1 1 CLEAN AGENTS 2015 Updates to the NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2015 Edition APRIL 2015 M O-KAN SFPE CHAPTER M EETING APRIL 6, 2015 PRESENTED BY C. DAVIS & D. O DONNELL
2 Taking Effect in NFPA 2001: 2012 Edition Chapter 4 Components Section Control Equipment , January 1, 2016 (also in 2015 edition) Removal of an electric actuator from the agent storage container discharge( Selector) valve that it controls shall result in an audible and visual indication of system impairment at the system releasing control panel & Does not apply to Chapter 8 Marine Systems with exception of 8.6 (Class B >6000ft3 cylinder storage within hazard) 2
3 3 Chapter 2 Referenced Publications Section 2.3 Other Publications NFPA 70 (NEC) References 2014 edition NFPA 72 (Fire Alarm & Signaling) References 2013 edition ASME Boiler and Pressure Vessel Code References 2013 edition ASME B31.1 Power Piping Code References 2012 edition ANSI/UL 2127 (Inert Gas) & 2166 (Halocarbon Gas) 2012 Edition, UL aligned to ANSI to ease international efforts
4 4 Chapter 3 Definitions Section 3.2 NFPA Official Definitions Standard An NFPA Standard, the main text of which contains only mandatory provisions using the word shall to indicate requirements and that is in a form generally suitable for mandatory reference by another standard or code or for adoption into law. Nonmandatory provisions are not to be considered a part of the requirements of a standard and shall be located in an appendix, annex, footnote, informational note, or other means as permitted in the NFPA Manuals of Style. When used in a generic sense, such as in the phrase standards development process or standards development activities, the term standards includes all NFPA Standards, including Codes, Standards, Recommended Practices, and Guides.
5 5 Section 3.3 General Definitions Two definitions have been added: Recovered Agent Agent that has been removed from a system and kept for future use or until it is destroyed, without necessarily testing or processing it in any way Recycle Agent Agent that has been recovered, tested, and processed as necessary and found to be in compliance with the quality requirement of
6 6 Chapter 4 Components Section Agent Storage Containers Means to determine pressure in containers changed from refillable superpressurized containers to containers of inert gas agents, superpressurized liquid agents, and superpressurized liquefied compressed gas agents. More specific to pressurized containers Took out wording on external heating or cooling of containers.
7 7 Chapter 4 Components Section 4.2 Distribution Pipe Updated reference requirements of B (3) Added specifies inert gas piping shall use and Updated to better reflect the common use of pressure reducers in inert gas piping. Highlighted section below added/updated:
8 Chapter 4 Components Section 4.2 Distribution continued Table (a) New storage pressure added to Nitrogen (IG-01) and updated, reduced pressures for Inergen (IG-55). See Highlighted data below. 8 Added Further guidance on pressure reducing device: design pressure for piping based on flow calculation after the pressure reducing device.
9 Chapter 4 Components Section 4.2 Distribution continued Added Piping for pre-engineered systems shall be designed in accordance with the manufacturers listed manual & , Simplifies and highlights that there is to be NO USE OF FITTINGS NOT RATED FOR PROPER PRESSURES! Added Flanged valves require proper class of flange to connect. 9
10 Chapter 4 Components Section 4.2 Distribution continued Added provides guidance on distances from obstructions required to nozzle location. Also added annex material on this subject. Added automatic type systems in non occupied spaces do not require manual release. This covers bulb and Direct type systems. 10
11 11 Chapter 5 System Design Added Which requires calibration of cup burner method equipment and helps to keep the agent manufacturers testing consistent. 5.5 Total Flooding Quantity Added equation for minimum and maximum temperature concentration calculation per standard requirements Reference to Total Flooding quantities tables in Annex moved to , this information is still available in the annex. Replaced with , new now requires that the halocarbon agent concentration calculated at the highest and lowest temps shall be included on the system as-built drawings and flow calculations Equation updated for ease of use
12 12 Chapter 5 System Design Continued now requires that agent concentration calculated at the highest and lowest temps shall be included on the system as-built drawings and flow calculations 5.6 Duration of protection 85% of adjusted minimum design shall be held at the highest level of combustibles has been changed to highest height of protected content removed elaborated on what rate of application is, unnecessary
13 13 Chapter 6 Local Application Systems Local App Discharge Time added wording on mechanical rundown time for extended discharges Local App Linear Detection Tubing Direct type system now allowed.
14 Chapter 7 Inspection, Testing, Maintenance, and Training Inspection reports can be filed using electronic media (ie Building Reports) Added new Clarifies that recovered Clean Agents shall not be released into the atmosphere Old became (Inspection Tag) Added & Stating that installation acceptance testing shall be documented in a test report and maintained by the owner for the life of the system through Clarifies the pipe pressurization checkout method wording 14
15 15 Appendix Test Report
16 16 Changes to Appendix A.1.6 GWP & ODP Defined
17 17 Changes to Appendix New Section Added A Considerations and Conditions Requiring Increased Design Factors Unclosable Openings Acid Gas Formation Considerations Fuel Geometry Considerations Enclosure Geometry Obstructions Within the Enclosure
18 18 Changes to Appendix FSSA (Fire Suppression Systems Association) now referenced for multiple publications to assist designers. A Detection & Control Guide A (28) Pressure Relief Estimating Document A Design Guide A.7.2 Container Guide
19 19 Summary of Primary Changes Requirement of notification on electrical actuator removal Recovered/Recycled Agents now defined; recycled agents permitted Agent calculation requirement for low and high temperature of protected space No manual release required for automatic systems when unoccupiable & personnel not normally present Detection tubing permitted for use as nozzle in local app Annex Changes Environmental definitions FSSA references added Addition of acceptance test report Design factor considerations
20 20 Burning Questions? Upcoming Trends/Concerns within the Industry?
21 21 Thank You For Your Time Cole Davis Derek O Donnell dodonnell@phoenixfire.com
Committee Input No. 9-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement
Committee Input No. 9-NFPA 2001-2016 [ Global Input ] Incorporate revisions per the attached file. Supplemental Information File Name 2001-CI_9.pdf Description Data and specific revisions presented at
More informationNFPA 96, 2017 REVIEW SUMMARY
NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile
More informationFM-200 In-Cabinet Series
1. GENERAL SPECIFICATION 1.1 A total flooding, In-Cabinet fire suppression system, employing FM-200 superpressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by
More informationNFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless
More informationFirst Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM
1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling
More informationPublic Input No. 52-NFPA [ Section No [Excluding any Sub-Sections] ]
8 of 93 11/6/2015 7:41 AM Public Input No. 52-NFPA 30-2015 [ Section No. 21.2 [Excluding any Sub-Sections] ] For the purpose of this chapter, the term in this section shall have the definitions given.
More informationSECTION FM-200 FIRE SUPPRESSION SYSTEM
SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to
More informationSPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM
1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationFIRE SUPPRESSION SYSTEM
FIRE SUPPRESSION SYSTEM An effective fire suppression systems work fundamentally in three ways; The corner stone has to be an efficient means of early warning/detection. Followed by either an Oxygen reduction
More informationAustralian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS
AS 4214 2002 (Incorporating Amendment No. 1) AS 4214 2002 Australian Standard Gaseous fire extinguishing systems This Australian Standard was prepared by Committee FP-011, Gaseous Fire Protection. It was
More informationSPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection
1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in
More informationA. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.
1. GENERAL SPECIFICATION 1.1 A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationFirst Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM
of 25 7/30/2015 1:35 PM First Revision No. 49-NFPA 17A-2015 [ Detail ] Make the following change to 5.2.1.10.2: 5.2.1.10.2* The manual actuation device shall clearly identify the hazard protected and provide
More information2007 ASME Boiler & Pressure Vessel Code 2007 Edition July 1, 2007
AN INTERNATIONAL CODE 2007 ASME Boiler & Pressure Vessel Code 2007 Edition July 1, 2007 VI RECOMMENDED RULES FOR THE CARE AND OPERATION OF HEATING BOILERS ASME Boiler and Pressure Vessel Committee Subcommittee
More informationBOC FS125 The Fire Extinguishing Solution
BOC FS125 The Fire Extinguishing Solution Background - Montreal Protocol With the introduction of the Montreal Protocol in 1987, Halon is no longer available in most countries and alternatives must be
More informationISO 6183 INTERNATIONAL STANDARD. Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation
INTERNATIONAL STANDARD ISO 6183 Second edition 2009-06-15 Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation Équipement de protection contre l'incendie
More informationAMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER
AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER The 2016 Denver Building and Fire Code includes the following codes except as amendment herein. 2015 IBC (Building) 2015 IFC (Fire)
More informationPublic Safety [661] Chapter 226, Liquefied Petroleum Gas, Amended for Application within the State of Iowa
Public Safety [661] Chapter 226, Liquefied Petroleum Gas, Pursuant to the authority of Iowa Code section 101.1, the State Fire Marshal hereby adopts new Chapter 226, Liquefied Petroleum Gas, Iowa Administrative
More informationSPECIFICATION: ARGONITE Engineered Fire Suppression System
1. GENERAL SPECIFICATION 1.1 A total flooding, clean agent, fire suppression system, filled with Argonite agent shall be installed to meet a minimum design concentration of %, by volume in all designated
More informationFire suppression systems for server rooms and data centres
Fire suppression systems for server rooms and data centres Fire suppression systems for server rooms and data centres Fire suppression systems for server rooms and data centres are essential to the server
More informationMSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017
Procedure Number: E1-03 Revision Date: 02/16/2017 References: S. T. Brady, CDR, Chief, Engineering Division a. National Fire Protection Association (NFPA) 750, 1996 Edition, Standard on Water Mist Fire
More informationSecond Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM
1 of 14 6/22/2016 3:15 PM Second Revision No. 1-NFPA 17A-2016 [ Section No. 4.3.3 ] 4.3.3 All discharge nozzles shall be provided with caps or other suitable devices to prevent the entrance of grease vapors,
More informationKidde Nitrogen Inert Gas Clean Agent Fire Suppression System
1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering
More information26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR
INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1007 26 June 2001 GUIDELINES FOR THE
More informationFirst Revision No. 20-NFPA [ Section No ]
of 25 7/15/2015 8:30 AM First Revision No. 20-NFPA 56-2015 [ Section No. 1.1.2 ] 1.1.2 Nonapplication of Standard. This standard shall not apply to the following items: (1)* Piping systems covered by NFPA
More informationCERTIFICATE OF FIRE APPROVAL
CERTIFICATE OF FIRE APPROVAL This is to certify that The product detailed below will be accepted for compliance with the applicable Lloyd s Register Rules and Regulations and with the International Convention
More informationM E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter
More information2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content
Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015
More informationSafe, Effective, Environment-friendly
IG-55 (Argon/Nitrogen) Safe, Effective, Environment-friendly Introduction With the phase out of the most commonly used but environmentally damaging Halon 1301 and CO 2 fire suppressant, inert gases are
More informationCO 2 Fire Extinguishing Systems
Guidelines for Fire Extinguishing Systems Planning and Installation Content 0 Foreword... 10 0.1 Application of the VdS guidelines... 10 1 General... 10 1.1 Scope... 10 1.2 Aims... 11 1.3 Description...
More informationSecond Revision No. 3-NFPA [ Section No. 2.3 ]
Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler
More informationCOMDTPUB P NVIC JUNE 1995
COMDTPUB P16700.4 NVIC 3-95 19 JUNE 1995 NAVIGATION AND VESSEL INSPECTION CIRCULAR NO. 3-95 Electronic Version for Distribution on the World Wide Web Subj: PERIODIC INSPECTION AND TESTING OF FIXED HALON
More informationENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
More informationChange all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.
1 of 9 10/21/2015 1:22 PM First Revision No. 3-NFPA 99B-2015 [ Global Input ] Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.
More informationGUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS
12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety
More informationAdobe Connect - Invitation to NFPA 385 Second Draft Web Conference
Matthews, Diane Subject: Location: Start: End: Show Time As: Recurrence: Meeting Status: Organizer: Required Attendees: Adobe Connect - Invitation to NFPA 385 Second Draft Web Conference http://nfpa.adobeconnect.com/rpbmeet/
More informationHospitals and Major Medical Centers
Hospitals and Major Medical Centers INERGEN Fire Suppression Systems AUTOPULSE Detection and Control Equipment SENTRY Hand Portable Fire Extinguishers Medical centers have special concerns for fire safety
More informationJune 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS
June 20, 2011 TO: PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS SUBJECT: New Acceptance Criteria for Fixed Condensed Aerosol Fireextinguishing Systems, Subject AC432-0611-R1
More informationAustralian Standard. Water mist fire protection systems System design, installation and commissioning AS
AS 4587 1999 Australian Standard Water mist fire protection systems System design, installation and commissioning This Australian Standard was prepared by Committee FP/12, Aqueous Fire Protection Systems.
More informationM E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment
M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The
More informationThe Science Behind Water Mist Protection of Typical Building Hazards
The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested
More informationCLEAN AGENT SYSTEMS. TABLE 1 Agents Recognized in NFPA 2001
GAP.13.6.1 A Publication of Global Asset Protection Services LLC CLEAN AGENT SYSTEMS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection agreed on by
More informationPublic Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document
of 79 1/27/2016 2:09 PM Public Input No. 1-NFPA 59-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) ANSI/API and replace with API. (2) ANSI/UL
More informationReport on First Revision November 2013 NFPA 750
750 FR1 (Chapter 2) Recommendation: Update the following references: Chapter 2 Referenced Publications 2.1 General. The documents or portions thereof listed in this chapter are referenced within this standard
More informationIMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS
INTERNATIONAL MARITIME ORGANIZATION E IMO ASSEMBLY 23rd session Agenda item 17 A 23/Res.951 25 February 2004 Original: ENGLISH Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED
More informationCommittee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM
1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:
More informationRequirements for ships carrying hydrogen and compressed natural gas vehicles
Lloyd's Register briefing IMO FP 55 Summary report for clients Overview The 55 th session of the IMO Fire Protection Sub Committee (FP) was held from 25 th to 29 th July 2011, at the IMO headquarters in
More informationMAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES
SHIPPING NOTICE Maritime Authority of the Cayman Islands Head Office 3 rd Floor, Government Administration Building, 133 Elgin Avenue PO Box 2256, Grand Cayman, KY1-1107, Cayman Islands Tel: +1 345 949
More informationCO2 COCO GAS FLOODING SYSTEM
PRE INTRODUCTION: CO2 COCO GAS FLOODING SYSTEM The importance of erection, testing and commissioning are overlooked, in many projects while installing fixed Co2 extinguishing system. It is very common
More informationrpsa FIRE PROTECTION ENGINEERS
FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator
More informationNotice on the implementation of the amendments to the FSS Code in resolution MSC.339(91)
C C S 通函 Circular China Classification Society (2013) Circ.111 /Total No.397 25/07/2013 (total pages:18) To relevant departments of CCS Headquarters, Shanghai Rules and Research Institute, plan approval
More informationCLEAN AGENTS & CLASS C FIRE HAZARDS
CLEAN AGENTS & CLASS C FIRE HAZARDS NEW DEVELOPMENTS Presented by: Jeff L. Harrington, P.E., FSFPE For: Fire Safety Annual Conference Greater Atlanta Chapter Society of Fire Protection Engineers March
More informationM E M O R A N D U M. NFPA Technical Committee on Gaseous Fire Extinguishing Systems. NFPA 2001 Second Draft TC FINAL Ballot Results (F2014 Cycle)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Gaseous Fire
More informationRESOLUTION MSC.339(91) (adopted on 30 November 2012) AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE)
THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization concerning the functions of the Committee, NOTING resolution MSC.98(73), by which it
More informationGASEOUS HYDROGEN SYSTEMS
CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall
More informationSPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND
1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation
More informationApplication of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE
Application of BS 8489 to the Protection of Generator Enclosures IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE Agenda Generator Enclosure Characteristics Generator Fire Characteristics Machinery
More informationSecond Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement
of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections
More informationCarbon Dioxide Fire Suppression Systems
Carbon Dioxide Fire Suppression Systems The original "clean agent," carbon dioxide suppresses fire without leaving behind water, foam or dry chemical to damage sensitive equipment. And because there is
More informationAn Overview of Extinguishing Systems for Computer Equipment
Risk Solutions An Overview of Extinguishing Systems for Computer Equipment Various types of automatic suppression systems are available for protecting computer equipment. This report discusses the uses
More informationPOSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS
FIRE EXTINGUISHING INSTALLATIONS SECTION POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS Version 1 29-09-04 0 Eurofeu position paper on water mist for fire fighting applications 1 Scope The
More informationCARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS
CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS Town of Brighton Office of the Fire Marshal October 2018 Carbon Dioxide Systems for Beverage Dispensing Requirements Scope The intent
More informationSPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM
1. GENERAL SPECIFICATION 1.1 An Engineered Carbon Dioxide Fire Suppression System shall be installed to meet a minimum design concentration of %, by volume in all designated spaces/areas to be protected.
More informationPRODUCT LISTING DATA SHEET (Active Fire Protection Equipment)
LISTING NUMBER afp - 2086 Commonwealth Scientific and Industrial Research Organisation, Australia Ph.: 61 (0)3 9252 6000 Fax: 61 (0)3 9252 6011 Web site: http://www.activfire.gov.au E-mail: info@activfire.gov.au
More informationVaults 5/03/2015. Introduction. Vault Types. Stand alone building Free standing structure VAULTS
Protect your Media Vault Protect your Assets Fire Protection Services Vaults Presented by Peter Glodic Introduction Vault Types VAULTS Vault Types Vault Construction Media Types Fire Types Extinguishing
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationTable OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
More informationDENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES
DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES NOTE: Each proposed Denver amendment to the International Codes must be justified. In order to be considered, the amendment proposal must address climate,
More informationSTANDARDS FOR ACTIVE FIRE PROTECTION. Stewart Kidd Loss Prevention Consultancy Ltd
STANDARDS FOR ACTIVE FIRE PROTECTION Stewart Kidd Loss Prevention Consultancy Ltd This presentation will consider: The risks to both new and existing buildings which can be countered by active fire protection
More informationMOBILE FOOD VENDING Food Trucks & Trailers
MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE MOBILE FOOD VENDING Food Trucks & Trailers These guidelines are to be followed when a business, facility or organization plans to operate a food truck or
More informationSafety Tips for the Office
Safety Tips for the Office An office fire can be devastating - resulting in business interruption or permanent closure, loss of lives, jobs, property and information. Offices are loaded with combustible
More informationSAF-BCF SECOND REVISIONS WITH STATEMENTS
Page 196 of 331 32.2.1.3 ] Second Revision No. 153-NFPA 101-2013 [ New Section after 32.2.1.4 Multiple-Level Buildings. For purposes of applying requirements of this chapter that utilize the term level
More informationFire Suppression. Water-Mist : A Revolutionary Green Technology in. - by Nimit Sheth TALL, SMART, SAFE BUILDINGS FOR SMART CITIES.
Water-Mist : A Revolutionary Green Technology in Fire Suppression - by Nimit Sheth Introduction Water-Mist... A Revolutionary Green Technology in Fire Suppression is being researched for more than 50-years
More informationGAS EXTINGUISHING SYSTEMS INERT GAS. Argon Extinguishing Systems. Fire Protection Systems
GAS EXTINGUISHING SYSTEMS Argon Extinguishing Systems Fire Protection Systems EFFECTIVE NATURAL no damage to the atmosphere technology for complex applications EXAMPLE GAS EXTINGUISHING SYSTEMS solution
More informationPage 1 of 37 Public Input No. 1-NFPA 30A-2012 [ New Section after 1.1.2 ] 1.1.3 This code shall not apply to aircraft fuel dispensing facilities. NFPA 30A is commonly referenced, in my opinion, incorrectly,
More informationNFPA 45 NFPA 211 NFPA 1600
NFPA 45 NFPA 211 NFPA 1600 Prepared by: William E. Koffel, P.E., FSFPE Expertly Engineering Safety From Fire 1 Objectives Overview of the NFPA process Understand the scope and application of NFPA 45, NFPA
More information(h) Pesticide Application.
Fire Code Cannabis Amendment Section 13.20.066 is added to the Marysville Municipal Code to read in its entirety as follows: 13.20.066 Cannabis Growing, Processing, or Extraction Facilities (a) Application.
More informationElement C3.4 Fire Fighting Equipment
.4 Fire Fighting Equipment Classification of Fires Class A Solids. Wood, paper, plastics Class B Liquids Petrol oil, paint Class C Gases LPG, natural gas Classification of Fires Class D Metals Zinc, sodium,
More informationTypes of Detection. Fusible Link Detection - Most Common
Types of Detection Fusible Link Detection - Most Common Types of Detection Electric Detection Types of Detection Pneumatic Detection-Tubing Pneumatic Tubing 3 Year Service life Survey Hazard 1) List all
More informationCompliance Guidance for non-technical managers
11699 Brookpark Road Cleveland, OH 44130 USA P: 888-826-3473 F: 216-398-8403 www.combustionsafety.com -WHITEPAPER- NFPA 56 (2012 Ed.) Standard for Fire and Explosion Prevention During Cleaning and Purging
More informationNFPA 12A. Standard on. Halon 1301 Fire Extinguishing Systems Edition. Copyright 2004, National Fire Protection Association, All Rights Reserved
NFPA 12A Standard on Halon 1301 Fire Extinguishing Systems 2004 Edition Copyright 2004, National Fire Protection Association, All Rights Reserved This edition of NFPA 12A, Standard on Halon 1301 Fire Extinguishing
More informationAbove Ground Fuel Tank Requirements
FIRE DEPARTMENT in cooperation with Above Ground Fuel Tank Requirements The purpose of this document is to provide information about general Fire Code requirements for above ground storage within the unincorporated
More informationMAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and
More informationBSR/ASHRAE Addendum b to ANSI/ASHRAE Standard FORWORD
(This foreword is for information only and is not part of this addendum) FORWORD Changes in this addendum to ANSI/ASHRAE 15-1994 are made to add water as a refrigerant, include absorption refrigeration
More informationNFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES
NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES Sharon S. Gilyeat, P.E., Principal Koffel Associates, Inc. www.koffel.com sgilyeat@koffel.com Expertly Engineering Safety From Fire
More informationFig. 1 - Unit PGD4, PGS4, WPG4
OWNER S MANUAL 14 SEER Single -Package Air Conditioner and Gas Furnace System with R -410A Refrigerant Single Phase 2 to 5 Nominal Tons Three Phase 3 to 5 Nominal Tons PGD4andPGS4SeriesE,WPG4SeriesB Fig.
More informationNEW YORK CITY FIRE DEPARTMENT. Notice of Public Hearing and Opportunity to Comment on Proposed Rule
NEW YORK CITY FIRE DEPARTMENT Notice of Public Hearing and Opportunity to Comment on Proposed Rule What are we proposing? The Fire Department is proposing to comprehensively update Section 3004-01 of Title
More informationNFPA 72 is in the same cycle as NFPA 80. The extracted text will be updated with a Second Revision during the second draft meeting.
Input No. 7-NFPA 80-2013 [ Section No. 3.3.8 ] 3.3.8 Automatic Fire Detector. A device designed to detect the presence of a fire signature and to initiate action. For the purpose of this standard, automatic
More informationFirst Revision No. 22-NFPA [ Global Input ] Submitter Information Verification. Committee Statement
of 28 2/2/2016 9:39 AM First Revision No. 22-NFPA 37-2015 [ Global Input ] Add the following definitions to chapter 3: 3.3.x Service Regulator. A pressure regulator installed by the serving gas supplier
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during
More informationFEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS
FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS ARE BASED UPON LIVE FIRE TESTING OF PREP STATIONS
More informationANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL
Annex 2, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL Section 1 Application 1 The following new sentence is added to the end of paragraph 1.2:
More informationCertificate of Conformity Certificate num. Registration date Version Valid until
CSIRO Verification Services Highett, Victoria, Australia +61 (0)3 9252 6000 http://www.activfire.gov.au/ Page 1 of 5 Issued by Product designation Tyco Safety Products, INERGEN 300 bar, engineered total
More informationSTANDARDS FOR VAPOUR EMISSION CONTROL SYSTEMS ( MARPOL reg VI/15 )
STANDARDS FOR VAPOUR EMISSION CONTROL SYSTEMS ( 92-98 MARPOL reg VI/15 ) MSC/Circ.585 16 April 1992 1 The Maritime Safety Committee, at its sixtieth session, recognized the necessity of the international
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationFIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION
CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition
More informationPage 1 of 126 First Revision No. 113-NFPA 45-2013 [ Global Input ] Change all references to Material Safety Data Sheets (MSDS) to Safety Data Sheets (SDS) Submittal Date: Thu May 09 11:40:44 EDT 2013 Response
More informationPublic Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item
Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method
More informationCARBON MONOXIDE ALARM STANDARDS ACT - ENACTMENT Act of Dec. 18, 2013, P.L. 1229, No. 121 Cl. 35 An Act
CARBON MONOXIDE ALARM STANDARDS ACT - ENACTMENT Act of Dec. 18, 2013, P.L. 1229, No. 121 Cl. 35 An Act Providing standards for carbon monoxide alarms; and imposing penalties. The General Assembly of the
More informationPublic Input No. 1-NFPA [ Global Input ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document
National Fire Protection Association Report of 113 http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 2/9/2016 10:50 AM Public Input No. 1-NFPA 87-2015 [ Global Input ] Throughout standard
More information