Technology Design Guidelines. Version 8.0. February 2, 2015

Size: px
Start display at page:

Download "Technology Design Guidelines. Version 8.0. February 2, 2015"

Transcription

1 TECHNOLOGY SERVICES Version 8.0 February 2, Prescott Street Greensboro, NC P

2 SECTION 01 Project Scope Part 1 Project Scope 1.1. The shall be used for all construction and renovation projects involving technology items within Guilford County Schools (GCS). A. Technology Items include: 1. Access Control 2. Audio/Video 3. Data Communications 4. Fire Alarm 5. Installed Sound 6. Intrusion Detection 7. Video Surveillance 8. Voice Communications 1.2. The Architect and Engineer shall use the as a reference for all design activities. Part 2 Variance 2.1. Variance from these guidelines must be approved by GCS and GCS Facilities. Part 3 Master Technology Specification 3.1. Architects and Engineers shall read and understand all sections of the Master Technology Specification and use that information in all design activities All sections of the Master Technology Specification shall be considered to be a part of these guidelines. End of Section 01 SECTION 02 Version History Part 1 General 1.1. Version 8 is an original version. End of Section 02 SECTION 03 Substitution Procedures Part 1 Standard Products 1.1. All products specified in this document have been approved by prior North Carolina State approved selection process, unless noted as or approved substitute. Or approved substitute products shall meet all requirements as listed and must be approved by submittal to Guilford County Schools. Deviations from the specified products are not allowed without prior written approval from Guilford County Schools. Part 2 Substitutions 2.1. Substitutions shall be limited Only equal or superior quality and with cost savings to Guilford County Schools will be considered. Version 8 Page 2 of 27 February 2, 2013

3 2.3. Architect/Engineer shall submit a substitution request in writing to GCS Technology Services. A. Request shall include all required submittals and shall be complete with reasons for substitution and savings. B. Approval of alternate or substitute equipment or material in no way voids the guideline requirements. C. Guilford County Schools shall not be required to prove that an item proposed for substitution is not equal to the specified item. Architect/Engineer shall submit all evidence to support the contention that an item is equal to the specified item. The Guilford County Schools decision as to the equality of substitution shall be final and without further recourse. Part 3 Products 3.1. Product listings can be found in the Master Technology Specification. End of Section 03 SECTION 04 Drawing Requirements Part 1 General 1.1. Due to the specific and detailed needs of the technology design, certain specific drawings are required. Part 2 Contractor Specific Drawings 2.1. Drawings for each contractor (Infrastructure, Integrated, and Security) should be included A single drawing with layers that can be turned on and off is sufficient for this requirement Each drawing or layer should show only those items that are the responsibility of that contractor. Part 3 Backbone Riser 3.1. A diagram of all backbone cables shall be included Diagram shall include each telecommunication closet with each type of backbone cable and quantity clearly shown. Part 4 Horizontal Telecommunications Closet 4.1. Drawings should have a method for identifying the telecommunications closet termination point for all cabling. This is essential for equipment counts. Part 5 Overhead Speaker Rigging 5.1. A diagram of acceptable rigging shall be included. End of Section 04 SECTION 05 Pathways for Communications Systems Part 1 General 1.1. Inaccessible Ceiling Areas A. Inaccessible Ceiling Areas such as lock in ceiling tiles, drywall or plaster, will not be used as distribution pathways. B. Inaccessible areas, such as parking lots, roads, etc. shall be avoided as distribution pathways Size and Count Version 8 Page 3 of 27 February 2, 2013

4 A. The minimum conduit size for communication pathways is 0.75 (3/4 ). B. The count and size of pathways are dependent on the number of services being installed and the number and type of cables the pathways support. A maximum 40% fill ratio shall be maintained. A. Pathways will not be shared with any other service (e.g. electrical). Part 2 Interior Pathways 2.1. Cable Support Sling A. Use Cable Support Slings to provide a pathway between cable tray and conduit. B. Install multiple paths along a route to provide fill capacity of 40% or less. C. Maintain minimum 12 clearance from all other services (HVAC, fire, electrical, etc.) and lighting Metal Conduit and Tubing A. Conduit should be used to provide pathway from outlet box to ceiling space. B. Conduits shall serve no more than one communication outlet. C. Technology Conduits will not be shared with any other service (e.g. electrical). D. Textile Innerduct 1. All backbone conduits shall be fitted with textile innerduct. 2. Innerduct should be sized appropriately for conduit size Power/Communication Poles A. The use of power/communication poles should be limited to areas where no other means of pathway is available Boxes, Enclosures, and Cabinets A. Outlet Boxes 1. Outlet boxes should be placed as needed to accommodate the scheduled outlets. B. Floor Boxes 1. The use of floor boxes should be limited to areas where no other means is available Surface Raceway A. Pathways for walls that cannot be flush mounted will be created by use of vertical and/or horizontal nonmetallic raceway. B. Raceway may be used in exposed areas where multiple conduits would be required Cable Tray A. Usage 1. Cable tray shall be used in corridors and major pathways. 2. Wire basket shall be used in technology rooms. B. Coordination 1. Coordinate layout and installation of cable trays and suspension system with other construction that penetrates ceilings or is supported by them, including light fixtures, HVAC equipment, fire suppression system, and partition assemblies. C. Rod Hangers 1. Hang cable tray using threaded, galvanized rod hangers, with rods extended through support steel and double nutted. Size support member with load rating of straight section and without visible deflection. Install cable tray level and straight. Supports must be provided to prevent leaning. All mounting methods must meet manufacturer s recommendations. D. Wall Hangers Version 8 Page 4 of 27 February 2, 2013

5 1. Mount cable tray to wall using angle brackets of same manufacturer and of appropriate size and strength. E. Clearance 1. Cable tray shall be installed above the ceiling grid at nominal height of 12 above the ceiling grid. 2. Cable tray will not interfere with, or be placed within 12 of lighting fixture ballasts or duct work. 3. Conduits pipes or sprinkler heads are not to go through the cable tray. F. Walls 1. Cable trays shall not pass through any wall. Cable tray shall end before the wall and transition to a minimum of (2) 4 EMT sleeves with connectors and insulated bushings. Additional sleeves should be designed to ensure a maximum 40% fill ratio. Part 3 Exterior Pathways 3.1. Coordination A. Coordinate layout and installation of ducts, manholes, handholes, and boxes with final arrangement of other utilities, site grading, and surface features as determined in the field Exterior pathways should be sized as required. A. Minimum requirement between TER and TC in a separate building: 1. One 3 inch conduit with 3 inch 3 cell textile inner duct for fiber. 2. Multiple 3 inch conduits with 3 inch 3 cell textile inner duct as required for copper backbone. 3. One 2 inch conduit with 2 inch 3 cell textile inner duct for coax. B. Count will depend on application and should be designed to accommodate a maximum 40% fill ratio Slope A. Pitch conduits a minimum slope of 1:300 down toward holes and away from buildings and equipment. Slope conduits between holes from a high point such that water drains in both directions Holes A. Conduits shall run no more than 500 before a handhole or manhole is installed. B. Handholes and manholes shall not be shared with public utilities Curves and Bends A. Conduits shall have no more than two 90 degree bends before a handhole or manhole is installed Building Wall Penetrations A. Make a transition from PVC to rigid steel at least 10 feet outside the building wall without reducing slope away from the building, and without forming a trap in the line. Use fittings manufactured for this purpose. B. Waterproofing Seals 1. Provide watertight expanding link type seals for installation between the conduit and the sleeve or core drilled hole Clearances A. Install conduits with a minimum of 3 inches between conduits for like services and 6 inches between power and signal conduits. B. Conduits shall be a minimum of 24 below grade. Version 8 Page 5 of 27 February 2, 2013

6 C. Conduits shall extend 12 in the entrance room, and shall be no more than 2 from the nearest wall Textile Innerduct A. All underground conduits shall be fitted with textile innerduct. B. Innerduct should be sized appropriately for conduit size. End of Section 05 SECTION 06 Communications Entrance Part 1 Entrance Pathways 1.1. Conduit # 1 A. Main (4 inch) telecommunications entrance conduit with 4 inch 3 cell textile inner duct. B. Shall be reamed and bushed to eliminate entrance cable damage. C. Will be capped until cable installation and sealed immediately following Conduit # 2 A. Spare (4 inch) telecommunications entrance conduit with 4 inch 3 cell textile inner duct. B. Shall be capped at both ends for future use Conduit # 3 A. CATV (2 inch) telecommunications entrance conduit with 2 inch 3 cell textile inner duct. B. Shall be reamed and bushed to eliminate entrance cable damage. C. Will be capped until cable installation and sealed immediately following. Part 2 Protection 2.1. Provide a complete entrance protection system, including surge protection equipment and surge protection modules Products A. CommScope 310 VDSL Connector Panel or approved equal B. CommScope 3 Type Gas Discharge Tube Protector or approved equal End of Section 06 SECTION 07 Communications Closets Part 1 Technology Closets 1.1. Shall provide a transition between the horizontal, backbone, and entrance pathways and provide space for telecommunications systems components Shall provide adequate space for cable terminations (horizontal and backbone), active and passive equipment, cross connection wiring and hardware, and any other materials or equipment associated with the building technology systems Shall be dedicated to the technology systems and related support systems, and shall not be shared with electrical or other services Shall not have duct work, piping, etc. that is overhead or through the room. No building structure or services shall block access to the room. Duct work, piping, conduits, etc. shall not obstruct current or future pathway entrance. A. Drainage troughs shall be placed under any water pipes to prevent leakage onto the equipment within the room. Version 8 Page 6 of 27 February 2, 2013

7 Part 2 Types of Rooms 2.1. Technology Equipment Room (TER) A. Entrance facility and demark. B. Main backbone cable distribution hub. C. Local horizontal cable distribution hub. D. Active network, paging, CATV, security equipment Technology Closet (TC) A. Local horizontal cable distribution hub. B. Active network, paging, CATV, security equipment REbox TC A. Small area horizontal cable distribution hub. B. Active network equipment. Part 3 Architectural 3.1. Location A. Shall be located in a dry area not subject to flooding. B. Shall be as close as possible to an electrical service room in order to reduce the length of the bonding conductor to electrical grounding. C. Shall have separation from sources of EMI as specified in the ANSI/TIA/EIA 569 B Pathways and Spaces Standard. D. Shall not be shared with building services that may interfere with the telecommunications systems or be used for custodial services or storage. E. Shall be accessible for delivery and installation of large equipment throughout its useful life. F. Access to the room shall not be from the exterior of the building. G. Rooms shall open directly to a corridor and not be within another room/space. H. Shall be placed such that no more than two walls are adjacent to non movable building structures such as rest rooms, exterior walls, etc. I. Shall not be adjacent to elevator shafts or elevator equipment rooms. J. TER 1. Shall be located inside or adjacent to the Media Center. 2. TER shall not support multiple floors of a multi story building. K. TCs 1. Shall be placed in the center of the area served by that room. 2. TC shall not support multiple floors of a multi story building. L. The maximum horizontal distance from any TER or TC to any outlet (cable distance via the horizontal pathway system) must be less than 85 meters (280 feet). A circle with radius of 60 meters (200 feet) centered on TC can be used to gauge distance requirements. Additional rooms shall be placed as appropriate to support this distance limitation. M. The TC rooms in a multistory building shall be stacked vertically directly above one another Size A. Floor plans must be reviewed by Guilford County Schools during the schematic design phase to ensure rooms are sized adequately. B. Room sizes assume the door opens outward. Larger rooms are required if the door opens inward. C. TER 1. The TER shall be sized to support all telecommunications systems for the building served, including: backbone data, voice, & CATV cabling; horizontal data, voice, & CATV cabling; CATV distribution equipment; paging equipment; network electronics; security, fire alarm and fire suppression. 2. Minimum Size: 300 Square Feet, 20 x 15. Version 8 Page 7 of 27 February 2, 2013

8 a) For each additional rack beyond the standard three, add 40 Square Feet. D. TC 1. The TC rooms shall be sized to support all telecommunications systems for the area served. The room sizes below are for rooms that support horizontal cabling for data, voice, CATV, and paging services only, and do not include other special equipment (i.e. servers). 2. Minimum Size: 100 Square Feet, 10 x 10. a) For each additional rack beyond the standard two, add 40 Square Feet HVAC A. The need for separate HVAC for Technology Rooms is defined in NFPA B. The TER shall have an individual, wall mounted, split HVAC unit that is designed to dissipate the heat generated by electrically powered communications equipment. 1. Wall Mounted, Split Unit, Cooling Only 2. Compact side discharge outdoor unit 3. Wireless remote control 4. Automatic restart after power outage 5. 15,000 Btu/h, SEER /230V, 1 Phase 7. Mitsubishi Electric, Mr. Slim or approved equal C. HVAC shall be available 24 hours per day, 365 days per year. D. HVAC shall not be controlled by energy management systems. E. The control for the HVAC services shall be placed 72 AFF. F. No heating diffusers shall be placed in any Telecommunications rooms Air Exhaust A. The TCs shall have an individual exhaust fan that is designed to dissipate the heat generated by electrically powered communications equipment. 1. Minimum 500 CFM 2. Should provide a 3 minute air change. 3. Wire guard 4. Always On B. Exhaust fan shall run 24 hours per day, 365 days per year. C. Exhaust fan shall not be controlled by energy management systems. D. No heating diffusers shall be placed in any Telecommunications rooms Ceiling A. TER ceiling height shall be a minimum of 10 AFF. B. TC ceiling height shall be a minimum of 9 AFF. C. If fire proofing is sprayed onto the exposed ceiling, the fire proofing shall be treated to mitigate airborne dust and a drop ceiling must be provided. D. Ceiling protrusions (e.g. sprinkler heads, lights, etc.) shall be placed to assure a minimum height of 8 6 AFF and shall not be located directly above any racks, cabinets, or equipment Floor A. TER Floor shall be covered in anti static vinyl. B. TC Floor shall be covered in anti static vinyl or smooth concrete. C. Finishes shall be light in color. D. In existing buildings any carpet shall be removed and the floor cleaned and resurfaced in anti static vinyl Walls A. Walls shall be treated to eliminate dust and painted with a light finish. B. Walls should be stud and wall board construction from floor to roof deck Lighting Version 8 Page 8 of 27 February 2, 2013

9 A. Lighting shall be mounted a minimum of 8 6 AFF and a minimum of 12 from wire basket tray. It shall be mounted such that it does not interfere with the cable pathways in the room. B. Lighting shall provide a minimum of 50 foot candles measured at a height of 3 AFF. C. Lighting should not be powered by the same electrical distribution panel as the power outlets in the room Door A. The door shall be a minimum of 36" wide and 80" tall and shall hinge outward. Door will be solid. No windows. B. TER and TCs will be equipped with Fob readers. C. Locks shall be keyed alike and unique from all other locks for all technology closets. Locks should be part of the interior master key. A copy of the building interior master key will be provided to at the time of core switch. D. Construction lock cores shall be keyed alike for all technology closets. Locks should be part of the interior master key. A copy of the building interior master key will be provided to at the time of construction core installation Windows A. Technology rooms will NOT have windows. B. In an existing building, if the TER or a TC has windows, they shall be filled in and painted to match the color of the room Fire Protection A. Fire protection of technology rooms should ideally be of an electronic safe material. B. If sprinkling is the only method available, the heads shall be provided with wire cages to prevent accidental operation. C. Drainage troughs shall be placed under the sprinkler pipes to prevent leakage onto the equipment within the room Naming and Labeling A. Labeling of TER and TC rooms shall begin with the TER being designated the A room and the first TC designated as the B room. All TCs after the first TC shall follow a consecutive alphabetic lettering scheme. REboxes are considered to be a TC and shall be labeled accordingly. B. Nameplate style signs indicating the TER and TC room and rack number identifier shall be placed on the center of the top crossbar of the racks. As an example the second rack in a TER would be labeled TER A2 and the second rack in the B TC room would be labeled TC B2. The nameplate style signs shall be a minimum of 1 ½ inches in height and consist of black letters on a white background. Nameplates may be engraved or printed. Hand written nameplates are not acceptable. Part 4 Electrical 4.1. Equipment in the Technology Rooms is considered to be part of a Critical Operations Data System as defined in NFPA As such, all power outlets in Technology Rooms shall be on generator circuits (if a generator is on site) TC A. One 120 volt 20 amp AC non switched duplex outlet shall be installed on each wall of the TC at a height of 16 above the finished floor for test gear, tools, etc. These four outlets will share one circuit not shared with other outlets or other electrical devices. These four outlets will be connected to the building generator. B. One 120 volt 20 amp AC duplex outlet shall be installed per 19 equipment rack, mounted on the rear of the base plate of the rack. Each outlet will be on a unique circuit not shared with other outlets, and will be connected to the building generator. Power conduits may be installed from above or below and shall NOT be put on the front of the rack, inside the rack, or in the vertical management. C. All outlets shall be labeled with the breaker panel and breaker number. Version 8 Page 9 of 27 February 2, 2013

10 D. All outlets shall be orange in color to signify generator power TER A. One 120 volt 20 amp AC duplex outlet shall be installed every 10 feet on each wall of the TER. A minimum of two outlets shall be on each wall. The outlet shall be at a height of 16 AFF. Each wall will be on a unique circuit not shared with other outlets or other electrical devices. B. One 220 volt 30 amp AC (NEMA L6 30R) outlet shall be installed on the wall directly centered behind the racks. This outlet will be on a unique circuit. C. One 120 volt 20 amp AC duplex outlet shall be installed per 19 equipment rack, mounted on the rear of the base plate of the rack. Each outlet will be on a unique circuit not shared with other outlets. D. Power conduits will be installed from above or below and shall NOT be put on the front of the rack, inside the rack, or in the vertical management. E. All outlets shall be labeled with the breaker panel and breaker number. F. All outlets shall be orange in color to signify generator power Electrical Grounding A. A grounding bar shall be installed in the TER and in each TC room for connecting the racks, frames, etc. B. This grounding bar shall be connected to the building ground system such that all TCs and the TER ground bars are at the same potential. C. Each rack must be direct wire bonded to the grounding bar. D. All wire basket tray shall be bonded to the grounding bar. Each individual section of basket shall be bonded. E. Bonding wires must be secured to the wire basket tray every 12 inches. Part 5 Wire Basket Tray 5.1. Wire basket tray shall be installed in the TER and all TCs at a nominal height of 8 AFF or under the raised floor Must be sized such that a 40% or less fill capacity is maintained Shall not interfere with, or be placed within 12 of lighting fixture ballasts Mounting methods will include wall brackets for tray adjacent to a wall, and trapeze for tray not adjacent to a wall. Support must meet manufacturer s recommendations. Provide adequate support to prevent leaning Shall have a minimum width of 18" and a minimum depth of Shall be routed over each row of equipment racks such that access is allowed between all racks and around the entire perimeter of the room Each rack must have direct access to the wire basket tray without traveling over other racks or spaces Appropriate spillways will be installed to accommodate any transitions to or from the wire basket The wire basket tray shall have protective end caps. Part 6 REbox TCs 6.1. REboxes may be used for small areas or areas with a high density (such as computer labs). The data cabling ONLY will be terminated in an enclosed wall mounted Hubbell REbox cabinet (RE 4X) (42 H x 24.2 W x10 D) mounted such that the top of the REbox is 72 inches AFF. The REbox shall be mounted on a wall that will not be used for room expansion (i.e. a corridor wall, rest room wall, etc.). A minimum of 36 inches clearance is required in front of the REbox for proper working space. The REbox shall be grounded to building steel or ground system The location of the REbox unit will be identified by Guilford County Schools Technology Services at the time of design A 120 volt 20 amp duplex AC Power outlet shall be provided within the REbox. The outlet will be placed at bottom left corner of REbox. Version 8 Page 10 of 27 February 2, 2013

11 Part 7 Racks, and Frames 7.1. Racks A. Floor Mounted Racks 1. Racks shall be located a minimum of 60 from center of rack to the wall directly behind. Clearance on the front side of the rack shall be a minimum of There shall be a minimum of four racks in the TER and two racks in each of the TCs. 3. Racks will be mounted side by side with the appropriate management between. 4. Nameplate style signs indicating the TER and TC room and rack number identifier shall be placed on the center of the top crossbar of the racks. As an example the second rack in a TER would be labeled TER A2 and the second rack in the B TC room would be labeled TC B2. B. Cable Management 1. Vertical Management a) All racks shall have one 8 inch wide vertical management panel on the right and left side of the rack. b) Between multiple racks there shall be a 12 inch vertical management between each rack and an 8 inch vertical management on each end rack Frames A. Backboard 1. Mount two (2) sheets of backboard plywood to one (1) wall of a TC. 2. Mount two (2) sheets of backboard plywood to two (2) walls of TER, a total of (4). 3. Mount backboard two (2) inches above electrical outlets, or cut out around outlets. 4. Paint plywood with white fire retardant paint. Mask one (1) fire rating label on each sheet for inspection verification. Part 8 Termination Panels 8.1. Category 6 Patch Panel A. Separation 1. Separate and distinct patch panels will be maintained for Data, Media, Security, and Wireless. B. Mounting 1. Patch panels shall be mounted in the center most rack of three or more racks, in the left most rack of two. 2. Racking Order from top to bottom: a) Fiber Enclosure b) Data Patch Panel c) Media Patch Panel d) Wireless Patch Panel e) Security Patch Panel 3. A space equal to one patch panel shall be left between each type of panel Block A. Voice and paging cabling terminations and equipment shall be mounted to the plywood backboard. Voice and paging cabling terminations shall NOT be directly behind or in interference with data racks. B. Horizontal cables shall be terminated on blocks separate from backbone cable. Version 8 Page 11 of 27 February 2, 2013

12 End of Section 07 SECTION 08 Backbone Cabling Part 1 Copper Backbone Cabling 1.1. See Section Master Technology Specification Provide multiple pair copper cable in quantities to ensure a maximum usage of 80% of cable pairs. Include speakers, paging signaling, analog phone cables, and other possible usage in count Provide outside plant copper with solid state protection clamped to 90 volts. Part 2 Fiber Backbone Cabling 2.1. See Section Master Technology Specification Fiber backbone shall consist of a 24 strand fiber to each TC from the TER and a 6 strand fiber from each REbox to the TER. Part 3 Coaxial Backbone Cabling 3.1. See Section Master Technology Specification Provide two coaxial backbone cables between the TER and each TC Provide two coaxial backbone cables between TER and CATV cabinet. End of Section 08 SECTION 09 Horizontal Cabling Part 1 Data 1.1. See Section Master Technology Specification Distance A. The maximum cable length shall be 90 meters (290 feet) including rise and fall. B. All cables are full run. Splices or inline connectors are not allowed Clearance A. Maintain a 12 inch minimum clearance from lighting fixtures, motors, or other objects that may cause interference. Part 2 Voice 2.1. See Section Master Technology Specification Distance A. The maximum cable length shall be 90 meters (290 feet) including rise and fall. B. All cables are full run. Splices or inline connectors are not allowed Clearance A. Maintain a 12 inch minimum clearance from lighting fixtures, motors, or other objects that may cause interference. Part 3 Integrated AV 3.1. See Section Master Technology Specification Distance A. RapidRun Plenum Rated Multi Format Runner Cable 1. The maximum cable length shall be 75 feet. 2. All cables are full run. Splices or inline connectors are not allowed. B. RapidRun Plenum Rated Digital Plenum Runner Cable Version 8 Page 12 of 27 February 2, 2013

13 1. The maximum cable length shall be 25 feet. 2. All cables are full run. Splices or inline connectors are not allowed. C. USB Extender 1. The maximum cable length shall be 100 feet. 2. All cables are full run. Splices or inline connectors are not allowed. End of Section 09 SECTION 10 Outlet Types Part 1 Outlet Symbols 1.1. Analog Communications A. A Analog Phone/FAX 1.2. Audio/Video A. AES Audio Enhancement System B. AVD Display C. AVF Front D. AVH HDMI E. AVP Projector F. M Media G. UR USB Receiver H. UT USB Transmitter 1.3. Paging/Intercom A. CB Call Button B. IS Intercom Speaker C. PS Paging Speaker D. VC Volume Control 1.4. Data A. D2 Data, 2 Jacks B. D4 Data, 4 Jacks C. R2 Rebox, 2 Jacks D. R4 Rebox, 4 Jacks 1.5. Panels A. PD Display 1. AVD 2. M B. PF Front 1. AVF 2. AVH C. PP Projector 1. AVF 2. AVH 3. AVP 4. UR D. PT Teacher 1. AVD Version 8 Page 13 of 27 February 2, 2013

14 2. AVP 3. D2 4. UT 1.6. Security A. SA Access Control B. SC Camera C. SK Keypad D. SM Motion Detector E. SN Node F. SS Switch 1.7. Wireless A. W Wireless Part 2 Outlet Details 2.1. See Sections , , Master Technology Specification. End of Section 10 SECTION 11 Room Descriptions Part 1 General 1.1. The following lists the basic requirements for types of rooms. Individual schools, and individual rooms will have specific requirements to be determined during the design phase Not all room types are listed. Some rooms will have specific designs created during the design phase. Part 2 Administrative Office 2.1. D2 Two (2) on adjacent walls coordinated with furniture PS One (1) in ceiling VC One (1) near door. Part 3 Cafeteria 3.1. Dining A. D2 Two (2) on opposite walls. B. M Two (2) on opposite walls. C. PS Number and spacing to be determined. Speakers should be placed a distance apart equal to twice the ceiling height. D. CB One (1) near serving line, but accessible when serving line is closed. E. IS One (1) near serving line, but accessible when serving line is closed Office A. D2 Two (2) on adjacent walls. B. PS One (1) in ceiling. C. VC One (1) near door Serving Line A. Note: all outlet boxes must be sealed for health code. B. D2 One (1) at each point of sale location. C. CB One (1) at each serving line. D. IS One (1) over each serving line. Version 8 Page 14 of 27 February 2, 2013

15 Part 4 Classroom 4.1. AES One (1) in ceiling near center CB One 1) near door D4 One (1) on side wall IS One (1) in ceiling near center PD One (1) on teaching wall PF One (1) on teaching wall PP One (1) on teaching wall PT One at teacher desk location W One (1) in ceiling near center. Part 5 Computer Lab 5.1. AES One (1) in ceiling near center CB One 1) near door D4 One (1) on side wall IS One (1) in ceiling near center PD One (1) on teaching wall PF One (1) on teaching wall PP One (1) on teaching wall PT One at teacher desk location D2 or R2 Twenty (20) arranged to fit room and furniture. (Teacher Panel D2 is not included in this number) W One (1) in ceiling near center. Part 6 Conference Room 6.1. AVD Two (2) total, one (1) at M, one (1) below M at 16 AFF AVH Two (2) total, one (1) at M, one (1) below M at 16 AFF D2 Two (2) total, one on viewing wall, one (1) on opposite M One (1) on viewing wall at 96 AFF PS One (1) in ceiling VC One (1) near door W One (1) in ceiling. Part 7 Corridors and Common Spaces 7.1. M To be determined during design phase PS Number and spacing to be determined. Speakers should be placed a distance apart equal to twice the ceiling height W To be determined during design phase. Part 8 HVAC Control 8.1. D2 One (1) at each HVAC control unit. Part 9 Media Center (Elementary/Middle) 9.1. AES One (1) near marker board or teaching area CB One (1) at circulation desk D2 A. Two (2) in circulation desk. B. Five (5) in the book stacks area. C. Five (5) in the mini lab M Version 8 Page 15 of 27 February 2, 2013

16 A. One (1) behind circulation desk. B. One (1) in general seating area IS One (1) over circulation desk PF One (1) under marker board or teaching area PP One (1) over marker board or teaching area PS Number and spacing to be determined. Speakers should be placed a distance apart equal to twice the ceiling height PT One (1) near marker board or teaching area. Part 10 Media Center (High) AES One (1) near marker board or teaching area CB One (1) at circulation desk D2 A. Three (3) in circulation desk. B. Seven (7) in the book stacks area. C. Five (5) in mini lab 1. D. Five (5) in mini lab M A. One (1) behind circulation desk. B. One (1) in general seating area IS One (1) over circulation desk PF One (1) under marker board or teaching area PP One (1) over marker board or teaching area PS Number and spacing to be determined. Speakers should be placed a distance apart equal to twice the ceiling height PT One (1) near marker board or teaching area. Part 11 Media Office D2 Two (2) coordinated with furniture PS One (1) in ceiling VC One (1) in ceiling. Part 12 Principal / Assistant Principal D2 Two (2) on adjacent walls coordinated with furniture M One (1) on wall opposite desk location PS One (1) in ceiling VC One (1) near door. Part 13 Reception A One (1) on counter D2 Two (2) on counter D2 One (1) on back wall M One (1) Viewable from reception waiting area PS One (1) in ceiling VC One (1) on back wall W One (1) in center of room. Part 14 Workroom (Admin) A One (1) on counter D2 Two (2), one on counter, one on opposite wall. Version 8 Page 16 of 27 February 2, 2013

17 14.3. PS One (1) in ceiling VC One (1) near door. End of Section 11 SECTION 12 Wireless Design Part 1 General 1.1. The following should be used to create a basic starting design. Final design will be created during the design phase Wireless outlets in suspended ceilings will be mounted inside a Panduit PZWC35I PanZone Wireless Access Point Enclosure Wireless outlets in hard ceiling will be mounted inside a Panduit PZWC35 PanZone Wireless Access Point Enclosure for surface mount Wireless outlets on walls will be mounted inside a Panduit PZWC35 PanZone Wireless Access Point Enclosure for surface mount. Part 2 Administration 2.1. One (1) in reception area One (1) every 50 feet. Minimum of one (1). Part 3 Classroom 3.1. One (1) in each classroom or lab space. Part 4 Common Spaces (Cafeteria, Gym, Multipurpose, etc.) 4.1. Two (2) located above doorways. Shall not be blocked by goals, etc. Part 5 Corridors (Non Classroom) 5.1. One (1) every 50 feet. Minimum of one (1). Part 6 Exterior 6.1. Exterior locations will have the outlet inside the building with a sleeve for antenna cable to exterior Bus Loading 6.3. Car Loading 6.4. Playground Part 7 Loading Dock 7.1. One (1). Part 8 Media Center 8.1. Two (2). End of Section 12 SECTION 13 Security Design Part 1 General 1.1. The following should be used to create a basic starting design. Final design will be created during the design phase. Part 2 Access Control 2.1. SA FOB Reader A. All SA locations must have an electric strike on the door. B. One (1) at each exterior door that is used for normal building access. Version 8 Page 17 of 27 February 2, 2013

18 C. One (1) at each telecommunications closet. D. One (1) at each classroom exterior door if used for playground, outdoor classroom, etc. E. Main entrance door reader shall be included in a camera/intercom door access system provided by GCS SN MicroNode A. Placed as needed to support SAs SS Door Contact Switch A. On each exterior door. Part 3 Intrusion Detection 3.1. SM Motion Detector A. One (1) at each exterior door. B. One (1) in each computer lab. C. One (1) every 100 feet in corridors, minimum of one per corridor. D. One (1) in every large space (cafeteria, gym, etc.) that does not have exterior doors. Part 4 Video Surveillance 4.1. SC Security Camera A. Interior 1. One (1) at each exterior door. 2. One (1) at media circulation desk. 3. One (1) at each cafeteria serving line. 4. One (1) in reception area. 5. Corridors, stairwells, common areas should be covered. Restrooms doors should be covered. B. Exterior 1. One (1) at bus loading. 2. One (1) at car loading area. 3. One (1) at loading dock. 4. Perimeter coverage of building. End of Section 13 SECTION 14 Audio Video Special Requirements Part 1 Wall Support 1.1. Flat Screen Display and Projector will require additional support to be installed in the wall system Support should consist of appropriately engineered studs, cross bracing, back panels, etc Support will be provided by the construction contractor Flat Screen Display support must handle a load of 100 lbs Projector support must handle a load of 50 lbs. Part 2 Audio Enhancement Support 2.1. The audio enhancement system requires support from the building structure. Hanger wires must be provided. Part 3 Overhead Speaker Rigging 3.1. Overhead speakers in gyms and auditoriums shall be designed to meet all codes and safety requirements. Version 8 Page 18 of 27 February 2, 2013

19 3.2. Rigging diagrams shall be included in drawings. End of Section 14 SECTION 15 Clock System Part 1 General 1.1. A clock system as described in Section of Master Technology Specification shall be designed All classrooms, offices, work rooms, gathering spaces, and any other space occupied by staff or students shall have a clock. End of Section 15 SECTION 16 Fire Alarm Design Part 1 General 1.1. All Fire Alarm System design and installation shall comply with requirements of the latest edition of NC State Construction Office (NCSCO) guidelines and policies Engineer of Record shall design a complete fire detection system with total smoke detector coverage The installation shall meet NFPA 72, chapter 6 Requirements for Notification 1.4. Appliances for Fire Alarm Systems. A performance specification may be used to ensure compliance with all applicable codes, however the minimum quantity of notification appliances shall be as shown on plans and risers. A performance specification may be used to ensure the required audible signal levels are achieved The Fire Alarm Control Panel (FACP) or annunciator, shall be mounted at the building s designated emergency entrance. Annunciation of all building alarms shall occur in one central location. This includes fire, ventilation failure, and gas monitor alarms. Part 2 Materials and Standards 2.1. The fire alarm system design shall include at a minimum: A. A dual contact time delay relay (minimum 60 seconds capability) installed at the main FACP to delay system trouble signals to the Emergency Communications Center. B. Compression type fittings for all conduit with insulated throats. C. If duct smoke detectors and/or linear beam smoke detectors are installed, a Remote Alarm Indicating Light (RAIL) that includes a test switch mounted at 8' 0" AFF shall be provided. D. Magnet test capability for all smoke detectors. E. Pull stations with keyed locks for resetting purposes. Allen key type locks are unacceptable. Two (2) keys for each pull station shall be supplied to GCS. F. Three (3) isolation modules for each addressable loop; two (2) at the FACP and one (1) midway through the loop address scheme. G. Devices for addressable systems to match the brand of FACP installed. 1. These devices shall be addressable analog devices. H. The following bypass switches must be programmed into the system: 1. Audio/visual bypass 2. Tamper switch bypass (programmed as non latching) Version 8 Page 19 of 27 February 2, 2013

20 3. Waterflow bypass (silenceable only) I. Wiring color codes shall be: 1. Conventional initiating circuit, white/red, 14 gauge stranded, THHN 2. Door holders, orange+/grey, 14 gauge stranded, THHN. J. CO/Freon gas alarms that require monitoring shall tie directly to the DAC. K. Air Handing Units 15,000 cfm or larger require duct detectors on the supply and return sides of the unit. L. Duct detectors in laboratory buildings shall shut down air handlers only when smoke is detected at the duct detector. General alarm shall not shut down these units. M. A minimum of one addressable loop shall be provided per building floor. N. A minimum of one addressable loop shall be provided per wing. O. All fire alarm system devices located on any exterior building surface shall be weatherproof as defined by the National Electric Code. P. Systems installed in building additions or renovations shall be U.L. listed, matching existing devices or approved compatible devices for use with the existing fire alarm control panel (FACP). End of Section 16 Version 8 Page 20 of 27 February 2, 2013

21 Classroom Teaching Wall Version 8 Page 21 of 27 February 2, 2013

22 Teaching Wall Detail Version 8 Page 22 of 27 February 2, 2013

23 Cafeteria Version 8 Page 23 of 27 February 2, 2013

24 Administrative Offices Version 8 Page 24 of 27 February 2, 2013

25 Flat Screen and Projector Mount Version 8 Page 25 of 27 February 2, 2013

26 Overhead Speaker Rigging Version 8 Page 26 of 27 February 2, 2013

27 End of Version 8 Page 27 of 27 February 2, 2013

Charleston excellence is our standard County SCHOOL DISTRICT

Charleston excellence is our standard County SCHOOL DISTRICT Charleston excellence is our standard County SCHOOL DISTRICT FACILITY SECURITY ACCESS CONTROL, INTRUSION DETECTION, AND SURVEILLANCE DESIGN SPECIFICATIONS FOR NEW CONSTRUCTION, ADDITIONS, AND MAJOR RENOVATIONS

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

SECTION INTRUSION DETECTION SYSTEM

SECTION INTRUSION DETECTION SYSTEM SECTION 13845 INTRUSION DETECTION SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete, operable, tested intrusion detection system, bearing Underwriters Laboratories (UL) mercantile listing

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. The present fire alarm system manufactured by Gamewell was installed with the 1982 renovation. It is a non addressable, zoned system. It includes

More information

MEDIA CENTER September 30, 2010

MEDIA CENTER September 30, 2010 MEDIA CENTER September 30, 2010 I. PROGRAM REQUIREMENTS Refer to the project-specific Schedule of Spaces for student stations, square footage, and for any requirements that may differ from the prototype

More information

Page 1 of General

Page 1 of General Page 1 of 8 16.1 General 1. This section covers items common to sections of CSI s Master Format - Division 16. 2. Dalhousie University is certified by IBEW for new construction and all electrical contractors

More information

Electrical Inspection Special Electrical

Electrical Inspection Special Electrical 0941 Fire Alarm System Devices, panels, wiring, conduit, etc. Description of the building system The school is equipped with a hard wired fire alarm control panel, and automatic dialer. The fire alarm

More information

Library stacks and records storage 150 LB/SF live load

Library stacks and records storage 150 LB/SF live load SPACE TYPE: LIBRARY Construction Criteria The unit costs for Library space types are based on the construction quality and design features in the following table. This information has been generally organized

More information

SECTION INTRUSION DETECTION

SECTION INTRUSION DETECTION (NOTE TO DESIGNER: These Specifications are basic minimum criteria to be met in preparing the final specifications for this section, which is the responsibility of the Designer.) SECTION 28 16 00 INTRUSION

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District

HOLUM EDUCATION CENTER. Architectural. January 13, 2014 DeForest Area School District HOLUM EDUCATION CENTER Architectural The existing building has approximately 41,823 square feet and sets on a lot about 4.14 acres in size. Parking lots are located along the east and west sides of the

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ). SECTION 28 13 00 - ACCESS CONTROL PART I - GENERAL 1.1 SUMMARY A. This specification section describes the furnishing, installation, commissioning, and programming of a complete, turnkey, hardwired Andover

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods 1. BASIC ELECTRICAL MATERIALS 1. All conduit and raceway must be 3/4" or larger. Exposed raceway in finished areas shall be in 700 or larger wiremold. Exception: runs to individual devices 10 or less,

More information

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings 1 T Consultant: NOTES, SYMBOLS & ABBREVIATIONS - MECHANICAL Number Description M001 Vestibule 117 LAN/IT Coffee 115 116 Mail Room 118 114 113 112 Scanning 119 Open Office 101 FIRST FLOOR PLAN - MECHANICAL

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cabinets, Racks, Frames and Enclosures

Section COMMUNICATION EQUIPMENT ROOM FITTINGS. Section Communications Cabinets, Racks, Frames and Enclosures PART 1 GENERAL 1.1 WORK INCLUDED Section 27 11 00 COMMUNICATION EQUIPMENT ROOM FITTINGS Section 27 11 16 Communications Cabinets, Racks, Frames and Enclosures A. Provide all labor, materials, and equipment

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions: SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

5. Identification products.

5. Identification products. Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 [SECTION 260523- CONTROL-VOLTAGE ELECTRICAL POWER CABLES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SPACE TYPE: JUDICIAL CHAMBER

SPACE TYPE: JUDICIAL CHAMBER SPACE TYPE: JUDICIAL CHAMBER Construction Criteria The unit costs for Judicial Chamber space types are based on the construction quality and design features in the following table. This information has

More information

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15

F. GENERAL REQUIREMENTS Electrical Design Criteria 2006 Edition 4/3/06 School District Palm Beach County Page-1 of 15 ELECTRICAL DESIGN CRITERIA TABLE OF CONTENTS I GENERAL...2 II CRITERIA...2 A. POWER DISTRIBUTION SYSTEMS...2 1. NORMAL POWER:...2 2. EMERGENCY POWER...3 B. LIGHTING...4 1. GENERAL...4 2. AVERAGE MAINTAINED

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

PLATTEVILLE MIDDLE SCHOOL

PLATTEVILLE MIDDLE SCHOOL Architectural The building has aluminum clad wood awning windows in combination with aluminum fixed glass units. They appear to be exterior glazed with insulated glazing. See photo 2. Platteville Middle

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

GARCIA GALUSKA DESOUSA Consulting Engineers

GARCIA GALUSKA DESOUSA Consulting Engineers L#57297 /Page 1/July 21, 2017 ELECTRICAL SYSTEMS NARRATIVE REPORT The following is the Electrical Systems narrative, which defines the scope of work and capacities of the Power and Lighting systems, as

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

GENERAL ASSIGNMENT CLASSROOM DESIGN STANDARDS

GENERAL ASSIGNMENT CLASSROOM DESIGN STANDARDS University of Iowa FSG - Design & Construction Services Design Reference Manual 2 Design Standards 2.02 Classroom Design Standards Classroom Design Standards GENERAL ASSIGNMENT CLASSROOM DESIGN STANDARDS

More information

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School

ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL SYSTEMS ASSESSMENT Hanover High School ELECTRICAL DISTRIBUTION SYSTEM:?? The existing electrical service consists of an underground primary service originating at a utility pole on Cedar Street,

More information

PLAN REVIEW SUBMITTAL GUIDE

PLAN REVIEW SUBMITTAL GUIDE PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.

More information

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup. SECTION 23 70 00- CENTRAL HVAC EQUIPMENT PART 1: GENERAL 1.1 PURPOSE: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW) SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill

More information

Telecommunications Survey

Telecommunications Survey Victor Valley College Telecommunications Survey Victor Valley College 18422 Bear Valley Road Victorville, CA 92395 November 30, 2010 Submitted by P2S Engineering, Inc. Executive Summary Background and

More information

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17

F. GENERAL REQUIREMENTS Electrical Design Criteria 2009 Edition 11/23/2009 School District Palm Beach County Page-1 of 17 ELECTRICAL DESIGN CRITERIA TABLE OF CONTENTS I GENERAL...2 II CRITERIA...2 A. POWER DISTRIBUTION SYSTEMS...2 1. NORMAL POWER:... 2 2. EMERGENCY POWER... 3 B. LIGHTING...4 1. GENERAL... 4 2. AVERAGE MAINTAINED

More information

Special Provision No. 682S27 June This Special Provision refers to the following standards, specifications or publications:

Special Provision No. 682S27 June This Special Provision refers to the following standards, specifications or publications: CONTROLLER CABINETS, POLE MOUNTED - Item No. Special Provision No. 682S27 June 2017 1. SCOPE This Special Provision covers the requirements for the installation of pole mounted controller cabinets and

More information

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6 SECTION 601 GENERAL 601.1 Scope. Duct systems used for the movement of air in air-conditioning, heating, ventilating and exhaust systems shall conform to the provisions of this chapter except as otherwise

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY

DIVISION 28 ELECTRONIC SAFETY AND SECURITY 281300 - ACCESS CONTROL A. General DIVISION 28 ELECTRONIC SAFETY AND SECURITY At the beginning of the project, schedule a meeting with the Facilities Access/Maintenance Coordinator with questions and concerns.

More information

Changes to this Division since the last issuance are indicated with yellow highlighted text.

Changes to this Division since the last issuance are indicated with yellow highlighted text. Table of Contents 28 10 00 ELECTRONIC ACCESS CONTROL AND INTRUSION DETECTION... 2 A. GENERAL... 2 B. DESIGN REQUIREMENTS... 2 C. CONSTRUCTION REQUIREMENTS... 3 28 20 00 ELECTRONIC SURVEILLANCE... 4 A.

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

Special Provision No. 683S28 December 2017

Special Provision No. 683S28 December 2017 FIBRE OPTIC COMMUNICATION CABLES, AERIAL ON MESSENGER CABLE - Item No. FIBRE OPTIC COMMUNICATION CABLES, AERIAL ON MESSENGER CABLE (TEMPORARY) - Item No. Special Provision No. 683S28 December 2017 1. SCOPE

More information

Related Sections: TBD. Effective Date: January 1, 2016

Related Sections: TBD. Effective Date: January 1, 2016 Description: The purpose of the section is to highlight the current applicable UMCP Design Standards for the design, selection and, installation of lighting fixtures within buildings. Related Sections:

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY

DIVISION 28 ELECTRONIC SAFETY AND SECURITY DIVISION 28 ELECTRONIC SAFETY AND SECURITY CENTRALLY MANAGED ELECTRONIC ACCESS CONTROL, VIDEO SURVEILLANCE, AND INTRUSION ALARM SYSTEMS 1. All questions on equipment approvals in this section shall be

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Coaxial cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control

More information

Port of Portland Conveying Equipment Guidelines

Port of Portland Conveying Equipment Guidelines Role: Consultant for the Port Design Guidelines Port of Portland Conveying Equipment Guidelines ELEVATOR, ESCALATOR, AND MOVING WALK DESIGN OVERVIEW The Division 14 specification sections include appropriate

More information

FIRE SPRINKLER SYSTEMS POLICY

FIRE SPRINKLER SYSTEMS POLICY FIRE SPRINKLER SYSTEMS POLICY Revised 1/1/17 DESIGN AND SUBMITTAL REQUIREMENTS All new and existing fire sprinkler systems within the jurisdiction of the City Fire Department shall meet all of the applicable

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

BSD Technical Standard. Division 28: Electronic Safety & Security

BSD Technical Standard. Division 28: Electronic Safety & Security Division 28: Electronic Safety & Security I. PURPOSE This Technical Standard is a narrative describing Beaverton School District s (BSD s) basis of design for electronic safety and security in BSD facilities.

More information

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT State College Area School District High School South Building Prepared by CenterPoint Engineering 08 February 2013 FACILITY ASSESSMENT SUMMARY PHYSICAL PLANT General HVAC This report is a snapshot of the

More information

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.

More information

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain

More information

Dates of Construction Construction Start 2/28/1999 Date of Completion 4/2000 Occupancy 5/2000

Dates of Construction Construction Start 2/28/1999 Date of Completion 4/2000 Occupancy 5/2000 Executive Summary The Milton S. Hershey Medical Center Academic Support Building is located on The Pennsylvania State University's campus in Hershey, PA. The building is owned by The Pennsylvania State

More information

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE SECTION 21 1313 WET-PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.02 RELATED

More information

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR September 2012, rev. 00 26 0553 Identification for Electrical Systems PART 1. GENERAL 1.01 Summary A. Section Includes: 1.02 Submittals 1. Identification for raceways. 2. Identification of power and control

More information

University Design Standard Fire Alarm Systems

University Design Standard Fire Alarm Systems 1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101

More information

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE

TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE TAB C-6 KEYLESS ACCESS AND SECURITY SYSTEM GUIDELINE The University of Arizona has implemented a Keyless Access and Security System program to provide a cost effective, efficient, and maintainable means

More information

CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN

CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN CLEVELAND HEIGHTS UNIVERSITY HEIGHTS CITY SCHOOL DISTRICT MONTICELLO & ROXBORO MIDDLE SCHOOLS INTERIOR DESIGN 04.13.2017 1 MONTICELLO INTERIOR FINISHES PAINT MOULDING WALLS ACCENT DOORS DOOR TRIM/STAIRS

More information

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC SECTION 08 35 13.23 ACCORDION FOLDING FIRE DOORS PART 1 GENERAL 1.01 SUMMARY OF WORK A. Division 0 and 1, as indexed, apply to this section. B. Furnish and install

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Design Guideline Element includes design standards and requirements for telecommunications service and distribution. This is a design standard and is not intended

More information

DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD

DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD LIGHTING FIXTURES AND CIRCUITRY & SWITCHING SECONDARY SCHOOLS 1. GENERAL 1.1.1. Consultants MUST prepare a Summary of Fixtures which will include catalogue

More information

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 DESCRIPTION Fire-suppression wet and manual dry standpipes. 1.2 SCOPE OF WORK SECTION 21 12 00 A. Design, installation and testing shall be in accordance with NFPA 14 except for specified

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

Guide Specifications. HyperPod System PART 1 - GENERAL 1.01 SUMMARY

Guide Specifications. HyperPod System PART 1 - GENERAL 1.01 SUMMARY Guide Specifications HyperPod System THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI) MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED

More information

Sprinkler Permit Applications

Sprinkler Permit Applications REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations

More information

DIVISION 13 - SPECIAL CONSTRUCTION

DIVISION 13 - SPECIAL CONSTRUCTION DIVISION 13 - SPECIAL CONSTRUCTION I. GENERAL A. This division contains the following elements: 1. Relocatable Buildings. 2. Telephone and Data Systems. 3. Intercom and Clock/Bell System. 4. Wiring and

More information

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler

More information

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. DIVISION 26 ELECTRICAL SECTION 26 27 26 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings. B. Specialty switches and outlets

More information

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS WHITE PLAINS SMOKE CONTROL CODE a. Application of Code. PART 1. GENERAL REQUIREMENTS The following uniform standards and procedures shall apply to the design, installation and testing of new smoke purge

More information

Leviton Combination Switch And Tamper Resistant Outlet Wiring Diagram

Leviton Combination Switch And Tamper Resistant Outlet Wiring Diagram Leviton Combination Switch And Tamper Resistant Outlet Wiring Diagram Leviton SmartLockPro 15 Amp Tamper-Resistant Combination GFCI Duplex Outlet and Switch - White-R02-X7299-00W - The Home Depot. From

More information

Additions & Alterations to Ascension Parish Library Galvez Prairieville, Louisiana Project No. 1401

Additions & Alterations to Ascension Parish Library Galvez Prairieville, Louisiana Project No. 1401 Henry L. Chauvin, Architect, LLC 9429 Highway 941 Gonzales, Louisiana 70737 (225) 612-0707 Fax: (224) 612-4565 Email: henry.chauvin@outlook.com Additions & Alterations to Ascension Parish Library Galvez

More information

SECTION PUBLIC ADDRESS SYSTEMS

SECTION PUBLIC ADDRESS SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Amplifier and control equipment B. Input equipment C. Raceways and communications cable D. List of equipment for gym PA system E. List of equipment for cafeteria

More information

APPENDIX H (DESIGN SUBMISSION CRITERIA)

APPENDIX H (DESIGN SUBMISSION CRITERIA) APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation

More information

FIRE SPRINKLER SYSTEMS POLICY

FIRE SPRINKLER SYSTEMS POLICY FIRE SPRINKLER SYSTEMS POLICY VERSION 1.012/2015 FIRE SPRINKLER SYSTEMS Design and Submittal requirements All new and existing fire sprinkler systems within the jurisdiction of the City of San Mateo Fire

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

SECTION (13900) - FIRE SUPPRESSION SYSTEMS PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

DIVISION 13 SPECIAL CONSTRUCTION

DIVISION 13 SPECIAL CONSTRUCTION DIVISION 13 SPECIAL CONSTRUCTION This division contains the following elements: 1.1 General. 1.2 Utility Provisions for Future Expansions. 1.3 Telecommunications Systems. 1.4 Intercom and Clock/Bell System.

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

B. Special Documentation Requirements. C. Materials and methods of Construction

B. Special Documentation Requirements. C. Materials and methods of Construction DIVISION 13 SPECIAL CONSTRUCTION 13100 LIGHTNING PROTECTION 1. Lightning Protection: Each building shall be considered individually to determine the necessity for lightning protection. The building location,

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

CENTRAL AIR CONDITIONER SPLIT SYSTEM

CENTRAL AIR CONDITIONER SPLIT SYSTEM CENTRAL AIR CONDITIONER SPLIT SYSTEM WITH ELECTRONIC CONTROL SERIES: DS INSTALLATION INSTRUCTIONS INDEX GENERAL... 2 UNIT LOCATION CRITERIA... 2 DIMENSIONAL DRAWINGS... 3 INDOOR UNIT INSTALLATION... 5

More information

DESIGN & CONSTRUCTION GUIDELINES

DESIGN & CONSTRUCTION GUIDELINES ADMINISTRATIVE SERVICES 4202 E. FOWLER AVENUE, FPC110 PHONE: (813) 974-2625 FACILITIES PLANNING & CONSTRUCTION TAMPA, FLORIDA 33620-7550 WEBSITE: USF.EDU/FPC DESIGN & CONSTRUCTION GUIDELINES DIVISION 21

More information

SECTION EXTERIOR LIGHTING

SECTION EXTERIOR LIGHTING SECTION 26 56 00 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of exterior luminaries, controls, poles and supports. 1.2 RELATED WORK A. Section 26

More information