MA Electric Code Challenges for Architects

Size: px
Start display at page:

Download "MA Electric Code Challenges for Architects"

Transcription

1 MA Electric Code Challenges for Architects Boston Society of Architects Codes Committee March 19, 2013 Presented by Doug Anderson 313 Congress Street Boston, MA fax

2 Best Practice Commercial Construction Consulting is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members. Certificates of Completion for non-aia members are available upon request. This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

3 SL1 Learning Objectives Basics of electrical engineering Scope of the NEC and review of the MA Amendments Differences between emergency and standby power Architectural impacts of electrical code requirements

4 Slide 3 SL1 Needs a 4th learning objective Sara Lavado, 3/15/2013

5 Basics of Electrical Engineering V = Voltage The force behind electricity I = Current (amperes) The volume of flow of electricity R = Resistance (ohms) The resistance to the flow W = Power (watts) Measure of work

6 Basics of Electrical Engineering Ohm s Law V = Voltage I = Current (amperage) R = Resistance V = I * R

7 Basics of Electrical Engineering DC = Direct Current AC = Alternating Current

8 Basics of Electrical Engineering Power V = Voltage I = Current (amperage) P = Power (watts) (AC & DC) VA = Volt-amperes (AC) P = V * I * pf (power factor)

9 Basics of Electrical Engineering AC Power VA = V * I P = V * I * pf (power factor)

10 Basics of Electrical Engineering Three phase AC Power

11 Basics of Electrical Engineering Three phase AC Power

12 Basics of Electrical Engineering Power Losses P = V * I P = (I*R) * I P = I 2 * R

13 Basics of Electrical Engineering Power Losses 10,000 kw: 480V * 21A (#10, 3.3 ohms/3,000 ft) 240V * 42A (#6, 1.3 ohms/3,000 ft)

14 Basics of Electrical Engineering Power Losses P = I 2 * R 21 2 * 3.3 ohms = 1,450 VA loss 42 2 * 1.3 ohms = 2,300 VA loss

15 Basics of Electrical Engineering Transformers 240V * 42A 480V * 21A Power is constant

16 Scope of the NEC Installations Wiring Methods Wiring Materials Equipment Special Conditions (emergency and stand by)

17 Scope of the NEC, MA amendments

18 Scope of the NEC, MA amendments

19 Scope of the NEC, Installations Working Space/ Working Clearance

20 Scope of the NEC, Installations Working Space Working Clearance

21 Scope of the NEC, Installations Working Space Working Clearance

22 Scope of the NEC, Installations Working Space Working Clearance

23 Scope of the NEC, Installations Working Space Working Clearance

24 Emergency & Stand-By Power Scoping requirements for each are in the Building Code Emergency Power: Exit Signs Egress Lighting Elevator (travel >70 feet, 524 CMR) High Rise: Fire Pump Elevator Fire Alarm and Detection Systems Voice Evacuation

25 Emergency & Stand-By Power Legally Required Stand-by Power: High Rise: Fire Command Center Smoke Control systems

26 Emergency & Stand-By Power Sources of Emergency and Stand-by Power: Generators Batteries

27 Emergency & Stand-By Power Sources of Emergency and Stand-by Power: Separate Service Fuel Cells

28 Emergency & Stand-By Power Installation Requirements of Emergency and Stand-by Power Two Hour Separation required for Prime Mover ATS Smoke Control Controls Emergency Only: Feeders to Panelboards

29 Architectural Impacts Room Sizes Room Locations Room Ratings Shafts

30 Thank you for your time! Questions? This concludes The American Institute of Architects Continuing Education Systems Program Doug Anderson 313 Congress Street Boston, MA fax

31 C 3 Services: MEP / FP Engineering Due Diligence Construction Management Owner s Representatives Development Advisory Code Advisory Building Envelope 313 Congress Street Boston, MA fax

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Richard B. Alpert, P.E. Senior FPE, Clark Nexsen Clark Nexsen is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of

More information

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com

More information

Sprinklers in Wood-Frame Construction:

Sprinklers in Wood-Frame Construction: Sprinklers in Wood-Frame Construction: What Architects and Engineers Need to Know Presented by: Brian D. Kuhn Jr., P.E. (MA, CA, DC, 6 others), LEED Green Associate Please add relevant logo here Disclaimer:

More information

SP07: Coordinating New Door Assembly Installation with Access Control Systems

SP07: Coordinating New Door Assembly Installation with Access Control Systems SP07: Coordinating New Door Assembly Installation with Access Control Systems Keith E. Pardoe, DAHC, CDC, CDT Door and Hardware Institute (DHI) Thursday, April 11, 2013 Provider #: K054 Learning Objectives

More information

Preview of the MA Building Code (780 CMR) 9 th edition

Preview of the MA Building Code (780 CMR) 9 th edition Preview of the MA Building Code (780 CMR) 9 th edition Presented by: Ron Melucci, P.E. Engineering Planning and Management, Inc rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering Planning and Management,

More information

LED Lighting: Technology Selection and System Commissioning Course Number: CXENERGY1519

LED Lighting: Technology Selection and System Commissioning Course Number: CXENERGY1519 AABC Commissioning Group AIA Provider Number: 50111116 LED Lighting: Technology Selection and System Commissioning Course Number: CXENERGY1519 Michael Chow, P.E., CxA, LEED AP BD+C, Metro CD Engineering

More information

Common Building Code Misinterpretations

Common Building Code Misinterpretations Common Building Code Misinterpretations Presented by: Ron Melucci, P.E. Technical Manager, FP Division Engineering Planning and Management, Inc. rbm@epm inc.com www.epm inc.com 508 875 2121 Engineering

More information

Building Analytics and Compliance: How analytics can be used to aid in performancebased certifications. Bryant M. Kirkland Jr, PE, CCP, LEED AP

Building Analytics and Compliance: How analytics can be used to aid in performancebased certifications. Bryant M. Kirkland Jr, PE, CCP, LEED AP Building Analytics and Compliance: How analytics can be used to aid in performancebased certifications Bryant M. Kirkland Jr, PE, CCP, LEED AP AIA Quality Assurance The Building Commissioning Association

More information

2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments

2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments 2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments Based on the International Residential Code (IRC ) GR PPN 1208 Course Approval # 12085 Description This seminar reviews and

More information

Applied Lighting Controls

Applied Lighting Controls Better Buildings By Design 2010 Applied Lighting Controls Steven Mesh, LC, IESNA Senior Lighting Program Coordinator Pacific Energy Center (Pacific Gas & Electric) 851 Howard Street, San Francisco, CA

More information

ELECTRICAL Seminar. B A L A Consulting Engineers, Inc. Edward J. Lynch, PE Vice President, Electrical Department Manager.

ELECTRICAL Seminar. B A L A Consulting Engineers, Inc. Edward J. Lynch, PE Vice President, Electrical Department Manager. B A L A Consulting Engineers, Inc. PECO Line 13.2kV Incoming Service No. 1 Utility/Generator Medium Voltage Switchgear PECO Line 13.2kV Incoming Service No. 2 Unit Substation ELECTRICAL Seminar HVAC Equip.

More information

Roofing Industry Update. Welcome!

Roofing Industry Update. Welcome! Welcome! CRCA / OSHA Alliance CRCA Trade Show Committees CRCA & RCI Updates Roofing Past, Present, Future CRCA is a Registered Provider with The American Institute of Architects Continuing Education Systems.

More information

Green and Gray Infrastucture

Green and Gray Infrastucture Learning Objectives Make Your Vegetated Roof Work Harder as a Stormwater BMP Richard C. Hayden, RLA ASLA CLARB American Hydrotech, Inc. Brian Taylor, PE AMEC 1. Learn how vegetated roofs can be used as

More information

Establishing the Risk Basis of Building Size Limits

Establishing the Risk Basis of Building Size Limits Establishing the Risk Basis of Building Size Limits A look at the history of development of our building codes and safety opportunities to facilitate wood design initiatives. Presented on January 27, 2015

More information

How to Heat Water in All-Electric Homes & Apartments?

How to Heat Water in All-Electric Homes & Apartments? How to Heat Water in All-Electric Homes & Apartments? March 2015 NEW YORK, NY WASHINGTON, DC NORWALK, CT Robb Aldrich Steven Winter Associates, Inc. raldrich@swinter.com 1 AIA CEU Info Credit(s) earned

More information

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx Case Study: Furman University Charles H. Townes Center for Science Michael K. Mantai, PE, CCP President System WorCx AIA Quality Assurance Learning Objectives 1. Case study example of Chilled Beam technology

More information

Questions related to specific materials, methods, and services will be addressed at the conclusion of the presentation.

Questions related to specific materials, methods, and services will be addressed at the conclusion of the presentation. SAFTI FIRST is a Registered Provider with the American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.

More information

ELECTRICAL POWER SYSTEMS

ELECTRICAL POWER SYSTEMS Scope The various Codes applicable to the University's electrical power system are mainly based upon a model of a single utility service, connected to a single premise. The University s electrical system,

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

Steven Winter Associates, Inc. J827

Steven Winter Associates, Inc. J827 Steven Winter Associates, Inc. J827 Multifamily Domestic Hot Water Design: How Can We Do Better? GBPP 109 Dylan Martello 2/16/2018 Steven Winter Associates Since 1972, SWA has been providing research,

More information

Impact of Minimum Fan Efficiency Grade. Dr. John Cermak Executive Vice President ACME Engineering and Manufacturing Corp.

Impact of Minimum Fan Efficiency Grade. Dr. John Cermak Executive Vice President ACME Engineering and Manufacturing Corp. Impact of Minimum Fan Efficiency Grade Dr. John Cermak Executive Vice President ACME Engineering and Manufacturing Corp. Learning Objec-ves 1. Describe Fan Efficiency Grade (FEG) 2. Describe the use and

More information

Opportunities for Local Program Implementers Under the Energy Policy Act of Energy Bill Efficiency Sections

Opportunities for Local Program Implementers Under the Energy Policy Act of Energy Bill Efficiency Sections Opportunities for Local Program Implementers Under the Energy Policy Act of 2003 Steven Nadel American Council for an Energy-Efficient Economy Washington, DC Energy Bill Efficiency Sections Tax credits

More information

Historic Preservation s Future : Willowbank School of Restoration Arts. Lisa Prosper

Historic Preservation s Future : Willowbank School of Restoration Arts. Lisa Prosper Historic Preservation s Future : Willowbank School of Restoration Arts Lisa Prosper AIA Rochester Our mission is to promote the profession and practice of Architecture in the Greater Rochester Area. We

More information

Fire Rated Door Assemblies: Compliant Designs

Fire Rated Door Assemblies: Compliant Designs Fire Rated Door Assemblies: Compliant Designs Steel Door Institute www.steeldoor.org AIA Provider #G389 Course #: SDIFIRE 1 HSW CE hour 1 Credit(s) earned on completion of this course will be reported

More information

2016 Annual Conference

2016 Annual Conference 2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance

More information

Engineering Systems an Incremental Response to Terrorist Threat

Engineering Systems an Incremental Response to Terrorist Threat ctbuh.org/papers Title: Authors: Subject: Keywords: Engineering Systems an Incremental Response to Terrorist Threat Norman D. Kurtz, Principal, WSP Flack + Kurtz Andrew Hlushko, Director, WSP Flack + Kurtz

More information

Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT

Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.com Gary Klein, 2012 Efficiency

More information

CLT Adhesive Tests in Support of Mass Timber Buildings

CLT Adhesive Tests in Support of Mass Timber Buildings CLT Adhesive Tests in Support of Mass Timber Buildings DES604 Jason Smart, P.E. Manager, Engineering Technology American Wood Council Sam Francis, C.B.O. Senior Director, National Programs American Wood

More information

FM Approval Standard For Cavity Walls And Rainscreens

FM Approval Standard For Cavity Walls And Rainscreens FM4411 - Approval Standard For Cavity Walls And Rainscreens Mark D. Tyrol, P.E. FM Approvals Air Barrier Association of America (ABAA) is a Registered Provider with The American Institute of Architects

More information

Design for New Construction and

Design for New Construction and Presentation Restore Media Photographs & Illustrations Stephen A. Mouzon Design for New Construction and This presentation qualifies for AIA Continuing Education credit as detailed on subsequent images.

More information

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators GPS 140 NEC Requirements for Generators WHAT YOU WILL LEARN NEC requirements for on-site power generation. Recent events have created increased interest in standby power This module organizes NEC requirements

More information

Discover how much Water You re Using and Use that Information to Optimize Your Facility

Discover how much Water You re Using and Use that Information to Optimize Your Facility AABC Commissioning Group AIA Provider Number 50111116 Discover how much Water You re Using and Use that Information to Optimize Your Facility Course Number: CXENERGY1704 Brent Baird Instruments Direct

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

Fire Protection Coffee Break Training May 2016

Fire Protection Coffee Break Training May 2016 Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers

More information

Compliance with Lighting Standards and Management Systems (ANSI C137)

Compliance with Lighting Standards and Management Systems (ANSI C137) Compliance with Lighting Standards and Management Systems (ANSI C137) Howard Wolfman, PE Lumispec Consulting O 847 656 5753 M 847 366 6700 h.wolfman@ieee.org 1 AABC Commissioning Group AIA Provider Number

More information

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15

Item Referenced and Amendments Building 1 Building 2 Analysis, Review and Remarks. Page 1 of 15 N/A N/A 2015 International Fire Code 2015 International Building Code Codes Jurisdictions for Fire and Building Codes Source of Information Building Fire Plumbing Mechanical Electrical Energy Code Accessibility

More information

Passive House Northwest AIA CEU Provider. Aubrey Gewehr March 27, 2015

Passive House Northwest AIA CEU Provider. Aubrey Gewehr March 27, 2015 Passive House Northwest AIA CEU Provider Multifamily Ventilation Strategies Workshop AIA Course # phnw082 Aubrey Gewehr March 27, 2015 Credit(s) earned on completion of this course will be reported to

More information

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates Prescriptions for Critical Healthcare Cx John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. Medical Industry Changes and how they impact Design, Construction,

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

What are the Concerns and How Can we Mitigate

What are the Concerns and How Can we Mitigate What are the Concerns and How Can we Mitigate Len Garis, Fire Chief City of Surrey, Adjunct Professor - School of Criminology and Criminal Justice & Associate to the Centre for Social Research University

More information

Convergence: The Integration of Lighting and Micro Sensor Technology

Convergence: The Integration of Lighting and Micro Sensor Technology Convergence: The Integration of Lighting and Micro Sensor Technology Presented by: Paul Mitchell Scott Jackson Sternberg Lighting The MH Companies pmitchell@sternberglighting.com scott@mhlighting.com www.sternberglighting.com

More information

Green Maintenance Needed to Keep HVAC Systems Green

Green Maintenance Needed to Keep HVAC Systems Green Green Maintenance Needed to Keep HVAC Systems Green Robert G. (Bob) Baker BBJ Consulting Service 235 Apollo Beach Blvd. #157 Apollo Beach, Florida bbaker@bbjconsultingservice.com ASHRAE is a Registered

More information

EMERGENCY POWER SYSTEMS

EMERGENCY POWER SYSTEMS 263213 EMERGENCY POWER SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. Section includes: 1. University guidelines for the installation of Emergency Power Systems (EPS). 2. Addresses the design and installation

More information

Step by Step Detailed Procedure Expected Result Observations Verify power off at all loads on emergency power. Verify all loads have power.

Step by Step Detailed Procedure Expected Result Observations Verify power off at all loads on emergency power. Verify all loads have power. 1. ATS Breaker Open ATS Breaker Verify power off at all loads on emergency power. Close ATS Breaker & put ATS Sw. to Auto Verify all loads have power. 2. Generator Cold Open normal power breaker & immediately

More information

Lindsay Frederick. Lighting + Electrical. Ron Dodson Faculty Advisor. Native American Cultural Center Arizona. Technical Report 2

Lindsay Frederick. Lighting + Electrical. Ron Dodson Faculty Advisor. Native American Cultural Center Arizona. Technical Report 2 Lindsay Frederick Lighting + Electrical Ron Dodson Faculty Advisor Native American Cultural Center Arizona Technical Report 2 Native American Cultural Center Technical Report 2 p. 2 Executive Summary The

More information

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum. September 29, 1997 Firecycle III 433 a 1. PRODUCT NAME VIKING Model E-1 Manufactured 1997 Present 2. MANUFACTURED FOR THE VIKING CORPORATION 210 N Industrial Park Road Hastings, Michigan 49058, U.S.A.

More information

16620 EMERGENCY POWER SYSTEMS

16620 EMERGENCY POWER SYSTEMS 16620 EMERGENCY POWER SYSTEMS PART 1: GENERAL 1.01 SUMMARY A. This Section provides the University guidelines for the installation of Emergency Power Systems. B. This standard is developed primarily to

More information

Applied Lighting Controls

Applied Lighting Controls Applied Lighting Controls Updated for 2011 Better Buildings By Design Burlington, Vermont February 9, 2011 Instructor: Steven Mesh, LC, IESNA 140 Gardenside Drive, #304 San Francisco, CA 94131 415-516-8126

More information

Welcome! AIA/CES Approved Seminar 1.0 LU/HSW. RAB8: Specifying a Networked Lighting Control System

Welcome! AIA/CES Approved Seminar 1.0 LU/HSW. RAB8: Specifying a Networked Lighting Control System Welcome! AIA/CES Approved Seminar 1.0 LU/HSW RAB8: Specifying a Networked Lighting Control System Jane Slade, MID, LC, LEED AP, IES Specification Sales Manager Updated July 2016 What has happened to our

More information

Electrical Inspection Service & Distribution

Electrical Inspection Service & Distribution 0911 Distribution Panels & Switchgear Equipment, conduit, feeders, and grounding 480 Volt Switchboard: This switchboard contains the utility meter and two main, service, circuit breakers. One circuit breaker

More information

UL's Effort to Harmonize Product Safety Requirements for A2L, A2, and A3 Refrigerants. San Antonio, Texas 2012 Annual Conference

UL's Effort to Harmonize Product Safety Requirements for A2L, A2, and A3 Refrigerants. San Antonio, Texas 2012 Annual Conference UL's Effort to Harmonize Product Safety Requirements for A2L, A2, and A3 Refrigerants San Antonio, Texas 2012 Annual Conference Learning Objectives for this Session First Learning Objective (The status

More information

Canadian Wood Council Fire and Safety Risks Posed by Wood Frame Residential Construction Professor / Fire Chief Len Garis July 15, 2015

Canadian Wood Council Fire and Safety Risks Posed by Wood Frame Residential Construction Professor / Fire Chief Len Garis July 15, 2015 Canadian Wood Council Fire and Safety Risks Posed by Wood Frame Residential Construction Professor / Fire Chief Len Garis July 15, 2015 Credit(s) earned on completion of this course will be reported to

More information

The Residences at Christina Landing Wilmington, DE

The Residences at Christina Landing Wilmington, DE 5.0 FIRE PROTECTION EXISTING CONDITIONS 5.1 Project Specific Fire Protection Data Codes, Regulations, and Standards Building Officials and Code administrators (BOCA) National Building Code [1996] with

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation. Aurel von Richthofen, Architect and Assistant Professor at The German University of Technology in Oman, (GUtech) is a Registered Provider with The American Institute of Architects Continuing Education

More information

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control File: S8485 Wiring Diagram This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control Panel. The operation of this product is intended for indoor

More information

3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials

3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials AMCA International Design Tips For Fire and Smoke Barriers William E. Koffel, P.E., FSFPE President, Koffel Associates, Inc. www.koffel.com Air System Engineering & Technology (ASET) Conference US San

More information

David Stymiest, PE, CHFM, CHSP, FASHE cell Copyright 2014, Smith Seckman Reid, Inc.; All rights reserved

David Stymiest, PE, CHFM, CHSP, FASHE cell Copyright 2014, Smith Seckman Reid, Inc.; All rights reserved AHCA 2014 Fall Conference Changes in Emergency Power Codes & Standards David Stymiest, PE, CHFM, CHSP, FASHE DStymiest@ssr-inc.com, cell 504.232.1113 Copyright 2014, Smith Seckman Reid, Inc.; All rights

More information

6 th Annual Green Building Conference

6 th Annual Green Building Conference 6 th Annual Green Building Conference Sponsored by & USGB New York Chapter OnCenter, Syracuse, NY Sustainability in our Community How can we measure or evaluate sustainability in our residential neighborhoods?

More information

Iowa (2) Delete section and insert in lieu thereof the following new section:

Iowa (2) Delete section and insert in lieu thereof the following new section: Iowa Iowa Admin. Code 661-301.3(103A) Iowa Administrative Code Agency 661 Public Safety Department Chapter 301 State Building Code-General Provisions 661-301.3(103A) General provisions. The provisions

More information

Accessories & General Information

Accessories & General Information Accessories & General Information Lamp Data...108-109 Unit Accessories...110 Mounting Plate Series...111 Wire Guards...1-113 Wire Size Guide...114 National Electrical Code...115-116 Life Safety Code...117-119

More information

INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES

INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES By: Mehrdad Ghods Integrated Engineering Student Sept. 06, 2002 University of British Columbia Vancouver, BC i PREFACE: The purpose of this

More information

Wire Guard CATALOG NUMBER WG5 CATALOG NUMBER WG1 CATALOG NUMBER WG2 CATALOG NUMBER WG6 CATALOG NUMBER WG3 CATALOG NUMBER WG7 CATALOG NUMBER WG4

Wire Guard CATALOG NUMBER WG5 CATALOG NUMBER WG1 CATALOG NUMBER WG2 CATALOG NUMBER WG6 CATALOG NUMBER WG3 CATALOG NUMBER WG7 CATALOG NUMBER WG4 Wire Guard CATALOG NUMBER WG1 Series DM & DS (Top Mounted Heads); SQ & SQ-D (Semi Recessed); ELF644 (Surface Mount); MG Series; QLX500-MR (exit only-wall Mount) 14 12 13-3/4 16 5 CATALOG NUMBER WG5 Series

More information

Diesel Fuel System Report

Diesel Fuel System Report Transbay Transit Center San Francisco, CA Prepared for: Pelli Clarke Pelli Architects 1056 Chapel Street New Haven, CT 06510 Prepared by: WSP 405 Howard Street, Suite 500 San Francisco, CA 94105 Mechanical

More information

Executive Summary. CNBC Global Headquarters Christine Cajilig

Executive Summary. CNBC Global Headquarters Christine Cajilig Executive Summary This report contains an analysis and description of the existing electrical distribution of the including the distribution type, emergency power, uninterruptible power system, over current

More information

Copyright 2018 American Wood Council 1

Copyright 2018 American Wood Council 1 Fire Tests in Support of Tall Mass Timber Buildings DES603 Sam Francis Senior Director, National Programs American Wood Council Jason Smart, P.E. Manager, Engineering Technology American Wood Council The

More information

Fee $15 Course: NEC Changes 5 This course is valid for these credentials: Credential Description Cred Code Credit Hours

Fee $15 Course: NEC Changes 5 This course is valid for these credentials: Credential Description Cred Code Credit Hours www.garyklinka.com Page 1 of 9 Instructions: Fee $15 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Modular Construction. Live/Work Urban Infill Townhome. Modular Construction. Enclosure Design. San Francisco Bay Area Net Zero Urban Infill

Modular Construction. Live/Work Urban Infill Townhome. Modular Construction. Enclosure Design. San Francisco Bay Area Net Zero Urban Infill Learning Objectives for this Session Kohta, June 25-29, 11, Montreal, QC Compare the present and predicted future affordability of net zero energy homes. Provide an estimate of required PV price for NZEH

More information

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement Second Revision No. 5501-NFPA 5000-2016 [ New Section after 29.2.1.2 ] 29.2.1.3 Bathtubs, bathtub-shower combinations, and nonemergency showers shall be provided with grab bars in accordance with the provisions

More information

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: Manitoba Regulation 221/2015 and Manitoba Regulation 222/2015 DATE: MARCH 17, 2016 1. INTRODUCTION On April 1, 2016, new building and

More information

2009 ELECTRICAL CODE REQUIREMENTS

2009 ELECTRICAL CODE REQUIREMENTS 2009 ELECTRICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Inspection Request Line (231) 533-3510 Electrical requirements

More information

Why Selective Coordination is Mandatory -- It Fills the Reliability Hole --

Why Selective Coordination is Mandatory -- It Fills the Reliability Hole -- Why Selective Coordination is Mandatory -- It Fills the Reliability Hole -- The NEC has mandatory selective coordination requirements for the following systems. Emergency Systems- Article 700 700.27 Legally

More information

12F052 ADVANCED FLORIDA (MULTIPLE OCCUPANCY BUILDINGS)

12F052 ADVANCED FLORIDA (MULTIPLE OCCUPANCY BUILDINGS) 11I058 ALLOWABLE HEEIGHTS AND AREAS IN THE INTERNATIONAL BUILDING CODE 12F052 ADVANCED FLORIDA BUILDING CODE (MULTIPLE OCCUPANCY BUILDINGS) www.codeaccess.net 2 AIA HSW LUH S AIA COURSE NUMBER 12F052 FLORIDA

More information

Efficiency Vermont The American Institute of Architects Continuing Education Systems (AIA/CES) AIA/CES AIA/CES

Efficiency Vermont The American Institute of Architects Continuing Education Systems (AIA/CES) AIA/CES AIA/CES Efficiency Vermont is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of this program will be reported to AIA/CES

More information

SAFEPATH Mass Notification System (SPMNS)

SAFEPATH Mass Notification System (SPMNS) Supersedes February 2016 SAFEPATH Mass Notification System (SPMNS) SP40S SPB-320 SPB-80/4 SPB-160 PS-8-LP SPMNS-MIC SP4Z-A/B Contents Page SPMNS.... 2-4 SPMNS-MIC...3 Expansion Options SAFEPATH 2-zone

More information

RELEASE DEVICE CONTROLS

RELEASE DEVICE CONTROLS RELEASE DEVICE CONTROLS RELEASE DEVICE MODEL C+ INSTALLATION MANUAL UL LISTED CANADIAN LISTED CSFM: 7300-48:00 GENERAL DESCRIPTION: MADE IN THE U.S.A. S/N: The LM0-C+ Release Device/Control Panel is a

More information

NORTH CAROLINA. Downloaded (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided:

NORTH CAROLINA. Downloaded (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided: Housekeeping/Laundry/Maintenance NORTH CAROLINA Downloaded 01.15.11 (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided: (3) a soiled utility room with counter,

More information

Trane Engineers Newsletter Live

Trane Engineers Newsletter Live Trane Engineers Newsletter Live Presenters: John Murphy, Dustin Meredith and Jeanne Harshaw (host) Trane program number: APP-CMC059-EN Agenda Trane Engineers Newsletter Live Series Abstract The Air Movement

More information

SEMINAR 48 (ADVANCED) International Codes and Standards Issues Impacting use of A2L Refrigerants in Unitary Heat Pump and Air-Conditioning Equipment

SEMINAR 48 (ADVANCED) International Codes and Standards Issues Impacting use of A2L Refrigerants in Unitary Heat Pump and Air-Conditioning Equipment SEMINAR 48 (ADVANCED) International Codes and Standards Issues Impacting use of A2L Refrigerants in Unitary Heat Pump and Air-Conditioning Equipment Standards Development for 2L Flammable Refrigerants

More information

1 Exam Prep Understanding and Servicing Alarm Systems Tabs and Highlights

1 Exam Prep Understanding and Servicing Alarm Systems Tabs and Highlights 1 Exam Prep Understanding and Servicing Alarm Systems Tabs and Highlights These 1 Exam Prep Tabs and Highlights are based on Understanding and Servicing Alarm Systems. Each 1 Exam Prep Tabs sheet has five

More information

TECHNICAL DATA OBSOLETE

TECHNICAL DATA OBSOLETE Deluge Devices 270a 1. PRODUCT NAME VIKING PAR-3 Available since 1991 2. MANUFACTURED FOR: THE VIKING CORPORATION 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone: (269) 945-9501 (877)

More information

High Performance or Hype Performance? Marc Rosenbaum, Some Real World Data. Marc Rosenbaum, P.E. South Mountain Company West Tisbury, MA

High Performance or Hype Performance? Marc Rosenbaum, Some Real World Data. Marc Rosenbaum, P.E. South Mountain Company West Tisbury, MA High Performance or Hype Performance? Some Real World Data Marc Rosenbaum, P.E. South Mountain Company West Tisbury, MA Welcome NESEA is a Registered Provider with e American Institute of Architects Continuing

More information

Revisions for the 2014 National Electrical Code Part 3

Revisions for the 2014 National Electrical Code Part 3 PDH Course E430 Revisions for the 2014 National Electrical Code Part 3 Patrick S. Ouillette, P.E. 2014 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org

More information

The Public Architect as City Builder

The Public Architect as City Builder The Public Architect as City Builder WE 203: The Public Architect as City Builder Wednesday, April 26, 2017, 8:30am 5:30pm Learning Units 7.50 LUs/HSW/RIBA This presentation is protected by U.S. and international

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

FireNET Plus Wiring Instructions

FireNET Plus Wiring Instructions FireNET Plus Wiring Instructions This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET Plus panels, which supports our finest Hochiki s DCP protocol. Note: Refer to

More information

Beyond the Great Debate: Assessing Post Installation Manufactured Soils Performance

Beyond the Great Debate: Assessing Post Installation Manufactured Soils Performance Beyond the Great Debate: Assessing Post Installation Manufactured Soils Performance Kelby Fite, PhD Bartlett Research Labs Eric Kramer, ASLA Reed Hilderbrand Bryant Scharenbroch, PhD Morton Arboretum Robert

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

Seminar 34 Refrigerants Today, Tomorrow, and Beyond

Seminar 34 Refrigerants Today, Tomorrow, and Beyond m Bianca W. Hydutsky, Ph.D. DuPont Chemicals & Fluoroproducts bianca.hydutsky@dupont.com Seminar 34 Refrigerants Today, Tomorrow, and Beyond Thermal Stability Studies to Evaluate Low-GWP Refrigerants 1

More information

Autonomous control unit

Autonomous control unit Supersedes October 2016 Autonomous control unit Description Eaton s Autonomous Control Unit (), part of the ALERiTY integrated MNS platform, is a supervised in-building emergency communications system

More information

FACILITY CONNECTION STANDARD

FACILITY CONNECTION STANDARD FACILITY CONNECTION STANDARD Preface: This Facility Connection Standard applies to any connection to the electric system of Westar Energy, Inc. or Kansas Gas and Electric Company, both doing business as

More information

Robotic Mowers (battery powered and charging station connected to electric mains or low voltage supply)

Robotic Mowers (battery powered and charging station connected to electric mains or low voltage supply) Compliance Guide Edition 05/2018 Robotic Mowers (battery powered and charging station connected to electric mains or low voltage supply) European Garden Machinery Federation EGMF Bd Reyers 80, 1030 Brussels,

More information

Developments in Australian Standard AS (Emergency Lighting)

Developments in Australian Standard AS (Emergency Lighting) Developments in Australian Standard AS2293.2 (Emergency Lighting) Russell Porteous Chief Executive Officer, Firewize Australian Standards Committee LG-007 Disclaimer Firewize policy is one of continuous

More information

FIRE STATION BUILDING COMMITTEE

FIRE STATION BUILDING COMMITTEE FIRE STATION BUILDING COMMITTEE May 2, 2018 East Milton Fire Station Recommendation Going Forward Synopsis Based on the lot size of the present East Milton Fire Station available for constructing a modern,

More information

Help Us Help YOU! A Guide to Requirements for. Commercial Electrical Permit Applications in the City of Winnipeg

Help Us Help YOU! A Guide to Requirements for. Commercial Electrical Permit Applications in the City of Winnipeg Help Us Help YOU! A Guide to Requirements for Commercial Electrical Permit Applications in the City of Winnipeg PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT August 2015 How can my electrical permit be

More information

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 STUDY AND TEST MATERIAL FOR THE FA2 and FA4 ASSESSMENTS (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 This document contains sample questions to help participants study for the FA2 and FA4

More information

Standard Duct Heaters Open Coil

Standard Duct Heaters Open Coil HUA Slip-In and HUP Flanged Heaters The 80% Rule HEATREX recommends the heater should occupy at least 80% of the actual inside area of the duct, as shown in Figure 45. Only small amounts of air will bypass

More information

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation PS6 SERIES Power Supplies PS6 SERIES Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option Installation and Specifications Manual ISDPS6_SERIES 08121590 PCN15016 R05/15GR

More information