BX-MDI8 Input module for SecuriLine extended
|
|
- Lionel Franklin
- 5 years ago
- Views:
Transcription
1 Input module for Securi extended Beginning with edition number The has 8 monitored inputs for connecting detection zones or for polling potential-free contacts. The module requires a redundant, external power supply for operation. It meets the Secui extended specification for operation on the addressable loop of the SecuriFire fire detection system. Fig. Description The can be connected to the Securi extended addressable loop of the SecuriFire fire detection system. Interfaces Addressing and parameter assignment for the is performed with PC software via the fire alarm control panel. The module includes a short-circuit isolator. In the event of wire breakage or a short-circuit, this functionality ensures that the fault is localised and at the same time maintains the full operability of the addressable loop. features External power supply galvanically separated from Securi extended Each of the 8 inputs is individually plannable Jumpers for setting the mode of operation Addressing and parameter assignment with PC software via Securi extended Up to 3 modules per loop can be connected Connectable detectors per input: * Detector series SecuriStar 5x/563 * MCP 5/55 * MMD30Ex-i via GTW * HX30 * HX30Ex-i via GTW The monitoring of the detector lines complies with EN 54-3 (interruption and short-circuiting of the transmission path). Integrated short circuit isolator Robust plastic housing Fig. interfaces Securi extended (X) Terminal Designation Description Data A A 3 B 4 Data B 5 SHD Screen support point 6 SHD Screen support point External power supply (X3) Terminal Designation Description VEXT_A A INCOMING EXT_A A INCOMING 3 VEXT_A A OUTGOING 4 EXT_A A OUTGOING 5 VEXT_B B INCOMING 6 EXT_B B INCOMING 7 VEXT_B B OUTGOING 8 EXT_B B OUTGOING Securiton AG Alpenstrasse Zollikofen Switzerland T 8 43 en / 7
2 Detector Number of detectors per alarm line Detectorbase Termination resistance 0,5 W 5% Connectors for detection zones and inputs (X) Detection zones and surveyed inputs can be connected to the X interface. Every input / line has its own current -limited output driver which supplies the connected peripheral devices with power. The operation mode and subtype selection is carried out individually for each detection zone and input. This is accomplished by means of software planning (SecuriFire Studio) and with jumper settings X to X8 on the module. If the jumper setting does not match the planning, a fault is reported on the SCP after startup Input no. Designation Function Jumper no. COM X8 X7 X6 X5 X4 X3 X X The following applies to all jumpers from X to X8: Detection zone mode of operation Detection zones SecuriStar 5 / 53 / 563 Conventional MCP MMD30 Ex-i HX 30 HX 30 Ex-i (NOT VdS compliant!) Surveyed input mode of operation Surveyed input 6K7 VDS mode of operation Surveyed input 3K VdS extinguishing input Valve monitoring How the modes of operation work All modes of operation supported by the function in accordance with the current increase principle. A defined resistance at the end of each stub line serves as line monitor. In the event of actuation, a defined alarm resistance must be switched parallel to the terminal resistor. The terminal resistor is monitored for creeping wire breakage and short-circuit when quiescent. The following information about the number of detectors per zone is based on the technical system limits and may be restricted by directives and regulations. Detection zone mode of operation SCD 563 TCD 563 MCP 5 MCP 55 max. 3 USB 50-x max. 0 MMD30 Ex-i max. 0 USB 50-7 Ex-i (via safety barrier GTW) 3 k 4,7 k ORM30 Ex-i 43 Ex-i WDM 5 Ex-i max. 0 (via safety barrier 4,7 k WMM 6 Ex-i SSD 5 UTD 5 max. 3 GTW) USB 50-x 3 k ORM 30 A/Y ORM 30 A/K WDM 5 A max , 43 K 3 k WMM 6 A UFM 840 max. 4 43, 43 K 3 k DFM 435 Wx max. 0 3 k Surveyed input mode of operation Termination resistance Alarm resistance Surveyed input 6K7 6,7 k ±5 %; 0,5 W 8, k ±5 %;0,5 W VDS mode of operation Termination resistance Alarm resistance VdS- extinguishing input 3,3 k ±5 %; 0,5 W 680 ±5 %; W Surveyed input 3 k ±5 %; 0,5 W,5 k ±5 %; 0,5 W 3K Valve monitoring 3 k ±5 %; 0,5 W,5 k ±5 %; 0,5 W (,5 k pre-alarm) Input DFG-60 BK3 3 k ±5 %; 0,5 W,5 k ±5 %; 0,5 W / 7 T 8 43 en
3 Power requirement When both detectors and modules are operated on an addressable loop, note that the has a higher power consumption than a detector. For security reasons a maximum of 3 s are permitted per addressable loop. Connection examples Connection principle External power supply A tool is available for calculating the maximum possible loop length and the maximum number of participants. Planning and projection Planning is to be carried out in accordance with the applicable standards and directives. According to EN54 a max. of 3 detectors are permitted per. Automatic and non-automatic detection zones cannot be combined on a stub line due to regulations. The can be operated in the Securi as well as in the Securi extended mode. PSU (+4V) Securi / Securi extended ) Possible only if all modules and detectors are located in the same fire sector Fig. 3 Connection principle Connection the Securi extended and the external power supply ) The desired function can be assigned to each input with SecuriFire Studio. Also, the mode of operation of each input on the module must be set with the appropriate jumper. An external power supply compliant with EN 54-4 is required to operate the. External power supply + + If the and power supply are mounted at separate locations, the power supply line must be redundantly implemented with separate fusing. The external power supply must be dimensioned to the maximum power consumption of the connected peripheral devices, dimensioned to the bridging time and the maximum lengths of the power supply line. Supplying power to multiple modules from the same power supply is permitted only if all detectors and inputs are located in the same fire sector. Due to the high power consumption, a length calculation must be performed for the power supply lines. EXT_B VEXT_B EXT_B VEXT_B EXT_A VEXT_A EXT_A VEXT_A SHD SHD OOP OOP X 3 X additional additional Fig. 4 Connection the Securi extended and the external power supply T 8 43 en 3 / 7
4 R4 R3 R (RE) R5 R4 R3 R (RE) R5 Connecting the detector series 5 / 53 / 563 and MCP 5 / 55 USB End detector USB X COM X8 X7 X6 X5 X4 X3 X X Fig. 5 Connecting detector base USB 50 MCP 5N k5 3K last manual call point In the last manual call point a 3K resistor must be used MCP 5N k5 X COM X8 X7 X6 X5 X4 X3 X X Fig. 6 Connecting MCP 5N manual call points Do not remove R (RE)! R MCP last manual call point Remove R (RE)! R MCP X COM X8 X7 X6 X5 X4 X3 X X Fig. 7 Connecting MCP 55 manual call points 4 / 7 T 8 43 en
5 4k7 + + Connecting the detector series MMD30 Ex-i with direct current isolating transformer GTW 0 This connection does NOT fulfil the requirements of VdS Directive 489. Ex area Max. 0 USB 50-7 Ex-i detector bases USB 50-7 Ex-i USB 50-7 Ex-i ast detector GTW 0 X COM X8 X7 X6 X5 X4 X3 X X Fig. 8 Connecting detector base USB50-7 Ex-i with direct current isolating transformer GTW 0 Connecting the detector base 43 Ex-i with direct current isolating transformer GTW 0 This connection does NOT fulfil the requirements of VdS Directive 489. Ex area Detector base 43 Ex-i End detector max. 0x 43 Ex-i detector bases Detector base 43 Ex-i GTW X COM X8 X7 X6 X5 X4 X3 X X Fig. 9 Connecting the detector base 43 Ex-i with direct current isolating transformer GTW 0 T 8 43 en 5 / 7
6 3 680 R Connecting surveyed inputs 6k7 8k k5 X COM X8 X7 X6 X5 X4 X3 X X Fig. 0 Connecting surveyed input 6K7 / surveyed input 3K Connecting extinguishing systems X k5 k5 a b a or b = pre-active a and b = active Extinguishing control panel COM X8 X7 X6 X5 X4 X3 X X Fig. Valve monitoring / Extinguishing input in accordance with VdS 6 / 7 T 8 43 en
7 Article numbers / spare parts Short designation Art. number CH Art. number Input module MOD 3 IP66 Map case for Technical data Securi extended (X) Function Input module Operating voltage to 30 V-DC Power consumption (module's power consumption only) 6 ma Signal transmission Serial data transmission, -line technology Connection Screw terminals max..5 mm Monitored inputs (X) 8 Output voltage 30 V-DC Short circuit current 5 ma resistance max. 50 Ω length max. 000 m Connection Screw terminals max..5 mm External power supply (X3) 8 Operating voltage to 30 V-DC Power consumption dependent on the input voltage and the number of used inputs, max. Operating current 70 ma 45 ma 40 ma Per activated line (fault WB) ma,5 ma ma Per activated line (normal operation) 0 ma 4 ma 0 ma Per activated line (pre-alarm) 40 ma 5 ma 0 ma Per activated line (alarm) 80 ma 50 ma 40 ma resistance max. 4 Ω mm max. 80 m Connection Screw terminals max..5 mm General Protection type 66 with map case IP Ambient temperature -0 to C Humidity ambient conditions 5 to 95 %, without condensation rel.h VdS approval applied for Declaration of performance CPR DE-EN Dimensions (H x W x D) 80 x 5 x 0 mm Dimensions with map case (H x W x D) 94 x 80 x 57 mm Weight approx. 5 g T 8 43 en,.0.04 Rd 7 / 7 First edition:.0.04 Rd The product specifications contained in this document are subject to change without notice. Copyright by Securiton
SecuriFire SecuriLine extended board B5-DXI2
SecuriFire SecuriLine extended board B5-DXI Technical description Securiton AG Alpenstrasse 0 305 Zollikofen Switzerland T 8 3 en c Imprint Imprint This document, T 8 3, is valid only for the product
More informationSecuriFire. SecuriLine Unit B6-LXI2. Technical Description. Securiton AG Alpenstrasse Zollikofen Switzerland
SecuriFire SecuriLine Unit B6-LXI2 Technical Description Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 8 067 en Imprint Imprint This document, T 8 067, is valid only for the product described
More informationSonos-SB Siren/Beacon
Sonos-SB Siren/Beacon Audible/optical signal transmitter compliant with EN 54-3 and EN 54-23 for fire alarm systems, in red and white. Wall mounting (category W) and ceiling mounting (category C) for indoor
More informationOn the job around the clock 24/7: Fire detection systems
On the job around the clock 24/7: Fire detection systems Version 02.2010 Version: 02.2010 Product catalogue Fire detection systems This product catalogue is intended for sales purposes only. For planning,
More informationSecuriFire 500. Mounting and Installation. Technical Description. Securiton AG Alpenstrasse Zollikofen Switzerland
SecuriFire 500 Mounting and Installation Technical Description Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 8 065 en Imprint Imprint Notice This document, T 8 065, is valid only for the
More informationADW 535 Line type heat detector
ADW 535 Line type heat detector Beginning with production version 140214 and FW version 01.00.19 The ADW 535 is an integrating line type heat detector that consists of the cable terminal processor and
More informationASD 535 Aspirating smoke detector
ASD 535 Aspirating smoke detector From production number 3072 and FW version 0.06.00 The ASD 535 aspirating smoke detector performs the task of taking continuous air samples via one or two sampling pipe
More information1. MAIN CONTROL UNIT MCU Accessories for MCU OPERATING AND DISPLAY PANELS... 10
Contents 1. MAIN CONTROL UNIT... 6 1.1 MCU... 6 1.2 Accessories for MCU211... 7 2. OPERATING AND DISPLAY PANELS... 10 2.1 SecuriLan... 10 2.2 SecuriLine... 15 2.3 SecuriPro cases for panels... 17 3. INPUT
More informationZIOU/230 - MAINS IO INSTRUCTION MANUAL
Description ZIOU/230 - MAINS IO INSTRUCTION MANUAL The Mains IO Modules are fully monitored loop powered devices which permit the interfacing of third party equipment with the Fire Alarm Control panel
More informationInterface and EOL Modules 8
Interface and EOL Modules Interface Modules Series 420 25 Interface Modules Series 100 291 EOL Modules 293 254 Interface and EOL Modules Interface Modules Series 420 Interface Modules Serie 420 Interface
More informationDC1192 Input /Output module
DC1192 Input /Output module Interactive, AnalogPLUS/SynoLOOP, collective/synoline600 AlgoRex Synova In-/output module suitable for collective fire detection system as detection line coupler interactive
More informationFC330A-ECO Auto-addressing analogue 1-Loop fire detection panel
FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel Synova TM Commissioning in no time thanks to automatic address allocation Auto-addressing makes setting dip switches unnecessary Automatic
More informationEngineering Guideline. pac-carriers Type SIEMENS ET-200M Fail-safe signal modules
Engineering Guideline pac-carriers Type 9195 SIEMENS ET-200M Fail-safe signal modules pac-carrier Type 9195 2 Engineering Guideline/SIEMENS 19.05.2015 pac-carrier Type 9195 Integration of conventional
More informationSecuriFire 500/1000/2000/3000
SecuriFire 500/1000/2000/3000 Product Catalogue 2016 Content 1. Cabinets variants... 11 1.1. SecuriFire 500 fire alarm control panel... 11 1.2. SecuriFire 1000 fire alarm control panel... 12 1.3. SecuriFire
More informationFire Detection Systems Product Catalogue (Version )
Fire Detection Systems Product Catalogue (Version 2015-01) Version 2015-01 Product Catalogue Fire Detection Systems This product catalogue is intended for sales purposes only. For planning, installation,
More informationFire control panels FC360
Cerberus TM FIT Fire control panels FC360 FC361-ZZ, FC361-ZA, FC361-YZ, FC361-YA Fire control panels (1-loop) for addressable peripheral devices with integrated operating unit One loop with 126 addresses
More informationMulti line separator module
Sinteso Cerberus PRO Multi line separator module FDCL221-M Multi line separator module, addressed (FDnet/C-NET) Automatic module with several separate line separators Formation of stub lines (T-branches)
More informationGeneral Routing Interface
General Routing Interface Features The General Routing Interface Card is an optional module to provide Fire and Fault Routing Outputs compliant with BSEN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1: 2002.
More informationFDCL221-M Multi line separator module
FDCL221-M Multi line separator module addressable (FDnet/C-NET) Sinteso TM Cerberus PRO Automatic module with several line separators Creation of T taps (stub lines) in the FDnet/C-NET Operation of the
More informationSecuriSens LIST Product Catalogue 2015
SecuriSens LIST Product Catalogue 2015 Content 1. Processor Units... 5 2. Cable... 7 3. Accessories List... 8 4. Spare Parts... 13 5. Services... 15 6. Product Type Index... 16 2 Securiton Product Catalogue
More informationCombi B Alarm box. Mounting instructions
Combi B Alarm box Mounting instructions EN Mounting instructions Alarm box Combi B VdS, G113064, G113065, G113066 Table of Contents 1 Description... 3 2 System overview... 3 3 Structure... 3 3.1 Power
More informationSecuriFire fire detection systems. System description
SecuriFire fire detection systems System description The SecuriFire system family Table of contents 1 The SecuriFire system family 3 1.1 Fire alarm control panel 3 1.2 Extinguishing control panel 4 2
More informationSystem 800 Addressable Fire Detection & Alarm System
SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools
More informationDC1136, DC1131-AA, DC1134-AA, DC1136-AA Input / Output modules
DC1136, DC1131-AA, DC1134-AA, DC1136-AA Input / Output modules AnalogPLUS AlgoRex DC1130 Series Thanks to its robust construction, the input/output modules can be used in both dry and dusty / wet areas
More informationFire control panel detect 3004 plus and accessories
Fire control panel detect 3004 and accessories The modular fire alarm panel detect 3004 is the basic version of a broad product portfolio of the system detect 3000. Up to 20 fire control panels can be
More informationFC724 Fire control panel
FC724 Fire control panel Series FS720 (IP4) Cerberus PRO Compact, prefabricated microprocessor-controlled fire control panel for the connection of up to 504 addresses Fire control panel can be used as
More informationBuilding Technologies SIGMASYS M Multifunctional danger alarm control and indicating panel
R33/422 Building Technologies SIGMASYS M Multifunctional danger alarm control and indicating panel SIGMASYS M multifunctional danger alarm control and indicating panel Application Description Features
More informationEngineering Guideline. pac- Carriers Type Universal
Engineering Guideline pac- Carriers Type 9195 Universal Integration of conventional process automation interfaces pac- Carrier The pac- Carrier reflects the intention of R. STAHL to provide state-of-the-art
More informationFC722 Fire control panel
FC722 Fire control panel Series FS720 (IP4) Cerberus PRO Compact, prefabricated microprocessor-controlled fire control panel for the connection of up to 252 addresses Fire control panel can be used as
More informationFire control panels FC726 FC726-XA
Fire control panels FC726 FC726-XA Modular, pre-confectioned, microprocessor-controlled fire control panel for up to max. 1512 device addresses Integrated, user-friendly operating unit Detection and automatic
More informationFC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel
FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel Synova Commissioning in no time thanks to automatic address allocation Auto-addressing makes setting dip switches, punch cards, etc. unnecessary
More informationFC722 Fire control panel
FC722 Fire control panel Series FS720 (MPXS) Cerberus PRO Compact, prefabricated microprocessor-controlled fire control panel for the connection of up to 252 addresses Fire control panel can be used as
More information561-MB256 plus. Intruder alarm control panel. Performance features
561-MB256 plus Intruder alarm control panel The intruder alarm control panel 561-MB256 plus is designed for use in private and commercial zones and is highly suitable for setting up medium to large-sized
More informationIRIS Touch Quick Installation & Maintenance Guide. Version 1.0
IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction... 3 2. Product Features... 3 3. Package Contents... 4 4. Board Configuration... 4 5. Before You Start... 5 6. Installing
More informationED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR
ED820 24V MODEL fire DETECTOR INSTRUCTION MANUAL Address: Enigma House, Enigma Business Park, Malvern, Worcestershire, WR14 1GD Tel: 44 (0)1684 891500 Fax: 44 (0)1684 891600 Email: sales@electronicdevices.co.uk
More informationFDCL221-Ex Line adapter (Ex)
FDCL221-Ex Line adapter (Ex) Addressed (FDnet-Ex/C-NET-Ex) For operating FDnet-Ex/C-NET-Ex peripheral devices in potentially explosive areas Sinteso Cerberus PRO Electrical isolation of Ex and non-ex lines
More informationFC724 Fire control panel
FC724 Fire control panel Series FS720 (IP5) Cerberus PRO Compact, prefabricated microprocessor-controlled fire control panel for the connection of up to 504 addresses Fire control panel can be used as
More informationFC2020 Fire control panel
FC2020 Fire control panel Series FS20 (MP4.0) Sinteso Compact, prefabricated, microprocessor-controlled fire control panel for the connection of up to 252 addresses Fire control panel can be used as stand-alone
More informationSecuriFire 500/1000/2000/3000
SecuriFire 500/1000/2000/3000 Product Catalogue 2013 Content 1. Cabinets variants... 11 1.1. SecuriFire 500 fire alarm control panel... 11 1.2. SecuriFire 1000 fire alarm control panel... 12 1.3. SecuriFire
More informationInterface Modules for SENTRI
EQUIPMENT INTERFACED Data and Installation Interface s for SENTRI Low voltage (LV) / SEN-INT-INPUT 1- Interface (low voltage) SEN-INT-OUTPUT 1- & 1- Interface (low voltage) SEN-INT-4IO # 4- / Interface
More informationReliably Advanced Extinguishing Control
Reliably Advanced Extinguishing Control The Best Choice for Asset Protection What suppression and extinguishant control panel would you choose to protect the literary collection of an entire nation? 47
More informationInput module, input/output modules
Sinteso / Cerberus PRO Input module, input/output modules FDCI222, FDCIO222, FDCIO224 Input module and input/output modules for the automatically addressed detector line Input module FDCI222: Four monitored
More informationXC10 Extinguishing control panels
XC10 Extinguishing control panels Market package 2.1 Advanced control panels for detection and alarming as well as for the activation of the extinguishing process Microprocessor-controlled fire detection
More informationIRIS Touch Quick Installation & Maintenance Guide. Version 1.0
IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Page 2 of 16 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction...4 2. Product Features...4 3. Package
More informationDC1154 / DC1154-AA / DC1156-AA / DC1157-AA Input / Output modules
DC1154 / DC1154-AA / DC1156-AA / DC1157-AA Input / Output modules Interactive AlgoRex DC1150 Series Thanks to its robust construction, the line modules can be used in both dry and dusty / wet areas Housing
More informationOptical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator
TECHNICAL GUIDE Optical Smoke Detector Heat Detector Manual Call Point Output Unit Isolator The XPlorer Range XPlorer is a new range of analogue addressable detectors and interfaces developed for all who
More informationPlanning Instructions MEW01776 Revision -
Planning Instructions MEW01776 Revision - Fire Alarm System EBL512 G3 V2.2.x Author: Jan Pettersson Date of issue: 2015-01-19 Date of rev: This page has deliberately been left blank. Table of contents
More informationFC723 Fire control panel
FC723 Fire control panel FS720 series (IP5) Cerberus PRO Modular, prefabricated, microprocessor-controlled fire control panel with integrated user-friendly operating unit for up to max. 756 addresses Processes
More informationFC700A Fire detection control unit
FC700A Fire detection control unit Synova 4-16 Loop analogue addressable control panel 128 devices per loop (SynoLOOP) and up to 1000 devices per panel Up to 24 collective lines for Synova TM 600 serie
More information600 Range Dialer Installation Manual. Version 1.0
600 Range Dialer Installation Manual Version 1.0 The information contained is supplied without liability for any errors or omissions. No part may be reproduced or used except as authorised by contract
More informationPROCESS AUTOMATION PROTECTING YOUR PROCESS THE DEFINITION FOR INTRINSIC SAFETY K-SYSTEM K-SYSTEM THE MOST TRUSTED NAME.
PROCESS AUTOMATION K-SYSTEM THE MOST TRUSTED NAME PROCESS AUTOMATION PROTECTING YOUR PROCESS THE SYSTEM ELECTRONICS Availability: Power feed modules for a simplex or redundant supply on Power Rail Transmission
More informationInput module, input/output module
Sinteso / Cerberus PRO Input module, input/output module FDCI221, FDCIO221 Input module and input/output module for the automatically addressed detector line Input module FDCI221: Monitorable contact input
More informationSolution F2. Fire Alarm Control Panels one step ahead.
Solution F2 Fire Alarm Control Panels one step ahead. Sicherheitstechnik Sicherheitstechnik GmbH GmbH The Fire Alarm Control Panel Solution F2 Solution F2 in B2 enclosure (B01090-00) The Concept The Solution
More informationOOH740, OOHC740 Automatic fire detectors
OOH740, OOHC740 Automatic fire detectors ASAtechnology TM For the automatic addressable detector bus C-NET Collective / Conventional (OOH740 only) Cerberus PRO Signal processing with ASAtechnology TM Event-controlled
More informationFLAME AMPLIFIER MODULE 3001
SYSTEM 3000 / 4000 FLAME AMPLIFIER MODULE 3001 TECHNICAL DESCRIPTION EDITION TB_3001_EN_REV03 BFI Automation Mindermann GmbH, Eggerscheidter Str. 57, D-40883 Ratingen Phone +49 (0) 2102 96 82 0, Fax +49
More informationHigh-precision aspirating smoke detectors for every requirement.
High-precision aspirating smoke detectors for every requirement. SecuriRAS ASD 535, ASD 532 and ASD 531 aspirating smoke detectors Securiton AG Alarm and Security Systems Alpenstrasse 20, 3052 Zollikofen,
More informationMimic display driver, LED ribbon cable
Sinteso / Cerberus PRO Mimic display driver, LED ribbon cable FT2001-A1, F50F410 FDnet/C-NET mimic display driver and LED ribbon cable for the fire detection systems Sinteso FS20 and Cerberus PRO FS720.
More informationDevice Technology. Supply Operating voltage Implemented via the bus KNX: V DC XIB: 12 V DC (rated voltage) Voltage range: 10.
2 Device technology XS/S 1.1 2CDC 071 115 F0008 The Interface XS/S 1.1 integrates the Intrusion Alarm Panel L240 into the KNX intelligent installation system. It is connected to the XIB bus of the Intrusion
More informationSita200plus. 200detectors. Single loop analogue addressable System
Single loop analogue addressable System Fast short circuit isolator in every device 15 combinations of smoke & heat detection modes Loop length up to 2km long with spurs INTELLIGENT FIRE TECHNOLOGY A D
More informationIRIS Touch Quick Installation & Maintenance Guide. Version 1.0
IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Page 2 of 16 IRIS Touch Quick Installation & Maintenance Guide Version 1.0 Contents 1. Introduction... 4 2. Product Features... 4 3. Package
More informationFDA241, FDA221 Siemens ASD
FDA241, FDA221 Siemens ASD Patented Technology Compatible with the Siemens FDnet/C-NET loops (requires FDCC221S option) Advanced dual Wavelength optical detection (Blue & Infra-red) Configurable as a Standalone
More informationControl and Indicating Equipment
VdS Guidelines for Fire Detection and Fire Alarm Systems VdS 2540en Requirements and Test Methods VdS 2450en : 2018-12 (03) Publisher and publishing house: VdS Schadenverhütung GmbH Amsterdamer Str. 172-174
More informationCentaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE
Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE General Description This guide provides a summary for installing and configuring the Centaur TM Cube Slave Alarm Signalling Equipment
More informationCall stations and extensions
Novigo Call stations and extensions PT2001-A1, PT2002-A1, PT2008-A1, PT2009-A1, PTO2001-A1, PTO2002-A1, PTO2003-A1, PTO2004-A1, PTO2005-A1, PTO2006-A1, PTO2008-A1 EN 54-16-certified alarm and business
More information1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER
Application The unit is primarily intended for use where there is a requirement to integrate a limited fire protection function into a larger control equipment scheme, or in specialist applications where
More informationFire control panel for modernization
Sinteso Fire control panel for modernization FC2030 Modular, pre-assembled fire control panel with integrated, user-friendly operating unit for gradual migration to Sinteso. Fire control panel for a maximum
More informationSM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option
SM3000 Videographic Recorder User Guide (RTU) Communications Option ABB The Company We are an established world force in the design and manufacture of instrumentation for industrial process control, flow
More informationSUPREMATouch. Modular Fire & Gas Detection System
SUPREMATouch Modular Fire & Gas Detection System Tel: +44 (0)8 9388 Email: info@ Fire & Gas Detection Solutions MSA permanent gas detection systems are used throughout the world to protect plant and personnel
More informationApplication, Installation, Operation & Maintenance Manual
APPROVED BY:JBJ PRESCIENT III FIRE ALARM & GAS EXTINGUISHING CONTROL PANEL Application, Installation, Operation & Maintenance Manual PAGE 1 of 43 CONTENTS 1. INTRODUCTION... 3 2. GENERAL DESCRIPTION...
More informationFC2040. Fire control panel. Sinteso. FS20 series, MP6
FC2040 Sinteso Fire control panel FS20 series, MP6 Compact, pre-assembled, microprocessor-controlled fire control panel with integrated operating unit for up to 504 addresses Fire control panel can be
More informationEsmi Sense FDP Fire detection panel with ALC2 loop controller
Esmi Sense FDP Fire detection panel The intelligent and modular Esmi Sense FDP fire detection panel provides multiple new features for efficient and reliable fire safety. The Esmi Sense FDP fire detection
More informationASD 533 Aspirating Smoke Detector
ASD 533 Aspirating Smoke Detector Technical description as of firmware version 01.07.00 Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 140 287 b en Imprint Imprint This document, T 140 287,
More informationBuilding Technologies. FDUL221 en Line tester operating instructions for electricians
FDUL221 en Line tester operating instructions for electricians 1. Intended use The FDUL221 line tester is used to diagnose an addressed detector line in FDnet/C-NET. During diagnosis, the detector line
More informationOperation Manual Part-No
Version 2.2, 08/2016 VISATRON Remote Indicator II For Oil Mist Detectors Operation Manual Part-No. 180050 VNxxx/87plus VNxxx/93 VNxxx/87-EMC VN115/87plus EX VN301plus (EX) Part-No. 150998 Page 2 of 20
More informationSUPREMATouch. Modular Fire & Gas Detection System
SUPREMATouch Modular Fire & Gas Detection System Fire & Gas Detection Solutions MSA permanent gas detection systems are used throughout the world to protect plant and personnel from hazardous gases in
More informationASD 535 Aspirating Smoke Detector
ASD 535 Aspirating Smoke Detector Application guidelines for refrigerated warehouses Beginning with SW version 01.02.01 Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 131 390 en Imprint Imprint
More informationINDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...
GUIDE MANUAL INDEX 1- Introduction...5...5...6 4- The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops...7 4.2- The Control Panel 4 and 8 Loops...9 5- Installation Guide...10 5.1- Pre-Installation
More informationASD 535 Aspirating Smoke Detector
ASD 535 Aspirating Smoke Detector Technical Description Beginning with FW version 01.06.00 Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 131 192 e en Imprint Imprint This document, T 131
More informationFire alarm system EBL512 G3
Fire alarm system EBL512 G3 An analog addressable fire alarm system for early detection - without any unwanted alarms. Third generation. www.panasonic-fire-security.com 2010-04-23 Page 1 of 6 The demands
More informationFDCL221 Line separator
FDCL221 Line separator Technical manual Fire Safety & Security Products Technical specifications and availability subject to change without notice. 2004-2009 Copyright Siemens, Inc. We reserve all rights
More informationFDA241, FDA221 Siemens ASD
FDA241, FDA221 Siemens ASD Patented Technology Sinteso TM Cerberus PRO Compatible with the Siemens FDnet/C-NET loops (requires FDCC221S option) Advanced dual Wavelength optical detection (Blue & Infra-red)
More informationQuick Selection Guide Fire Systems LSN Periphery
Local SecurityNetwork Easy wiring Auto configuration capability (self-learning mode) Central programming of all device configurations from the panel Flexible network structure (Loop, stub, T-tap & mixed
More informationOilSET-1000 (12 VDC)
Labkotec Oy Myllyhaantie 6 FI-33960 PIRKKALA FINLAND Tel: +358 29 006 260 Fax: +358 29 006 1260 Internet: www.labkotec.fi 20.03.2009 1/11 OilSET-1000 (12 VDC) Oil Separator Alarm Device Copyright 2009
More informationFIRE DETECTOR TYPE ED816 ZONE 5 ZONE 4 ZONE 6 ZONE 7 FIRE FIRE FIRE FIRE FAULT FAULT FAULT FAULT DISABLED DISABLED DISABLED DISABLED OFF OFF OFF OFF
DETECTOR TYPE ED816 ZE 1 ZE 2 ZE 3 ZE 4 ZE 5 ZE 6 ZE 7 S ZE 8 CIRCUIT 1 ZE 9 ZE 10 ZE 11 ZE 12 ZE 13 ZE 14 ZE 15 ZE 16 CIRCUIT 1 POWER POWER SUPPLY GENERAL MENT DC GENERAL SYSTEM ALARM DELAYED ALARM RESOUND
More informationSOUNDER CONTROL MODULE SCM-AS4
1 of 9 INTRODUCTION DESCRIPTION The forms part of the Nittan (UK)'s SENSORTEC-ANALOGUE range of Analogue Addressable Devices. This module is designed to control a group of bells or sounders from the detection
More informationSiemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation
Sinteso Cerberus PRO FDA241, FDA221 ASD Aspirating smoke detector Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation Patented technology Early
More informationPlanning Instructions MEW01090 Revision 4
Planning Instructions MEW01090 Revision 4 Fire Alarm System EBL128 V1.1.x Author: Jan Pettersson Date of issue: 2008-07-11 Date of rev: 2011-04-08 This page has deliberately been left blank. Table of contents
More information5.1 Safety instructions for system configuration and explosion protection. Zone-specific conditions for system configuration
Planning and configuration of the I.S. 1 system 5 ENGINEERING 5.1 Safety instructions for system configuration and explosion protection During engineering, comply with the guidelines set out in EN 60 079-14.
More informationReliably Advanced Extinguishing Control
Reliably Advanced Extinguishing Control 14 years. 60 countries. Still Advanced. We re the same people, with the same commitment to excellence and customer satisfaction and now we have a brand that reflects
More informationFire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology
Fire-Cryer Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX Shaping Alarm Technology Fire-Cryer Plus The Fire-Cryer range of voice sounders was first introduced to the market by Vimpex in 1999.
More informationSynova TM product catalog.
Synova product catalog Synova TM product catalog. Fire protection products and accessories. Siemens Switzerland Ltd Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel
More informationFDCW241 Radio gateway Mounting
FDCW241 Radio gateway Mounting 2017-01-05 Control Products and Systems Legal notice Legal notice Technical specifications and availability subject to change without notice. Transmittal, reproduction, dissemination
More informationEngineering Guideline. pac-carriers Type for Yokogawa ProSafe-RS
Engineering Guideline pac-carriers Type 9195 for Yokogawa ProSafe-RS 2 Engineering Guideline / Yokogawa ProSafe-RS 06.06.2017 Integrated solutions for Yokogawa R. STAHL offers a wide range of customized
More informationMBZ300. Emergency power control unit. GB Installation instructions MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 MBZ300 PME PME. Reset.
24V 24V PME PME CM DM SM DM WM Reset Reset Emergency power control unit GB Installation instructions 1 Table of contents 1 Symbols and illustrations...3 2 Product liability...3 3 Safety instructions...3
More informationFire Alarm Panels. Product Manual.
Fire Alarm Panels Product Manual The operation and functions described in this manual are available from Software Version 5000-050-04 onwards. Specifications: Item Specification Details Part Number: Mx-5100
More information2000 Series Sensors Installation Guide
2000 Series Sensors Installation Guide Revision 5.1: August 2000 (unreleased) Aritech is a trademark of SLC Technologies B.V. COPYRIGHT SLC Technologies B.V. 2000. All rights reserved. SLC Technologies
More informationAlgo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)
Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0)
More informationSinteso TM product catalog.
Sinteso product catalog Sinteso TM product catalog. Fire protection products and accessories. Siemens Switzerland Ltd Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug
More informationOOH740-A9-Ex Multi-sensor fire detector
OOH740-A9-Ex Multi-sensor fire detector ASAtechnology TM For potentially explosive areas Cerberus PRO Collective Signal processing with ASAtechnology Multiple protocol detector (collective/c-net-ex) Event-controlled
More informationAddressable and Conventional Fire Protection
Addressable and Conventional Fire Protection Simply reliable F I R E P R O T E C T I O N The MAGPro and Fireline systems has been created to balance performance, reliability and aesthetics whilst being
More information