum pumps. Characteristics. Ø max. vacuum air drawn in L2 model nozzle (%) Specifications. Curves: see page 9/27. Branch-specific applications (electric vacuum and blow-off control) Description The communication between both elements, electronic vacuum switch and gripping valve control allows the consumption of compressed

More information

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG Suitable for a wide range of applications Steam Injection humidifiers from DRI-STEEM use steam from an external source, such as an

More information

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction Air Comfort Air Treatment Energy Recovery eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction eco PREMIUM - Technical Instruction REDA 2 Contents Description Applications... 3 Quality & environment...

More information

Duct smoke housing, 2-wire D340/D340P

Duct smoke housing, 2-wire D340/D340P Duct smoke housing, 2-wire D340/D340P en Installation manual Duct smoke housing, 2-wire Notices en 3 1 Notices These instructions cover the installation of the D340 Duct smoke housing and D340P Duct smoke

More information

System 800 Addressable Fire Detection & Alarm System

System 800 Addressable Fire Detection & Alarm System SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools

More information

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

INSTALLATION DO S AND DON TS

INSTALLATION DO S AND DON TS 4.0 NOISE CONTROL Figure 4.1. - Transitions Abrupt transitions immediately adjacent to an attenuator will cause the attenuator pressure drop to increase. Ensure transitions close to attenuators are gradual

More information

Installation Instructions

Installation Instructions 48/50A2,A3,A4,A5020-060, 48/50P2,P3,P4,P5030-100, 48/50N 75 to 105 Ton Return Smoke Detector Accessory Installation Instructions Part No. CRSMKDET002C00 CONTENTS GENERAL........................................

More information

DNR-AUS Duct Smoke Detector

DNR-AUS Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3642-000R DNR-AUS Duct Smoke Detector Specifications Operating Temperature: 20 to 70 C ( 4 to 158 F) 0 C to 49 C (32 F to 120 F) with module installed in the

More information

EUKC Cooling Unit. Compulsory declaration and recurring. The unit must NOT be used in any other way than as a cooling unit!

EUKC Cooling Unit. Compulsory declaration and recurring. The unit must NOT be used in any other way than as a cooling unit! Safety Precautions IMPORTANT INFORMATION! The unit must NOT be used in any other way than as a cooling unit! Carefully read, study and understand the Operation and Maintenance Instructions before you commission

More information

CV Circular electric duct heaters

CV Circular electric duct heaters Circular electric duct heaters C I R C U L A R E L E C T R I C D U C T H E A T E R S Circular electric duct heaters VEAB circular electric duct heaters are used for heating the ventilation air supplied

More information

Primo Hotel. General. Indoor climate units for hotel rooms

Primo Hotel. General. Indoor climate units for hotel rooms Indoor climate units for hotel rooms General Primo Hotel indoor climate unit Ceiling-mounted indoor climate units for ventilation, cooling and heating High capacity; occupies little space Dry system without

More information

FireNET Vapor VPR-SD2

FireNET Vapor VPR-SD2 FireNET Vapor VPR-SD2 Product Guide October 2012 Document: 21538_00 Part Number: HA-06-333 Hochiki America Corporation FireNET Vapor VPR-SD2 Product Guide Intellectual Property and Copyright This document

More information

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU Type FK-EU FOR DIVERSE APPLICATIONS Rectangular fire damper for the isolation of duct penetrations between fire compartments,

More information

USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel

USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel PU SENS 01 CONTENTS Safety requirements... 3 Purpose... 4 Technical data... 4 Overall dimensions [mm]... 4 Mounting and set-up... 5

More information

FDBZ290 Air sampling smoke detection kit

FDBZ290 Air sampling smoke detection kit FDBZ290 Air sampling smoke detection kit Sinteso Cerberus PRO Reliable monitoring for smoke of supply air, exhaust air and recirculation ducts of air conditioning and ventilation systems Suitable for air

More information

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS Contents Page User instructions 3-5 General 3 Fan installation 3-4 Maintenance 3 Electrical installation 5 Troubleshooting 5 Technical description 6-8 General

More information

DH500 Intelligent Air Duct Smoke Detector Housing

DH500 Intelligent Air Duct Smoke Detector Housing INSTALLATION AND MAINTENANCE INSTRUCTIONS DH500 Intelligent Air Duct Smoke Detector Housing 3825 Ohio Avenue, St. Charles, Illinois 60174 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com Specifications

More information

DNR Duct Smoke Detector

DNR Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS I56-3051-004R DNR Duct Smoke Detector Specifications Operating Temperature: 4 to 158 F ( 20 to 70 C); 32 F to 120 F (0 C to 49 C) with module installed in the

More information

LASER ASPIRATED SMOKE DETECTOR

LASER ASPIRATED SMOKE DETECTOR LASER ASPIRATED SMOKE DETECTOR LASD1 (Single Channel) INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS (CE) 1 INTRODUCTION The LASD1 utilises one or two high-sensitivity laser point detectors in an aspirated

More information