SERVICE MANUAL PCH-P50GAH PCH-P60GAH PCH-P71GAH PCH-P100GAH PCH-P125GAH PCH-P140GAH. May 2008

Size: px
Start display at page:

Download "SERVICE MANUAL PCH-P50GAH PCH-P60GAH PCH-P71GAH PCH-P100GAH PCH-P125GAH PCH-P140GAH. May 2008"

Transcription

1 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS SERVICE MANUAL May 008 No. OC8 REVISED EDITION-B Indoor unit [Model names] [Service Ref.] PCA-RP0A PCA-RP0A PCA-RP0A# PCA-RP0A PCA-RP0A PCA-RP0A# PCA-RP0A PCA-RP0A PCA-RP0A# PCA-RP7A PCA-RP7A PCA-RP7A# PCA-RP00A PCA-RP00A PCA-RP00A# PCA-RPA PCA-RPA PCA-RPA# PCA-RP0A PCA-RP0A PCA-RP0A# PCH-P0AH PCH-P0AH PCH-P7AH PCH-P00AH PCH-PAH PCH-P0AH PCH-P0AH PCH-P0AH PCH-P7AH PCH-P00AH PCH-PAH PCH-P0AH Revision : PCA-RP0~0A()# are added in REVISED EDITION-B. RoHS PARTS LIST added. Some descriptions have been modified. Please void OC8 REVISED EDITION-A NOTE: This manual describes only service data of the indoor units. RoHS compliant products have <> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List. INDOOR UNIT TEMP. ON/OFF REMOTE CONTROLLER Model name indication CONTENTS. TECHNICAL CHANES.... REFERENCE MANUAL.... SAFETY PRECAUTION.... PART NAMES AND FUNCTIONS SPECIFICATIONS NOISE CRITERION CURVES OUTLINES AND DIMENSIONS WIRIN DIARAM REFRIERANT SYSTEM DIARAM TROUBLESHOOTIN.... SPECIAL FUNCTION.... DISASSEMBLY PROCEDURE.... PARTS LIST.... RoHS PARTS LIST... 0

2 TECHNICAL CHANES PCA-RP0A() PCA-RP0A PCA-RP7A PCA-RP00A PCA-RPA PCA-RP0A PCA-RP0A()# PCA-RP0A# PCA-RP7A# PCA-RP00A# PCA-RPA# PCA-RP0A# INDOOR CONTROLLER BOARD(I.B.) has been changed. REFERENCE MANUAL -. OUTDOOR UNIT S SERVICE MANUAL Service Ref. MXZ-8A0VA / VA/ VA / VA SUZ-KA0/0/7VA().TH SUZ-KA0/0/7VA().TH-A PUHZ-RP/0/0/7/00//0VHA() PUHZ-RP00//0YHA PUHZ-RP7/00//0VHA()-A PUHZ-RP00/0YHA()() PUHZ-RP00/0YHA()-A PU(H)-P VAA.UK PU(H)-P YAA.UK PUHZ-P00//0VHA.UK PUHZ-RP/0/0/7/00//0VHA() PUHZ-RP00//0YHA() PUHZ-RP/0/0/7/00VHA PUHZ-RP00YHA PU(H)-P7/00VHA().UK PU(H)-P00//0YHA().UK PUHZ-P00//0VHA().UK PUHZ-RP7/00//0VHA-A PUHZ-RP00//0YHA-A PUHZ-BP00//0VHA-A PUHZ-BP00/0YHA-A PUHZ-P00/0YHA PUHZ-HRP7/00VHA PUHZ-HRP00/YHA PUHZ-RP00/0YHA Service Manual No. OC OC OC OC OC7 OC8 OC9 OC OC9 OC7 OC79 OCH / OCB OCH / OCB OCH / OCB OCH / OCB OCH / OCB OCH8 / OCB8 -. TECHNICAL DATA BOOK Series (Outdoor unit) PUHZ-RP HA(-A) PU(H)-P AA.UK SUZ-KA VA PUHZ-RP HA PUHZ-P HA PU(H)-P HA PUHZ-P VHA, PUHZ-P YHA PUHZ-RP HA-A PUHZ-BP HA PUHZ-HRP HA Manual No. OCS0 OCS0 OCS0 OCS0 OCS0 OCS07 OCS08 OCS09 OCS0 OCS

3 SAFETY PRECAUTION -. ALWAYS OBSERVE FOR SAFETY Before obtaining access to terminal, all supply circuits must be disconnected. -. CAUTIONS RELATED TO NEW REFRIERANT Cautions for units utilising refrigerant R07C Do not use the existing refrigerant piping. The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant deterioration of the new unit. Use liquid refrigerant to charge the system. If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop. Use low residual oil piping If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result. Store the piping to be used during installation indoors with keep both ends sealed until just before brazing. (Store elbows and other joints in a plastic bag.) If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result. Use ESTER, ETHER or HAB as the lubricant to coat flares and flange connection parts. If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc. Do not use a refrigerant other than R07C. If another refrigerant (R, etc.) is used, the chlorine in the refrigerant may cause the lubricant deterioration. Use a vacuum pump with a reverse flow check valve. The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant deterioration. Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.

4 [] Cautions for service After recovering the all refrigerant in the unit, proceed to working. Do not release refrigerant in the air. After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant. [] Refrigerant recharging () Refrigerant recharging process Direct charging from the cylinder. R07C cylinder are available on the market has a syphon pipe. Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant) Unit ravimeter () Recharge in refrigerant leakage case After recovering the all refrigerant in the unit, proceed to working. Do not release the refrigerant in the air. After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant. [] Service tools Use the below service tools as exclusive tools for R07C refrigerant. No. Tool name Specifications auge manifold Only for R07C. Use the existing fitting SPECIFICATIONS. (UNF7/) Use high-tension side pressure of.mpa or over. Charge hose Only for R07C. Use pressure performance of.0mpa or over. Electronic scale as leak detector Use the detector for Ra or R07C. Adapter for reverse flow check. Attach on vacuum pump. Refrigerant charge base. 7 Refrigerant cylinder. For R07C Top of cylinder (Brown) Cylinder with syphon 8 Refrigerant recovery equipment.

5 CAUTIONS RELATED TO NEW REFRIERANT Cautions for units utilising refrigerant R0A Use new refrigerant pipes. In case of using the existing pipes for R, be careful with the followings. For RP0/7VHA and RP00//0, be sure to perform replacement operation before test run. Change flare nut to the one provided with this product. Use a newly flared pipe. Avoid using thin pipes. Make sure that the inside and outside of refrigerant piping is clean and it has no contamination such as sulfur hazardous for use, oxides, dirt, shaving particles, etc. In addition, use pipes with specified thickness. Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc. Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.) If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor. Use ester oil, ether oil or alkylbenzene oil (small amount) as the refrigerant oil applied to flares and flange connections. If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc. Charge refrigerant from liquid phase of gas cylinder. If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered. Do not use refrigerant other than R0A. If other refrigerant (R etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc. Use a vacuum pump with a reverse flow check valve. Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil etc. Use the following tools specifically designed for use with R0A refrigerant. The following tools are necessary to use R0A refrigerant. Tools for R0A auge manifold Flare tool Charge hose Size adjustment gauge as leak detector Torque wrench Keep the tools with care. If dirt, dust or moisture enter into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor. Do not use a charging cylinder. Vacuum pump adaptor Electronic refrigerant charging scale If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered. Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released. [] Cautions for service () Perform service after collecting the refrigerant left in unit completely. () Do not release refrigerant in the air. () After completing service, charge the cycle with specified amount of refrigerant. () When performing service, install a filter drier simultaneously. Be sure to use a filter drier for new refrigerant. [] Additional refrigerant charge When charging directly from cylinder Check that cylinder for R0A on the market is syphon type. Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)

6 Unit ravimeter [] Service tools Use the below service tools as exclusive tools for R0A refrigerant. No. auge manifold Only for R0A Charge hose Only for R0A Electronic scale Specifications Use the existing fitting specifications. (UNF/) Use high-tension side pressure of.mpa or over. Use pressure performance of.09mpa or over. as leak detector Use the detector for Ra, R07C or R0A. Adaptor for reverse flow check Attach on vacuum pump. Refrigerant charge base 7 Refrigerant cylinder Only for R0A Top of cylinder (Pink) 8 Refrigerant recovery equipment Cylinder with syphon

7 PART NAMES AND FUNCTIONS Indoor Unit Left/right guide vanes Change the direction of airflow from the horizontal blower. Air outlet Long-life filter Removes dust and foreign matter from air coming in through the grille (Recommended cleaning interval : Approx, every,00 operating hours) Up/down guide vanes Change the direction of airflow from the vertical blower. Intake grille Air intake Remote controller Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button. Operation buttons Set Temperature buttons ON/OFF button Down Up Fan Speed button Timer Menu button (Monitor/Set button) Mode button (Return button) Filter button (<Enter> button) TEMP. ON/OFF Test Run button Set Time buttons Check button (Clear button) Back MENU ON/OFF FILTER Ahead Timer On/Off button (Set Day button) BACK PAR-MAA MONITOR/SET DAY CLOCK OPERATION CHECK TEST CLEAR Airflow Up/Down button Louver button ( Operation button) Opening the door. To preceding operation number. Ventilation button ( Operation button) To next operation number. 7

8 Display For purposes of this explanation, all parts of the display are shown as lit. During actual operation, only the relevant items will be lit. Identifies the current operation Shows the operating mode, etc. * Multilanguage display is supported. Day-of-Week Shows the current day of the week. Time/Timer Display Shows the current time, unless the simple or Auto Off timer is set. If the simple or Auto Off timer is set, shows the time remaining. Sensor indication Displayed when the remote controller sensor is used. Locked indicator Indicates that remote controller buttons have been locked. Clean The Filter indicator Comes on when it is time to clean the filter. Centrally Controlled indicator Indicates that operation of the remote controller has been prohibited by a master controller. Timer Is Off indicator Indicates that the timer is off. Temperature Setting Shows the target temperature. F C TIME SUN MON TUE WED THU FRI SAT TIMER Hr ON AFTER AFTER OFF ERROR CODE F C ONLYHr. Up/Down Air Direction indicator The indicator shows the direction of the outcoming airflow. One Hour Only indicator Displayed if the airflow is set to weak and downward during COOL or DRY mode. (Operation varies according to model.) The indicator goes off after one hour, at which time the airflow direction also changes. FUNCTION FILTER WEEKLY SIMPLE AUTO OFF Room Temperature display Shows the room temperature. Louver display Indicates the action of the swing louver. Does not appear if the louver is stationary. (Power On indicator) Indicates that the power is on. Timer indicators The indicator comes on if the corresponding timer is set. Fan Speed indicator Shows the selected fan speed. Ventilation indicator Appears when the unit is running in Ventilation mode. Caution Only the Power on indicator lights when the unit is stopped and power supplied to the unit. If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the Not Available message. If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at the parent unit. When power is turned ON for the first time, it is normal that PLEASE WAIT is displayed on the room temperature indication (For max. minutes). Please wait until this PLEASE WAIT indication disappear then start the operation. 8

9 SPECIFICATIONS INDOOR UNIT INDOOR UNIT INDOOR UNIT INDOOR UNIT Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight W D H Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight W D H Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight W D H W D H A A /min(cfm) Pa(mmAq) db kg(lbs) A A /min(cfm) Pa(mmAq) db kg(lbs) A A /min(cfm) Pa(mmAq) db kg(lbs) A A /min(cfm) Pa(mmAq) db kg(lbs) 9 PCA-RP0A, PCA-RP0A# Cooling Heating Single phase, 0Hz, 0V Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (-90--0) 0(direct blow) Remote controller & built-in (),000(9-/8) 80(-/) 0(8-/) 7(0) PCA-RP0A, PCA-RP0A# Cooling Heating Single phase, 0Hz, 0V Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (9-0--) 0(direct blow) Remote controller & built-in (),0(-9/) 80(-/) 0(8-/) (7) PCA-RP0A, PCA-RP0A# Cooling Heating Single phase, 0Hz, 0V Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (9-0--) 0(direct blow) Remote controller & built-in (),0(-9/) 80(-/) 0(8-/) (7) PCA-RP7A, PCA-RP7A# Cooling Heating Single phase, 0Hz, 0V Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (9-0--) 0(direct blow) Remote controller & built-in (),0(-9/) 80(-/) 0(8-/) (7)

10 INDOOR UNIT INDOOR UNIT INDOOR UNIT Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight W D H Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight W D H Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight W D H A A /min(cfm) Pa(mmAq) db kg(lbs) A A /min(cfm) Pa(mmAq) db kg(lbs) A A /min(cfm) Pa(mmAq) db kg(lbs) PCA-RP00A, PCA-RP00A# Cooling Heating Single phase, 0Hz, 0V Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x ( ) 0(direct blow) Remote controller & built-in 0--- (),0(-9/) 80(-/) 70(0-/8) 7(8) PCA-RPA, PCA-RPA# Cooling Heating Single phase, 0Hz, 0V Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (9-,00-,0-,00) 0(direct blow) Remote controller & built-in --- (),0(-/) 80(-/) 70(0-/8) (9) PCA-RP0A, PCA-RP0A# Cooling Heating Single phase, 0Hz, 0V Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (9-,00-,0-,00) 0(direct blow) Remote controller & built-in ---8 (),0(-/) 80(-/) 70(0-/8) (99) 0

11 INDOOR UNIT INDOOR UNIT Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Booster heater Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Booster heater Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight W D H W D H A A /min(cfm) Pa(mmAq) db kg(lbs) A A /min(cfm) Pa(mmAq) db kg(lbs) Cooling Cooling PCH-P0AH Heating Single phase, 0Hz, 0V 0.09<.9> 0.<.>.0<.> Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (-90--0) 0(direct blow) <.9> Remote controller & built-in (),000(9-/8) 80(-/) 0(8-/) 8.() PCH-P0AH Heating Single phase, 0Hz, 0V 0.<.9> 0.<8.9>.7<8.9> Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (9-0--) 0(direct blow) <.9> Remote controller & built-in (),0(-9/) 80(-/) 0(8-/) (79) INDOOR UNIT Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Booster heater Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions W D H Weight : < > Shows the only booster heater rating. A A /min(cfm) Pa(mmAq) db kg(lbs) Cooling PCH-P7AH Heating Single phase, 0Hz, 0V 0.<.9> 0.<8.9>.7<8.9> Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (9-0--) 0(direct blow) <.9> Remote controller & built-in (),0(-9/) 80(-/) 0(8-/) (79)

12 INDOOR UNIT Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Booster heater Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight W D H A A /min(cfm) Pa(mmAq) db kg(lbs) Cooling PCH-P00AH Heating Single phase, 0Hz, 0V 0.<.8> 0.9<0.78>.8<0.78> Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x ( ) 0(direct blow) <.8> Remote controller & built-in 0--- (),0(-9/) 80(-/) 70(0-/8) 9.(87) INDOOR UNIT Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Booster heater Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight W D H A A /min(cfm) Pa(mmAq) db kg(lbs) Cooling PCH-PAH Single phase, 0Hz, 0V Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (9-,00-,0-,00) 0(direct blow) <.7> Remote controller & built-in --- (),0(-/) 80(-/) 70(0-/8) (0) Heating 0.<.7>.0<.00>.0<.00> INDOOR UNIT Service Ref. Mode Power supply(phase, cycle, voltage) Input Running current Starting current External finish Heat exchanger Fan Fan(drive) x No. Fan motor output Airflow(Low-Medium-Medium-High) External static pressure Booster heater Operation control & Thermostat Noise level(low-medium-medium-high) Unit drain pipe I.D. Dimensions Weight W D H : < > Shows the only booster heater rating. A A /min(cfm) Pa(mmAq) db kg(lbs) Cooling PCH-P0AH Single phase, 0Hz, 0V Munsell 0.70Y 8.9/0.97 Plate fin coil Sirocco fan (direct) x (9-,00-,0-,00) 0(direct blow) <.7> Remote controller & built-in ---8 (),0(-/) 80(-/) 70(0-/8) 8(0) Heating 0.<.7>.0<.00>.0<.00>

13 NOISE CRITERION CURVES PCA-RP0A PCA-RP0A# PCH-P0AH NOTCH High Medium Medium Low SPL(dB) LINE PCA-RP0A PCA-RP0A# PCA-RP0/7A PCA-RP0/7A# PCH-P0/7AH NOTCH High Medium Medium Low SPL(dB) 9 7 LINE OCTAVE BAND SOUND PRESSURE LEVEL, db (0 db = μbar) NC-70 NC-0 NC-0 NC-0 NC-0 OCTAVE BAND SOUND PRESSURE LEVEL, db (0 db = μbar) NC-70 NC-0 NC-0 NC-0 NC APPROXIMATE THRESHOLD OF HEARIN FOR CONTINUOUS NOISE NC APPROXIMATE THRESHOLD OF HEARIN FOR CONTINUOUS NOISE NC-0 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz PCA-RP00A PCA-RP00A# PCH-P00AH NOTCH High Medium Medium Low SPL(dB) 0 LINE PCA-RPA PCA-RPA# PCH-PAH NOTCH High Medium Medium Low SPL(dB) LINE OCTAVE BAND SOUND PRESSURE LEVEL, db (0 db = μbar) APPROXIMATE THRESHOLD OF HEARIN FOR CONTINUOUS NOISE NC-70 NC-0 NC-0 NC-0 NC-0 NC-0 OCTAVE BAND SOUND PRESSURE LEVEL, db (0 db = μbar) APPROXIMATE THRESHOLD OF HEARIN FOR CONTINUOUS NOISE NC-70 NC-0 NC-0 NC-0 NC-0 NC-0 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

14 PCA-RP0A PCA-RP0A# PCH-P0AH NOTCH High Medium Medium Low SPL(dB) 8 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, db (0 db = μbar) APPROXIMATE THRESHOLD OF HEARIN FOR CONTINUOUS NOISE BAND CENTER FREQUENCIES, Hz NC-70 NC-0 NC-0 NC-0 NC-0 NC-0 m ceiling m about.m unit MICROPHONE

15 7 OUTLINES AND DIMENTIONS INDOOR UNIT PCA-RP0A PCA-RP0A# PCH-P0AH Unit : mm NOTES:. Use M0 or W/8 screws for anchor bolt.. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping Electrical box liquid 0 gas (Drainage) (suspension bolt pitch) Air outlet Air intake ~7 Electrical box [Front view] When electrical box is pulled down Ceiling Drainage pipe connection (mm I.D.) Drainage pipe connection (for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement 7 Knockout hole for left drain pipe arrangement 8 Knockout hole for wiring arrangement Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size LIQUID SIDE AS SIDE RP P : Initial flare nut size

16 PCA-RP0A PCA-RP0A# PCA-RP0A PCA-RP7A PCA-RP0A# PCA-RP7A# PCH-P0AH PCH-P7AH Unit : mm NOTES:. Use M0 or W/8 screws for anchor bolt.. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping. 0 0 (suspension bolt pitch) Electrical box Air outlet (liquid) (/8F gas) (Drainage) 79 Air intake Electrical box ~7 When electrical box is pulled down [ Front view ] Ceiling Drainage pipe connection (mm I.D.) Drainage pipe connection (for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement 7 Knockout hole for left drain pipe arrangement 8 Knockout hole for wiring arrangement Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size RP0 LIQUID SIDE. 9. AS SIDE.7.88 RP RP7,P0,P : Initial flare nut size

17 PCA-RP00A PCA-RP00A# PCH-P00AH Unit : mm NOTES:. Use M0 or W/8 screws for anchor bolt.. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping (suspension bolt pitch) Electrical box Air outlet (/8F liquid) (/8F, /F gas) (Drainage) Air intake 8 90 Electrical box [ Front view ] Ceiling 9 When electrical box is pulled down ~ Drainage pipe connection (mm I.D.) Drainage pipe connection (for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement 7 Knockout hole for left drain pipe arrangement 8 Knockout hole for wiring arrangement Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size RP00 LIQUID SIDE 9. AS SIDE P :Initial flare nut size 7

18 PCA-RPA PCA-RP0A PCA-RPA# PCA-RP0A# PCH-PAH PCH-P0AH Unit : mm NOTES:. Use M0 or W/8 screws for anchor bolt.. When optional drain lift-up mechanism is installed, always provide upward piping for refrigerant piping (suspension bolt pitch) Electrical box Air outlet (/8F liquid) (/8F, /F gas) (Drainage) Air intake 90 Electrical box [ Front view ] Ceiling 9 When electrical box is pulled down ~ Drainage pipe connection (mm I.D.) Drainage pipe connection (for the left arrangement) Knockout hole for left drain-piping arrangement Refrigerant-pipe connection (gas pipe side/flared connection) Refrigerant-pipe connection (liquid pipe side/flared connection) Knockout hole for upper drain pipe arrangement 7 Knockout hole for left drain pipe arrangement 8 Knockout hole for wiring arrangement Use the current nuts meeting the pipe size of the outdoor unit. Available pipe size RP,0 P,0 LIQUID SIDE AS SIDE :Initial flare nut size 8

19 8 WIRIN DIARAM PCA-RP0A PCA-RP0A PCA-RP0A PCA-RP7A PCA-RP00A PCA-RPA PCA-RP0A PCA-RP0A# PCA-RP0A# PCA-RP0A# PCA-RP7A# PCA-RP00A# PCA-RPA# PCA-RP0A# PCH-P0AH PCH-P0AH PCH-P7AH PCH-P00AH PCH-PAH PCH-P0AH SYMBOL NAME P.B INDOOR POWER BOARD I.B INDOOR CONTROLLER BOARD FUSE FUSE (T.AL0V) ZNR VARISTOR CNL CONNECTOR(LOSSNAY) CN CONNECTOR(REMOTE SWITCH) CN CONNECTOR(HA TERMINAL-A) CN CONNECTOR(CENTRALLY CONTROL) SW SWITCH (MODEL SELECTION) See Table. SW SWITCH (CAPACITY CODE) See Table. SWE SWITCH(EMERENCY OPERATION) X RELAY(DRAIN PUMP) X RELAY(FAN MOTOR) BCR FAN CONTROL ELEMENT LED POWER SUPPLY(I.B) LED POWER SUPPLY(R.B) LED TRANSMISSION(INDOOR-OUTDOOR) C CAPACITOR(FAN MOTOR) SYMBOL MF MV DP DS TB TB TB,TB TH TH TH R.B NAME FAN MOTOR VANE MOTOR DRAIN-UP MACHINE (OPTION) DRAIN SENSOR (OPTION) TERMINAL BLOCK (HEATER) PCH-P.AH models only or option for PCA RP.A() models. TERMINAL BLOCK(INDOOR/OUTDOOR CONNECTIN LINE) TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE ) ROOM TEMP.THERMISTOR (0 /k, /.k DETECT) PIPE TEMP.THERMISTOR/LIQUID (0 /k, /.k DETECT) COND./EVA.TEMP.THERMISTOR (0 /k, /.k DETECT) WIRED REMOTE CONTROLLER BOARD SYMBOL NAME W.B WIRELESS REMOTE CONTROLLER BOARD(OPTION) RU RECEIVIN UNIT BZ BUZZER LED LED(RUN INDICATOR) LED LED(HOT ADJUST) SW SWITCH(HEATIN ON/OFF) SW SWITCH(COOLIN ON/OFF) HEATER FS, THERMAL FUSE(98 0A:0AH/7 A:00AH 0 A:0,7,,0AH) H HEATER H HEATER THERMAL SWITCH 88H HEATER CONTACTOR MF C RED WHT BLK I.B FAN D.U.M POWER POWER CNP CNDK CND VANE (WHT) (BLU) (RED) (ORN) POWER INDOOR/OUTDOOR CNV CND(WHT) COMMUNICATION (RN) X CNC(BLU) BCR X ZNR CN CNL SWE ON OFF SW DS X PCH-P0~P0AH models only SW (OPTION) DP X H P.B CNDK (RED) DC.V RED WHT LED LED LED FS D.SENSOR CN (WHT) Refer to tables and for service PCB. When installing optional drain-up machine disconnect the CN jumper connector CN and replace it with the DRAIN SENSOR drain sensor (DS). (WHT) When installing drain-up machine (Optional part). FS RED WHT YLW ORN CNS (WHT) FUSE INTAKE CN0 (RED). When work to supply power separately to Indoor and Outdoor unit was applied, refer to Fig.. For power supply system of this unit, refer to the caution label located near this diagram. BLK WHT BLK BLK TH CN LIQUID CN (WHT) BRN ORN BLK BLK CN PIPE CN9 (BLK) TH I.B YLW YLW BLU BLU TH 88H TB RED RED L BLU N RN/YLW WIRELESS CN90 (WHT) REMOCON CN (BLU) HEATER CN (YLW) RED RY RED 88H MV 9 BZ TB YLW S ORN S ORN S BRN 0~7 TYPE MV 00~0 TYPE MV CNB RU RECEIVER LED LED SWSW W.B TRANSMISSION WIRES DCV TB R.B POWER SUPPLY ~(PHASE) 0V 0Hz H (Fig.) I.B YLW ORN TB [Servicing] Fasten terminal of the terminal board "TB"equips lock system. To remove the fastened terminal, pull it while pressing the protruding portion (locking lever) of the terminal. The fastened terminal protruding portion should face upward. POWER CND (ORN) INDOOR/OUTDOOR COMMUNICATION CNC (BLU) TO OUTDOOR UNIT Please set the voltage using the remote controller. For the setting method, please refer to the indoor unit Installation Manual. TB RED L BLU N RN/YLW YLW TB S ORN ORN S BRN S POWER SUPPLY ~(PHASE) 0V 0Hz TO OUTDOOR UNIT Table MODELS PCA-RP.A PCH-P.AH SW Service board ON OFF Table MODELS PCA-RP0A PCH-P0AH PCA-RP0A PCA-RP0A PCH-P0AH PCA-RP7A PCH-P7AH SW Service board MODELS ON PCA-RP00A OFF PCH-P00AH ON PCA-RPA OFF PCH-PAH ON PCA-RP0A OFF PCH-P0AH Service board ON OFF ON OFF ON OFF NOTES:. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (S, S, S).. Make sure that the main power supply of the booster heater is independent.. Symbols used in wiring diagram above are, : Connector, : Terminal (block). 9

20 9 REFRIERANT SYSTEM DIARAM PCA-RP0A PCA-RP0A PCA-RP0A PCA-RP7A PCA-RP00A PCA-RPA PCA-RP0A PCA-RP0A# PCA-RP0A# PCA-RP0A# PCA-RP7A# PCA-RP00A# PCA-RPA# PCA-RP0A# PCH-P0AH PCH-P0AH PCH-P7AH PCH-P00AH PCH-PAH PCH-P0AH Unit : mm Heat exchanger Condenser/evaporator temperature thermistor (TH) Strainer #0 Refrigerant AS pipe connection (Flare) Refrigerant flow in cooling Refrigerant flow in heating Room temperature thermistor (TH) Pipe temperature thermistor/liquid (TH) Distributor with strainer #0 Strainer #0 Refrigerant LIQUID pipe connection (Flare) 0

21 0 TROUBLESHOOTIN 0-. TROUBLESHOOTIN <Error code display by self-diagnosis and actions to be taken for service (summary)> Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service and the trouble reoccurrence at field are summarized in the table below. Check the contents below before investigating details. Unit conditions at service Error code Actions to be taken for service (summary) The trouble is reoccurring. The trouble is not reoccurring. Displayed Not displayed Logged Not logged Judge what is wrong and take a corrective action according to SELF-DIANOSIS ACTION TABLE (0-). Conduct troubleshooting and ascertain the cause of the trouble according to TROUBLESHOOTIN BY INFERIOR PHENOMENA (0-). Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, and wiring related. Reset error code logs and restart the unit after finishing service. There is no abnormality in electrical components, controller boards, and remote controller. Recheck the abnormal symptom. Identify the cause of the trouble and take a corrective action according to TROUBLESHOOTIN BY INFERIOR PHENOMENA (0-). Continue to operate unit for the time being if the cause is not ascertained. There is no abnormality in electrical components, controller boards, remote controller etc.

22 0-. SELF-DIANOSIS ACTION TABLE Note: Refer to the manual of outdoor unit for the details of display such as F, U, and other E. Error Code Abnormal point and detection method Cause Countermeasure P Room temperature thermistor (TH) The unit is in -minute resume prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after minutes. (The unit returns to normal operation, if it has been reset normally.) Constantly detected during cooling, drying, and heating operation. Short: -90: or more Open: -0: or less Defective thermistor characteristics Contact failure of connector (CN0) on the indoor controller board (Insert failure) Breaking of wire or contact failure of thermistor wiring Defective indoor controller board Check resistance value of thermistor. 0:.0k" 0: 9.k" 0:.k" 0:.k" 0:.0k" If you put force on (draw or bend) the lead wire with measuring resistance value of thermistor, breaking of wire or contact failure can be detected. Check contact failure of connector (CN0) on the indoor controller board. Refer to 0-. Turn the power on again and check restart after inserting connector again. Check room temperature display on remote controller. Replace indoor controller board if there is abnormal difference with actual room temperature. Turn the power off, and on again to operate after check. P Pipe temperature thermistor/liquid (TH) The unit is in -minute resume prevention mode if short/open of thermistor is detected. Abnormal if the unit does not reset normally after minutes. (The unit returns to normal operation, if it has been reset normally.) Constantly detected during cooling, drying, and heating (except defrosting) operation Short: 90: or more Open: -0: or less Defective thermistor characteristics Contact failure of connector (CN) on the indoor controller board (Insert failure) Breaking of wire or contact failure of thermistor wiring Defective refrigerant circuit is causing thermistor temperature of 90: or more or -0: or less. Defective indoor controller board Check resistance value of thermistor. For characteristics, refer to (P) above. Check contact failure of connector (CN) on the indoor controller board. Refer to 0-. Turn the power on and check restart after inserting connector again. Check pipe <liquid> temperature with remote controller in test run mode. If pipe <liquid> temperature is extremely low (in cooling mode) or high (in heating mode), refrigerant circuit may have defective. Check pipe <liquid> temperature with remote controller in test run mode. If there is extremely difference with actual pipe <liquid> temperature, replace indoor controller board. Turn the power off, and on again to operate after check. P P Drain sensor (DS) Defective thermistor Suspensive abnormality, if short/open characteristics of thermistor is detected for 0 seconds continuously.compressor and indoor fan will be turned off Short/open is detected for 0 seconds continuously during suspensive abnormality. (The unit returns to normal operation, if it has normally reset.) Detect the following condition. During cooling and drying operation. In case that pipe <liquid> temperature - room temperature <-0deg (Except defrosting) When pipe <liquid> temperature or room temperature is short/open temperature. During drain pomp operation. Malfunction of drain pump (DP) Suspensive abnormality, if thermistor of drain sensor is let heat itself and temperature rises slightly. Compressor and indoor fan will be turned off. Drain pomp is abnormal if the condition above is detected during suspensive abnormality. Constantly detected during drain pump operation. Contact failure of connector (CN) on the indoor controller board. (Insert failure). Breaking of wire or contact failure of drain sensor wiring. Defective indoor controller board. Malfunction of drain pump Defective drain Clogged drain pump Clogged drain pipe Attached drop of water at the drain sensor Drops of drain trickles from lead wire. Clogged filter is causing wave of drain. Defective indoor controller board. Check resistance value of thermistor. 0:....0k" 0:....9k" 0:....k" 0:....8k" 0:....k" Check contact failure of connector (CN) on the indoor controller board. Refer to 0-. Turn the power on again and check restart after inserting connector again. Replace indoor controller board if drain pump operates with the line of drain sensor connector CN- and is short-circuited, and abnormality reappears. Turn the power off, and on again to operate after check. Check if drain-up machine works. Check drain function. Check the setting of lead wire of drain sensor and check clogs of the filter. Replace indoor controller board if drain pump operates with the line of drain sensor connector CN- and is short-circuited and abnormality reappears. Refer to 0-. Turn the power off, and on again to operate after check.

23 Error Code Abnormal point and detection method Cause Countermeasure Freezing/overheating protection is working (Cooling or drying mode) (Cooling or drying mode) Clogged filter (reduced airflow) Check clogs of the filter. Freezing protection (Cooling mode) Short cycle of air path Remove shields. The unit is in -minute resume prevention mode if pipe <liquid or condenser/ operation out of the tolerance Low-load (low temperature) evaporator> temperature stays under range -: for minutes, minutes after the compressor started. Abnormal if it stays Defective indoor fan motor Refer to 0-. under -: for minutes again within Fan motor is defective. minutes after -minute resume prevention mode. Indoor controller board is defective. Defective outdoor fan control Overcharge of refrigerant 7 Defective refrigerant circuit (clogs) Check outdoor fan motor. 7 Check operating condition of refrigerant circuit. P Overheating protection (Heating mode) The units is in minute resume prevention mode if pipe <condenser / evaporator> temperature is detected as over 70: after the compressor started. Abnormal if the temperature of over 70: is detected again within 0 minutes after minute resume prevention mode. (Heating mode) Clogged filter (reduced airflow) Short cycle of air path Over-load (high temperature) operation out of the tolerance range Defective indoor fan motor Fan motor is defective. Indoor controller board is defective. Defective outdoor fan control Overcharge of refrigerant 7 Defective refrigerant circuit (clogs) 8 Bypass circuit of outdoor unit is defective. (Heating mode) Check clogs of the filter. Remove shields. Refer to 0-. Check outdoor fan motor. ~8Check operating condition of refrigerant circuit. P8 Pipe temperature <Cooling mode> Detected as abnormal when the pipe temperature is not in the cooling range minutes after compressor start and minutes after the liquid or condenser/evaporator pipe is out of cooling range. Note ) It takes at least 9 minutes to detect. Note ) Abnormality P8 is not detected in drying mode. Cooling range : - C ] (TH-TH) TH: Lower temperature between: liquid pipe temperature (TH) and condenser/evaporator temperature (TH) TH: Intake temperature <Heating mode> When 0 seconds have passed after the compressor starts operation and the hot adjustment mode has finished, the unit is detected as abnormal when condenser/ evaporator pipe temperature is not in heating range within 0 minutes. Note ) It takes at least 7 minutes to detect abnormality. Note ) It excludes the period of defrosting. (Detection restarts when defrosting mode is over.) Heating range : C [ (TH-TH) Slight temperature difference between indoor room temperature and pipe <liquid or condenser / evaporator> temperature thermistor Shortage of refrigerant Disconnected holder of pipe <liquid or condenser / evaporator> thermistor Defective refrigerant circuit Converse connection of extension pipe (on plural units connection) Converse wiring of indoor/ outdoor unit connecting wire (on plural units connection) Defective detection of indoor room temperature and pipe <condenser / evaporator> temperature thermistor Stop valve is not opened completely. ~ Check pipe <liquid or condenser / evaporator> temperature with room temperature display on remote controller and outdoor controller circuit board. Pipe <liquid or condenser / evaporator> temperature display is indicated by setting SW of outdoor controller circuit board as follows. Conduct temperature check with outdoor ( controller circuit board after connecting A-Control Service Tool(PAC-SKST). ) Check converse connection of extension pipe or converse wiring of indoor/outdoor unit connecting wire.

24 Error Code Abnormal point and detection method Cause Countermeasure P9 Pipe temperature thermistor / Condenser-Evaporator (TH) The unit is in -minute resume protection mode if short/open of thermistor is detected. Abnormal if the unit does not get back to normal within minutes. (The unit returns to normal operation, if it has been reset normally.) Constantly detected during cooling, drying, and heating operation (except defrosting) Short: 90: or more Open: -0: or less Defective thermistor characteristics Contact failure of connector (CN) on the indoor controller board (Insert failure) Breaking of wire or contact failure of thermistor wiring Temperature of thermistor is 90: or more or -0: or less caused by defective refrigerant circuit. Defective indoor controller board Check resistance value of thermistor. For characteristics, refer to (P) above. Check contact failure of connector (CN) on the indoor controller board. Refer to 0-7. Turn the power on and check restart after inserting connector again. Operate in test run mode and check pipe <condenser / evaporator> temperature with outdoor controller circuit board. If pipe <condenser / evaporator> temperature is extremely low (in cooling mode) or high (in heating mode), refrigerant circuit may have defect. Operate in test run mode and check pipe <condenser / evaporator> temperature with outdoor control circuit board. If there is extreme difference with actual pipe <condenser / evaporator> temperature, replace indoor controller board. There is no abnormality if none of above comes within the unit. Turn the power off and on again to operate. ( ) In case of checking pipe temperature with outdoor controller circuit board, be sure to connect A-control service tool (PAC-SKST). E0 or E Remote controller transmission error(e0)/signal receiving error(e) Abnormal if main or sub remote controller cannot receive any transmission normally from indoor unit of refrigerant address 0 for minutes. (Error code : E0) Abnormal if sub remote controller could not receive any signal for minutes. (Error code: E0) Abnormal if indoor controller board can not receive any data normally from remote controller board or from other indoor controller board for minutes. (Error code: E) Indoor controller board cannot receive any signal from remote controller for minutes. (Error code: E) Contact failure at transmission wire of remote controller All remote controllers are set as sub remote controller. In this case, E0 is displayed on remote controller, and E is displayed at LED (LED, LED) on the outdoor controller circuit board. Miswiring of remote controller Defective transmitting receiving circuit of remote controller Defective transmitting receiving circuit of indoor controller board of refrigerant addresses 0. Noise has entered into the transmission wire of remote controller. Check disconnection or looseness of indoor unit or transmission wire of remote controller. Set one of the remote controllers main if there is no problem with the action above. Check wiring of remote controller. Total wiring length: max. 00m (Do not use cable x or more.) The number of connecting indoor units: max. units The number of connecting remote controller: max. units When it is not the above-mentioned problem of ~ Diagnose remote controllers. a) When RC OK is displayed, Remote controllers have no problem. Turn the power off, and on again to check. If abnormality generates again, replace indoor controller board. b) When RC N is displayed, Replace remote controller. c)when RC E or ERC 00- is displayed, noise may be causing abnormality. * If the unit is not normal after replacing indoor controller board in group control, indoor controller board of address 0 may be abnormal. E or E Remote controller transmission error(e)/signal receiving error(e) Abnormal if remote controller could not find blank of transmission path for seconds and could not transmit. (Error code: E) Remote controller receives transmitted data at the same time and compares the received and transmitted data. Abnormal if these data are judged to be different 0 continuous times. (Error code: E) Abnormal if indoor controller board could not find blank of transmission path. (Error code: E) Indoor controller board receives transmitted data at the same time and compares the received and transmitted data. Abnormal if these data are judged to be different 0 continuous times. (Error code: E) remote controllers are set as main. (In case of remote controllers) Remote controller is connected with indoor units or more. Repetition of refrigerant address Defective transmitting receiving circuit of remote controller Defective transmitting receiving circuit of indoor controller board Noise has entered into transmission wire of remote controller. Set a remote controller to main, and the other to sub. Remote controller is connected with only one indoor unit. The address changes to a separate setting. ~ Diagnose remote controller. a) When RC OK is displayed, remote controllers have no problem. Turn the power off,and on again to check. When becoming abnormal again, replace indoor controller board. b)when RC N is displayed, replace remote controller. c)when RC E or ERC 00- is displayed, noise may be causing abnormality.

25 Error Code Abnornal point and detection method Cause Countermeasure E Indoor/outdoor unit communication error (Signal receiving error) Abnormal if indoor controller board cannot receive any signal normally for minutes after turning the power on. Abnormal if indoor controller board cannot receive any signal normally for minutes. Consider the unit abnormal under the following condition: When or more indoor units are connected to an outdoor unit, indoor controller board cannot receive a signal for minutes from outdoor controller circuit board, a signal which allows outdoor controller circuit board to transmit signals. Contact failure, short circuit or, miswiring (converse wiring) of indoor/outdoor unit connecting wire Defective transmitting receiving circuit of indoor controller board Defective transmitting receiving circuit of indoor controller board Noise has entered into indoor/ outdoor unit connecting wire. * Check LED display on the outdoor control circuit board. (Connect A-control service tool, PAC-SKST.) Refer to outdoor unit service manual. Check disconnection or looseness of indoor/ outdoor unit connecting wire of indoor unit or outdoor unit. Check all the units in case of twin triple indoor unit system. - Turn the power off, and on again to check. If abnormality generates again, replace indoor controller board or outdoor controller circuit board. * Other indoor controller board may have defect in case of twin triple indoor unit system. E7 Indoor/outdoor unit communication error (Transmitting error) Abnormal if receiving is detected 0 times continuously though indoor controller board has transmitted 0. Defective transmitting receiving circuit of indoor controller board Noise has entered into power supply. Noise has entered into outdoor control wire. - Turn the power off, and on again to check. If abnormality generates again, replace indoor controller board. Fb Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board. Defective indoor controller board Replace indoor controller board. E or E Remote controller control board Abnormal if data cannot be read normally from the nonvolatile memory of the remote controller control board. (Error code: E) Abnormal if the clock function of remote controller cannot be operated normally. (Error code: E) Defective remote controller Replace remote controller. PA Forced compressor stop (due to water leakage abnormality) When the intake temperature subtracted with liquid pipe temperature is less than -0:, drain sensor is detected whether it is soaked in the water or not at the interval of 90 seconds. (Drain pump will start operating when the drain sensor is detected to be soaked in the water.) The unit has a water leakage abnormality when the following conditions, a and b, are satisfied while the above-mentioned detection is performed. a) The drain sensor is detected to be soaked in the water 0 times in a row. b) The intake temperature subtracted with liquid pipe temperature is detected to be less than -0: for a total of 0 minutes. (When the drain sensor is detected to be NOT soaked in the water, the detection record of a and b will be cleared.) The drain sensor detection is performed in operations other than cooling. (When the unit stops operating, during heating or fan operation, when the unit stops because of some abnormality) *Once the water leakage abnormality is detected, abnormality state will not be released until the main power is reset. Drain pump trouble Drain defective Drain pump clogging Drain pipe clogging Open circuit of drain sensor side heater Contact failure of drain sensor connector Dew condensation on drain sensor Drain water descends along lead wire. Drain water waving due to filter clogging. Extension piping connection difference at twin, triple, quadruple system. 7 Mis-wiring of indoor/ outdoor connecting at twin, triple, quadruple system. 8 Room temperature thermistor / liquid pipe temperature thermistor detection is defective. Check the drain pump. Please confirm whether water can be drained. Confirm the resistance of the drain sensor. Check the connector contact failure. Check the drain sensor leadwire mounted. Check the filter clogging Check the piping connection. 7 Check the indoor/ outdoor connecting wires. 8 Check the room temperature display of remote controller. Check the indoor liquid pipe temperature display of outdoor controller board.

26 0-. TROUBLESHOOTIN BY INFERIOR PHENOMENA Note: Refer to the manual of outdoor unit for the detail of remote controller. Phenomena Cause Countermeasure When LED on indoor controller board is also off. Power supply of rated voltage is not supplied to outdoor unit. ()LED on indoor controller board is off. Defective outdoor controller circuit board. Power supply of 0~0V is not supplied to indoor unit. Defective indoor power board. Defective indoor controller board. (For the separate indoor/outdoor unit power supply system) Power supply of 0~0V AC is not supplied to indoor unit. The connectors of the optional replacement kit are not used. Defective indoor controller board. Defective indoor power board. When LED on indoor controller board is lit. Mis-setting of refrigerant address for outdoor unit (There is no unit corresponding to refrigerant address 0.) Check the voltage of outdoor power supply terminal block (L, N) or (L, N). When AC 0~0V is not detected. Check the power wiring to outdoor unit and the breaker. When AC 0~0V is detected. Check (below). Check the voltage between outdoor terminal block S and S. When AC 0~0V is not detected. Check the fuse on outdoor controller circuit board. Check the wiring connection. When AC 0~0V is detected. Check (below). Check the voltage between indoor terminal block S and S. When AC 0~0V is not detected. Check indoor/outdoor unit connecting wire for mis-wiring. When AC 0~0V is detected. Check (below). Check voltage output from CNS on indoor power board (DC.V). Refer to 0--. When no voltage is output. Check the wiring connection. When output voltage is between DC.V and DC.7V. Check (below). Check the wiring connection between indoor controller board and indoor power board. Check the fuse on indoor controller board. Check the voltage of indoor power supply terminal block (L,N). When AC0~0V is not detected. Check the power supply wiring. When AC0~0V is detected. -Check (below). Check that there is no problem in the method of connecting the connectors. When there are problems in the method of connecting the connectors. Connect the connector correctly referring to installation manual of an optional kit. When there is no problem in the method of connecting the connectors. -Check (below). Check voltage output from CNDK on indoor controller board. When AC0~0V is not detected. Check the fuse on indoor controller board. Check the wiring connection between indoor power supply terminal block and CND on indoor controller board. When AC0~0V is detected. -Check (below). Check voltage output from CNS on indoor power board. When no voltage output. Check the wiring connection between CNDK on indoor controller board and CNSK on indoor power board. If no problem are found,indoor power board is defective. When DC.~.7V is detected. Check the wiring connection between CNS on indoor power board and CND on indoor power board. If no problem are found,indoor controller Reconfirm the setting of refrigerant address for outdoor unit Set the refrigerant address to 0. (For grouping control system under which or more outdoor units are connected, set one of the units to 0.) Set refrigerant address using SW (-) on outdoor controller circuit board.

27 Note: Refer to the manual of outdoor unit for the detail of remote controller. Phenomena Cause Countermeasure ()LED on indoor controller board is blinking. ()Upward/downward vane performance failure ()Receiver for wireless remote controller When LED on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire When LED is lit. Mis-wiring of remote controller wires Under twin triple indoor unit system, or more indoor units are wired together. Refrigerant address for outdoor unit is wrong or not set. Under grouping control system, there are some units whose refrigerant address is 0. Short-cut of remote controller wires Defective remote controller The vane is not downward during defrosting and heat preparation and when the thermostat is OFF in HEAT mode. (Working of COOL protection function) Vane motor does not rotate. Defective vane motor Breaking of wire or connection failure of connector Up/down vane setting is No vanes. Upward/downward vane does not work. The vane is set to fixed position. Weak batteries of wireless remote controller. Contact failure of connector (CNB) on wireless remote controller board. (Insert failure) Contact failure of connector (CN90) on indoor controller board.(insert failure) Contact failure of connector between wireless remote controller board and indoor controller board. Check indoor/outdoor unit connecting wire for connection failure. Check the connection of remote controller wires in case of twin triple indoor unit system. When or more indoor units are wired in one refrigerant system, connect remote controller wires to one of those units. Check the setting of refrigerant address in case of grouping control system. If there are some units whose refrigerant addresses are 0 in one group, set one of the units to 0 using SW (-) on outdoor controller circuit board. Remove remote controller wires and check LED on indoor controller board. When LED is blinking, check the shortcut of remote controller wires. When LED is lit, connect remote controller wires again and: if LED is blinking, remote controller is defective; if LED is lit, connection failure of remote controller terminal block etc. has returned to normal. Normal operation (The vane is set to horizontal regardless of remote control.) Check (left). Check the vane motor. (Refer to How to check the parts.) Check for breaking of wire or connection failure of connector. Check Up/down vane setting. (Unit function selection by remote controller). Normal operation (Each connector on vane motor side is disconnected.) Replace batteries of wireless remote controller. ~ Check contact failure of each connector. If no problems are found of connector, replace indoor controller board. When the same trouble occurs even if indoor controller board is replaced, replace wireless remote controller board. 7

28 0-. When wired remote controller or indoor unit micro computer troubles. If there is not any other wrong when trouble occurs, emergency operation starts as the indoor controller board switch (SWE) is set to ON. During the emergency operation the indoor unit is as follows; () Indoor fan high speed operation () Drain-up machine operation(option). When emergency operating for COOL or HEAT, setting of the switch (SWE) in the indoor controller board and outdoor unit emergency operation are necessary.. Check items and notices as the emergency operation () Emergency operation cannot be used as follows; When the outdoor unit is something wrong. When the indoor fan is something wrong. When drain over flow protected operation is detected during self-diagnosis. (Error code : P) () Emergency operation will be serial operation by the power supply ON/OFF. ON/OFF or temperature, etc. adjustment is not operated by the remote controller. () Do not operate for a long time as cold air is blown when the outdoor unit starts defrosting operation during heat emergency operation. () Cool emergency operation must be within 0 hours at most. It may cause heat exchanger frosting in the indoor unit. () After completing the emergency operation, return the switch setting, etc. in former state. () Since vane does not work at emergency operation, position the vane manually and slowly. 8

29 0-. HOW TO CHECK THE PARTS PCA-RP0/0/7/00//0A PCA-RP0/0/7/00//0A# PCA-RP0A PCA-RP0A# PCH-P0/0/7/00//0AH Fan motor Relay connector Orange Red Pink Parts name Room temperature thermistor (TH) Pipe temperature thermistor (TH) Condenser/evaporator temperature thermistor (TH) Vane motor Red White Black Protector OFF : 0 ON : 80 0 M Yellow Brown Blue Check points Disconnect the connector then measure the resistance with a tester. (At the ambient temperature 0 ~0 ) Normal.k ~9.k Abnormal Open or short Measure the resistance between the terminals using a tester. (Winding temperature 0 ) Motor terminal or Relay connector Red Black White Black Connector Brown Yellow Brown Blue Red Orange Red Pink 0A A 8~ 0A 0, Normal (Refer to the next pege for a detail.) Normal 0A, 0, 7 0~ Abnormal, Open or short Abnormal Open or short Pink Orange Red M Yellow Blue Connector Red Yellow Red Blue Red Orange Red Pink Normal 00,, 0 0~0 Abnormal Open or short Heater (Only PCH) Measure the resistance of each heater element with a tester. (At the ambient temperature 0 ) V Normal 0, V V, V Abnormal Open or short Drain-up mechanism (Option) ray ray Measure the resistance between the terminals with a tester. (Winding temperature 0 ) Normal 9 Abnormal Open or short Contactor (Only PCH) Measure the resistance between the terminals with a tester. Normal 0~0 88H 0 Abnormal Open or short 9

30 <Thermistor Characteristic graph> Thermistor for lower temperature Room temperature thermistor(th) Pipe temperature thermistor(th) Condenser/evaporator temperature thermistor(th) 0 0 < Thermistor for lower temperature > Thermistor R0=k ± % Fixed number of B=80 ± % Rt=exp { 80( 7+t 7 ) } 0: k 0: 9.k 0:.k :.k 0:.k 0:.0k Resistance (k ) Temperature ( ) 0-.TEST POINT DIARAM 0--. Power board PCA-RP0A PCA-RP0A# PCA-RP0AH PCA-RP0A PCA-RP0A# PCA-RP0A PCA-RP0A# PCA-RP0AH PCA-RP7A PCA-RP7A# PCA-RP7AH PCA-RP00A PCA-RP00A# PCA-RP00AH PCA-RPA PCA-RPA# PCA-RPAH PCA-RP0A PCA-RP0A# PCA-RP0AH CNS Connect to the indoor controller board (CND) Between to.-.7v DC (Pin (+)) CNSK Connect to the indoor controller board (CNDK) Between to 0-0V AC 0

31 0--. Indoor controller board PCA-RP0/0/7/00//0A PCA-RP0/0/7/00//0A# PCH-P0/0/7/00//0AH PCA-RP0A PCA-RP0A# CNC Transmission (Indoor/ outdoor) (0~V DC) CND Connect to the indoor power board (CNS) (.~.7V DC) LED Power supply (I.B) LED Power supply (R.B) LED Transmission (Indoor/ outdoor) CN Connect to the terminal block(tb) (Remote controller connecting wire) (0.~.V DC) CNDK Connect to the indoor power board (CNSK) (0~0V AC) CN0 Room temperature thermistor (TH) CN Pipe temperature thermistor/liquid (TH) CN9 Condenser/evaporator temperature thermistor (TH) FUSE (. A 0 V) CN Drain sensor (DS) CND Power supply input (0~0V AC) CN90 Connect to the wireless remote controller board (CNB) CNP Drain-pump output (DP) (0~0V AC) CNV Vane motor output (MV) CN Connector (HA terminal-a) CN Centrally control CN Heater output (V DC) SWE Emergency operation CNL Connector (LOSSNAY) FAN Fan motor output Jumper wire J, J Pair number setting with wireless remote controller SW Capacity setting SW Model setting

32 0-7. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE Each function is controlled by the dip switch and the jumper wire on control p.c. board. SW and SW are equipped only for service parts. Model setting and capacity setting are memorized in the nonvolatile memory of the control p.c. board of the unit. (Marks in the table below) Jumper wire ( : Short : Open) Jumper wire Functions Setting by the dip switch and jumper wire Remarks For service board SW Model settings ON OFF SW Capacity settings MODELS PCA-RP0A PCH-P0AH Service board ON OFF PCA-RP0A PCA-RP0A PCH-P0AH ON OFF PCA-RP7A PCH-P7AH ON OFF PCA-RP00A PCH-P00AH ON OFF PCA-RPA PCH-PAH ON OFF PCA-RP0A PCH-P0AH ON OFF J J Pair number setting with wireless remote controller Wireless remote controller setting 0 ~ 9 Control PCB setting J J <Initial setting> Wireless remote controller: 0 Control PCB: (for both J and J) Four pair number settings are supported. The pair number settings of the wireless remote controller and indoor control PCB (J/J) are given in the table on the left. (' ' in the table indicates the jumper line is disconnected.) JP Unit type setting Model Without TH With TH JP There is no jumper (JP) because these models have the cond./eva. temperature thermistor (TH). JP Indoor controller board type setting Indoor controller board type For product Service parts JP

33 SPECIAL FUNCTION -. ROTATION FUNCTION(AND BACK-UP FUNCTION, ND STAE CUT-IN FUNCTION) For PCA-RP0/0/7/00//0A#,PCA-RP0A# --. Operation () Rotation function (and Back-up function) Outline of functions Main and sub unit operate alternately according to the interval of rotation setting. w Main and sub unit should be set by refrigerant address.(outdoor Dip switch setting) Refrigerant address"00" Main unit Refrigerant address"0" Sub unit When error occurrs to one unit, another unit will start operation.(back-up function) System constraint This function is available only by the grouping control system(indoor UNIT : OUTDOOR UNIT=:) of refrigerant groups.(refer to Fig. ) Main indoor unit should be connected for wired remote controller and the transmission line(tb) for main and sub unit should also be connected. (Refer to Fig. ) (This function cannot be set by wireless remote controller.) Set refrigerant address of each unit.(dip switch on the outdoor unit Refrigerant address 00/0) Operation pattern [Back-up function only] Request code number "" Error occurs on main unit. Start operation Main Sub Main unit IC- Run Abnormal condition Fig. Main unit Refrigerant address "00" OC- Refrigerant address "0" OC- () () Sub unit Sub unit IC- Stop Run [Rotation function] & [Back-up function] Request code number "~8" RC Error occurs on main unit. Start operation Main Sub Sub Main Main Sub OC : Outdoor unit Main unit IC- Run Stop Run Abnormal condition IC- IC : Indoor unit RC : Wired remote controller IC- Sub unit IC- Stop Run Stop Run ~8 days ~8 days (Ex:When the request code number is "", each unit operates alternately in daily cycle.) Note: When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start operation. To operate the main unit, refer to the --. and set the requet code No. which is not the same as the current one, and set again the former request code No. () nd stage cut-in function Outline of functions Number of operating units is determined according to the room temperature and set point. When room temperature becomes higher than set point, standby unit starts.( units operation) When room temperature falls below set point -:, standby unit stops.( unit operation) System constraint This function is available only in rotation operation and back-up function in cooling mode. [nd stage cut-in function] Request code number "~" Main unit IC- Start operation Run Room temp. Set point Sub unit start operation Room temp. < Set point - Sub unit stop Sub unit IC- Stop Run Stop

34 --. How to set rotation function(back-up function, nd stage cut-in function) You can set these functions by wired remote controller.(maintenance monitor) NOTICE Both main and sub unit should be set in same setting. Every time replacing indoor controller board for servicing, the function should be set again. () Request Code List Rotation setting Setting No. (Request code) No. (0) No. () No. () No. () No. () No. () No.7 () No.8 (7) No.9 (8) Setting contents Monitoring the request code of current setting. Rotation and Back-up OFF (Normal group control operation) Back-up function only Rotation ON (Alternating interval = day) and back up function Rotation ON (Alternating interval = day) and back up function Rotation ON (Alternating interval = day) and back up function Rotation ON (Alternating interval = 7day) and back up function Rotation ON (Alternating interval = day) and back up function Rotation ON (Alternating interval = 8day) and back up function Initial setting nd stage cut-in setting Setting No. (Request code) No. (0) No. () No. () No. () No. () Setting contents Monitoring the request code of current setting. Cut-in function OFF Cut-in Function ON(Set point = Set temp.+ C(7. F)) Cut-in Function ON(Set point = Set temp.+ C(0.8 F)) Cut-in Function ON(Set point = Set temp.+ 8 C(. F)) Initial setting

35 () Setting method of each function by wired remote controller B: Refrigerant address C: Data display area D: Request code display area. Stop operation( ).. Press the TEST button ( ) for seconds so that [Maintenance mode] appears on the screen ( ). After a while, [00] appears in the refrigerant address number display area.(at ). Press the CHECK button ( ) for seconds to switch to [Maintenance monitor]. Note) It is not possible to switch to [Maintenance monitor] during data request in maintenance mode (i.e., while ---- is blinking) since no buttons are operative. [----] appears on the screen ( ) when [Maintenance monitor] is activated. (The display ( ) now allows you to set a request code No.). Press the [TEMP ( and )] buttons ( ) to select the desired refrigerant address. [ScreenB]. Press the [CLOCK ( and )] buttons ( ) to set the desired request code No.( ~8, ~ ). Press the FILTER button ( ) to perform function setting. If above setting operations are done correctly, "Request code number will appear in data display area.( ) [Example: When the "" of "Request code number" is set, [] appears on the screen.( )] [Refererence] You can check current "request code number" setting by setting the "request code number"( 0 or 0 ) and pressing the FILTER button.( ) [Example: When the current setting is "Setting No.(Request code )", [] appears on the screen.( )] 7. To return to normal mode, press the ON/OFF button ( ).

36 DISASSEMBLY PROCEDURE PCA-RP0/0/7/00//0A PCA-RP0/0/7/00//0A# PCA-RP0A PCA-RP0A# PCH-P0/0/7/00//0AH OPERATIN PROCEDURE. Removing the air intake grille () Slide the intake grille holding knobs backward to open the intake grill. () When the intake grille left open, push the stoppers on the rear hinges to pull out the intake grille. PHOTOS&ILLUSTRATIONS Figure Intake grill Intake grill Holding knobs slide Pull out the intake grill Hinges. Removing the electrical box () Remove the air intake grille. (See the figure ) () Remove the screw from the beam and remove the beam. () Remove the screws from the electrical cover, and remove the electrical cover. () Disconnect CNV, CN and CN9. () Remove the screws from the electrical box and pull out the electrical box. Figure Slide to the left Beam <Electrical parts in the electrical box> Terminal block (for indoor / outdoor connecting line) Terminal block (for electric heater : PCH only) Terminal block (for remote controller) Fan motor capacitor Indoor control board Relay (PCH only) Power board Screw(electrical cover) Electrical cover Screw(electrical box) Photo Clamp Fan motor capacitor Relay (PCH only) Power board Indoor control board Terminal block (Electric heater) Terminal Terminal block block (remote control) (Indoor / outdoor connecting line)

37 OPERATIN PROCEDURE. Removing the fan motor () Remove the intake grille. (See the figure ) () Disconnect the fan motor connector. () Remove screws for removing the motor guard. () Remove screws for removing the fan guard. () Remove the screw for removing the motor support at both left and right side. () Loosen the set screws at the fan motor side of the connecting joint. (7) Slide the fan motor to the left side and pull it out. PHOTOS&ILLUSTRATIONS Photo Screws Motor guard Motor Set screws Motor support Connecting joint. Removing the sirocco fan () Remove the air intake grille. (See the figure ) () Remove beam. () Remove screws for removing the motor guard. () Remove screws for removing the fan guard. () Remove the lower casing while pressing the stoppers at upper side of the casing. () Loosen the set screws at the connecting joint. (7) Remove the sirocco fan and shaft together by sliding the shaft to the left. Photo Motor guard Fan guard (Note) Make sure that the upper side casing is snapped to the fan plate securely with catch. Motor Sirocco fan Casing Connecting joint Bearing. Removing the side panel () Remove the air intake grille. (See the figure ) () Remove the screw from the side panel, and remove the side panel by sliding the panel to the front. Figure Side panel Sliding the panel to the front Screw 7

38 OPERATIN PROCEDURE. Removing the vane motor () Remove the air intake grille. (See the figure ) () Remove the left side panel. (See the figure ) () Remove the relay connector of vane motor. () Remove the electrical box. () Remove the screws of vane motor, then remove vane motor. (Note) Connect the lead wires and connectors properly and place them in the proper position so that the wires are not pinched by other parts. Photo Relay connector of the vane motor PHOTOS Screw Vane motor 7. Removing the Indoor coil thermistor () Remove the air intake grille. (See the figure ) () Remove the right side panel. (See the figure ) () Remove the relay connector of the pipe thermistor. () Remove the screw, and remove the check panel. () Extract the indoor coil thermistor from the holder. <Caution for the installation> There is a possibility for the short circuit when connector gets wet by water through the thermistor lead wire. Therefore, lead wire of the indoor coil thermistor should be tied as shown in the photo. Photo Screw Check panel Relay connector of the pipe thermistor Left side panel Photo Hold Indoor coil thermistor Clamp 8. Removing the Under panel () Remove the air intake grille. (See the figure ) () Remove the beam. () Remove the side panel (right and left). (See the figure ) () Remove the 9 screws of the under panel, then remove the under panel. w Weight of the under panel : approx. kg. Photo 7 Screws Under panel 8

39 OPERATIN PROCEDURE 9. Removing the drain pan () Remove the air intake grille. (See the figure ) () Remove the beam. () Remove the side panels of right and left. (See the figure ) () Remove the under panel. Remove the screws of the right and left side drain pan. () Remove the insulations in centre of the drain pan, and after removing the screws, remove the drain pan. (Note) Please aware that there might be drain left in the drain pan when you remove the drain pump (option). Photo 8 PHOTOS Screw Drain pan Screw (Insulation) Screw 0. Removing the guide vane () Remove the intake grille. (See the figure ) () Remove the beam. () Remove the side panels on right and left. (See the figure ) () Remove the under panel. (See the photo 7) () Remove the drain pan. (See the photo 8) () Remove the screw from the guide vane, then remove the guide vane. Photo 9 Drain pan uide vane Screw. Removing the Auto vane () Remove the intake grille. (See the figure ) () Remove the left side panel. (See the figure ) () Remove the left side box. () Remove the under panel. () Remove the screw from the auto vane. () Slide the auto vane to the right side and pull the auto vane out. Photo 0 Auto vane Screw 9

40 OPERATIN PROCEDURE. Removing the electric heater. (PCH only) () Remove the air intake grille. (See the figure ) () Remove the beam. () Remove the electrical box cover and disconnect the connector (P red) of the heater. () Loosen clamps for the heater lead wires. () Remove the side panel (right and left). (See the figure ) () Remove the under panel. (See the photo 7) (7) Remove the drain pan. (See the photo 8) (8) Remove the screws from the service panel. (9) Pull out the heater with the service panel. Photo PHOTOS Screws Clamp Connector (heater) Service panel Electrical box. Removing the heat exchanger. () Remove the air intake grille. (See the figure ) () Remove the beam. () Remove the side panel (right and left). (See the figure ) () Disconnect the relay connector of the pipe thermistor. () Remove the under panel. (See the photo 7) () Remove the drain pan. (See the photo 8) (7) Unscrew the screw of the pipe cover, and remove the pipe cover. (8) Unscrew the screw of the pipe support, and remove the pipe support. (9) Unscrew the screw of the heat exchanger, and remove the heat exchanger. Remove the heat exchanger with care. Since this is quite heavy, removing work should be done with more than people. wweight of heat exchanger : approx..kg Photo Pipe support Screws Pipe cover Screws Heat exchanger 0

41 PARTS LIST(non-RoHS compliant) FAN AND HEATER PARTS PCH-P0AH PCA-RP0A R0 7J 0 MOTOR LE P0AH Q'ty / set RP0A Remarks (Drawing No.) Wiring Diagram Symbol No. Parts No. Parts Name Specifications PCH- PCA- Recommended Q'ty R0 7J 0 CASIN R0 7J SIROCCO FAN T7W 9J 7 FAN UARD R0 E 0 ROOM TEMPERATURE THERMISTOR TH R0 E PIECE (MOTOR) 7 R0 7J 0 FAN MOTOR D09BPMS MF 8 R0 7J DRAIN PLU 9 T7W 7J 7 FAN UARD 0 R0 A 9 DRAIN PAN ASSY T7W 8J 7 FAN UARD R0 K 700 THERMAL SWITCH OFF:0 ON: H R0 8J 0 R0 0J 0 INSULATOR INSULATOR T7W J 00 HEATER ELEMENT 80V W H R0 7J 0 PIPE TEMPERATURE THERMISTOR TH R0 E7 0 CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR TH 7 R0 E8 80 T7W K00 80 HEAT EXCHANER HEAT EXCHANER 8 R0 P0 70 THERMAL FUSE 0V 98 0A FS,

42 FAN AND HEATER PARTS PCH-P0AH, PCA-RP0A PCH-P7AH, PCA-RP7A Q'ty / set R0 9J 0 MOTOR LE P7 AH RP7 A Remarks (Drawing No.) Wiring Diagram Symbol No. Parts No. Parts Name Specifications PCH- PCA- P0 RP0 AH A Recommended Q'ty T7W 0J 7 FAN MOTOR DO9CP70MS MF R0 700 SHAFT JOINT R0 E PIECE (MOTOR) R0 9J SIROCCO FAN T7W 0J 7 FAN UARD 7 R0 E 0 ROOM TEMPERATURE THERMISTOR TH 8 R0 9J 00 SHAFT (FAN) 9 T7W J 7 FAN UARD 0 R0 E00 0 SLEEVE BEARIN R0 9J BEARIN SUPPORT R0 7J DRAIN PLU R0 A 9 DRAIN PAN ASSY T7W 8J 7 FAN UARD R0 7J 0 CASIN R0 J SIROCCO FAN 7 R0 0J 0 R0 0J 0 INSULATOR INSULATOR 8 T7W 0J 00 HEATER ELEMENT 80V 700W H 9 R0 7J 0 PIPE TEMPERATURE THERMISTOR TH 0 R0 E7 0 CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR TH R0 H00 80 T7W K0 80 HEAT EXCHANER HEAT EXCHANER T7W J 70 THERMAL FUSE 0 A 0V FS, R0 K 700 THERMAL SWITCH OFF:0 ON: H

43 FAN AND HEATER PARTS PCH-P00AH PCA-RP00A Q'ty / set Remarks (Drawing No.) No. Parts No. Parts Name Specifications PCH- PCA- P00AH RP00A R0 E PIECE (MOTOR) R0 J 0 MOTOR LE R0 J 0 FAN MOTOR D0BP90MS R0 700 SHAFT JOINT R0 J SIROCCO FAN T7W J 7 FAN UARD 7 R0 E 0 ROOM TEMPERATURE THERMISTOR 8 R0 9J 00 SHAFT 9 T7W J 7 FAN UARD 0 R0 E00 0 SLEEVE BEARIN R0 J BEARIN SUPPORT R0 7J DRAIN PLU R0 A 9 DRAIN PAN ASSY T7W J 7 FAN UARD R0 J 0 CASIN R0 9J SIROCCO FAN 7 R0 0J 0 INSULATOR R0 J 0 INSULATOR 8 T7W 9J 00 HEATER ELEMENT 80V 900W 9 R0 7J 0 PIPE TEMPERATURE THERMISTOR 0 R0 E7 0 CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR R0 E 80 HEAT EXCHANER T7W K0 80 HEAT EXCHANER T7W THERMAL FUSE 7 A 0V R0 K 700 THERMAL SWITCH OFF:0 ON: Wiring Recommended Diagram Symbol Q'ty MF TH H TH TH FS, H

44 FAN AND HEATER PARTS PCH-PAH, PCA-RPA PCH-P0AH, PCA-RP0A No. Parts No. Parts Name Specifications R0 9J 00 R0 J 0 R0 J 0 R0 E R0 J T7W J 7 R0 E 0 T7W J 7 R0 J R0 700 R0 A7 9 T7W J 7 R0 9J R0 7J T7W J 7 R0 J 0 R0 E00 0 R0 J R0 0J 0 R0 J 0 T7W J 00 R0 7J 0 R0 E7 0 T7W K0 80 T7W K0 80 T7W K0 80 T7W K0 80 T7W J 70 R0 K 700 SHAFT MOTOR LE FAN MOTOR D0BP0MS PIECE (MOTOR) SIROCCO FAN FAN UARD ROOM TEMPERATURE THERMISTOR FAN UARD SIROCCO FAN SHAFT JOINT DRAIN PAN ASSY FAN UARD SIROCCO FAN DRAIN PLU FAN UARD CASIN SLEEVE BEARIN BEARIN SUPPORT INSULATOR INSULATOR HEATER ELEMENT 80V 000W PIPE TEMPERATURE THERMISTOR CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR HEAT EXCHANER HEAT EXCHANER HEAT EXCHANER HEAT EXCHANER THERMAL FUSE 0 A 0V THERMAL SWITCH OFF:0 ON: Q'ty / set PCH- P AH P0 AH PCA- RP A RP0 A Remarks (Drawing No.) Wiring Recommended Diagram Symbol Q'ty MF TH H TH TH FS, H

45 STRUCTURAL PART PCA-RP0A PCH-P0AH Part numbers that are circled are not shown in the figure. Q, ty/set No. Parts No. Parts Name Specifications PCA-RP0A PCH-P0AH R0 7N S.PLATE-L R0 A 00 L.L FILTER R0 7J 0 RILLE HINE R0 8J 9 RILLE ASSY R0 7J 9 RILLE ASSY R0 7J 0 RILLE CATCH 7 R0 A 00 L.L FILTER 8 REAR SUPPORT 9 R0 7J 9 UNDER PANEL 0 BEAM(A) T7W E0 070 W.BOARD CASE R0 8J S.PLATE-R R0 7J 808 RIHT LE (R) R0 7J 8 SERVICE PANEL R0 7J RIHT SIDE PANEL R0 7J 07 RIHT SIDE BOX 7 R0 7J 08.V ASSY-R 8 R0 E00 0 VANE SUPPORT 9 R0 7J FRONT PANEL 0 R0 7J 00 AUTO VANE R0 7J 08.V ASSY-L R0 A 7 REAR PANEL R0 7J 08 LEFT SIDE BOX R0 E0 VANE MOTOR R0 7J 809 LEFT LE (L) R0 7J LEFT SIDE PANEL 7 R0 7J JOINT SOCKET 8 T7W E00 07 DRAIN HOSE COVER Remarks (Drawing No.) (B0HK0) (B7HH08) Wiring Recommended Diagram Symbol Q'ty MV

46 STRUCTURAL PART PCA-RP0A PCA-RP7A PCA-RP00A PCH-P0AH PCH-P7AH PCH-P00AH Part numbers that are circled are not show in the figure No. Parts No. Parts Name Specifications R0 7J R0 J R0 7J 809 R0 7N R0 J R0 A 7 R0 A 7 R0 7J 0 R0 7J 0 R0 7J 9 R0 A 00 R0 9J 9 T7W E0 070 R0 8J R0 E00 R0 7J R0 J R0 7J 808 R0 7J 8 R0 8J 8 R0 7J 07 R0 J 07 R0 9J R0 J R0 9J 00 R0 E0 00 R0 E00 0 R0 E0 0 R0 7J 08 R0 7J 087 R0 7J 08 R0 7J 08 R0 E00 08 R0 9J R0 J R0 7J T7W E00 07 LEFT SIDE PANEL LEFT SIDE PANEL LEFT LE S.PLATE-L S.PLATE-L REAR PANEL REAR PANEL RILLE HINE RILLE CATCH RILLE ASSY L.L FILTER UNDER PANEL W.BOARD CASE REAR SUPPORT BEAM (A) S.PLATE-R S.PLATE-R RIHT SIDE PANEL RIHT SIDE PANEL RIHT LE SERVICE PANEL SERVICE PANEL RIHT SIDE BOX RIHT SIDE BOX FRONT PANEL FRONT PANEL AUTO VANE AUTO VANE VANE SUPPORT VANE SUPPORT.V ASSY-R.V ASSY-C.V ASSY-L LEFT SIDE BOX LEFT SIDE BOX VANE MOTOR VANE MOTOR JOINT SOCKET DRAIN HOSE COVER Q, ty/set PCA-RP/PCH-P 0/7 00 A/AH Remarks (Drawing No.) (B0HK0) (B7HH08) Wiring Recommended Diagram Symbol Q'ty MV MV

47 STRUCTURAL PART PCA-RPA PCA-RP0A PCH-PAH PCH-P0AH Part numbers that are circled are not shown in the figure. No. Parts No. Parts Name Specifications R0 J R0 J R0 A7 7 R0 A 00 R0 7J 0 R0 8J 9 R0 7J 0 R0 7J 9 R0 A 00 R0 J 9 T7W E0 070 R0 J R0 7J 808 R0 8J 8 R0 J 07 R0 E00 R0 J R0 E0 00 R0 J 08 R0 J 087 R0 E0 0 R0 J 08 R0 E00 08 R0 J R0 7J 809 R0 7J T7W E00 07 LEFT SIDE PANEL S.PLATE-L REAR PANEL L.L FILTER RILLE HINE RILLE ASSY RILLE CATCH RILLE ASSY L.L FILTER UNDER PANEL W.BOARD CASE REAR SUPPORT BEAM(A) RIHT SIDE PANEL RIHT LE SERVICE PANEL RIHT SIDE BOX S.PLATE-R FRONT PANEL AUTO VANE.V ASSY-R.V ASSY-C VANE SUPPORT.V ASSY-L LEFT SIDE BOX VANE MOTOR LEFT LE JOINT SOCKET DRAIN HOSE COVER 7 Q, ty/set PCA-RP/0A PCH-P/0AH Remarks (Drawing No.) (B0HK0) (B7HH08) Wiring Recommended Diagram Symbol Q'ty MV

48 ELECTRICAL PARTS PCA-RP0A PCA-RP0A PCA-RP7A PCA-RP00A PCA-RPA PCA-RP0A 7 TEMP. ON/OFF No. Parts No. Parts Name Specifications R0 0L CAPACITOR 0V T7W 9J CAPACITOR 0V R0 A CAPACITOR 0V R0 E0 9 FUSE 0V.A T7W E0 0 INDOOR CONTROLLER BOARD T7W E 7 TERMINAL BLOCK P(S,S,S) T7W 7 TERMINAL BLOCK P(,) CONTROL BOX 0 Q, ty PCA-RP 0/7 00 A /0 Remarks (Drawing No.) (B00N0) Wiring Diagram Symbol C C C FUSE I.B TB TB Recommended Q'ty 7 R0 E0 POWER BOARD CONTROL COVER (B0A807) P.B 8 CONTROL COVER (B0A808) CONTROL COVER (B0A809) 9 T7W A00 0 REMOTE CONTROLLER CORD 0 T7W E08 7 REMOTE CONTROLLER PAR-MAA R.B 8

49 ELECTRICAL PARTS PCH-P0AH, PCH-P00AH PCH-P0AH, PCH-PAH PCH-P7AH, PCH-P0AH TEMP. ON/OFF 0 No. Parts No. Parts Name Specifications R0 0L CAPACITOR 0V T7W 9J CAPACITOR 0V R0 A CAPACITOR 0V R0 E0 9 FUSE 0V.A T7W E0 0 INDOOR CONTROLLER BOARD T7W A 7 TERMINAL BLOCK P (L,N, ) T7W E 7 TERMINAL BLOCK P (S,S,S) T7W 7 TERMINAL BLOCK P (,) 7 CONTROL BOX 8 R0 E0 POWER BOARD 9 R0 7 RELAY JC-A DCV CONTROL COVER 0 CONTROL COVER CONTROL COVER T7W A00 0 REMOTE CONTROLLER CORD 0m T7W E08 7 REMOTE CONTROLLER PAR-MAA Q'ty / set PCH-P 0 0/7 00 /0 AH Remarks (Drawing No.) (B00N0) (B0A807) (B0A808) (B0A809) Wiring Diagram Symbol C C C FUSE I.B TB TB TB P.B 88H R.B Recommended Q'ty 9

50 RoHS PARTS LIST FAN AND HEATER PARTS PCH-P0AH PCA-RP0A PCA-RP0A# RoHS No. Parts No. Parts Name Specifications PCH-P PCA-RP 0AH 0A 0A# 0 Q'ty / set R0 J 0 R0 8J 0 R0 E T7W J 7 R0 H08 0 R0 E R0 8J 0 R0 8J T7W 0J 7 R0 E7 9 T7W 9J 7 R0 E 700 MOTOR LE CASIN SIROCCO FAN FAN UARD ROOM TEMPERATURE THERMISTOR PIECE (MOTOR) FAN MOTOR DRAIN PLU FAN UARD DRAIN PAN ASSY FAN UARD THERMAL SWITCH D09BPMS OFF:0 ON: R0 J 0 INSULATOR R0 J 0 INSULATOR T7W E 00 HEATER ELEMENT 80V 7W R0 H0 0 R0 H09 0 PIPE TEMPERATURE THERMISTOR CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR 7 R0 N08 80 HEAT EXCHANER T7W H 80 HEAT EXCHANER 8 R0 P0 70 THERMAL FUSE 0V 98 0A Remarks (Drawing No.) Wiring Recommended Diagram Symbol Q'ty TH MF H H TH TH FS,

51 FAN AND HEATER PARTS PCA-RP0A PCA-RP0A# PCA-RP0A PCA-RP7A PCA-RP0A# PCA-RP7A# PCH-P0AH PCH-P7AH RoHS No. Parts No. Parts Name Specifications PCH- P PCA- RP 0AH 7AH 0A 0A 0A# R0 0J 0 T7W 0J 7 R0 800 R0 E R0 E7 T7W 9J 7 R0 H08 0 R0 0J 00 T7W 8J 7 R0 E0 0 R0 0J R0 8J R0 A8 9 T7W 7J 7 R0 8J 0 R0 E R0 J 0 R0 0J 0 T7W E 00 R0 H0 0 R0 H09 0 R0 J 80 T7W H 80 T7W H7 80 T7W J 70 R0 E 700 MOTOR LE FAN MOTOR DO9CP70MS SHAFT JOINT PIECE (MOTOR) SIROCCO FAN FAN UARD ROOM TEMPERATURE THERMISTOR SHAFT (FAN) FAN UARD SLEEVE BEARIN BEARIN SUPPORT DRAIN PLU DRAIN PAN ASSY FAN UARD CASIN SIROCCO FAN INSULATOR INSULATOR HEATER ELEMENT 80V 700W PIPE TEMPERATURE THERMISTOR CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR HEAT EXCHANER HEAT EXCHANER HEAT EXCHANER THERMAL FUSE 0 A 0V THERMAL SWITCH OFF:0 ON: Q'ty / set 0A# 7A 7A# Remarks (Drawing No.) Wiring Recommended Diagram Symbol Q'ty MF TH H TH TH FS, H

52 FAN AND HEATER PARTS PCH-P00AH PCA-RP00A PCA-RP00A# RoHS Q'ty / set No. Parts No. Parts Name Specifications PCH-P PCA-RP 00AH 00A 00A# R0 E R0 J 0 R0 9J 0 R0 800 R0 E9 T7W J 7 R0 H08 0 R0 0J 00 T7W J 7 R0 E0 0 R0 J R0 8J R0 E8 9 T7W J 7 R0 9J 0 R0 E0 PIECE (MOTOR) MOTOR LE FAN MOTOR SHAFT JOINT SIROCCO FAN FAN UARD ROOM TEMPERATURE THERMISTOR SHAFT FAN UARD SLEEVE BEARIN BEARIN SUPPORT DRAIN PLU DRAIN PAN ASSY FAN UARD CASIN SIROCCO FAN D0BP90MS 7 R0 J 0 INSULATOR R0 J 0 INSULATOR 8 T7W E 00 HEATER ELEMENT 80V 900W 9 0 R0 H0 0 R0 H09 0 PIPE TEMPERATURE THERMISTOR CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR R0 N09 80 HEAT EXCHANER T7W H 80 HEAT EXCHANER T7W 70 R0 E 700 THERMAL FUSE THERMAL SWITCH 7 A 0V OFF:0 ON: Remarks (Drawing No.) Wiring Recommended Diagram Symbol Q'ty MF TH H TH TH FS, H

53 FAN AND HEATER PARTS PCA-RPA PCA-RP0A PCA-RPA# PCA-RP0A# PCH-PAH PCH-P0AH Q'ty / set Wiring Recommended No. Parts No. Parts Name Specifications PCH- P PCA- RP Remarks Diagram A (Drawing No.) AH 0A 0AH Symbol Q'ty A# 0A# R0 0J 00 R0 J 0 R0 0J 0 R0 E R0 E8 T7W J 7 R0 H08 0 T7W J 7 R0 E9 R0 800 R0 E9 9 T7W J 7 R0 E0 R0 8J T7W J 7 R0 9J 0 R0 E0 0 R0 J SHAFT MOTOR LE FAN MOTOR PIECE (MOTOR) SIROCCO FAN FAN UARD ROOM TEMPERATURE THERMISTOR FAN UARD SIROCCO FAN SHAFT JOINT DRAIN PAN ASSY FAN UARD SIROCCO FAN DRAIN PLU FAN UARD CASIN SLEEVE BEARIN BEARIN SUPPORT D0BP0MS MF TH 9 R0 J 0 INSULATOR R0 J 0 INSULATOR 0 T7W E 00 HEATER ELEMENT 80V 000W H R0 H0 0 R0 H09 0 PIPE TEMPERATURE THERMISTOR CONDENSER / EVAPORATOR TEMPERATURE THERMISTOR TH TH T7W H 80 HEAT EXCHANER T7W H 80 HEAT EXCHANER T7W H 80 HEAT EXCHANER T7W H7 80 HEAT EXCHANER T7W J 70 R0 E 700 THERMAL FUSE THERMAL SWITCH 0 A 0V OFF:0 ON: FS, H RoHS

PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL PKH-P60FALH PKH-P71FALH PKH-P100FALH

PKA-RP60FAL PKA-RP71FAL PKA-RP100FAL PKH-P60FALH PKH-P71FALH PKH-P100FALH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS May 005 No.OC33 SERVICE MANUAL Indoor unit [Model names] PKA-RP60FAL PKA-RP7FAL PKA-RP00FAL [Service Ref.] PKA-RP60FAL PKA-RP7FAL PKA-RP00FAL

More information

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA PEAD-RP100EA(2) PEAD-RP125EA PEAD-RP140EA

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-RP50EA PEAD-RP60EA PEAD-RP71EA PEAD-RP100EA(2) PEAD-RP125EA PEAD-RP140EA SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 005 SERVICE MANUAL Series PEAD R7C/RA Service ref. Models RP35EA() RP50EA RPEA RP7EA RP00EA() RP5EA RPEA NOTE: This manual describes only service data

More information

PKA-RP60KAL.TH PKA-RP71KAL.TH PKA-RP100KAL.TH

PKA-RP60KAL.TH PKA-RP71KAL.TH PKA-RP100KAL.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS SERVICE MANUAL May 2011 No. OCH452 REVISED EDITION-A Indoor unit [Model names] PKA-RP60KAL PKA-RP71KAL PKA-RP100KAL [Service Ref.] PKA-RP60KAL.TH

More information

SLZ-KF25VA.TH SLZ-KF35VA.TH SLZ-KF50VA.TH SLZ-KF60VA.TH

SLZ-KF25VA.TH SLZ-KF35VA.TH SLZ-KF50VA.TH SLZ-KF60VA.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL October 205 No. Indoor unit [Model Name] SLZ-KF25VA SLZ-KF35VA SLZ-KF50VA SLZ-KF60VA [Service Ref.] SLZ-KF25VA.TH SLZ-KF35VA.TH SLZ-KF50VA.TH

More information

PKA-RP35HAL PKA-RP50HAL

PKA-RP35HAL PKA-RP50HAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS March 2009 No. OCH453 SERVICE MANUAL Indoor unit [Model names] PKA-RP35HAL PKA-RP50HAL [Service Ref.] PKA-RP35HAL PKA-RP50HAL NOTE: This

More information

PKA-RP35HAL PKA-RP35HALR1 PKA-RP35HALR1-ER PKA-RP50HAL PKA-RP50HALR1 PKA-RP50HALR1-ER

PKA-RP35HAL PKA-RP35HALR1 PKA-RP35HALR1-ER PKA-RP50HAL PKA-RP50HALR1 PKA-RP50HALR1-ER SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS SERVICE MANUAL July 2014 No. OCH453 REVISED EDITION-A Indoor unit [Model Name] PKA-RP35HAL PKA-RP50HAL [Service Ref.] PKA-RP35HAL PKA-RP35HALR1

More information

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 2010 SERVICE MANUAL PEA-RP200GAQ PEA-RP250GAQ PEA-RP400GAQ PEA-RP500GAQ. [Model names] CONTENTS

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 2010 SERVICE MANUAL PEA-RP200GAQ PEA-RP250GAQ PEA-RP400GAQ PEA-RP500GAQ. [Model names] CONTENTS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 00 SERVICE MANUAL [Model names] PEA-RP00GAQ PEA-RP50GAQ PEA-RP400GAQ PEA-RP500GAQ This manual describes only service data of the indoor units. CONTENTS Indoor unit.

More information

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-SP100JA(L) PEAD-SP125JA(L) PEAD-SP140JA(L) Models PEAD-SP71JA(L) <indoor unit>

SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS PEAD-SP100JA(L) PEAD-SP125JA(L) PEAD-SP140JA(L) Models PEAD-SP71JA(L) <indoor unit> SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 4 SERVICE MANUAL Series PEAD R4A Models PEAD-SP7JA(L) PEAD-SPJA(L) PEAD-SP5JA(L) PEAD-SPJA(L) NOTE: This manual describes only service data of the indoor

More information

SEZ-KD25VAQ.TH SEZ-KD35VAQ.TH SEZ-KD50VAQ.TH SEZ-KD60VAQ.TH SEZ-KD71VAQ.TH

SEZ-KD25VAQ.TH SEZ-KD35VAQ.TH SEZ-KD50VAQ.TH SEZ-KD60VAQ.TH SEZ-KD71VAQ.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL December No.HWE0 REVISED EDITION-B Indoor unit [Model names] SEZ-KD25VAQ SEZ-KD35VAQ SEZ-KDVAQ SEZ-KDVAQ SEZ-KD71VAQ [Service Ref.] SEZ-KD25VAQ.TH

More information

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

TECHNICAL & SERVICE MANUAL. Ceiling Concealed STAND BY DEFROST CHECK CLOCK ON OFF NOT AVAILABLE FILTER CHECK MODE TEST RUN FUNCTION SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL Series SEZ Ceiling Concealed R40A.OC0 REVISED EDITION-A

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 12 TECHNICAL & SERVICE MANUAL Series SEZ Model name SEZ-KD25VA(L) SEZ-KD35VA(L) SEZ-KDVA(L) SEZ-KDVA(L) SEZ-KD71VA(L) INDOOR UNIT ON/OFF TEMP TEMP.

More information

SERVICE MANUAL. Series PEA SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS CONTENTS

SERVICE MANUAL. Series PEA SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS CONTENTS SPLIT-TYPE, HEAT PUMP AIR CDITIERS 0 SERVICE MANUAL Series PEA Model name PEA-RP00GAQ PEA-RP0GAQ PEA-RP00GAQ PEA-RP00GAQ This manual describes only service data of the indoor units. CTENTS

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL RESET SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. OC0 TECHNICAL & SERVICE MANUAL Series SLZ Ceiling Cassettes R0A Indoor unit [Model names] SLZ-A09AR SLZ-AAR SLZ-A8AR [Service Ref.] SLZ-A09AR.TH SLZ-AAR.TH

More information

PKA-M35HA PKA-M50HA PKA-M35HAL PKA-M50HAL SERVICE MANUAL R32/R410A. No. OCH660

PKA-M35HA PKA-M50HA PKA-M35HAL PKA-M50HAL SERVICE MANUAL R32/R410A. No. OCH660 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS March 2017 No. SERVICE MANUAL R32/R410A Indoor unit [Model Name] PKA-M35HA PKA-M50HA [Service Ref.] PKA-M35HA PKA-M50HA Notes: This manual

More information

PKFY-P15VBM-E PKFY-P20VBM-E PKFY-P20VBM-ER1 PKFY-P25VBM-E PKFY-P25VBM-ER1

PKFY-P15VBM-E PKFY-P20VBM-E PKFY-P20VBM-ER1 PKFY-P25VBM-E PKFY-P25VBM-ER1 SPLIT-TYPE, HEAT PUMP AIR CDITIERS November No. OCH REVISED EDITI-A TECHNICAL & SERVICE MANUAL RA R7C R Indoor unit [Model names] PKFY-PVBM-E PKFY-PVBM-E PKFY-PVBM-E [Service Ref.] PKFY-PVBM-E PKFY-PVBM-E

More information

SERVICE MANUAL PKA-M60KA.TH PKA-M71KA.TH PKA-M100KA.TH PKA-M60KAL.TH PKA-M71KAL.TH PKA-M100KAL.TH R32/R410A. No. OCH661.

SERVICE MANUAL PKA-M60KA.TH PKA-M71KA.TH PKA-M100KA.TH PKA-M60KAL.TH PKA-M71KAL.TH PKA-M100KAL.TH R32/R410A. No. OCH661. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS SERVICE MANUAL Indoor unit [Model Name] PKA-M60KA PKA-M7KA PKA-M00KA PKA-M60KAL PKA-M7KAL PKA-M00KAL [Service Ref.] R32/R40A PKA-M60KA.TH

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL No. OCH468 REVISED EDITI-A HFC utilized R4A June 2 [Model name] MXZ-8B48NA PAC-AKA5BC PAC-AKA3BC (Indispensable

More information

AA PLA-RP AA2 PEAD-RP EA PEAD-RP EA2 PEAD-RP GA PKA-RP GAL PKA-RP FAL PCA-RP GA PCA-RP HA PSA-RP GA

AA PLA-RP AA2 PEAD-RP EA PEAD-RP EA2 PEAD-RP GA PKA-RP GAL PKA-RP FAL PCA-RP GA PCA-RP HA PSA-RP GA SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL DATA BOOK [Model names] [Model names] PLA-RP AA PLA-RP AA PEAD-RP EA PEAD-RP EA PEAD-RP GA PKA-RP GAL PKA-RP FAL PCA-RP GA PCA-RP

More information

Ceiling Cassettes PLH-3AKH1.UK PLH-3AKH.UK PLH-4AKHS1.UK PLH-4AKHS.UK PLH-5AKHS1.UK PLH-5AKHS.UK PLH-6AKHS1.UK PLH-6AKHS.UK

Ceiling Cassettes PLH-3AKH1.UK PLH-3AKH.UK PLH-4AKHS1.UK PLH-4AKHS.UK PLH-5AKHS1.UK PLH-5AKHS.UK PLH-6AKHS1.UK PLH-6AKHS.UK T AVAILABLE C AMPM AMPM SPLIT-TYPE, HEAT PUM PAIR CDITIERS No. OC REVISED EDITI-A TECHNICAL & SERVICE MANUAL Series PLH Indoor unit [Model names] PLH-3AK PLH-3AKH PLH-AKS PLH-AKHS PLH-5AKS PLH-5AKHS PLH-6AKS

More information

Floor Standing PFFY-P20VKM-E PFFY-P20VKM-ER1 PFFY-P25VKM-E PFFY-P25VKM-ER1 PFFY-P32VKM-E PFFY-P32VKM-ER1 PFFY-P40VKM-E PFFY-P40VKM-ER1

Floor Standing PFFY-P20VKM-E PFFY-P20VKM-ER1 PFFY-P25VKM-E PFFY-P25VKM-ER1 PFFY-P32VKM-E PFFY-P32VKM-ER1 PFFY-P40VKM-E PFFY-P40VKM-ER1 SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL November 008 No. OC0 REVISED EDITI-A Series PFFY Indoor unit [Model names] PFFY-P0VKM-E PFFY-PVKM-E PFFY-PVKM-E PFFY-P0VKM-E Floor Standing

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS 004 TECHNICAL & SERVICE MANUAL R40A Outdoor unit [model names] PUHZ-RP.6VHA PUHZ-RPVHA PUHZ-RP.5VHA PUHZ-RP3VHA PUHZ-RP4VHA PUHZ-RP5VHA PUHZ-RP6VHA [Service Ref.] PUHZ-RP.6VHA

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS TECHNICAL & SERVICE MANUAL R07C Outdoor unit [model names] No.OC6 REVISED EDITION-B PUH-PVGAA PUH-P.6VGAA PUH-P.6YGAA PUH-PVGAA PUH-PYGAA

More information

Series PEAD SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS R32/R410A PEAD-SM100JA(L) PEAD-SM125JA(L) PEAD-SM140JA(L) Models PEAD-SM71JA(L)

Series PEAD SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS R32/R410A PEAD-SM100JA(L) PEAD-SM125JA(L) PEAD-SM140JA(L) Models PEAD-SM71JA(L) SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS 2018 SERVICE MANUAL Series PEAD R32/R4A Models PEAD-SM71JA(L) PEAD-SM0JA(L) PEAD-SM125JA(L) PEAD-SM1JA(L) NOTE: This manual describes only service data

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL RA December 22 No. OCH REVISED EDITI-C Indoor unit [Model names] PKFY-PVBM-E PKFY-P2VBM-E PKFY-P2VBM-E [Service Ref.] PKFY-PVBM-E PKFY-PVBM-ER2

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CITIERS TECHNICAL & SERVICE MANUAL January 00 No. OC REVISE EITI-A Indoor unit [Model names] PCH-AK PCH-.AK PCH-AK PCH-AK PCH-AK PCH-AK PCH-AKH PCH-.AKH PCH-AKH PCH-AKH PCH-AKH

More information

PKFY-P32VGM-E PKFY-P40VGM-E PKFY-P50VGM-E

PKFY-P32VGM-E PKFY-P40VGM-E PKFY-P50VGM-E SPLIT-TYPE, HEAT PUMP AIR CDITIERS July 00 No. OC0 REVISED EDITI-A TECHNICAL & SERVICE MANUAL Series PKFY Wall Mounted R0A R0C R [Model names] PKFY-PVGM-E PKFY-P0VGM-E PKFY-P0VGM-E [Service

More information

TECHNICAL & SERVICE MANUAL. Wall Mounted. Series PKFY PKFY-P20VAM-A PKFY-P25VAM-A R407C R22 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No.

TECHNICAL & SERVICE MANUAL. Wall Mounted. Series PKFY PKFY-P20VAM-A PKFY-P25VAM-A R407C R22 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. SPLIT-TYPE, HEAT PUMP AIR CDITIERS 00 No. OC TECHNICAL & SERVICE MANUAL Series PKFY Wall Mounted R07C R Indoor unit [Model names] PKFY-P0VAM-A [Service Ref.] PKFY-P0VAM-A CTENTS INDOOR UNIT. SAFETY PRECAUTI.

More information

PMFY-P-VBM-E. Ceiling cassette (1-way flow type) R410A Data G8 1. SPECIFICATIONS EXTERNAL DIMENSIONS CENTER OF GRAVITY 1-100

PMFY-P-VBM-E. Ceiling cassette (1-way flow type) R410A Data G8 1. SPECIFICATIONS EXTERNAL DIMENSIONS CENTER OF GRAVITY 1-100 Ceiling cassette (-way flow type) RA Data G8 -P-VBM-E. SPECIFICATIONS - 98. EXTERNAL DIMENSIONS - 99 3. CENTER OF GRAVITY -. ELECTRICAL WIRING DIAGRAMS -. SOUND LEVELS -. Sound levels -. NC curve 6. TEMPERATURE/AIRFLOW

More information

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E

SERVICE MANUAL INDOOR UNIT MFZ-KA25VA - MFZ-KA50VA - MFZ-KA35VA - No. OB409. Models. Revision E: SPLIT-TYPE AIR CONDITIONERS REVISED EDITION-E SPLIT-TYPE AIR CONDITIONERS Revision E: MFZ-KA5VA- E5, MFZ-KA35VA- E5 and MFZ-KA50VA- E5 have been added. Please void OB409 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OB409 REVISED EDITION-E Models

More information

SERVICE TECHNICAL GUIDE

SERVICE TECHNICAL GUIDE SPLIT-TYPE, HEAT PUMP AIR CDITIERS SERVICE TECHNICAL GUIDE [Model names] PLA-RP AA PKA-RP GAL PKA-RP FAL PCA-RP GA PEA-RP EA PEAD-RP EA PEAD-RP GA [Model names] PUHZ-RP VHA

More information

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models

SERVICE MANUAL MLZ-KA25VA - MLZ-KA35VA - MLZ-KA50VA - E1 INDOOR UNIT. No. OBH483. Ceiling cassette type Models CEILING CASSETTE TYPE, HEAT PUMP AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. OBH483 Ceiling cassette type Models E1 MLZ-KA25VA - E1 MLZ-KA35VA - MLZ-KA50VA - E1 Outdoor unit service manual MXZ-A VA Series

More information

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No.

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 MSZ-GE60VA - E1 MSZ-GE71VA - E1 INDOOR UNIT. No. SPLIT-TYPE AIR CONDITIONERS Revision E: Detail of the indoor fan speed control in COOL or DRY operation has been added (9-1.3, 9-2.3). Please void OBH515 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL.

More information

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1

SERVICE MANUAL MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA - U1 MSZ-GL18NA - U1 MSZ-GL24NA - U1 Revision B: 3. SPECIFICATION has been corrected. Please void OBH732 REVISED EDITION-A. INDOOR UNIT SERVICE MANUAL. OBH732 REVISED EDITION-B Models MSZ-GL06NA - U1 MSZ-GL09NA - U1 MSZ-GL12NA - U1 MSZ-GL15NA

More information

PUHZ-SHW140YHA PUHZ-SHW230YKA

PUHZ-SHW140YHA PUHZ-SHW230YKA 1 Specifications Model Name PUHZ-SHW1YHA PUHZ-SHWYKA Power supply (phase, cycle, voltage) 3φ, 0V, Hz 3φ, 0V, Hz Max. current A 13.0 6.0 Breaker size A 16 3 Outer casing Galvanized plate Galvanized plate

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models SPLIT-TYPE AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. OBH529 Models MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 service manual MU-GA VB Series (OB386) MUH-GA VB Series

More information

PLFY-P15VCM-E3.TH PLFY-P20VCM-E3.TH PLFY-P25VCM-E3.TH PLFY-P32VCM-E3.TH PLFY-P40VCM-E3.TH

PLFY-P15VCM-E3.TH PLFY-P20VCM-E3.TH PLFY-P25VCM-E3.TH PLFY-P32VCM-E3.TH PLFY-P40VCM-E3.TH SPLIT-TYPE, HEAT PUMP AIR CDITIERS TECHNICAL & SERVICE MANUAL June 04 No. Indoor unit [Model Name] PLFY-PVCM-E PLFY-P0VCM-E PLFY-PVCM-E PLFY-PVCM-E PLFY-P40VCM-E R40A [Service Ref.] PLFY-PVCM-E.TH PLFY-P0VCM-E.TH

More information

SERVICE MANUAL MUZ-GB50VA - MUZ-GB50VA - E2 OUTDOOR UNIT. No. OB455 REVISED EDITION-D. Wireless type Models HFC

SERVICE MANUAL MUZ-GB50VA - MUZ-GB50VA - E2 OUTDOOR UNIT. No. OB455 REVISED EDITION-D. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision D: RoHS PARTS LIST has been changed. Please void OB455 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A. OB455 REVISED EDITION-D Wireless

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision A: MSZ-SF25/35/42/50VE- E2 and MSZ-SF25/35/ 42/50VE- EN2 have been added. Please void OBH600. INDOOR UNIT SERVICE MANUAL. OBH600 REVISED EDITION-A Models MSZ-SF25VE

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL October 202 No. OCH446 REVISED EDITION-E HFC utilized R40A [Model name] PUMY-P00VHMB PUMY-P25VHMB PUMY-P40VHMB PUMY-P00VHMB-BS

More information

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-D30NA / - MUZ-D36NA / - MUY-D30NA / - MUY-D36NA / - OUTDOOR UNIT. No. OBH502. Models HFC. Revision E: REVISED EDITION-E R410A Revision E: Capacity corrections have been corrected [7-1. 2), 3)]. OBH502 REVISED EDITION-D is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 REVISED EDITION-E Models MUZ-D30NA / - 1 / -

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

SERVICE MANUAL MSC-A07YV - (WH) MSC-A09YV - (WH) MSC-A12YV - (WH) HFC. Wireless type Models

SERVICE MANUAL MSC-A07YV - (WH) MSC-A09YV - (WH) MSC-A12YV - (WH) HFC. Wireless type Models SPLIT-TYPE, AIR CONDITIONERS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MSC-A07YV - (WH) E MSC-A09YV - (WH) E MSC-AYV - (WH) HFC utilized R40A. OB39 CONTENTS Indication

More information

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467. SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-HC35VA- E2 and MUZ-HC35VAB- E2 have been added. Please void OBH467 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH467 REVISED EDITION-B

More information

Air-Conditioners PKA-A HA/PKA-A HAL PCA-A KA. Indoor unit OPERATION MANUAL. English

Air-Conditioners PKA-A HA/PKA-A HAL PCA-A KA. Indoor unit OPERATION MANUAL. English Air-Conditioners Indoor unit PKA-A HA/PKA-A HAL PCA-A KA OPERATION MANUAL FOR USER For safe and correct use, please read this operation manual thoroughly before operating the air-conditioner unit. English

More information

SERVICE MANUAL MFZ-KA25VA - MFZ-KA35VA - MFZ-KA35VA - E1. Wireless type Models FLOOR-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MFZ-KA25VA - MFZ-KA35VA - MFZ-KA35VA - E1. Wireless type Models FLOOR-TYPE, HEAT PUMP AIR CONDITIONERS. No. FLOOR-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models MFZ-KAVA - MFZ-KA3VA - E E. OB409 MFZ-KA0VA - E Indication of model name MFZ-KAVA - E MFZ-KA3VA - E MFZ-KA0VA - E NOTE: This service

More information

SERVICE MANUAL. R410A Outdoor unit [model names] SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS April 2007

SERVICE MANUAL. R410A Outdoor unit [model names] SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS April 2007 SPLIT-TYPE, HEAT PUMP AIR CDITIERS SPLIT-TYPE, AIR CDITIERS April 007 No.OC379 REVISED EDITI-C SERVICE MANUAL R0A Outdoor unit [model names] PU-P7VHA PU-P7YHA PU-P00VHA PU-P00YHA PU-P5YHA PU-P0YHA PUH-P7VHA

More information

SERVICE MANUAL R410A. June 2014 AIR TO WATER HEAT PUMP. No. OCH562. Outdoor unit [Model Name] [Service Ref.] PUHZ-W112VHA PUHZ-W112VHA-BS CONTENTS

SERVICE MANUAL R410A. June 2014 AIR TO WATER HEAT PUMP. No. OCH562. Outdoor unit [Model Name] [Service Ref.] PUHZ-W112VHA PUHZ-W112VHA-BS CONTENTS AIR TO WATER HEAT PUMP June 204 No. SERVICE MANUAL R40A Outdoor unit [Model Name] PUHZ-W2VHA Salt proof model PUHZ-W2VHA-BS [Service Ref.] PUHZ-W2VHA PUHZ-W2VHA-BS Note: This manual describes service data

More information

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy SPLIT-TYPE AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. OBH589 Models MSZ-EF22VEW - MSZ-EF22VEW - E1 MSZ-EF25VEW - E1 MSZ-EF22VEB - E1 MSZ-EF35VEW - E1 MSZ-EF22VES E1 - MSZ-EF42VEW - E1 MSZ-EF25VEW - E1

More information

SERVICE MANUAL PUHZ-ZRP250YKA3.UK R410A. No. OCH680. November 2017 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. Outdoor unit [Model Name]

SERVICE MANUAL PUHZ-ZRP250YKA3.UK R410A. No. OCH680. November 2017 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. Outdoor unit [Model Name] SPLIT-TYPE, HEAT PUMP AIR CDITIERS SERVICE MANUAL R40A November 07 No. Outdoor unit [Model Name] PUHZ-ZRP00YKA3 PUHZ-ZRP50YKA3 [Service Ref.] PUHZ-ZRP00YKA3.UK PUHZ-ZRP50YKA3.UK Note: This manual describes

More information

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A

SERVICE MANUAL MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA OUTDOOR UNIT. No. OBH502. Wireless type Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH502 Wireless type Models MUZ-D30NA MUZ-D30NA- U1 MUZ-D36NA MUZ-D36NA- U1 MUY-D30NA MUY-D36NA Indoor unit service manual MSZ-D NA Series (OBH501) MSY-D

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL OUTDOOR UNIT. No. OBH530. Models MU-GE50VB- E1 MUH-GE50VB- E1 HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH530 Models MU-GE50VB- E1 - E1 Indoor unit service manual MS/MSH-GE VB Series (OBH529) CONTENTS 1. TECHNICAL CHANGES 2 2. PART

More information

SERVICE MANUAL MSC-GA20VB - (WH) MSC-GA25VB - (WH) MSC-GA35VB - (WH) Wireless type Models

SERVICE MANUAL MSC-GA20VB - (WH) MSC-GA25VB - (WH) MSC-GA35VB - (WH) Wireless type Models SPLIT-TYPE, AIR CONDITIONERS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MSC-GA0VB - (WH) E MSC-GAVB - (WH) E MSC-GAVB - (WH). OB8 Indication of model name MSC-GA0VB -

More information

PEFY-P20VMS-E, PEFY-P40VMS-E PEFY-P25VMS-E, PEFY-P50VMS-E PEFY-P32VMS-E, PEFY-P63VMS-E

PEFY-P20VMS-E, PEFY-P40VMS-E PEFY-P25VMS-E, PEFY-P50VMS-E PEFY-P32VMS-E, PEFY-P63VMS-E 2006 Air-Conditioners TECHNICAL & SERVICE MANUAL Models PEFY-P20VMS-E, PEFY-P40VMS-E PEFY-P25VMS-E, PEFY-P50VMS-E PEFY-P2VMS-E, PEFY-P6VMS-E For use with R40A, R407C, & R22 Safety Precautions Read before

More information

Air-Conditioners. Indoor unit PSA-RP KA OPERATION MANUAL. English

Air-Conditioners. Indoor unit PSA-RP KA OPERATION MANUAL. English Air-Conditioners Indoor unit PSA-RP KA OPERATION MANUAL FOR USER For safe and correct use, please read this operation manual thoroughly before operating the air-conditioner unit. English Contents 1. Safety

More information

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1 OUTDOOR UNIT. No. OB381. Models HFC

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1 OUTDOOR UNIT. No. OB381. Models HFC FLOOR AND CEILIN TYPE AIR CONDITIONERS Revision B: The fan guard for MUCFH-A 60VBhas been changed. Please void OB8 REVSED EDITION-A. E OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A. OB8 REVISED EDITION-B

More information

TECHNICAL & SERVICE MANUAL. Ceiling Cassettes

TECHNICAL & SERVICE MANUAL. Ceiling Cassettes RESET RESET SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS TECHNICAL & SERVICE MANUAL Series SLH/SL Indoor unit [Model names] SLH-AR SLH-.6AR SLH-AR SL-AR SL-.6AR SL-AR Ceiling Cassettes

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07KGTA ASYG09KGTA ASYG12KGTA ASYG14KGTA OUTDOOR AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA DR_AS049EF_02 2017.10.11 Notices: Product

More information

Contents. 1. Safety Precautions

Contents. 1. Safety Precautions Contents. Safety Precautions....................................... Parts Names........................................... 3 3. Screen Confi guration.................................... 6 4. Setting the

More information

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE INDOOR UNIT. No. OBH623. Models SPLIT-TYPE AIR CONDITIONERS

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE INDOOR UNIT. No. OBH623. Models SPLIT-TYPE AIR CONDITIONERS SPLIT-TYPE AIR CONDITIONERS INDOOR UNIT SERVICE MANUAL. Models MSZ-FH25VE MSZ-FH35VE - E1 - E1 Outdoor unit service manual MUZ-FH VEHZ Series (OBH625) MUZ-FH VE Series MXZ-D VA Series CONTENTS 1. TECHNICAL

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL For Extra Cold Climate Area INDOOR ASU18RLF ASU24RLF OUTDOOR AOU18RLXFWH AOU24RLXFWH DR_AS014EF_04 2017.03.10 Notices: Product specifications

More information

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Models HFC

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Models HFC Revision G: Errors in TROUBLESHOOTING have been corrected. Please void OB455 REVISED EDITION-F. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB455 REVISED EDITION-G Models MUZ-GB50VA - E1 MUZ-GB50VA

More information

SERVICE MANUAL R410A PUHZ-SP100VHA.UK PUHZ-SP125VHA.UK PUHZ-SP125VHA PUHZ-SP140VHA.UK PUHZ-SP140VHA PUHZ-SP100YHA.UK PUHZ-SP100YHA PUHZ-SP125YHA.

SERVICE MANUAL R410A PUHZ-SP100VHA.UK PUHZ-SP125VHA.UK PUHZ-SP125VHA PUHZ-SP140VHA.UK PUHZ-SP140VHA PUHZ-SP100YHA.UK PUHZ-SP100YHA PUHZ-SP125YHA. SPLIT-TYPE, HEAT PUMP AIR CDITIERS SERVICE MANUAL R40A January 05 No. OCH566 REVISED EDITI-A Outdoor unit [Model Name] PUHZ-SP00VHA PUHZ-SP5VHA PUHZ-SP40VHA PUHZ-SP00YHA PUHZ-SP5YHA PUHZ-SP40YHA [Service

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG07LMCE ASYG09LMCE ASYG12LMCE ASYG14LMCE OUTDOOR AOYG07LMCE AOYG09LMCE AOYG12LMCE AOYG14LMCE DR_AS037EF_01 2016.12.05 Notices: Product

More information

SERVICE MANUAL MLZ-KP25VF MLZ-KP35VF MLZ-KP50VF INDOOR UNIT. No. OBH801. Models

SERVICE MANUAL MLZ-KP25VF MLZ-KP35VF MLZ-KP50VF INDOOR UNIT. No. OBH801. Models INDOOR UNIT SERVICE MANUAL. Models MLZ-KP25VF MLZ-KP35VF MLZ-KP50VF - E1, ER1 - E1, ER1 - E1, ER1 Outdoor unit service manual MXZ-D VA Series (OBH626) MXZ-E VA Series (OBH723) MXZ-F VF Series (OBH790)

More information

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE MSZ-FH25VE2 MSZ-FH35VE2 MSZ-FH50VE2 INDOOR UNIT. No. OBH623. Models

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE MSZ-FH25VE2 MSZ-FH35VE2 MSZ-FH50VE2 INDOOR UNIT. No. OBH623. Models Revision D: MSZ-FH25VE2- E1, ER1, MSZ- FH35VE2- E1, ER1 and MSZ- FH50VE2- E1, ER1 have been added. Please void OBH623 REVISED EDITION-C. INDOOR UNIT SERVICE MANUAL. OBH623 REVISED EDITION-D Models MSZ-FH25VE

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASYG18KLCA ASYG24KLCA OUTDOOR AOYG18KLTA AOYG24KLTA DR_AS069EF_01 2018.03.16 Notices: Product specifications and design are subject to

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE, HEAT PUMP AIR CDITIERS December No. OCH7 REVISED EDITI-B TECHNICAL & SERVICE MANUAL RA R7C R Indoor unit [Model names] PKFY-PVKM-E PKFY-PVKM-E [Service Ref.] PKFY-PVKM-E.TH PKFY-PVKM-ER.TH

More information

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA

More information

SERVICE MANUAL PUHZ-RP35VHA PUHZ-RP50VHA PUHZ-RP60VHA PUHZ-RP71VHA PUHZ-RP100VHA PUHZ-RP125VHA PUHZ-RP140VHA PUHZ-RP100YHA PUHZ-RP125YHA PUHZ-RP140YHA

SERVICE MANUAL PUHZ-RP35VHA PUHZ-RP50VHA PUHZ-RP60VHA PUHZ-RP71VHA PUHZ-RP100VHA PUHZ-RP125VHA PUHZ-RP140VHA PUHZ-RP100YHA PUHZ-RP125YHA PUHZ-RP140YHA SPLIT-TYPE, HEAT PUMP AIR CDITIERS June 005 No.OC334 SERVICE MANUAL R40A Outdoor unit [model names] PUHZ-RP35VHA PUHZ-RP50VHA PUHZ-RP60VHA PUHZ-RP7VHA PUHZ-RP00VHA PUHZ-RP5VHA PUHZ-RP40VHA PUHZ-RP00YHA

More information

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT-TYPE,HEAT PUMP AIR CDITIERS 1997 No. OC135 TECHNICAL & SERVICE MANUAL Series PCH Ceiling Suspended Indoor unit [Models names] [Service Ref.] PCH-2GKHA PCH-2.5GKHA PCH-3GKHA PCH-4GKHSA PCH-5GKHSA

More information

SERVICE MANUAL INDOOR UNIT. No. OBH788

SERVICE MANUAL INDOOR UNIT. No. OBH788 INDOOR UNIT SERVICE MANUAL. Models MSZ-AP25VG - E1, EN1 MSZ-AP35VG - E1, EN1 MSZ-AP42VG - E1, EN1 MSZ-AP50VG - E1, EN1 MSZ-AP25VGK - E1, EN1 MSZ-AP35VGK - E1, EN1 MSZ-AP42VGK - E1, EN1 MSZ-AP50VGK - E1,

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF97R5IAA CAF98MR5IAA CAF127R5IAA CAF128MR5IAA CAF187R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. CAF97R5IAA CAF127R5IAA CAF187R5IAA CAF98MR5IAA CAF128MR5IAA

More information

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

SERVICE MANUAL MUH-GA50VB- MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1 OUTDOOR UNIT. No. OB368 REVISED EDITION-B. Wireless type Models HFC.

SERVICE MANUAL MUH-GA50VB- MUH-GA50VB - MUH-GA60VB - MUH-GA80VB - E1 OUTDOOR UNIT. No. OB368 REVISED EDITION-B. Wireless type Models HFC. Revision:B - E has been added. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Please void OB68 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A. OB68 REVISED EDITION-B Wireless type Models E -

More information

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G09LTCN AO*G12LTCN AO*G14LTCN

R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G09LTCN AO*G12LTCN AO*G14LTCN SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS*G09LTCB AS*GLTCB AS*G4LTCB AO*G09LTCN AO*GLTCN AO*G4LTCN R40A CONTENTS. DESCRIPTION OF EACH

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOU9RLS2H AOU12RLS2H AOU15RLS2H

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AOU9RLS2H AOU12RLS2H AOU15RLS2H SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU9RLS ASURLS ASU5RLS AOU9RLSH AOURLSH AOU5RLSH R40A CONTENTS. DESCRIPTION OF EACH CONTROL

More information

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A

SPLIT TYPE ROOM AIR CONDITIONER. WALL MOUNTEDtype INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW1 AOU12RLFW1 ASU 9RLF1 ASU12RLF1 R410A SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF AOU 9RLFW AOURLFW R40A CONTENTS. DESCRIPTION OF EACH CONTROL OPERATION. COOLING

More information

MUH-24RV - MSH-30RV -

MUH-24RV - MSH-30RV - SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models Refer to the Service Manual OB85 REVISED EDITION C when MSH-8RV- E is connected with MXZ-NV- E or MXZ-NV- E as multi system units.

More information

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Wireless type Models HFC. Revision E: REVISED EDITION-E R410A

SERVICE MANUAL MUZ-GB50VA - E1 MUZ-GB50VA - E2 MUZ-GB50VA - E3 OUTDOOR UNIT. No. OB455. Wireless type Models HFC. Revision E: REVISED EDITION-E R410A Revision E: MUZ-GB50VA- E3 has been added. Please void OB455 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB455 REVISED EDITION-E Wireless type Models MUZ-GB50VA - E1 MUZ-GB50VA -

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AO* R09LECN AO* R12LECN

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AO* R09LECN AO* R12LECN SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS* A09LEC AS* A12LEC AO* R09LECN AO* R12LECN R410A CONTENTS 1. DESCRIPTION OF EACH CONTROL

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH

SERVICE MANUAL OUTDOOR UNIT MUZ-FH06NAH MUZ-FH09NAH MUZ-FH06NA MUZ-FH09NA MUZ-FH09NA - 1 MUZ-FH09NAH - 1 MUZ-FH12NA MUZ-FH12NAH Revision D: Capacity corrections have been corrected [7-1. 2), 3)]. OBH684 REVISED EDITION-C is void. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH684 REVISED EDITION-D Models MUZ-FH06NA MUZ-FH09NA

More information

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1. Wireless type Models HFC FLOOR AND CEILING TYPE AIR CONDITIONERS. No.

SERVICE MANUAL MUCFH-GA35VB - MUCFH-GA50VB - MUCFH-GA60VB - E1. Wireless type Models HFC FLOOR AND CEILING TYPE AIR CONDITIONERS. No. FLOOR AND CEILING TYPE AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MUCFH-GA35VB - E MUCFH-GA50VB - MUCFH-GA60VB - E HFC utilized R40A. OB38 CONTENTS Indication of model name MUCFH-GA50VB - E.

More information

SERVICE MANUAL R410A SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. December No.OCH415 REVISED EDITION-F

SERVICE MANUAL R410A SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. December No.OCH415 REVISED EDITION-F SPLIT-TYPE, HEAT PUMP AIR CDITIERS SERVICE MANUAL Outdoor unit [Model names] PUHZ-P00VHA PUHZ-P5VHA PUHZ-P40VHA PUHZ-P00VHA3 PUHZ-P5VHA3 PUHZ-P40VHA3 PUHZ-P00VHA4 PUHZ-P00YHA PUHZ-P00YHA PUHZ-P5YHA PUHZ-P40YHA

More information

KSGD-01W/S SEMI CONDUCTOR STAND ALONE REFRIGERANT LEAK DETECTOR. Instructions for :- KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector

KSGD-01W/S SEMI CONDUCTOR STAND ALONE REFRIGERANT LEAK DETECTOR. Instructions for :- KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector Issue 1 KSGD-01W/S SEMI CONDUCTOR STAND ALONE REFRIGERANT LEAK DETECTOR Installation Manual Instructions for :- For safe and correct use please read the installation manuals supplied with the equipment.

More information

TECHNICAL & SERVICE MANUAL SUZ-SA71VA.TH. R410A Outdoor unit SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. May 2014 HFC. No.OCH561 R410A CONTENTS

TECHNICAL & SERVICE MANUAL SUZ-SA71VA.TH. R410A Outdoor unit SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. May 2014 HFC. No.OCH561 R410A CONTENTS SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS May 2014. TECHNICAL & SERVICE MANUAL R410A Outdoor unit [Model Name] SUZ-SA71VA [Service Ref.] HFC utilized R410A te: This service manual describes technical data

More information

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC

SERVICE MANUAL. No. OBH747 REVISED EDITION-A. Models HFC Revision A: MUZ-HM09/12NA- U8, MUZ-HM09/12NA2- U8, MUZ-HM15/18NA- U1, MUZ-HM15/18NA2- U1 and MUZ-HM24NA2- U1 have been added. Please void OBH747. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A.

More information

Air Conditioner CONTENTS

Air Conditioner CONTENTS ORDER NO. MAC0509068C2 Air Conditioner CS-F24DD1E5 CU-B24DBE5 CS-F28DD1E5 CU-B28DBE5 CS-F28DD1E5 CU-B28DBE8 CS-F34DD1E5 CU-B34DBE5 CS-F34DD1E5 CU-B34DBE8 CS-F43DD1E5 CU-B43DBE8 CS-F50DD1E5 CU-B50DBE8 CONTENTS

More information

SERVICE MANUAL MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA INDOOR UNIT. No. OBH501. Wireless type Models

SERVICE MANUAL MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA INDOOR UNIT. No. OBH501. Wireless type Models INDOOR UNIT SERVICE MANUAL. OBH501 Wireless type Models MSZ-D30NA MSZ-D36NA MSY-D30NA MSY-D36NA CONTENTS Outdoor unit service manual MUZ-D NA Series (OBH502) MUY-D NA Series (OBH502) 1. TECHNICAL CHANGES

More information

MSZ-GE06NA- 8, 9 MSZ-GE09NA- 8, 9 MSZ-GE12NA- 8, 9 MSZ-GE15NA- 8, 9 MSZ-GE18NA- 8, 9

MSZ-GE06NA- 8, 9 MSZ-GE09NA- 8, 9 MSZ-GE12NA- 8, 9 MSZ-GE15NA- 8, 9 MSZ-GE18NA- 8, 9 SPLIT-TYPE AIR CONDITIONERS Revision D: MSZ-GE06/09/12/15/18NA- 9 and MSY- GE09/12/15/18NA- 9 have been added. Please void OBH548 REVISED EDITION-C INDOOR UNIT SERVICE MANUAL. OBH548 REVISED EDITION-D

More information

SUZ-SA71VA3.TH SUZ-SA100VA2.TH

SUZ-SA71VA3.TH SUZ-SA100VA2.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS TECHNICAL & SERVICE MANUAL R410A Outdoor unit [Model Name] SUZ-SA71VA3 SUZ-SA100VA2 [Service Ref.] SUZ-SA71VA3.TH SUZ-SA100VA2.TH January 2018. HFC utilized R410A

More information

GUG-01SL-E GUG-02SL-E GUG-03SL-E

GUG-01SL-E GUG-02SL-E GUG-03SL-E 1604876HE5501 DIRECT EXPANSION COIL UNIT FOR LOSSNAY MODELS: GUG-01SL-E GUG-02SL-E GUG-03SL-E Installation Instructions DIRECT EXPANSION COIL UNIT FOR LOSSNAY MODELS: GUG-01SL-E GUG-02SL-E GUG-03SL-E Installation

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G24LFL AO*G24LFCC AO*G30LFT

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit AO*G24LFL AO*G24LFCC AO*G30LFT SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit AS*G4LFCA AS*G4LFCC AS*G0LFCA AO*G4LFL AO*G4LFCC AO*G0LFT R40A CONTENTS. DESCRIPTION OF EACH

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC Revision E: MUZ-FH25VE- E4, ER4, ET3, MUZ- FH35VE- E3, ER3, ET3 and MUZ- FH50VE- E2, ER2, ET2 have been added. Please void OBH624 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624

More information

SERVICE MANUAL MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA INDOOR UNIT. No. OBH746 REVISED EDITION-B. Models

SERVICE MANUAL MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA INDOOR UNIT. No. OBH746 REVISED EDITION-B. Models Revision B: 3-1. OPERATING RANGE has been modified. Please void OBH746 REVISED EDITION-A. INDOOR UNIT SERVICE MANUAL. OBH746 REVISED EDITION-B Models MSZ-HM09NA MSZ-HM12NA MSZ-HM15NA MSZ-HM18NA MSZ-HM24NA

More information

SERVICE MANUAL MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBH621 REVISED EDITION-A. Models

SERVICE MANUAL MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBH621 REVISED EDITION-A. Models SPLIT-TYPE AIR CONDITIONERS Revision A: MS-GF50VA- E1, MS-GF60VA- E1 and MS-GF80VA- E1 have been added. Please void OBH621. INDOOR UNIT SERVICE MANUAL. OBH621 REVISED EDITION-A Models MS-GF20VA MS-GF25VA

More information

SERVICE MANUAL MUH-A18WV - MUH-A24WV - MUH-A30WV - E1. Wireless type Models HFC

SERVICE MANUAL MUH-A18WV - MUH-A24WV - MUH-A30WV - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision A: Resistance of LEV (Expansion valve) has been modified. Power input and others have been added to SPECIFICATION. Method of check of R.V. coil has been

More information

SERVICE MANUAL MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 INDOOR UNIT. No. OBH750. Models

SERVICE MANUAL MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 INDOOR UNIT. No. OBH750. Models INDOOR UNIT SERVICE MANUAL. Models MSZ-DM25VA - E1, ER1 MSZ-DM35VA - E1, ER1 Outdoor unit service manual MUZ-DM VA Series (OBH751) MXZ-DM VA Series (OBH739) MSZ-DM25VA MSZ-DM35VA CONTENTS 1. TECHNICAL

More information

SERVICE MANUAL MSZ-HC25VA - E1 MSZ-HC35VA - E1 MSZ-HC35VA - E2 MSZ-HC35VAB - E1 MSZ-HC35VAB - E2 INDOOR UNIT. No. OBH466. Models

SERVICE MANUAL MSZ-HC25VA - E1 MSZ-HC35VA - E1 MSZ-HC35VA - E2 MSZ-HC35VAB - E1 MSZ-HC35VAB - E2 INDOOR UNIT. No. OBH466. Models SPLIT-TYPE AIR CONDITIONERS Revision B: MSZ-HC35VA- E2 and MSZ-HC35VAB- E2 have been added. Please void OBH466 REVISED EDITION-A. INDOOR UNIT SERVICE MANUAL. OBH466 REVISED EDITION-B Models MSZ-HC25VA

More information