1 CERTIFICATE OF APPROVAL No. ME 5005 PO Box 22436, Industrial Area 13,Sharjah, UAE Tel: Fax: Website: Have been assessed against the requirements of the Technical Schedule(s) denoted below and are approved for use subject to the conditions appended hereto: CERTIFIED PRODUCT FM200 Fire Suppression System (comprising the components as listed) BRAND NAME TEST STANDARD NFPA Standard on clean agent fire suppression systems FIREX, AQUAPLUS, FIRE BELL, FIRE TECH, FIRST, GUARD, JOFFCO, OMEGA, POWER, SOS INTERNATIONAL, TORNADO, TRI STAR FIREX 200 PRODUCT REFERENCE FIREX 200 Signed and sealed for and on behalf of Warrington Certification Ltd Sir Ken Knight Issued: 8 th April 2012 Chairman - Management Council Page 1 of 5
2 Approval Information: 1. The performance relates only to the behaviour of the specimen under the particular conditions of test. They are not intended to be the sole criteria for assessing performance in use, nor do they reflect the actual behaviour in fires. 2. The approval relates to on-going production. Products shall be identified with the certification mark including the certification number, and the manufacturer s name and the product name or code reference. 3. This approval is applicable to complete systems only. 4. For verification of the validity of this certificate or inspection of installed systems, please contact Warrington Certification Ltd. Page 2 of 5 Signed Issued: 8 th April 2012
3 Certification Evidence: 1- Certification File No. FX Previous Exova Certification and Inspection certificate No. 02A FX Product Description and Performance: 1 FM200 (HFC-227ea) Total Flooding Fire Extinguishing Systems are engineered or preengineered total flooding or local application gaseous fire suppression systems. The systems consist of a storage pressure vessel or vessels that store the agent as a liquid and include assemblies designed for automatic and manual actuation, discharge assemblies, manifold check valves, selector valves (depending on the system requirements) and discharge nozzles. The storage cylinders are super-pressurised with nitrogen to discharge the agent and to provide a two phase flow through pipework reticulation with gas being distributed via nozzles within the protected enclosure. 2 The system discharge is initiated via a fire detection system that electronically operates the storage cylinder s discharge valve (the valve is a differential pressure valve that can be reused following system discharge). 3 The assembled systems are intended to be designed and installed in accordance with the manufacturer s design, installation and maintenance manual based on the listed flow calculation software program and complying with the relevant design standards adopted in the jurisdiction of installation by the AHJ. 4 The HFC-227Ea system design and installation shall be undertaken in full accordance with a verified pre-engineered design manual or empirical calculation. Further, these systems must be designed only by FIREX by approved and trained design engineers. 6 HFC-227ea - Agent concentration in the design application or enclosure shall not exceed the concentration limitations listed in NFPA 2001 with NFPA, NOAEL and LOAEL concentrations being based on the toxicological effect known as cardiac sensitization. 7 Marine Applications - The use of FM200 systems for marine applications is excluded. Page 3 of 5 Signed Issued: 8 th April 2012
4 System Components: Components Manufacturer / Supplier Reference / Description Agent Tanks ( lbs) FIREX HFCY001 (A to E) Design Software Megadragon Software Development Company Ltd. FMCAD Releasing Panel Mircom FR320-Series FM200 Agent ShanggaiWaymos HFC 227EA Manual Release Unit FIREX FXMRS017 Abort Switch FIREX FXAS 015 System Brackets and Straps FIREX Warning Name Plate FIREX FXWS018 Gas Discharge Nozzles 180/360 FIREX FXDN013 / FXDN014 Discharge Valve Ceodeux B0481 / B0482 Double Knock Releasing Panel Mircom FR-320 Optical Smoke Detector Mircom MIR-318 Break Glass Mircom MS-700U Fire Alarm Bell 6 Mircom BL-6A Horn with Strobe Mircom FHS-240 Fire Resistance Cable FIREX FIREX Page 4 of 5 Signed Issued: 8 th April 2012
5 Approved Manufacturing Locations: Emirates Fire Fighting Equipment Factory LLC (FIREX) PO Box 22436, Industrial Area 13, Sharjah UAE. Page 5 of 5 Signed Issued: 8 th April 2012
CERTIFICATE OF APPROVAL No. ME 5008 EMIRATES FIRE FIGHTING EQUIPMENT FACTORY LLC (FIREX)
EWCL 5 CERTIFICATE OF APPROVAL No. ME 5008 PO Box 22436, Industrial Area 13, Sharjah, UAE Tel: +971 6 5340300 Fax: +971 6 5340090 Website: www.firexuae.com Have been assessed against the requirements of
More informationSPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM
1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected.
More informationCERTIFICATE OF APPROVAL No ME 5085
CERTIFICATE OF APPROVAL No ME 5085 1 Suite No. 52, 5 th Floor, Martin Burn Building, 1 RN Mukherjee Road, Kolkata- 700001 (West Bengal), India Tel: +91 33 40276600 Have been assessed against the requirements
More informationCERTIFICATE OF APPROVAL No CF 5236 EMVER PAINTS INDUSTRIES LLC
CERTIFICATE OF APPROVAL No CF 5236 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Jebel Ali Industrial
More informationGAS FLOODING SYSTEM FOR CIFF AT BASEMENT
CONSTRUCTION OF BUILDINGS FOR LABORATORIES AND ASSOCIATED FACILITIES INSTEM BANGALORE SCHEDULE OF QUANTITIES FOR (EQUIPMENT ROOM 3 & 4) Sl.No. Description Unit Quantity Rate (in INR) in figure HFC-227ea
More informationENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
More informationCERTIFICATE OF APPROVAL No CF 392 EXIDOR LIMITED
CERTIFICATE OF APPROVAL No CF 392 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Progress Drive, Cannock,
More informationA. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.
1. GENERAL SPECIFICATION 1.1 A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationSPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection
1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in
More informationNFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless
More informationSECTION FM-200 FIRE SUPPRESSION SYSTEM
SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to
More informationFIRE SUPPRESSION SYSTEM
FIRE SUPPRESSION SYSTEM An effective fire suppression systems work fundamentally in three ways; The corner stone has to be an efficient means of early warning/detection. Followed by either an Oxygen reduction
More informationTechnologies Gas extinguishing systems. MX 200 Fire Extinguishing Systems Fighting Fire using HFC-227ea
Technologies Gas extinguishing systems MX 200 Fire Extinguishing Systems Fighting Fire using HFC-227ea ire protection Efficient and compact MX 200 fire extinguishing systems fight fires using HFC-227ea.
More informationHospitals and Major Medical Centers
Hospitals and Major Medical Centers INERGEN Fire Suppression Systems AUTOPULSE Detection and Control Equipment SENTRY Hand Portable Fire Extinguishers Medical centers have special concerns for fire safety
More informationSPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM
1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 21 2400CA - CLEAN AGENT CHEMICAL SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationCertificate of Conformity Certificate num. Registration date Version Valid until
CSIRO Verification Services Highett, Victoria, Australia +61 (0)3 9252 6000 http://www.activfire.gov.au/ Page 1 of 5 Issued by Product designation Tyco Safety Products, Sapphire, engineered, total flooding
More informationFM-200 In-Cabinet Series
1. GENERAL SPECIFICATION 1.1 A total flooding, In-Cabinet fire suppression system, employing FM-200 superpressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by
More informationCERTIFICATE OF FIRE APPROVAL
CERTIFICATE OF FIRE APPROVAL This is to certify that The product detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations and with the International Convention
More informationCertifiedSafetyPassion. CertifiedSafetyPassion. Distributors and UL AML
CertifiedSafetyPassion SAFETY HI - TECH. Founded in 1990, Safety Hi-Tech is a customer-focused provider of innovative fire suppression solutions, focusing on Clean Agent Extinguishing Systems. Safety Hi-Tech
More informationSPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND
1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation
More informationSafe, Effective, Environment-friendly
IG-55 (Argon/Nitrogen) Safe, Effective, Environment-friendly Introduction With the phase out of the most commonly used but environmentally damaging Halon 1301 and CO 2 fire suppressant, inert gases are
More informationAustralian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS
AS 4214 2002 (Incorporating Amendment No. 1) AS 4214 2002 Australian Standard Gaseous fire extinguishing systems This Australian Standard was prepared by Committee FP-011, Gaseous Fire Protection. It was
More informationCERTIFICATE OF APPROVAL No CF 520 ASSA ABLOY LTD T/A ASSA ABLOY SECURITY DOORS
CERTIFICATE OF APPROVAL No CF 520 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 21 Ferguson Drive,
More informationGUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS
12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety
More informationCERTIFICATE OF APPROVAL No CF 5507 CONSORT ARCHITECTURAL HARDWARE LTD
1 CERTIFICATE OF APPROVAL No CF 5507 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 29-31 Lower Loveday
More informationCERTIFICATE OF APPROVAL No CF 5038 FREEMAN & PARDOE T/A ARROW ARCHITECTURAL
CERTIFICATE OF APPROVAL No CF 5038 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Tything Road, Arden
More informationTechnologies Gas extinguishing systems. MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230
Technologies Gas extinguishing systems MX 1230 Fire Extinguishing Systems Fighting Fire using 3M Novec 1230 ire protection Efficient and compact MX 1230 fire extinguishing systems fight fires using Novec
More informationCERTIFICATE OF APPROVAL No CF 494 HOPPE (UK) LIMITED
CERTIFICATE OF APPROVAL No CF 494 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Gailey Park Industrial
More informationAmerex Clean Agent System with FM200. Potential Applications: System Coverage Overview: Approvals and Standards:
Amerex Clean Agent System with FM200 Utilizing the industry recognized FM-200 suppression agent, Amerex has developed an affordable pre-engineered clean agent fi re suppression system to protect areas
More information+91-8048763768 Cease Fire & Electrical Services http://www.ceasefireengineers.com/ We are the supplier, trader and service provider of fire alarm equipment, fire suppression system, fire detection system,
More informationCarbon Dioxide Fire Suppression Systems
Carbon Dioxide Fire Suppression Systems The original "clean agent," carbon dioxide suppresses fire without leaving behind water, foam or dry chemical to damage sensitive equipment. And because there is
More informationCERTIFICATE OF APPROVAL No CF 418 PROMAT UK LTD
CERTIFICATE OF APPROVAL No CF 418 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of The Sterling Centre,
More informationSECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM
SECTION 13966 TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM Display hidden notes to specifier by using Tools / Options / View / Hidden Text. PART 1 GENERAL 1.1 SECTION INCLUDES A. Total
More informationSinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea
s Data Sheet Fire Safety Products Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea ARCHITECT AND ENGINEER SPECIFICATIONS System Overview Sinorix
More informationCommittee Input No. 9-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement
Committee Input No. 9-NFPA 2001-2016 [ Global Input ] Incorporate revisions per the attached file. Supplemental Information File Name 2001-CI_9.pdf Description Data and specific revisions presented at
More informationCERTIFICATE OF APPROVAL No CF 252 GEZE UK LIMITED
CERTIFICATE OF APPROVAL No CF 252 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Blenheim Way, Fradley
More informationCERTIFICATE OF APPROVAL No CF 136
certifire CERTFCATE OF APPROVAL No CF 136 This is to certify that, in accordance with TSOOGeneral Requirements for Certification of Fire Protection Products The undermentioned products of lorent POl YPRODUCTS
More informationSPECIFICATION: ARGONITE Engineered Fire Suppression System
1. GENERAL SPECIFICATION 1.1 A total flooding, clean agent, fire suppression system, filled with Argonite agent shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationSTANDARDS FOR ACTIVE FIRE PROTECTION. Stewart Kidd Loss Prevention Consultancy Ltd
STANDARDS FOR ACTIVE FIRE PROTECTION Stewart Kidd Loss Prevention Consultancy Ltd This presentation will consider: The risks to both new and existing buildings which can be countered by active fire protection
More informationMAXIMUM KNOCKDOWN ABILITY Large Dry Chemical Fire Suppression Systems
MAXIMUM KNOCKDOWN ABILITY Large Dry Chemical Fire Suppression Systems ANSUL PIONEERED DRY CHEMICAL FIRE PROTECTION IN 1939, WHICH HELPED CREATE LARGE DRY CHEMICAL SYSTEMS WITH SUPERIOR FIREFIGHTING CAPABILITIES
More informationKidde Nitrogen Inert Gas Clean Agent Fire Suppression System
1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering
More informationCylinder Mortice Dead lock Lockcase(mm) A=87 Backset (mm) B=55. Follower (mm) 8 Latch Bolt
Product ID: KL.1902 Name: Cylinder Mortice Dead lock Lockcase(mm) A=87 Backset (mm) B=55 Centres C=N/A Follower (mm) 8 Latch Bolt N/A Mechanism Euro- Profile Forend Finish SSS Rebates available (mm) KL.1902A
More informationCLEAN AGENTS Updates to the NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2015 Edition
1 CLEAN AGENTS 2015 Updates to the NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2015 Edition APRIL 2015 M O-KAN SFPE CHAPTER M EETING APRIL 6, 2015 PRESENTED BY C. DAVIS & D. O DONNELL
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More informationD. Reference Standards (Utilize latest editions available):
1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fireextinguishing systems other than water-based fire suppression systems. This document is
More informationSECTION CLEAN AGENT FIRE SUPPRESSION SYSTEMS
SECTION 21 22 00 CLEAN AGENT FIRE SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTE: Delete between // --- // if not applicable to the project. Also delete any other item or paragraph
More informationCERTIFICATE OF APPROVAL No CF 5530 TALLERES DE ESCORIAZA S.A.U.
CERTIFICATE OF APPROVAL No CF 5530 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Barrio de Ventas
More informationTitle: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Indicative fire test WF Report
More informationReleasing Systems. Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd.
Releasing Systems Rob Mennie Senior Consultant Gage-Babcock & Associates Ltd. Releasing Systems What is a releasing system? System designed to detect a fire Causes release of an extinguishing system in
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More informationC E R T I F I C A T E O F C O M P L I A N C E
Issued to: SAFETY HI-TECH SRL VIA CAVOUR 96 67051 AVEZZANO AQ ITALY This is to certify that representative samples of CLEAN AGENT EXTINGUISHING SYSTEM UNITS See Addendum Have been investigated by UL in
More informationCERTIFICATE OF APPROVAL No CF 117 DORMA UK LTD
CERTIFICATE OF APPROVAL No CF 117 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Wilbury Way, Hitchin,
More informationDon t Compromise on Fire Safety Choose Certified Quality Products
Don t Compromise on Fire Safety Choose Certified Quality Products THERMO-ACT AUTOMATIC FIRE DETECTION AND SUPPRESSION Quick, Automatic Fire Detection and Suppression Superior Coverage and Suppress Fires
More informationCO2 COCO GAS FLOODING SYSTEM
PRE INTRODUCTION: CO2 COCO GAS FLOODING SYSTEM The importance of erection, testing and commissioning are overlooked, in many projects while installing fixed Co2 extinguishing system. It is very common
More informationCopyright 2013 Fike 12/13 SECTION CLEAN-AGENT FIRE-EXTINGUISHING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS
SECTION 212200 - CLEAN-AGENT FIRE-EXTINGUISHING SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationCertificate of Conformity Certificate num. Registration date Version Valid until
CSIRO Verification Services Highett, Victoria, Australia +61 (0)3 9252 6000 http://www.activfire.gov.au/ Page 1 of 5 Issued by Product designation Tyco Safety Products, INERGEN 300 bar, engineered total
More informationJune 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS
June 20, 2011 TO: PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS SUBJECT: New Acceptance Criteria for Fixed Condensed Aerosol Fireextinguishing Systems, Subject AC432-0611-R1
More informationCERTIFICATE OF APPROVAL No CF 5516 ALLGOOD PLC
CERTIFICATE OF APPROVAL No CF 5516 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of 63-83 Brearley street,
More informationFirst Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM
of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide
More informationJonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany
Making rail systems more efficient by using on-board Fire Protection Systems Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany Key Presentation Take-Aways Holistic approach to
More informationPAFSS Fire Suppression Systems from Jactone. Automatic Fixed Fire Suppression Systems. JACTONE.COM/PAFSS +44 (0)
PAFSS Fire Suppression Systems from Jactone Automatic Fixed Fire Suppression Systems JACTONE.COM/PAFSS +44 (0)1902 357777 pafss@jactone.com Protect your assets from fire with PAFSS JACTONE.COM/PAFSS +44
More informationSPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125
More informationPRODUCT LISTING DATA SHEET (Active Fire Protection Equipment)
LISTING NUMBER afp - 2086 Commonwealth Scientific and Industrial Research Organisation, Australia Ph.: 61 (0)3 9252 6000 Fax: 61 (0)3 9252 6011 Web site: http://www.activfire.gov.au E-mail: info@activfire.gov.au
More informationMSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017
Procedure Number: E1-03 Revision Date: 02/16/2017 References: S. T. Brady, CDR, Chief, Engineering Division a. National Fire Protection Association (NFPA) 750, 1996 Edition, Standard on Water Mist Fire
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire-extinguishing systems other than water-based fire suppression systems.
More informationSheetz Inc. Fire Protection Service Guidelines
Sheetz Inc. Fire Protection Service Guidelines Overview The following are guidelines for Sheetz Fire Protection Services for the 2016/2018 contract year. Each key area is listed below with the appropriate
More informationFirst Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement 4/15/ :08 AM
First Revision No. 1-NFPA 1403-2015 [ Section No. 1.2.1 ] 1.2.1 The purpose of this standard shall be to provide a process for conducting live fire training evolutions to ensure that they are conducted
More informationVaults 5/03/2015. Introduction. Vault Types. Stand alone building Free standing structure VAULTS
Protect your Media Vault Protect your Assets Fire Protection Services Vaults Presented by Peter Glodic Introduction Vault Types VAULTS Vault Types Vault Construction Media Types Fire Types Extinguishing
More informationWater Mist Fire Suppression
Water Mist Fire Suppression How less water has a big impact. HELPING PROTECT YOUR BUSINESS AND VALUED ASSETS WITH WATER MIST FIRE PROTECTION SYSTEM INTRODUCTION Many buildings have specific areas that
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in
More informationHow can you minimize consequential damages in case of a fire?
How can you minimize consequential damages in case of a fire? With intelligent extinguishing solutions from Siemens. Sinorix 227 fast, effective, and reliable. Answers for infrastructure. Reliability the
More informationPERFORMANCE TECHNICAL SPECIFICATION *************************************************************************** SECTION D40 FIRE PROTECTION 02/18
NAVFAC PTS-D40 (February 2018) -------------------------------- Preparing Activity: NAVFAC SUPERSEDING PTS-D40 (September 2016) PERFORMANCE TECHNICAL SPECIFICATION SECTION D40 FIRE PROTECTION 02/18 NOTE:
More informationElement C3.4 Fire Fighting Equipment
.4 Fire Fighting Equipment Classification of Fires Class A Solids. Wood, paper, plastics Class B Liquids Petrol oil, paint Class C Gases LPG, natural gas Classification of Fires Class D Metals Zinc, sodium,
More informationData/ Specification Sheet
Data/ Specification Sheet MONARCH Dry Chemical Automotive Paint Spray Booth Fire Suppression System TM 1. Fixed temperature mechanical or thermal detectors 2. Electrical conduit protecting stainless steel
More informationTRI-LAKES MONUMENT FIRE PROTECTION DISTRICT
TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter
More informationHKIE CPD Training Course (II) 23, 25 June and 7, 9 July 2009
(II) 23, 25 June and 7, 9 July 2009 Organization by Co-organized by the Association of Registered Fire Service Installation contractors of Hong Kong Ltd (FSICA) Gas and Foam Suppression Systems Peter Bressington
More informationSERVICE MANUAL (v1) UL / ULC. WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK
STRIKE FIRST CORPORATION AKC SERVICE MANUAL (v1) UL / ULC WET CHEMICAL HAND PORTABLE RESTAURANT KITCHEN FIRE EXTINGUISHERS Model: SF-6LK / WBDL-6LK All fire extinguishers should be installed, inspected
More informationCERTIFICATE OF APPROVAL No CF 5527 TALLERES DE ESCORIAZA S.A.U.
CERTIFICATE OF APPROVAL No CF 5527 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Bo Ventas, 35 E-20305
More informationEngineering Specifications
Engineering Specifications ANSUL INERGEN Clean Agent Fire Suppression System with AUTOPULSE Control System 2012-AUG-20 FIRE DETECTION / INERGEN FIRE SUPPRESSION SYSTEM ENGINEERING SPECIFICATIONS Tyco
More informationWhat extinguishes fires without pressure peaks?
What extinguishes fires without pressure peaks? Intelligent extinguishing solutions from Siemens. Sinorix CDT innovative, sustainable, and safe. Answers for infrastructure. Innovative technology the intelligent
More informationGAS EXTINGUISHING SYSTEMS INERT GAS. Argotec with argon or nitrogen
GAS EXTINGUISHING SYSTEMS INERT GAS Argotec with argon or nitrogen NATUR AL without any damage to the atmosphere The extinguishing gases Argon and nitrogen extinguish a fire by oxygen displacement. When
More informationCERTIFICATE OF APPROVAL No CF 5118 ASSA ABLOY LTD
CERTIFICATE OF APPROVAL No CF 5118 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of School Street, Willenhall,
More informationBUILDING CODE INTERPRETATION
BUILDING CODE INTERPRETATION November 2017 14-BCI-009 Page 1 of 6 FIRE ALARM AND FIRE SUPPRESSION SYSTEM VERIFICATION AND TESTING CERTIFICATES PURPOSE This STANDATA has been developed to give municipalities
More informationCERTIFICATE OF APPROVAL No CF 646 EUROSPEC ARCHITECTURAL HARDWARE LIMITED
CERTIFICATE OF APPROVAL No CF 66 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of EUROSPEC ARCHITECTURAL
More informationFire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours
Fire Protection Systems Operation and Maintenance 3 PDH / 3 CE Hours United Facilities Criteria U. S. Department of Defense UFC 3-601-02 PDH Academy PO Box 449 Pewaukee, WI 53072 www.pdhacademy.com pdhacademy@gmail.com
More informationCarbon Dioxide Extinguishing Systems Fighting fire with CO2
Carbon Dioxide Extinguishing Systems Fighting fire with CO2 TECHNOLOGIES GAS-BASED SUPPRESSION SYSTEMS Highly effective for many applications Quick and effective fire fighting is the strong point of carbon
More informationFIRE PROTECTION TECHNOLOGY Solutions never thought of before
FIRE PROTECTION TECHNOLOGY Solutions never thought of before More than 25 years in engineering, manufacturing and maintenance of certified fire fighting systems and products. TEMA SISTEMI There was a time
More informationSPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent
More informationCERTIFICATE OF APPROVAL No CF 111 INGERSOLL RAND SECURITY TECHNOLOGIES - BRITON
CERTIFICATE OF APPROVAL No CF 111 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Bescot Crescent, Walsall,
More informationAn Overview of Extinguishing Systems for Computer Equipment
Risk Solutions An Overview of Extinguishing Systems for Computer Equipment Various types of automatic suppression systems are available for protecting computer equipment. This report discusses the uses
More informationCERTIFICATE OF APPROVAL No CF 5179 LORIENT POLYPRODUCTS LIMITED
CERTIFICATE OF APPROVAL No CF 5179 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Endeavour House, Fairfax
More informationWater Mist and Heritage Buildings Case - St. Mark s Dome, Venice
Water Mist and Heritage Buildings Case - St. Mark s Dome, Venice By Nino Frisina Sales Director Marioff Italy IWMA Conference I Rome I 25 October 2017 Shutterstock.com AGENDA Background Case - St. Mark
More informationBS 476: Part 6: 1989+A1:2009
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS 476: Part 6: 1989+A1:2009 Method Of Test
More informationTHE FIRE PROTECTION SPECIALISTS
THE FIRE PROTECTION SPECIALISTS www.firetechint. INTRODUCTION Fire Tech Security & Safety Equipment LLC, established and licensed at Abu Dhabi and Sharjah, in U.A.E. This is one of the fastest growing
More informationPlanned Preventative Maintenance Schedule. Fire Suppression PPM Schedule
Planned Preventative Maintenance Schedule Fire Suppression PPM Schedule Support Planned and contracted maintenance services To ensure that data centre or building services are always operating to their
More informationApplication of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE
Application of BS 8489 to the Protection of Generator Enclosures IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE Agenda Generator Enclosure Characteristics Generator Fire Characteristics Machinery
More informationFull Service Central Station Fire Alarm Listing Evaluation
Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm
More informationCO 2. fire extinguishing systems
fire extinguishing systems Extinguishing technique is a colourless, odourless and electrical non-conductive gas. In systems the is mixed with a special identifiable odour. The extinguishing effect of is
More informationEN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com EN 45545-2: 2013 Summary Test Report Requirement
More information