EXICALL EN70MR EXICALL EN70-ATEX (upright version EXICALL EN70MR) (horizontal version EXICALL EN70MR)
|
|
- Lillian Linette Watson
- 5 years ago
- Views:
Transcription
1 Use Instruction EXICALL EN70 EXICALL EN70MR EXICALL EN70-ATEX Order-No. Order-No. Order-No. Order-No (upright version EXICALL EN70) (horizontal version EXICALL EN70) (upright version EXICALL EN70MR) (horizontal version EXICALL EN70MR) Order-No (upright version EXICALL EN70-ATEX) Issue Version 8-48
2 Table of contents Safety instructions EXICALL EN Installation Specification sheet Programming Installation Commissioning Operation Functional description: Elevator alarm Functional description: Door phone Other Features Advanced programming Accessories Specifications Declaration of conformity
3 Safety instructions Telephone connection EXICALL EN70 is designed to connect to an analogue telephone line. This connection must remain in service for at least one hour after a mains power loss according to EN These are: analogue PSTN analogue port of an ISDN terminal (ISDN-NT has to be reprogrammed for emergency operation at the ab-port) analogue port of a private exchange using UPS (Uninterruptible power supply 1h buffering) GSM Interface with TÜV approval, i.e. EA-GSM-Interface P.37 Multiple EXICALL EN70 sharing one line: Ensure that the first alarm number is always available, because if multiple alarms triggered at the same time it is possible that only first number can be reached A maximum of three units can share one line In case of star cable routing (max. 15 Ω difference per connection = Calc 2 x conductor resistance!) up to 4 diallers can be connected. Example: AWG 24 (U72) = 2 x 90 Ω / km => difference in length max. 15 Ω / (2 x 90 Ω / km) = 0.083km In case of a two-step-dialling-in the number of diallers is doubled P.26 Not suitable: VoIP or cable modem, as in case of power loss it is not functional! The voltage of the telephone network is defined in EN It is higher than 40 V and therefore please beware for electrical hazard and disconnect the phone line during wiring. Lightning protection interface for landline. P.37 Supply Safety precautions In case of a power loss EXICALL EN70 can still dial calling number 1 using power from the telephone line. The components of the sub-unit EA-LMK and EA-LMK70B are connected to the telephone line potential. Therefore, the connections must be transferred free of soil and net (safety standard EN60950), and may not be touchable (isolation 3.75kV). Check functionality after each changing of parameter or wiring P.14 Please note an alarm by telephone is only successful if the subscriber takes care of the following points: Alarm must not be answered by an answering machine or equal equipment Sometimes connection a mobile phone can be redirected to a Combox (Mailbox) directly or after some ringing-cycles! Do not open housing. Do not bring the device into contact with a liquid (water). 3
4 EXICALL EN70 View ➊ ➋ ➌ ➍ ➎ ➏ ➐ ➑ Functional elements 1. Speaker 2. Microphone 3. Yellow LED indicates Call is activated S Green LED indicates Please speak P Call button P.14 incl. backlight P Red LED for K2, green LED for K3, yellow LED for K2&K3 P Green Mode LED P.8 8. Connections P.12 Meaning of LED indicators Yellow LED Call is activated Green LED Please speak idicates that remote party is listening LED-Mode Green flash: standby Green Ready for program. Red -connection active LED-Output (Relais) Red K2 active Green K3 active Yellow K2 & K3 4
5 Installation Procedure Proceed systematically. This will ensure that EXICALL EN70 is installs correct and the function is ensured. 1. Complete specification sheet P.6 2. Is EXICALL EN70 pre-programmed or do you program yourself? Self programming P.8 Pre-programmed P Montage P Commissioning P Operation P.15 5
6 Specification sheet General Information Company: Name: Location: Elevator no.: Profile Please see profile table below.. Dial-in number Telephone line where EXICALL EN70 is connected PIN-Code. (Factory setting: 0000) User language German French English Italian Dialling-in procedure with PIN-Code without PIN-Code Serial-No. EXICALL EN70 EXICALL EN70MR EXICALL EN70-ATEX Calling number(s) Periodical test call number Dialling sequence 1: : : : : : : : Individual announcement (12 seconds at max) User announcement type...(please see announcement table below) Advanced programming..=.....=... 6
7 Profile table Profile Type of use Dialing in / Remote access Individual announcement 0 Speed dailing P.20 without PIN-Code None 1 No speed dailing P.20 without PIN-Code None 7 without PIN-Code None No misuse protection P.18 8 without PIN-Code One time No misuse protection P.18 9 without PIN-Code One time Misuse protection P with PIN-Code One time Misuse protection P with PIN-Code Repeated Mit Missbrauch P.18 Factory default: Profile 10 Programming P.23 = Door phone = Elevator alarm User announcement type Value ANNOUNCEMENT after pressing call button ANNOUNCEMENT during phone connection 0 One time Emergency call activated, you are about to be connected bearbeitet Activated Repeated every seconds Repeated every sec. One time Individual announcement + cause of alarm + to stop press 0 to speak press 1 - Individual announcement Factory default for elevator alarm: 0 Programming P.23 Factory default for door phone: 254 7
8 Programming Preparation 1. EXICALL EN70 will be programmed locally over the microphone using a DTMF-dialler (Touch-Tone-Dialler). Therefore, ambient noise can affect the programming. 2. Connect supply voltage P Place Dialler over the microphone. Enable programming 4. Press call button briefly. The mode LED Mode changes from flashing to permanently green. 5. Press key *. on the dialler. The mode LED changes to off. 6. A. You hear one beep followed by the announcement "Programming disabled, PIN". Enter the PIN code (factory setting: 0000) followed by key #.. You will hear two beep sounds and the programming is enabled. Wait for any announcements and continue with step B. You hear one beep only. EXICALL EN70 is now in programming mode. Start programming sequence by entering first key within 5 seconds, otherwise programming mode is exited (go back to step 4, if you want to proceed with programming). Information on programming Programming will be PIN-code protected automatically after first call started from the EXICALL EN70 to ensure that EXICALL EN70 is protected against unauthorized changes after the installation. The programming mode is left automatically when there will be no DTMF received within 5 seconds (=timeout). As long as the yellow LED is on, you are not able to do any programming. Wait until the yellow LED is off. Programming remains stored even after power-loss. 8
9 How to program calling numbers *. *. 1. ANNOUNCEMENT *. Calling number according to specification sheet Wait for 5 sec. *. *. 2. ANNOUNCEMENT *. Calling number according to specification sheet Wait for 5 sec. *. *. 3. ANNOUNCEMENT *. Calling number according to specification sheet Wait for 5 sec *. *. 8. ANNOUNCEMENT *. Calling number according to specification sheet Wait for 5 sec. You can program up to 8 or 9 calling numbers. If you want to alarm more than the first three calling numbers you have to adapt calling number sequence. P.9 Calling number 9 is used for periodical test call according EN Digit #. as part to the calling number results in a 5 seconds dialling delay. This may be necessary in combination with a private exchange, when a pause is required after taking an external line. Program calling number as following: Office Number + #. + Phone number If you require Hotline-mode (= private exchange dials telephone number after EXICALL EN70 seizes line) you program calling number 1 with #. only. If the private exchange needs flash-pulse to dial internal numbers you have to program calling number as following: 2. #. + internal number. Calling number 1 cannot be deleted and is the only calling number to be dialled in case of a supply power loss. Digit *. as part of the calling number will result into a Point-IDconnection. P.21 How to program periodical test number According to EN81-28 EXICALL EN70 has to call his service facility at least every 72 hours => periodical test call. Therefore you have to program calling number 9. S.8 *. *. 9. ANNOUNCEMENT *. Calling number according to specification sheet Wait for 5 sec. If the periodical test call is activated EXICALL EN70 calls this number in the programmed interval. P.25 The periodical test can be activated / de-activated i.e. during a remote access (dialling in) using DTMF commands. P.16 How to check calling numbers Check calling numbers i.e. calling number 1 by entering: *. *. 1. ANNOUNCEMENT Wait for 20 sec. 9
10 How to program calling number sequence The factory default for calling number sequence is EXICALL EN70 calls the numbers of the sequence consecutively until the call is acknowledged or the end of the sequence is reached. You can adapt the sequence in case you want to call a certain number repeatedly. Examples: Calling number sequence factory setting : Call number 1, then number 2 followed by number 3. Calling number sequence : Call number 1 two times, followed by two attempts on number 2, followed by four attempts on number 3. Calling number sequence : First call to number 2, than number three and number 1 in the end. In case of a power loss only calling number 1 can be dialled. S.8 *. *. 0. ANNOUNCEMENT *. Calling cumber sequence accordign to spec. sheet Wiat for 5 sec. The calling number sequence can contain up to 9 digits. The calling number sequence may be altered using day/night-input (S4). If so, enter calling number other sequence while input signal S4 is active. During operation the calling number sequence follows the input signal on S4. P.21 If a calling number is not programmed or erased, this number will be skipped when still programmed in calling number sequence. In case of a power loss EXICALL EN70 can alarm calling number 1 only. Please make sure that at least on calling number is available in any case at any time, i.e. calling number sequence= 231: Unit powered Calling number sequence 231 In case of power loss Calling numbe 1 only 2: 0#044 1: 0#043 3: 0#079-1: 0#043 - How to program individual announcement / Select language You can record an individual announcement to identify your EXICALL EN70. The optional input <n> allows altering the user language: Press 1. for German, 2 for French, 3. for English, 4. for Italian. *. *. #. ANNOUNCEMENT <n> *. Announcement according to specification sheet #. Wait for 5 sec. The maximum recording time is 12 seconds Depending on the selected profile this announcement will be played once at the beginning of each alarm connection, or repeated every <x> seconds during the connection or even without any announcement (i.e. as door phone) P.7 How to program the PIN-Code The PIN code protects the EXICALL EN70 against unauthorized remote dial-up or programming. It also can be used to identify the unit during phone connection (i.e. commission number of elevator) S.8 #. PIN code accroding to specification sheet #. Repeat PIN code #. The PIN code must be between four and seven digits. The factory setting for the PIN code is Program a different code for security reasons. 10
11 Montage Mechanical Assembly Front panel Mounting accessories Flash-mounting front panel: Alum or stainless steel P.29 MDF housing (wall insert) for front panel P.31 Die-cast aluminium box for surface mounting P.32 ABS-enclosure with transparent door for surface mounting P.33 Front panel (Alum) suitable for ABS-enclosure P.34 Flash-mounting front panel (Exitel upgrade cover): stainless steel P.35 11
12 Wiring The electrical wiring is split into supply, telephone line and the periphery. Proceed as follows: Connect the two-wire shielded phone line. Connect supply voltage. EXICALL EN70 performs a self test. P.14 Start test call. Press call button for one second. P.14 Connect accessory and or input/output. Supply voltage (X12:3 poles) 10 35V DC or 8 25 V AC If you power by mains, us 230V AC power adapter. Line (X1:RJ12) EXICALL EN70: two wire (red/green) MR-type: fore wire (red/green,black/yellow) Twisted and shieled and free from connection to other wires. Call button backlight - Shunt PIN 1 and 2 Input-/Output (X13:12 pole) - Misuse protection signal (S1): Connect signal according to the elevators door state. - External call signal (S2): not ready in case of power loss! - Alarm signal (S3) - Day-/Night switching signal (S4) If you want an individual calling number sequence. - Parallel contact (K1) Potential free contact of call button. - Systeme contact (K2): Connection to a building control system (filtered alarm) or connection of video, light or display "help omes." - Door opener contact (K3): Connect door opening system in case of intercom use. Accessory (X2:RJ45) - Sub-unit EA-LMK: - Sub-unit EA-LMK70B - Potential free external call button 12
13 Terminals X13 X12 X2 X1 Supply voltage X12 X12 Description Function PIN 1 GND Earth PIN 2 PIN 3 SP SP Supply voltage V DC or 8-25 V AC max. 4 W, arbitrary polarity Telephone line X1 X1 Color Function PIN 2 Black to machine rrom Telefone or remote-unit LMK72B PIN 3 Red to PSTN (connection a) PIN 4 Green to PSTN (connection b) PIN 5 Yellow to machine rrom Telefone or remote-unit LMK72B Leitronic-Accessories X2 X2 Terminal for Leitronic accessories Input/Output X13 X13 Descreption Function PIN 1 BEL White backlight PIN 2 BEL White backlight PIN 3 K3 Relay (Normaly open) i.e. door opener PIN 4 K3 Relay (Normaly open) i.e. door opener PIN 5 KCOM Common pole for relay K1 and K2 PIN 6 K1 Call button parallel contact (Normally open) PIN 7 K2 Filtered alarm contact (Normally closed) PIN 8 SCOM Common pole for signal inputs S1-S4 PIN 9 S4 Day/Night input signal PIN 10 S3 PIN 11 S2 PIN 12 S1 Technical alarm signal External alarm contact Misuse protection signal (i.e. door state) Signal inputs (S1 - S4) Output contact (K1/K3) Normally open Output contact (K2) Normally closed active: 10 V - 40 V AC/DC max. 4 A/50 V AC/DC max. 100 ma/50 V AC/DC 13
14 Commissioning Connecting supply After power up EXICALL EN70 starts a self-test, checking for.. Telephone line: If no dial tone is detected, you will hear the announcement "phone line failure". Please check phone line. Alarm input S3: If the input is active, you will hear the announcement "Sensor-3 activated. Call Setup connection Hands-free connection Terminate connection Press the call button at least one second to start call. During two minutes EXICALL EN70 tries to establish connection. Adjusting timer P.25. During this time-out the LED Telephone is activated. During connection setup the user announcement will be played once, repeated or ignored depending on selected profile. Adjust user announcement type P.7 If there is not connection please check calling number. P.9 Called party can listen to the user announcement or skip announcement by sending DTMF command 1. or 3. P.15. Doing so activates LED Speak. Check if hands-free communication is fine. Beware of the hands-free connection timeout of 2 minutes P seconds before disconnecting EXICALL EN70 plays announcement Abort. The connection timer can be re-started using DTMF command 1. or 3.. Called party can terminate call by sending DTMF command 0.. Other commands P.15 14
15 Operation Answer call During connection the called party can initiate remote instructions by sending the following DTMF commands: Play announcements: Individual message / Cause of alarm Status information Switch to hands-free connection Stop announcements and reload connection timer Deactivated output K Activated output K2 Disarm system Arm system Additional remote commands Table below * 0 # Read out PIN code (Identification) Acknowledge alarm and disconnect Pass on Alarm to next alarm number If more than one alarm number is programmed P.9, the call must be acknowledged /answered by sending DTMF command 0.. Otherwise EXICALL EN70 starts to dial the next alarm number. If you want to pass on the alarm to the next alarm number immediately, you can do so by sending DTMF command
16 Other remote controls / Elevator alarm and Door phone mode DTMF commands Do not delay more than two seconds between two digits. *. *. 0. Read-out/ Modify calling number sequence (1->-2->3) *. *. 1. Read-out / Modify calling number1.... *. *. 8. Read-out / Modify calling number 8 *. *. 9. Read-out / Modify periodical test number *. *. #. 0. Deactivate periodical test to calling number 9 *. *. #. 1. <n> Activate periodical test to calling number 9 (first time in 72 h or after <n> hours) *. *. #. 2. Start communication test to calling number 9 in two minutes (once only) *. *. #. #. Modify individual message Other remote controls / Door phone Do not delay more than two seconds between two digits. DTMF commands EXICALL EN70 disconnets *. 2. Close contact K3 for 2 seconds Yes *. 3. Close contact K3 for 4 seconds Yes *. 4. Close contact K3 for 8 seconds Yes *. 5. Contact K3 on 3s, off 1s, on 3s Yes *. 6. Close contact K3 for 2 seconds No *. 7. Close contact K3 for 4 seconds No *. 8. Close contact K3 for 8 seconds No *. 9. Close contact K3 until disconnection No *. 0. Disconnect if S1 (door contact) is active If input S1 is active *. 1. EXICALL EN70 disconnects Yes 16
17 Dialling in/remote access There are two ways of remote access: <with PIN-Code protection> or <without PIN-Code> according to selected profile. P.7 Dialling in/remote access without PIN-Code Dialling in/remote access using PIN-Code 0000 Dial phone number of EXICALL EN70. After selected ringing-cycles P.26 EXICALL EN70 answers call and changes to hands-free connection. This change will be signalled by three gongs and the green Speak -Symbol (EN81-70). So a person inside the cabin will be informed about the established hands-free connection. Dial number of EXICALL EN70. After selected ringing-cycles P.26 EXICALL EN70 answers call and asks for PIN (Default = 0000). If the correct PIN-Code is entered, EXICALL EN70 changes to service-mode where the microphone and speaker remain inactive followed by the announcement to stop press 0, to speak press 1. With key 1. you can change to hands-free-connection. This change will be signalled by three gongs and the green Speak -Symbol (EN81-70). So a person inside the cabin will be informed about the established hands-free connection. Dialling in/remote access: Special mode: Two step dialling in Dial phone number of EXICALL EN70. Let it ring two times and hang-up. Wait for 20 seconds and re-dial phone number. After selected ringing-cycles P.26 EXICALL EN70 answers call! Dialling in/remote access: Special mode in case of power loss In case of a power loss on supply terminal EXICALL EN70 answers call immediately! 17
18 Functional description: Elevator alarm Elevator emergency call If the emergency call is triggered by pressing the emergency button for at least one second P.24 the yellow indicator is activated. EXICALL EN70 dials the programmed number(s) and established a hands-free connection. When the called party sends DTMF command 1. the LED Speak is activated. ANNOUNCEMENT Emergency call activated. You are about to be connected Call button backlight To activate the push-button backlight short the two BEL terminals. Misuse-Protection (S1) The misuse protection signal is used to separate real emergency calls. During the maximum duration of cabin travel P.24 you will hear the announcement: ANNOUNCEMENT Emergency call activated. You are about to be connected. If the door state changes during this timeout you will hear: ANNOUNCEMENT acknowledged Door is open. Emergency call deactivated. Alarm If the door state does not alter during this timeout EXICALL EN70 starts to dial the calling number(s) playing ANNOUNCEMENT Emergency call activated Factory setting for misuse timeout: 30 seconds. P.24 Misuse-protection is only available when supply voltage is applied. Connection to building control system. P.19 There are two ways to connect misuse-protection signal: 1. Connect voltage following the 2. Use supply voltage SP and connect door state between S1 and SCOM. door contact. SCOM S1 SCOM S1 active: 10 V - 40 V AC/DC SP SP Door contact 18
19 External alarm signal (S2) SCOM S2 SP SP Alarmcontact Note: This optocoupler input cannot be used in case of a supply power loss. Alternative: Potential free call button (normally open) connected to the subunit EA-LMK/EA-LMK70B or connected using suitable connection cord between PIN 3 and 6 (EXT-terminal). System contact (K2) The normally closed contact (K2) is used in the emergency lift profiles as a filtered alarm (for connection to a building management system) or activate display "Help is coming" display. While K2 is active the LED K2/3 is red or yellow. When K2 is used as in mode "filtered alarm" the contact is activated after the abuses of misuse timeout P.24 and deactivated when the door state changes. When used in mode "help is coming" K2 contact is activated after receiving DTMF command 6. and deactivated when the door state changes or if the alarm remains unacknowledged. Setting the K2 mode P.26. KCOM K2 Periodical test call (WinMOS 300) to management system or "help is coming" lamp 100 ma/50 V AC/DC According to EN81-28 a dialler has to indicate its state at least every 72 hours. EXICALL EN70 can perform this test call towards calling number 9 automatically P.9 The periodical test can be activated during remote access P.17 using DTMF command sequence *. *. #. 1.. P.16 ANNOUNCEMENT Periodical test activated Adjust periodical test timer P.25 Machine room communication (EXICALL EN70MR only) Connect PIN 3/4 of the machine room phone MR- with PIN 2/5 of -LINE terminal X1 of the EXICALL EN70MR. Lifting up the machine room handset starts a hands-free connection with the cabins EXICALL EN70MR indicated by the green LED Speak. Hanging up the handset terminates hands-free connection. By dialling the prefix 0. the handset/modem is connected to the external line. An existing external connection will be disconnected if EXICALL EN70MR has to dial out due to an alarm. In case of dialling-in EXICALL EN70MR can be adjusted to work together with the machine room phone or modem P.17. This functionality mentioned above is only available with applied power. In case of power loss, the machine room handset/modem and EXICALL EN70MR are connected in parallel to the PSTN. Fire brigade solution according to EN81-72 (EXICALL EN70MR only) P.38 19
20 Functional description: Door phone Door phone (Intercom) A call is triggered by pressing the button for at least one second P.24 indicated by the yellow LED. EXICALL EN70 dials the programmed number(s) and established a hands-free connection. When the called party sends DTMF command 1. the LED Speak is activated. ANNOUNCEMENT Activated Call button backlight To activate button backlight connect the two BEL terminals. Intercom with speed dialling EXICALL EN70 can be used to call individual numbers according to the activated buttons => i.e. call several apartments of a house (intercom). Button T1 to T6 dials corresponding calling numbers 1 to 6. The internal call button of the EXICALL EN70 is equal to button T1. To activate speed dialling select profile 0 P.23 VOC- SP SCOM S4 S3 S2 S1 VOC+ SP min. 10 V T6 T4 T5 T3 T1 T2 System contact (K2) The normally closed contact (K2) is used in all door phone profiles as switching output for video / lighting. If K2 is active LED K2/3 is red or yellow. K2 opens when a call is activated and closes 2 minutes after terminating the connection. Supply KCOM K2 Video/Light Door opener contact (K3) You can use contact K3 to open a door or barrier. If K3 is active the LED K2/3 is green or yellow. There are several DTMF commends to activate/deactivate K3 P.16 K3 K3 to door opener max. 4 A/50 V AC/DC 20
21 Other Features Service mode connection The service connection is used in case of a silent alarm or remote access. In service mode microphone and speakers remain inactive. This connection mode is used i.e. in case of a technical alarm (S3 P.21) or periodical test ( P.9) and depending on the settings at dialling-in P.27. During service mode DTMF command 1. switches to the hands-free connection indicated by three gong signals. Alarming using alarm protocols EXICALL EN70 supports protocols Point-Contact ID or Contact-ID. Thus, the alarm can be routed to most emergency operations centre. When an alarm is triggered EXICALL EN70 first transmits protocol to first calling number followed by a second call using hands-free connection. Enable Point-ID transmission P.28 Parallel contact (K1) Contact (K1) is the potential free parallel contact of the call button. K1 can be used for the connection to a building control system or a doorbell. KCOM K1 Technical alarm input (S3) to building control system / door bell max. 4 A/50 V AC/DC The response on the alarm input (S3) can be selected according to P.24 If a signal is applied: If a contact is connected: SCOM S3 SCOM S3 active: 10 V - 40 V AC/DC SP SP Day/Night input signal (S4) Two different calling number sequences can be determined depending on the signal at input S4. Program individual calling number sequence, once when S4 is active and once when S4 is inactive. During operation EXICALL EN70 dials calling numbers according to calling number sequence depending on the state of S4 (day/night). If a signal is applied: If a contact is connected: SCOM S4 SCOM S4 active: 10 V - 40 V AC/DC SP SP Alarmcontact Day/Nightcontact 21
22 Announcement overview Announcement depends on selected profile and can be adjusted according to P.7 Announcement overview: ANNOUNCEMENT Cause Individual announcement Abort Alarm due to S1/S3 Alarm acknowledged To change press star, to stop press hash Output activated Surveillance 1 activated Surveillance 2 activated First announcement in case of an alarm Connection will be terminated Alarm due to signal applied to sensor 1 or 3 inputs If DTMF command 0. was sent User guidance during programming Relay K2 is activated No signal on input S4 (Day/Night) Signal on input S4 (Day/Night) Emergency call activated Emergency call activated by pressing call button Emergency call deactivated, alarm acknowledged PIN Programming deactivated: PIN Programming acknowledged Programming, Abort Line failure Door is open. Emergency call deactivated, alarm acknowledged Failure Unacknowledged alarms: n Calling number Emergency call has been acknowledged or cancelled by changing door state during misuse protection timeout Prompt to enter PIN code Prompt to enter PIN codes to enable programming mode Remote programming successful Remote programming not successful No dial tone present during self test after power up Emergency call is cancelled due to change of door state during misuse protection timeout Erroneous entry during programming. The old value retain active Number of unacknowledged alarms Calling number announcement Calling number sequence Calling number sequence S.9 Periodical test A periodical test call is active S.19 22
23 Advanced programming Profile selection read/change Attention: Changing these parameters below does influence the operating mode. Therefore only necessary parameters should be changed. Please check behaviour before going into operation. Table with all profiles according P.7 * #. #. VALUE *. Value #. Programming profile does not change calling numbers, calling number sequence and individual announcement. But all other parameters and registers and the PIN-code will be set to default value. Factory settings Alarm repetition If you want to reset to factory default please re-program profile. P.23 EXICALL EN70 calls calling numbers according to the calling number sequence P.10 for every new alarm event. You can read-out or modify this register as following: * #. #. VALUE *. Value #. Value Description 0 EXICALL EN70 calls calling numbers of the sequence once per alarm even (Factory setting) 1-9 EXICALL EN70 repeats calling number sequence 1 9 times or until the alarm is acknowledged. Announcement type Select announcement type according to table P.7 Note: Different factory settings according to profile! You can read-out or modify this register as following: * #. #. VALUE *. Value #. 23
24 Misuse timeout (sensor S1) If the door state changes within the specified timeout an emergency call will be cancelled automatically. Adjust timeout according to maximum duration of cabin travel. You can read-out or modify timer as following: * #. #. VALUE *. Value #. Value Description Timer in seconds (Factory setting: 30) Change profile if you want to de-activate misuse-protection! Activation time for call button S2 EXICALL EN70 starts call when the call button has been activated longer as certain time is pressed for a specified time. You can read-out or modify timer as following: * #. #. VALUE *. Value #. Value Description Activation timeout in 20 ms-steps. (Factory setting: 50 * 20 ms, => 1 second) Technical alarm (sensor S3) The activation type for technical alarm signal S3 can be read-out or modified as following: * #. #. VALUE *. Value #. Value Description 1 Announcement Alarm due to sensor 3, in case signal is applied (Factory setting) 3 Announcement Alarm due to sensor 3, in case signal there is no signal applied 24
25 Dial-up connection time-out During this timeout EXICALL EN70 tries to establish connection. You can read-out or modify timer as following: * #. #. VALUE *. Value #. Value Description Timeout in steps of 10 seconds (Factory setting: 12 * 10, => 120 s=2 minutes) Hands-free connection time-out During this timeout EXICALL EN70 stays in hands-free connection. You can read-out or modify timer as following: * #. #. VALUE *. Value #. Value Description Timeout in steps of 10 seconds (Factory setting: 12 * 10, => 120 s=2 minutes) Periodical communication test The timeout between two periodical calls can be read-out or modified as following: * #. #. VALUE *. Value #. Value Description EXICALL EN70 starts call to calling number 9 every * 20 minutes. (Factory setting: 216 * 20min=4320min=72h) Green indicator LED Speak The activation type can be read-out or modified as following: * #. #. VALUE *. Value #. Value Description 2 LED Speak will be activated manually during connection using DTMF 1. (Factory setting for elevator alarm). 4 LED Speak is activated automatically after connection is established (Factory setting for door phone). 25
26 Relay K2 (LMK-OUT) The function of this relay can be read-out or modified as following: * #. #. VALUE *. Value #. Value Description 0 K2 inactiv (Factory setting for elevator alarm without Misues-protection) 1 Video/Light (Factory setting for door phone) Relay will be activated by activating call button. Relay will be de-activated two minutes after disconnection. 193 Filtered alarm to connect to master control system (Factory setting for elevator alarm): Relay is activated when alarm is activated (after the misuse timeout). Relay is deactivated if door state as changed. 208 Help is coming : Relay is activated using touch-tone 6.. Relay is de-activated if the door state changes or an alarm remains unacknowledged. Program ringing cycles / dialling-in The number of ringing cycles before EXICALL EN70 answers the call can be read-out or modified as following: * #. #. VALUE *. Value #. Value Description 0 EXICALL EN70 does not answer incoming call 2..9 EXICALL EN70 answers call after 2-9 ringing cycles (Factory setting: 2) In case of a power loss this setting is not relevant => EXICALL EN70 answers call immediately. Dialling-in sequence Behaviour on dialling-in mode can be read-out or modified as following: * #. #. VALUE *. Value #. Value Description 0 Direkte Ferneinwahl (Werkseinstellung) 1 Etappierte Ferneinwahl 26
27 Connection mode after dialling-in Phone connection mode after dialling-in can be read-out or modified as following: * #. #. VALUE *. Value #. Value Description 0 After PIN-Code-entry Connection in service-mode Handsfree connection using DTMF 1 1 After PIN-Code-entry Connection directly in hands-free mode, indicated by three rings 2 After PIN-Code-entry or time-out 15s Connection in servicemode Hands-free connection using DTMF 1 3 After PIN-Code-entry or time-out 15s Connection directly in hands-free mode, indicated by three rings 5 Without PIN-Code-query Connection directly in hands-free mode, indicated by three rings Remote programming Remote programming of calling number, calling number sequence and individual announcement can be read-out or modified as following: * #. #. VALUE *. Value #. Value Description 0 Remote programming disabled 1 Remote program of calling number/ calling number sequence and individual announcement is allowed (Factory setting) Hands-free volume adjustment The EXICALL EN70 hands-free volume can be read-out or modified as following: * #. #. VALUE *. Value #. Value Description is low volume, 15 is maimum volume (Factory setting: 8) Note: Changing this value influences the behaviour of handsfree switching mode. 27
28 Back-Ground-Noise In case of a loud background noise in the cabin (i.e. ventilator, train station..) you may activate BGN-function to improve hands-free communication: * #. #. VALUE *. Value #. Value Description 0 BGN inactive (Factory setting) 103 BGN filter activted Point-ID communication to alarm centre Calling number <n> consists of the telephone number and user account number. The user account no. is separated from the calling number by.*.. *. *. <n> ANNOUNCEMENT *. Calling number + *. + user ccount number Wait for 5 seconds The 1st calling number must not be programmed with point-id communication, as otherwise in case of a power failure there could no voice connection be established. Instead, program the 2nd calling number with Point ID and change calling number sequence i.e. to P.10 Example: 2. Calling number= , User account number=3456 Program calling number as following: *. *. 2. and wait for announcement * * wait until timeout (5 s). Alarm code for Point-ID for several alarm causes: Code Cause of alarm Zone 120 Call button Alarm due to sensor S Test call Periodical call (72h)
29 Accessories Flash-mounting front panel: Alum or stainless steel Mounting frame made of aluminium or stainless steel fitted for wooden wall inlay box Order-No. Order-No (plain anodised aluminium) (stainless steel) 29
30 Wall recess for wall mounting Wall recess and dowel holes for mounting frame / panel. 30
31 Wooden wall inlay box Wooden box made of MDF for wall inlay. Fitted for front panel or Order-No
32 Die-cast aluminium box (surface mounting) Die-cast alum housing (colour: white) for surface mounting Order-No
33 ABS-enclosure for on-wall mounting with transparent door Housing made of ABS with transparent door and grip closure for surface mounting. Order-No
34 Front panel (Alum) suitable for ABS-enclosure Fitted for ABS-enclosure Order-No
35 Flash-mounting front panel (Exitel upgrade cover): stainless steel Order-No
36 Programming tool Touch-tone dialler (DTMF pad)) Supply voltage: 2 AAA batteries Order-No DIN-AC-adapter 10 VA (1TE) for up to three EXICALL EN70 or one USV Supply voltage: 230 V AC / 50 Hz Output voltage: 14.3 V DC Nominal power: 10 VA Order-No Uninterrupted power supply interace (UPS) (2TE) Supply voltage: 14.3 V DC i.e. from Backup: 12 V plump accumulater i.e Output: permanent 12 V DC 400 ma or one Exicall EN70 switched 12 V DC 200 ma for emegency light Order-No Plump accumulator 12 V / 1.2 Ah Order-No AC-adapter 6VA AC-adapter 18 VA Heating Sub-unit EA-LMK Euro-connector AC-adapter for up to 2 EXICALL EN70 Supply voltage: Output voltage: Nominal power: V AC/50 60 Hz 12 V DC 6 VA Order-No Euro-connector AC-adapter for up to 6 EXICALL EN70 or 1 EXICALL EN70 plus 1 heating Supply voltage: Output voltage: Nominal power: 230 V AC/50 Hz 12 V DC 18 VA Order-No Heater for outdoor use to be mounted to EXICALL EN70. Dimension: 217 x 72 x 20 mm (L x W x H) Supply voltage: Nominal power: Connectors: 12 V 12 VA open ends Order-No The sub-unit EA-LMK allows starting an alarm call and get in hands-free communication, i.e. as option in big elevators or on top of the cabin. Housing material: ABS Dimension: 112 x 56 x 21 mm (L x W x H) Width including plug: 74 mm Weight: Plug X2: Order-No g (without cable) Emergency button (on telephone potential) 36
37 Sub-unit EA-LMK70B Same as EA-LMK but with integrated external powered amplifier plus integrated LED or external indicators (yellow/green) according to EN Supply voltage: Plug X7: Plug X2: 8 35 V DC Order-No Primary connections Emergency button (on telephone potential) Lightning protection interface (3TE) protects the telephone input of EXICALL EN70(MR) from voltages higher than 150 V and filters ADSL signals. Dimension: 90 x 52 x 30 mm (L x W x H) Weight: 53 g Order-No Intercom-unit EA-ICOM DECT-Interface GSM-Modules Supply voltage: Nominal power: 230 V AC / 50 Hz 4 W (Standby)/8 W (Operation) Dimension: 165 x 85 x 29 mm (L x W x H) Connectors: Emergency mode: Weight: Order-No xPSTN, 4xInternal (Screw terminal) Internal 1 is connected to PSTN over relay in case of power loss 600 g (incl. AC-adapter) The DECT interface establishes a connection between the machine room and an EXICALL EN70 in the cabin. Application: Technology: Supply voltage: Connectors: Diagonal elevators DECT/GAP 230 V AC / 50 Hz Telephone RJ11 The GSM-Modules simulates the analogue telephone line Application: Backup: Connectors: Indicators: PSTN replacement 12 V battery Phone, Supply, Ready: Pluggable screw-terminal GSM-field intensity as LED Protection-housing (IP56) / Supply voltage 230 V AC / 50Hz Order-No Order-No incl. modem-interface DB9/USB DIN-housing / Supply voltage 230 V AC / 50Hz or V DC Order-No. Order-No. Machine room phone: Machine room solution 1AC.0812 with modem-interface (Accessory) 1DC.0812 with modem-interface (Accessory) Wall mount phone in machine room to get in connection with EXICALL EN70MR in the cabinet. Order-No
38 Remote-unit EA-LMK72B-WG: Fire brigade solution according to EN81-72 with EXICALL EN70MR The remote-unit gives immediate access to the main-units EXICALL EN70MR over a two wire connection (max. wire resistance 15 Ohm). Up to two remote-units can be connected to a main-unit EXICALL EN70MR. Supply voltage: 8 35 V DC Order-No. Order-No B (EA-FWS-Set) B (EA-FWS-IP-Box-Set) mounted in protective housing (IP54) with Talk -button and display Special manual available for this application 2 Modem Maschinenraum 2 2 Telefonleitung / Amt Kabine Schacht Externe Notruftaste Missbrauchsunterdrückung Stromversorgung V DC notstromgepuffert! Optionale zweite Sprechstelle: EA-LMK System-Kontakt Anbindung an ein Gebäudeleitsystem (gefilterter Alarm) Anschluss Hilfe kommt Anzeige Feuerwehrmodus: Speisung: 8-35V DC Feuerwehr Functional description: Key switch activates fire brigade mode. Standby: Microphone in the cabin is active (Speak); Machine room and fire brigade entry are in listening mode. If Speak -Button is pressed the microphone of this location is active (Speak) and the other locations are in listening mode. ATEX-Application Special manual available for this application Main-Unit EXICALL EN70-ATEX Order-No Sub-unit LMK-ATEX Order-No Remote-unit LMK72B-ATEX Order-No II 3G Ex na nl IIC T6 II 3D Ex td A22 IP64 T45 C Ta: 0 C C Supply voltage: V DC 2 or 4W SEV 09 ATEX 0141 X 38
39 Specifications Supply voltage Voltage range Maximum power V DC / 8 25 V AC EXICALL EN70MR: max. 4 W EXICALL EN70-ATEX: max. 4 W EXICALL EN70: max. 3 W Safety regulations Standard EN 60950/EN Input-/ Output Inputs (S1-S4) NO contacts (K1/K3) NC contact (K2) active: 10 V - 40 V AC/DC in-active: < 3V max. 4 A/50 V AC/DC max. 100 ma/50 V AC/DC Environmental conditions Temperature 0 to 40 C Humidity 20 % - 70 % relative humidity, noncondensing Housing Dimension 80 x 275 x 41 mm (W x H x T) Weight ca. 500 g Approvals European R&TTE Directive 1999/5/EC of 09.March 1999 Telephone line Type Equivalent circuit a,b (analogue) a 820 Ohm 220 Ohm b Dialling mode DTMF 115 nf 39
40 Declaration of Conformity Declaration of Conformity According to the R&TTE Directive 1999/5/EC of 09.March 1999 Manufacturer s Name: Leitronic AG Manufacturer s Address: Engeloostrasse 16 CH-5621 Zufikon, Switzerland declares that the product Product Name: EXICALL EN70 Model Number: EXI-EN70 EXI-EN70MR EXI-EN70-ATEX conforms to the following product specifications: Safety (R&TTE, Article 3.1a): EN 60950: 1992+A1+A2+A3+A4 EMC (R&TTE, Article 3.1b): EN , 1992 EN , 1997 Class B Telephone: CTR21 as specified in Council Decision 98/482/EC Supplementary Information The product herewith complies with the requirements of the following Directives and carries the CE marking accordingly: the EMC directive 89/336/EWG the Low Voltage Directive 93/68/EEC Zufikon, 1. Juli 2009 Silvan Tognella 40
EXICALL EN70 EXICALL EN70MR EXICALL EN70-ATEX
LEITRONIC AG Swiss Security Systems ELEVATOR EMERGENCY DIALLER EXICALL EN70 EXICALL EN70MR EXICALL EN70-ATEX Issue: 18 August 011 1. Door phone (EXICALL EN70) EN81-70 emergency button Center> 90cm (
More informationEasyAlarm ELEVATOR LEITRONIC AG
LEITRONIC AG Swiss Security Systems ELEVATOR EMERGENCY DIALLER BROCHURE EasyAlarm ELEVATOR Independent elevator emergency call by Swiss market leader can be installed / operated by any elevator company
More informationEA-MINI / EA-MINI-V. LEITRONIC AG Swiss Security Systems
4923 Table of contents Overview... 2 2 Applications... 3 2. Door-phone... 3 2.. Wiring... 3 2.2 Alarm dialler... 4 2.2. Wiring... 4 3 Mechanical fitting... 5 3. Retrofit solutions to existing elevators...
More informationUser instructions EasyAlarm CONTROL
LEITRONIC AG Swiss Security Systems TELEMONITORING / TELECONTROLLING SYSTEM User instructions EasyAlarm CONTROL Interface-Modul Potential free relay switch: 10..230V AC or DC AC-switch: max. 2A / 230V
More informationLEITRONIC AG Swiss Security Systems EasyAlarm ELEVATOR
LEITRONIC AG Swiss Security Systems EasyAlarm ELEVATOR Code: 0221 Isue: Issue: 7/2017 11 / 2014 Start-up Program calling numbers 5.1 Write down numbers 1 Announcement 2 Announcement 3 Announcement 4 Announcement
More informationMemcom Emergency Telephone
Memcom Emergency Telephone Installation Guide Ref No. 450 900 (GB) Version 2 + + Simple wiring for quick installation + + Integrated LCD display shows you what you have programmed + + All code based programming
More informationADE Gen4. Speech Dialler Engineering Information. Description. Features
ADE Gen4 Speech Dialler Engineering Information Description The Informa is a Speech Dialler for use with intruder alarm systems. When the control panel recognises an alarm it triggers the Informa. The
More informationHELPY QUICK-TL GSM INTL
Alarm system for elevators HELPY QUICK-TL GSM INTL QUICK GUIDE 04/02/16 DESCRIPTION A B C D E F G H I L M N O Connector for external LEDs Connector for built-in loudspeaker Built-in loudspeaker Connector
More informationMEDI-CALL UNIT INSTALLATION MANUAL. Medi-Call V2.0 - V2.7 Installation Manual
MEDI-CALL UNIT INSTALLATION MANUAL Medi-Call V2.0 - V2.7 Installation Manual Copyright SmartLink International Pty Ltd February 2006 475 Nepean Highway, Brighton VIC 3186 Australia Telephone: +61 3 9596
More informationA1UL PERS. Personal Emergency Response System. For Technical Support Please Contact Your Service Provider Or Distributor
A1UL PERS Personal Emergency Response System TABLE OF CONTENTS 1. READ THIS FIRST... 1 2. SYSTEM OVERVIEW.. 1 3. COMPONENTS 2 4. UNIT OPERATION! Standby Mode.. 3! Emergency Activation. 3! Answering Incoming
More informationThe Windcrest Remote Alarm for Passenger and Goods Lifts with Optional BS EN81-28 & BS EN81-70
The Windcrest Remote Alarm for Passenger and Goods Lifts with Optional BS EN81-28 & BS EN81-70 1. Identify the Equipment and carry out a Risk Assessment before installation AD1000EN- 1R Main Unit EN1 Speaker
More informationANEP S-BOX EMERGENCY TELEPHONE FOR ELEVATORS.
ANEP S-BOX EMERGENCY TELEPHONE FOR ELEVATORS www.anepanywhere.com SUMMARY 1 - TECHNICAL CHARACTERISTICS Page 4 1.1 - Technical characteristics 1.2 - Machine room Intercom and fireman until functionnality
More informationTo activate using remote control: press [ ] key once. To activate using keyboard: on panel keyboard [ ] keys once.
Table of Content 1.1General Description----------------------------------------------------------------------2 2.2System Setup-----------------------------------------------------------------------------3
More informationAUTODIALER SYSTEM FOR LIFTS MANUAL HELPY 2W-V
AUTODIALER SYSTEM FOR LIFTS MANUAL HELPY 2W-V 05/06/2018 DESCRIPTION Autodialer to be fitted behind the cop or on top of the car / retrofit. A Connector for Esse-ti power supply (12 Vdc) B Micro SD Card
More informationMOBILE CALL GSM Alarm System User s Manual
MOBILE CALL GSM Alarm System User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. Contents Function Introduction (3) Alarm Host Diagram
More informationAGRI-ALERT 9600 ALARM SYSTEM USER MANUAL
AGRI-ALERT 9600 ALARM SYSTEM USER MANUAL M 890-00279 rev. 14 K 895-00004 rev. 00 Manufacturer: Viatron Electronics 5200, Armand-Frappier St-Hubert (Quebec) Canada J3Z 1G5 WARNINGS The warranty can be void
More informationBENTEL SECURITY reserves the right to modify the technical features of this product without prior notice.
BENTEL SECURITY reserves the right to modify the technical features of this product without prior notice. via Florida Z.I. Valtesino - 63013 GROTTAMMARE (AP) - ITALY Installation and Quick guide: DUAL
More informationPreface. Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock.
Preface Thank you for purchasing our GSM Security Alarm System ( The System )! The System will keep your home and property safe around the clock. The GSM Security Alarm ( The Alarm ) adopts the most advanced
More informationl 02-April-2010 For INSTANT CARE
l 02-April-2010 For INSTANT CARE Table of Contents 1. Application Overview 1 1.1. Identifying The Parts 1 1.2. The Power Supply 3 1.3. Line Capture 3 1.4. Line Failure Detection 4 1.5. How to install the
More informationSecurity GSM Alarm System
Security GSM Alarm System USER MANUAL 4 wired and 6 wireless defense zones; Can preset and store 6 voice phones and 3 message phones; Remote two-way intercom; Telephone (mobile phone) remote control programming;
More informationMemcom + Emergency Telephone
Memcom + Emergency Telephone Installation Guide Ref No. 453 901AU (GB) Version 4 + + Simple wiring for quick installation + + Integrated LCD display shows you what you have programmed + + All code based
More informationALARM SYSTEM USER S MANUAL Rev
ALARM SYSTEM USER S MANUAL Rev.06 890-00011 Manufacturer: Viatron Electronics 3514 1st Street, St-Hubert (Quebec) Canada J3Y 8Y5 WARNINGS the warranty can be void if the Agri-Alert 2400 is used in a manner
More informationTYDOM 315. * _Rev.2* GSM domotics transmitter. 1. Presentation
TYDOM 5 GSM domotics transmitter ) Présentation. Presentation Delta Dore hereby declares that the equipment complies with the essential requirements and other relevant provisions of the R&TTE Directive
More informationHELPY CONTROLLER QUICK GUIDE
Alarm system for elevators compliant with the European Standard EN 81-28:2018 HELPY CONTROLLER QUICK GUIDE 05/04/2019 DESCRIPTION Autodialer specifically designed for installation on elevator controller.
More informationProfile. For a better understanding of this product, please read this user manual thoroughly before using it.
Intelligent GSM Auto-Dial Alarm System User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. Contents Function Introduction (3) Alarm
More informationDYGIZONE GJD910 Lighting Controller & Enunciator
DYGIZONE GJD910 Lighting Controller & Enunciator MASTER WIRING IDENTIFICATION Power up to the DygiZone and you will see: All the LED s (red,yellow,green and blue buttons) will flash All the LCD icons will
More informationIntelligent Wireless GSM Alarm System
Intelligent Wireless GSM Alarm System 00M2K User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. Contents [Function Instruction] [Alarm
More informationV1.0. Smart Home Alarm System. User Manual. APP download via QR Code scanning. Please read the manual carefully before using.
V1.0 Smart Home Alarm System User Manual APP download via QR Code scanning Please read the manual carefully before using. Content FUNCTION PROFILE 2 THE SCHEMATIC GRAPH OF HOST 3 PROCESS OF BOOTING 6 OPERATION
More information1. User features of the GSM dialer
1. User features of the GSM dialer The JA60GSM dialer offers many useful features described in detail below. The installer should properly demonstrate the use of the system to the user after installation
More informationDESCRIPTION INSTALLATION
DESCRIPTION The Model 10A11 Two-Way Audio/Voice Alarm Module allows two-way communication with a central station after an alarm, paging and listening from an on-premises or remote phone, annunciation of
More informationAll-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160
All-In-One Wireless Security System V3.2 Programming Guide Model # MG6130 / MG6160 We hope this product performs to your complete satisfaction. Should you have any questions or comments, please visit www.paradox.com
More informationUser Manual (LS-GSM-006)
GSM Home/Business Alarm System User Manual (LS-GSM-006) Profile For a better understanding of this product, please read this user manual thoroughly before using it. - 1 - Catalogue: Function Introduction
More informationIRIS Touch Firmware Enhancements and Additions from Version to Version
Overview IRIS Touch Firmware Enhancements and Additions from Version 1.14.3 to Version 1.19.1 This document details enhancements to the feature set of the IRIS Touch from firmware Version 1.14.3 to Version
More informationUSER S MANUAL. Profile. MOBILE CALL GSM Alarm System
MOBILE CALL GSM Alarm System USER S MANUAL System disarmed 00/00/00 00:00 ARM STAY CALL 1 2 3 4 5 6 7 8 9 Power Set Signal Alarm SOS ESC 0 ENTER Profile For a better understanding of this product, please
More informationAT60 AUTO DIALLER User Guide
AT60 AUTO DIALLER User Guide Power on LED MIC Power on LED MIC 1 2 3 4 5 6 7 8 9 REC/PLAY 0 STORE M1 M2 M3 Table of Contents I. Overview 3 II. Installation 4 III. Initialize the Dialer 5 IV. Using the
More informationWolf Guard Touch Keypad GSM Wireless alarm system User s Manual
Wolf Guard Touch Keypad GSM Wireless alarm system User s Manual Page 1 Warning Do not remove the front or back cover of the unit and keep it intact. There are no parts inside this unit that can be repaired
More informationANEP BOX - TA EMERGENCY TELEPHONE AND INTERCOM SYSTEM FOR LIFTS EMERGENCY TELEPHONE FOR LIFTS.
ANEP BOX - TA EMERGENCY TELEPHONE FOR LIFTS EMERGENCY TELEPHONE AND INTERCOM SYSTEM FOR LIFTS www.anepstore.com SUMMARY 1 - TECHNICAL CHARACTERISTICS Page 4 1.1 - Technical characteristics 1.2 - Machine
More informationElite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand
6 Elite 16D Version 16 Zone Controller Arrowhead Alarm Products Ltd Operating Guide 1 Proudly Designed and Manufactured in New Zealand CONTENTS Page No. INTRODUCTION 3 About your Alarm 3 OPERATING YOUR
More informationNESS 5000 SERIES DIALLER
NESS 5000 SERIES DIALLER INSTALLATION MANUAL This manual is designed to provide the installation instructions on the NESS SECURITY PRODUCT'S 5000 SERIES Dialler. For complete details on the warranty or
More informationGSM RFID VOICE Alarm System
GSM RFID VOICE Alarm System User s Manual For a better understanding of this product, please read this user manual thoroughly before using it. CONTENTS [Function Instruction] [Control Panel] Control Panel
More informationContents. Glossary
Contents Glossary ------------------------------------------------------------------------------------------------------ 6 1. Introduction to the IDS 1632 -------------------------------------------------------------
More informationVoice Board. Installation and Programming Guide. Runner 4/8,PowerWave 4/8/16 &, Elite64. Add-on Board For Storing Recorded Voice Messages
ELECTRONIC ENGINEERING LTD. Voice Board Runner 4/8,PowerWave 4/8/16 &, Elite64 Add-on Board For Storing Recorded Voice Messages And listen-in. Installation and Programming Guide. P/N 7101372 Rev. C V.K
More informationAny additional devices linked to the system ET08 (computer, sensors, relays etc.) must be approved by LST EN standard.
COMMUNICATOR ET08 User Manual v1.0 Safety instructions Please read and follow these safety guidelines in order to maintain safety of operators and people around: GSM communicator (gateway) ET08 (further
More informationCONTENTS. (User s Manual)
CONTENTS (User s Manual) 1. Foreword & Main Features & Brief introduction of the Product 2. Understanding of Alarm Host 3. Specifications 4. Type and definition of Defense Line 5. Programming the alarm
More informationSC-F3G User Manual 1.0
SC-F3G User Manual 1.0 Table of Contents 1. Introduction... 3 2. Functions... 3 3. Features... 3 4. Package Contents... 3 5. Device Configuration... 4 6. Status LED signals... 5 7. Before You Start...
More informationWIRELESS ALARM SYSTEM WITH TELEPHONE AUTO DIALER
BAT.LOW AC WIRELESS ALARM SYSTEM WITH TELEPHONE AUTO DIALER THE SYSTEM THAT CALLS YOU! Our WIRELESS ALARM SYSTEM WITH TELEPHONE AUTO DIALER is designed to allow you to create your own security system.
More informationBasic Installation Manual
SAR SAR-V.7 Program or Higher Alarm Equipment for Lifts Basic Installation Manual in HIDRA System controllers Revision 0 (EN) NOTES FROM THE MANUFACTURER Carlos Silva SA shall not be responsible for any
More informationHRX Technical Manual. Version 1.2
HRX 5000 Technical Manual Version 1.2 Contents: Specification...2 Connectors...5 RS-485 Network Connectors (J6 and J7)...5 RS-232 to Printer (J19)...6 RS-232 to PC (J8)...7 TCP/IP...8 Power (J21)...9 Fire
More informationSOFTWARE VERSION 2.20 CONTROL PANEL RESET:
-961112-0002 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3
More informationEVO192 v3.0 Fire and Burglary What s New
EVO192 v3.0 Fire and Burglary What s New Compatibility: EVO192 v3.0 TM50 v1.31 K641 v2.41 Overview: CP-01 Compliancy Wiring Diagram The following sections/options have been added to the EVO192 panel. They
More informationVersion 1.03 January-2002 USER S MANUAL
Version 1.03 January-2002 1 USER S MANUAL 2 Version 1.03 January-2002 System Details CUSTOMER:...... PHONE:... FAX:... INSTALLED BY:...... PHONE:... FAX:... MAINTENANCE & SERVICE:...... PHONE:... FAX:...
More informationUSER & INSTALLATION GUIDE
Reach Plus At Home Alarm Unit Touch Personal Pendant USER & INSTALLATION GUIDE www.tynetec.co.uk SECTION 1 USER INSTRUCTIONS Section Topic Page 1.1 Important Information 3 1.2 Unpacking the Reach Plus
More informationRVRC Training Manual Fast Trace Installer Menu
RVRC Training Manual Fast Trace Installer Menu Advanced Independent Monitoring Introduction The following guide is explain how to set up a Fast Trace or Fast TX and common areas to look out for and check
More informationUniversal fault annunciator for panel mounting
Universal fault annunciator for panel mounting Communication over Ethernet USM - Universal-fault annunciator for panel mounting Low depth housing for panel mounting Versions with 8, 16, 32 or 48 inputs
More informationSOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)
-961112-0003 SOFTWARE VERSI 2.20 CTROL PANEL RESET: Installer lock must be unlocked. ( 255: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (4) Wait 3
More informationGSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System
MOBILE CALL GSM Alarm System GSM Alarm System System disarmed 11/26/2013 User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. CONTENTS
More informationHEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING
-961212-0004 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. ( 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2) Connect
More informationQUICKFIT INSTALL HOOK-UP SHEET FOR ESL KIT REV 1.17 OP
QUICKFIT INSTALL HOOK-UP SHEET FOR ESL KIT REV 1.17 OP PROGRAMMING STARTS Entering Installer mode If you want to get into program mode press followed by your installer code, default set to 000000
More informationAES IntelliTAP. Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device. Version Installation Guide CONTENTS
AES IntelliTAP Satellite / Remote Dialer Data Receiver Page 1 AES IntelliTAP Model 7068 Digital Dialer Interface A Supplemental Alarm Reporting Device Version 1.10 Installation Guide CONTENTS How it Works
More informationOPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL
ap15_2manual04/22/13 Page 1 4/22/2013 1 Serial Number : Option: OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL Micro Seven, Inc. 1095-K N.E. 25th Hillsboro, OR 97124 U.S.A. phone: 503-693-6982
More informationFire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96
Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96 XL-2G Gold Product Overview 7 Zones (6 programmable + panic or keyswitch zone) Fast Loop Response
More informationUser guide Fire brigade communication system EN 81-72
User guide Fire brigade communication system EN 81-72 SCHAEFER GmbH Winterlinger Straße 4 72488 Sigmaringen Germany Telephone +49 7571 722-0 Fax +49 7571 722-98 info@ws-schaefer.de www.ws-schaefer.de SCHAEFER
More informationD169 2-Way Voice Verification Module. Installation and Operating Manual Radionics 34105B 3/97
D169 2-Way Voice Verification Module Installation and Operating Manual Notice The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be reliable.
More informationHEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING
48ESEP-01 SOFTWARE VERSION 3.10 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 058: enter any value other than 147) Power down reset (1) Remove battery and AC to power down the unit. (2)
More informationElite 64 Version 64 Zone Controller Arrowhead Alarm Products Ltd. Operating Guide. Proudly Designed and Manufactured in New Zealand
2 Elite 64 Version 64 Zone Controller Arrowhead Alarm Products Ltd Operating Guide Proudly Designed and Manufactured in New Zealand 1 CONTENTS Page No. INTRODUCTION 3 About your Alarm 3 OPERATING YOUR
More informationEC-P Zone Intruder Alarm System
EC-P10 10-20 Zone Intruder Alarm System Installation Manual Contents 1. System Overview... 4 System Configuration... 4 Control Panel... 5 Remote Keypads... 5 EC-LED Remote Keypad... 5 EC-LCD Remote Keypad...
More informationComfort, the Intelligent Home System. Comfort Evaluation Kit
Comfort, the Intelligent Home System Comfort Evaluation Kit Contents SECTION 1 Overview and Specifications...1 Introduction...1 Components Included*...2 Documents Included*...4 Presentation/Training*...4
More informationAD1000EN-1R configured to operate as a DG1000
AD1000EN-1R configured to operate as a DG1000 Install the Main Unit on top of the lift car and mount the Microphone in the COP. Mount the Plastic speaker box so the speaker holes align up with some holes
More informationSolution-16/ Solution-16 Safecom Installation Manual ISSUE 2.10
Solution-16/ Solution-16 Safecom Installation Manual ISSUE 2.10 MA880I Solution-16/ This page has been included for you to cut out and insert into the spine of the folder Solution-16 Safecom Installation
More informationCC880/LP880, SC8016. Operators Guide Solution-16, Solution-16 Safecom
CC880/LP880, SC8016 EN Operators Guide Solution-16, Solution-16 Safecom CC880/LP880, SC8016 Operators Guide EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch
More informationPipo Communications. Model ST-888. DTMF ANI/ENI Display Decoder
Pipo Communications Model ST-888 DTMF ANI/ENI Display Decoder 1516 Cassil Place Hollywood, California 90028-7106 Phone: 323-466-5444 Fax: 323-466-1520 www.pipo.cc Manual # 68-9888 May 1, 2002 Rev. 5/02
More informationSection 9 System Operation
Section 9 System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this
More information2G & 3G GSM Door Contact Alarm
2G & 3G GSM Door Contact Alarm www.gsm-activate.co.uk MODEL RF - PIR PAGE 1 Product Information Our 2G/3G GSM Door Contact Alarm is a standalone alarm system for smaller rooms inside properties. It will
More informationGSM Smart Home Alarm Apparatus. [99+4 defense zones] Instruction for Use
GSM Smart Home Alarm Apparatus [99+4 defense zones] Instruction for Use Table of content Ⅰ. Introduction to the system... 2 Ⅱ. Introduction to function... 2 Ⅲ. System composition and use method... 3 Ⅳ.
More informationAuto Dialer. Manual E-921APQ E-921GPQ
Troubleshooting: Auto dialer will not arm/disarm Auto dialer will not dial out Unit doesn t respond to a call-back Difficulty in activating room monitor by telephone remote control Make sure that you have
More informationInstallation Manual Premier 412/816/832. Issue 10
Installation Manual Premier // Issue 0 Premier // Installation Manual 5. Operating the System Introduction Before attempting to operate the alarm system ensure you have familiarised yourself with all the
More informationAgri-Alert 800EZe. Alarm System. Alarm. System in Standby. Burglary Armed. Online (phone) Green = zone activated Amber = zone bypassed.
Agri-Alert 800EZe Alarm System User s Manual Alarm System in Standby Burglary Armed 1 2 ZONES 5 6 Online (phone) 3 7 4 8 Green = zone activated Amber = zone bypassed ZONE LIGHTS LEGEND Red = zone in alarm
More informationDL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL
DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL TABLE OF CONTENTS 1. GENERAL DESCRIPTION... 2 2. STANDARD AND OPTIONAL PARTS LIST... 2 3. FEATURE DEFINITIONS... 3 4. TERMINAL DRAWING AND SPECIAL
More informationRadio fire warning panel SRC 3000
Radio fire warning panel SRC 3000 6 zone radio fire warning panel Operating instructions Version 1.2 Art. 32487 detectomat GmbH Headquarter: Phone: +49 (0) 4102-2114-60 An der Strusbek 5 Fax: +49 (0) 4102-2114-670
More informationAlarm Control Panel WIC-16Z4P WIC-5Z2P. Installation & Operation User Manual
WIC-16Z4P WIC-5Z2P Installation & Operation User Manual Page : 1/34 INDEX # Function Page 1 Abort Current Communication and Clear Reporting Queue (*59) 13 2 Abort Current Communications (*59) 10 3 Account
More informationAgri-Alert 800 EZe Alarm System Owner s manual
Agri-Alert 800 EZe Alarm System Owner s manual Read this guide carefully before using the alarm system. Manufacturer: Viatron Electronics 5200, Armand-Frappier St-Hubert (Quebec) Canada J3Z 1G5 WARNINGS
More informationQuick Installation Manual LED Touch Keypad Autodial Wireless Alarm System
Quick Installation Manual LED Touch Keypad Autodial Wireless Alarm System By shield4u http:// (Version 20110816) A. Alarm Understanding Away Disarm Home Emergency Function Signal Interpretation Buzzer
More informationDestiny Destiny Owners Manual
Destiny 4100 Destiny 4100 Owners Manual TABLE OF CONTENTS INTRODUCTION Control Panel...3 Detection Devices...3 Telephone Keypads...3 GLOSSARY... 4-5 LOCAL PHONE ACCESS Using Your Telephones As Keypads...6
More informationBURGLAR ALARM PANEL BS-468
BURGLAR ALARM PANEL BS-468 Contents 1. Description... 3 2. Instructions for the user... 4 2.1Basic operations... 4 Complete system.... 4 Split system.... 4 2.2 Armed system indication... 5 2.3 Advanced
More informationGSM Emergency Alarm. User s Manual. For a better understanding of this porduct,please read this user manual thoroughly before using it.
Version: MS1 GSM Emergency Alarm User s Manual For a better understanding of this porduct,please read this user manual thoroughly before using it. CONTENTS CONTENTS Ⅰ. Introduction Ⅱ. Product Appearance
More information2000 Series. Program Entry Guide. Control Panels
2000 Series EN Program Entry Guide Control Panels 2000 Series Program Entry Guide About This Manual EN 2 About This Manual This guide describes the programming parameters available to the 2000 Series Control
More informationAVCOM System Installation Instructions
AVCOM System Installation Instructions Index 1) AVCOM EN-1 System Drawings - AVCOM EN1 System.. Page 1 - AVCOM EN1 with 2COP.. Page 2 - AVCOM EN1 FF System.. Page 3 -AVCOM EN1 Evacuation System Page 4
More informationSystem. For a better understanding of this product, please read this user manual thoroughly before using it.
GSM Alarm System User s Manual For a better understanding of this product, please read this user manual thoroughly before using it. Chapter 1. Features Chapter 2. Control Panel Introduction Chapter 3.
More informationProCom The App for Alarm Systems in the Protect Series Operating Manual
ProCom The App for Alarm Systems in the Protect Series Operating Manual Contents Before You Start........................................... 4 Read the Operating Manual....................................
More information1. Introduction. 2. Product overview
1. Introduction The AG400011 GSM Alarm panel is a control panel that is compatible with other H-net security devices from Everspring, such as wireless sensors, remote keyfobs, tags, and keypad. With this
More informationJA-63 PROFI Alarm System MGK55402
Contents: 1 Architecture of the control panel... 4 2 Control panel installation... 4 2.1 Mains supply connection... 5 3 Antenna for the radio module... 5 3.1 Rubber rod antenna used in the control panel...
More informationDigiPlus INSTRUCTION MANUAL
DigiPlus INSTRUCTION MANUAL Introduction DigiPlus DigiPlus is a converter for use with Digital Communicators (and Control Panels with built-in Digital Communicators) that use Fast Format DTMF signalling
More informationCC408. Quick Reference Guide Solution 880
CC408 EN Quick Reference Guide Solution 880 CC408 Quick Reference Guide Notices EN 2 Copyright Notice Unless otherwise indicated, this publication is the copyright of Bosch Security Systems Pty Ltd ( Bosch
More informationGSM AUTO DIALLER WIRELESS ALARM SYSTEM MODEL AD-SD MODEL AD-SD-W www.gsm-activate.co.uk Model AD-SD & Model AD-SD-W PAGE 1 Product Information Our AD-SD Auto Dialler is a versatile unit which can be attached
More informationInstallation & Operation Manual March 2017 Rev. 4.1
Installation & Operation Manual March 2017 Rev. 4.1 #200, 550 71 st Avenue SE Phone: (403) 255-9544 Calgary, Alberta, Canada Fax: (403) 259-2343 T2H 0S6 www.barnettprotalk.com email: sales@barnettprotalk.com
More informationUSER CODES. User Codes (1-6 digits) Access Levels + Access Levels. Time Control Address Address Address Address User 1 (Master)
User Codes (1-6 digits) Access Levels Access Levels + Time Control User 1 (Master) 1 1 2 3 25 49 73 0 User 2 2 26 50 74 0 User 3 3 27 51 75 0 User 4 4 28 52 76 0 User 5 5 29 53 77 0 User 6 6 30 54 78 0
More informationCentaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE
Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment
More informationL900 series USER MANUAL
INTRODUCTION The BLUGUARD Control Panel is designed for simple operation yet provides the maximum protection for you. Please read this manual carefully and follow the instructions contained in this book.
More informationUser Manual. with LED Keypad. Alarm Control Panel CA10 plus (software version 4.7) GDAŃSK. ca10pldu_e 07/03
User Manual Alarm Control Panel CA10 plus (software version 4.7) with LED Keypad GDAŃSK ca10pldu_e 07/03 WARNING In order to avoid any operational problems with the control panel, it is recommended that
More informationSection 8 System Operation
Section 8 System Operation Operation of the control panel is simple. Menus guide you step-by-step through operations. This section of the manual is an overview of the operation menus. Please read this
More information