Electrical Essentials corrected calculation slides only

Size: px
Start display at page:

Download "Electrical Essentials corrected calculation slides only"

Transcription

1 Electrical Essentials corrected calculation slides only IAEI Southern Nevada Chapter/Educode 2015

2 Electrical Theory 1 Feeders and OCP 5 NEC Structure 2 Service and Grounding 6 Print Reading 3 Fault Current Calcs 7 Load Calculations 4 Plans Check/Inspections 8

3 Load Calculations Calculate each type of occupancy 1 Office Calculate loads for three office spaces 2 Residential Calculate loads for four apartments 3 Retail/ business Calculate loads for four businesses 4 House panel Calculate loads on house panel (common areas)

4 Office 1 Square Footage (general lighting) 2800 sq x 3.5 = 9800 VA x 1.25= 12,250 VA Receptacle Loads (larger of (K)(1) or (2)) 8 x 180 VA = 1440 VA < 2800 sq x 1 VA/sq = 2800 VA Equipment - Instant water heater = 1600 VA Heating and Cooling VA/ton = 8000 VA VA/ton = 6000 VA 25% of largest motor= 2000 VA Total load 32,650 VA Divide by Voltage 32,650 VA/208 V = 157 A Three Phase divisor 157 A/1.73 = 91 A

5 Office 2 Square Footage (general lighting) 1800 sq x 3.5 = 6300 VA x 1.25= 7875 VA Receptacle Loads (larger of (K)(1) or (2)) 7 x 180 VA = 1260 VA < 1800 sq x 1 VA/sq = 1800 VA Equipment - Instant water heater = 1600 VA Heating and Cooling VA/ton = 9000 VA 25% of largest motor= 2250 VA Total load 22,525 VA Divide by voltage 22,525/208 V = 108 A Three Phase divisor 108 A/1.73 = 63 A

6 Office 3 Square Footage (general lighting) 1400 sq x 3.5 = 4900 VA x 1.25= 6125 VA Receptacle Loads (larger of (K)(1) or (2)) 4 x 180 VA = 720 VA < 1400 sq x 1 VA/sq = 1400 VA Equipment - Instant water heater = 1600 VA Heating and Cooling VA/ton = 7000 VA 25% of largest motor= 1750 VA Total load 17,875 VA Divide by voltage 17875/208 V = 86 A Three Phase divisor 86/1.73 = 50 A

7 Load Calculations Calculate each type of occupancy 1 Office Calculate loads for three office spaces 2 Residential Calculate loads for four apartments 3 Retail/ business Calculate loads for four businesses 4 House panel Calculate loads on house panel (common areas)

8 Units 1 and 4 Square footage for general lighting 1400 sq x 3 VA = 4200 VA Kitchen small appliance loads 1500 x 2 = 3000 VA Laundry load 1500 VA Sum = 8700 VA Demand applied First 3000 VA + (.35 x 5700) VA = 4995 VA General lighting = 4995 VA

9 Units 1 and 4 continued Fixed in place appliances Dishwasher 1800 VA Disposal 600 VA Microwave 1200 VA Trash compactor 1500 VA Sum = 5100 VA Demand x.75 = 3825 VA The following are gas: water heater, dryer, heating and cooking A/C load 3.5 ton unit at 2000 VA/ton 7000 VA

10 Units 1 and 4 completion General Lighting = 4995 VA Appliances = 3825 VA Heating cooling = 7000 VA 25% of largest motor load = 1750 VA Sum = 17,570 VA 17,570 VA/208 V = 85 A Three phase divisor 85 A/1.73 = 49 A

11 Units 2 and 3 Square footage for general lighting 1550 sq x 3 VA = 4650 VA Kitchen small appliance loads 1500 VA x 2 = 3000 VA Laundry load 1500 VA Sum = 9150 VA Demand applied First 3000 VA + (.35 x 6150) VA = 5153 VA General lighting = 5153 VA

12 Units 2 and 3 continued Fixed in place appliances Dishwasher 1800 VA Disposal 600 VA Microwave 1200 VA Trash compactor 1500 VA Sum = 5100 VA Demand x.75 = 3825 VA The following are gas: water heater, dryer, heating and cooking A/C load 4 ton unit at 2000 VA/ton 8000 VA

13 Units 2 and 3 completion General Lighting = 5153 VA Appliances = 3825 VA Heating cooling = 8000 VA 25% of largest motor load = 2000 VA Sum = 18,978 VA 18,978 VA/208 = 91 A Three phase divisor 91/1.73 = 53 A

14 Load Calculations Calculate each type of occupancy 1 Office Calculate loads for three office spaces 2 Residential Calculate loads for four apartments 3 Retail/ business Calculate loads for four businesses 4 House panel Calculate loads on house panel (common areas)

15 Diner Loads General Lighting 1600 Sq x 2 VA = 3200 VA x 1.25 = 4000 VA Show Window 12 x 200 VA/ = 2400 VA Sign 1200 VA x 1.25 = 1500 VA General purpose receptacles 5 x 180 VA = 900 VA Total lighting and receptacles = 8800 VA Heating and cooking units are gas

16 Diner - Kitchen Equipment Dishwasher = V, 3 phase 22 A x 208 V = 4576 VA x 1.73 = 7916 VA Disposal V, 1 phase 12 A x 208 V = 2496 VA Refrigerator V 15 A x 120 V = 1800 VA Freezer V 18 A x 120 V = 2160 Microwave V 14 A x 120 V = 1680 VA Food Strip Heaters V 12 A x 120 V = 1440 VA x 2 = 2880 VA Total Equipment 18,932 VA x.65 = 12,306 VA

17 Diner - Mechanical Equipment 4 ton A/C unit 2000 VA/ton x 4 = 8000 VA Exhaust Fan 1/2 hp, 120 V at 9.8 A 9.8 A x 120 V = 1176 VA x 1.25 = 1470 VA Makeup air unit 1/2 hp, 120 V at 9.8 A 9.8 A x 120 V = 1176 VA x 1.25 = 1470 VA Plus 25% of largest motor load = 2000 V Total Mechanical equipment = 12,940 VA

18 Diner - Totals Lighting and Receptacles = 8800 VA Equipment = 12,306 VA Mechanical = 12,940 VA Total = 34,046 VA 34,046/208 V = 164 A 164 A/1.73 = 95 A

19 Coffee House General lighting 1500 Sq x 3 VA = 4500 VA x 1.25 = 5625 VA 4 receptacles 4 X 180 VA = 720 VA 24 track lighting at 150 VA/2 12 x 150 VA = 1800 VA x 1.25 = 2250 VA Sign 1200 VA x 1.25 = 1500 VA Show Window VA/ x 12 = 2400 VA Total lighting and receptacles = 12,495 VA Water heater and space heating is gas

20 Coffee House - Equipment 2 Espresso 25 A, 208 V, 3 phase 25 x 208 = 5200 x 1.73 = 8996 x 2 = 17,992 VA 2 Coffee 16 A, 208 V, 3 phase 16 A x 208 A = 3328 VA x 1.73 = 5757 VA x 2 = 11,514 VA 2 12 A, 120 V 12 A x 120 V = 1440 VA x 2 = 2880 VA Total equipment = 32,386 VA Mechanical Equipment 4 ton 2000 VA/ton 4 x 2000 = 8000 VA 25% or largest motor load = 2000 VA Total mechanical equipment = 10,000 VA

21 Coffee House - Totals Lighting and Receptacles = 12,495 VA Equipment = 32,386 VA Mechanical = 10,000 VA Total = 54,881 VA 54,881 VA/208 V = 264 A 264 A/1.73 = 153 A

22 Fitness Center General lighting 1500 Sq x 3 VA = 4500 VA x 1.25 = 5625 VA 5 receptacles 5 x 180 VA = 900 VA Sign 1200 VA x 1.25 = 1500 VA Show Window 12 x 200 VA/ 12 x 200 = 2400 VA

23 Fitness Center continued Instant water heater = 1600 VA 4 Ton A/C 4 x 2000 = 8000 VA 25% of largest motor load = 2000 VA Total = 22,025 VA 22,025/208 = 106 A 106/1.73 = 61 A

24 Jewelry Store General Lighting 1600 Sq x 3 VA = 4800 VA x 1.25 = 6000 VA 5 receptacles 5 x 180 VA = 900 VA 88 track lighting 88 /2 = 44 x 150 = 6600 x 1.25= 8250 VA Sign 1200 VA x 1.25 = 1500 VA Show Window x 200 VA = 2400 VA

25 Jewelry continued Instant water heater = 1600 VA A/C 4 ton 4 x 2000 = 8000 VA 25% of largest motor load = 2000 VA Total = 30,650 VA 30,650/208 = 147 A 147/1.73 = 85 A

26 Load Calculations Calculate each type of occupancy 1 Office Calculate loads for three office spaces 2 Residential Calculate loads for four apartments 3 Retail/ business Calculate loads for four businesses 4 House panel Calculate loads on house panel (common areas)

27 House Panel Lighting: 7 A3 Fixtures 7 x 90 VA = 630 VA 4 BB1 Fixtures 4 x 50 VA = 200 VA 2 F2 Fixtures 2 x 60 VA = 120 VA 2 AA1 Fixtures 2 x 60 VA = 120 VA Lighting Subtotal = 1070 x 1.25 = 1338 VA

28 House panel - Equipment and Receptacles Receptacles 6 6 x 180 VA = 1080 VA A/C unit 2 x 2000 = 4000 VA Elevator 5 hp 16.7 A x 208 = 3474 VA* 25% of largest load = 1000 VA Equipment and receptacle subtotal = 9554 VA Total house panel 1338 VA VA = 10,892 VA 10,892/208 = 52 A 53/1.73 = 30 A *This value is from the 3 Phase Table

29 Electrical Theory 1 Feeders and OCP 5 NEC Structure 2 Service and Grounding 6 Print Reading 3 Fault Current Calcs 7 Load Calculations 4 Plans Check/Inspections 8

30 What size Panels and Feeders are the minimum for each occupancy? According to our calculated loads what size could we use as a minimum? Office A Office 2-70 A Office 3-50 A Residence 1 & 4-50 A Residence 2 & 3-60 A Diner A Coffee House A Fitness - 70 A Jewelry - 90 A House - 30A

31 A good designer doesn t usually size the equipment for the minimum. This just isn t good for the customer, since we all know that, sooner or later, the tenant will want to add another piece of equipment or add load to the electrical system.

32 What size Panels and Feeders would be a good design for each occupancy? Office A Office A Office A Residence 1 & A Residence 2 & A Diner A Coffee House A Fitness A Jewelry A House - 100A

33 Using THHN/THHW cu wire, what size conductors would we use according to Table (B)(16) for the: 200 A Feeders = 3/0 AWG cu 150 A feeders = 1/0 AWG cu 100 A feeders = 3 AWG cu (however 3 AWG frequently isn t stocked so 2 AWG is used) What about (B)(7) for residential feeder sizing?

34 Dwelling Services and Feeders This language changed in the 2014 NEC (B)(7) 120/240-Volt, Single-Phase Dwelling Services and Feeders. For one-family dwellings and the individual dwelling units of two-family and multifamily dwellings, service and feeder conductors supplied by a single-phase, 120/240volt system shall be permitted be sized in accordance with (B)(7)(1) through (4).

35 Electrical Theory 1 Feeders and OCP 5 NEC Structure 2 Service and Grounding 6 Print Reading 3 Fault Current Calcs 7 Load Calculations 4 Plans Check/Inspections 8

36 Calculate the Service Size

37 Residential 5900 ft x 3 VA = 17,700 VA Small Appliance Circuits 4 x 3000 VA = 12,000 VA Laundry 4 x 1500 = 6000 Total Residential general lighting 35,700 VA First 3000 at 100% Remainder at 35% 3000 VA + 12,495 VA = 15,495 VA

38 Residential appliances (Look back at each unit total) Each unit had 4 items that totaled 5100 VA, therefore: 4 x 5100 VA = 20,400 VA Demand factor 20,400 x 75% = 15,300 VA Residential totals: 15, ,300 Total: 30,795 VA

39 Sums 1) Residential = 30,795 VA 2) 3) 4) 5)

40 Office general lighting and receptacles Receptacles are taken as the larger of 180 VA each or 1 VA per sq ; since 1 VA/sq is the larger value the combined lighting and receptacle load can be calculated as: 6000 sq x (3.5 VA + 1 VA) = 27,000 VA Continuous loads? Yes: 27,000 x 125% = 33,750 VA (At the engineer s discretion, the lighting could have been taken as continuous and the receptacles as non-continuous; often, you will see them calculated as one value.)

41 Sums 1) Residential = 30,795 VA 2) Office lighting and receptacles = 33,750 VA 3) 4) 5)

42 Diner/Coffee House General lighting (1600 Sq x 2) + (1500 Sq x 3) = 7700 VA Continuous: 7700 x 125% = 9625 VA Receptacles 9 x 180 VA = 1620 VA Diner Kitchen Equipment = 12,306 VA Coffee House Appliances = 32,386 Restaurant/Coffee House totals , ,386 = 55,937 VA

43 Sums 1) Residential = 30,795 VA 2) Office lighting and Receptacles = 33,750 VA 3) Diner/Coffee lighting and appliances = 55,937 VA 4) 5)

44 Fitness and Jewelry General lighting 3100 Sq x 3 VA = 9300 VA Continuous load 9300 x 125% = 11,625 VA Receptacles 10 x 180 = 1800 VA Track lighting 136 / 2 = 68 x 150 = 10,200 VA 10,200 VA x 125% = 12,750 VA

45 Fitness and Jewelry Continued Show windows 48 x 200 VA = 9600 VA House panel lighting and receptacles 1338 VA VA = 2418 VA Signs 4 x 1200 = 4800 x 1.25 = 6000 VA Store and misc lighting 11, = 44,193 VA

46 1) 2) 3) 4) 5) Sums Residential sub total = 30,795 VA Office lighting and Receptacles = 33,750 VA Diner/Coffee lighting and appliances = 55,937 VA Fitness/jewelry and misc lighting/recpt = 44,193 VA

47 Building Mechanical Equipment A/C equipment 1-2 ton unit 1-3 ton unit ton units 7-4 ton units ton unit Total tonnage = 48 tons 48 x 2000 = 96,000 VA Exhaust fan and makeup unit = 2940 VA 5 hp elevator = 3470 VA 25% of largest = 2250 VA Mechanical totals 96, = 104,660 VA

48 1) 2) 3) 4) 5) Sums - final Residential sub total = 30,795 VA Office lighting and Receptacles = 33,750 VA Restaurant lighting and appliances = 55,937 VA Stores and misc lighting = 44,193 VA Mechanical Equipment = 104,660 VA Building total = 269,335 VA Divide by Voltage 269,335 / 208 V = 1295 A three phase divisor 1295 / 1.73 = 748 A Therefore, an 800 amp Service is required.

49 Service Entrance Conductors (assuming customer owned service and using the same conductor types as used for the sub-feeders) 2 Parallel runs of 500 kcmil cu 380 A x 2 = 760 A

50 Sizing Equipment Grounds and Grounding Electrode Conducts Grounding Electrode Conductor to concrete encased electrode Table Total service conductor size = 1000 kcmil 2/0 AWG cu *Read (B) Size for concrete encased electrode 4 AWG cu

51 Metal Water Piping system bonding (A)(1) refers us to Table What size do we use for the Water Piping Bond conductor? 2/0 AWG cu Structural Steel? 2/0 AWG cu

52 Size the sub-feeder equipment grounding conductors Article Table A feeder would require 8 AWG cu conductor 150 A feeder would require 6 AWG cu conductor 200 A feeder would require 6 AWG cu conductor

53 Contact Us Christel Hunter Hunter Howard Herndon IAEI Southern Nevada Chapter

Dwelling unit feeder/service conductor calculations

Dwelling unit feeder/service conductor calculations Dwelling unit feeder/service conductor calculations http://ecmweb.com/code-basics/dwelling-unit-feederservice-conductor-calculations Whether they're for journeymen, master electricians, or contractors,

More information

2009 ELECTRICAL CODE REQUIREMENTS

2009 ELECTRICAL CODE REQUIREMENTS 2009 ELECTRICAL CODE REQUIREMENTS ANTRIM COUNTY BUILDING DEPARTMENT PO BOX 188 205 CAYUGA STREET BELLAIRE, MI 49615 (231) 533-8373 FAX (231) 533-6041 Inspection Request Line (231) 533-3510 Electrical requirements

More information

TABLE LIGHTING POWER DENSITIES FOR BUILDING EXTERIORS ASHRAE Uncovered Parking Areas. Building Grounds. Walkways 10 feet wide or greater

TABLE LIGHTING POWER DENSITIES FOR BUILDING EXTERIORS ASHRAE Uncovered Parking Areas. Building Grounds. Walkways 10 feet wide or greater TABLE 9.4.5 LIGHTING POWER DENSITIES FOR BUILDING EXTERIORS ASHRAE 90.1 Uncovered Parking Areas Parking Lots and drives Building Grounds Walkways less that 10 feet wide Walkways 10 feet wide or greater

More information

ll. Consistency Questions

ll. Consistency Questions Our Goal is FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT with us and that together we keep people and structures safe and buildings economically viable to serve the needs of our community. We strive

More information

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017

CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 CHAPTER 15 PART IV NATIONAL ELECTRICAL CODE, 2017 The City of Portsmouth adopts the State Building Code, which adopts by reference The National Electrical Code, 2017(NEC), as Chapter 15, Part IV, of the

More information

Kitchen south wall, living room north and south wall outlets 3. not working properly; no GFCI.

Kitchen south wall, living room north and south wall outlets 3. not working properly; no GFCI. UNIT # NOTES Receptacle in living room, south wall not working properly; 1 kitchen east, north, west wall receptacles have no power. Living room north wall outlet not working properly; kitchen 2 south

More information

ONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016)

ONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016) Cheboygan County Department of Building Safety 870 South Main Street P.O. Box 70 Cheboygan, Michigan 49721 TX: (231) 627-8813 FX: (231) 627-8454 www.cheboygancounty.net Service Entrance ONE- AND TWO-FAMILY

More information

Mechanical Systems Submittal Guide

Mechanical Systems Submittal Guide 5200 Dover Center Road 440-777-8000 North Olmsted, OH 44070 North-Olmsted.com Mechanical Systems Submittal Guide Residential Code of Ohio (RCO) n applicant is free to submit any mechanical systems description

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Is low voltage cable allowed to be run through drilled

More information

Proposed Amendments To The 2008 National Electrical Code

Proposed Amendments To The 2008 National Electrical Code Southern Nevada Building Officials c/o City of Henderson Building & Fire Safety Dept 240 Water Street Henderson, NV 89015 Phone: 702-267-3611 Fax: 702-267-3605 Email: Michael.Bouse@ cityofhenderson.com

More information

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch

More information

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod Journeyman and Master Common Exam 2 1 The grounding terminal of a grounding-type receptacle installed in a metal box shall be? A. Connected to the equipment ground B. Bonded to the box C. Connected to

More information

Graded Project. National Electrical Code

Graded Project. National Electrical Code Graded Project National Electrical Code National Electrical Code INTRODUCTION This next portion of your program is a project-based assignment designed for you to demonstrate your understanding of the

More information

NEC Study Guide CORRECT: C NEC (A)(1)

NEC Study Guide CORRECT: C NEC (A)(1) 1 According to the NEC, the maximum distance from the point of entrance to the building that the water pipe may be used as a grounding electrode interconnect is: A. 3' B. 4' C. 5' D. 6' CORRECT: C NEC

More information

WIRING AND PROTECTION

WIRING AND PROTECTION 5997ch02.qxd_mg_cc 4/6/05 12:42 PM Page 5 2 WIRING AND PROTECTION (Excerpts from Chapter 2) 210.1 Scope ARTICLE 210 BRANCH CIRCUITS I. General Provisions Article 210 applies to all branch circuits except

More information

Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004

Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004 Rocky Mountain Chapter IAEI Annual Meeting Northglenn, CO March 18-19, 2004 1. A 2 PVC conduit was installed in the ground prior to setting a factory manufactured home on the foundation. The required service

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

This fee schedule is for Building Inspection Fees only.

This fee schedule is for Building Inspection Fees only. Building Permit Fees: Minimum Fee, all permits Residential, one- and two-family including additions and.35/total sq. ft. attached garages Residences, Apartments, Three Family and Over, Row.35/total sq.

More information

Electrical Tech Note 107

Electrical Tech Note 107 Electrical Tech Note 107 Biosystems & Agricultural Engineering Department Michigan State University Understanding the Construction Code Rules, Part 8 1 Based on the 2014 NEC and the 2015 MRC The State

More information

Building & Safety PERMIT APPLICATION

Building & Safety PERMIT APPLICATION (661) 255-4935 PERMIT APPLICATION 1 Project Location Please complete all applicable fields. Optional fields are surrounded by dashes --------. Address: Assessor s Parcel No. (APN): Street Number Street

More information

Instructor: L. Keith Lofland

Instructor: L. Keith Lofland One and Two Family Dwelling Electrical Systems 2014 NEC AFCIs, GFCIs, and Other Dwelling Unit Requirements Training Presentation by: International Association of Electrical Inspectors Instructor: L. Keith

More information

Residential Wiring According to 2011 NEC (Homestudy)

Residential Wiring According to 2011 NEC (Homestudy) Residential Wiring According to 2011 NEC (Homestudy) Utah Electrical License This course will cover the requirements in the 2011 NEC for installing electrical systems in dwelling units. Code sections for

More information

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE 1. BUILDING FEES: 1 AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE ESTABLISHMENT OF FEES PURSUANT TO N.J.A.C.

More information

Residential Wiring (2014 NEC) (Homestudy)

Residential Wiring (2014 NEC) (Homestudy) Residential Wiring (2014 NEC) (Homestudy) Oregon Electrical License This course will cover the requirements in the 2014 NEC for installing electrical systems in dwelling units. Code sections for residential

More information

Residential Wiring (2017 NEC) (Homestudy)

Residential Wiring (2017 NEC) (Homestudy) Residential Wiring (2017 NEC) (Homestudy) Idaho Electrical License This course will cover the requirements in the 2017 NEC for installing electrical systems in dwelling units. Code sections for residential

More information

ELECTRICAL INSTALLATION PERMIT HOMEOWNER

ELECTRICAL INSTALLATION PERMIT HOMEOWNER www.technicalsafetybc.ca contact@technicalsafetybc.ca Toll Free: 1 866 566 7233 ELECTRICAL INSTALLATION PERMIT HOMEOWNER Payment Card Industry Data Security Standards prevent the use of credit card information

More information

SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE

SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE SOUTHERN NEVADA PROPOSED AMENDMENTS TO THE 2011 NATIONAL ELECTRICAL CODE ELECTRICAL CODE COMMITTEE SEPTEMBER 12, 2012 PREFACE This document was developed by the Southern Nevada Building Officials Electrical

More information

Bulletin An application for inspection not required Rule 2-005

Bulletin An application for inspection not required Rule 2-005 Bulletin 2-3-16 An application for inspection not required Rule 2-005 Scope Issued May 2016 Supersedes Bulletin 2-3-15 (1) Rule 2-005 - An application for inspection not required (Basic exemption) (a)

More information

THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO TELEPHONE: (440) FAX: (440) Building Department

THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO TELEPHONE: (440) FAX: (440) Building Department THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO 44039 TELEPHONE: (440) 353-0822 FAX: (440) 353-0823 Building Department INSTRUCTIONS FOR DECKS REQUIREMENTS FOR PERMIT: Completed

More information

Cable Limiters Increase System Reliability Decrease Downtime

Cable Limiters Increase System Reliability Decrease Downtime Limiters Increase System Reliability Decrease Downtime Increase system reliability and versatility with Ferraz Shawmut Limiters. Limiters are designed for the protection of low voltage distribution networks,

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2016-22 An Ordinance Changing/Increasing/Establishing Fees for Liquor License Publications, Direct Sellers Permits, and certain Building, Electrical, Heating, Ventilating, Air Conditioning,

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

P-16 ENGINEER NO. DATE DESCRIPTION 1 01/19/2016 FOR CONSTRUCTION 2 03/11/2016 REVISION # 2 DRAWN BY: CHECKED BY: DATE: SCALE: DRAWING NUMBER

P-16 ENGINEER NO. DATE DESCRIPTION 1 01/19/2016 FOR CONSTRUCTION 2 03/11/2016 REVISION # 2 DRAWN BY: CHECKED BY: DATE: SCALE: DRAWING NUMBER PRESSIONAL P-16 PRESSIONAL PRESSIONAL PRESSIONAL 1 ONE LINE DIAGRAM 3 EMEGENCY LIGHTING SCHEME 2 FEEDER SCHEDULE PRESSIONAL PRESSIONAL PRESSIONAL PRESSIONAL LOCAL SINGLE POLE SWITCH 3-WAY SWITCH 3-WAY

More information

Commercial, Manufacturing and Industrial: Office Areas.18/total sq. ft. Agricultural buildings, detached garages, and accessory.15/total sq. ft.

Commercial, Manufacturing and Industrial: Office Areas.18/total sq. ft. Agricultural buildings, detached garages, and accessory.15/total sq. ft. Building Permit Fees: Minimum Fee, all permits Residential, one- and two-family including additions and.18/total sq. ft. attached garages Residences, Apartments, Three Family and Over, Row.18/total sq.

More information

Inspection Report 123 My Street Midland, GA

Inspection Report 123 My Street Midland, GA Buying, Selling or Building Your Home Inspection Company ROFESSIONAL INSPECTION SERVICES, LLC P.O. Box 9774 Columbus, GA 31908 706-565-0333 1-866-298-4251 Inspection Report 123 My Street Midland, GA This

More information

2017 NEC Presented by: Russ LeBlanc

2017 NEC Presented by: Russ LeBlanc 2017 NEC Presented by: Russ LeBlanc 1. 90.2(A)-installation and removal 2. 90.3-code layout 3. 100-readily accessible 4. 100-field evaluation body (FEB) 5. 100-field labeled 6. 100-receptacle 7. 100-structure

More information

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS

2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY REMODEL REQUIREMENTS City of Redwood City Community Development Department Building and Inspection Department 1017 Middlefield Road Redwood City, CA 94063 Phone (650) 780-7350 2016 CALIFORNIA CODES KITCHEN, BATH & LAUNDRY

More information

CITY OF BARTOW (COB)

CITY OF BARTOW (COB) CITY OF BARTOW (COB) WATT CHOPPER knows how to take a bite out of your electric bill and save both energy and money... 5 Quick Steps for you to Conserve Energy Today... 1. CHANGE A LIGHT Replace three

More information

AFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults?

AFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults? RECEPTACLEFAQs AFCI 1 What is an arc fault? UL provides a definition for an arc fault in UL 1699 (Standard for Safety Arc Fault Circuit Interrupters). It is an unintentional arcing condition in a circuit.

More information

Town of Cicero Local Code Amendments

Town of Cicero Local Code Amendments Town of Cicero Local Code Amendments 2009 International Residential Code Local Amendments: DELETE Table R302.1 (Exterior Walls), see Attachment A. DELETE Exception for Subsection R313.2 (One and Two-Family

More information

District 1. 1 Tony Tadysak Craig Mulder

District 1. 1 Tony Tadysak Craig Mulder STATE OF WISCONSIN Department of Safety and Professional Services 1400 E Washington Ave. Madison WI 53703 Web: dsps.wi.gov Governor Scott Walker Secretary Dave Ross Electrical Program Web: Electrical Program

More information

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016

IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS. June 17th, 2016 IMPORTANT NOTICE BUILDERS AND CONTRACTORS WORKING IN NORTH RICHLAND HILLS, TEXAS June 17th, 2016 RE: City Council Adopts 2014 National Electrical Code with Pool Alarm Requirements On April 25th, 2016 the

More information

CONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA

CONTINUING EDUCATION FOR OREGON ELECTRICIANS. AMERICAN ELECTRICAL INSTITUTE PO Box Spokane, WA American Electrical Institute 2014 PART 2 83 CONTINUING EDUCATION FOR OREGON ELECTRICIANS AMERICAN ELECTRICAL INSTITUTE PO Box 31131 Spokane, WA 99223 www.aeitraining.com 84 PART 3 American Electrical

More information

CHAPTER 14 ELECTRICAL CODE

CHAPTER 14 ELECTRICAL CODE CHAPTER 14 ELECTRICAL CODE (Entire Chapter Rep.& Recr. #98-21) 14.01 -- Definitions 14.02 -- Electrical Licenses Required 14.03 -- General Restrictions (1) Electrical Contractor's License (2) Restricted

More information

ORDINANCE NO. BE IT ORDAINED, by the Township Committee of the Township of Neptune, County of Monmouth, State of New Jersey, as follows:

ORDINANCE NO. BE IT ORDAINED, by the Township Committee of the Township of Neptune, County of Monmouth, State of New Jersey, as follows: ORDINANCE NO. AN ORDINANCE TO AMEND VOLUME I, CHAPTER XI, SECTION 11-1.3 OF THE CODE OF THE TOWNSHIP OF NEPTUNE BY FURTHER AMENDING THE CONSTRUCTION FEE SCHEDULE IN ACCORDANCE WITH THE UNIFORM CONSTRUCTION

More information

THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO TELEPHONE: (440) FAX: (440) Building Department

THE CITY OF NORTH RIDGEVILLE 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO TELEPHONE: (440) FAX: (440) Building Department 7307 AVON BELDEN ROAD, NORTH RIDGEVILLE, OHIO 44039 TELEPHONE: (440) 353-0822 FAX: (440) 353-0823 INSTRUCTIONS FOR SWIMMING POOLS REQUIREMENTS FOR PERMIT: Completed application form Plot plan showing lot

More information

Electrical Systems. Electrical Plans. Electrical Plans. Essential to ensure. National Electrical Code (NES) Consider electrical needs.

Electrical Systems. Electrical Plans. Electrical Plans. Essential to ensure. National Electrical Code (NES) Consider electrical needs. Electrical Systems Electrical Plans Essential to ensure Proper wiring National Electrical Code (NES) Electrical Plans Consider electrical needs Office equipment Lighting E t t i t t Entertainment systems

More information

2011 and 2014 National Electrical Code Changes Residential Only

2011 and 2014 National Electrical Code Changes Residential Only 2011 and 2014 National Electrical Code Changes Residential Only Sponsored By: and.net Instructor: Fritz Gunther, Chief Electrical Inspector 585-436-4460 www.nyeia.com NEW YORK ELECTRICAL INSPECTION AGENCY

More information

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators GPS 140 NEC Requirements for Generators WHAT YOU WILL LEARN NEC requirements for on-site power generation. Recent events have created increased interest in standby power This module organizes NEC requirements

More information

Comprehensive Inspection Agency (CIA) RESIDENTIAL & COMMERCIAL FEE SCHEDULE

Comprehensive Inspection Agency (CIA) RESIDENTIAL & COMMERCIAL FEE SCHEDULE (CIA) RESIDENTIAL & COMMERCIAL FEE SCHEDULE Phone: 570-573-28251 Fax: 570-385-3010 Page 1 of 7 Phone: 570-573-2825 CIA Fax: 570-385-3010 RESIDENTIAL FEES BUILDING / MISCELLANEOUS Plan Review $ 0 New Construction,

More information

Axiom Property Inspections

Axiom Property Inspections Cover Page Axiom Property Inspections Property Inspection Report 868 Wally Avenue, Henderson NV, 89178 Inspection prepared for: John Doe Agent: David Lawson - Axiom Inspection Date: 8/12/2010 Time: 2:30

More information

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013 Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013 1. Is a standard wire-nut approved for a wet location as in an outside j-box? Is there a listed

More information

Spring Test 6 due 04/26/2013

Spring Test 6 due 04/26/2013 Spring Test 6 due 04/26/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. The article that covers TV wiring installations in residences

More information

$ Each additional variance per petition. $ All Other Zoning Districts: One variance per petition

$ Each additional variance per petition. $ All Other Zoning Districts: One variance per petition 2015 SCHEDULE COMMUNITY DEVELOPMENT DEPT. ENGINEERING PLAN REVIEW Single Family New Construction All Other Plan Reviews Minimum Engineering Fee Planned Unit Development - PUD: Step #1: Step #2: See Site

More information

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE

SCHEDULE OF FEES. Penalty Fees. Building Fee Schedule FEE SCHEDULE OF S Penalty Fees. The fee for construction work performed before securing permit(s), where required, may be charged a fee of TWO TIMES THE COST OF THE PERMIT (S). Building Fee Schedule Residential

More information

LIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES

LIGHT LEVEL REQUIREMENTS MINIMUM ACCEPTABLE FOOT CANDLES LIGHT LEVEL REQUIREMENTS LOCATION Classrooms and instrumental areas- Study Halls, Lecture Rooms, Art Rooms, Offices, Libraries, Conference Rooms, Work Rooms, Shops, Laboratories and Secondary School Cafeterias.

More information

Craig A. Rush Presents Edinborough Circle, Perrysburg

Craig A. Rush Presents Edinborough Circle, Perrysburg Craig A. Rush Presents 26029 Edinborough Circle, Perrysburg O P E N F L O O R P L A N C A R R I W O N G T O N O D S Gorgeous house on park-like setting in Carrington Woods! Two story foyer. Living room,

More information

Schedule of Approved Fees

Schedule of Approved Fees Schedule of BUILDINGMISCELLANEOUS Inspection not otherwise covered by a fee and is regulated by LA County Oridnance OCCUPANCY INSPECTIONS Group R or Group M Other Groups other than R or M (Floor Area)

More information

SDEC 2017 Questions, Group 1

SDEC 2017 Questions, Group 1 SDEC 2017 Questions, Group 1 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing? Answer: NEC 410.36(B)

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

Oregon Non-Residential Building Energy Code

Oregon Non-Residential Building Energy Code Oregon Non-Residential Building Energy Code Interior Connected Lighting Power Requirements The requirements for interior lighting power are one of the most important sections of the Oregon Energy Code.

More information

GRILLE, REGISTER AND DIFFUSER SCHEDULE

GRILLE, REGISTER AND DIFFUSER SCHEDULE ROOFTOP UNIT SCHEDULE (NATURAL GAS HEAT) MARK MANUFACTURER MODEL SUPPLY FAN COOLING COIL HEAT EXCHANGER MIN. MIN. MCA MOCP V/PH WEIGHT NOTES FAN CFM MIN ESP REFR. TH SH EAT LAT MIN. OUTPUT MIN. EFF. NOM.

More information

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015

NEC Requirements for Standby Power Systems. New England Building Officials Education Association Annual Conference October 5, 2015 NEC Requirements for Standby Power Systems New England Building Officials Education Association Annual Conference October 5, 2015 Emergency & Standby Power Systems Alternative power sources are utilized

More information

Charter Township of Flushing Construction Permit Fee Schedule.Construction and Development Services Department

Charter Township of Flushing Construction Permit Fee Schedule.Construction and Development Services Department Charter Township of Flushing Construction Permit Fee Schedule.Construction and Development Services Department 1. CONSTRUCTION PERMIT FEES: A. General: Fee basis/value of construction shall be determined

More information

CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST

CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST CITY OF LOS ANGELES LARUCP ELECTRICAL PLAN CHECK LIST Plan Check No. Plan Check Expiration Date Job Address: Square Footage Use Zone Fire Zone Occ. Group Type of Construction No. of Stories Applicant Phone

More information

BUILDING PERMIT FEES

BUILDING PERMIT FEES CITY OF MOULTRIE SCHEDULE OF PERMIT FEES BUILDING PERMIT FEES Pre-Inspection/Missed Inspection / Re-Inspection...$45.00 Customer Service Inspection...$20.00 Residential Construction Calculation Method

More information

City of Calabasas Building and Safety Division Fee Schedule

City of Calabasas Building and Safety Division Fee Schedule City of Calabasas Building and Safety Division Fee Schedule Resolution History: [91-52 September 25, 1991], [94-282 July 7, 1994], [2009-1171 January 14, 2009], [2011-1304 August24, 2011] [2014-1430 August

More information

CODE PANEL QUESTIONS

CODE PANEL QUESTIONS NORTH CAROLINA ELECTRICAL INSTITUTE 89 th ANNUAL MEETING APRIL 3-4, 2018 HILTON NORTH RALEIGH RALEIGH, NORTH CAROLINA CODE PANEL QUESTIONS Opinions of the Code Panelist are NOT interpretations issued by

More information

For more information on the MARR program or any questions on the product list, please refer to or contact MARR at

For more information on the MARR program or any questions on the product list, please refer to   or contact MARR at Major Appliance Recycling Roundtable Updated Major Appliance Recycling Roundtable - and s Background: The following document provides a detailed list of products and relevant definitions captured by the

More information

Inspector FX Field Forms

Inspector FX Field Forms Inspector FX Field Forms PROPERTY / CLIENT Customer File # Customer Contact Address City, St, Zip Phone Fax Email Inspection location Send report to Phone Neightborhood Main entry faces East North South

More information

IEC and NCCER Mapping for Year 1

IEC and NCCER Mapping for Year 1 Craft: 26102-14 Safety IEC and NCCER Mapping for Year 1 Perform a visual inspection on various types of ladders 102.4 STATE GENERAL SAFETY CONSIDERATIONS IN ELECTRICAL INSTALLATIONS (LADDER SAFETY, SLECTION

More information

Second Revision No. 321 NFPA [ Detail ] Submitter Information Verification. Committee Statement. Make the following changes to 210.

Second Revision No. 321 NFPA [ Detail ] Submitter Information Verification. Committee Statement. Make the following changes to 210. Second Revision No. 321 NFPA 70 2015 [ Detail ] Make the following changes to 210.8(B): (B) Other Than Dwelling Units. All 125 volt, single phase, 15 and 20 ampere receptacles phase receptacles rated 150

More information

SW District 1. 1 Tony Tadysak Craig Mulder

SW District 1. 1 Tony Tadysak Craig Mulder STATE OF WISCONSIN Department of Safety and Professional Services 1400 E Washington Ave. Madison WI 53703 Web: dsps.wi.gov Governor Scott Walker Secretary Dave Ross Electrical Program Web: Electrical Program

More information

NEC CODE QUESTIONS and ANSWERS Wisconsin Chapter IAEI Green Lake, Wisconsin May 16-18, 2012

NEC CODE QUESTIONS and ANSWERS Wisconsin Chapter IAEI Green Lake, Wisconsin May 16-18, 2012 NEC CODE QUESTIONS and ANSWERS Wisconsin Chapter IAEI Green Lake, Wisconsin May 16-18, 2012 1. Can we install 120 Volt conductors in the same space with 277 Volt conductors? If the answer is yes, are there

More information

Design Architect s/applicant s Certification Of Threshold Criteria

Design Architect s/applicant s Certification Of Threshold Criteria Design Architect s/applicant s Certification Of Threshold Criteria The Agency has requested certain certifications from the architect and applicant in connection with the submission of an application.

More information

FOOD ESTABLISHMENT LICENSE APPLICATION Fee Required with Submission of Application

FOOD ESTABLISHMENT LICENSE APPLICATION Fee Required with Submission of Application Serving: Grant Mercer Morton Oliver Sioux Counties www.custerhealth.com 403 Burlington St SE Mandan, North Dakota 58554 701-667-3370 Fax: 701-667-3371 1-888-667-3370 FOOD ESTABLISHMENT LICENSE APPLICATION

More information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017 It has come to the attention of the electrical authorities having jurisdiction (AHJs) at the DOE sites there is inconsistency

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

Construction Codes Advisory Council

Construction Codes Advisory Council Construction Codes Advisory Council An overview of the National Electrical Code (NEC) adoption process This is where it all begins.. Minnesota Statute Chapter 326B establishes the State Building Code Minnesota

More information

Estimate Form for Kitchen Design and Installation

Estimate Form for Kitchen Design and Installation Form for Kitchen Design and Installation Name: Home Address: City: State: Phone (Home): Phone (Office): Phone (Office): Phone (Office): Phone (Jobsite): Jobsite Address: City: State: By: Hereafter called

More information

GE Industrial Solutions. Residential Electronic Circuit Interrupters

GE Industrial Solutions. Residential Electronic Circuit Interrupters GE Industrial Solutions Residential Electronic Circuit Interrupters Dual Function Circuit Interrupter (DFCI) Provides ground fault and arc fault circuit protection in one unit The 2014 National Electric

More information

Bay Wide Commercial and Home Inspection Thackeray Avenue/ Mail address Hayward, Calif TH AVENUE SAN LEANDRO, CALIFORNIA

Bay Wide Commercial and Home Inspection Thackeray Avenue/ Mail address Hayward, Calif TH AVENUE SAN LEANDRO, CALIFORNIA 27966 Thackeray Avenue/ Mail address Hayward, Calif. 94544 2011 150TH AVENUE SAN LEANDRO, CALIFORNIA 21:12 August 07, 2015 Page 1 of 11 Table of Contents Definitions 2 General Information 2 Lots and Grounds

More information

Corbin Building. Technical Assignment 2. Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth

Corbin Building. Technical Assignment 2. Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth Corbin Building Technical Assignment 2 Matthew Trethaway Lighting/ Electrical AE 481W 10/26/2011 Advisor: Ted Dannerth 10/26/2011 Technical Report II 1 Executive Summary The following report is an overview

More information

APPENDIX G THE LOAD ALLOCATED TO EACH LOAD CATEGORY CLOAD MODELS

APPENDIX G THE LOAD ALLOCATED TO EACH LOAD CATEGORY CLOAD MODELS APPENDIX G THE LOAD ALLOCATED TO EACH LOAD CATEGORY CLOAD MODELS This Appendix obtains the percentage load allocated to each load category CLOAD models. To obtain these percentages the load class mix is

More information

EasyWire Between Joists Installation Instructions

EasyWire Between Joists Installation Instructions EasyWire Between Joists Installation Instructions General Our product, EasyWire, is intended to bring up the floor temperature to a comfortable condition (no cold feet). Read instructions carefully I.

More information

8. Multi-Family Residential Buildings

8. Multi-Family Residential Buildings Mu lti-f a mily Re s id e n tia lbu ild in g s 2016 Electric Service Requirements, 3rd Edition Section 8 Section 8 Multi-Family Residential Buildings Directory Page 8.1 General 61 8.2 Maximum Available

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2017-08-031 AN ORDINANCE OF THE CITY OF LANCASTER, TEXAS, REPEALING THE NATIONAL ELECTRICAL CODE 2014 EDITION IN ITS ENTIRETY AND REPLACING IT WITH THE ADOPTION OF THE NATIONAL ELECTRICAL

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 17 From: Kimberly Shea, Project Administrator

More information

2009 WESTERN SECTION CODE PANEL QUESTIONS

2009 WESTERN SECTION CODE PANEL QUESTIONS 2009 WESTERN SECTION CODE PANEL QUESTIONS 1. The local inspector red-tagged the temporary wiring for a new store of type III construction because he said Romex wasn t allowed to be run in the open according

More information

McKinney Inspection Company

McKinney Inspection Company McKinney Inspection Company Copyright 2013 New Image Software, Inc. All rights reserved. Rev 7/1/2013 Copyright 2013 New Image Software, Inc. All rights reserved General Terminology McKinney Inspection

More information

RESIDENTIAL OVER. 4. Would it be permissible to hard- wire the dishwasher in question 3? If so, under what conditions?

RESIDENTIAL OVER. 4. Would it be permissible to hard- wire the dishwasher in question 3? If so, under what conditions? WELCOME TO THE EASTERN SECTION CODE BREAKFAST CODE BREAKFAST QUESTIONS FOR THE EASTERN SECTION ANNUAL MEETING 93 rd ANNUAL EASTERN SECTION MEETING, KING OF PRUSSIA, PA RESIDENTIAL ALL QUESTIONS BASED ON

More information

INNOVEL DELIVERY & INSTALLATION SERVICES COSTCO GUIDELINES

INNOVEL DELIVERY & INSTALLATION SERVICES COSTCO GUIDELINES INNOVEL DELIVERY & INSTALLATION SERVICES COSTCO GUIDELINES 1 INNOVEL DELIVERY & INSTALLATION GUIDELINES THANK YOU FOR CHOOSING INNOVEL! We want to ensure a smooth delivery and installation of your appliance.

More information

Lovely 2 Bedroom Super Close to Airport and UMED Districts! Great Reviews!

Lovely 2 Bedroom Super Close to Airport and UMED Districts! Great Reviews! Lovely 2 Bedroom Super Close to Airport and UMED Districts! Great Reviews! Summary This apartment is warm and welcoming!you will find a well stocked kitchen to make cooking a breeze, a very large living

More information

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Suppression Systems; and Chapter 34-National Electric

More information

Electrical Program. Electrical Laws & Rules. Electrical RCW WAC B. Permits Inspections Access Description Directions Comments.

Electrical Program. Electrical Laws & Rules. Electrical RCW WAC B. Permits Inspections Access Description Directions Comments. Electrical Laws & Rules Licensing Electrical Work Scope Administrator Duties Certification Supervision RCW 19.28 WAC 296-46B Permits Inspections Access Description Directions Comments Electrical Program

More information

FOOD ESTABLISHMENT PLAN REVIEW APPLICATION. Ogle County Health Department 907 West Pines Road Oregon, Illinois

FOOD ESTABLISHMENT PLAN REVIEW APPLICATION. Ogle County Health Department 907 West Pines Road Oregon, Illinois FOOD ESTABLISHMENT PLAN REVIEW APPLICATION Ogle County Health Department 907 West Pines Road Oregon, Illinois 61061 815-732-7330 1 OGLE COUNTY HEALTH DEPARTMENT FOOD ESTABLISHMENT PLAN REVIEW APPLICATION

More information

Appliance Solutions for Property Managers

Appliance Solutions for Property Managers Appliance Solutions for Property Managers 2002 Merchandising The training guide to selling appliance replacements from The Home Depot. Introducing Introducing ARDD Program Appliances specially designed

More information

A WORD ABOUT PORTABLE ELECTRIC GENERATORS

A WORD ABOUT PORTABLE ELECTRIC GENERATORS A WORD ABOUT PORTABLE ELECTRIC GENERATORS Portable fuel-burning generators may be used to supply electricity for the operation of small electrical appliances in the event of a power outage. The most common

More information

INSTALLATION AND OPERATING INSTRUCTIONS. For Reliance Controls Emergency Power Transfer Switch Kit Model Number 30216BRK

INSTALLATION AND OPERATING INSTRUCTIONS. For Reliance Controls Emergency Power Transfer Switch Kit Model Number 30216BRK INSTALLATION AND OPERATING INSTRUCTIONS For Reliance Controls Emergency Power Transfer Switch Kit Model Number 30216BRK Congratulations on your purchase of the Reliance Controls Generator Power Transfer

More information

Overview of Significant 2017 NEC Changes

Overview of Significant 2017 NEC Changes Overview of Significant 2017 NEC Changes National Fire Protection Association. All rights reserved. Five New NEC Articles Article 426 Fixed Resistance and Electrode Industrial Heating Equipment Article

More information