Report of Inspection/Test
|
|
- Rodger Cox
- 5 years ago
- Views:
Transcription
1 Report of Inspection/Test West Howard Lane Suite 4 Austin, Texas Phone: Fax: Inspection Type: Pump - Annual Inspection Date: 2/24/217 1::2 AM Building Address:88 South Independence Boulevard Building Name: Property: Wilson Lending Corporation Owner/Agent: Conducted by: Doug Wilson GENERAL INFORMATION System Name FIRE PUMP #1 Manufacturer PEERLESS Make 1-B Serial Number Driver Type Electric Pump Type Centrifugal Split Case Suction Size 8 Discharge Size 6 Water Source CITY Stages 1 UL/FM Listing UL and FM Impeller Diameter PUMP RATING Cut In Pressure 137 Sprinkler Demand gpm Rating PUMP CONTROLLER gpm 15 gpm 225 gpm Controller_Manufacturer FIRETROL Make Model Serial Number Controller_Amps 128 Controller_Volts 46 Controller_Hertz 6 Controller_Horsepower 1 Controller_Phase 3 UL/FM Listing UL and FM Timer on Controller No Transfer Switch Yes Transfer Switch Make FIRETROL Transfer Switch Model T Transfer Switch Serial Number JOCKEY PUMP Cut In Pressure 157 Cut Off Pressure 147 Make GRUND Model Serial Number 67372B8282BH Pump Type Electric Motor Make TYSON Motor Horsepower 1.5 Motor RPM 355 Motor Volts 24 Controller Make FIRETROL; Controller Model Controller SerialNumber Controller Volts 24
2 PUMP DRIVER Make WEG Model 82726T1811 Serial Number Horsepower 1 RPM 355 Amps 128 Volts 46 Hertz 6 Phase 3 UL/FM Listing UL and FM Fail N/A SI Fire Pumps NFPA General C.FP.1 System inspection and test results Pump FIRE PUMP #1 Tag Color BLUE C.FP.2 Record work order number Work Order # 669 Owner Information OI.FP.1.1 Is the building occupied? OI.FP.1.2 Has the occupancy classification and hazard of contents remained the same since the last inspection? OI.FP.1.3 Are all fire protection systems in service? OI.FP.1.4 Has the system remained in service without modification since the last inspection? OI.FP.1.5 Was the system free of actuations of devices or alarms since the last inspection? General Inspection IW.FP Pump house not less than 4 degrees F (4.4 degrees C)? (Diesel pumps w/out engine heaters) IW.FP Ventilating louvers are free to operate? IW.FP Pump suction, discharge, and bypass valves are fully open? IW.FP Piping is free of leaks? IW.FP Suction line pressure gauge reading is within acceptable range? IW.FP System line pressure gauge reading is within acceptable range? IW.FP Waterflow test valves are in the closed position? Electric Pump Inspection IW.FP Controller indicating power is on? IW.FP Transfer switch normal pilot light is illuminated (3) IW.FP Isolating switch is closed - standby (emergency) source? IW.FP Pump is in correct phase? IW.FP Power is provided to the jockey pump? Electric Pump System Maintenance MM.FP.1 Exercise isolating switch and circuit breaker. MS.FP.3 Operate manual starting means (electrical). MA.FP.4 Inspect and operate emergency manual starting means (without power).
3 MA.FP.8 Grease motor bearings. MA.FP.9 Check voltmeter and ammeter for accuracy (to within 5%). MA.FP.11 Check for cracked cable/wire insulation. MA.FP.12 Check for leaks in plumbing parts. MA.FP.13 Check for signs of water on electrical parts. Annual Pump Tests TA.FP.1 Pump test conducted at minimum, rated, and peak flows and results are acceptable? TA.FP.1.1 Circulation and pressure relief valves operated properly during all flow tests? TA.FP.2.1 Alarm conditions simulated and alarm indicating devices observed for operation? TA.FP.2.4 Fire pump and driver alignment checked and any misalignment corrected, if necessary? TA.FP.2.6 Emergency generator sets tested and passed? TA.FP.2.7 Pump room environmental conditions pass? General Pump Maintenance MA.FP.21 Lubricate pump bearings. MA.FP.22 Check pump shaft end play. MA.FP.23 Check accuracy of pressure gauges and sensors. When inspection and testing are complete C.FP.999 Capture customer and inspector signatures. Fire Pump Test Results Pump Type Pump Manufacturer Centrifugal Split Case PEERLESS Pump Rating 122 gpm gpm gpm Pump operation passed at minimum, rated, and peak flows Hose Suction PSI Discharge PSI Pitot PSI GPM Total GPM Net PSI RPM Volts Amps Churn Hose 1: % Hose 1: Hose 2: Hose 3: Hose 4: Hose 5: Hose 6: 15% Hose 1: Hose 2: Hose 3: Hose 4: Hose 5: Hose 6: Churn Hose 1: OWNER: Except as noted, the building is occupied with the same occupancy classification and hazard of contents as last inspection. Also, the system has remained in service without modification and been free of actuation of devices or alarms.
4 INSPECTOR: I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
5
6 Report of Inspection/Test West Howard Lane Suite 4 Austin, Texas Phone: Fax: Occupant Name: Address: Wilson Lending Corporation Inspection Date: 2/24/ South Independence Boulevard InspectionType: City: Austin Inspected By: Doug Wilson State: TX Zip Code: 781 Pump - Annual, Sprinkler - 3 Year, Sprinkler - Annual, Standpipe & Hose Annual Fail - Corrected Fail Total Inspected Total Devices Control Dry Pipe Low Air Supervisory Switch Preaction Pressure Reducing Waterflow Switch Floor -1 Fail - Corrected Fail Total Inspected Total Devices Dry Pipe Low Air Supervisory Switch PARKING GARAGE FIRE Control PARKING GARAGE DRY 4 INCH OS&Y SPRINKLER RISER ROOM SYSTEM CONTROL PARKING GARAGE FIRE SPRINKLER RISER ROOM Dry Pipe PARKING GARAGE FIRE Low Air SPRINKLER RISER Supervisory ROOM Switch Pressure Reducing PARKING GRAGE DRY SYSTEM PARKING GARAGE DRY SYSTEM HI/LOW -1 FLOOR PRESSURE REDUCING FIRE HOSE 4 INCH FIRELOCK S/768 Type of trip test performed today (partial/full): FULL Pressure before test (air/water): 14/11 Trip air pressure: 4 Trip time: 26 Water delivery time to Inspector Test (ITV): 45 PS-4 Tripped at (air pressure): 1 PSI 2.5 INCH POTTER PRV-1 Notes: FLOWED 25GPM AT
7 Floor 1 Fail - Corrected Fail Total Inspected Total Devices Control Control 1ST FLOOR FIRE SPRINKLER CONTROL Control STAND PIPE ISOLATION CONTROL 6 INCH BUTTERFLY Pressure Reducing 1ST FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 1ST FLOOR FIRE SPRINKLER Time to Alarm (sec.): 37 Floor 2 Fail - Corrected Fail Total Inspected Total Devices Control 2ND FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 2ND FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 2ND FLOOR FIRE SPRINKLER Time to Alarm (sec.): 41 Floor 3 Fail - Corrected Fail Total Inspected Total Devices Control Low Air Supervisory Switch Preaction RD FLOOR ROOM 2Y.OO3 Control 3RD FLOOR DATA SERVER ROOM PRE-ACTION CONTROL 2.5 INCH OS&Y 3RD FLOOR Low Air ROOM 2Y.OO3 Supervisory Switch 3RD FLOOR Preaction ROOM 2Y.OO3 3RD FLOOR DATA SERVER ROOM PRE-ACTION HI/LOW 3RD FLOOR DATA SERVER ROOM PRE-ACTION PS-4 PRESSURE 2.5 INCH VICTAULIC FIRELOCK NXT LP S/769 Tripped at (air pressure): 8/17 Type of trip test performed today (partial/full): FULL Pressure before test (air/water): 12/129
8 Control 3RD FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 3RD FLOOR PRESSURE REDUCING FIRE HOSE Waterflow Switch 3RD FLOOR FIRE SPRINKLER WATER FLOW PRV-1 Trip air pressure: 3 Trip time: 14 Water delivery time to Inspector Test (ITV): 36 Notes: FLOWED 25GPM AT Time to Alarm (sec.): 37 Floor 4 Fail - Corrected Fail Total Inspected Total Devices Control 4TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 4TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 4TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 4 Floor 5 Fail - Corrected Fail Total Inspected Total Devices Control 5TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 5TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 5TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 4 Floor 6 Fail - Corrected Fail Total Inspected Total Devices
9 Control 6TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 6TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 6TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 45 Floor 7 Fail - Corrected Fail Total Inspected Total Devices Control 7TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 7TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 7TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 39 Floor 8 Fail - Corrected Fail Total Inspected Total Devices Control Control 8TH FLOOR FIRE 2.5 INCH SPRINKLER CONTROL BUTTERFLY Control STAND PIPE ROOF TEST HEADER CONTROL 6 INCH BUTTERFLY Specifications: NORMALLY CLOSED Pressure Reducing 8TH FLOOR PRESSURE REDUCING FIRE HOSE Waterflow Switch 8TH FLOOR FIRE SPRINKLER WATER FLOW PRV-1 Notes: FLOWED 25GPM AT Time to Alarm (sec.): 33 OWNER: Except as noted, the building is occupied with the same occupancy classification and hazard of contents as last inspection. Also, the system has remained in service without modification and been free of actuation of devices or alarms. INSPECTOR: I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operational condition upon completion of this inspection
10 except as noted.
11 Report of Inspection/Test West Howard Lane Suite 4 Austin, Texas Phone: Fax: Inspection Type: Sprinkler - 3 Year, Sprinkler - Annual, Standpipe & Hose Annual Inspection Date: 2/24/217 1::2 AM Building Address:88 South Independence Boulevard Building Name: Property: Wilson Lending Corporation Owner/Agent: Conducted by: Doug Wilson License: RMEI- System Name: BUILDING STAND PIPE WITH PRV HOSE S System Type: Sprinkler - Stand Pipe Fail N/A Fail N/A SI Sprinkler Systems NFPA Notifications After Testing and Maintenance C.SS.92 Notifications made after testing or maintenance? SI Standpipe and Hose Systems NFPA General C.GE.1 System inspection test results. Inspection and Test Result System(s) BUILDING STAND PIPE WITH PRESSURE REDUCING FIRE HOSE S Tag Color YELLOW C.GE.2 Record work order number. Work Order # 669 Owner Information C.OI.1.1 Is the building occupied? C.OI.1.2 Has the occupancy classification and hazard of contents remained the same since the last inspection? C.OI.1.3 Are all fire protection systems in service? C.OI.1.4 Has the system remained in service without modification since the last inspection? C.OI.1.5 Was the system free of actuations of devices or alarms since the last inspection? Notification Prior to Testing and Maintenance C.NO.1 Notifications made prior to testing or maintenance?
12 Supervisory Service Name Time of Notification NORTH STAR FIRE ALARM MONITORING 7AM AHJ Name Time of Notification AUSTIN FIRE DISPATCH 7AM Building Management Name Time of Notification CHRIS DAVIS 63AM Control s IW.CV.1 s are in normal open or closed position? IW.CV.2 s are sealed, locked, or supervised? IW.CV.3 s are free of external leaks? IW.CV.4 s are accessible and protected from physical damage? IW.CV.5 Correct wrenches are provided? IW.CV.6 Each valve is identified and has sign indicating system or portion of system it controls? TS.CV.8 supervisory switches indicate movement? TA.CV.9 Each control valve operated through full range and returned to normal position? Alarm s / Sys Riser Check s IM.AV.1 Gauges indicate normal supply water pressure is being maintained? IM.AV.2 Alarm valves are free of physical damage? IM.AV.3 s are in the appropriate open or closed position? IM.AV.4 Retarding chamber or alarm drains are not leaking? Hose Connection Pressure Reducing s IA.HC.1 Handwheels are not missing or broken? IA.HC.2 Outlet hose threads are not damaged? IA.HC.3 s are not leaking? IA.HC.4 Reducer and cap are in place? Fire Department Connections IQ.FD.1 Fire department connections are visible, accessible, and in good condition? IQ.FD.2 Couplings or swivels are not damaged and rotate smoothly? IQ.FD.3 Plugs or caps are in place and are undamaged? 1 DEFICIENCY: MISSING 1 FDC CAP AT NORTH FDC THAT SUPPLIES STAND PIPE FDC. CORRECTIVE ACTION: REPLACE MISSING FDC CAP. IQ.FD.4 Gaskets are in place and are in good condition. IQ.FD.5 Identification signs are in place? IQ.FD.6 Check valve is not leaking? IQ.FD.7 Automatic drain valve is in place and operating properly? IQ.FD.8 Connection clapper is in place and operating properly?
13 IQ.FD.9 If plugs or caps are not in place, is interior free of obstructions and is connection clapper operational over its full range? Hydraulic Information Sign IA.HI.1 Hydraulic design information sign is attached and legible? Piping IA.PI.1 Visible pipe and pipe supports in good condition? Waterflow Devices TQ.WD.1 Mechanical waterflow alarm devices actuated and flow observed? General Testing and Maintenance IM.GT.1 Gauges on wet system are in good condition and indicate normal water supply pressure is being maintained? MO.GT.6 Obstruction investigation for system or yard main piping conducted if required? CONDUCTED ON 9/216 NEXT 5 YEAR INTERNAL INSPECTION DUE 9/221. Notifications After Testing and Maintenance C.NA.1 Notifications made after testing or maintenance? Supervisory Service Name Time of Notification NORTH STAR FIRE ALARM MONITORING 3PM AHJ Name Time of Notification AUSTIN FIRE DISPATCH 3PM Building Management Name Time of Notification CHRIS DAVIS 3PM C.NA.2 Capture customer and inspector signatures. OWNER: Except as noted, the building is occupied with the same occupancy classification and hazard of contents as last inspection. Also, the system has remained in service without modification and been free of actuation of devices or alarms. INSPECTOR: I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operational condition upon completion of this inspection except as noted. 1. IQ.FD.3.
14
15 Report of Inspection/Test West Howard Lane Suite 4 Austin, Texas Phone: Fax: Occupant Name: Address: Wilson Lending Corporation Inspection Date: 2/24/ South Independence Boulevard InspectionType: City: Austin Inspected By: Doug Wilson State: TX Zip Code: 781 Pump - Annual, Sprinkler - 3 Year, Sprinkler - Annual, Standpipe & Hose Annual Fail - Corrected Fail Total Inspected Total Devices Control Dry Pipe Low Air Supervisory Switch Preaction Pressure Reducing Waterflow Switch Floor -1 Fail - Corrected Fail Total Inspected Total Devices Dry Pipe Low Air Supervisory Switch PARKING GARAGE FIRE Control PARKING GARAGE DRY 4 INCH OS&Y SPRINKLER RISER ROOM SYSTEM CONTROL PARKING GARAGE FIRE SPRINKLER RISER ROOM Dry Pipe PARKING GARAGE FIRE Low Air SPRINKLER RISER Supervisory ROOM Switch Pressure Reducing PARKING GRAGE DRY SYSTEM PARKING GARAGE DRY SYSTEM HI/LOW -1 FLOOR PRESSURE REDUCING FIRE HOSE 4 INCH FIRELOCK S/768 Type of trip test performed today (partial/full): FULL Pressure before test (air/water): 14/11 Trip air pressure: 4 Trip time: 26 Water delivery time to Inspector Test (ITV): 45 PS-4 Tripped at (air pressure): 1 PSI 2.5 INCH POTTER PRV-1 Notes: FLOWED 25GPM AT
16 Floor 1 Fail - Corrected Fail Total Inspected Total Devices Control Control 1ST FLOOR FIRE SPRINKLER CONTROL Control STAND PIPE ISOLATION CONTROL 6 INCH BUTTERFLY Pressure Reducing 1ST FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 1ST FLOOR FIRE SPRINKLER Time to Alarm (sec.): 37 Floor 2 Fail - Corrected Fail Total Inspected Total Devices Control 2ND FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 2ND FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 2ND FLOOR FIRE SPRINKLER Time to Alarm (sec.): 41 Floor 3 Fail - Corrected Fail Total Inspected Total Devices Control Low Air Supervisory Switch Preaction RD FLOOR ROOM 2Y.OO3 Control 3RD FLOOR DATA SERVER ROOM PRE-ACTION CONTROL 2.5 INCH OS&Y 3RD FLOOR Low Air ROOM 2Y.OO3 Supervisory Switch 3RD FLOOR Preaction ROOM 2Y.OO3 3RD FLOOR DATA SERVER ROOM PRE-ACTION HI/LOW 3RD FLOOR DATA SERVER ROOM PRE-ACTION PS-4 PRESSURE 2.5 INCH VICTAULIC FIRELOCK NXT LP S/769 Tripped at (air pressure): 8/17 Type of trip test performed today (partial/full): FULL Pressure before test (air/water): 12/129
17 Control 3RD FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 3RD FLOOR PRESSURE REDUCING FIRE HOSE Waterflow Switch 3RD FLOOR FIRE SPRINKLER WATER FLOW PRV-1 Trip air pressure: 3 Trip time: 14 Water delivery time to Inspector Test (ITV): 36 Notes: FLOWED 25GPM AT Time to Alarm (sec.): 37 Floor 4 Fail - Corrected Fail Total Inspected Total Devices Control 4TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 4TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 4TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 4 Floor 5 Fail - Corrected Fail Total Inspected Total Devices Control 5TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 5TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 5TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 4 Floor 6 Fail - Corrected Fail Total Inspected Total Devices
18 Control 6TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 6TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 6TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 45 Floor 7 Fail - Corrected Fail Total Inspected Total Devices Control 7TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 7TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 7TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 39 Floor 8 Fail - Corrected Fail Total Inspected Total Devices Control Control 8TH FLOOR FIRE 2.5 INCH SPRINKLER CONTROL BUTTERFLY Control STAND PIPE ROOF TEST HEADER CONTROL 6 INCH BUTTERFLY Specifications: NORMALLY CLOSED Pressure Reducing 8TH FLOOR PRESSURE REDUCING FIRE HOSE Waterflow Switch 8TH FLOOR FIRE SPRINKLER WATER FLOW PRV-1 Notes: FLOWED 25GPM AT Time to Alarm (sec.): 33 OWNER: Except as noted, the building is occupied with the same occupancy classification and hazard of contents as last inspection. Also, the system has remained in service without modification and been free of actuation of devices or alarms. INSPECTOR: I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operational condition upon completion of this inspection
19 except as noted.
20 Report of Inspection/Test West Howard Lane Suite 4 Austin, Texas Phone: Fax: Inspection Type: Sprinkler - 3 Year, Sprinkler - Annual, Standpipe & Hose Annual Inspection Date: 2/24/217 1::2 AM Building Address:88 South Independence Boulevard Building Name: Property: Wilson Lending Corporation Owner/Agent: Conducted by: Doug Wilson License: RMEI- System Name: 3RD FLOOR DATA SERVER ROOM PRE-ACTION System Type: Sprinkler - Pre-Action Fail N/A SI Sprinkler Systems NFPA General C.SS.1 System inspection and test results System(s) 3RD FLOOR DATA SERVER ROOM PRE-ACTION Tag Color BLUE C.SS.2 Record work order number Work Order # 669 Owner Information OI.SS.1.3 Are all fire protection systems in service? Notifications Prior to Testing and Maintenance C.SS.94 Notifications made prior to testing or maintenance? Supervisory Service Name Time of Notification NORTH STAR FIRE ALARM MONITORING 7AM AHJ Name Time of Notification AUSTIN FIRE DISTPATCH 7AM Building Management Name CHRIS DAVIS
21 Time of Notification 6:3AM Control s IW.SS.2.1 Control valves identified and have proper signage? IW.SS.2.3 s are in normal open or closed position? IW.SS.2.4 s are sealed, locked, or supervised? IW.SS.2.5 s are free from external leaks? IM.SS.93 s are accessible and protected from physical damage? TA.SS.3.1 Each control valve operated through full range and returned to normal position? TS.SS.3.1 supervisory switches indicate movement? MA.SS.1 Operating stems of all OS&Y valves lubricated, completely closed, and reopened? Main Drain TQ.SS.3.1 Main drain test: Flow observed? Results comparable to previous test? Test Results System 3RD FLOOR DATA SERVER ROOOM PRE-ACTION Static Pressure (psi) 99 Residual Pressure (psi) 65 Restored Pressure (psi) 11 Preaction /Deluge s ID.SS.1 enclosure temperature at 4 degrees F (4.4 degrees C) minimum? IW.SS.4.1 Gauges in good condition and show normal air and water pressure? IM.SS.4.3 External inspection of valves passed? IA.SS.914 Internal inspection of valves passed? TQ.SS.5.1 Priming water level tested and passed? IQ.SS.925 Low air pressure alarm tested? TQ.SS.5.3 s free of grease/other sealing materials? TA.SS.4.3 Preaction system trip test - results comparable to design values? MA.SS.2 During trip test, interior of preaction or deluge valve cleaned and parts repaired / replaced as needed? MO.SS.1.2 Maintenance performed per manufacturer's instructions? Gauges IM.SS.919 Gauges in good condition and displaying normal pressure? Last Test Date 216 Year of Gauge 216 Waterflow Devices IQ.SS.1 Waterflow and supervisory devices free of physical damage? Sprinklers IA.SS.5.1 Sprinklers are oriented correctly (upright, pendent, sidewall)?
22 IA.SS.5.3 Sprinklers free from paint, corrosion, leakage, or other damage or impairment. IA.SS.5.6 Minimum sprinkler clearance maintained? IA.SS.5.7 Proper number and type of spares on hand? Fire Department Connections IQ.SS.4.1 FD connections (exterior) are visible, accessible, and in good condition. IQ.SS.4.2 Couplings or swivels are not damaged and rotate smoothly. IQ.SS.4.3 Plugs or caps are in place and undamaged. IQ.SS.4.4 Gaskets are in place and in good condition. IQ.SS.4.5 Identification signs are in place. IQ.SS.4.6 Check valve is not leaking. IQ.SS.4.7 Automatic drain valve is in place and operating properly. IQ.SS.4.8 Connection clapper(s) is in place and operating properly. Piping, Hangers, and Braces IA.SS.3 Visible pipe hangers and seismic braces not damaged or loose? IA.SS.4.1 Pipe and fittings in good condition, free of mechanical damage, leakage, and corrosion? IA.SS.4.2 It appears that the sprinkler piping is not subjected to external loads? Backflow Prevention Assemblies IW.SS.98 Backflow preventer isolation valves are in the normal open position? General Inspection, Testing, and Maintenance IQ.SS.2 Hydraulic nameplate attached securely and legible? MO.SS.3 Obstruction investigation for system or yard main piping conducted if required? CONDUCTED ON 9/216 NEXT 5 YEAR INTERNAL INSPECTION DUE 9/221. Notifications After Testing and Maintenance C.SS.92 Notifications made after testing or maintenance? Supervisory Service Name Time of Notification NORTH STAR FIRE ALARM MONITORING 83AM AHJ Name Time of Notification AUSTIN FIRE DISTPATCH 83AM Fail N/A C.SS.999 Capture customer and inspector signatures. SI Standpipe and Hose Systems NFPA Notifications After Testing and Maintenance C.NA.2 Capture customer and inspector signatures. OWNER: Except as noted, the building is occupied with the same occupancy classification and hazard of contents as last inspection. Also, the system has remained in service without modification and been free of
23 actuation of devices or alarms. INSPECTOR: I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
24 Report of Inspection/Test West Howard Lane Suite 4 Austin, Texas Phone: Fax: Occupant Name: Address: Wilson Lending Corporation Inspection Date: 2/24/ South Independence Boulevard InspectionType: City: Austin Inspected By: Doug Wilson State: TX Zip Code: 781 Pump - Annual, Sprinkler - 3 Year, Sprinkler - Annual, Standpipe & Hose Annual Fail - Corrected Fail Total Inspected Total Devices Control Dry Pipe Low Air Supervisory Switch Preaction Pressure Reducing Waterflow Switch Floor -1 Fail - Corrected Fail Total Inspected Total Devices Dry Pipe Low Air Supervisory Switch PARKING GARAGE FIRE Control PARKING GARAGE DRY 4 INCH OS&Y SPRINKLER RISER ROOM SYSTEM CONTROL PARKING GARAGE FIRE SPRINKLER RISER ROOM Dry Pipe PARKING GARAGE FIRE Low Air SPRINKLER RISER Supervisory ROOM Switch Pressure Reducing PARKING GRAGE DRY SYSTEM PARKING GARAGE DRY SYSTEM HI/LOW -1 FLOOR PRESSURE REDUCING FIRE HOSE 4 INCH FIRELOCK S/768 Type of trip test performed today (partial/full): FULL Pressure before test (air/water): 14/11 Trip air pressure: 4 Trip time: 26 Water delivery time to Inspector Test (ITV): 45 PS-4 Tripped at (air pressure): 1 PSI 2.5 INCH POTTER PRV-1 Notes: FLOWED 25GPM AT
25 Floor 1 Fail - Corrected Fail Total Inspected Total Devices Control Control 1ST FLOOR FIRE SPRINKLER CONTROL Control STAND PIPE ISOLATION CONTROL 6 INCH BUTTERFLY Pressure Reducing 1ST FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 1ST FLOOR FIRE SPRINKLER Time to Alarm (sec.): 37 Floor 2 Fail - Corrected Fail Total Inspected Total Devices Control 2ND FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 2ND FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 2ND FLOOR FIRE SPRINKLER Time to Alarm (sec.): 41 Floor 3 Fail - Corrected Fail Total Inspected Total Devices Control Low Air Supervisory Switch Preaction RD FLOOR ROOM 2Y.OO3 Control 3RD FLOOR DATA SERVER ROOM PRE-ACTION CONTROL 2.5 INCH OS&Y 3RD FLOOR Low Air ROOM 2Y.OO3 Supervisory Switch 3RD FLOOR Preaction ROOM 2Y.OO3 3RD FLOOR DATA SERVER ROOM PRE-ACTION HI/LOW 3RD FLOOR DATA SERVER ROOM PRE-ACTION PS-4 PRESSURE 2.5 INCH VICTAULIC FIRELOCK NXT LP S/769 Tripped at (air pressure): 8/17 Type of trip test performed today (partial/full): FULL Pressure before test (air/water): 12/129
26 Control 3RD FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 3RD FLOOR PRESSURE REDUCING FIRE HOSE Waterflow Switch 3RD FLOOR FIRE SPRINKLER WATER FLOW PRV-1 Trip air pressure: 3 Trip time: 14 Water delivery time to Inspector Test (ITV): 36 Notes: FLOWED 25GPM AT Time to Alarm (sec.): 37 Floor 4 Fail - Corrected Fail Total Inspected Total Devices Control 4TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 4TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 4TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 4 Floor 5 Fail - Corrected Fail Total Inspected Total Devices Control 5TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 5TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 5TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 4 Floor 6 Fail - Corrected Fail Total Inspected Total Devices
27 Control 6TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 6TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 6TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 45 Floor 7 Fail - Corrected Fail Total Inspected Total Devices Control 7TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 7TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 7TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 39 Floor 8 Fail - Corrected Fail Total Inspected Total Devices Control Control 8TH FLOOR FIRE 2.5 INCH SPRINKLER CONTROL BUTTERFLY Control STAND PIPE ROOF TEST HEADER CONTROL 6 INCH BUTTERFLY Specifications: NORMALLY CLOSED Pressure Reducing 8TH FLOOR PRESSURE REDUCING FIRE HOSE Waterflow Switch 8TH FLOOR FIRE SPRINKLER WATER FLOW PRV-1 Notes: FLOWED 25GPM AT Time to Alarm (sec.): 33 OWNER: Except as noted, the building is occupied with the same occupancy classification and hazard of contents as last inspection. Also, the system has remained in service without modification and been free of actuation of devices or alarms. INSPECTOR: I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operational condition upon completion of this inspection
28 except as noted.
29 Report of Inspection/Test West Howard Lane Suite 4 Austin, Texas Phone: Fax: Inspection Type: Sprinkler - 3 Year, Sprinkler - Annual, Standpipe & Hose Annual Inspection Date: 2/24/217 1::2 AM Building Address:88 South Independence Boulevard Building Name: Property: Wilson Lending Corporation Owner/Agent: Conducted by: Doug Wilson License: RMEI- System Name: PARKING GARAGE DRY SYSTEM System Type: Sprinkler - Dry Pipe Fail N/A SI Sprinkler Systems NFPA General C.SS.1 System inspection and test results System(s) PARKING GARAGE DRY SYSTEM Tag Color BLUE C.SS.2 Record work order number Work Order # 669 Control s IW.SS.2.1 Control valves identified and have proper signage? IW.SS.2.3 s are in normal open or closed position? IW.SS.2.4 s are sealed, locked, or supervised? IW.SS.2.5 s are free from external leaks? IM.SS.93 s are accessible and protected from physical damage? TA.SS.3.1 Each control valve operated through full range and returned to normal position? TS.SS.3.1 supervisory switches indicate movement? Main Drain TQ.SS.3.1 Main drain test: Flow observed? Results comparable to previous test? Test Results System PARKING GARAGE DRY SYSTEM Static Pressure (psi) 99 Residual Pressure (psi) 7 Restored Pressure (psi) 1
30 Dry Pipe s / Quick Opening Devices ID.SS.2 enclosure temperature at 4 degrees F (4.4 degrees C) minimum? IW.SS.1.1 Gauges in good condition and show normal air and water pressure? IW.SS.5.7 Signage indicates number and location of auxiliary drains? IM.SS.5 External inspection of dry pipe valve passed? IA.SS.7.2 Interior of dry pipe valve inspected and passed? TQ.SS.6.1 Priming water level tested and passed? TQ.SS.6.2 Low air pressure alarms passed test? TQ.SS.6.3 Quick opening devices tested? TA.SS.5.2 Trip test - Results comparable to previous tests? (Partial - annually; Full - every 3 yrs) TA.SS.6 Auto air pressure maint devices tested during dry pipe valve trip test? MA.SS.3 During trip test, interior of dry pipe valve cleaned and parts repaired/replaced as needed? MA.SS.4 Condensation drained from the air compressor? MO.SS.4.1 Customer has been instructed on late fall draining/checking and locations of drum drips? Gauges IM.SS.919 Gauges in good condition and displaying normal pressure? Waterflow Devices TS.SS.2 Vane-type and pressure switch-type waterflow devices actuated and flow observed? Sprinklers IA.SS.5.1 Sprinklers are oriented correctly (upright, pendent, sidewall)? IA.SS.5.3 Sprinklers free from paint, corrosion, leakage, or other damage or impairment. IA.SS.5.6 Minimum sprinkler clearance maintained? IA.SS.5.7 Proper number and type of spares on hand? Piping, Hangers, and Braces IA.SS.3 Visible pipe hangers and seismic braces not damaged or loose? IA.SS.4.1 Pipe and fittings in good condition, free of mechanical damage, leakage, and corrosion? IA.SS.4.2 It appears that the sprinkler piping is not subjected to external loads? General Inspection, Testing, and Maintenance IQ.SS.2 Hydraulic nameplate attached securely and legible? Fail N/A Notifications After Testing and Maintenance C.SS.92 Notifications made after testing or maintenance? SI Standpipe and Hose Systems NFPA Notifications After Testing and Maintenance C.NA.2 Capture customer and inspector signatures. OWNER: Except as noted, the building is occupied with the same occupancy classification and hazard of contents as last inspection. Also, the system has remained in service without modification and been free of actuation of devices or alarms.
31 INSPECTOR: I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
32 Report of Inspection/Test West Howard Lane Suite 4 Austin, Texas Phone: Fax: Occupant Name: Address: Wilson Lending Corporation Inspection Date: 2/24/ South Independence Boulevard InspectionType: City: Austin Inspected By: Doug Wilson State: TX Zip Code: 781 Pump - Annual, Sprinkler - 3 Year, Sprinkler - Annual, Standpipe & Hose Annual Fail - Corrected Fail Total Inspected Total Devices Control Dry Pipe Low Air Supervisory Switch Preaction Pressure Reducing Waterflow Switch Floor -1 Fail - Corrected Fail Total Inspected Total Devices Dry Pipe Low Air Supervisory Switch PARKING GARAGE FIRE Control PARKING GARAGE DRY 4 INCH OS&Y SPRINKLER RISER ROOM SYSTEM CONTROL PARKING GARAGE FIRE SPRINKLER RISER ROOM Dry Pipe PARKING GARAGE FIRE Low Air SPRINKLER RISER Supervisory ROOM Switch Pressure Reducing PARKING GRAGE DRY SYSTEM PARKING GARAGE DRY SYSTEM HI/LOW -1 FLOOR PRESSURE REDUCING FIRE HOSE 4 INCH FIRELOCK S/768 Type of trip test performed today (partial/full): FULL Pressure before test (air/water): 14/11 Trip air pressure: 4 Trip time: 26 Water delivery time to Inspector Test (ITV): 45 PS-4 Tripped at (air pressure): 1 PSI 2.5 INCH POTTER PRV-1 Notes: FLOWED 25GPM AT
33 Floor 1 Fail - Corrected Fail Total Inspected Total Devices Control Control 1ST FLOOR FIRE SPRINKLER CONTROL Control STAND PIPE ISOLATION CONTROL 6 INCH BUTTERFLY Pressure Reducing 1ST FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 1ST FLOOR FIRE SPRINKLER Time to Alarm (sec.): 37 Floor 2 Fail - Corrected Fail Total Inspected Total Devices Control 2ND FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 2ND FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 2ND FLOOR FIRE SPRINKLER Time to Alarm (sec.): 41 Floor 3 Fail - Corrected Fail Total Inspected Total Devices Control Low Air Supervisory Switch Preaction RD FLOOR ROOM 2Y.OO3 Control 3RD FLOOR DATA SERVER ROOM PRE-ACTION CONTROL 2.5 INCH OS&Y 3RD FLOOR Low Air ROOM 2Y.OO3 Supervisory Switch 3RD FLOOR Preaction ROOM 2Y.OO3 3RD FLOOR DATA SERVER ROOM PRE-ACTION HI/LOW 3RD FLOOR DATA SERVER ROOM PRE-ACTION PS-4 PRESSURE 2.5 INCH VICTAULIC FIRELOCK NXT LP S/769 Tripped at (air pressure): 8/17 Type of trip test performed today (partial/full): FULL Pressure before test (air/water): 12/129
34 Control 3RD FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 3RD FLOOR PRESSURE REDUCING FIRE HOSE Waterflow Switch 3RD FLOOR FIRE SPRINKLER WATER FLOW PRV-1 Trip air pressure: 3 Trip time: 14 Water delivery time to Inspector Test (ITV): 36 Notes: FLOWED 25GPM AT Time to Alarm (sec.): 37 Floor 4 Fail - Corrected Fail Total Inspected Total Devices Control 4TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 4TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 4TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 4 Floor 5 Fail - Corrected Fail Total Inspected Total Devices Control 5TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 5TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 5TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 4 Floor 6 Fail - Corrected Fail Total Inspected Total Devices
35 Control 6TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 6TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 6TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 45 Floor 7 Fail - Corrected Fail Total Inspected Total Devices Control 7TH FLOOR FIRE SPRINKLER CONTROL Pressure Reducing 7TH FLOOR PRESSURE Notes: FLOWED 25GPM AT REDUCING FIRE HOSE PRV-1 Waterflow Switch 7TH FLOOR FIRE SPRINKLER Time to Alarm (sec.): 39 Floor 8 Fail - Corrected Fail Total Inspected Total Devices Control Control 8TH FLOOR FIRE 2.5 INCH SPRINKLER CONTROL BUTTERFLY Control STAND PIPE ROOF TEST HEADER CONTROL 6 INCH BUTTERFLY Specifications: NORMALLY CLOSED Pressure Reducing 8TH FLOOR PRESSURE REDUCING FIRE HOSE Waterflow Switch 8TH FLOOR FIRE SPRINKLER WATER FLOW PRV-1 Notes: FLOWED 25GPM AT Time to Alarm (sec.): 33 OWNER: Except as noted, the building is occupied with the same occupancy classification and hazard of contents as last inspection. Also, the system has remained in service without modification and been free of actuation of devices or alarms. INSPECTOR: I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operational condition upon completion of this inspection
36 except as noted.
Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System
Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Building/Business Name: Address of Property: Inspector Name: Joe Price THE CORNERSTONE 1425 NE 7TH AVENUE PORTLAND OR Date
More informationAnnual Water-Based Fire Protection Systems Inspection
Annual Water-Based Fire Protection Systems Inspection 2425 Amann Drive Belleville, IL 62220 www.boyerfire.com Phone: 618-222-1500 Fax: 618-222-1502 Inspector: Steve Love Inspection date: 04/03/17 Inspection
More informationOxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)
Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including
More informationFIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
SANTA MONICA FIRE DEPARTMENT Fire Prevention Division 333 Olympic Drive 2 nd Floor Santa Monica, CA 90401 310-458-8915 / Fax 310-395-3395 FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
More information2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7
WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves
More informationSPRINKLER SYSTEM DRY WET
Seattle Fire Department Confidence Test Report (use one form per sys.) 206-386-1448 Confidence Testing Officer 206-615-1068 (fax) 206-233-7219 Red Tag Hotline SPRINKLER SYSTEM DRY WET Status Given CONFIDENCE
More informationMAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and
More informationA. This section includes design and performance information for fire protection and suppression systems.
SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials
More informationSystem Test Report CLEAN AGENT
City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information
More informationCubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM
SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for
More informationESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 8 Annual Sprinkler System Inspection Revised
Engine Module Page 1 of 8 ANNUAL INSPECTOR S TEST Note: In 2014 the Escondido Fire Department discontinued performing an Inspector s Test on sprinkler systems electing to inspect the system as outlined
More informationSECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE
SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department
More informationOwner/Operator Guide for Successful Sprinkler and Fire Pump Systems
Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems Adam Olomon, P.E. Associate Consultant Fire & Life Safety and Fire Protection Introduction Adam Olomon Licensed Professional Engineer
More informationInspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems
Inspection of Fire Sprinkler Systems NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Objective To familiarize Facility Managers with the process of routine inspection
More informationSECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE
SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED
More informationC. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.
SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this
More informationInspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance. For
Inspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance For CarDon & Associates Fall Creek Health & Living Prepared by: L.Thompson/T.Roe 7/31/2014 Report Length:
More information2. Welding Materials and Procedures shall conform to the ASME Code.
PART 1 GENERAL 1.01 Scope of Standard A. The design guidelines contained herein include the requirements for systems, materials, fittings and valves utilized for fire protection systems at Sam Houston
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL
SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationGas Station & C Store SECTION CWM Job No
SECTION 21 1300 - PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract
More informationResidential Fire Sprinkler Inspection
Residential Fire Sprinkler Inspection Hickory, NC 88.38.6363 Charleston, SC 843.78.08 Greensboro, NC 336.373.3973 Columbia, SC 803.99.00 Raleigh, NC 99.834.9644 Greenville, SC 864.458.7070 Charlotte, NC
More informationWest District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8
City of Ottawa Project No. CR006230 Page 1 of 8 PART 1 - GENERAL 1.1 Reference Standards.1 Conform to the following:.1 Provincial and municipal building and fire regulations as approved by Provincial Fire
More informationSECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE
SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationSECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section
PART 1 - GENERAL 1.00 GENERAL PROVISIONS A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section 1.01 DESCRIPTION OF WORK A. Work Included: Provide
More informationSECTION DRY-PIPE SPRINKLER SYSTEMS
SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply
More informationGlobal Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More informationFire Sprinkler Plan Submittal Form
Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10
More informationQuick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/
Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA 25 2017 & NFPA 13/72 2016 The purpose of this guide is to help you determine if the system will work as
More informationMontgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040
Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler
More informationFIRE INSPECTION CHECKLIST
Applicable Base Codes FIRE INSPECTION CHECKLIST Florida Fire Prevention Code, 5th Edition NFPA 1, Uniform Fire Code, Florida 2012 Edition NFPA 101, Life Safety Code, Florida 2012 Edition NFPA 13, 2010
More informationDeluge/Preaction Systems Annotated Instructor s Guide
Deluge/Preaction Systems Annotated Instructor s Guide Module 18301-07 Module Overview This module covers different types of preaction and deluge systems. It discusses deluge valves, auxiliary detection
More informationDeluge/Preaction Systems Annotated Instructor s Guide
Deluge/Preaction Systems Annotated Instructor s Guide Module 18301-13 Module Overview This module covers different types of preaction and deluge systems. It discusses deluge valves, auxiliary detection
More information1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:
SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.
More informationSECTION : FIRE PROTECTION SYSTEMS
SECTION 21 00 10: FIRE PROTECTION SYSTEMS 1. GENERAL A. This section applies to the design and performance information for fire protection and suppression systems. B. All fire protection materials and
More informationA. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:
SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationGlobal Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More informationFIRE SAFETY SYSTEMS MAINTENANCE INFORMATION
FIRE SAFETY SYSTEMS MAINTENANCE INFORMATION To be kept in school administration office Crown Copyright, Province of Nova Scotia 2004 Prepared by Nova Scotia Department of Education No part of this document
More informationEnvironmental Health & Safety
Environmental Health & Safety Oklahoma State University FIRE SPRINKLER SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu
More informationRevision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.
SECTION 211300 FIRE SUPPRESSION SYSTEMS 1.0 All new and renovated buildings shall be provided with automatic sprinklers throughout and fire standpipe systems. The design and installation of these systems
More informationSECTION FIRE PUMP AND CONTROLS
SECTION 15320 FIRE PUMP AND CONTROLS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Fire pump, jockey pump, and controls including necessary accessories as shown in Construction Documents, specified
More informationTECHNICAL DATA OBSOLETE
January 27, 2012 311a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking supervised Single Interlocked Preaction Systems utilize a Viking Deluge Valve and a pneumatically pressurized automatic sprinkler system.
More informationB. The sprinkler system shall be designed to meet the more stringent of the requirements of NFPA 13 and FM Global requirements.
SECTION 21 13 13 FIRE PROTECTION SPRINKLER SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section includes labor and materials for the installation of a hydraulically calculated automatic, wet-pipe sprinkler
More informationUSAutomatic Sprinkler Corporation
Inspection Report Information For CITY OF WESTFIELD - PUBLIC SAFETY Prepared by: T.Hughes, C.Gibbs a fire protection company Sheet 1 of 2 Phone: (317) 573-8160 Fax: (317) 573-8161 110370 REPORT OF INSPECTION
More informationDIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES
DIVISION 21 FIRE SUPPRESSION PART 1 GENERAL 1.01 DESCRIPTION A. Provide UL listed, FM approved listed fire protection specialties or accessories as required by either the equipment manufacturer or the
More informationSECTION SPRINKLER SYSTEMS
SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department
More informationAUTOMATIC FIRE SPRINKLER SYSTEMS
MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system
More informationSECTION FIRE SUPPRESSION SYSTEMS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2
More informationTECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.
Page 1 of 9 1. (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally held closed by supervisory
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationSECTION SPRINKLER SYSTEMS
SECTION 13900 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,
More informationDIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION
DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation
More informationSECTION Fire Pumps
SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.
More informationDIVISION 21 - FIRE SUPPRESSION
DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,
More informationTECHNICAL DATA. 319a. January 27, 2012
January 27, 2012 319a 1. DEsCrIpTIoN (Refer to Figures 1-3.) Viking Electric/Pneumatic Double Interlocked Preaction Systems utilize a Viking deluge valve controlled by a pneumatic actuator (E.1), normally
More informationDESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES
SECTION 21 30 00 FIRE PUMPS GENERAL This standard provides general requirements of The University of South Alabama in Mobile Alabama for fire pumps. This document is not intended to serve as a guide specification.
More informationChapter 4: Fire Protection Systems
Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system
More informationWayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No
SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationPHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps
Note: The A/E must choose all design values in brackets below before using in project specifications 1 General 1.1 Provide UL listed and FM approved fire pump complete with pump, driver, controller and
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:
More informationSECTION WET-PIPE SPRINKLER SYSTEMS
SECTION 21 13 13 PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The design and installation of a hydraulically
More informationDISTRICT OF SECHELT. Inspection and Testing of Fire Protection Equipment Bylaw No. 397, 2002
DISTRICT OF SECHELT Inspection and Testing of Fire Protection Equipment Bylaw No. 397, 2002 WHEREAS Section 653 of the Local Government Act authorizes Council by bylaw to regulate businesses, business
More informationSprinkler Inspection Certificate
Sprinkler Inspection Certificate For New Dimensions High School 4900 Old Pleasant Hilll Road Kissimmee, FL 34746 Tested to NFPA 25 Standards This Inspection was performed in accordance with applicable
More informationEXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5
UNIT PRICING IS A "NOT TO EXCEED" PRICE EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5 Unit Pricing to perform all required Test
More informationInspection and Testing of Water-Based Systems
Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level II Content Outline The candidate for NICET certification at Level II in the Inspection and Testing of Water- Based
More informationSECTION ELECTRIC-DRIVEN, FIRE PUMPS
SECTION 21 30 13 ELECTRIC-DRIVEN, FIRE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between // --- // if not applicable to the project. Also delete any other item or paragraph including
More informationDIVISION 21 - FIRE SUPPRESSION
DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,
More informationUBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6
Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 20 00 05 Mechanical - General Requirements.2 Section 22 05 00 Plumbing - General Requirements.3 UBC Standard Fire Hydrant Drawings.4 Section
More informationService Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT
58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE PUMP REVIEW Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;
More informationWorldwide Contacts.
Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed
More informationADDENDUM NO. 3 March 19, 2018
ADDENDUM NO. 3 March 19, 2018 PROJECT: MT. VIEW ELEMENTARY CASSIA SCHOOL DISTRICT NO 151 BURLEY, IDAHO The following addenda apply to the Project Manual and / or Drawings for this project and shall be
More informationSECTION WATER BASED FIRE SUPPRESSION SYSTEMS
PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University-San Marcos for automatic fire sprinkler and standpipe systems.
More informationWET-PIPE SPRINKLER SYSTEMS
SECTION 211313 - WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipes, fittings, and specialties. 2. Fire-protection valves. 3. Fire-department connections. 4. Sprinklers.
More informationTHE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION
SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression
More informationCITY OF PASADENA FIRE DEPARTMENT
Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in
More informationUNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1
GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and
More informationSlide 2 NFPA 25: 2017
Slide 1 Changes for 2017 NFPA 25 Handbook Supplement 8 contains a table highlighting the significant technical changes to NFPA 25 for the 2017 edition, along with a brief comment regarding the reason for
More informationB. Section Identification for Fire Suppression Piping and Equipment.
SECTION 211300 - FIRE SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 RELATED
More informationSECTION PREACTION SPRINKLER SYSTEMS
PART 1 GENERAL SECTION 211316 - PREACTION SPRINKLER SYSTEMS 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationA. All Fire Suppression System design and installation shall comply with the most current and adopted version of NFPA 13.
21 10 00 PART 1 - GENERAL 1.01 SCOPE A. The following standards and procedures apply to the design and installation of all wet pipe and dry pipe sprinkler systems. The design of fire suppression systems
More informationMAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1040 East Hillsdale Blvd Foster City, CA 94404 (650) 522-7940 FAX: (650) 522-7941 MAINTENANCE AND SERVICE OF AUTOMATIC FIRE
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review Minooka Fire Protection District Maintaining Your Fire Safety Systems Fire continues to be a major threat
More informationTotalPac X Single interlock SUREFIRE system
DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a trim totally preassembled, pre-wired and factory tested. All electrical and mechanical components of
More informationCITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS
CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS Fire Protection Systems includes the following: Alternate Fire Suppression Systems Atrium Fire Protection Systems Automatic Fire Sprinkler
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationFalse Sense of Security???
IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire
More informationTotalPac 3 Wet pipe system c/w retard chamber
DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of an integrated wet type sprinkler riser assembly with retard chamber, totally pre-assembled, prewired and
More informationTotalPac 3 Firecyle III Deluge Remote controlled system
(Optional) DESCRIPTION This TOTALPAC 3 integrated fire protection system by FireFlex Systems Inc. consists of a Firecycle III system trim totally preassembled, pre-wired and factory tested. All electrical
More informationSPRINKLERS TABLE OF CONTENTS
SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
More information1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.
Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1
More informationTechnical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:
Worldwide Contacts www.tyco-fire.com DV-5 Red-E Cabinet Integrated Preaction Fire Protection Package General Description The TYCO DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed
More informationTECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE
Page 1 of 12 1. DESCRIPTION (Refer to Figures 1-6.) Viking Electric/Pneu-Lectric Double Interlocked Preaction Systems utilize a Viking deluge valve, pneumatic supervision of the automatic sprinkler system,
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved;
More informationSECTION FIRE-SUPPRESSION STANDPIPES
PART 1 - GENERAL 1.1 DESCRIPTION Fire-suppression wet and manual dry standpipes. 1.2 SCOPE OF WORK SECTION 21 12 00 A. Design, installation and testing shall be in accordance with NFPA 14 except for specified
More informationPLAN REVIEW CHECKLIST
PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor
More informationTABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5
DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING
More informationTotalPac X Firecycle III Preaction Double interlock system
DESCRIPTION This TOTALPAC X integrated fire protection system by FireFlex Systems Inc. consists of a multicycling Firecycle III system trim totally pre-assembled, pre-wired and factory tested. All electrical
More informationTECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5
Page 1 of 5 1. SYSTEM DESCRIPTION Viking supervised, single interlocked preaction pre-primed systems utilize a Viking Deluge Valve (A.1) and a hydraulically pressurized automatic sprinkler system. The
More informationSECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS
SECTION 15501 WET AUTOMATIC FIRE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Wet automatic fire sprinkler systems including fire pump, fire pump controller, alarms, safety devices,
More information