EXISTING CONDITIONS SUMMARY
|
|
- Aldous Cameron Davis
- 5 years ago
- Views:
Transcription
1 SITE Fire alarm system does meet current requirements Accessible path of travel lacking throughout campus Announcer s booth at Football Field booth not ADA compliant Covered and non covered outdoor eating areas needed Existing parking area and driveway paving in need of maintenance Storm drainage issues across campus Mature trees and landscaping in need of revitalization Exterior Eating Area Clear sense of entry and school identity Variety of Quads provide potential for gathering, outdoor learning, and performance activities Quad Behind Administration SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 2
2 CLASSROOMS, ADMINISTRATION & MPR Serious water/moisture intrusion at basement level Basement level not habitable Extensive Accessibility updates required throughout Interior ramps not ADA compliant Repair and restoration needed on historic exterior Administration Rear Exit Enhance front entry and provide ADA compliant entrance Acoustical and natural lighting enhancements Large corridors provide opportunity for display, small group instruction Entry Lobby SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 3
3 NORTH GYMNASIUM Interior accessibility while maintaining existing spatial quality Repair and restoration needed on historic exterior North Gymnasium Entry Make second fl oor accessible Large community meeting or group instructional space Ample natural light North Gymnasium Interior SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 4
4 AUDITORIUM Theater needs comprehensive modernization Extensive accessibility updates required throughout Repair and restoration of historic exterior Auditorium Interior Provide accessible entry at front of auditorium Provide more direct access from exterior to backstage area Improve lobby/reception area Auditorium Entry SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 5
5 SCIENCE BUILDING & FOOD SERVICE Aged facilities in need of modernization Evidence of water intrusion in some locations Lacking ADA compliant room signage Exterior of food service barren and lacks character Food Service Exterior Classroom and teacher workroom confi guration can be reconfi gured for shared space Opportunity for physical or visual connectivity between spaces Access to covered and open outdoor learning Improve natural lighting Chemistry Lab Interior SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 6
6 LIBRARY Newer building in need of future modernization Repurposing Computer Room as technology becomes more mobile Computer Room Interior Central Location and overall building condition and confi guration Integrate spaces into cohesive whole and connect to outside Library Entry SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 7
7 AG BARN, AGRICULTURE, VMT, & SHOP Aged buildings in need of modernization Non ADA compliant door hardware, sinks, restrooms & drinking fountains Wood Shop Interior Adjacent outdoor work areas support outdoor learning Improve natural light and ventilation Shop Building Exterior SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 8
8 DESOTO HALL Newer building with little modernization needed Some evidence of water intrusion Building Exterior Improve light in classrooms Classroom Interior SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 9
9 MUSIC BUILDING Aged facilities in need of modernization Evidence of water intrusion in some locations Lacking ADA compliant access and room signage Repair and restoration of historic exterior Building Exterior Brighten interior spaces Dance Room Interior SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 10
10 SOUTH GYMNASIUM Aged facilities in need of modernization Evidence of water intrusion in some locations Lacking ADA compliant room signage South Gymnasium Exterior Entry Provide ADA access to Coaches offi ces Repurpose shower areas Improve light and ventilation in Locker & Team Rooms Coaches Office SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 11
11 ARTQUEST BUILDINGS Aged facilities in need of major modernization Classroom entry doors are not ADA accessible Black Box Theater is not ADA accessible Art Classroom Interior Outdoor spaces provide opportunity for outdoor learning Improve signage at Drama Building for increased street presence Develop outdoor sculpture area Art Classroom Exterior SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 12
12 PORTABLE BUILDINGS Portable Classroom Clusters: Rooms & rooms entries not ADA compliant Portable Classroom Clusters: Room & aging structures in need of replacement Mesa Necessary School: Portable Classrooms 32, 33 & 34 past useful life Portable Building Exterior Replace with permanent construction buildings Portable Classroom Interior SANTA ROSA CITY SCHOOLS FACILITIES MASTER PLAN 13
PROCTOR TERRACE ELEMENTARY SCHOOL
SCHL DAA Address: Bryden Lane Santa Rosa, CA 95404 Established: 50 Permanent Classrooms: 3 Portable Classrooms: 9 Building Area: Site Area: 40, sq ft 5 acres Students in 5: 484 Students in (Projected):
More informationBriar Crest Elementary
Promises Kept This document includes partial lists of major projects completed at Pattonville Schools since 1986 as part of past bond issues approved by the Pattonville community. Briar Crest Elementary
More informationNYC Department of Education
Asset: NEW UTRECHT AF - BROOKLYN, 1601 80 STREET, New York, 11214 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior 2017-10-31 4:06 PM 2018-06-13 10:51 AM AA : Architectural
More informationNYC Department of Education
Architectural Inspection Building Assessment Survey 2017-2018 Asset: LEHMAN AF - BRONX, 3000 EAST TREMONT AVENUE, New York, 10461 Inspection Id Inspection Type Time In Last Edited SA : Architectural -
More informationPresentation of Concept Design to Parish 29 January 2017 ST. PETER S PARISH HOUSE
ST. PETER S PARISH HOUSE Presentation of Concept Design to Parish 29 January 2017 A Bold Vision for St. Peter s Future To create a space of hospitality a new parish house as a graceful complement to the
More information3. 21st Century Learning A. Districtwide Flexible Learning - Allowance for Flexible Furniture $600,000 Subtotal $600,000
1. Safety and Security A. Additional Cameras District Wide $382,000 B. Interior Locks Upgrades Allowance $300,000 C. Tilden Entrance Upgrades D. Door and Glass Improvements Allowance $500,000 E. Alert
More informationLINCOLN HIGH SCHOOL MODERNIZATION BEX IV COMMUNITY MEETING JUNE 23, 2016
LINCOLN HIGH SCHOOL MODERNIZATION BEX IV COMMUNITY MEETING JUNE 23, 2016 PROJECT OVERVIEW PROJECT OVERVIEW + PRE-DESIGN BEGAN IN FALL OF 2015 + EXISTING CONDITIONS ANALYSIS + PROJECTED GROWTH IN HIGH SCHOOL
More informationDesign Presentation. Chief Operations Officer Willie Burroughs
Design Presentation Chief Operations Officer Willie Burroughs Agenda Introduction Community Feedback Project updates 2 Feedback Citizens Advisory Committee meetings Growth and Development meetings Community
More informationFORT ERIE SECONDARY SCHOOL FACILITY INFORMATION. Lake Erie Corridor Secondary Schools Accommodation Review
FORT ERIE SECONDARY SCHOOL FACILITY INFORMATION Lake Erie Corridor Secondary Schools Accommodation Review November 2012 LAKE ERIE CORRIDOR SECONDARY SCHOOLS ACCOMMODATION REVIEW Fort Erie Secondary School
More informationNew High School Concept
Approved Bond Projects for Alamance-Burlington Schools In November 2018, Alamance County citizens approved a $150 million bond project proposal. Bond funds will pay to construct a new high school and provide
More informationNYC Department of Education
Asset: COLUMBUS AF - BRONX, 925 ASTOR AVENUE, New York, 10469 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior 2017-10-31 9:21 AM 2017-11-29 8:45 AM AA : Architectural - Associate
More informationEdward Jenner Elementary Academy of the Arts
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationChariho Regional School District Five-Year Capital Facilities Improvement Plan (2/10/15)
Chariho Regional School District Five-Year Capital Facilities Improvement Plan (2/10/15) School/Department FY 16 FY 17 FY18 FY19 FY20 Chariho Regional High School FY 16 FY 17 FY18 FY19 FY20 *Repair Bleachers
More informationMichigan State University Barrier-Free/Accessibility Project Status Summary March 2017
Projects Completed FY14, FY15 and FY16 (arranged alphabetically) Abrams Planetarium Install automatic door opener on main doors of the Planetarium. Completed: Summer 2016 Cost: $13,000 Akers Hall Renovations
More informationMaster Project List Report
Blue Hills Elementary School 01-8215 Site Utilities Replacement $52,835 01-8502 Modernization $3,135,933 01-8525 Exterior Painting $181,478 01-8552 Kindergarden Fencing $13,180 Install new backflow preventer.
More informationAntelope Valley College
Academic Commons Building Antelope Valley College C18-006-PID Science and Technology FACILITIES TECH ED TECH ED CTE INST TECH ED HEALTH & SCIENCES CSUB UNIV CENTER CDC APPLIED ARTS C18-006-PID Historic
More informationREPORT CARD TO THE COMMUNITY MAY 15, 2018
REPORT CARD TO THE COMMUNITY MAY 15, 2018 O On May 10, 2014 voters in Greenville ISD approved a $72,275,000 bond election. BOND PROPOSAL PROJECT BOND AMOUNT CONSTRUCT A NEW BOWIE ELEMENTARY SCHOOL $17,600,000
More informationENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING
Mechanical Systems Information The mechanical system at Reed Middle School is comprised of seventy six Trane DX/Gas rooftop units (RTUs). The recommended useful life for DX equipment is 15 years. Seventy
More informationCharles W Earle Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationIchabod Crane Central School District 2018 Capital Project Preliminary Estimate
Health & Safety 1,399,000 Academics & Program 17,140,800 Physical Education & Athletics 5,922,000 Building Infrastructure 3,103,800 Site Infrastructure 1,049,600 TOTAL SCOPE OF WORK 28,615,200 PROPOSED
More information2015 Building Condition Survey Summary Mosaic Associates Architects 02/19/16
1. General: This summary is offered as a supplement to the 2015 Building Condition Survey being filed with SED on behalf of the District. All cost estimates are preliminary, and should be re-evaluated
More informationCalmeca Academy of Fine Arts and Dual Language
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationMaster Facility Planning Update School Board Meeting May 26, 2016
Master Facility Planning Update School Board Meeting May 26, 2016 Master Facilities Committee Overview Reflection of Committee Work Review of District Wide Facility Issues Identified District Wide Facility
More informationKenmore Town of Tonawanda Union Free School District : Capital Improvement Project Phase 2
Kenmore Town of Tonawanda Union Free School District : Capital Improvement Project Phase 2 Adams Field Kenmore East High School Kenmore West High School Crosby Field Charles Lindbergh Elementary Thomas
More informationWILLIAM & MARY CUSTODIAL TASK & FREQUENCY LIST. PUBLIC SPACE: ENTRANCES, LOBBIES, AND CORRIDORS Daily Weekly Monthly Quarterly Yearly
WILLIAM & MARY CUSTODIAL TASK & FREQUENCY LIST PUBLIC SPACE: ENTRANCES, LOBBIES, AND CORRIDORS Daily Weekly Monthly Quarterly Yearly Collect & properly dispose of recycling as needed Dust, or wipe all
More informationG W C C GREENMOUNT WEST COMMUNITY CENTER GWCA - COMMUNITY CENTER. design recommendations
G W C C GREENMOUNT WEST COMMUNITY CENTER design recommendations GWCA - COMMUNITY CENTER PROGRAM SIDEWALK 1... ENTRANCE/EXIT A... MECHANICAL 2... LOBBY B... ELECTRICAL 1 3... RECEPTION C... MEN S TOILET
More informationVOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED
Ashton Elementary School 1 Masonry Repair $ 42,781.50 2 Replace HVAC $ 375,000.00 3 Replace SAT @ Various Locations $ 92,364.00 3 Recoat & Resurface Exterior Paved Play Area $ 135,978.30 3 Various Technological
More informationRichard Henry Lee Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationEmergency Management Resource Guide. Appendix A: Crime Prevention Through Environmental Design CPTED Principles Checklist for Kentucky Public Schools
Appendix A: Crime Prevention Through Environmental Design CPTED Principles Checklist for Kentucky Public Schools 143 Crime Prevention Through Environmental Design CPTED Principles Checklist for Kentucky
More informationMADISON ELEMENTARY SCHOOL
TWIN RIVERS UNIFIED SCHOOL DISTRICT MADISON ELEMENTARY SCHOOL 54 HARRISON STREET NORTH HIGHLANDS, CALIFORNIA 95660 ORIGINAL BUILDING COMPLETED: 96, 67 BUILDING AREA: 45,69 SITE ACREAGE: 0 BUILDING CAPACITY:
More informationAgustin Lara Elementary Academy
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationNEIGHBORS SOUTHWEST NEIGHBORHOOD MEETING December 17, 2014 BEAVERTON SCHOOL DISTRICT SOUTH COOPER MOUNTAIN HIGH SCHOOL
NEIGHBORS SOUTHWEST NEIGHBORHOOD MEETING December 17, 2014 AGENDA NEIGHBORHOOD MEETING Design Criteria Review 3 Concepts Discussion Q&A DESIGN CRITERIA NEIGHBORHOOD MEETING IMAGE & IDENTITY CIVIC PRESENCE
More informationCAPITAL OUTLAY REQUEST - IDENTIFIED AND EMERGING PROJECTS - RANKED 3-Jun-14
2014-2015 CAPITAL OUTLAY REQUEST - IDENTIFIED AND EMERGING PROJECTS - RANKED 3-Jun-14 School Item Amount a. Classroom A/R (Increase CR capacity to 804, add l Resource and tutoring spaces needed. Teacher
More informationOxford Hills School District Capital Renewal Plan Updated March 2017
Color Coding Guide Recently Completed In Progress FY 2017 Budget in FY 2018 Future Budgets/Projects 3/20/17 Capital Renewal Plan Updated March 2017 Capital Renewal Plan - Harrison Elementary Harrison add
More informationA NEW AMERICAN HIGH SCHOOL
A NEW AMERICAN HIGH SCHOOL typical American high school trends: large, dense, sprawling MANHATTAN HIGH SCHOOL GOULDEVANS MANHATTAN, KANSAS SANDY HIGH SCHOOL DULL OLSON WEEKES ARCHITECTS SANDY, OREGON
More information4. Plumbing fixtures. a) The plumbing fixtures are from the original building. They are appear old and not to comply with ADA requirements.
From: Jian Zhang Sheet: 1 of 8 Date of Visit: 12/7/10 Coach House: Plumbing Systems b) All original building storm piping shows significant signs of aging. b) All original building sanitary piping shows
More informationGenevieve Melody Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationCustom Report // Priorities 1+2
Custom Report // Priorities + All costs are shown in 08 dollars. The cost of all work items after this date should be adjusted accordingly. Print Date: 4/3/08 Foothill High School DESCRIPTION Building
More informationMASTER PLAN DIAGRAMS DISTRICT CAMPUS OVERVIEW
DISTRICT CAMPUS OVERVIEW Classrooms, CR Special Education Computer Lab INTERSTATE 5 FW - Faculty Work, FL - Faculty Physical Education / Athletics Support Spaces S - Storage, T - Toilets, U - Utility,
More informationHEALTH/LIFE SAFETY ANNUAL INSPECTION CHECKLIST (ROE)
HEALTH/LIFE SAFETY ANNUAL INSPECTION CHECKLIST (ROE) Administrative and General Building Requirements Safety reference plans (1) Fire alarm audibility (10) Alcohol hand-rub-dispensers (19) School safety
More informationEducate Challenge. LONG RANGE FACILITIES PLAN Long Range Facilities Plan Committee. June 11, :30 pm 7:30 pm
1 LPA LONG RANGE FACILITIES PLAN Long Range Facilities Plan Committee June 11, 2013 5:30 pm 7:30 pm Educate Challenge Inspire Agenda Campus Observations Update Overview of Demographics High School Program
More informationCAMPUS MASTER PLAN DRAFT PLAN UPDATE JANUARY
NEW MEXICO HIGHLANDS UNIVERSITY CAMPUS MASTER PLAN DRAFT PLAN UPDATE JANUARY 27 2010 MASTER PLANNING GOALS TO BALANCE THE STRATEGIC GOALS OF THE UNIVERSITY WITH THE PHYSICAL CAMPUS through the assessment
More informationMeasure W Review. East Nicolaus High School District March 9, 2017
Measure W Review East Nicolaus High School District March 9, 2017 To improve the quality of education with funding that cannot be taken by the State; repair or replace leaky roofs; modernize outdated classrooms,
More informationOscar DePriest Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationFACILITIES CONDITION ASSESSMENT WAGNER RANCH ELEMENTARY SCHOOL. Orinda Union School District Facilities Master Plan
FACILITIES CNDITIN ASSESSMENT WAGNE ANCH ELEMENTAY SCHL 0 0 60 0 AT MAE CL SCI SP INT IT BASC BASC LIB INCLUSIN SPECIALIST MU FW FL IT U ADMIN C MP IT Property line shown is estimated. CE Core Curriculum
More informationOhlone College Measure G Project Scope Revisions
Scope Revisions Current Title Revised Title Current Scope Revised Scope 6101 Relocated Baseball Field Athletic Fields Create new sustainable baseball field with synthetic turf, bleacher seating and batting
More informationWashington Irving Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationArch 464 ECS Spring 2012
1 Arch 464 ECS Spring 2012 Name Quiz #4 "Restoration Hall" Read and look at everything before you write! The newly remodeled Winters Building in Richmond, CA, houses the East Bay Center for the Performing
More informationJosefa Ortiz De Dominguez Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationAIA Albuquerque 2016 Design Awards
AIA Albuquerque 2016 Design Awards Citation Award General Design San Juan College School of Energy Dekker/Perich/Sabatini Citation Award General Design CNM Main Campus Wayfinding Studio Collaboration
More informationNumber of persons with a disability that live with a disability in your community?
Building name: re Dame Location: Owen Sound Assessment by: Cathy Smart Date: August 25, 2003 Total number of students: 378 Number of students living with a disability? Deaf/Hard of hearing Blind/Low vision
More informationEncumbered Balance (E-D) Branham HVAC Implementation Complete 100% 03/04/19 07/19/19 $765, $635, $635, $130, $0.
Branham High School Budget Remaining 1 906030 Branham HVAC Implementation Complete 100% 03/04/19 07/19/19 $765,473.00 $635,342.00 $635,342.00 $130,131.00 $0.00 2 970205 Branham Interim Housing - 12 Portable
More informationFACT SHEET Program: Event Fire Safety
FIRE AND LIFE SAFETY GUIDELINES FOR EVENTS INTRODUCTION The purpose of this fact sheet is to provide information for a safe environment for events and insure compliance with fire safety standards and regulatory
More informationCh. 54 GROUP B EDUCATIONAL 34 CHAPTER 54. GROUP B EDUCATIONAL OCCUPANCY GROUP
Ch. 54 GROUP B EDUCATIONAL 34 CHAPTER 54. GROUP B EDUCATIONAL OCCUPANCY GROUP Sec. 54.1. Group B occupancies. 54.2. Classification. 54.3. Nursery schools, day care centers and the like. 54.4. Separation
More informationWhite Bear Lake Area Schools District 624 ENERGY GUIDELINES
White Bear Lake Area Schools District 624 ENERGY GUIDELINES Developed by: White Bear Lake Area Schools Energy Steering Committee as part of the Schools for Energy Efficiency (SEE) Program ISD 624 Energy
More informationJohn Palmer Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationALLISON ELEMENTARY SCHOOL 4315 Don Julio Blvd., North Highlands, CA 95660
ALLISON ELEMENTARY SCHOOL 4315 Don Julio Blvd., North Highlands, CA 95660 Year Built 1960 // Age 58 years Building Area 31,688 Square Feet Student Capacity 389 Current Enrollment (2017-2018) 466 Priority
More informationDEERFIELD SCHOOL DISTRICT REFERENDUM Committed to Excellence and Equity in Educating Our Students
DEERFIELD SCHOOL DISTRICT REFERENDUM Committed to Excellence and Equity in Educating Our Students FACILITY NEEDS THE CHALLENGE Deerfield Middle School/High School building has served the community for
More informationFlorence High School / Middle School Page 1 of 3 Florence, WI
Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October
More informationGreenwood Elementary School 5550 South Holly Street Greenwood Village, Colorado 80111
Greenwood Elementary School 5550 South Holly Street Greenwood Village, Colorado 80111 Year Opened 1958 Current Square Footage 50,504 Site Acreage 8.53 greenwood.cherrycreekschools.org $220,720 Electrical
More informationElectrical Inspection Special Electrical
0941 Fire Alarm System Devices, panels, wiring, conduit, etc. The present fire alarm system manufactured by Gamewell was installed with the 1982 renovation. It is a non addressable, zoned system. It includes
More informationTIFT COUNTY SCHOOLS E-SPLOST HISTORY
TIFT COUNTY SCHOOLS E-SPLOST HISTORY July 1, 1997 June 30, 2002 $28,766,187.16 collected July 1, 2002 June 30, 2007 $39,025,830.10 collected July 1, 2007 June 30, 2012 $41,886,155.46 collected July 1,
More informationBeaufort County Community College. Maintenance and House Keeping Plan
Beaufort County Community College Maintenance and House Keeping Plan Summary: The College s facility management is handled by the Maintenance Department. The Director of Plant and Maintenance Operations
More informationInterior signs are an extension of the exterior sign system and their content and design should take this into consideration.
General Guideline The Interior Sign standard is developed to address the need for a cost effective, functional, flexible and serviceable sign system. The intent is to assure code compliance, consistency
More informationKerrville ISD has called for a bond election in the amount of $88,960,000 for November 6, 2018
Kerrville ISD has called for a bond election in the amount of $88,960,000 for November 6, 2018 WHAT IS A BOND ELECTION? Provide communities an opportunity to vote to give the Board of Trustees authority
More informationSchool Property REVIEWING YOUR BUILDINGS & GROUNDS
School Property REVIEWING YOUR BUILDINGS & GROUNDS Risk Management CHECKLIST Instructions: Use this checklist to record issues that may affect your school s security and safety. Check needs attention and
More informationMOUNT PLEASANT MIDDLE SCHOOL HVAC. M-01 Heating Plant: M-02 Heating & Ventilating Systems: Livingston School District Mount Pleasant Middle School
MOUNT PLEASANT MIDDLE SCHOOL HVAC M-01 Heating Plant: The existing boilers have recently been upgraded. (3) steam boilers (8660 mbh each) manufactured by Weil- McLain have been installed. Newer hot water
More informationPLAN REVIEW SUBMITTAL GUIDE
PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide
More informationAllisonville Elementary School Facilities Highlights Built: 1960 Last Major Renovation: 28 years ago Capacity: 650 Current Enrollment: 767
Allisonville Elementary School Built: 1960 Last Major Renovation: 28 years ago Capacity: 650 Current Enrollment: 767 ADA improvements are Fire alarms need to be updated Playground equipment needs to be
More informationNorth Elevation Existing trees along Pike Street were preserved and enhanced with extensive planting.
Project Information Project Name: The Northwest School at 401 E. Pike Street Lot Size: 9,652 sf Building Area: 38,300 sf Location: Seattle, Washington Project Type: Educational The Northwest School is
More informationTRINITY LUTHERAN SCHOOL RENOVATIONS
MASTER PLAN FOR PHASED IMPROVEMENTS AUGUST 26, 2013 WITH DESIGN AND PLANNING GUIDANCE FROM WIGHT & COMPANY` Recognizing the importance of its school facility s general appearance, school officials initiated
More informationAlessandro Volta Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationMechanical Inspection Plumbing
0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,
More information2014 Bond Project Guide
2014 Bond Project Guide Bush Elementary School Page 1 Instructional Technology Computers, Projectors, Mobile Carts, Document Cameras and Printers Wireless Connectivity New Construction New Tech Center
More informationStanfield School District Cleaning Standards
Stanfield School District Cleaning Standards Universal Precautions Always wear protective gloves. Do not use gloves that have holes or tears. Treat all body fluid spills as if they were contaminated. Items
More informationAngela M. Bollinger. architecture & interior design project management facilities management PORTFOLIO
Angela M. Bollinger architecture & interior design project management facilities management PORTFOLIO 2016 Outdoor Recreation Sport Complex Create a new Outdoor Recreation Sports Complex for NIU Campus
More informationSCHEMATIC DESIGN PRESENTATION
August 5, 2014 SCHEMATIC DESIGN PRESENTATION ADDITIONS & RENOVATIONS Greenville Independent School District Acknowledgments 2 Narrative 3-6 Crockett Elementary School 7-12 L.P. Waters Early Childhood Center
More informationSPLOST I, II, III,IV
ACWORTH ES (OLD) ACWORTH INTERMEDIATE Construction projects not done due to school replacement Land Acquisition, 61 IU Replacement Elementary School Access Controls, Temperature monitors for walk in coolers
More informationLONG-RANGE FACILITIES PLAN
FACILITIES ASSESSMENT December 11, 2018 LONG-RANGE FACILITIES PLAN 2018-2019 The Facilities Assessment Process What is the charge? How is the information gathered? Format of the Report District-Wide &
More informationPLATTEVILLE MIDDLE SCHOOL
Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle
More informationTech Report. September 9,
Rendering courtesy of the S L A M Collaborative Tech Report I Part I Elizabeth Kimble Lighting/Electrical Option Dr. Houser University Research Building Northeast United States September 9, 2013 Executive
More informationVirginia Department of Planning and Budget Project Request Justification
DPB Form CNJ June 2005 Virginia Department of Planning and Budget Project Request Justification 2006-2008 Biennium Date: July 22, 2005 A. General Information 1. Agency name: Virginia Tech 2. Agency code:
More informationHIGH SCHOOL SPACE REQUIREMENTS AND SPECIAL CONDITIONS. New School and Facility Planning August 2006 MALL CONCEPT PROTOTYPE 2000 HIGH SCHOOL
HIGH SCHOOL SPACE REQUIREMENTS AND SPECIAL CONDITIONS New School and Facility Planning August 2006 MALL CONCEPT PROTOTYPE 2000 HIGH SCHOOL EDUCATIONAL REVIEW COMMITTEE A special thanks to the educational
More informationANNUAL COMPREHENSIVE SAFETY INSPECTION REPORT STATE BOARD OF EDUCATION ADMINISTRATIVE RULE - SREF 2014 & F.A.C. 69A-58 FISCAL YEAR
ANNUAL COMPREHENSIVE SAFETY INSPECTION REPORT STATE BOARD OF EDUCATION ADMINISTRATIVE RULE - SREF 2014 & F.A.C. 69A-58 FISCAL YEAR 2017-2018 College Facility: South Florida State College SCHOOL / FACILITY:
More informationJoseph Brennemann Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationdusty. Room shakes and Student restrooms across All vents need cleaning
Timestamp Observation: 01B. TEMPERATURE: Room Number or Location/Name: Comments for this room: ADMINISTRATION CUSTODIAL 6/1/2017 15:08:34 Uncomfortable 01B. TEMPERATURE: 310 Etremely warm 6/1/2017 15:11:42
More informationForest Hills Facilities Plan
Forest Hills Facilities Plan Extensive updates to 8 of our 9 schools Replace Wilson Elementary Enhance learning environments across the district Build additional classrooms to accommodate gradual implementation
More informationFACILITIES CONDITION ASSESSMENT WAGNER RANCH NATURE AREA. Orinda Union School District Facilities Master Plan
FACILITIES CNDITIN ASSESSMENT WAGNE ANCH NATE AEA 0 30 60 0 AT MAE CL SCI SP INT 4 IT 3 3 BASC BASC INCLSIN SPECIALIST M FW FL IT ADMIN C MP IT Property line shown is estimated. CE Core Curriculum (Language
More informationGENERAL ASSIGNMENT CLASSROOM DESIGN STANDARDS
University of Iowa FSG - Design & Construction Services Design Reference Manual 2 Design Standards 2.02 Classroom Design Standards Classroom Design Standards GENERAL ASSIGNMENT CLASSROOM DESIGN STANDARDS
More informationDRAFT. Widen Elementary School Site Summary 74,523 SF. Introduction
1 Widen Elementary School Site Summary Address 5605 Nuckols Crossing Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 1986 Total Campus Building Area (combined) 74,523
More informationConference-Seminar Table & chair Case Study (tiered) Swivel chairs, Continuous Counter Top
III. DESIGN 3.03 Academic Building Interior Space Square Footage Standards A. Plan academic spaces in new buildings and in the major renovation of existing buildings to conform to the following space standards:
More informationZen Center Space Programming ( )
Zen Center Space Programming (1-17-17) As a sangha, we worked together to create an extensive list of spaces and functions that we feel are necessary components of the future Des Moines Zen Center. We
More informationNYACK PUBLIC SCHOOLS CAPITAL IMPROVEMENT PLANNING PROCESS
NYACK PUBLIC SCHOOLS CAPITAL IMPROVEMENT PLANNING PROCESS DECEMBER 3, 2013 KEY QUESTIONS 1. What is the time sequence for available funding? (In what years will the funding be available?) 2. What is the
More informationSafety & Security Checklist by Layers of Building and Grounds The Church Safety and Security Guidebook (Brotherhood Mutual Insurance)
Appendix D Safety & Security Checklist by Layers of Building and Grounds The Church Safety and Security Guidebook (Brotherhood Mutual Insurance) Assessing Specific Areas Look at each Layer of Security
More informationMcLean High School 2017 All-Night Graduation Party. Volunteer Security and Emergency Procedures. Emergency Contact Information
McLean High School 2017 All-Night Graduation Party Volunteer Security and Emergency Procedures Date June 15, 2017 June 16, 2017 Time Location 11:00 pm 4:30 am Set-up scheduled to be completed by 10:00
More informationWilliam S. Hart Union High School District. MODERNIZATION UPDATE May 7, 2008
William S. Hart Union High School District MODERNIZATION UPDATE May 7, 2008 Completed D B Z C L T A E H Q F J M R R STAGING AREA G K N S V Canyon High School O P Canyon High School Phase II Science Building
More informationGARDEN GROVE FIRE DEPARTMENT
GARDEN GROVE FIRE DEPARTMENT PRE-INSPECTION CHECKLIST PROGRAM FOR SCHOOLS The Garden Grove Fire Department provides an annual school life safety inspection each year to protect lives and property in the
More informationGarfield Elementary School Feasibility Study for New Library Building Project Number A C
Larry Teixeira Selma Unified School District 3036 Thompson Avenue Selma, CA 93662 Subject: Feasibility Study for New Library Building Project Number A 12-8581.00 C Dear Mr. Teixeira: At your request, we
More informationSprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS
EXISTING MECHANICAL CONDITIONS SUMMARY The items listed below are based on our site visit on Nov 10, 2016. Our review is based on current conditions and anticipated future use of these building. In the
More informationFacilities Procedure for Accessibility or Compliance Related Requests:
Facilities Procedure for Accessibility or Compliance Related Requests: All doorways, entry ways, equipment height, etc. will be checked to ensure compliance with the Americans with Disabilities Act (ADA)
More information