THE DESIGN FIRM ADDENDUM #1 PINE GROVE BAPTIST FELLOWSHIP HALL RENOVATION 759 PINE GROVE RD. HARVEST, AL MAY 10, 2017

Size: px
Start display at page:

Download "THE DESIGN FIRM ADDENDUM #1 PINE GROVE BAPTIST FELLOWSHIP HALL RENOVATION 759 PINE GROVE RD. HARVEST, AL MAY 10, 2017"

Transcription

1 THE DESIGN FIRM A N I T A J. D E N S O N A R C H I T E C T 102 ASHWOOD DRIVE! DECATUR, ALABAMA 35603! OFFICE: HOME: ! CELL: ADDRESS: thedesignfirm@ bellsouth.net ADDENDUM #1 PINE GROVE BAPTIST FELLOWSHIP HALL RENOVATION 759 PINE GROVE RD. HARVEST, AL MAY 10, 2017 The following addendum as prepared by The Design Firm on the project is hereby made a part of the Drawings dated 4/6/17: CHANGES AND CLARIFICATIONS TO THE DRAWINGS TO ARCHITECTURAL DRAWINGS: A3 REMOVE NOTE #4 ABOUT PEWS BEING REMOVED. A4 & LS1 SEE ADDENDUM NUMBER 1 DRAWINGS A & B FOLLOWING THIS PAGE FOR CLARIFICATION OF DOORS, PERCENT OF ALTERATIONS TO BE DONE AND FURNITURE IN FELLOWSHIP HALL. ALL ITEMS CONCERNING ARCHITECTURAL PART OF THE REVIEW HAVE BEEN ADDRESSED OR WERE ALREADY ON THE DRAWINGS. THIS DESIGN MEETS OR EXCEEDS THE REQUIREMENTS POINTED OUT IN THE REVIEW.. MECHANICAL AND PLUMING: M1, M2, P1 AND P2 SEE ATTACHED 2 PAGE RESPONSE FROM MECHANICAL ENGINEER AND REVISED M1, M2, P1 AND P2 ALSO INCLUDED IN THIS ADDENDUM. ELECTRICAL: E1, E2 AND E3 - SEE ATTACHED 2 PAGE RESPONSE FROM ELECTRICAL ENGINEERS TO REVIEW COMMENTS AND E1, E2, AND E3 REVISED ALSO INCLUDED IN THIS ADDENDUM. ANITA J. DENSON, ARCHITECT AL. REG. NO. 3519

2

3

4 May 5, 2017 Mr. Dale Robinson Madison County Public Works 266-C Shields Rd. Huntsville, AL Project: Subject: Pine Grove Missionary Baptist Church Engineer response to plan review comme Dale, below are my responses to plan review plumbing and HVAC comments. The design documentation (drawing) were also revised to reflect actions taken in the responses as following: 16. ComCheck: Indicate ComCheck compliance for existing units being reused. Existing furnace units are not relocated and are not in contract (not touched) 17. Sheet P-1 Show hot and cold water piping. The is a personal preference only and not required. Isometric drawing indicates work to be accomplished. Adding piping to P-1 only clutters the plumbing plan. 18. Sheet P-2 Specify for ASSE 1070 thermostatic mixing valves be provided at every tempered faucet / fixture ADA and non-ada as required by the 2003 IPC. CONCUR, REVISED PLUMBING SCHEDULE TO USE WATTS FAUCET Specify supply and waste trap ADA insulation wrap and off-set grid strainer for knee space clearance. CONCUR, REVISED PLUMBING SCHEDULE TO USE TRAP WRAP WITH OFF SET TRAP. Show and size water hammer arrestors on the cold and hot water riser diagram. Concur, added to P-2 Domestic Water Riser. 3" vent at floor cleanout is a non-compliant location for vents. Vents must be located downstream of the fixture so that use of fixture washes out bottom of vent as required by the 2003 IPC. CONCUR REVISED SOIL, WASTE AND VENT RISER TO SHOW. General Notes: Provide the applicable IPC year for the Contractor to reference. CONCUR REVISED NOTES Plumbing Notes: o Provide the applicable IPC year for the Contractor to reference. CONCUR REVISED NOTES 19. Sheet M-l Provide 2003 IMC required outside air and calculations with the respect to occupancy the two existing relocated units for the Fellowship Hall. OVERCOME BY EVENTS. FURNACE UNITS NO LONGER RELOCATED. WORK TO BE PERFORMED ONLY IN KITCHEN AREA. FRESH AIR VOLUMN FOR THE KITCHEN AND MISC. ASSOCIATED ROOMS BASED ON IMC 2003 VENTILATION REQUIREMENTS. A hood and a fire suppression system are to be provided. o Indicate fire suppression pull station location. CONCUR, INDICATED ON DRAWING SHEET M-1. If hood does not have a supply plenum at the face of the hood, provide conditioned supply fan / unit to make up hood exhaust. Make up air must be within IO O F of room set point per 2003 IMC. CONCUR, VENTILATION AIR THRU HVAC UNIT AND INFILTRATION PROVIDES MAKEUP AIR FOR HOOD. NO CHANGE REQUIRED Existing furnaces do not show flue vent terminations. OVERCOME BY EVENTS. FURNACE UNITS NO LONGER RELOCATED. WORK TO BE PERFORMED ONLY IN KITCHEN AREA.

5 Show gas piping sizes, developed length and total connected capacity. OVERCOME BY EVENTS. FURNACE UNITS NO LONGER RELOCATED. WORK TO BE PERFORMED ONLY IN KITCHEN AREA. 20. Sheet M-2 Note of Engineer not being responsible for performance and /or function of the existing equipment should be removed and the Engineer of Record verify the existing equipment is adequate for the occupancy, outside air requirements, building envelope, heat loads, etc. CONCUR, NOTE NO LONGER APPLICABLE AND WAS REMOVED. General Notes: Some words are clipped and the notes shall be replaced and continuous. CONCUR AND REVISED Note 2: Specify the year of the applicable Codes referenced. CONCUR AND REVISED Note 4: Provide Sequence of Operation as noted..) OVERCOME BY EVENTS. FURNACE UNITS NO LONGER RELOCATED. WORK TO BE PERFORMED ONLY IN KITCHEN AREA. NOTE REMOVED. Indicate if C02 control to be provided..) OVERCOME BY EVENTS. FURNACE UNITS NO LONGER RELOCATED. WORK TO BE PERFORMED ONLY IN KITCHEN AREA. NOTE REMOVED. Note 6: Specify filter efficiency / CONCUR MERV 8 RATING AND 1 THICKNESS INDICATED IN HVAC NOTES. Indicate supply gas pressure, outlet pressure to appliance and CFH requirements per regulator / appliance. OVERCOME BY EVENTS. FURNACE UNITS NO LONGER RELOCATED. WORK TO BE PERFORMED ONLY IN KITCHEN AREA. Gas Notes: Note 4: Indicate regulators are located outdoors or that if located indoors the regulator must be vented to the outdoors. OVERCOME BY EVENTS. FURNACE UNITS NO LONGER RELOCATED. WORK TO BE PERFORMED ONLY IN KITCHEN AREA. Provide outside air calculations for each system per 2003 IMC. ) OUTSIDE AIR CFM FOR AHU 1 BASED ON 2003 IMC, CALCULATIONS NOT REQUIRED BY IMC TO BE INDICATED ON PLAN. Provide a Legend for all noted abbreviations. NON-CONCUR, ABBREVIATION MEANINGS SHOWN ON SIMPLIFIED DRAWINGS IN LIEU OF LEGEND HVAC Schedule: Note 6: AHU-2 is not indicated on the Contract Documents. CONCUR AND REMOVED. ALABAMA DAVID REGISTERED No PROFESSIONAL R ENG NEER AL I D R JR, IDGE

6 Arlie C Ramsey Jr, Phone: Electrical Engineer ckramsey@nehp.net Ramsey Engineering Service LLC 8409 Green Moss Ct Owens Cross Roads, AL May 10, 2017 Ms. Anita J. Denson The Design Firm 102 Ashwood Dr Decatur, AL Dear Ms. Denson: This letter serves to document the responses to the electrical comments provided by the Madison County Public Works dated May 4, The drawings will be updated as indicated in the responses below: 7. IEBC Sect Means of Egress lighting required to comply with IBC Note Sect requires this throughout entire floor. RESPONSE: Concur. We will ensure existing lights complies with IBC 2003, section We will supplement with new emergency where existing emergency lights are not in compliance. 8. IEBC Sect Exit signs to comply with IBC Note Sect requires this throughout entire floor. RESPONSE: Concur. Existing exit lights comply with IBC 2003, section Verify no fire alarm required by occupancy load and occupancy type. I 0. Sheet E-1 Specifications 1.4 refers to "latest published NEC" and E-3 Nond welling load calculations refer to 2011 N EC. Madison County has adopted 2002 version of N EC. Also building codes in Specification s section 1.4 should be 2003 version. RESPONSE: Concur. Will ensure calculation complies with 2003 NEC and will modify calculation table to reference the correct version of the NEC Sheet E-2: Location of existing 400A panel not shown. RESPONSE: Concur. Will show the 400A panel on the power plan. 12. Sheet E-2 :No room names. RESPONSE: Non-concur. Sheet E-2 provides room names for all rooms that are part of this renovation.

7 Page 2 May 10, Sheet E-2: Verify kitchen hood does not require automatic shutdown. RESPONSE: Concur. Will provide a shunt trip breaker on the branch circuit feeding the range and will require the shunt trip to operate upon activation of Anusl extinguishing system. 14. Sheet E-3: Light fixture "P" remarks indicate to provide with 0-1OV dimming (Osram 0-10 volt dimming ballast OZI O selected) but legend on sheet E-1 shows $30 switch to be 120 volt dimmer switch. RESPONSE: Concur. Will modify description in legend for Dimming switch to indicate dimmer shall operate on 0-10V. 15. Sheet E-3: Existing emergency lighting locations denoted with hex note "2" do not appear to comply with 2003 IBC I requirements of one footcandle average and 0. 1 footcandle minimum at any point. RESPONSE: We will ensure existing lights complies with IBC 2003, section We will supplement with new emergency where existing emergency lights are not in compliance. Sincerely, Arlie C Ramsey Jr., PE Electrical Engineer

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

PLATTEVILLE MIDDLE SCHOOL

PLATTEVILLE MIDDLE SCHOOL Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle

More information

Gulfport, Mississippi 21 May 2007

Gulfport, Mississippi 21 May 2007 G PLUMBING GENERAL REQUIREMENTS The D-BC shall design the plumbing system to comply with this criteria and the Plumbing Code. Piping shall be shown on the same plan as the fixtures being served. Pipe size

More information

The following information shall become and form part of the contract documents.

The following information shall become and form part of the contract documents. October 4, 206 To: Attention: Re: All Bidders All Bidders JCBE Gymnasium HVAC Upgrades BC#: 206433 Edmonds Project No.: BHM6090 All bidders, The following information shall become and form part of the

More information

Dear Concessionaire,

Dear Concessionaire, Dear Concessionaire, In order to provide a comprehensive review & inspection of the Vendor application please review the following as guidance to a complete application and preparedness for inspection.

More information

FIRE AND SAFETY PROJECT REVIEW REPORT

FIRE AND SAFETY PROJECT REVIEW REPORT 1. A001 2. A001 3. A001 4. D102/103 5. A102/103 *VA enforces/applies the National Fire Protection Association (NFPA) 101 (current edition is 2015) and not the International Building Code (IBC). Ideally

More information

SECTION COMMERCIAL-KITCHEN HOODS

SECTION COMMERCIAL-KITCHEN HOODS SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber

More information

9 E. Scarborough Park Concession Stand and Restroom And / Or Lake Kirby Park Softball Fields Restroom Addition

9 E. Scarborough Park Concession Stand and Restroom And / Or Lake Kirby Park Softball Fields Restroom Addition Addendum NO. 1 Issue Date: October 20, 2016 Project: City of Abilene 10 20 2016 Scarborough Park Concession Stand and Restroom And / Or Lake Kirby Park Softball Fields Restroom Addition I WILL STAT AMR.DUNCA

More information

SHOE PALACE HUNTINGTON PARK M.200

SHOE PALACE HUNTINGTON PARK M.200 M.200 SPLIT SYSTEM CONDENSING UNIT SCHEDULE MARK SERVICE MODEL NO. COOLING DIMENSIONS ELECTRICAL REMARKS CAPACITY AMBIENT DB REFRIGERANT LENGTH WIDTH HEIGHT WEIGHT VOLT/PHASE MCA MOP (MBH) (DEG F) (IN)

More information

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code 2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code Welcome! Shawn Strausbaugh Director PMG Technical Resources ICC Government Relations sstrausbaugh@iccsafe.org

More information

2012 International Mechanical Code Significant Changes. About the Significant Changes

2012 International Mechanical Code Significant Changes. About the Significant Changes Significant Changes to the International Mechanical Code and the International Fuel Gas Code With Louisiana Amendments Copyright Materials This presentation is protected by US and International Copyright

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

XRRS Specification Fire Ready Hood

XRRS Specification Fire Ready Hood XRRS Specification Fire Ready Hood ************************************************************************************************************************ Note to User: This document is subject to copyright

More information

Design Architect s/applicant s Certification Of Threshold Criteria

Design Architect s/applicant s Certification Of Threshold Criteria Design Architect s/applicant s Certification Of Threshold Criteria The Agency has requested certain certifications from the architect and applicant in connection with the submission of an application.

More information

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016

Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Summary of BBS Proposed Ohio Plumbing Code Rule Changes October 2016 Ohio Administrative Code Rule Number OPC Section IPC origin Reason for proposed 4101:3-2-01 Alternate on-site 2015 Added definition

More information

Commercial Remodel/ Add On Rules and Regulations

Commercial Remodel/ Add On Rules and Regulations Commercial Remodel/ Add On Rules and Regulations Public Works and Community Development Department City of Shenandoah 29955 I-45 North Shenandoah, Texas 77381 281-298-5522 www.shenandoahtx.us Construction

More information

COMcheck Software Version Interior Lighting Compliance Certificate

COMcheck Software Version Interior Lighting Compliance Certificate Section 1: Project Information Energy Code: 2009 IECC Project Title: Berry Farms Animal Hospital Project Type: New Construction COMcheck Software Version 4.0.3.0 Interior Lighting Compliance Certificate

More information

Cook - Wissahickon Elementary School

Cook - Wissahickon Elementary School Cook - Wissahickon Elementary School 201 E. Salaignac St., Philadelphia, PA 19128 HVAC Replacement Project Scope Determination Report May 10, 2018 Prepared by: G.P. Lamina, Jr., P.E., MBA School District

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.

More information

900 N. Via Piemonte Ontario, CA

900 N. Via Piemonte Ontario, CA 2 3 L 8 5'-0" 6'-1" 5'-0" 4'-0" 2'-0" D.5 6" 9'-9" K 2 1 2 " 5'-0" 2'-0" 1'-2" 8" 4 4.3 7'-0" C.6 1'-8 1 2 " 7'-0" 8" 10'-6" 5'-0" 8" 6" 6'-6" 6'-3" PLUMBING SCOPE OF WORK - DRAINS 7'-3" 6'-8" KEC TO PROVIDE:

More information

SAFETY PLUMBING PACKAGES. Quality Products & Value Packages SUSTAINABILITY. Residential Solutions ANTI-SCALE SYSTEMS FIRE PROTECTION

SAFETY PLUMBING PACKAGES. Quality Products & Value Packages SUSTAINABILITY. Residential Solutions ANTI-SCALE SYSTEMS FIRE PROTECTION Quality Products & Value Packages Residential Solutions FIRE PROTECTION COMFORTSUSTAINABILITYCONTROL PRESSURE REGULATORS TRENCH DRAINSHVAC SYSTEMS SAFETY ANTI-SCALE SYSTEMS HEATING & COOLING CONTROLS PLUMBING

More information

Additions & Alterations to Ascension Parish Library Galvez Prairieville, Louisiana Project No. 1401

Additions & Alterations to Ascension Parish Library Galvez Prairieville, Louisiana Project No. 1401 Henry L. Chauvin, Architect, LLC 9429 Highway 941 Gonzales, Louisiana 70737 (225) 612-0707 Fax: (224) 612-4565 Email: henry.chauvin@outlook.com Additions & Alterations to Ascension Parish Library Galvez

More information

COMcheck Software Version Review Mechanical Compliance Certificate

COMcheck Software Version Review Mechanical Compliance Certificate COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project

More information

1. Packaged Variable Air Volume (VAV) Rooftop Units (RTU) with Hot Water Reheat. 2. Geothermal Heat Pump VAV Rooftop Units with Hot Water Reheat

1. Packaged Variable Air Volume (VAV) Rooftop Units (RTU) with Hot Water Reheat. 2. Geothermal Heat Pump VAV Rooftop Units with Hot Water Reheat July 6, 2017 City of Countryside Attn: Mayor Sean McDermott City Hall 5550 East Avenue Countryside, IL 60525 RE: New City Hall & Police Building HVAC Options Dear Mayor McDermott, Per your request at our

More information

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Title: Fire Sprinkler System Permit Requirements

Title: Fire Sprinkler System Permit Requirements Title: Fire Sprinkler System Permit Requirements Category: Operational Procedure Policy No: OP-03 Classification: Development PURPOSE: 1. To provide clear direction to the fire Sprinkler contractors, general

More information

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H

More information

NGV MAINTENANCE FACILITIES Code Related Modifications For NGVs In Existing Maintenance Facilities

NGV MAINTENANCE FACILITIES Code Related Modifications For NGVs In Existing Maintenance Facilities NOVEMBER 09, 2017 WISCONSIN CLEAN CITIES - ROUNDTABLE NGV MAINTENANCE FACILITIES Code Related Modifications For NGVs In Existing Maintenance Facilities Steve Arnold, P.E. VP ENGINEERING TODAYS AGENDA NGV

More information

Commercial Rules and Regulations

Commercial Rules and Regulations Commercial Rules and Regulations Public Works and Community Development Department City of Shenandoah 29955 I 45 North Shenandoah, Texas 77381 281 298 5522 www.shenandoahtx.us Construction Documents Submit

More information

Florida Department of Transportation

Florida Department of Transportation Page 1 of 7 RICK SCOTT GOVERNOR Florida Department of Transportation 1109 S. Marion Avenue Lake City, Florida 32025 ANANTH PRASAD SECRETARY September 27, 2011 To: Proposal Holders Addendum No: 1, E2Q23,

More information

Appendix B. Facilities Assessment Report

Appendix B. Facilities Assessment Report Mile Lane Army Reserve Center Redevelopment Plan September 2008 Appendix B Facilities Assessment Report RKG Associates, Inc. Mile Lane Army Reserve Base Middletown, CT MEP System Evaluation For RKG Associates

More information

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available. PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

COMcheck Software Version Interior Lighting Compliance Certificate

COMcheck Software Version Interior Lighting Compliance Certificate Section 1: Project Information Energy Code: 2009 IECC Project Type: New Construction COMcheck Software Version 4.0.2.8 Interior Lighting Compliance Certificate Construction Site: Owner/Agent: Designer/Contractor:

More information

High Performance Building Guide 1

High Performance Building Guide 1 Description This Guide is intended to be used for projects with a Vermont Certified: High Performance energy efficiency goal. This High Performance goal is a whole-building efficiency approach rather than

More information

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes 2012 International Fire Code Significant Changes Andrew M. Schneider, P.E. Senior Fire Protection Engineer aschneider@koffel.com Koffel Associates, Inc. www.koffel.com Expertly Engineering Safety From

More information

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY STAFF USE ONLY Thurston County Resource Stewardship 2000 Lakeridge Dr. S.W. Olympia, WA 98502 (360)786-5490 / (360)754-2939 (Fax) TDD Line (360) 754-2933 Email: permit@co.thurston.wa.us www.co.thurston.wa.us/permitting

More information

NOTICE TO ALL FIRMS. Bid RFI Questions and Answers

NOTICE TO ALL FIRMS. Bid RFI Questions and Answers Purchasing Department 227 West 27 th Street New York, NY 10001 Purchasing Dept. Tel. 212-217-3630 Purchasing Dept. Fax 212-217-3631 Purchasing@fitnyc.edu NOTICE TO ALL FIRMS Date: March 8, 2018 To: From:

More information

Unit # E ± 1,200 SF Width ± 20' Depth ± 60'

Unit # E ± 1,200 SF Width ± 20' Depth ± 60' Lease Outline Drawing ±60' Lease Line Sunnymead Plaza 24907 Sunnymead Blvd., Unit # E, Moreno Valley, CA 92553 Unit # E ± 1,200 SF Width ± 20' Depth ± 60' Plans produced by: ID Plans 6/13/2017 (813) 657-2545

More information

LAV FCO WCO NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS.

LAV FCO WCO NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS. ELECTRIC WATER HEATER SCHEDULE DESIGNATION MODEL MANUFACTURER STORAGE RECOVERY TEMPERATURE LEAVING ELECTRICAL CHARACTERISTICS REMARKS/SPECIAL INSTRUCTIONS NUMBER GALLONS RATE RISE WATER K.W. VOLTAGE PHASE

More information

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP Open to Below: A Discussion of Allowed Floor Openings Kevin S. Hastings, P.E., LEED AP Jay A. Ierardi, Ph.D., P.E., LEED AP R.W. Sullivan Engineering (617) 523-8227, Fax (617) 523-8016 http://www.rwsullivan.com

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

2009 IPC ,IMC Q &A ANDIFGC

2009 IPC ,IMC Q &A ANDIFGC 2009 IPC,IMC ANDIFGC Q &A TABLE OF CONTENTS PREFACE.... ix ABOUT THE INTERNATIONAL CODE COUNCIL...x IPC CHAPTER 1 SCOPE AND ADMINISTRATION...1 Section 101 General... 1 Section 102 Applicability... 1 Section

More information

Small Building Program Design Phase Assistance

Small Building Program Design Phase Assistance Small Building Program Design Phase Assistance Customer s Facility/Project Location XXXX/YYY, MA Project Team (if selected) Contact Firm Phone Email Customer: Electric PA: Gas PA: PAs s Technical Consultant:

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,

More information

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE

AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE 1. BUILDING FEES: 1 AN ORDINANCE TO AMEND CHAPTER 7-BUILDING REGULATIONS, ARTICLE 1-UNIFORM CONSTRUCTION CODE, SECTION 7-2 -FEES TO ESTABLISH A NEW FEE SCHEDULE ESTABLISHMENT OF FEES PURSUANT TO N.J.A.C.

More information

Terminal Commissioning Case Study- Terminal A Logan International Airport

Terminal Commissioning Case Study- Terminal A Logan International Airport Terminal Commissioning Case Study- Terminal A Logan International Airport ACI-NA Environmental and Operations & Technical Conference May 4, 2008 Brad Jones, PE, AP Sebesta Blomberg Sam Sleiman, PE, CCM

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015 Peter McDonnell, PE, LEED AP BD+C McClure Engineering UL DAMPER TEST STANDARDS UL 555 - FIRE DAMPERS UL555S SMOKE DAMPERS UL555C CEILING

More information

DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES

DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES NOTE: Each proposed Denver amendment to the International Codes must be justified. In order to be considered, the amendment proposal must address climate,

More information

Unit # H ± 2,000 SF Width ± 25' Depth ± 80'

Unit # H ± 2,000 SF Width ± 25' Depth ± 80' ±80' Lease Line Lease Outline Drawing Sunnymead Plaza 24907 Sunnymead Blvd., Unit # H, Moreno Valley, CA 92553 Unit # H ± 2,000 SF Width ± 25' Depth ± 80' Unit # H Plans produced by: ID Plans 6/13/2017

More information

Consultant shall design elevators to comply with current ASME A117.1, ASME A117.2, UBC and NEC codes.

Consultant shall design elevators to comply with current ASME A117.1, ASME A117.2, UBC and NEC codes. DIVISION 14 - CONVEYING SYSTEMS Section 14000 - General Discussion Introduction The size, number, and location of elevators must be addressed at the earliest stages of the design, to ensure that neither

More information

A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings.

A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 51 13 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install luminaires, lamps, ballasts and in-line fuses as herein specified and shown on the Drawings. B. Luminaire

More information

RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan

RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan ADDENDUM NO. 2 RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan TO: All Bidders Gentlemen: You are hereby directed to make the following changes in the Project Manual and/or

More information

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents Table of Contents Chapter 1 Administration Chapter 2 Definitions Chapter 3 General Regulations Chapter 4 Ventilation. Chapter 5 Exhaust Systems Chapter 6 Duct Systems Chapter 7 Combustion Air Chapter 8

More information

Unit # 1038 ± 900 SF Width ± 15' Depth ± 60'

Unit # 1038 ± 900 SF Width ± 15' Depth ± 60' ±60' Lease Line Lease Outline Drawing Needles Towne Center 1004 E. Broadway St.,, Needles, CA 92363 ± 900 SF Width ± 15' Depth ± 60' Plans produced by: ID Plans 6/16/2017 (813) 657-2545 C 2017 Site map

More information

SIGNIFICANT CHANGES TO MINOR WORK AND ORDINARY MAINTENANCE

SIGNIFICANT CHANGES TO MINOR WORK AND ORDINARY MAINTENANCE SIGNIFICANT CHANGES TO MINOR WORK AND ORDINARY MAINTENANCE Pursuant to adoption in the March 5, 2018 New Jersey Register, the requirements for minor work and ordinary maintenance have changed. This document

More information

Commercial Application/Plan Review Submittal Checklist

Commercial Application/Plan Review Submittal Checklist Commercial Application/Plan Review Submittal Checklist The following checklist has been compiled to assist in expediting the commercial plan review and permit issuance process. Please take a moment to

More information

HWC NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS.

HWC NOTES: CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR MOUNT HEIGHTS AND SPECIAL MOUNTING INSTRUCTION AND LIMITATIONS. ELECTRIC WATER HEATER SCHEDULE DESIGNATION MODEL MANUFACTURER STORAGE RECOVERY TEMPERATURE LEAVING ELECTRICAL CHARACTERISTICS REMARKS/SPECIAL INSTRUCTIONS NUMBER GALLONS RATE RISE WATER K.W. VOLTAGE PHASE

More information

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS EXISTING MECHANICAL CONDITIONS SUMMARY The items listed below are based on our site visit on Nov 10, 2016. Our review is based on current conditions and anticipated future use of these building. In the

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

SPECIFIC APPLIANCES CHAPTER 6

SPECIFIC APPLIANCES CHAPTER 6 CHAPTER 6 SPECIFIC APPLIANCES SECTION 601 (IFGC) GENERAL 601.1 Scope. This chapter shall govern the approval, design, installation, construction, maintenance, alteration and repair of the appliances and

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 4.0.6.2 Mechanical Compliance Certificate Project Information Energy Code: Location: Climate Zone: Project Type: 90.1 (2007) Standard HALCYON Bldg. 400 Alpharetta, Georgia 3a

More information

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS RHODE ISLAND STATE BUILDING CODE SBC-4 State Mechanical Code Effective August 1, 2007 Replaces Regulation SBC-4 Dated September 1, 2004 STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS Department of Administration

More information

VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED

VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED Ashton Elementary School 1 Masonry Repair $ 42,781.50 2 Replace HVAC $ 375,000.00 3 Replace SAT @ Various Locations $ 92,364.00 3 Recoat & Resurface Exterior Paved Play Area $ 135,978.30 3 Various Technological

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 83 00.00 20 (April 2006) -------------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-15768N (September 1999) UNIFIED FACILITIES GUIDE

More information

SAFETY SHOWERS AND EYEWASHES 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

SAFETY SHOWERS AND EYEWASHES 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS 224500 SAFETY SHOWERS AND EYEWASHES Cornell s Design and Construction Standards provide mandatory design constraints and acceptable or required products for all construction at Cornell University. These

More information

BULLETIN. Permitting Tips (11/10)

BULLETIN. Permitting Tips (11/10) BULLETIN Permitting Tips (11/10) This bulletin is to make you aware of issues that have been identified by the City or other retailers and suggests Tenant s architect and engineer pursue further as it

More information

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved SCO # 1Punch listed items were noted below on

More information

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc. Memphis Housing Authority High Rise Fire Alarm Upgrades Questions from Contractors (Through Addendum #2) Communications Systems, Inc.: Legend 1. DL - Dome light symbol should be on the tenant emergency

More information

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS! SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N 238-44219-00 (Replaces pg. 2 in instruction manual.) CONGRATULATIONS! You have just purchased one of the finest water heaters on

More information

Osceola County Department of Fire Rescue and Emergency Medical Services

Osceola County Department of Fire Rescue and Emergency Medical Services St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner

More information

Wappingers Central School District Energy Performance Contract. 01/29/2013 7:00am 9:00am

Wappingers Central School District Energy Performance Contract. 01/29/2013 7:00am 9:00am ECG ENGINEERING, P.C. Inspection Report #3 ECG 2685 Wappingers Central School District Energy Performance Contract Inspection Dates: Inspector: 01/25/2013 10:30am 1:00pm 01/29/2013 7:00am 9:00am Harold

More information

Building and Safety Division Civic Center Dr, Bellflower, CA, (562) x

Building and Safety Division Civic Center Dr, Bellflower, CA, (562) x Building and Safety Division 16600 Civic Center Dr, Bellflower, CA, 90706 (562) 804-1424 x 2006 www.bellflower.org RESIDENTIAL BATHROOM REMODELS Information Bulletin: BS -004 Effective: 01-01-2011 Revised:

More information

General Kitchen, Bath & Bedroom Remodeling Notes County of Marin, Building Inspection Division

General Kitchen, Bath & Bedroom Remodeling Notes County of Marin, Building Inspection Division These Notes are intended to assist in issuing simple remodel permits. It provides information on the most common requirements relating to the construction or remodeling of kitchens, bathrooms and bedrooms.

More information

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005

ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 ICC Update - Laboratory Issues Code Changes / Proposals / Trends of Interest 10/2005 Kenneth Kretchman, CIH, CSP Mgr, Industrial Hygiene NC State University Ken_Kretchman@ncsu.edu International Building

More information

CHAPTER 5: EXHAUST SYSTEMS

CHAPTER 5: EXHAUST SYSTEMS MOTORS, FANS AND FILTERS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such

More information

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply:

COMMERCIAL PERMIT APPLICATION AND CHECKLIST. Depending on the scope of your project, the following submittal requirements will apply: Planning/Building Department 115 Ramsdell Street Fircrest WA 98466 (253) 564-8902 COMMERCIAL PERMIT APPLICATION AND CHECKLIST Depending on the scope of your project, the following submittal requirements

More information

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY PART I - GENERAL 1.1 SUMMARY A. This section addresses the general requirements for air handling distribution systems, including air handlers, ductwork, ductwork accessories, terminal units, air devices,

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California ADDENDUM NO. 3

HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California ADDENDUM NO. 3 HMC ARCHITECTS 2495 Natomas Park Drive, Studio 100 Sacramento, California 95833 September 15, 2016 Woodland Joint Unified School District Spring Lake Area Elementary School HMC No. 3535003.000 DSA Appl.

More information

SECTION LIGHTING CONTROLS

SECTION LIGHTING CONTROLS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 09 23 LIGHTING CONTROLS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite

More information

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

08/17/2011 Rev. 4 PULL STATION EXHAUST HOOD 10 TO 20 FEET FROM HOOD LOCATE ONE NEAR EVERY POINT OF EGRESS FROM HOOD

08/17/2011 Rev. 4 PULL STATION EXHAUST HOOD 10 TO 20 FEET FROM HOOD LOCATE ONE NEAR EVERY POINT OF EGRESS FROM HOOD 24V CORE TOTAL FLOOD PROTECTION INSTALLATION SUMMARY CORE WATER LINE- 30 TO 70 PSI OPERATING PRESSURE, 90 PSI MAX STATIC PRESSURE, 1.5 GPM PER FOOT OF HOOD 3/4 INCH NPT FITTING, CONNECTED TO SUPERVISED,

More information

Liberty Township Fire Department Fire Prevention Bureau. Clean Agent Fire Protection Plan Submittal Checklist

Liberty Township Fire Department Fire Prevention Bureau. Clean Agent Fire Protection Plan Submittal Checklist Liberty Township Fire Department Fire Prevention Bureau Clean Agent Fire Protection Plan Submittal Checklist Project Name: Date: Project Address: Designers Name: Company Name: Phone Number: Email: Fax:

More information

Facilities Master Planning

Facilities Master Planning Facilities Master Planning DeForest Area School District DeForest, WI PRA Project #130343-01 January 13, 2014 DRAFT Table of Contents DeForest Area School District PRA Project # 130217-01 Section 1 Existing

More information

2016 Plumbing Supplemental Plan Review List

2016 Plumbing Supplemental Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Plumbing Supplemental Plan Review List POTABLE WATER SYSTEM P1. Specify which fixtures are for private use and which are for

More information

Uniform Dwelling Code 2017 Updates SPS 323

Uniform Dwelling Code 2017 Updates SPS 323 Uniform Dwelling Code 2017 Updates SPS 323 Lenny Kanter UDC Engineering Consultant Department of Safety and Professional Services 608 261 6541 voice 608 267 9723 fax robert.kanter@wi.gov Plan Review and

More information

Unit HH Gregg. ± 30,000 SF Width ±26' Lakeland Retail Center. Lease Outline Drawing. Unit HH Gregg. Depth ± 145' HVAC Units & Information

Unit HH Gregg. ± 30,000 SF Width ±26' Lakeland Retail Center. Lease Outline Drawing. Unit HH Gregg. Depth ± 145' HVAC Units & Information Lease Outline Drawing Lakeland Retail Center 4000 US Hwy. 98, Unit HH Gregg, Lakeland, FL 33809 ±26' ±200' Lease Line Unit HH Gregg ±46' Lease Line ±21' Unit HH Gregg ±145' Lease Line ± 30,000 SF Width

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

Appendix E: Photo Documentation

Appendix E: Photo Documentation Appendix E: Photo Documentation Brown County Library Central Branch Building Assessment Appendix E: Photo Documentation Architectural and Structural Brown County Library Central Branch Building Assessment

More information

MH Non-Residential Permit Fees All Commercial Permit fees require a 3% BBS State Tax and are subject to a plan review and base fee.

MH Non-Residential Permit Fees All Commercial Permit fees require a 3% BBS State Tax and are subject to a plan review and base fee. BUILDING New Building $.45 per sq ft $3,500 Min $.40 per sq ft $1,000 Min $.20 per sq ft $250 Min Demolition $.10 per sq ft $150 Min Accessory Structure (over 200 sq ft) $.40 per sq ft $750 Min Retaining

More information

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR

ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR ADDENDUM NO. 2 COOK LIBRARY BATHROOM RENOVATIONS PROJECT NUMBER TU-1874-SBR 5/9/18 Procurement Towson University 8000 York Road Towson, MD 21252-0001 t. 410 704-2171 f. 410 704-8233 Ladies and Gentlemen:

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 3.8.2 Mechanical Compliance Certificate 90.1 (2007) Standard Section 1: Project Information Project Type: New Construction Project Title : Rudy's Star Motors Construction Site:

More information