Design guide for DVM Chiller. Design guide for DVM Chiller

Size: px
Start display at page:

Download "Design guide for DVM Chiller. Design guide for DVM Chiller"

Transcription

1 Design guide for DVM Chiller 1

2 Modification history Date Ver. Modifier Modified detail 30 May Junho Lim - New 23 Mar F Weddington - North American Market 27 Mar J McCloskey - Table added, minor changes

3 Contents 1. Introduction Air-cooled chiller vs Water-cooled chiller What is DVM Chiller? Basic configurations Pump system Chiller arrangement Water piping Water piping elements Water pipes Pumps Expansion tank (vessel) Maintenance Water pipe installation Water quality Freeze prevention of water pipe Chilled water management External contact connection A-Terminal block B-Terminal block C-Terminal block Check before use Module or group operation Operation pattern for modules Product configuration DVM Chiller configuration Module controller

4 ` ` ` Design guide for DVM Chiller 1. Introduction Please note that this document is for reference only and is not an actual design manual. In practice, construction and plumbing methods may vary according to the project requirements and local code. To complete design and installation of the system, please consult your local engineer. 1-1 Air-cooled chiller vs Water-cooled chiller An air-cooled chiller has a condenser that uses air for heat transfer. Air-cooled chillers are preferred for small or medium installations but recently the quality improvement in their structure allows the use in modular setups for large installations as well. An air-cooled chiller is preferred especially in cases where there is not enough water or the water is very expensive. Water-cooled chillers have a water cooled condenser connected with a cooling tower and are usually preferred for medium and large installations where there is a sufficient amount of water. In addition, they are also preferred in cases where there is a demand for constant operation of the system, independently of the ambient temperature (industrial air conditioning, air conditioning of digital systems etc.), because the capacity of the water-cooled chillers are less affected by the ambient temperature conditions. ( Air-cooled chiller ) ( Water-cooled chiller ) Condenser Water Pump Cooling Tower Cooling Tower Circuit Chiller Chilled Water Circuit Chilled Water Pump AHU Chilled Water Circuit Chiller AHU Chilled Water Pump 4

5 1. Introduction 1-2 What is DVM Chiller? DVM Chiller is a air-cooled chiller. It is a machine that exchanges heat from water via vapor-compression. DVM Chiller makes chilled water or hot water and can be used in various applications such as commercial, industrial, and institutional facilities. DVM Chiller uses Inverter driven scroll type compressors manufactured by SAMSUNG. The efficiency of the DVM Chiller is higher than conventional water cooled chiller. Also, DVM Chiller can be installed and configured into a module system for large installations. On the water side of the system, the heat source (water) is supplied to DVM Chiller units throughout the building via the water circuit, which incorporates ancillary elements such as heat exchangers, pumps, valves, strainers, expansion tanks, air vents and water treatment equipment etc. Work scope Design - Outdoor unit (Chiller) : Samsung - Water plumbing including pump : MEP company (Mechanical Engineer) 5

6 Approved Modular Combinations Nominal Tons Standard AG010KSVA*H/AA AG015KSVA*H/AA Recommended Pipe Diameter " " " High Efficiency AG010KSVA*H/AA AG015KSVA*H/AA Recommended Pipe Diameter /2" 3 2 1/2" /2" " " " 6 3" /2" /2" " " 9 4" " " " " 12 4" " " " " 15 5" " " " " " " " 6

7 2. Basic configurations 2-1 Pump system 3 common chilled water system configuration 1) Constant primary flow 2) Primary secondary flow 3) Variable primary flow Constant primary flow Primary secondary flow Variable primary flow Multiple chiller and Multiple chiller and -Small plants multiple loads where operator multiple loads with high Application (Few coils serving is not existed loads like data center similar loads) (Many coils serving similar (Many coils serving similar loads or dissimilar loads) loads or dissimilar loads) Pump energy Pump energy is wasted 50~60% less than constant primary flow 60~75% less than constant primary flow S y s t e m Primary Fixed speed pump Fixed speed pump Variable speed pump Secondary - Variable speed pump - Control valve 3Way valve 2Way valve 2Way valve Remark Simple Common Control complex 7

8 2. Basic configurations 2-1 Pump system 1) Constant primary flow The chilled water pumps are constant speed. For constant flow rate, a 3way valve is placed on the outlet of each coil. A 3way valve is maintaining the set point of the air leaving temperature. T 8

9 2. Basic configurations 2-1 Pump system 2) Primary secondary flow A decoupler pipe separates the two loops hydronically. Primary circuit must contain minimum water volume as stated in the installation guide. T ΔP 9

10 2. Basic configurations 2-1 Pump system 2) Primary secondary flow Decoupler sizing and location Decoupler pipe size should cover the flow rate of the largest primary pump. The pressure drop less than 1.5 ft. The higher the pressure drop, the more the pumps tend to act like they are in series instead of independent loops. Proper decoupler size will prevent this from occuring. Buffer tank Generally buffer tank is recommended to ensure proper water volume to chillers. Because if secondary pump stops and primary pump continues running, then water volume of the system with a decoupler may be too low. Chiller requires minimum flow rates. 10

11 2. Basic configurations 2-1 Pump system 3) Variable primary flow Variable primary flow design uses variable pump instead of constant speed pump. A bypass valve ensures minimum flow rates. The valve should be automatically controlled by using flow meter in primary circuit or secondary P. T ΔP 11

12 2. Basic configurations 2-2 Chiller arrangement 1) Parallel chillers configuration Parallel configuration is more common than series configuration. Parallel configuration use usually same capacity and type of chiller. ` ` ` When only one chiller is operating, supply chilled water temperature rises. Operating chiller can be reset to produce target water temperature. (Increasing chiller energy consumption) * To avoid this problem, primary pump must be variable speed. This can solve the flow mixing problem. *But below 50% load, only on chiller pump is operating. All of coils receive less water flow rate. Also to avoid short circuit problem, a check valve or isolation valve should be installed. *ASHRAE Standard 90.1 : When a parallel chiller is shut down, flow rate must be reduced. 12

13 2. Basic configurations 2-2 Chiller arrangement 2) Series chillers configuration The mixing problem and less flow can be solved in series chiller system. But each chiller must accommodate double flow rate. This increases pressure drop. To compensate pressure drop, series chiller applies to low flow system. [higher ΔT than ] Upstream chiller Downstream chiller T T Parallel chiller GPM System pressure drop : 7.25 psi Series chiller GPM System pressure drop : 26.1 psi Upstream chiller starts first. When upstream chiller can not achieve target water set temperature, downstream chiller is operated. 13

14 2. Basic configurations 2-3 Water piping 1) Direct return piping When designed with direct return piping, the pressure drop and flow rates will be uneven between near and far side from the pump due to different piping lengths. Because of different friction loss the water flow rate of each chiller and load will not be same. It requires to install additional flow control valves near the inlet side of each load to balance water flow. Flow rates of each load 25% 50% 75% 100% 100% C Fan Coil Units (installed in parallel) Modular Chillers (installed in parallel) 75% 50% C C C C C C 25% C ΔP Pump C : Flow control valve ΔP Profile of Pressure Drop between inlet and outlet 14

15 2. Basic configurations 2-3 Water piping 2) Reverse return piping If the pipe length between supply and return is the same, it has approximately the same friction loss, which will produce approximately the same flow rate. Fan Coil Units (installed in parallel) Modular Chillers (installed in parallel) Equal ΔP Pump Equal ΔP Profile of Pressure Drop between inlet and outlet Although reverse return system is closer to self-balancing than direct return systems, make sure each load is similar to balance water flow 15

16 3. Water piping elements When designing a water piping system, the following should be considered : Water must be supplied to the required locations according to the needs of each DVM Chiller. Head and friction losses should be kept minimum. Water velocity should be properly controlled to avoid water flow noise, pipe vibration, and pipe expansion/contraction issues due to temperature differences. Attention should be paid to water management : Impact of the water quality, corrosion prevention, freeze prevention etc. Proper arrangements should be provided for easy service and maintenance. Process Pipe design Direct or reverse return Pipe route design Minimization of pipe length Flow rate calculation Head loss, friction loss calculation Select pipe size Select other parts Calculation total head loss Select water pump 16

17 3. Water piping elements 3-1 Water pipes 1) Constant water flow a. Constant flow valve The constant flow valve maintains a steady flow rate for the stable operation. This constant water flow valve is required for each DVM Chiller C C C C C : Constant flow valve b. Reverse return piping If the pipe length between supply and return is the same, it has approximately the same friction loss, which it makes the same flow rate. 17

18 3. Water piping elements 3-1 Water pipes 2) Friction losses In order to force a fluid through a pipe, pressure is required to overcome the viscous friction forces. Friction loss occurs when water flow through a pipe. Note The Darcy equation is the basis of all fluid flow equations and relates the pipe pressure drop required to overcome the fluid viscous friction forces : P = ( ρ * f * l * v² ) / ( 2 * d ) Where : P = friction losses (Pa) ρ = fluid density (kg/m³) f = friction factor, depending on the roughness of the internal surface of the pipe l = pipe length (m) v = fluid velocity (m/s) d = internal pipe diameter (m) Most air conditioning systems use steel pipe or copper tubing. Based on the Darcy equation, the pipe friction / flow tables are made. 18

19 3. Water piping elements 3-1 Water pipes 2) Friction losses Example (By Hazen-Williams Equation chart) 19

20 3. Water piping elements 3-1 Water pipes 3) Water velocity The recommended water velocity through the piping is depending on two conditions : Pipe diameter Effect of erosion Pipe selection guide Velocity High Low Reliability Erosion accelerating, vibration and noise Damaging wear and tear of pipes and fittings Laminar flow reduces the chiller efficiency * Design water velocity must be decided by the design engineer as erosion is a function of time [ Recommended velocity range ] Pipe diameter [inch] *Velocity range [ft/s] 5 or more 6.9 ~ 8.9 2~4 3.9 ~ 6.9 About ~ 3.9 [ Max allowable velocity to minimize erosion ] Running time (hr/year) Velocity(ft/s) 1, , , , , , * 1 year = 8,760 hr 20

21 Flow rate Design guide for DVM Chiller 3. Water piping elements 3-1 Water pipes 4) Example of sizing water pipes : * Condition - Type : Stainless steel pipe, Water flow : 200 l/min, Friction loss : less than 1.2 kpa Case #1 Pipe size : 50 A, Velocity : 1.99 m/s, Friction loss : 1.05 kpa Case #2 Pipe size : 60 A, Velocity : 1.28 m/s, Friction loss : 0.36 kpa (Lower than 0.4 kpa Not efficiency) 40 mm high friction loss (2.04 kpa/m) 75 mm low velocity (0.79 m/s) Friction loss 21

22 3. Water piping elements 3-1 Water pipes 4) Example of sizing water pipes : * Example (By Hazen-Williams Equation chart) Model 15HP Model 20HP Model 25HP Water Flow 120 LPM Water Flow 160 LPM Water Flow 200 LPM Diameter 40 A Diameter 40 A Diameter 50 A Velocity 1.35 m/s Velocity 1.82m/s Velocity 1.99m/s Friction loss 0.58 kpa/m Friction loss 0.95 kpa/m Friction loss 1.05 kpa/m Flow rate Friction loss 22

23 3. Water piping elements 3-2 Pumps Water pump selection 3 Factors for pump selection 1) Flow rate, 2) Total Head, 3) Power 1) Flow rate Sum of required flow rate of each DVM Chiller 2) Total Head H_t = H_a + H_p + H_f + H_u H_a : Head pressure by level difference ( H_a value is 0 in closed loop as no level difference ) H_p : Friction loss by straight pipes H_f : Equivalent length of friction loss by fittings H_u : Friction loss from the condenser / evaporator in the units ( PHE of DVM Chiller) H_a Actual head of Delivery H_a Actual head of Delivery H_a Actual head of Delivery Actual head of suction Actual head of suction Water head 23

24 3. Water piping elements 3-2 Pumps Water pump selection Equivalent length of friction loss by fitting [ft] Pipe size ¾ Elbow (Long Radius) Tee (line flow) Tee (branch flow) Globe valve **Above chart is for reference only** Resistance of valves and fittings to flow of fluids 24

25 3. Water piping elements 3-2 Pumps Water pump selection 3) Power Motor power calculation : This value will be used to select motor of water pump Power[kW] = q x ρ x g x h / (3.6 x 10^6) / η q = Flow rate (m3/h) ρ = Density of fluid (kg/m3), * 1,000 for water g = Gravity (9.81 m/s2) h = Differential head (m) η = Pump efficiency 25

26 3. Water piping elements 3-2 Pumps Water pump selection Example DVM Chiller 15 Ton FCU 24k Btu/h * 4 EA Required flow rate : 120 l/min Pressure loss PHE of DVM Chiller : 60 kpa FCU : 25 kpa Supply Flow rate : 120 l/min Length : 25 m Pipe diameter : 40 A Velocity : 1.35 m/s Friction loss : 59 mmaq/m Return Flow rate : 120 l/min Length : 20 m Pipe diameter : 40 A Velocity : 1.35 m/s Friction loss : 59 mmaq/m DVM Chiller Elbow : 4 ea T-connection straight through : 1 ea Globe valve : 1 ea [ Pump catalogue ] Pump Efficiency : 60% FCU 32.8 feet - Flow rate : 120 l/min = 7.2m3/hr - Total head pressure(h_t) = = kpa (12,6 maq) * H_a : 0, * H_p : (25+20) x 59 = 2,655 mmaq = 26.0 kpa, * H_f : (1.3x4)x59 +( 0.9x1)x59+(16x1)x59 = 1,304 mmaq = 12.8 kpa, * H_u : = 85.0 kpa Refer to the table about equivalent length of friction loss by fitting - Power = 5.76 x 1,000 x 9.81 x 12.6 / (3.6 x 10^6) / 0.6 = 0.33 kw 26

27 3. Water piping elements 3-2 Pumps Water pump selection Use selection software of the pump manufacturer - Input flow rate & Head pressure * Reference site : 27

28 3. Water piping elements 3-3 Expansion tank (vessel) The purpose of the expansion tank is to maintain system pressure by allowing the water to expand when the water temperature increases in order to prevent pipe and equipment damage. The tank is partially filled with air, whose compressibility cushions shock caused by water hammer and absorbs excess water pressure caused by thermal expansion. An expansion tank is required in a closed system. In an open system, the reservoir acts as the expansion tank. The expansion tank can be of the open or closed type. The open expansion tank (reservoir) is located at the suction side of the pump, above the highest point in the system. At this location, the tank provides atmospheric pressure equal to or higher than the pump suction, preventing air from leaking into the system. The closed expansion tank is used in small systems and is designed larger than open expansion tanks. The tank is located at the suction side of the pump. Expansion tank (vessel) location It may occur cavitation It can prevent cavitation 14.5 psi 14.5 psi P P E Expansion tank E 14.5 psi 14.5 psi P P Pump off Pump off 0 psi 14.5 psi P P E E 14.5 psi 29 psi P P Pump on Pump on 28

29 3. Water piping elements 3-3 Expansion tank (vessel) Expansion tank (vessel) sizing Open expansion tank In the case of open expansion tanks, corrosion prevention is required. - Size(l) = Vw x (v_high - v_low) x α * Vw(l) : Total water amount in the system * v_high(l/kg) : water specific highest water temp * v_low(l/kg) : water specific lowest water temp * α : Safety factor Closed expansion tank - Size(l) = Vw x (v_high - v_low) / [(Pa / P0) (Pa / P1)] x α * Vw(l) : Total water amount in the system * v_high(l/kg) : water specific highest water temp * v_low(l/kg) : water specific lowest water temp * Pa(kgf/cm2) : Atmospheric pressure 1.03 * P0(kgf/cm2) : System initial cold pressure * P1(kgf/cm2) : System operating hot pressure * α : Safety factor 29

30 4. Maintenance 4-1 Water pipe installation Example of water pipe installation No. Name No. Name 01 Drain pipe 07 Valve 02 Flange 08 Air vent valve 03 Strainer 09 Check valve 04 Drain valve 10 Pump 05 Temperature gauge 11 Flexible joint 06 Pressure gauge 12 Expansion tank If the hydronic pipe is not managed periodically, it may affect the operation and may cause noise, maintenance, and service difficulty. Hydronic pipe should be insulated per local code. If water piping is not insulated, or poorly installed, there may be heat loss, and may cause frozen damage during cold weather. When using indoor units such as two or more fan coil units, make sure each unit is installed with valving to maintain proper balanced water flow. Install the expansion tank that can absorb expansion and contraction of water due to temperature change. Location of tank based on type used, open or closed. Install automatic air vents at high points in the piping to aid in the removal of air When using expansion tanks or automatic air vents, give 1/250 slant to horizontal pipes. 30

31 4. Maintenance 4-1 Water pipe installation Install drain valves at low points of the loop. If the system is large, install drain valves for each of the main pipes so that draining is easier for maintenance. Water pump should be installed on the inlet side of DVM Chiller heat exchanger. A stainless steel strainer (50 Mesh or more) is mandatory at heat exchanger inlet. Use flexible joint at inlet/outlet of heat DVM Chiller heat exchanger connections pipe to aid in absorption of vibration and stress. Install temperature gauge and pressure gauge at inlet/outlet of DVM Chiller heat exchanger connections for monitoring, maintenance, and service. Connect water pipes to the product by cut and groove coupling. Install the pipe and the product in a manner it can be easily disconnected if needed for service. Install valves at inlet/outlet of pipes, drain valve at inlet, and air purge valve at outlet of water pipe. Maintain the water volume as listed in technical documents. If the volume is too low, compressor may short cycle with light load on the system. Such operation may result in shortening the life of the product and/or product malfunction due to repetition of compressor operation. Be aware of the volume, if water temperature and capacity control is done by a bypass system. There is a possibility of scale generated on plate type heat exchanger, periodical chemical cleaning may be necessary to remove scale. Install chemical input between valve and the product. If the product is stopped for a long periods of time during winter, or stops operation for unoccupied times, take appropriate countermeasures (water drain, circulating pump operation, heater, etc.) to prevent freezing in cold regions where outdoor temperature falls below 32. When water in the system freezes, it will cause damage to the plate type heat exchanger and therefore preventive measure must be taken. Example: Pumping heat exchanger with glycol is a preventative measure. 31

32 4. Maintenance 4-1 Water pipe installation Water maintenance is standard for chilled/heating water with circulating water. Using untreated water may cause corrosion and performance issues. Also, avoid autofill water systems that do not have chemical treatment. Water storage must be used within the range listed in installation manuals. 50 ~ 200 % of rated water storage can be used, but using rated water storage is recommended. - If water volume is low, it may cause performance decrease due to scale accumulation, thermal protection operation to prevent freezing, and potential gas leakage. - If water storage is over, it may cause corrosion. Be aware of any cavitation when checking flow rate of water system, installation of expansion tank, and air purging placed in the middle of the loop. In case of semi-closed chilled/heating water system with thermal storage, exchange water (once every 1 ~ 2 years), clean and maintain thermal storage periodically. New concrete thermal storage may elute foreign substances, so ph of thermal storage water may be affected. If ph is over the standard, copper may corrode faster. Exchange the water periodically in this situation. Also, over time if thermal storage is used water leakage may occur due to cracks. - In case of using sea water or contaminated underground water, corrosion may occur by slime generated by microbes or calcium carbonate. Installation of chemical pot feeder is recommended for ease of water treatment maintenance. 32

33 4. Maintenance 4-2 Water quality If chilled/heating water is not maintained by the following standard, corrosion and scale accumulation may occur. It may decrease the performance of heat exchange, and may also cause product malfunction due to heat exchanger damage by freezing. Extra care is necessary, and water should be maintained to keep the water within the standards. Item Chilled water system Circulation water (below 68 ) Supply water Heating water system Low level medium temp. heating gauge Circulation water (68 ~140 ) Supply water Corrosion effect Forming scale ph (77 ) 6.8~ ~ ~ ~8.0 O O Electric conductivity (ms/m, 77 ) {μs/cm, 77 } Below 40 {Below 400} Below 30 {Below 300} Below 30 {Below 300} Below 30 {Below 300} O O Chloride ion (mgcl-/l) Below 50 Below 50 Below 50 Below 50 O Basic Sulfate ion (mgso42-/l) Below 50 Below 50 Below 50 Below 50 O item Acid consumption (ph4.8, mgcaco3/l) Below 50 Below 50 Below 50 Below 50 O Full hardness (mgcaco3/l) Below 70 Below 70 Below 70 Below 70 O Calcium hardness (mgcaco3/l) Below 50 Below 50 Below 50 Below 50 O Ion-like silica (mgsio2/l) Below 30 Below 30 Below 30 Below 30 O Iron (mgfe/l) Below 1.0 Below 0.3 Below 1.0 Below 0.3 O Copper (mgcu/l) Below 1.0 Below 0.1 Below 1.0 Below 0.1 O Reference item Sulfide ion (mgs2-/l) Not detected Not detected Not detected Not detected O Ammonium ion (mgnh4+/l) Below 1.0 Below 0.1 Below 0.3 Below 0.1 O Chlorine residual (mgcl/l) Below 0.3 Below 0.3 Below 0.25 Below 0.3 O Free carbon (mgco2/l) Below 4.0 Below 4.0 Below 0.4 Below 4.0 O 33

34 4. Maintenance 4-3 Freeze prevention of water pipe (If not using Anti-freeze) When outdoor temperature is low or during winter months, water in pump and piping may freeze and may cause damage to the product and the piping system. Insulate piping and all accessories to help prevent freezing. Use of heat trace is recommended. In low ambient conditions operate the pump while the product is off or if possible, drain the system. Stopping during winter Do not cut-off the power supply. - This may result in water leakage or pipe damage because pump will not operate to prevent freezing. Do not cut-off the power supply for the pump. Stop the operation with water pipe valve opened. - Stop the operation with valve opened to make water circulate when the pump operates. If the water does not circulate, it may freeze and cause product malfunction. Stopping for an extended time Drain water from water pipes and water side heat exchanger. - Open drain valves on water pipe system and drain plug in DVM CHILLER when draining water. - Product may be damaged if water freezes inside the piping and water side of the heat exchanger when temperatures are below 32 F. Cut-off the power supply after draining water. - Pump may operate for protection even there is no water when power is supplied and it may cause pump malfunction. 34

35 4. Maintenance 4-4 Chilled water management If the chilled water storage exceeds optimal range, stop the operation until cause is taken care before re-start the operation. * Range: 50 ~ 200 % of rated flow rate Item Water flow rate working range (GPM) Rated condition Working range Model AG010* AG015* AG010* AG015* Cooling / Heating ~ ~

36 4. Maintenance 4-4 Chilled water management Water temperature range - Operate the product within the following range. For product protection, compressor operation may be limited. Rated condition Range(Water Outlet) Classification (Inlet / Outlet) Water Brine Cooling 53.6 / ~ ~ 77 Heating 104 / ~ 131 When using in brine condition in cooling mode, maintain concentration of brine properly. The product should be set in low temperature usage. * To use low temperature function, hydro controller option No. 34 and Seg 23 of advanced option 05 = "E" should be all set. * Anti-freeze standard data Water outlet temperature, 14 ~ 23 23~32 32~ ~ ~ 68 Ethylene glycol, % Propylene glycol, % Minimum water outlet temperature,

37 4. Maintenance 4-4 Chilled water management Minimum water storage - If the length of water pipe is too short, water volume within the system becomes lower and ON/OFF operation of the compressor occurs more often. For stable operation, maintain certain water volume by applying header or Buffer tank. - If total water volume is under the minimum volume, install another tank to retain more water volume. Model name Minimum water volume (gal) AG010KSV Series 72 AG015KSV Series Total water volume in the system = water volume within the water pipe + water volume in DVM CHILLER + water volume in AHU (or fan coil) Minimum capacity of buffer tank = Minimum water volume - water volume within the water pipe system 37

38 5. External contact connection Configuration of terminal block T/B : Terminal Block A-T/B B-T/B C-T/B DVM Chiller 5-1 A-Terminal block Hydro control box - Purpose is to check the status of product in control room. Cooling/Heating display Operation display Freeze protection display * A-T/B : Output contact * Output contact can be connected neutral contact and open/short only * Apply dry contact(no current) Warning display Defrost operation display Pump operation display Pump operation Comp operation display 38

39 5. External contact connection No. Name Function Contact short Contact open signal 1-2 Cooling/Heating display Display when operating in heating mode Heat 3-4 Operation display Display when operation ON Operate Stop 5-6 Warning display Display when error occurs Error occurred No error Cool A-T/B 7-8 Defrost operation display Display when in defrost Defrost On Defrost Off 9-10 Pump operation display Display when pump is operating Pump On Pump Off Comp operation display Display when compressor is operating Compressor On Compressor Off Pump operation Signal of pump operation Pump signal On Pump signal Off Freeze protection display Display when in freeze protection Pump On for Freeze protection Others Dry contact 5-2 B-Terminal block Pump interlock Operation On/Off * B-T/B : Input contact * Input contact can be connected neutral contact and open/short only * Apply dry contact(no current) Operation On/Off Operation mode Hot water(cool storage) mode Hot water(cool storage) Thermostat signal Standard for Hot water (Cool storage) control 39

40 5. External contact connection 1 Pump interlock (Mandatory) - Prevents operating DVM Chiller without pump operation. If DVM Chiller operates without pump operation, it may be cause product damage. - Works by contact signal between DVM Chiller and pump. - After checking for pump operation, the product operates.(apply interlock system) If pump does not operate, the product will not operate. - The power of pump should be supplied separately. DVM Chiller provides only a dry contact for reliability of product. Product can be damaged because of problem of a pump which is installed in field. Operation on signal to pump Feedback signal from the pump for delay time? Yes Detect the water flow for 10sec? Yes DVM Chiller Operation On No No Operation OFF Error display *E918 Operation OFF Error display *E911/E913 Hydro option setting - Delay time of pump operation signal feedback is determined in the No. 13 of hydro option setting. *E911 : Dose not detect the signal of flow switch E913 : Six times detection of E911 (Operation is not possible) *E918 : No feedback interlock signal of pump operation Option No. Option Item Option value Factory default Definition Setting unit 13 Delay time of pump operation signal feedback 10~ Second unit Main unit of module ** Pump interlock may be proven by means of flow switch or control interlock. 40

41 5. External contact connection 1 Pump interlock Wiring connection Dry Contact or flow proving device Relay Input signal Voltage supply Power supply (Field supplied) Relay Pump Caution * Some voltage is necessary to activate relay * Input cannot be connected by jumper No. Function Contact short Contact open Setting unit A-T/B Pump operation Pump signal ON Pump signal OFF Each unit B-T/B 7-8 Pump interlock Pump on Pump off Each unit 41

42 5. External contact connection 2 Operation contact signal - It is possible to control operation by contact signal. You can select the operation method by either Module control/dms or external contact. - Hydro option setting is required for this function. (Option No. 1 / Option No. 28) Value of hydro option No. 28? 1 0 Is there input signal? (B-T/B, 9/10) No Operation OFF (Contact : Open) Yes DVM Chiller Operation ON (Contact : Short) Is there input signal? (B-T/B, 13/14) No Cooling operation start (Contact : Open) Yes Heating operation start (Contact : Short) No No Is there input signal? (B-T/B, 9/10) Is there input signal? (B-T/B, 11/12) Yes Yes DVM Chiller Operation ON (Contact : Short) DVM Chiller Operation OFF (Contact : Short) Is there input signal? (B-T/B, 13/14) No Cooling operation start (Contact : Open) Yes Heating operation start (Contact : Short) Hydro option setting - The input signal pattern is determined in the No. 28 of hydro option setting at first. Option No. Option Item Option value Factory default Option Definition Setting unit 28 Signal pattern of operation ON/OFF by external contact 0/1 0 0 Usual input signal Main unit 1 Instant input signal of group - To use this external contact, the input method of operation on/off in hydro setting needs to be set to 1. Option No. Option Item Option value Factory default Option Definition Setting unit 1 Input method of operation ON/OFF 0/1 0 0 Module control/dms Main unit 1 External contact of group 42

43 5. External contact connection 2 Operation contact signal Wiring connection Operation ON contact signal Operation mode contact signal DDC DDC Dry contact Dry contact Dry contact DDC External controller (DDC : Direct Digital Control) Input signal Input signal (Field supplied) (Field supplied) Input signal No. Function Contact short Contact open Signal type Setting unit B-T/B 9-10 Operation on/off Refer to the below or Instant input signal Operation mode Heat Cool Usual input Main unit of group Signal type No. 9~10 No. 11~12 Signal type Short(Operation on) Open(Operation off) - Usual input signal (Open/short) Short(Operation on) Short(Operation off) Instant input signal (Pulse input) 43

44 5. External contact connection 3 Hot water / Cool storage - Able to store the thermal energy in water tank for later use. DVM Chiller Thermo on (Contact : Short) DVM Chiller Operation ON Is there input signal? (B-T/B, 15/16) Yes Cool storage (Hot water) operation (Contact : Short) Is there input signal? (B-T/B, 19/20) Yes B-T/B 9-10 : on No Cooling(Heating) operation (Contact : Open) - Cool storage operation B-T/B 13/14 : open - Hot water signal : B-T/B 13/14 : short No DVM Chiller Thermo off (Contact : Open) Hydro option setting - To use this external contact, the input method of operation mode in hydro setting have to be set to 1. Option No. Option Item Option value Factory default Option Definition Setting unit 3 Input method of operation mode (Cool/Heat, Cool storage/hot water) 0/1 0 0 Module control/dms Main unit 1 External contact of group Module control setting - Service mode setting of Module control is required for this function. Main menu 9 Sub menu Function Option value Factory default 4 Use Cool storage mode 0/1-5 Use Hot water mode 0/1 - Option Definition Save 0 Disable 1 Enable 0 Disable 1 Enable Save at DVM Chiller 44

45 5. External contact connection 3 Hot water / Cool storage Wiring connection (Field supplied) Dry contact Dry contact DDC DDC Dry contact DDC Input signal Input signal External controller(ddc : Direct Digital Control) Input signal No. Function Contact short Contact open Signal type Setting unit Hot water(cool storage) mode Cool storage or Hot water Cool or Heat Usual input B-T/B Hot water(cool storage) control method Control by set temperature Control by thermostat Usual input Main unit of group Hot water(cool storage) Thermostat signal Thermo on Thermo off Usual input 45

46 5. External contact connection 5-3 C-Terminal block T/B : Terminal Block Silent mode function Demand function * C-T/B : Input contact * Input contact can be connected neutral contact and open/short only * Apply dry contact(no current) except C-T/B No. 17~20 Forced fan function Unusual condition reset Water law function External water outlet Temperature (4~20mA) Set temperature / Room temperature Sensor(4~20mA) Sensor Type: PT100 1 Silent mode function - Reduces the noise of outdoor unit in night time during low demand. - When silent mode function is enabled by module control, only cooling mode is possible. - If silent mode is enabled by external contact, both Cooling and Heating mode are possible by signal of external contact. 46

47 5. External contact connection By module control DVM Chiller Operation ON After 6hr from highest ambient temp? Yes Hydro option value of No. 12? 1~3 Silent mode operation (Only Cooling mode) No 0 No Yes Normal operation Normal operation After 12hr from mode entry or mode off? By external contact DVM Chiller Operation ON Is there input signal? (C-T/B, 1/2) Yes Hydro option value of No. 12? 1~3 Silent operation (Cooling or Heating mode) No 0 Normal operation (Contact : Open) Normal operation Hydro option setting - Silent mode function level is determined in the No. 12 of hydro option setting at first. Option No. Option Item Option value Factory default 12 Silent mode function level 0~3 1 Option Definition 0 Default(100%) 1 Level 1 2 Level 2 3 Level 3 Setting unit Main unit of module - To use external contact, the input method of silent mode function in hydro setting have to be set to 1. Option No. Option Item Option value Factory default Option Definition Setting unit 6 Input method of silent mode function 0/1 0 0 Module control/dms Main unit 1 External contact of group 47

48 5. External contact connection 1 Silent mode function Wiring connection Dry contact DDC External controller (DDC : Direct Digital Control) (Field supplied) Input signal No. Function Contact short Contact open Signal type Setting unit C-T/B 1-2 Silent mode function On Off Usual input Main unit of group 48

49 5. External contact connection 2 Demand function - Used to limit power consumption of the product to manage efficiency. - Hydro option setting is required for this function. (Option No. 5 : Demand control level) It can be set as no limit or range of 50 ~ 100%. (Interval : 5%) - If it is enabled by external contact, Hydro option setting is required for this function (Option No. 4 : Input method of Demand control) DVM Chiller Operation ON Demand control On by Module control or DMS? Yes Demand control operation No Normal operation No Demand control Off by Module control or DMS? Yes Normal operation Use of external contact Is there input signal? (C-T/B, 3/4) Yes Demand control operation No Normal operation (Contact : Open) 49

50 5. External contact connection Hydro option setting - Demand control level is determined in the No. 5 of hydro option setting at first. Option No. Option Item Option value Factory default 5 Demand control level 0~11 3 Option Definition 0 Default(100%) 1 95% 2 90% 3 85% 4 80% 5 75% 6 70% 7 65% 8 60% 9 55% 10 50% 11 Not applied(no Limit) Setting unit Main unit of module - To use external contact, the input method of Demand control in hydro setting have to be set to 1. Option No. Option Item Option value Factory default Option Definition Setting unit 4 Input method of Demand control 0/1 0 0 Module control/dms Main unit 1 External contact of group 50

51 5. External contact connection 2 Demand function Wiring connection External controller (DDC : Direct Digital Control) Dry contact DDC (Field supplied) Input signal No. Function Contact short Contact open Signal type Setting unit C-T/B 3-4 Demand function On Off Usual input Main unit of group 51

52 5. External contact connection 3 Water law function - Used to optimize the operation state of product depending on ambient conditions to save power cost. - Leaving water temperature of product is set automatically by ambient or room temperature. - If it is enabled by external contact, Hydro option setting is required for this function. (Option No. 8 : Input method of Water law function) - Water law control method is determined by No. 15 of hydro option setting. (Based on ambient temperature or room temperature) - In case of using water law by room temperature, The room temperature sensor must be installed connected at No.17/18 of C-T/B. Leaving water temp.[ F] [Cooling / Heating Mode] Tcool1 or Theat1 Tcool2 or Theat2 AirCool1 or AirHeat1 AirCool2 or AirHeat2 Ambient temp.[ F] Leaving water temp. F] [Cooling / Heating Mode] Tcool1 or Theat1 Tcool2 or Theat2 RoomCool1 or RoomHeat1 RoomCool2 or RoomHeat2 Room temp.[ F] 52

53 5. External contact connection Hydro option setting - Water law control standard is determined in the No. 15 of hydro option setting. Option No. Option Item Option value Factory default Option Definition Setting unit 15 Water law control standard 0/1 0 0 Ambient temperature Main unit 1 Room temperature of group - To use external contact, the input method of Water law in hydro setting have to be set to 1. Option No. Option Item Option value Factory default Option Definition Setting unit 8 Input method of Water law function 0/1 0 0 Module control/dms Main unit 1 External contact of group - The value of parameters are determined by No. 16~27 of hydro option setting. Option No. Option Item Option value Factory default Definition 16 AirCool1(For Water law) 0~20 10 Standard1 outdoor temperature for cooling 17 AirCool2(For Water law) 30~40 35 Standard2 outdoor temperature for cooling 18 RoomCool1(For Water law) 15~24 20 Standard1 room temperature for cooling 19 RoomCool2(For Water law) 25~35 30 Standard2 room temperature for cooling 20 Tcool1(For Water law) -10~25 15 Standard1 set temperature for cooling 21 Tcool2(For Water law) -10~25 7 Standard1 set temperature for cooling 22 AirHeat1(For Water law) -20~5-10 Standard1 outdoor temperature for heating 23 AirHeat2(For Water law) 10~20 15 Standard2 outdoor temperature for heating 24 RoomHeat1(For Water law) 15~24 20 Standard1 room temperature for heating 25 RoomHeat2(For Water law) 25~35 30 Standard2 room temperature for heating 26 Theat1(For Water law) 35~55 45 Standard1 set temperature for heating 27 Theat2(For Water law) 35~55 35 Standard1 set temperature for heating Setting unit Main unit of group ** All values are in ºC 53

54 5. External contact connection 3 Water law function Wiring connection Dry contact DDC Input signal (Field supplied) Sensor SMPS 24V External controller(ddc : Direct Digital Control) (Field supplied) No. Function Contact short Contact open Signal type Setting unit C-T/B Water law Water law control Set temp. input / Room temp. sensor Water outlet set Temp. control Usual input Main unit of group 4 ~ 20mA Current input Main unit of group Correlation of both room temp. sensor and current (Room temperature sensor for water law( ) = 6.25 x Current(mA) 75) Current(mA) Temperature( ) Temperature( F)

55 5. External contact connection 4 External water temperature sensor - External water temperature sensor is used for control instead of product s water outlet temperature sensor - Hydro option setting is required for this function. (Option No. 14 : External water outlet temperature sensor) - The external water temperature sensor should be installed in the common building return header. This will allow the mixed temperature of water to be accurately read. - It must be connected at No. 19/20 of C-T/B External water temp. sensor use? Yes Operation pattern of DVM Chiller is not standard control? Yes External water temp. sensor control No No Water outlet temp. sensor control of each product Water outlet temp. sensor control of each product Hydro option setting - It has to be set to 1, when an external water temp. sensor is used instead of individual unit s water outlet temp. sensor. Option No. Option Item Option value Factory default Option Definition Setting unit 14 External water outlet temperature sensor 0/1 0 0 Disuse Main unit 1 Use of group 55

56 5. External contact connection 4 External water temperature sensor Wiring connection Sensor SMPS 24V (Field supplied) No. Function Contact short Contact open Signal type Setting unit C-T/B External water outlet temperature 4~20mA Current input Main unit of group Correlation of both external water outlet temp. sensor and current (The value of water outlet set temp.( ) = 6.25 x Current(mA) 55) Current(mA) Temperature( ) Temperature( F)

57 6. Check List 6-1 Module or group operation Module/group operation is to combine multiple units in modules or groups of a single water pipe system and to operate depending on the working condition. A single module control can control a maximum of 16 DVM CHILLERs (0 ~ 15). - DVM CHILLER can have a maximum of 8 modules (1 ~ 8) and 4 groups (1 ~4). - A maximum of 8 units can be connected to a module, and a maximum of 16 units (module) can be connected to a group. Depending on the working condition below, set modules or groups. - A module or a group must be connected to a single water pipe. - When modules are controlled by a group, the modules cannot operate themselves and the display will not show the modules during the module operation. You can select an operation mode, a pattern operation (according to distribution method of compressor capacity) and an applied operation by each module or group. 57

58 6. Check List 6-2 Operation pattern for modules - The default is Standard control. This is can be changed at Module Controller. Contact a service center for further details. - When the current water temperature reaches the set temperature, On/Off control will be performed by each unit. 1) Standard control - All units connected to each module start operating at the same time, and then they control the water outlet temperature and the capacity of compressor separately. Standard control is suited to the site that has always a high cooling and heating load factor. 58

59 6. Check List 6-2 Operation pattern for modules 2) Rotation control - DVM CHILLER s water outlet temperature is controlled according to the water outlet temperature average value of all units which operates by pumps in a module. However, if you set Use for an external water temperature sensor, it controls the water outlet temperature according to a temperature value from the sensor. - Only one unit with the highest priority operates, and if the unit has the full load, a unit with the following priority will operate. - The unit with the lowest priority operates at the minimum capacity, and if the water outlet temperature reaches the set temperature, it performs On/Off control. The rotation control is suited to the site that has small capacity at load side during starting a DVM CHILLER and has a small fluctuation in momentary load. 59

60 6. Check List 6-2 Operation pattern for modules 3) Efficiency control - DVM CHILLER s water outlet temperature is controlled according to the water outlet temperature average value of all units which operates by pumps in a module. However, if you set Use for an external water temperature sensor, it controls the water outlet temperature according to a temperature value from the sensor. - The unit with the highest priority operates, and if that unit operates with optimum efficiency, a unit with the following priority will operate. - When all units reach efficient operating condition, each unit operates at capacity between efficient operating condition and the maximum capacity condition. - When all units reach efficient operating condition and the water outlet temperature reaches close to the set temperature, the unit with the lowest priority decreases compressor operating capacity. 60

61 6. Check List 6-2 Operation pattern for modules 3) Efficiency control The efficiency control is suited to the site that has both an operating section with the low load and a focused operating time. When all units operate with the optimum efficiency, they control the pressure of their compressors in a range between higher than *efficient Hz and lower than full load Hz separately. * Efficient Hz means the best efficient Hz of inverter. 61

62 7. Product configuration 7-1 DVM Chiller configuration 1) Product dimension Anchor Bolt 65 3/16 * Unit :inches Anchor Bolt 30 5/ / /8 9 1/ / /8 31 5/8 34 7/8 No Part Name Specification 1 Water Connections 50 A Cut Groove 2 Power Hole (front) 6 1/3 in*6 3/16 in 3 Power Hole (side) Left Φ 2 in, Right Φ 1 ¾ in 4 Communication Hole (Front) Φ 1 3/8 in 5 Monitoring Window 7 in* 5 1/16 in 62

63 7. Product configuration 7-1 DVM Chiller configuration 2) Part exploded view No Part Name No Part Name No Part Name 1 Air Heat Exchanger 10 Fan Motor 19 Water Connection 2 Water Heat Exchanger 11 Oil Return Valve 20 Water Pressure Sensor 3 4way Valve 12 High Pressure Sensor 21 PHE EEV 4 Accumulator 13 Hot Gas Bypass Valve 22 Air Vent 5 EVI Bypass Valve 14 Low Pressure Sensor 23 Water Temp. Sensor 6 Oil Separator 15 Vapor Injection Valve 24 EVI EEV 7 Receiver Tank 16 High Pressure Switch 25 Sub Cooler 8 Scroll Compressor 17 Accum. Return Valve 26 Fusible Plug 9 Propeller Fan 18 Main EEV 63

64 7. Product configuration 7-1 DVM Chiller configuration 2) Part exploded view (Hydro parts) [ AG010/015KSVA*H/AA ] 64

65 7. Product configuration 7-2 Module controller (MCM-A00N, Mandatory) 1) Function - A module controller controls DVM Chillers by each group or module. 2) Features - DVM Chiller On/Off control (Module / Group) - Operation mode, water outlet temperature setting - Optional operation setting - Module / Group setting - Weekly / Holiday operation schedule setting - Summer time (Daylight saving) support - Back light screen - User settings / Service mode support - Forced fan function (Anti snow accumulation) 65

SUBMITTAL AG015KSVAJH/AA Samsung DVM Heat Pump Chiller. Submitted to Reference Approval Construction Unit Designation Schedule #

SUBMITTAL AG015KSVAJH/AA Samsung DVM Heat Pump Chiller. Submitted to Reference Approval Construction Unit Designation Schedule # Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # Page 1 of 7 Performance Power Compressor 95 F Ambient, Entering Temperature: 54 F, Leaving

More information

Increase your flexibility.

Increase your flexibility. DVM CHILLER Increase your flexibility. Get the best of two worlds. This easy to expand, modular unit combines the benefits of VRF and Chiller systems. Product Registration Required Conditions Apply 2018

More information

SYSTEM DESIGN REQUIREMENTS

SYSTEM DESIGN REQUIREMENTS P a g e 1 SYSTEM DESIGN REQUIREMENTS WFC-S SERIES WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLERS / CHILLER-HEATERS Yazaki WFC-S Series water-fired chillers and chiller-heaters are available with nominal

More information

Water Piping and Pumps

Water Piping and Pumps Technical Development Program DISTRIBUTION SYSTEMS Water Piping and Pumps PRESENTED BY: Michael Ho carriertdp@gmail.com 424-262-2144 Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section

More information

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Chiller Plant Design. Julian R. de Bullet President debullet Consulting Chiller Plant Design Julian R. de Bullet President debullet Consulting 703-483-0179 julian@debullet.com This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer ASHRAE

More information

precision controlled industrial process chillers cooling capacity: ,255,668 BTU /hr ( tons) improved productivity & reduced costs

precision controlled industrial process chillers cooling capacity: ,255,668 BTU /hr ( tons) improved productivity & reduced costs next generation C precision controlled industrial process chillers cooling capacity: 6824 -,255,668 BTU /hr (0.6-04.6 tons) cooling capacity: 6,824 -,254,303 BTU/hr (0.6-04.5 tons) precision controlled

More information

Submitted to Reference Approval Construction Unit Designation Schedule #

Submitted to Reference Approval Construction Unit Designation Schedule # Page 1of5 Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # System Performance Modules Connected US Ton (nominal) Capacity (Btu/h) System Specifications

More information

Submitted to Reference Approval Construction Unit Designation Schedule #

Submitted to Reference Approval Construction Unit Designation Schedule # Page 1of Job Name Location Purchaser Engineer Submitted to Reference Approval Construction Unit Designation Schedule # System Performance Power Indoor Units Modules Connected US Ton (nominal) Capacity

More information

Scroll Water Cooled Chiller

Scroll Water Cooled Chiller Scroll Water Cooled Chiller SRW145 Nominal Cooling Capacity 77 to 1232 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data 5 Unit Performance 8 Chiller Selection 9 Physical

More information

Method to test HVAC equipment at part load conditions

Method to test HVAC equipment at part load conditions IPLV Method to test HVAC equipment at part load conditions For water cooled chillers: 100% load ( % hrs) + 75% ( Hrs ) + 50% ( Hrs ) + 25% ( Hrs ) = IPLV value Manufacturer can favor this number by tweaking

More information

1.0 CONDITIONS FOR CHILLED WATER SUPPLY (PRIMARY SIDE BY DHCS SUPPLIER)

1.0 CONDITIONS FOR CHILLED WATER SUPPLY (PRIMARY SIDE BY DHCS SUPPLIER) GENERAL This document contains the basic technical information for Architectural, Civil & Structural and M&E Building Services as required by supplier to achieve optimum operation. The time frame required

More information

DVM CHILLER. Installation manual. AG010KSV / AG015KSV Series

DVM CHILLER. Installation manual. AG010KSV / AG015KSV Series DVM CHILLER Installation manual AG010KSV / AG015KSV Series Thank you for purchasing this Samsung Product. Before operating this unit, please read this Installation manual carefully and retain it for future

More information

Screw Water Cooled Chiller SCW210

Screw Water Cooled Chiller SCW210 Screw Water Cooled Chiller SCW210 Nominal Cooling Capacity 185.1 to1480.8 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data 5 Unit Performance 8 Chiller Selection 9 Physical

More information

CHILLER Technical Data Book DVM CHILLER for Europe (R410A, 50/60Hz, HP)

CHILLER Technical Data Book DVM CHILLER for Europe (R410A, 50/60Hz, HP) CHILLER Technical Data Book DVM CHILLER for Europe (R41A, 5/6Hz, HP) Model : AG42/56/7KSV NH/EU History Version Modification Date Remark Ver.1. Release DVM Chiller(pump integrated) TDB for Europe 16. 5.

More information

technical data Water-cooled design guide air conditioning systems

technical data Water-cooled design guide air conditioning systems technical data Water-cooled design guide air conditioning systems technical data Water-cooled design guide air conditioning systems t t I I I I I I Water-cooled design guide ABLE OF CONENS II water-cooled

More information

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd Abstract This paper presents the design approach adopted for the expansion of a large existing

More information

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Introduction to Hydronics A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Hydronic heating systems use hot water or steam to deliver the

More information

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER

150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER GUIDE SPECIFICATIONS 150 & 200 RT MG-SERIES GAS FIRED DOUBLE-EFFECT EFFECT ABSORPTION CHILLER-HEATER HEATER 1. General Description The Contractor shall furnish and install (Qty) Yazaki model CH- Gas Fired,

More information

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies Pakistan s Largest Manufacturers of Air-Conditioners PACKAGE TYPE UNIT FOR MOBILE APPLICATIONS Provides Turnkey Projects Conceptual Planning to Commissioning of HVACR Projects THE LARGEST MANUFACTURER

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

DAIKIN Modular Inverter Air Cooled Chiller

DAIKIN Modular Inverter Air Cooled Chiller DAIKIN Modular Inverter Air Cooled Chiller R410A ODP=0 R410A ODP=0 R410A ODP=0 R410A ODP=0 1 EVOLUTION ULTIMATE DAIKIN has achieved a wealth of world s firsts over the last three centuries. Based on four

More information

DISTRIBUTION SYSTEMS. Water Piping and Pumps

DISTRIBUTION SYSTEMS. Water Piping and Pumps DISTRIBUTION SYSTEMS Water Piping and Pumps Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are targeted

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e.

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e. ORTEC Compressed Air, Gas & Fluid Technologies t a l r o n m e n i l y E n v F r i e n d t r a n l y R e i g e f r INDUSTRIAL FLUID CHILLERS FC SERIES (0-00 TONS) Application Flexibility Nortec Industrial

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall. Chapter 4 Variable-speed pumps. A variable-speed pump varies the flow rate by maintaining a constant pressure differential as zone valves open and close. A sensor measures the difference in pressure between

More information

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation Air-Cooled Liquid Chillers www.eurovent-certification.com www.certiflash.com Quality Management Systems 0RB 008-05 Nominal cooling capacity 8- The new generation of Aquasnap liquid chillers was designed

More information

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application 1 BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application By: T. S. Wan Date: Oct. 7, 1995 Copy Right 1995 by T. S. Wan All rights

More information

heat interface units A BOILER WITHOUT A FLAME

heat interface units A BOILER WITHOUT A FLAME A BOILER WITHOUT A FLAME heat interface units Communal Heat Networks A central boiler house will generate heat which is distributed through a network of pipe to each home or apartment in the building.

More information

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R Products That Perform...By People Who Care FORM NO: MS0455A WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R134a HXWC SERIES 205 to 560 Tons 60Hz INTRODUCTION Dunham-Bush's HXWC water cooled

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

c o n d e n s e r Glossary of Terms

c o n d e n s e r Glossary of Terms c o n d e n s e r Glossary of Terms ARI Standard Conditions 85 F. water inlet; 95 F. water out; 105 F. condensing; 0.0005 fouling factor Flow Rate or Velocity The speed at which the condensing water travels

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

500 EX Fusion Compressor Series

500 EX Fusion Compressor Series 500 EX Fusion Compressor Series R404A M/T R404A L/T Capacity RANGE 13.8kW - 20.4kW 7.7kW -11.2kW Copeland Fusion Semi-Hermetic Horizontal Scroll Compressors For Medium and Low Temperature Applications

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Installation, and Maintenance Manual IMM WGZ-2 Group: Chiller Part Number: 331374401 Effective: October 2005 Supercedes: IOMM WGZ-1 Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 120AW, Packaged

More information

MSRW MINI SERIES. Modular Water Cooled Scroll Chiller MSRW075 MSRW085 Nominal Capacity 73 to 1312 kw(r) Issue: 2.0 Date 07/08

MSRW MINI SERIES. Modular Water Cooled Scroll Chiller MSRW075 MSRW085 Nominal Capacity 73 to 1312 kw(r) Issue: 2.0 Date 07/08 MSRW MINI SERIES Modular Water Cooled Scroll Chiller MSRW075 MSRW085 Nominal Capacity 73 to 1312 kw(r) Issue: 2.0 Date 07/08 Contents FEATURES 1 C1 CONTROL 4 PHYSICAL DATA 5 UNIT CAPACITY 7 CHILLER SELECTION

More information

SECTION HYDRONIC PIPING AND SPECIALTIES

SECTION HYDRONIC PIPING AND SPECIALTIES SECTION 15511 HYDRONIC PIPING AND SPECIALTIES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Pipe Materials. 2. Fittings. 3. Specialty Items. 4. Glycol Antifreeze Protection. 5. Process Cooling B.

More information

MODELS LIST. Nominal Capacity RT

MODELS LIST. Nominal Capacity RT 1. MODELS LIST. NOMENCLATURE 3. FEATURES 4. PRODUCT DATA 5. PERFORMANCE CORRECTION 6. ANTIFREEZE 7. INSTALLATION 8. ELECTRICAL DATA 9. SCHEMATIC WIRING DIAGRAM 10.MICROPROCESSOR CONTROLLER 11.APPLICATION

More information

V4 Plus Heat Recovery VRF. Linda Lin Pre-sales Engineer

V4 Plus Heat Recovery VRF. Linda Lin Pre-sales Engineer V4 Plus Heat Recovery VRF Linda Lin Pre-sales Engineer VRF Line-up DC inverter VRFs 2-pipe 3-pipe Combinable Individual Watercooled Mini Heat recovery V5 X 8-88HP V4+S 8-64HP V4+I (side) 20-45kW V4+I (top)

More information

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated.

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated. NOMENCLATURE INTRODUCTION The HTT HWDX water-cooled chillers range is the latest addition to HTT s growing family of commercial products, featuring the most current technologies advances. The HWDX main

More information

Air Cooled Scroll Chiller / Heat Pump

Air Cooled Scroll Chiller / Heat Pump Air Cooled Scroll Chiller / Heat Pump SRA 145 Nominal Capacity 67.5 to 1080 kw Refrigerant: R407C and R134a Contents Features 1 MV7 Control 3 Physical Data R407c 5 Physical Data R134a 6 Unit Performance

More information

EN aquatech.piovan.com

EN aquatech.piovan.com EN aquatech.piovan.com Refrigeration Technologies: scroll-compressor chillers The scroll compressor is the most suitable component for the small and medium duty requirements in the industrial applications.

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Type of Compressors Compressor Rotary Scroll Reciprocating Screw Centrifugal Air Cooled Chiller 77 ~ 329TR (270 ~ 1156 kw) ACDX Series 100 ~ 520TR

More information

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1. Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration

More information

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual Suggestions for the hydraulic integration of chillers and heat pumps Table of Contents From practical experience, for your practical needs...

More information

Water cooled VRV IV W-series

Water cooled VRV IV W-series Water cooled VRV IV W-series Ideal for high rise buildings, using water as heat source Unified range for heat pump & heat recovery and standard & geothermal series 22 Indoor units VRV type indoor units

More information

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz EN Technical Catalogue Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: 321-1308 kw 50 Hz EKV/BS business Air cooled water chillers for outdoor installation. Flexibility in the

More information

Precise Temperature Control; Compact Footprint

Precise Temperature Control; Compact Footprint Precise Temperature Control; Compact Footprint The Conair EP1 Series Portable Chillers are designed for 1 to 3 ton applications. Available as air-cooled or water-cooled, with pump sizes from 1/4 to 3 Hp

More information

/2010 US/CA

/2010 US/CA 6 720 646 148-11/2010 US/CA (en) For the user User s Instructions Condensing gas boiler Logamax plus GB162-L.B. 80 kw/100 kw Please read thoroughly before operating This manual is available in the English

More information

DVM S Universal Communication Kit (UCK) Design Guide

DVM S Universal Communication Kit (UCK) Design Guide DVM S Universal Communication Kit (UCK) Design Guide MCM-D211UN MXD-A24K100E MXD-A32K100E MXD-A40K100E MXD-A64K100E Version 11192018 Definition of Universal Communication Kit Technical Specification AHU

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

INSTALLATION & OPERATION MANUAL

INSTALLATION & OPERATION MANUAL DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX30 INSTALLATION & OPERATION MANUAL Version 1.5 1 Table of Contents Safety Precautions... 3 Components... 4 Hydronic piping and design

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications A Technical Introduction to Cool Thermal Energy Storage Commercial Applications Cool Thermal Energy Storage is a new application of an old idea that can cut air conditioning energy costs in half while

More information

union swing check valve spring loaded check valve purging valve pressure relief valve relief valve metered balancing valve

union swing check valve spring loaded check valve purging valve pressure relief valve relief valve metered balancing valve VENT APPENDIX A: PIPING SYMBOL LEGEND GENERIC COMPONENTS CALEFFI COMPONENTS circulator circulator w/ ThermoBloc union circulator w/ swing check spring loaded balancing balancing w/ gate check globe s purging

More information

Centrifugal Chiller. GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series

Centrifugal Chiller. GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series Centrifugal Chiller High Efficiency GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series Centrifugal Chiller High Efficiency Centrifugal Chiller HC-F-GFG-SSC Series (Super High Efficiency Type) HC-F-GXG-S

More information

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System

More information

CXAV / CGAV. Trane Module Chiller. Industry top class efficiency and reliability

CXAV / CGAV. Trane Module Chiller. Industry top class efficiency and reliability CXAV / CGAV Trane Module Industry top class efficiency and reliability Trane Module Adopts resin coated blue fins Design registration n pending High-efficiency, high-durability and space-saving Resin coated

More information

Product Instructions. Hydronic Mixing Block Version Wiring Terminal Block Pressure/Temperature Sensor Delivery Fitting (3) Display Screen

Product Instructions. Hydronic Mixing Block Version Wiring Terminal Block Pressure/Temperature Sensor Delivery Fitting (3) Display Screen Hydronic Mixing Block Version 1.104 The Hydronic Mixing Block is a mixing device and boiler control, with a built in circulator and system controller. The block can provide either a fixed or reset water

More information

Product Catalogue CG-PRC002E-EN. CGAD Liquid Chillers Air-Cooled Scroll Compressor 20 to 150 Tons. July Models: 50 / 60 Hz

Product Catalogue CG-PRC002E-EN. CGAD Liquid Chillers Air-Cooled Scroll Compressor 20 to 150 Tons. July Models: 50 / 60 Hz Product Catalogue CGAD Liquid Chillers Air-Cooled Scroll Compressor 20 to Tons Models: 50 / 60 Hz CGAD CGAD CGAD CGAD CGAD CGAD CGAD CGAD CGAD CGAD CGAD CGAD July 2012 CG-PRC002E-EN Introduction IMPORTANT:

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

AIR-HANDLING UNIT (AHU) DESIGN GUIDELINE

AIR-HANDLING UNIT (AHU) DESIGN GUIDELINE INTERFACE AIR-HANDLING UNIT (AHU) DESIGN GUIDELINE September 2018 [Model Name] PAC-IF013B-E PAC-SIF013B-E Related document: Refer to the following manual PAC-IF013B-E/PAC-SIF013B-E INSTALLATION MANUAL

More information

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient PRODUCT SELECTION DATA Easy and fast installation Compact, reliable and efficient Class A variable speed circulator available Air-Cooled Liquid Chillers 0RB 008-015 CARRIER participates in the ECP programme

More information

DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX45

DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX45 DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX45 Installation and Operation Manual Version 1 1 Table of Contents Safety Precautions... 3 Components... 4 Hydronic piping and design

More information

Water-Cooled Scroll Compressor Chillers

Water-Cooled Scroll Compressor Chillers Installation, Operation and Maintenance Manual IOMM WGZ-1 Group: Chiller Part Number: 330389301 Effective: October 2004 Supercedes: IOMM WGZ Water-Cooled Scroll Compressor Chillers WGZ 030AW To WGZ 100AW,

More information

Process glycol chillers

Process glycol chillers Process glycol chillers The most advanced solutions in refrigeration technology. According to normative EN378 y F-Gas Compact chillers for outdoor installation Natural refrigerant Integrated hydraulic

More information

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762 AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation 4151 112 th Terrace North Clearwater, Florida 33762 COMMERCIAL REFRIGERANT DESUPERHEATER WASTE HEAT RECOVERY INSTALLATION/OPERATION/MAINTENANCE

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

Compendium DES July 2016, CARN

Compendium DES July 2016, CARN Compendium DES July 2016, CARN 1 Contents Contents... 2 1. Energy balance... 4 Using Energy Balance for analyzing energy systems... 4 Energy Balance definition... 4 Steady state, steady flow... 4 Methodology...

More information

DOUBLE EFFECT ABSORPTION CHILLERS

DOUBLE EFFECT ABSORPTION CHILLERS DOUBLE EFFECT ABSORTION CHILLERS STEAM CONSUMTION RATE3.9kg/(hUSRt) 3.95kg/(hUSRt) Model in this catalog is our model code. MODEL REW is; The double effect chiller is high efficiency model, The chiller

More information

Phillips. HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants

Phillips. HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants Phillips REFRIGERATION MECHANICAL PUMP RECIRCULATORS BULLETIN MPR-03E Engineering Data VALVES VESSELS SYSTEMS CONTROLS HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants

More information

Air Conditioners. Technical Data EEDEN13-201

Air Conditioners. Technical Data EEDEN13-201 Air Conditioners echnical Data Wa te r- co o l e d d e s i gn g u i d e EEDEN-20 Air Conditioners echnical Data Water-cooled design guide EEDEN-20 ABLE OF CONENS II Water-cooled design guide Introduction..........................................................

More information

Hydronic Mechanical Panels

Hydronic Mechanical Panels Hydronic Assemblies Inc. 56 Horse Hill Rd Concord NH 2015-2016 Hydronic Mechanical Panels Contact 4805 Main St. Waitsfield, Vermont 05673 Phone : 802-583-5500 WWW.Houseneeds.com Hydronic Assemblies Inc.

More information

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw AIR-COOLED LIQUID CHILLER REVERSIBLE AIR-TO-WATER HEAT PUMP PRO-DIALOG PLUS 30RB/RQ 039S-60S Refrigerant HFC-40A Nominal cooling capacity 40-58 kw Nominal heating capacity 4-59 kw The new generation of

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

MRVIII-C MRVIII-C. 4 way air return heat exchanger design. Two stages heat exchanger design. Double EEV design. Special Heat Exchanger Design

MRVIII-C MRVIII-C. 4 way air return heat exchanger design. Two stages heat exchanger design. Double EEV design. Special Heat Exchanger Design Special Heat Exchanger Design 4 way air return heat exchanger design Reduce the heat exchanger height (6mm), and the upper and lower wind speed uniform and high efficiency. Air Supply Chamber and Equipment

More information

GP SERIES Packaged Chillers

GP SERIES Packaged Chillers Material Handling Process Cooling Temperature Control Size Reduction Temperature Control Process Cooling Material Handling Size Reduction GP SERIES Packaged Chillers Precision Comprehensive Engineered

More information

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ SERIES: EWCBZ - Heat pump MODELS: 70, 80, 00, 0, 60, 00, 40, 00, 50 COOLING CAPACITIES from 5,9 kw to 78,5

More information

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual u Air-to-Water Reverse Cycle Heat Pumps AQH 40 to 130 40 to 131 kw 45 to 141 kw Engineering Data Manual EDM AQH-W.3GB Date : November 2007 Supersedes : TM AQH-W.2GB/03.04 Specifications The Aqu@Logic air-to-water

More information

Ultimate energy saving technology

Ultimate energy saving technology Ultimate energy saving technology CWT Chiller Series CWt purestream series water chillers The new CWT Purestream chiller range is specifically designed to meet the stringent cooling requirements of today

More information

Best Practices for Condensing Boilers

Best Practices for Condensing Boilers ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.cleaverbrooks.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

RECORD SUBMITTAL COVER SHEET

RECORD SUBMITTAL COVER SHEET RECORD SUBMITTAL COVER SHEET PROJECT TITLE: AXCELLERATE PHARMA EQUIPMENT DESCRIPTION: CARRIER AQUASNAP AIR-COOLED CHILLER CH-1 OWNER: AXCELLERATE PHARMA MECHANICAL ENGINEER: ARDEN DATE: JUNE 27, 2014 SUBMITTED

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

TWLC - Tempered Water Logic Controller. The Intelligent Control

TWLC - Tempered Water Logic Controller. The Intelligent Control TWLC - Tempered Water Logic Controller The Intelligent Control Chiller Controls Features: Up to six (6) stages: individual board for each stage maximizes redundancy. Menu driven access and programming.

More information

i-chiller 181 to 210 kw ic770 to ic780 ABOUT THE i-chiller RANGE RELIABILITY: ENERGY & PROCESS EFFICIENCY: EASE OF OPERATION & MAINTENANCE:

i-chiller 181 to 210 kw ic770 to ic780 ABOUT THE i-chiller RANGE RELIABILITY: ENERGY & PROCESS EFFICIENCY: EASE OF OPERATION & MAINTENANCE: ABOUT THE i-chiller RANGE The fully packaged, EcoDesign compliant, air-cooled i-chiller range is designed specifically for reliable and efficient process cooling. The unique evaporator is immersed within

More information

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100

HTD. High Temperature Non-Cycling Refrigerated Compressed Air Dryers. Operation & Maintenance Manual. MODELS HTD 21 thru HTD 100 HTD High Temperature Non-Cycling Refrigerated Compressed Air Dryers Operation & Maintenance Manual MODELS HTD 21 thru HTD 100 - TABLE OF CONTENTS - 1.0 GENERAL 2 1.1 How to use this manual 1.2 Symbols

More information

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw PROCESS CHILLERS AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw climaveneta.com PROCESS CHILLERS MAXIMUM EFFICIENCY IN EVERY TYPE OF PROCESS APPLICATION Air cooled liquid chiller for outdoor

More information

H4T R410A. refrigerant

H4T R410A. refrigerant H4T INDEX Polyvalent unit working modes...pag. 4 Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R410A...pag. 5 Scroll compressors...pag.

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

MANUAL FOR AIR COOLED INDUSTRIAL CHILLERS MODEL: UCS-10A

MANUAL FOR AIR COOLED INDUSTRIAL CHILLERS MODEL: UCS-10A MANUAL FOR AIR COOLED INDUSTRIAL CHILLERS MODEL: UCS-10A Universal Chilling Systems, LLC. 2 Unit Manual Contents 1. Specification 2. Transportation 3. Unit Installation 4. Electrical Installation 5. Commissioning

More information

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES COOLING CAPACITY FROM 76 TO 612 Kw 1 AND 2 COOLING CIRCUITS RAE 1702 F Kc + P2 28 Above picture is only indicative

More information

Condenser Water Pump Calculator Guide

Condenser Water Pump Calculator Guide Condenser Water Pump Calculator Guide Table of Contents 1.0 Introduction... 3 1.1 Units... 3 2.0 Disclaimer... 3 3.0 Overall Condenser Water System... 3 4.0 Condenser Water Pump Calculator - Inputs...

More information