1 ACTIVE FIRE PROTECTION SYSTEMS OVERVIEW ICC: International Code Council codes are updated on a 3-year revision cycle Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Fire Protection Systems Passive systems (generally architectural) Fire egress paths Fire rated constructions Spray-on fireproofing Areas of refuge portable extinguishers: previously discussed are an active, architectural system Active systems (primarily mechanical & electrical) Fire sprinklers Fire alarms Standpipes today s focus Other (specialized) systems Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 2 1

2 Standpipe and Hose Systems The left side of image big help System is designed by a mechanical engineer It is a manual system Going beyond first aid, this system provides an easily accessible and substantial water supply for fire extinguishment (big gesture versus small gesture) Code-optional OR mandatory (building type determines) System design issues Class of service (based upon intended users) Outlet locations (hose distance / spray coverage by code) Water supply help Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 3 Standpipe and Hose Systems Classes: I (for trained users; has large valve, no hose) II (for untrained users; smaller valve, with hose) III (for both user groups) Components: Water supply (may be volumetrically significant) Generally vertical pipe runs (easy to coordinate) Valves (and perhaps hoses/cabinets) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 4 2

3 Standpipe and Hose Systems non-freezing climate typical installation (pipe hidden) Class I bring your own hose; firefighters do so Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 5 Standpipe and Hose Systems casual user casual or trained user Class II element Class I element Class II Class III Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 6 3

4 Standpipe and Hose Systems custom architectural enclosure in an atrium with no opaque walls a solution that pushed the letter of the code, while meeting the intent Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 7 Standpipe/Hose & Extinguisher any ideas? oops! one-stop extinguishment stations with issues Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 8 4

5 Automatic Sprinkler Systems Automatic fire sprinkler system Designed by a mechanical engineer (or, more often, by a sprinkler contractor) Is an automatic system (no operator required) Code-optional OR mandatory (building type determines) Common in many building types (becoming increasingly common) System design issues System type (several) Sprinkler head locations and types Water supply a good place for a duct Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 9 Automatic Sprinkler Systems Types: Wet pipe by far the most common Dry-pipe where freezing of water is possible Deluge for high-hazard applications Pre-action where concern over water damage rules Components: Sprinkler heads Piping network (to connect heads to water supply) Water supply Appurtenances: control valves; alarms; drains; etc. Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 10 5

6 Wet-Pipe Sprinkler System Pipes are always filled with water Heat from a fire opens a sprinkler head by causing the head to fail (a metal link melts or a glass bulb breaks) Usually only one or two heads will open (those that experience higher temperatures near the fire) Water flows until it is shut off (usually manually) The open ( broken ) sprinkler head is replaced The system is reset Options: A wide variety of conventional sprinkler heads Recessed (flush) sprinkler heads Auto-shut-off heads (no longer manufactured due to quality control issues) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 11 Wet-Pipe Sprinkler System NFPA Fire Protection Handbook (20 th ed.) all pipes are filled with water; opening of a sprinkler head triggers water flow Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 12 6

7 Dry-Pipe Sprinkler System Pipes are not filled with water (but are pressurized with gas or air) Heat from a fire opens a sprinkler head Usually only one or two heads open Pressure drop in the piping (as air escapes from open head) opens a dry-pipe valve water valve (the dry-pipe valve) Water fills the piping network and then exits through the open sprinkler head(s) and sprays onto the fire Water flows until it is shut off The open sprinkler head is replaced System is reset news.thomasnet.com Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 13 Dry-Pipe Sprinkler System NFPA Fire Protection Handbook (20 th ed.) pipes in protected space are filled with inert gas/air; an opening sprinkler head triggers the system by releasing the gas, which reduces pressure and allows water to flow into the pipes and then out through the open sprinkler head Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 14 7

8 Deluge Sprinkler System Pipes are not filled with water (or gas) All sprinkler heads are pre-opened A signal from a fairly sensitive detection device mechanically opens a water valve Water fills the pipes and flows from all heads objective is to ensure that a very dangerous fire situation is quickly defused Water flows until it is shut off System is reset Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 15 Deluge Sprinkler System NFPA Fire Protection Handbook (20 th ed.) pipes in protected area are empty; a detector signal triggers the system, allowing water to enter pipes and flow from all sprinkler heads (which are already open) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 16 8

9 Pre-Action Sprinkler System Pipes are not filled with water All sprinkler heads are of standard type (they are normally closed) A detection device opens a water valve when it senses a triggering event (such as smoke) Water fills the pipes Water will only flow from a sprinkler head if it is opened by heat from a fire Water flows until shut off (or, more logically, detectors close the control valve) System is reset Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 17 Pre-Action Sprinkler System NFPA Fire Protection Handbook (20 th ed.) pipes in protected area are empty; a detector signal triggers the system, allowing water to enter pipes and flow into piping network; heat from a fire may then open a sprinkler head; accidental damage to a head will not result in water flow Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 18 9

10 Sprinkler Heads Basic types Upright Pendant Sidewall Tweaks Recessed heads Self-closing heads (taken off market) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik Sprinkler Heads frangible bulb fusible link The typical sprinkler head Is activated by heat (temperature) Opens when a triggering action occurs A frangible bulb breaks (color indicates temperature setting) A fusible link melts Water flows when the head is opened Water is manually shut off Once activated, head must be replaced Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 20 10

11 Sprinkler Heads pendant with frangible bulb >> Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 21 Sprinkler Heads pendant with fusible link >> Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 22 11

12 Sprinkler Heads sidewall with >> frangible bulb Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 23 Sprinkler Heads recessed head ( flush ) ^^ usually selected in order to reduce visual impact Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 24 12

13 Quality Control? minimizing visual impact not so much with this one Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 25 Typical Sprinkler Piping Installation often designed and installed by a contractor; not an engineer thus the sprinklers may not appear on project drawings, reducing coordination (BIM) opportunities Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 26 13

14 Atypical Sprinkler Piping Installation hopefully, a retrofit project Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 27 Exterior Sprinklers why? type? Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 28 14

15 Fire Protection Water Supply The required capacity (based upon flow rate and flow duration) of fire protection water supply is specified by building codes (based upon NFPA standards) NFPA = National Fire Protection Association NFPA publishes the National Fire Codes (an extensive set of standards, which includes NFPA 101 the Life Safety Code) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 29 Fire Protection Water Supply governed by NFPA 13; one of numerous NFPA standards Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 30 15

16 Fire Protection Water Supply NFPA 13 excerpts dealing with sprinkler system water supply requirements Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 31 Water Supply Approaches (applicable to fire protection and potable water systems) Direct upfeed (the street main provides necessary pressure; only feasible for low-rise buildings with adequate mains pressure) Gravity downfeed (water is pumped to a rooftop storage tank and then flows down by gravity) Pumped upfeed (variable speed pumps are used to provide water lift upon demand) Hydro-pneumatic tanks (water tanks are pressurized with air to permit upfeed an alternative to pumped upfeed) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 32 16

17 Water Supply Approaches direct upfeed lift limited by water main supply pressure; must provide lift and adequate residual pressure to deliver water through hose/nozzle or sprinkler head water main Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 33 Water Supply Approaches tank gravity downfeed no height limit; pump provides lift and gravity provides adequate residual pressure; control is simple; has architectural and structural implications pump water main Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 34 17

18 Water Supply Approaches pumped upfeed no height limit; pump provides lift and adequate residual pressure; requires sophisticated controls (to provide water for one or two or three or four sprinkler heads); has replaced gravity systems; will be zoned in a tall building water main pumps Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 35 Water Supply Approaches hydropneumatic system no height limit; air pressure provides lift and adequate residual pressure; control is simpler than direct upfeed, but system is more complex (and requires a storage tank) air compressor water main pump Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 36 18

19 Sprinkler System Artifacts siamese connections a fire department connection to the building fire protection water system; a fire truck can pump water into a building from street hydrants using such connections Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 37 Other Fire Protection Systems High expansion foams Inert gas flooding system Others Halon (shown here) is a serious greenhouse gas and has been replaced by less problematic compounds used where a conventional water system won t work Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 38 19

20 Inert Gas Fire Protection Systems langemachinery.en.ecplaza.net Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 39 fire protection systems: because fires happen Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 40 20

(ACTIVE) FIRE PROTECTION SYSTEMS OVERVIEW. Fire Protection Systems

(ACTIVE) FIRE PROTECTION SYSTEMS OVERVIEW. Fire Protection Systems (ACTIVE) FIRE PROTECTION SYSTEMS OVERVIEW Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Fire Protection Systems Passive systems (generally architectural) Fire egress paths Fire walls Spray-on

More information

FIRE PROTECTION OPR. Fire, Buildings, and Codes

FIRE PROTECTION OPR. Fire, Buildings, and Codes FIRE PROTECTION OPR Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Fire, Buildings, and Codes Fire is one of the major hazards to life and property in buildings. Regulations in respect of fire

More information

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

Equipment: PowerPoint Presentation: Sprinkler Systems: Review and Response Considerations

Equipment: PowerPoint Presentation: Sprinkler Systems: Review and Response Considerations Title: Sprinkler Systems: Review and Response Considerations Instructor: Danny Braitsch Time: 1.5 hours Equipment: PowerPoint Presentation: Sprinkler Systems: Review and Response Considerations Enabling

More information

SECTION SPRINKLER SYSTEMS

SECTION SPRINKLER SYSTEMS SECTION 15325 SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler systems. B. Preaction sprinkler systems. C. System design, installation, and certification. D. Fire department

More information

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids. SECTION 211300 FIRE SUPPRESSION SYSTEMS 1.0 All new and renovated buildings shall be provided with automatic sprinklers throughout and fire standpipe systems. The design and installation of these systems

More information

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY PLAN REVIEWS SITE PLANS: 1) Access to buildings (Volume V NC Building Code sections 602.6.1

More information

SMOKE CONTROL: ISSUES / APPROACHES. Smoke, Not Flame

SMOKE CONTROL: ISSUES / APPROACHES. Smoke, Not Flame SMOKE CONTROL: ISSUES / APPROACHES Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Smoke, Not Flame The most significant cause of death in building fires is smoke, which accounted for 73% of

More information

Objective 1: Describe fire alarm systems.

Objective 1: Describe fire alarm systems. Chapter 20 Test Name: Date: Directions: Write the correct letter on the blank before each question. Objective 1: Describe fire alarm systems. 1. The purpose of a fire alarm system is to: (1178) A. prevent

More information

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Smoke, Not Flame

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Smoke, Not Flame SMOKE CONTROL Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Smoke, Not Flame The most significant cause of death in building fires is smoke, which accounted for 73% of fire-related deaths

More information

Element C3.4 Fire Fighting Equipment

Element C3.4 Fire Fighting Equipment .4 Fire Fighting Equipment Classification of Fires Class A Solids. Wood, paper, plastics Class B Liquids Petrol oil, paint Class C Gases LPG, natural gas Classification of Fires Class D Metals Zinc, sodium,

More information

COURSE OUTLINE Fire Protection Systems

COURSE OUTLINE Fire Protection Systems Butler Community College Health, Education, and Public Services Division A. Yaghjian Revised Spring 2014 Implemented Fall 2014 COURSE OUTLINE Fire Protection Systems Course Description FS 145. Fire Protection

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

Detection, and Suppression Systems

Detection, and Suppression Systems Fire Detection, Protection, ti and Suppression Systems Objectives (1 of 5) Explain why all fire fighters should have a basic understanding of fire protection systems. Describe the basic components and

More information

Module 7. Control of Smoke & Highlights of Code Requirements

Module 7. Control of Smoke & Highlights of Code Requirements Module 7 Control of Smoke & Highlights of Code Requirements 1 Module 7 Overview This module will cover: 1. The requirements of smoke control in the Ohio Building Code Section 909 2. The differences between

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required

More information

An Overview of Extinguishing Systems for Computer Equipment

An Overview of Extinguishing Systems for Computer Equipment Risk Solutions An Overview of Extinguishing Systems for Computer Equipment Various types of automatic suppression systems are available for protecting computer equipment. This report discusses the uses

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Fire Alarm Systems Plan Review Checklist Date: Permit Number: Business Name: Address: Fire Alarm System Submittal

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 5 Sprinkler Heads Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 5 Sprinkler Heads Revised Engine Module Page 1 of 5 SPRINKLER HEADS Types of Sprinkler Heads There are many different types of sprinkler heads utilized in fire protection systems. Most are equipped with a thermal detector that

More information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review Minooka Fire Protection District Maintaining Your Fire Safety Systems Fire continues to be a major threat

More information

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder HVAC DISTRIBUTION and DELIVERY SYSTEMS (Part 2) Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 Contextual Reminder All-air systems Single zone Terminal reheat Multi-zone Dual-duct VAV Combinations

More information

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites

More information

Western Michigan University Facilities Management Engineering Division

Western Michigan University Facilities Management Engineering Division Western Michigan University Facilities Management Engineering Division Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG21-1 Fire Suppression Systems & Equipment I. GENERAL... 1 A. General

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:

More information

Enclosure 4- RISK ASSESSMENT

Enclosure 4- RISK ASSESSMENT Enclosure 4- RISK ASSESSMENT RISK ASSESSMENT Risk is a potential that a chosen action or activity will lead to a loss of human or property. Risk assessment is a step for Risk Management. Risk assessment

More information

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1 GENERAL: 1. All fire protection systems shall be installed in accordance with the International Fire Code and applicable NFPA standards. This guideline provides additional requirements for the design and

More information

Design & Construction Standards, Revised January

Design & Construction Standards, Revised January PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe

More information

MODULE 2. Water-Based Suppression System Basics

MODULE 2. Water-Based Suppression System Basics MODULE 2 Water-Based Suppression System Basics Based on the Ohio Building Code (OBC) National Fire Protection Association (NFPA) & Ohio Fire Code (OFC) 1 WATER-BASED SUPPRESSION SYSTEM BASICS-PART ONE

More information

HOW COMMERCIAL FIRE PROTECTION SPRINKLER SYSTEMS REALLY OPERATE

HOW COMMERCIAL FIRE PROTECTION SPRINKLER SYSTEMS REALLY OPERATE A Guide for Fire Sprinkler Maintenance and Operation Commercial fire protection sprinkler systems have been saving lives and reducing property damage for more than a century. New England s textile mills

More information

False Sense of Security???

False Sense of Security??? IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire

More information

Module 9: Ontario Building Code Fire Fighting Provisions

Module 9: Ontario Building Code Fire Fighting Provisions Ontario Building Code (OBC) 1. Sprinklers 2. Standpipes 3. Fire Alarms 4. Entrances Ontario Building Code (OBC) 1. Sprinklers 2. Standpipes 3. Fire Alarms 4. Entrances 1. Sprinklers i) Sprinkler Systems

More information

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007

More information

Sprinkler System Installer Level 2

Sprinkler System Installer Level 2 Sprinkler System Installer Level 2 Sprinkler System Installer Unit: A8 Electrical Principles* Level: Two Duration: 17 hours Theory: Practical: 14 hours 3 hours Overview: Upon completion of this unit the

More information

NFPA 80 Overview January 21, 2016

NFPA 80 Overview January 21, 2016 NFPA 80 Overview January 21, 2016 Kristin Bigda, P.E. Senior Fire Protection Engineer National Fire Protection Association Presenter Kristin Bigda, P.E. Senior Fire Protection Engineer, NFPA Building Fire

More information

Fire. IMO fire control signs - according to IMO Resolution A.654 (16) (mm) 150x x200

Fire. IMO fire control signs - according to IMO Resolution A.654 (16) (mm) 150x x200 IMO fire control signs - according to IMO Resolution A.654 (16) Safety and operating instructions for trained personnel (SIS) - As per ISO 24409, SIS signs are safety-related signs that replicate the symbols

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS > SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation,

More information

New Construction Fire Inspection Process

New Construction Fire Inspection Process New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific

More information

22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review

22A Belvedere Avenue, Parry Sound Sprinkler System Consulting Review Parry Sound District Social Services Administration Board Housing and Community Services October 10, 2018 c/o Andrew Ball, Properties and Capital Projects Coordinator Email:aball@psdssab.org 22A Belvedere

More information

ICC CODE CORNER 2015 International Fire Code

ICC CODE CORNER 2015 International Fire Code PART II GENERAL SAFETY PROVISIONS CHAPTER 4 EMERGENCY PLANNING AND PREPAREDNESS SECTION 401 GENERAL 401.1 Scope. Reporting of emergencies, coordination with emergency response forces, emergency plans and

More information

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT RAISA FASHIONS LTD. ACCORD ID: 11741 PLOT# B63, BSCIC INDUSTRIAL ESTATE, KANCHPUR, SONORGAON, NARAYANGANJ OTHER FACTORIES: NONE February 27, 2015 Page 2 SUMMARY was surveyed

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017

ELEVATORS. Integration of Codes between Fire Alarm, Sprinklers, and Elevators 12/5/2017 12/5/2017 1 ELEVATORS Integration of Codes between Fire Alarm, Sprinklers, and Elevators Encore Electric Inc. Prepared By John McGovern and Jeffrey Engelstad 12/5/2017 Encore Electric Inc. 2 Agenda Basics

More information

EASTERN ARIZONA COLLEGE Fire Department Operations II

EASTERN ARIZONA COLLEGE Fire Department Operations II EASTERN ARIZONA COLLEGE Fire Department Operations II Course Design 2015-2016 Course Information Division Allied Health Course Number FSC 102 Title Fire Department Operations II Credits 5 Developed by

More information

Deluge/Preaction Systems Annotated Instructor s Guide

Deluge/Preaction Systems Annotated Instructor s Guide Deluge/Preaction Systems Annotated Instructor s Guide Module 18301-07 Module Overview This module covers different types of preaction and deluge systems. It discusses deluge valves, auxiliary detection

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Deluge/Preaction Systems Annotated Instructor s Guide

Deluge/Preaction Systems Annotated Instructor s Guide Deluge/Preaction Systems Annotated Instructor s Guide Module 18301-13 Module Overview This module covers different types of preaction and deluge systems. It discusses deluge valves, auxiliary detection

More information

Fire protection on chemical manufacturing sites

Fire protection on chemical manufacturing sites CFPA-E No 18:2008 Fire protection on chemical manufacturing sites FOREWORD The European fire protection associations have decided to produce common guidelines in order to achieve similar interpretation

More information

DIVISION 21 FIRE SUPPRESSION

DIVISION 21 FIRE SUPPRESSION Table of Contents 21 00 00 FIRE SUPPRESSION...2 A. REFERENCE ABBREVIATIONS... 2 B. GENERAL... 2 C. DESIGN REQUIREMENTS... 2 D. DOCUMENTATION... 2 21 08 00 FIRE SUPPRESSION COMMISSIONING...2 A. PIPE CLEANING...

More information

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement

Second Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,

More information

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following: PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe

More information

GENERAL AREAS OF INSPECTION

GENERAL AREAS OF INSPECTION This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that

More information

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21 Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT PORTLAND TEXTILE LTD. ACCORD ID: 11873 PLOT NO. 14-15, SECTOR 6, CHITTAGONG EXPORT PROCESSING ZONE, CHITTAGONG OTHER FACTORIES: NONE November 3, 2015 Page 2 SUMMARY was surveyed

More information

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION INITIAL FIRE SAFETY ASSESSMENT - EXPANSION Factory Mogorkhal, Chowrasta, National University, Gazipur Gazipur Dhaka 09 May 2016 The Alliance for Worker Safety Page 1/13 09 May 2016 Introduction to the

More information

Branch Solution Wood based panel plants. Fire protection solutions for wood based panel plants

Branch Solution Wood based panel plants. Fire protection solutions for wood based panel plants Branch Solution Wood based panel plants Fire protection solutions for wood based panel plants afety throughout the production process R The versatility of wood as a raw material and the fact that it is

More information

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly.

SAFETY. USE OF SAFETY CHECK LISTS A safety check for compliance with current regulations should be performed yearly. SAFETY GENERAL Buildings must be designed according to building and fire safety codes and other regulatory standards at the time of construction. However, such codes and standards are continuously changing.

More information

2018 International Fire Code. Add new text as follows:

2018 International Fire Code. Add new text as follows: CCC-F-1-18 IFC: 311.2.2, 403.11.1.2, 1010.3.2; IBC: 424.3, 428.3.9, 506.2.2.1, 506.2.4.1, 1705.12.6, 2603.3, 3104.5.3, 2606.7.4; IRC: R101.2, R302.2.2, R313, R313.1, R313.1.1, R313.2, R313.2.1, R325.3,

More information

Protecting Your Property: Well Do You Know Your Fire Fire Systems Systems. Joe Szewczyk, Risk Control Consultant

Protecting Your Property: Well Do You Know Your Fire Fire Systems Systems. Joe Szewczyk, Risk Control Consultant Protecting Your Property: Protecting How Well Your Do Property: You Know How Your Well Do You Know Your Fire Fire Systems Systems Joe Szewczyk, Risk Control Consultant Joe Szewczyk, Risk Control Consultant

More information

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 Exam ID Examination Code Part BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015 BC3-7 Level III Exam 7 BCBC Part 3 (Part 3 Buildings Classification & Construction) BC3-8 Level III Exam 8 BCBC

More information

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows:

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows: Technical Bulletin #18-002 February 2018 / 2017 OFC Mobile Food Units Referenced Codes and Standards: OAC 1301:7-7-3(T); OFC 320 OAC 1301:7-7-2(B); OFC 202 OAC 1301:7-7-9(F); OFC 906 NFPA 58 (2014) NFPA

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT DANNY'S KNITWEAR LTD. ACCORD ID: 12228 SURABARI, GAZIPUR, SADAR, GAZIPUR Other Factories: ne October 17, 2015 Page 2 Fire Safety Inspection Report Introduction manufacturing

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory 214 Baiozid Bostami Road Nasirabad Industrial Area Chittagong 04 Sep 2016 The Alliance for Bangladesh Worker Safety Page 1/11 Factory 04 Sep 2016 Introduction to

More information

Aircraft Hangers. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409

Aircraft Hangers. ft. (3,716 sq. m) per hangar construction type as defined by NFPA 409 Aircraft Hangers DESCRIPTION Considering the value of commercial and military aircraft, it has become extremely important to have a reliable fixed fire protection system in aircraft storage, servicing,

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: Plot no. A102, BSCIC Industrial Estate, Tongi, Gazipur Tongi, Gazipur Emkay Enterprises 06 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/22

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:

Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX: Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean

More information

Active & Passive Fire Protection System. Page 1 Kalidasan S BT IN SSP-OP

Active & Passive Fire Protection System. Page 1 Kalidasan S BT IN SSP-OP Active & Passive Fire Protection System Page 1 Kalidasan S BT IN SSP-OP Fire Protection - Introduction Introduction: The definition of fire protection of a building refers to the building ability to detect,

More information

Fire Sprinkler Plan Submittal Form

Fire Sprinkler Plan Submittal Form Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10

More information

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT HAN A HATS & CAPS LTD. ACCORD ID: 12339 DAG NO. CS &SA-115/117, RS-188/181, KHOTION NO. CS-128, SA-274, BAIPAIL, ASHULIA, SAVAR, DHAKA. OTHER FACTORIES: TEXTSTREAM FASHION

More information

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome! Building & Fire Code Academy Building Better With Our Greatest Resource Education Welcome! Understanding the Sprinkler System Design Alternatives in the 2015 International Why inspect, test and maintain?

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Address: Plot 1175 & 1179, Bashan Sarak, Vogra, PO. National University, Gazipur Sadar, Gazipur Gazipur Dhaka Bangladesh 15 Jun 2016 The Alliance for Bangladesh Worker

More information

Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE

Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE TERM highly protected risk (HPR) is commonly used in

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

Deluge & Preac tion Systems

Deluge & Preac tion Systems Deluge & Preaction Systems Deluge Systems are normally used in special hazard installations where water must be applied to an entire area for protection. They use open sprinklers or spray nozzles attached

More information

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE SECTION 21 1316 DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE PART 1 GENERAL 1.01 SECTION INCLUDES A. Dry-pipe sprinkler system. B. System design, installation, and certification. C. Fire department

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Assessor: 180, Baizid Bostami Road Nasirabad I/A Area-1, Building -1, Chittagong Chittagong Chittagong Bangladesh Emkay Enterprises 31 Jan 2015 The Alliance for Bangladesh

More information

S p e c i a l P u r p o s e S p r i n k l e r s. Attic Spaces Retail Windows High Security Institutions Minimal Water Damage Conditions

S p e c i a l P u r p o s e S p r i n k l e r s. Attic Spaces Retail Windows High Security Institutions Minimal Water Damage Conditions SPecial Purpose Sprinklers The Tyco ILLUSION 11.2 K-factor sprinkler is designed specifically for Las Vegas' standards. A fast response, extra large orifice concealed pendant sprinkler, the ILLUSION is

More information

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor

More information

PART II: New Construction Inspections and Acceptance Testing Procedures

PART II: New Construction Inspections and Acceptance Testing Procedures Stafford County Fire Marshal s Office Handbook for Building/Fire Code Policies and Guidelines PART II: New Construction Inspections and Acceptance Testing Procedures Phone: 540-658-8648 Fax: 540-658-9128

More information

Contractor Safety. Workplace Safety & Environmental Division

Contractor Safety. Workplace Safety & Environmental Division Contractor Safety Workplace Safety & Environmental Division Click to edit Master title style This information is designed for tradespersons and persons supervising tradespersons who are performing work

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19 PART 3 Building and Equipment Design Features Chapters 5 through 19 Chapter 5 Fire Service Features No changes addressed Chapter 6 Building Services and Systems Chapter 7 Fire-Resistance-Rated Construction

More information

HIGH PRESSURE WATER MIST SYSTEM Application: High Rise Building Bindreiter Michael London,

HIGH PRESSURE WATER MIST SYSTEM Application: High Rise Building Bindreiter Michael London, HIGH PRESSURE WATER MIST SYSTEM Application: High Rise Building Bindreiter Michael London, 2018-09-19 1 Application High Rise Building Hotel & Apartment Office & Walkways Shopping mall & Lobbies Parking

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Dhanpur, Chapapur, Kotwali, Comilla COMILLA Chittagong The Alliance for Worker Safety Page 1/16 Introduction to the Report The following report contains a site profile and

More information

What are the Contents of an Effective Fire Safety Plan? Name: Date: Address of Project: Building Permit Number:

What are the Contents of an Effective Fire Safety Plan? Name: Date: Address of Project: Building Permit Number: What are the Contents of an Effective Fire Safety Plan? A study of fire safety plans that have already been produced illustrates that one size does not fit all. Depending upon the complexity of a given

More information

Explosion Protection Engineering Principles

Explosion Protection Engineering Principles Handbook of Fire and Explosion Protection Engineering Principles for Oil, Gas, Chemical and Related Facilities Second edition Dennis P. Nolan ELSEVIER AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD

More information

Osceola County Department of Fire Rescue and Emergency Medical Services

Osceola County Department of Fire Rescue and Emergency Medical Services St. Number Dir Street Name Street Type Inspected Time of Day to be Re-inspected Zip Code Occupancy Type Emergency Contact Phone (Inc. Area Code) Building Owner Building Owner Mailing Address Bldg. Owner

More information

DEALING WITH FIRE SAFETY

DEALING WITH FIRE SAFETY DEALING WITH FIRE SAFETY Personal Care Homes And Assisted Living Facilities Presented by: Harold D. Hicks, P.E., FSFPE Fire Protection Engineer 1 Atlantic Code Consultants 2 Our Objectives Recognize the

More information

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT 58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the

More information

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT INITIAL FIRE SAFETY ASSESSMENT Factory Mouza Chandra, Shafipur, Kaliakoir, Gazipur Gazipur Dhaka 24 Mar 2014 The Alliance for Worker Safety Page 1/12 24 Mar 2014 Introduction to the Report The following

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT TOYO COMPOSITE KNIT GARMENTS LTD 1, SOUTH KAMALAPUR SARDER COMPLEX, DHAKA Other Factories: Pure Cotton Ltd, Knit and Knitwear Ltd June 7, 2014 Page 2 Fire Safety Inspection

More information

ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND SHELTER FIRST EDITION APRIL 2015

ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND SHELTER FIRST EDITION APRIL 2015 ENGINEERING STANDARDA FOR FIRE FIGHTING HOSE BOX AND SHELTER FIRST EDITION APRIL 2015 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner. Neither whole

More information

Chapter 2: Definitions

Chapter 2: Definitions FLORIDA BUILDING CODE Existing Buildings 6 TH Edition (2017) Code Changes based on the document provided by DBPR - 2014 and 6th Edition (2017) Florida Building Code Comparison JUMP TO CHAPTER (click chapter

More information