Annual Water-Based Fire Protection Systems Inspection

Size: px
Start display at page:

Download "Annual Water-Based Fire Protection Systems Inspection"

Transcription

1 Annual Water-Based Fire Protection Systems Inspection 2425 Amann Drive Belleville, IL Phone: Fax: Inspector: Steve Love Inspection date: 04/03/17 Inspection Location 5555 West Park Ave. St. Louis, MO Phone: Fax: Customer 2425 Amann Drive Belleville, IL Phone: Fax: Inspection performed in accordance with NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2014 edition. A-IP Page 1 of 5

2 Building Owner/Representative Is building currently occupied Has building occupancy, hazard, water supply or building arrangement affecting system effectiveness remained the same since last inspection ( ) Are all fire protection systems in service (4.5.4) Areas containing water-filled piping used for fire sprinkler systems, maintain a minimum temperature of 40 deg F, and are not exposed to freezing conditions. ( ) Owner/Representative Signature System Summary Number of Systems at Site Items Total Systems Wet System 1 Wet System Sprinkler heads appear free of corrosion, foreign material, paint or damage, no signs of leakage and heads/deflectors installed in proper orientation ( ) Escutcheons and cover plates in place, if applicable. ( ) Minimum clearance maintained below all sprinklers ( ) # replacement sprinkler heads per number installed in the head box comply: 6 per 1-300: 12 per 301 to 1,000: 24 per 1,000 ( ) Sprinkler head wrench for each type head provided in head box ( ) List of sprinklers installed on the property posted on head box. ( ) System piping and fittings free of mechanical damage, leaks, corrosion, misalignment, or other loads or pipe hung from system (5.2.2) Pipe hangers and seismic braces secure and undamaged (5.2.3) Sprinklers in building that are at least 50 years old, has sprinkler sample been tested ( ) Fast response sprinklers over 20 years old, has sprinkler sample been tested ( ) Dry sprinklers in service for 10 years, has sprinkler sample been tested ( ) Exterior of connection in good condition and gauge operable ( ) Hydraulic nameplate, if applicable, securely attached and is legible (5.2.6) Pressure (psi) shown on the pressure gauge. 43 Size of main drain 2" Pressure (psi) shown on Supply Water pressure gauge. (13.2.5) 43 Residual Pressure with valve open (13.2.5) 30 Static Pressure after valve closed (13.2.5) 35 Main Drain Test Pressure less than 10% reduction in flow from original acceptance test or previous test results ( ) Adequate drainage available (13.2.4) Valve Status Test - Valves open when returned to service. ( ) Gauge on valve, when compared to calibrated gauge is error less than 3% full or gauge has been recalibrated or replaced (5.3.2) Other Components Fire Department Connection FDC visible and accessible, without damage and signs in place (13.7.1) Couplings and swivels free of damage and rotate smoothly (13.7.1) Caps, plugs and gaskets in place and free from damage (13.7.1) A-IP Page 2 of 5

3 Fire Department Connection Check valve clapper free from leaks and automatic drain valve in place and operating properly (13.7.1) Interior of the connection free of obstructions. (13.7.1(9)) Internal inspection of check valve - components operate properly, cleaned/repaired as needed ( ) Hydrostatic test results of piping from FDC to check valve acceptable. (13.7.4) Control Valves Type Area/Location Model Size Signs Condition Position Secured Exercised Seal Control Valve - locked/tamper Control Valve - locked/tamper Backflow #1 Backflow #2 Butterfly 6" NA Butterfly 6" NA Alarm Devices Type Area/Location Visual Insp Functional Test Horn/Strobe Waterflow Alarm - Pressure Switch/Vane 62 Seconds Comments A-IP Page 3 of 5

4 Deficiencies *PAR response indicated " After Repair". Technician notes a deficiency of a device, and repairs the deficiency during inspection. Exterior of connection in good condition and gauge operable ( ) Technician Response: Piping on main drain is severely corroded. Escutcheons and cover plates in place, if applicable. ( ) Technician Response: Missing 1 fully recessed escutcheon. # replacement sprinkler heads per number installed in the head box comply: 6 per 1-300: 12 per 301 to 1,000: 24 per 1,000 ( ) Technician Response: Need fully recessed sprinkler heads. There are 2 of them in East store front space. And a head wrench to match. List of sprinklers installed on the property posted on head box. ( ) Technician Response: No list provided. Not Inspected Fire Department Connection Question: Internal inspection of check valve - components operate properly, cleaned/repaired as needed ( ) Question: Hydrostatic test results of piping from FDC to check valve acceptable. (13.7.4) Question: Gauge on valve, when compared to calibrated gauge is error less than 3% full or gauge has been recalibrated or replaced (5.3.2) A-IP Page 4 of 5

5 Liability Release Statement: The owner and/or designated representative acknowledges the responsibility of the operating condition of the component parts at the time of this inspection. It is agreed that the inspection service provided by the contractor as prescribed herein is limited to performing a visual inspection and/or routine testing, and any investigation or unscheduled testing, modification, maintenance, repair, etc., of the component parts is not included as part of the inspection work performed. It is further understood that all information contained herein is provided to the best of the knowledge of the party providing such information. 4/3/17 4/3/17 Customer: Rich Boyer Tech: Steve Love A-IP Page 5 of 5

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Building/Business Name: Address of Property: Inspector Name: Joe Price THE CORNERSTONE 1425 NE 7TH AVENUE PORTLAND OR Date

More information

SPRINKLER SYSTEM DRY WET

SPRINKLER SYSTEM DRY WET Seattle Fire Department Confidence Test Report (use one form per sys.) 206-386-1448 Confidence Testing Officer 206-615-1068 (fax) 206-233-7219 Red Tag Hotline SPRINKLER SYSTEM DRY WET Status Given CONFIDENCE

More information

Report of Inspection/Test

Report of Inspection/Test Report of Inspection/Test 4616-2 West Howard Lane Suite 4 Austin, Texas 78727 Phone: 512-833-8 Fax: 512-833-7862 Inspection Type: Pump - Annual Inspection Date: 2/24/217 1::2 AM Building Address:88 South

More information

Residential Fire Sprinkler Inspection

Residential Fire Sprinkler Inspection Residential Fire Sprinkler Inspection Hickory, NC 88.38.6363 Charleston, SC 843.78.08 Greensboro, NC 336.373.3973 Columbia, SC 803.99.00 Raleigh, NC 99.834.9644 Greenville, SC 864.458.7070 Charlotte, NC

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

Environmental Health & Safety

Environmental Health & Safety Environmental Health & Safety Oklahoma State University FIRE SPRINKLER SYSTEM STANDARD Environmental Health and Safety University Health Services Suite 002 Stillwater, OK 74078 (405) 744-7241 www.ehs.okstate.edu

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 8 Annual Sprinkler System Inspection Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 8 Annual Sprinkler System Inspection Revised Engine Module Page 1 of 8 ANNUAL INSPECTOR S TEST Note: In 2014 the Escondido Fire Department discontinued performing an Inspector s Test on sprinkler systems electing to inspect the system as outlined

More information

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805) Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including

More information

Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/

Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/ Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA 25 2017 & NFPA 13/72 2016 The purpose of this guide is to help you determine if the system will work as

More information

Fire Sprinkler System Design and Installation Requirements

Fire Sprinkler System Design and Installation Requirements Fire Sprinkler System Design and Installation Requirements The Park City Fire Service District (PCFD) and Park City Municipal Corporation (PCMC) have made the following amendments to the State of Utah

More information

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT SANTA MONICA FIRE DEPARTMENT Fire Prevention Division 333 Olympic Drive 2 nd Floor Santa Monica, CA 90401 310-458-8915 / Fax 310-395-3395 FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves

More information

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems

Inspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Inspection of Fire Sprinkler Systems NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Objective To familiarize Facility Managers with the process of routine inspection

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The design and installation of a hydraulically

More information

FIRE SPRINKLER SYSTEMS POLICY

FIRE SPRINKLER SYSTEMS POLICY FIRE SPRINKLER SYSTEMS POLICY Revised 1/1/17 DESIGN AND SUBMITTAL REQUIREMENTS All new and existing fire sprinkler systems within the jurisdiction of the City Fire Department shall meet all of the applicable

More information

ADDENDUM #1 ITB# Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015

ADDENDUM #1 ITB# Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015 ADDENDUM #1 ITB# 2015-09-002 Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015 1. Building #222, The UPS Building, has one (1) dry Sprinkler riser, valve. (This is a

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

9/15/ Cantara Lane Vista, CA (760)

9/15/ Cantara Lane Vista, CA (760) 28 th Annual AHCA/FHEA SEMINAR Sprinkler System Inspection, Testing & Maintenance 1 Speaker Information: Bob Caputo, CFPS, CET Vice President Fire & Life Safety America 657 Cantara Lane Vista, CA 92081

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST STANDPIPE SYSTEMS Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved;

More information

FIRE SPRINKLER SYSTEMS POLICY

FIRE SPRINKLER SYSTEMS POLICY FIRE SPRINKLER SYSTEMS POLICY VERSION 1.012/2015 FIRE SPRINKLER SYSTEMS Design and Submittal requirements All new and existing fire sprinkler systems within the jurisdiction of the City of San Mateo Fire

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain

More information

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,

More information

1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)

1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors) 1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors) 1. What is the minimum diameter for a non-hydraulically calculated Class III fire standpipe that is part of a combined

More information

AUTOMATIC FIRE SPRINKLER SYSTEMS

AUTOMATIC FIRE SPRINKLER SYSTEMS MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information

System Test Report CLEAN AGENT

System Test Report CLEAN AGENT City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information

More information

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT 58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the

More information

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

A. Section includes wet-pipe sprinkler system, system design, installation, and certification. SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes wet-pipe sprinkler system, system design, installation, and certification. 1.2 REFERENCES A. General: Comply

More information

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1040 East Hillsdale Blvd Foster City, CA 94404 (650) 522-7940 FAX: (650) 522-7941 MAINTENANCE AND SERVICE OF AUTOMATIC FIRE

More information

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6

UBC Technical Guidelines Section Edition Fire Protection General Requirements Page 1 of 6 Page 1 of 6 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 20 00 05 Mechanical - General Requirements.2 Section 22 05 00 Plumbing - General Requirements.3 UBC Standard Fire Hydrant Drawings.4 Section

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 DESCRIPTION Fire-suppression wet and manual dry standpipes. 1.2 SCOPE OF WORK SECTION 21 12 00 A. Design, installation and testing shall be in accordance with NFPA 14 except for specified

More information

NFPA 25 and the Influence of Liability

NFPA 25 and the Influence of Liability NFPA 25 and the Influence of Liability NFPA 25 Summit Addison, IL Northern Illinois Fire Sprinkler Advisory Board/ Illinois Fire Inspectors Association Date: Speaker: July 28, 2017 Michael J Bosma Meet

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Installation of Residential Fire Sprinkler Systems STANDARD #C-002 EFFECTIVE 03-19-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain

More information

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Port of St Helens SIA Aircraft Hanger Scappoose, OR Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance

More information

SENJU SPRINKLER CO., LTD.

SENJU SPRINKLER CO., LTD. Page:1 of 8 SENJU SPRINKLER CO., LTD. Residential, Pendent Sprinkler Model FR-RES K-Factor: 4.9 SIN: SS4451 GENERAL DESCRIPTION The Model FR-RES Residential Pendent and Recessed Pendent Sprinklers are

More information

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS

UC Santa Cruz Campus Design Guide. Includes the following sections: None DESIGN REQUIREMENTS DIVISION 21 - FIRE SUPPRESSION Includes the following sections: None DESIGN REQUIREMENTS It is the policy of City of Santa Cruz to install fire sprinkler systems in all new construction/facilities. If

More information

CITY OF PASADENA FIRE DEPARTMENT

CITY OF PASADENA FIRE DEPARTMENT Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in

More information

Gas Station & C Store SECTION CWM Job No

Gas Station & C Store SECTION CWM Job No SECTION 21 1300 - PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

micromatic Standard response Horizontal Sidewall sprinkler

micromatic Standard response Horizontal Sidewall sprinkler Page 1 of 5 1. DESCRIPTION The Micromatic Viking Standard Response Horizontal Sidewall Sprinkler VK015 is a small thermosensitive glass bulb spray sprinkler available with various finishes and temperature

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

TECHNICAL DATA. Page 1 of 6

TECHNICAL DATA. Page 1 of 6 Page 1 of 6 1. DESCRIPTION Viking Quick Response Horizontal Sidewall Sprinkler VK360 is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings to meet

More information

Standpipe Systems for Fire Protection

Standpipe Systems for Fire Protection Standpipe Systems for Fire Protection Kenneth E. Isman Standpipe Systems for Fire Protection Kenneth E. Isman University of Maryland College Park, MD, USA ISBN 978-3-319-47749-7 DOI 10.1007/978-3-319-47750-3

More information

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM

SECTION ADDENDUM NO. 1 FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL DESCRIPTION A. Furnish all materials and labor for the detailed design and installation for new fire sprinkler wet pipe systems for Buildings A through R hereafter referred

More information

quick response horizontal sidewall sprinkler vk360 (K8.0)

quick response horizontal sidewall sprinkler vk360 (K8.0) February 26, 2010 Sprinkler 43o 1. DESCRIPTION Viking Quick Response Horizontal Sidewall Sprinkler VK360 is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature

More information

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA Page 1 of 5 1. DESCRIPTION The Viking VK3021 Quick Response Pendent Sprinkler is a small thermosensitive glass bulb spray sprinkler available with various finishes and temperature ratings to meet design

More information

Inspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance. For

Inspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance. For Inspection Report Nursing Home Life Safety Code Section 4 - Annual Fire Alarm Testing and Maintenance For CarDon & Associates Fall Creek Health & Living Prepared by: L.Thompson/T.Roe 7/31/2014 Report Length:

More information

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5 DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING

More information

Data Sheet 4.16 Issue D

Data Sheet 4.16 Issue D General Description The Model RD205 Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. These are decorative and fast response. The frame of the sprinkler

More information

FIRE INSPECTION CHECKLIST

FIRE INSPECTION CHECKLIST Applicable Base Codes FIRE INSPECTION CHECKLIST Florida Fire Prevention Code, 5th Edition NFPA 1, Uniform Fire Code, Florida 2012 Edition NFPA 101, Life Safety Code, Florida 2012 Edition NFPA 13, 2010

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE June 1, 2007 1. DESCRIPTION Viking Quick Response Fusible Element Pendent Sprinklers VK330, VK332, VK353 and HP Sprinklers VK318 and VK343 are small, thermosensitive, solder link spray sprinklers available

More information

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems General Description LFII Residential Flush Horizontal Sidewall

More information

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Extended Coverage (Light Hazard) Model: RC-QR-EC, K-Factor: 5.

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Extended Coverage (Light Hazard) Model: RC-QR-EC, K-Factor: 5. Page:1 of 6 Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Extended Coverage (Light Hazard) Model: RC-QR-EC, K-Factor: 5.6, SIN: SS3561 GENERAL DESCRIPTION The Model RC-QR-EC Commercial

More information

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with

More information

LIFE SAFETY TRAINING Nebraska Health Care Association Chris Moran November 1, 2017

LIFE SAFETY TRAINING Nebraska Health Care Association Chris Moran November 1, 2017 LIFE SAFETY TRAINING Nebraska Health Care Association Chris Moran November 1, 2017 WHO WE ARE We are a global company offering specialty engineering and consulting services for the built environment. We

More information

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21 Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.

More information

Residential Flush Horizontal Side-Wall Sprinkler Model HF-RES,K=4.2 (SIN / SS4423) (PTFE gasketed orifice seal design)

Residential Flush Horizontal Side-Wall Sprinkler Model HF-RES,K=4.2 (SIN / SS4423) (PTFE gasketed orifice seal design) Page:1 of 5 Residential Flush Horizontal Side-Wall Sprinkler Model HF-RES,K=4.2 (SIN / SS4423) (PTFE gasketed orifice seal design) General Description The Model HF-RES Residential Flush Horizontal Side-Wall

More information

SENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description

SENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description Page:1 of 5 SENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description The Model ZN-RES Residential Flush Pendent

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department

More information

WALL ESCUTCHEON PIPE SEAL WITH APPROVED FIRE CAULKING (SEE SPECIFICATIONS) NOTE: 12" 12" 24"

WALL ESCUTCHEON PIPE SEAL WITH APPROVED FIRE CAULKING (SEE SPECIFICATIONS) NOTE: 12 12 24 SOUTH TEJON ST., SUITE 00 COLORADO SPRINGS, CO. 00 TELE.: FAX: WALL ESCUTCHEON PACK ANNULAR SPACE WITH MINERAL WOOL GENERAL NOTES. THIS PROJECT INCLUDES THE DESIGN AND PROVISION OF A NEW WET SPRINKLER

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description Sprinklers (TY2284) are decorative, fast response, fusible solder sprinklers

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

FIGURE 1. Model RD107

FIGURE 1. Model RD107 General Description The Model RD107 Commercial Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. These are decorative and standard response. The frame of the sprinkler

More information

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX: Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean

More information

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8 City of Ottawa Project No. CR006230 Page 1 of 8 PART 1 - GENERAL 1.1 Reference Standards.1 Conform to the following:.1 Provincial and municipal building and fire regulations as approved by Provincial Fire

More information

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319) February 13, 2009 Sprinkler 43a 1. DESCRIPTION Viking Microfast and MicrofastHP Quick Response Horizontal Sidewall Sprinklers are small thermosensitive glass bulb spray sprinklers available with various

More information

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA Page 1 of 6 TECHNICAL DATA 1. DESCRIPTION Viking Quick Response Extended Coverage Horizontal Sidewall Sprinkler VK630 is a thermosensitive spray sprinkler available in several different finishes and temperature

More information

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0) Page 1 of 6 TECHNICAL DATA 1. DESCRIPTION Viking Quick Response Extended Coverage Horizontal Sidewall Sprinkler VK630 is a thermosensitive spray sprinkler available in several different finishes and temperature

More information

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure Sprinkler 41t 1. DESCRIPTION Viking Quick Response Upright and Pendent Sprinklers are small thermosensitive glass bulb spray available with various finishes and temperature ratings to meet design requirements.

More information

FIRE ALARM APPLICATION CITY OF MADISON HEIGHTS

FIRE ALARM APPLICATION CITY OF MADISON HEIGHTS FIRE ALARM APPLICATION CITY OF MADISON HEIGHTS www.madison-heights.org COMMUNITY DEVELOPMENT DEPARTMENT BUILDING DIVISION 300 W. THIRTEEN MILE RD. MADISON HEIGHTS, MICHIGAN 48071 (248) 583-0831 FAX (248)

More information

standard response elo upright and pendent sprinklers (storage-density/area)

standard response elo upright and pendent sprinklers (storage-density/area) December 5, 2008 Sprinkler 13e 1. DESCRIPTION The Viking Standard Response ELO Upright and Pendent Sprinklers are thermosensitive glass bulb spray sprinklers available in several different finishes and

More information

MONTECITO FIRE PROTECTION DISTRICT

MONTECITO FIRE PROTECTION DISTRICT Section 5a MONTECITO FIRE PROTECTION DISTRICT FIRE PROTECTION PLAN Residential Automatic Fire Sprinkler System Installations I Automatic Fire Sprinkler System Standards 1. Definition and Standard: An automatic

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE PUMP REVIEW Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;

More information

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following: SECTION 21 10 00 - WATER-BASED FIRE-SUPPRESSION PART I - GENERAL 1.1 SUMMARY A. Inclusion of sprinkler and standpipe systems shall be as determined by NFPA National Fire Code pamphlet 101 and program statement.

More information

B. Section Identification for Fire Suppression Piping and Equipment.

B. Section Identification for Fire Suppression Piping and Equipment. SECTION 211300 - FIRE SUPPRESSION SPRINKLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 RELATED

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319) February 3, 2014 Sprinkler 43a 1. DESCRIPTION Viking Microfast and MicrofastHP Quick Response Horizontal Sidewall Sprinklers are small thermosensitive glass bulb spray sprinklers available with various

More information

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. Page 1 of 6 1. DESCRIPTION Viking Quick Response Extra-Large Orifice Pendent Sprinkler VK377 is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings

More information

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3 Page 1 of 6 TECHNICAL DATA 1. DESCRIPTION The Viking Standard Response ELO Pendent Sprinkler is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings

More information

Residential Flat Concealed Sprinkler, Pendent, Model: CN-RES, K-Factor: 4.9, SIN: SS8421

Residential Flat Concealed Sprinkler, Pendent, Model: CN-RES, K-Factor: 4.9, SIN: SS8421 Page:1 of 7 Residential Flat Concealed Sprinkler, Pendent, Model: CN-RES, K-Factor: 4.9, SIN: SS8421 GENERAL DESCRIPTION The Model CN-RES Residential Flat Concealed Sprinklers are automatic sprinklers

More information

RESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY

RESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY RESIDENTIAL FIRE SPRINKLER SYSTEMS POLICY Plan Submittal and Inspection Requirements Revised 01/18/18 All residential fire sprinkler systems within the jurisdiction of the Fire Department shall meet all

More information

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required

More information

Residential Lead Free Flat Concealed Sprinkler, Pendent, Model: RC-RES, K-Factor: 4.9, SIN: SS8461

Residential Lead Free Flat Concealed Sprinkler, Pendent, Model: RC-RES, K-Factor: 4.9, SIN: SS8461 Page:1 of 8 Residential Lead Free Flat Concealed Sprinkler, Pendent, Model: RC-RES, K-Factor: 4.9, SIN: SS8461 GENERAL DESCRIPTION The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers

More information

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

Data Sheet 4.24 Issue F

Data Sheet 4.24 Issue F General Description The model RD207 residential flat concealed sprinklers are automatic sprinklers of the compressed fusible solder type. These are decorative and fast response. The cover plate assembly

More information

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA Page 1 of 5 1. DESCRIPTION Viking Quick Response Extended Coverage Horizontal Sidewall Sprinkler VK638 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings

More information

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data Page 1 of 5 1. DESCRIPTION Viking Quick Response Extended Coverage Horizontal Sidewall Sprinkler VK638 is a thermosensitive spray sprinkler available in several different finishes and temperature ratings

More information

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES SECTION 21 13 00 - FIRE SUPRESSION SPRINKLER SYSTEMS SCOPE OF WORK This standard provides general guidance concerning the specific preferences of The University of South Alabama for automatic fire sprinkler

More information