SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003

Size: px
Start display at page:

Download "SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003"

Transcription

1 SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved SCO # 1Punch listed items were noted below on October 16, ALL items listed below we're not found to be completed during our site visit on November 4, 2014: General notes: 1 Mechanical 1. Provide 2 inch air gap on all condensate drains in closets and tighten condensate piping. 6 Mechanical 2. Fire alarm system is not monitored. No phone line. Completed checked 11/04/ Electrical 3. ALL Wiring device plates MUST be leveled throughout project. Completed checked 11/04/ Electrical 4. Provide ID numbers on breakers in ALL electrical panels. 5 Electrical 4. Clean bottoms of ALL electrical panels. Completed checked 11/04/ Electrical 5. Clean ALL transformers. 7 Electrical 6. Clean light fixture lens. 8 Electrical 7. Set ALL OC sensors to maximum time. Completed checked 11/04/ Plumbing 8. Adjust mixing valves on ALL sinks. Completed checked 11/04/ Electrical 9. Device labels shall not be installed over cover plate screws. Completed checked 11/04/ Plumbing 11. Clean ALL return and exhaust grills. 12 Plumbing 12. Remove ALL galvanized straps from domestic water copper piping and install insolation support straps. 13. Provide moisture switches in ALL HVAC drain pans 13 Plumbing as per construction documents. Float switches are not acceptable. 14 Electrical 14. Electrical shall schedule lighting control vender to program and provide Owner training. 15. HVAC contractor and controls shall schedule date 15 Mechanical with Owner for Owner training. Provided signed letter from Owner that training was performed. Completed checked 11/04/2014

2 16 Electrical 16. Electrical contractor shall schedule date with Owner for fire alarm, CCTV, access control and electrical systems Owner training. Provide signed letter from Owner that training was performed. 17 Electrical 17. Electrical shall provide third party infrared scanning report of switchboards and panel boards no more than 60 days after building is occupied. See specification sections & Electrical 18. Provide duct detectors above ceiling in corridor and ceiling mounted test switches for ACU-8. See mechanical equipment schedule key note Electrical 19. CCTV cameras could not be tested no IP address provided by Owner. Completed checked 11/04/ Access control system was operation properly. Completed checked 10/16/14 East entrance lobby: 21 Electrical Replace broken fixture lens. 22 Electrical Level fire alarm annunciator. Custodian Fire Protection Fire protection shall provide exterior water motor alarm bell. Completed checked 11/04/2014 CR 101: 24 Fire Protection Sprinkler head does cover hole in ceiling tile. 25 Mechanical Tiles wet around supply air grills. Completed checked 11/04/ Mechanical Clean supply air grills. 27 Electrical Lamp out in light fixture. 28 Mechanical Provide duct liner on floor of return air plenums. 29 Mechanical Insulate ALL condensate drains. DATA 103: 30 Electrical Seal inside 4 inch conduits penetrating floor. Completed checked 11/04/ Plumbing Provide cover plate on clean out. Workroom 106: 32 Plumbing No hot water on building. Completed checked 11/04/ Plumbing Tighten mixing valve on sink. Office 105: 35 Electrical Ballast cover off on light. Office 107: 36 Electrical Light fixture is not setting in ceiling grid properly. 37 Electrical OC sensor is not covering hole in ceiling tile. Office 108: 38 Electrical OC sensor does not appear to be working properly. Completed checked 11/04/ Electrical OC sensor is not covering hole in ceiling tile. 40 Electrical Clean paint from fire alarm strobe in restroom. 41 Electrical Trap primer not working in restroom Completed checked 11/04/2014 Main office Electrical Ballast cover dropped down on emergency fixture. 43 Mechanical Wet tile at supply grill. Completed checked 11/04/2014

3 Conference 109: 44 Electrical OC sensor not working. 45 Electrical Loose receptacle on east wall. Library Mechanical Wet tile in ceiling by supply air grill. Completed checked 11/04/ Fire Protection Excusion missing on sprinkler head. 48 Electrical Holes cut to large for can lights over desk. 49 Mechanical Repair or replace supply grill at desk. 50 Plumbing Tighten toilet seat and caulk around toilet. 51 Electrical GFCI does cover wall opening in restroom. 52 Mechanical Straight bent supply grill at north desk. 53 Electrical Add one ceiling mounted smoke detector in library area. Vault Electrical Provide two light fixtures per drawings. Completed checked 11/04/ Storage Electrical Light not working. Completed checked 11/04/ Electrical Provide two light fixtures per drawings. Completed checked 11/04/2014 Office 114: 58 Electrical Lights not working. Completed checked 11/04/2014 Electrical Fixture lens missing and broken. North mechanical platform: 60 Plumbing Relocate water heater WH-2 to provide access to ERV. 61 Mechanical Repair duct insulation at ERV. Completed checked 11/04/ Electrical Install duct detectors in ERV-5. Completed checked 11/04/2014 Male restroom. 63 Plumbing Caulk around toilet. Completed checked 11/04/2014 Female restroom: 64 Plumbing Caulk around toilets. Completed checked 11/04/2014 Exterior: 65 Electrical CCTV cameras MUST be installed with no gaps showing between mounting plate and wall at west entrance. 66 Mechanical Repair suction line pipe insulation on CU Mechanical DCU- 1 appears to be short cycling on and off. 68 Mechanical Repaint top of DCU Electrical Provide emergency fixture type 10 at north and south Completed checked 11/04/2014 exit corridor doors as indicated on drawing E Mechanical Clean dirt from around CU-1 & 2. Completed checked 11/04/ Electrical Cupola lights have not been installed. 72 Electrical In ground fixtures type 22 have moisture in ALL fixtures. Contractor shall seal fixtures properly. Completed checked 11/04/ Electrical Provide screws on access covers of in ground lights type 22.

4 74 Electrical One in ground light type 22 was not working. 75 All Remove construction materials and debris around CU- 7. Completed checked 11/04/ Electrical Provide emergency fixture type 10 at East exit doors as indicated on drawing E2.1 Fire protection contractor shall install broken sprinkler head on inspectors test Completed checked 11/04/2014 pipe. Life safety items Fire alarm and emergency lighting was not completed therefore building is not substantially complete. ALL punch list items marked and initialed completed prior to scheduling another site visit by engineer. Punch list Items 1-28 below were noted November 4, 2014: Electrical 77 Electrical 1. Over door emergency light out on south west exit door of rotunda. 78 Electrical 2. Provide test switches on duct detectors for ACU Electrical 3. FP flow initiated alarm in 10 seconds. 80 Electrical 4. provide smoke detector in library classroom. 81 Electrical 5. Provide TVSS protection on PIV. 6. Fire alarm horns and strobes were tested and working properly. 82 Mechanical 7 AHU - 8 MUST shut down on fire alarm initiation. 83 Electrical 8. Provide plastic covers with integral alarm to sound when cover is removed on ALL pull stations. 84 Electrical 9. Exterior emergency light not working on south exit. 85 Electrical 11. North west and south west exits doors emergency lights are not working. 86 Electrical 12. East exit doors emergency door emergency lights not working. 87 Electrical 13. Emergency light not working in male toilet. 88 Electrical 14. Emergency light at north exit door not working. 89 Electrical 15. Emergency can light not working at library entrance. Light does cover ceiling opening. 90 Electrical 16. Repair lens on fixture type 21 at front entrance. 91 Electrical 17. Over head can light not working in front canopy. 92 Electrical 18. Provide added smoke detector in library per drawings. 93 Electrical 19. Camera 10 in Rotunda is not clear correct. 94 Electrical 20. Provide conveyance outlets on center equipment platform per plans. 95 Mechanical 21. Siemens controls has not completed graphics on new system. New building is connected to schools computer.

5 96 Electrical 22. Door release button has not been installed at APP phone master station. 97 Electrical 23. Relocate disconnect on ACU - 7 to accessible location. 98 Mechanical 24. Provide duct liner in bottom return air plenums of ACU- 1 & Plumbing 25. Relocate water heater and water & vent piping on south mechanical platform to provide access to ERV-5 & ACU Mechanical 27. Install KO plug in DHU-1 control panel. 101 Mechanical 28. Install HVAC condensate trap drains per detail sheet M4.2.

Florence High School / Middle School Page 1 of 3 Florence, WI

Florence High School / Middle School Page 1 of 3 Florence, WI Florence High School / Middle School Page 1 of 3 Florence, WI Plumbing Systems Review: The following report is the result of a site visit by Tim Kehoe of Muermann Engineering, LLC that occurred on October

More information

Library stacks and records storage 150 LB/SF live load

Library stacks and records storage 150 LB/SF live load SPACE TYPE: LIBRARY Construction Criteria The unit costs for Library space types are based on the construction quality and design features in the following table. This information has been generally organized

More information

SPACE TYPE: JUDICIAL CHAMBER

SPACE TYPE: JUDICIAL CHAMBER SPACE TYPE: JUDICIAL CHAMBER Construction Criteria The unit costs for Judicial Chamber space types are based on the construction quality and design features in the following table. This information has

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 174 - QUEENS, 65-10 DIETERLE CRESCENT, New York, 11374 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-01-25

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: NEW SCH FOR ARTS AND SCIENCE - X, 965 LONGWOOD AVENUE, New York, 10459 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-01 8:13 AM 2017-12-01

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 59 ANNEX - BRONX, 2120 QUARRY RD, New York, 10457 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-02-12

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 127 - BROOKLYN, 7805 7 AVENUE, New York, 11209 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-30

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 135 - QUEENS, 207-11 89TH AVENUE, New York, 11427 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 314 - BROOKLYN, 330 59 STREET, New York, 11220 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-23

More information

Appendix B. Facilities Assessment Report

Appendix B. Facilities Assessment Report Mile Lane Army Reserve Center Redevelopment Plan September 2008 Appendix B Facilities Assessment Report RKG Associates, Inc. Mile Lane Army Reserve Base Middletown, CT MEP System Evaluation For RKG Associates

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 86 - BROOKLYN, 220 IRVING AVENUE, New York, 11237 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-14

More information

NYC Department of Education

NYC Department of Education Asset: P.S. 5 - BROOKLYN, 820 HANCOCK STREET, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-25 8:54 AM 2018-06-04 10:18 AM Asset Data Type of Service Does Interactive

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 131 - QUEENS, 170-45 84TH AVENUE, New York, 11432 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-18

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 81 ANNEX (OLD 75) - QUEENS, 511 SENECA AVENUE, New York, 11385 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 310 - BRONX, 260 WEST KINGSBRIDGE RD, New York, 10463 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-07

More information

S AGE E NGINEERING A SSOCIATES, LLP

S AGE E NGINEERING A SSOCIATES, LLP S AGE E NGINEERING A SSOCIATES, LLP 1211 Western Avenue Albany, NY (518) 453 6091 F (518) 453 6092 Kingston Library Mechanical and Electrical Systems Field Report Date of Visits: Mechanical - September

More information

Beaufort County Community College. Maintenance and House Keeping Plan

Beaufort County Community College. Maintenance and House Keeping Plan Beaufort County Community College Maintenance and House Keeping Plan Summary: The College s facility management is handled by the Maintenance Department. The Director of Plant and Maintenance Operations

More information

SPACE TYPE: CHILD CARE

SPACE TYPE: CHILD CARE SPACE TYPE: CHILD CARE Construction Criteria The unit costs for Child Care Center space types are based on the construction quality and design features in the following table. This information has been

More information

PLATTEVILLE MIDDLE SCHOOL

PLATTEVILLE MIDDLE SCHOOL Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle

More information

INSTALLATION OF ACCESS FLOOR SYSTEMS IN GENERAL OFFICE AREA AND COMPUTER ROOM

INSTALLATION OF ACCESS FLOOR SYSTEMS IN GENERAL OFFICE AREA AND COMPUTER ROOM INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: Mech Code 601 Effective: 2-07-79 DOCUMENT NO. P/BC 2002-018 Revised: 9-25-03 Previously Issued As: RGA 2-79, MGD101 INSTALLATION OF ACCESS FLOOR

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 56 - STATEN ISLAND, 250 KRAMER AVE., New York, 10309 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-20

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: PS 152 ANNEX -BROOKLYN, 1087 OCEAN AVENUE, New York, 11210 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-03-20

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: HS OF AMERICAN STUDIES - BRONX, 2925 GOULDEN AVENUE, New York, 10468 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS

Sprinkler: The building does not have a fire protection system installed. MECHANICAL / PLUMBING / SPRINKLER SYSTEMS RECOMMENDATIONS EXISTING MECHANICAL CONDITIONS SUMMARY The items listed below are based on our site visit on Nov 10, 2016. Our review is based on current conditions and anticipated future use of these building. In the

More information

NYC Department of Education

NYC Department of Education Asset: LEARNING SUPPORT CENTER - K, 1665 ST. MARKS AVENUE, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-07 1:06 PM 2018-05-10 12:20 PM Asset Data Type of Service

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: HS FOR MATH, SCI & ENGINEERING-M, 240 CONVENT AVENUE, New York, 10031 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-12-20 11:37 AM 2018-01-09

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 47 - QUEENS, 9 POWER ROAD, New York, 11693 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-20 12:40

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: PRE-K CENTER @ 107-17 NORTHERN BOULEVARD - QUEENS, 107-17 NORTHERN BOULEVARD, New York, 11368 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

Steve Ramsey Home Inspections

Steve Ramsey Home Inspections Steve Ramsey Home Inspections I. STRUCTURAL SYSTEMS X A. Foundations Type of Foundation(s): Slab Foundation There is evidence of some foundation movement. Excessive caulk around windows, mortar and brick

More information

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.

Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc. Memphis Housing Authority High Rise Fire Alarm Upgrades Questions from Contractors (Through Addendum #2) Communications Systems, Inc.: Legend 1. DL - Dome light symbol should be on the tenant emergency

More information

FAIRA TRANSPARENCY REPORTS NE 117th Pl, #F8, Kirkland, WA 98034

FAIRA TRANSPARENCY REPORTS NE 117th Pl, #F8, Kirkland, WA 98034 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 12527 NE 117th Pl, #F8, Kirkland, WA 98034 Thank you for your interest in this Faira Certified

More information

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY ARCHITECTURE ROLLING HILLS ELEMENTARY SCHOOL Rolling Hills Elementary was built in 1999 and is the newest addition to the Mukwonago Area School District. The building contains approximately 64,900 gross

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED

VOTER BOND REFERENDUM 2018 SUMMARY OF WORK PROPOSED Ashton Elementary School 1 Masonry Repair $ 42,781.50 2 Replace HVAC $ 375,000.00 3 Replace SAT @ Various Locations $ 92,364.00 3 Recoat & Resurface Exterior Paved Play Area $ 135,978.30 3 Various Technological

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 184 - QUEENS, 163-15 21 ROAD, New York, 11357 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-05 11:46

More information

2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect

2 Main Office Building BLDG-955A Building Purpose Building Area Administration offices. Training room 7,610 SF Inspection Date August 16, 2016 Inspect 1 Site Summary Address 7200 Bluff Springs Road Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 2014 Total Campus Building Area (combined) 25,314 SF Introduction The

More information

ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING

ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING Mechanical Systems Information The mechanical system at Reed Middle School is comprised of seventy six Trane DX/Gas rooftop units (RTUs). The recommended useful life for DX equipment is 15 years. Seventy

More information

PENNSYLVANIA. Downloaded

PENNSYLVANIA. Downloaded Housekeeping/Laundry/Maintenance 205.26. Laundry. PENNSYLVANIA Downloaded 01.15.11 (a) A laundry room shall be provided in a facility where commercial laundry service is not used for the washing of soiled

More information

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

Maintence/Renewal Report

Maintence/Renewal Report Maintence/Renewal Report Property Address: C4U Inspections Lloyd Kenzle CPBC # 47652 3518 Webber Rd. West Kelowna, BC V4T 1H9 866 765-4434 Table of Contents Cover Page... 1 Table of Contents...2 I SUMMARY...

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1

Michigan State University DESIGN GUIDELINES. ELECTRICAL DESIGN Page 1 TABLE OF CONTENTS 1 Page 1 TABLE OF CONTENTS 1 ELECTRICAL 2 Summary Sustainability Electrical Distribution Lighting Detection and Alarm Communication Systems Lightning Protection Clock Systems Access Control Housekeeping

More information

Troy's Home Inspection Services LLC

Troy's Home Inspection Services LLC Cover Page Property Inspection Report 33706 Inspection prepared for: Cord King & Patricia King Real Estate Agent: Jane Freel - RE/MA Date of Inspection: 3/4/2017 Time: 8:30 Age of Home: 2008 Size: 3279

More information

DRAFT. Widen Elementary School Site Summary 74,523 SF. Introduction

DRAFT. Widen Elementary School Site Summary 74,523 SF. Introduction 1 Widen Elementary School Site Summary Address 5605 Nuckols Crossing Austin, TX 78744 Number of Permanent Campus Facilities 2 Original Year of Construction 1986 Total Campus Building Area (combined) 74,523

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 69 PORTABLE - QUEENS, 77-02 37TH AVENUE, New York, 11372 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-04-24 8:36 AM 2018-05-16

More information

FAIRA TRANSPARENCY REPORTS Stone Ave N, #205, Seattle, WA 98133

FAIRA TRANSPARENCY REPORTS Stone Ave N, #205, Seattle, WA 98133 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 11550 Stone Ave N, #205, Seattle, WA 98133 Thank you for your interest in this Faira Certified

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: I.S. 364 - BROOKLYN, 1426 FREEPORT LOOP, New York, 11239 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-11-16

More information

Appendix E: Photo Documentation

Appendix E: Photo Documentation Appendix E: Photo Documentation Brown County Library Central Branch Building Assessment Appendix E: Photo Documentation Architectural and Structural Brown County Library Central Branch Building Assessment

More information

Calmeca Academy of Fine Arts and Dual Language

Calmeca Academy of Fine Arts and Dual Language Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 371 (OLD 615) - BROOKLYN, 355 37 STREET, New York, 11232 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2017-10-23

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 80 AX(PETR COMPL-BLDG E)-S.I., 715 OCEAN TERRACE, New York, 10301 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

George B Swift Elementary Specialty School

George B Swift Elementary Specialty School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: DIV. COMPUTER INFO-DATA CENTER-K, 2 METROTECH CENTER, New York, 11211 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

Canadian Property Inspections

Canadian Property Inspections Cover Page Canadian Property Inspections Home Inspection Report N6J-3A8 Inspection prepared for: Josh Baran Date of Inspection: 3/7/2017 Time: 9am Age of Home: 40 Size: 1500 Weather: Cloudy,cool,light

More information

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL DISTRIBUTION SYSTEM:?? The existing electrical service consists of an underground primary service originating at a utility pole on Cedar Street,

More information

Inspection Report. 1 Inspection Way Orlando, FL Prepared for: Wanda Figueroa Prepared by: ACF Home Inspections Inc

Inspection Report. 1 Inspection Way Orlando, FL Prepared for: Wanda Figueroa Prepared by: ACF Home Inspections Inc Inspection Report 1 Inspection Way Orlando, FL 32825 Prepared for: Wanda Figueroa Prepared by: Page 1 of 25 Needs Service Summary This summary is not the entire report. The complete report may include

More information

FAIRA TRANSPARENCY REPORTS. November 21, 2016

FAIRA TRANSPARENCY REPORTS. November 21, 2016 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 7307 22 nd Ave NW, Seattle, WA

More information

20/20 Home Inspections. Photo Attachments

20/20 Home Inspections. Photo Attachments Page 1 of 9 Damaged roof shingles. Improper rof shingle installation; improper overlapping. Improper layout. Improper flashing at plumbing vent stack. Wrong size jack. No storm collar. Improper installation

More information

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire

Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Module number 8 provides an on-line, self-paced training seminar on portions of Chapter 14-Fuel Gas, Chapter 25-Ohio Plumbing Code; Chapter 29-Fire Suppression Systems; and Chapter 34-National Electric

More information

JANITORIAL SPECIFICATIONS

JANITORIAL SPECIFICATIONS JANITORIAL SPECIFICATIONS A. Office Areas 1. Empty and wipe outside wastebaskets, replacing liners, if necessary. Remove to appropriate receptacle for disposal. All bins will be returned to their original

More information

Forest Hills Facilities Plan

Forest Hills Facilities Plan Forest Hills Facilities Plan Extensive updates to 8 of our 9 schools Replace Wilson Elementary Enhance learning environments across the district Build additional classrooms to accommodate gradual implementation

More information

Richard Henry Lee Elementary School

Richard Henry Lee Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

General Kitchen, Bath & Bedroom Remodeling Notes County of Marin, Building Inspection Division

General Kitchen, Bath & Bedroom Remodeling Notes County of Marin, Building Inspection Division These Notes are intended to assist in issuing simple remodel permits. It provides information on the most common requirements relating to the construction or remodeling of kitchens, bathrooms and bedrooms.

More information

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on HOME PROPERTY SCAN INSPECTIONS The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on January 11, 2010 and

More information

FAIRA TRANSPARENCY REPORTS st Ave, #605, Seattle, WA June 2 nd, 2017

FAIRA TRANSPARENCY REPORTS st Ave, #605, Seattle, WA June 2 nd, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 1107 1st Ave, #605, Seattle, WA

More information

3. 21st Century Learning A. Districtwide Flexible Learning - Allowance for Flexible Furniture $600,000 Subtotal $600,000

3. 21st Century Learning A. Districtwide Flexible Learning - Allowance for Flexible Furniture $600,000 Subtotal $600,000 1. Safety and Security A. Additional Cameras District Wide $382,000 B. Interior Locks Upgrades Allowance $300,000 C. Tilden Entrance Upgrades D. Door and Glass Improvements Allowance $500,000 E. Alert

More information

900 N. Via Piemonte Ontario, CA

900 N. Via Piemonte Ontario, CA 2 3 L 8 5'-0" 6'-1" 5'-0" 4'-0" 2'-0" D.5 6" 9'-9" K 2 1 2 " 5'-0" 2'-0" 1'-2" 8" 4 4.3 7'-0" C.6 1'-8 1 2 " 7'-0" 8" 10'-6" 5'-0" 8" 6" 6'-6" 6'-3" PLUMBING SCOPE OF WORK - DRAINS 7'-3" 6'-8" KEC TO PROVIDE:

More information

Mechanical Inspection Plumbing

Mechanical Inspection Plumbing 0811 Fixtures Sinks, drinking fountains, water closets, showers, etc. Classroom Sinks. Classroom sinks (19) are enameled cast iron self rimming side ledge with gooseneck faucet trim with index handles,

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: FRANCIS LEWIS HS TRANSPORTABLE - Q, 58-20 UTOPIA PARKWAY, New York, 11365 Inspection Id Inspection Type Time In Last Edited EE :

More information

Technical Report Two

Technical Report Two Technical Report Two Yale Sculpture Building Advisors: Ted Dannerth Richard Mistrick Date: October 31, 2006 Electrical Systems Existing Conditions and Building Load Summary Report Executive Summary: This

More information

Cleaning Service Levels

Cleaning Service Levels Restrooms Empty waste receptacles and change liner, as needed. Restock dispensers: soap, paper towel and toilet tissue. Clean mirrors; clean and disinfect urinals, toilets, and sinks. Polish stainless

More information

CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN

CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN 04.13.2017 1 MONTICELLO INTERIOR FINISHES PAINT MOULDING WALLS ACCENT DOORS DOOR TRIM/STAIRS

More information

NYC Department of Education

NYC Department of Education NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 138 AX (CROWN HGTS ECC 1)-K, 960 PROSPECT PLACE, New York, 11216 Inspection Id Inspection Type Time In Last Edited EE : Electrical

More information

7/14/2016 CITY HALL ADA ENHANCEMENT/REMODEL ACTION PLAN 1978 Construction

7/14/2016 CITY HALL ADA ENHANCEMENT/REMODEL ACTION PLAN 1978 Construction CITY HALL ADA ENHANCEMENT/REMODEL 2016 ACTION PLAN 1978 Construction 1 HISTORY At the February 2, 2016 Council Workshop Council Motions included: The direction to staff to move forward with the City Hall

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

Food needs to be in sealed containers 03. FOOD: Unsealed, left in

Food needs to be in sealed containers 03. FOOD: Unsealed, left in 01A. ODOR: Unusual or 6/14/2017 14:15offensive Boys room Urine smell 01A. ODOR: Unusual or 6/14/2017 15:16offensive Office Odor and poor air flow x 01B. TEMPERATURE: 6/14/2017 13:42Uncomfortable 202 Warm

More information

Axiom Property Inspections

Axiom Property Inspections Cover Page Axiom Property Inspections Property Inspection Report 868 Wally Avenue, Henderson NV, 89178 Inspection prepared for: John Doe Agent: David Lawson - Axiom Inspection Date: 8/12/2010 Time: 2:30

More information

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM SUMMARY 1234 Main St.Severn 21144 Buyer Name 07/18/2018 9:00AM Henry Toman MD License 32391 1st American Home Inspection, LLC 443-685-4062 henrytoman61@gmail.com The summary is meant to organize the defects

More information

ALLISON ELEMENTARY SCHOOL 4315 Don Julio Blvd., North Highlands, CA 95660

ALLISON ELEMENTARY SCHOOL 4315 Don Julio Blvd., North Highlands, CA 95660 ALLISON ELEMENTARY SCHOOL 4315 Don Julio Blvd., North Highlands, CA 95660 Year Built 1960 // Age 58 years Building Area 31,688 Square Feet Student Capacity 389 Current Enrollment (2017-2018) 466 Priority

More information

Francis M McKay Elementary School

Francis M McKay Elementary School Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

DAMAGE CODES* CODE DAMAGE COST

DAMAGE CODES* CODE DAMAGE COST 2017-2018 DAMAGE CODES* CODE DAMAGE COST # CODE 100 DOORS 100 DOORS 101 DOOR JAMB REPAIR/REPLACEMENT 250 200 KEYS 102 DOOR KNOB SET REPLACEMENT (APTS) 120 300 WINDOWS 103 DOOR KNOB SET REPLACEMENT (RH)

More information

ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING

ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING Mechanical Systems Information The mechanical system at Duncanville High School is comprised entirely of DX/Gas rooftop units (RTUs) and DX split systems. A vast majority of the RTUs are Trane units that

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. Description of the building system The school is equipped with a hard wired fire alarm control panel, and automatic dialer. The fire alarm

More information

Division of Health Service Regulation STATEMENT OF DEFICIENCIES AND PLAN OF CORRECTION

Division of Health Service Regulation STATEMENT OF DEFICIENCIES AND PLAN OF CORRECTION SUMMARY PROVER'S PLAN OF CORRECTION J 000 Initial Comments J 000 Roger McCoy, Charles Brown, Chris Wood and Jeff Harms conducted the inspection. Roger McCoy was the lead inspector. This bi-annual jail

More information

The Salvation Army Southern Territory OFFICERS QUARTERS PROPERTY INSPECTION FORM

The Salvation Army Southern Territory OFFICERS QUARTERS PROPERTY INSPECTION FORM The Salvation Army Southern Territory OFFICERS QUARTERS PROPERTY INSPECTION FORM Property Address: Age of Quarters: Years Date of Inspection: INSPECTION TEAM: Names: Profession/Position (i.e. Board Member,

More information

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010 An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010 Putnam County Planning & Development Services Building & Zoning Division Compliance Section PO Box 1486 Palatka, FL 32178 1486 Office

More information

Bay Wide Commercial and Home Inspection Thackeray Avenue/ Mail address Hayward, Calif TH AVENUE SAN LEANDRO, CALIFORNIA

Bay Wide Commercial and Home Inspection Thackeray Avenue/ Mail address Hayward, Calif TH AVENUE SAN LEANDRO, CALIFORNIA 27966 Thackeray Avenue/ Mail address Hayward, Calif. 94544 2011 150TH AVENUE SAN LEANDRO, CALIFORNIA 21:12 August 07, 2015 Page 1 of 11 Table of Contents Definitions 2 General Information 2 Lots and Grounds

More information

PREPARED FOR: (Name of Client) CONCERNING: (Address of Property) BY: P Home. YOUR HOME CHECK 1305 FM 359, Suite G F

PREPARED FOR: (Name of Client) CONCERNING: (Address of Property) BY: P Home. YOUR HOME CHECK 1305 FM 359, Suite G F PREPARED FOR: l (Name of Client) CONCERNING: (Address of Property) BY: (Name of Technician) (Consultation Date) YOUR HOME CHECK 1305 FM 359, Suite G Richmond, TX 77469 P 281-342-Home F 281-342-4669 I.

More information

Habitability Guidelines

Habitability Guidelines Habitability Guidelines for Relocated Manufactured Homes dced.pa.gov/mh @PADCEDnews Purpose The purpose of these habitability guidelines is to provide a reasonable level of assurance that the relocated

More information

BURLEIGH MANOR MIDDLE SCHOOL HOWARD COUNTY PUBLIC SCHOOL SYSTEM

BURLEIGH MANOR MIDDLE SCHOOL HOWARD COUNTY PUBLIC SCHOOL SYSTEM BURLEIGH MANOR MIDDLE SCHOOL HOWARD COUNTY PUBLIC SCHOOL SYSTEM Built in 1992 108, 407 Square Feet 771 Student Population 91 Staff Population 2 Building Supervisors, 3 Custodians 102, 663 Square Feet of

More information

Port of Portland Conveying Equipment Guidelines

Port of Portland Conveying Equipment Guidelines Role: Consultant for the Port Design Guidelines Port of Portland Conveying Equipment Guidelines ELEVATOR, ESCALATOR, AND MOVING WALK DESIGN OVERVIEW The Division 14 specification sections include appropriate

More information

SUMMARY 1234 Main St.Edmonton AB T5T3E9 Buyer Name 07/05/2018 9:00AM

SUMMARY 1234 Main St.Edmonton AB T5T3E9 Buyer Name 07/05/2018 9:00AM SUMMARY 1234 Main St.Edmonton AB T5T3E9 Buyer Name 07/05/2018 9:00AM Banti Shaw InspecUs InspecUs 7808623549 bantishaw@inspecus.ca This Summary outlines potentially significant issues from a cost, safety

More information

I. STRUCTURAL SYSTEMS

I. STRUCTURAL SYSTEMS I. STRUCTURAL SYSTEMS A. Foundations Type of Foundation(s): Pier & Beam - Crawlspace Opinion: All exposed areas of the foundation were examined visually. Examination of the foundation was limited to photographs

More information

Sagebrush Elementary School East Temple Place Aurora, Colorado 80015

Sagebrush Elementary School East Temple Place Aurora, Colorado 80015 Sagebrush Elementary School 14700 East Temple Place Aurora, Colorado 80015 Year Opened 1977 Current Square Footage 57,100 Site Acreage 7.66 sagebrush.cherrycreekschools.org Asphalt and concrete work; electrical

More information