NYC Department of Education

Size: px
Start display at page:

Download "NYC Department of Education"

Transcription

1 Asset: UNIVERSITY NEIGHBORHOOD - M, 200 MONROE STREET, New York, Inspection Id Inspection Type Time In Last Edited ME : Mechanical :56 AM :14 PM Asset Data Are there fuel tanks? Total # of above ground tanks 1 Answer Total capacity of all above ground tanks in gal. 5,000 Total # of below ground tanks 0 Total capacity of all below ground tanks in gal. 0 Total # of water main service entries to the asset 2 MERs/Fan Rooms Locations Are there any spaces with Missing or Defective CO Detectors? Location(s) Science Demo 504 Are there any Emergency Stop Switches with Missing Hammers? Are there any Painted/Obstructed Sprinkler Heads? Have any Systems/Major Building Components been upgraded? Priority NYC Department of Education Building Assessment Survey Yes None Yes No No Yes Systems: Years: 2016 Systems: Years: 2015 Systems: Years: 2012 Electric Domestic Water Heater for Kitchen Fixtures - Staff And Other: Lavatory/Sinks (50%), Toilets (50%); Fixtures - Student: Lavatory/Sinks (50%), Toilets (50%), Urinals (70%); Climate Control System - Air Compressor; Exhaust Fans in Dance and Weight Rooms (2 of 3) DX Split System for 2nd Floor Camera Room Systems: Water Service (1 of 2) Years: 2009 Systems: Years: 2008 MDF Room - Dedicated A/C Equipment (DX Split System, 1 of 2) Priority Priority Exist Category Last Year? Description Component Affected Location Description Person(s) Notified Person(s) Title Status PhotoImage No No Defective Boiler Safety Auxiliary Defective Boiler Safety Auxiliary Boiler #1: Low-Water Cut-off and Water Column leaking Boiler #2: Low-Water Cut-off Leaks No Other Gas Leak at Gas Train and Vents for Boiler #2 HEATING PLANT Boiler System Steam Boiler HEATING PLANT Boiler System Steam Boiler HEATING PLANT Fuel System Gas Trains And Vent At The Boiler Kenny Liang Handyman Sent to DSF Kenny Liang Handyman Sent to DSF / Boiler #2 (gas leak) Patrick Gullottie Fireman Sent to DSF Inspection Mechanical AIR CONDITIONING Chilled Water System Condenser Water Distribution: Piping, Pumps and Auxiliaries PB/A&W Page 1 of 15

2 Building Assessment Survey AIR CONDITIONING Cooling Coil in Ductwork Cooling Tower DX Split System Indoor Unit 1 - Good Outdoor Unit 1 - Good Dry Cooler Packaged / Rooftop Unit Under Construction Packaged Terminal A/C Refrigerant Piping 1 - Good Return Fan CENTRAL ACID WASTE NEUTRALIZING TANK CLIMATE CONTROL SYSTEM BMS Pneumatic System Instance Throughout Instance Instance Quantity 1 Instance Building Area Covered by Operational System % Hybrid System Electric System COMPACTOR CONVEYING Dumbwaiter Elevator Are all the existing elevators operable? Yes Escalator Non-auditorium Handicap Lift - Vertical Non-auditorium Handicap Lift - Stair Ash Hoist Sidewalk Elevator DOMESTIC WATER SYSTEM Domestic Cold Water System Gravity System Supply Pump Roof Tank PB/A&W Page 2 of 15

3 Building Assessment Survey DOMESTIC WATER SYSTEM Domestic Cold Water System Gravity System Roof Tank NOT IN USE Location/Instance Penthouse Quantity 1 NO ACTION Urgency of Action PRIORITY 1 Purpose of Action LEVEL 1 Photo1 Pressure Booster System Electric Pressure Booster System Instance Instance 4 - Between Fair and Poor Instance Quantity 1 Instance Instance Manufacturer Dayton Electric Equipment N/A Capacity/Size Quantity 1 Capacity/Size UOM Total # Pumps Capacity/Size2 Quantity 2 Capacity/Size2 UOM Total Pumps HP Source of Capacity/Size Documented Installation Year 1985 Source of Installation Inspector Estimate DEFECTIVE CONTROLS Quantity 1 REPAIR Photo1 BEYOND USEFUL LIFE Location/Instance Quantity 1 Urgency of Action PRIORITY 1 Photo1 Hydraulic/Pneumatic Booster System Water Pressure Booster - Compressor PB/A&W Page 3 of 15

4 Building Assessment Survey DOMESTIC WATER SYSTEM Domestic Cold Water System Pressure Booster System Hydraulic/Pneumatic Booster System Water Pressure Booster - Compressor NOT IN USE Location/Instance Quantity 1 NO ACTION Urgency of Action PRIORITY 1 Purpose of Action LEVEL 1 Photo1 Pressure Booster Pump Location/Instance Quantity 1 NOT IN USE NO ACTION Urgency of Action PRIORITY 1 Purpose of Action LEVEL 1 Photo1 Domestic Cold Water Tank Water Service Instance Instance Instance Quantity 1 Instance Location/Instance Quantity 1 WATER MAIN: MISSING BACKFLOW PREVENTION DEVICE INSTALL Photo1 Instance Instance Instance Quantity 1 Instance Location/Instance Quantity Good WATER MAIN: MISSING BACKFLOW PREVENTION DEVICE INSTALL PB/A&W Page 4 of 15

5 Building Assessment Survey DOMESTIC WATER SYSTEM Domestic Cold Water System Water Service Photo1 Domestic Hot Water System Domestic Hot Water Remote Storage Tank Domestic Water Heat Exchanger Electric Domestic Water Heater Gas Fired Domestic Water Heater Instance Instance Instance Quantity 1 Instance Instance Manufacturer Equipment Capacity/Size Quantity 254 Capacity/Size UOM Capacity/Size2 Quantity 0 Capacity/Size2 UOM Source of Capacity/Size 1 - Good RayPak N/A MBH Input Gallons Installation Year 2002 Source of Installation Oil Fired Domestic Water Heater Domestic Water Distribution Piping DRAIN/WASTE/VENT AND STORM SYSTEM Interior Storm Piping Sewage/Waste/Vent Piping Sewage Ejector Pump Sump Pump DUAL TEMPERATURE SYSTEM (CHILLED AND HOT WATER) FIXTURES Staff And Other Inspector Estimate Inspector Estimate PB/A&W Page 5 of 15

6 Building Assessment Survey FIXTURES Staff And Other Janitor Sink Lavatory/Sink 2 - Between Good and Fair Toilet 2 - Between Good and Fair CLOGGED/LEAKING Location/Instance 2nd Floor Men's Toilet Room Quantity 1 MAINTENANCE Photo1 Urinal Student Drinking Fountain CLOGGED/LEAKING Location/Instance Corridor by Room 209 Quantity 1 MAINTENANCE Photo1 Lavatory/Sink Locker Room Shower Sink And Fountain Combo Unit Toilet Urinal GAS FIRED FURNACE GAS SERVICE HEATING Heating Coil In Ductwork 2 - Between Good and Fair 2 - Between Good and Fair 1 - Good Under Construction PB/A&W Page 6 of 15

7 Building Assessment Survey HEATING Hydronic Heating Radiator/Convector/Fin Tube RADIATOR/CONVECTOR: MISSING GUARD/SHIELD Location/Instance Custodian's Office Quantity 2 Photo1 Steam Heating F&T/Steam Drip Trap MER Steam and Condensate Piping Steam Condensate Return Piping Location/Instance Quantity 15 DAMAGED/MISSING INSULATION L.F. Photo1 Location/Instance Quantity 1 DEFECTIVE ISOLATION VALVE Photo1 Steam Condensate Return Pumping System Steam Piping Location/Instance Quantity 10 DEFECTIVE/LEAKS Basement L.F. Photo1 DEFECTIVE ISOLATION VALVE PB/A&W Page 7 of 15

8 Building Assessment Survey HEATING Steam Heating Steam Piping Location/Instance Quantity 3 Photo1 Location/Instance Quantity 10 DAMAGED/MISSING INSULATION 2nd Floor Toilet Room by Stair F L.F. Photo1 Terminal Unit Thermostatic Trap Steam supplied by External Sources Unit Heater/Cabinet Heater HEATING PLANT Replacement Quantity 6,068 Replacement Uom Burner Type Heating Plant Oil Number Boiler Auxiliaries Boiler Auxiliary Piping Boiler Emergency Stop Switch Boiler Feedwater System Boiler Feedwater Treatment(Automatic) Boiler Flue Exhaust Boiler Make-up Water Backflow Preventer MBH Net Dual Fuel (Gas/Oil) 2 PB/A&W Page 8 of 15

9 Building Assessment Survey HEATING PLANT Boiler Auxiliaries Boiler Make-up Water Backflow Preventer Steam And Condensate Piping Boiler Safety Valve Boiler System Coal-fired Boiler Hot Water Boiler Modular Boiler Steam Boiler Instance Instance Instance Quantity 3,034 Instance MBH Net Instance Manufacturer Superior Equipment Capacity/Size Quantity 4,029 Capacity/Size UOM Lbs/Hr steam Source of Capacity/Size Documented Installation Year 1977 Source of Installation Inspector Estimate DAMAGED CASING Quantity 1 REPAIR Photo1 Quantity 1 DEFECTIVE SAFETY AUXILIARY: LOW-WATER CUT-OFF, WATER COLUMN ASSEMBLY MAINTENANCE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 PB/A&W Page 9 of 15

10 HEATING PLANT Boiler System Steam Boiler NYC Department of Education Building Assessment Survey Location/Instance Quantity 1 BEYOND USEFUL LIFE Urgency of Action PRIORITY 1 Photo1 Instance Instance Instance Quantity 3,034 Instance Instance Manufacturer MBH Net Superior Equipment Capacity/Size Quantity 4,029 Capacity/Size UOM Source of Capacity/Size Installation Year 1977 Source of Installation Quantity 1 Lbs/Hr steam Documented Inspector Estimate LEAKY/PLUGGED TUBES Photo1 Quantity 1 DEFECTIVE SAFETY AUXILIARY: LOW-WATER CUT-OFF, WATER COLUMN ASSEMBLY MAINTENANCE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Location/Instance Quantity 1 BEYOND USEFUL LIFE Urgency of Action PRIORITY 1 PB/A&W Page 10 of 15

11 HEATING PLANT Boiler System Steam Boiler Photo1 NYC Department of Education Building Assessment Survey Fuel System Boiler Fresh Air Louver/Damper Burner/Burner Control Panel Fuel Oil Storage/Supply System Gas Trains And Vent At The Boiler DEFECTIVE Location/Instance / Boiler #2 (gas leak) Quantity 1 REPAIR Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Enclosed IDF Room Instance on Room 313 Dedicated A/C Equipment Instance on Room Between Fair and Poor DOES NOT EXIST Location/Instance Room 313 Quantity 1 INSTALL Photo1 KITCHEN CO Detector Not Required Not Required PB/A&W Page 11 of 15

12 Building Assessment Survey KITCHEN Gas System Grease Trap DEFECTIVE/CLOGGED Location/Instance Basement Quantity 1 MAINTENANCE Photo1 Hood Hood Exhaust Ductwork Hood Exhaust Fan Hood Fire Suppression System Hot Water Temperature Booster Kitchen Sink MDF Room Instance on 2nd Floor Room adjacent to Stairway B Dedicated A/C Equipment Instance on 2nd Floor Room adjacent to Stairway B SCIENCE DEMO ROOM Alternative use Alternative use Acid Waste Neutralizing Tank CO Detector 2 - Between Good and Fair Yes No Location/Instance Room 504 Quantity Between Fair and Poor DEFECTIVE/MISSING PB/A&W Page 12 of 15

13 Building Assessment Survey SCIENCE DEMO ROOM CO Detector MAINTENANCE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Emergency Shower Eye Wash Hood Exhaust Ductwork Hood Exhaust Fan Fixed Laboratory Hood Laboratory Sink Make-up Air Unit SCIENCE LAB Alternative use Acid Waste Neutralizing Tank CO Detector Not Required No PB/A&W Page 13 of 15

14 Building Assessment Survey SCIENCE LAB CO Detector Emergency Shower Eye Wash Hood Exhaust Ductwork Hood Exhaust Fan Fixed Laboratory Hood Laboratory Sink Make-up Air Unit SCIENCE PREP ROOM Alternative use No Acid Waste Neutralizing Tank CO Detector Emergency Shower Eye Wash Hood Exhaust Ductwork Hood Exhaust Fan 4 - Between Fair and Poor DEFECTIVE Location/Instance Room 501 Quantity 1 PB/A&W Page 14 of 15

15 Building Assessment Survey SCIENCE PREP ROOM Hood Exhaust Fan MAINTENANCE Photo1 Fixed Laboratory Hood Laboratory Sink Make-up Air Unit SPRINKLERS, STANDPIPE, FIRE SYSTEM Under Construction SWIMMING POOL VENTILATION Exhaust Fan Approximate Total # of Fans Between Good and Fair Heating And Ventilating Unit Metal Ductwork Supply Fan Unit Ventilator PB/A&W Page 15 of 15

NYC Department of Education

NYC Department of Education Asset: P.S. 104 - BROOKLYN, 9115 5TH AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-21 8:55 AM 2018-02-21 1:09 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 4 - MANHATTAN, 500 WEST 160TH STREET, New York, 10032 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-08 8:29 AM 2017-12-08 3:44 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 7 - MANHATTAN, 160 EAST 120 STREET, New York, 10035 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-02 8:44 AM 2018-03-12 10:45 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: I.S. 131 - BRONX, 885 BOLTON AVENUE, New York, 10473 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-10-17 8:54 AM 2017-12-05 5:41 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: MORRISANIA SEC ED COMPLEX-X, 1365 FULTON AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-03 8:53 AM 2017-11-03 5:47 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 198 - BRONX, 1180 TINTON AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-24 8:14 AM 2018-01-24 9:32 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 163 - BRONX, 2075 WEBSTER AVENUE, New York, 10457 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-22 8:33 AM 2018-03-22 3:13 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 188 - MANHATTAN, 442 EAST HOUSTON STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-08 8:52 AM 2018-06-13 5:06 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: FORSYTH HS (AUXSVC-OLD 91) - M, 198 FORSYTH STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-09-28 8:07 AM 2018-03-20 4:47 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: I.S. 2 - BROOKLYN, 655 PARKSIDE AVE, New York, 11226 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-11 9:35 AM 2018-05-22 3:53 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 199 ANNEX (@ ST. TERESA'S) - QUEENS, 50-15 44TH STREET, New York, 11377 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-18 11:39 AM 2018-05-14 12:27 PM Asset Data

More information

NYC Department of Education

NYC Department of Education Asset: AUTOMOTIVE TRADES VOC HS - K, 50 BEDFORD AVENUE, New York, 11222 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-01 8:09 AM 2018-05-10 2:18 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 146 - BRONX, 968 CAULDWELL AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-01 8:57 AM 2018-05-31 2:59 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 69 - STATEN ISLAND, 144 KEATING PLACE, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-19 8:39 AM 2018-01-23 4:33 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: ACHIEVEMENT FIRST ENDEAVOR CHARTER SCHOOL- BROOKLYN, 510 WAVERLY AVENUE, New York, 11238 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-14 8:42 AM 2018-03-23 10:17 AM

More information

NYC Department of Education

NYC Department of Education Mechanical Inspection Asset: P.S. 1 - MANHATTAN, 8 HENRY STREET, New York, 10038 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-09-28 8:39 AM 2017-10-12 5:28 PM Asset Data Are there

More information

NYC Department of Education

NYC Department of Education Asset: A. PHILLIP RANDOLPH HS - MANHATTAN, 443 WEST 135 STREET, New York, 10031 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-02-02 8:11 AM 2018-06-14 1:21 PM Asset Data Are there

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 194 - MANHATTAN, 244 WEST 144 STREET, New York, 10030 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-12 10:48 AM 2018-01-29 10:54 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: LIBERTY HS - MANHATTAN, 250 WEST 18 STREET, New York, 10011 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-29 11:32 AM 2018-02-01 10:16 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 841- QUEENS, 48-25 37TH STREET, New York, 11104 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-02 12:54 PM 2018-05-14 12:28 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: I.S. 45 - BRONX, 2502 LORILLARD PLACE, New York, 10458 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-05 9:14 AM 2017-12-20 11:42 AM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 160 - BROOKLYN, 5105 FORT HAMILTON PARKWAY, New York, 11219 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-03 8:01 AM 2018-05-18 1:45 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 32 - BRONX, 690 EAST 183 STREET, New York, 10458 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-13 9:25 AM 2017-11-16 5:46 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 111 - MANHATTAN, 440 WEST 53 STREET, New York, 10019 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-16 8:47 AM 2018-03-21 8:02 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 22 - STATEN ISLAND, 1860 FOREST AVENUE, New York, 10303 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-08 8:51 AM 2017-12-18 4:14 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 11 - MANHATTAN, 320 WEST 21 STREET, New York, 10011 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-23 8:27 AM 2018-01-23 3:21 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: J. K. ONASSIS HS FOR INT CAREERS-M, 120 WEST 46 STREET, New York, 10036 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-11 11:37 AM 2017-12-26 12:18 PM Asset Data Are there

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 161 - MANHATTAN, 499 WEST 133 STREET, New York, 10027 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-15 8:26 AM 2018-06-08 1:37 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 73 - BRONX, 1020 ANDERSON AVENUE, New York, 10452 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-16 8:29 AM 2017-11-28 10:59 AM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: PRE-K CENTER @ 7401 FORT HAMILTON PARKWAY - BROOKLYN, 7401 FORT HAMILTON PARKWAY, New York, 11228 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-27 11:12 AM 2017-11-27

More information

NYC Department of Education

NYC Department of Education Asset: P.S./I.S. 194 - BRONX, 2365 WATERBURY AVENUE, New York, 10462 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-24 8:34 AM 2018-02-01 10:02 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: MID MAN ADULT LRNG CTR (81) - M, 212 W 120TH ST, New York, 10027 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-17 8:16 AM 2018-01-17 8:17 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 29 - STATEN ISLAND, 1581 VICTORY BLVD, New York, 10314 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-10 11:28 AM 2018-01-17 11:37 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 23 - BROOKLYN, 545 WILLOUGHBY AVENUE, New York, 11206 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-31 8:47 AM 2018-06-05 3:45 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 183 - QUEENS, 2-45 B 79 STREET, New York, 11693 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-02 8:32 AM 2018-05-16 1:44 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 19 - STATEN ISLAND, 780 POST AVENUE, New York, 10310 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-10-26 8:58 AM 2017-11-14 1:37 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 157 - BRONX, 757 CAULDWELL AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-01 8:48 AM 2017-12-06 5:36 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 86 ANNEX - BRONX, 124 EAMES PLACE, New York, 10468 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-05 1:03 PM 2018-04-27 1:35 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: J.H.S. 216 - QUEENS, 64-20 175 STREET, New York, 11365 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-06 8:51 AM 2017-11-22 10:04 AM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 253 - BROOKLYN, 601 OCEAN VIEW AVENUE, New York, 11235 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-22 8:34 AM 2018-05-31 5:42 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 78 - QUEENS, 48-09 CENTER BLVD., New York, 11109 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-04-02 11:40 AM 2018-04-19 9:04 AM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 2 - MANHATTAN, 122 HENRY STREET, New York, 10002 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-05 9:21 AM 2018-01-16 12:15 PM Asset Data Are there fuel tanks? Total

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 92 - BROOKLYN, 601 PARKSIDE AVENUE, New York, 11226 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-13 8:31 AM 2017-11-27 11:43 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 128 - MANHATTAN, 560 WEST 169 STREET, New York, 10032 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-07 8:50 AM 2018-06-14 1:16 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-07 8:42 AM 2017-12-13 12:31 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 224 ANNEX - QUEENS, 221-21 CORBETT ROAD, New York, 11361 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-03-28 12:27 PM 2018-04-04 5:15 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: W.E.B. DUBOIS HS - BROOKLYN, 402 EASTERN PARKWAY, New York, 11225 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-04 1:02 PM 2017-12-27 4:16 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 205B (ECF) - BRONX, 2375 SOUTHERN BLVD, New York, 10460 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-12 12:29 PM 2018-01-12 3:14 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: HS FOR MATH, SCI & ENGINEERING-M, 240 CONVENT AVENUE, New York, 10031 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-12-20 12:04 PM 2018-01-05 5:32 PM Asset Data Are there

More information

NYC Department of Education

NYC Department of Education Asset: LEARNING SUPPORT CENTER - M, 333 7TH AVENUE, New York, 10001 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-01-23 8:46 AM 2018-01-30 10:47 AM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: CLINTON AF - BRONX, 100 W. MOSHOLU PKWY S, New York, 10468 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-11-20 8:24 AM 2017-12-31 2:04 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education Building Condition Assessment Survey :49AM :00PM

NYC Department of Education Building Condition Assessment Survey :49AM :00PM School: InspectionId Asset Data Inspection Type Building Assessment Survey 05-06 P.S. 70 - BROOKLYN, 4 EMERSON PLACE, BROOKLYN, NY, 05 Time In Last Edited 476 MECHANICAL 05-- 08:49AM 05-- 03:00PM Have

More information

NYC Department of Education

NYC Department of Education Asset: BAYSIDE AF - QUEENS, 204-29 29TH AVENUE, New York, 11361 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2017-10-31 9:42 AM 2017-11-20 4:21 PM Asset Data Are there fuel tanks?

More information

NYC Department of Education

NYC Department of Education Asset: JEFFERSON AF - BROOKLYN, 125-08 FLATLANDS AVENUE, New York, 11208 Inspection Id Inspection Type Time In Last Edited ME : Mechanical 2018-05-07 8:39 AM 2018-05-08 2:04 PM Asset Data Are there fuel

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 86 - BROOKLYN, 220 IRVING AVENUE, New York, 11237 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-14

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 184 - QUEENS, 163-15 21 ROAD, New York, 11357 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-05 11:46

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 59 ANNEX - BRONX, 2120 QUARRY RD, New York, 10457 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-02-12

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 5 - BROOKLYN, 820 HANCOCK STREET, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-25 8:54 AM 2018-06-04 10:18 AM Asset Data Type of Service Does Interactive

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 47 - QUEENS, 9 POWER ROAD, New York, 11693 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-20 12:40

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: I.S. 260 - MANHATTAN, 425 WEST 33RD STREET, New York, 10001 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-16

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 174 - QUEENS, 65-10 DIETERLE CRESCENT, New York, 11374 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-01-25

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 152 - MANHATTAN, 93 NAGLE AVENUE, New York, 10040 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-05

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 138 AX (CROWN HGTS ECC 1)-K, 960 PROSPECT PLACE, New York, 11216 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 80 AX(PETR COMPL-BLDG E)-S.I., 715 OCEAN TERRACE, New York, 10301 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: NEW SCH FOR ARTS AND SCIENCE - X, 965 LONGWOOD AVENUE, New York, 10459 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-01 8:13 AM 2017-12-01

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 131 - QUEENS, 170-45 84TH AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-18

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: PS 152 ANNEX -BROOKLYN, 1087 OCEAN AVENUE, New York, 11210 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 371 (OLD 615) - BROOKLYN, 355 37 STREET, New York, 11232 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-23

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 135 - QUEENS, 207-11 89TH AVENUE, New York, 11427 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 56 - STATEN ISLAND, 250 KRAMER AVE., New York, 10309 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-20

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 127 - BROOKLYN, 7805 7 AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-30

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-07

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 16 - BROOKLYN, 157 WILSON STREET, New York, 11211 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-30

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 81 ANNEX (OLD 75) - QUEENS, 511 SENECA AVENUE, New York, 11385 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: HS OF AMERICAN STUDIES - BRONX, 2925 GOULDEN AVENUE, New York, 10468 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education Asset: LEARNING SUPPORT CENTER - K, 1665 ST. MARKS AVENUE, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-07 1:06 PM 2018-05-10 12:20 PM Asset Data Type of Service

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 314 - BROOKLYN, 330 59 STREET, New York, 11220 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-23

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: FRANCIS LEWIS HS TRANSPORTABLE - Q, 58-20 UTOPIA PARKWAY, New York, 11365 Inspection Id Inspection Type Time In Last Edited EE :

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: I.S. 364 - BROOKLYN, 1426 FREEPORT LOOP, New York, 11239 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-16

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: HS FOR MATH, SCI & ENGINEERING-M, 240 CONVENT AVENUE, New York, 10031 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-20 11:37 AM 2018-01-09

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 90 MINISCHOOL - BRONX, 1116 SHERIDAN AVENUE, New York, 10456 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: PRE-K CENTER @ 107-17 NORTHERN BOULEVARD - QUEENS, 107-17 NORTHERN BOULEVARD, New York, 11368 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 69 PORTABLE - QUEENS, 77-02 37TH AVENUE, New York, 11372 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-24 8:36 AM 2018-05-16

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: TERS PREP HS(OL REDIRECTION)-K, 226 BRISTOL STREET, New York, 11212 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: DIV. COMPUTER INFO-DATA CENTER-K, 2 METROTECH CENTER, New York, 11211 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: FORT HAMILTON HS MODULAR UNIT - K, 8301 SHORE ROAD, New York, 11209 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

NYC Department of Education

NYC Department of Education Asset: NEW UTRECHT AF - BROOKLYN, 1601 80 STREET, New York, 11214 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior 2017-10-31 4:06 PM 2018-06-13 10:51 AM AA : Architectural

More information

NYC Department of Education

NYC Department of Education Asset: COLUMBUS AF - BRONX, 925 ASTOR AVENUE, New York, 10469 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior 2017-10-31 9:21 AM 2017-11-29 8:45 AM AA : Architectural - Associate

More information

NYC Department of Education

NYC Department of Education Architectural Inspection Building Assessment Survey 2017-2018 Asset: LEHMAN AF - BRONX, 3000 EAST TREMONT AVENUE, New York, 10461 Inspection Id Inspection Type Time In Last Edited SA : Architectural -

More information

SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL)

SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL) SITE SYSTEMS: FANNIE MAE EXPECTED USEFUL LIFE TABLES (FMEUL) Basketball Courts 15 25 Built Improvements Playgrounds, Site Furniture, etc. 20 20 Catch Basin 40 40 Cold Water Lines 40 40 Compactors DHW Supply

More information

Schedule of Fees Schedule B

Schedule of Fees Schedule B Schedule of Fees Schedule B BUILDING DEPARTMENT 2. Building Permit* $65.00 for value or valuation up to $1,000. After $1,000 of value $8.00 per $1,000. After $1,000,000 of value $6 per $1,000 3. Demolition

More information

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE SCHEDULE OF S Penalty Fees. The fee for construction work performed before securing permit(s), where required, may be charged a fee of TWO TIMES THE COST OF THE PERMIT (S). Building Fee Schedule Residential

More information

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply:

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply: Planning/Building Department 115 Ramsdell Street Fircrest WA 98466 (253) 564-8902 COMMERCIAL PERMIT APPLICATION AND CHECKLIST Depending on the scope of your project, the following submittal requirements

More information

21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device

21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device DIVISION 23800 APPENDIX A ASHTABULA CAMPUS: 1. Air Handling Equipment And Appurtenances 2. Exhaust Fans 3. Fume Hood Exhaust Fans 4. Fume Hood monitoring devices and annual certification of face velocity

More information

Bill de Blasio, MAYOR. build safe live safe. Rick D. Chandler P.E., COMMISSIONER

Bill de Blasio, MAYOR. build safe live safe. Rick D. Chandler P.E., COMMISSIONER E LAA limited alteration application - FILING GUIDE information you need to know Bill de Blasio, MAYOR build safe live safe Rick D. Chandler P.E., COMMISSIONER FIXTURES COMMENTS efile Backflow Preventer

More information

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

4. Plumbing fixtures. a) The plumbing fixtures are from the original building. They are appear old and not to comply with ADA requirements.

4. Plumbing fixtures. a) The plumbing fixtures are from the original building. They are appear old and not to comply with ADA requirements. From: Jian Zhang Sheet: 1 of 8 Date of Visit: 12/7/10 Coach House: Plumbing Systems b) All original building storm piping shows significant signs of aging. b) All original building sanitary piping shows

More information

Massachusetts School Building Authority

Massachusetts School Building Authority Massachusetts School Building Authority School District Revere District Contact Paul Dakin TEL: (781) 286-8226 Name of School Submission Date 3/6/2007 The following Priorities have been included in the

More information

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance

Tighe&Bond. Groton Heights School Mechanical Evaluation. 1 Existing Conditions. 1.1 Water Service Entrance Groton Heights School Mechanical Evaluation TO: FROM: Amy Vaillancourt, Project Manager Harley Langford, Project Manger Jason Curtis, P.E. DATE: February 24, 2016; Revised May 31, 2016 On Monday, December

More information

Edward Jenner Elementary Academy of the Arts

Edward Jenner Elementary Academy of the Arts Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information