Installation Instruction

Size: px
Start display at page:

Download "Installation Instruction"

Transcription

1 Installation Instruction CTS 600 by Nilan VPM 120 VPM 240 VPM 360 VPM 480 VPM 560 Version: 5.02,

2 Table of contents Table of contents... 2 Figures... 2 General information before installation... 3 Electrical installation... 4 Setting up VPM... 5 Condensation outlet/water lock... 6 Heating element, water (option)... 7 Guide to performance data, water heating element... 8 Heating element, electric (option) Guide to performance data for electric heating element Setting up the CTS 600 control system Activating service menu Heating element Air exchange Defroster Temp. control Inlet control Room control Restart Reset Manual Guide to unit dimensions Accessories/spare parts Figures Figure 1: CTS 600 control panel... 4 Figure 2: Setting up the unit... 5 Figure 3: Installing water lock... 6 Figure 4: Recommended water circulation system installation... 7 Figure 5: CTS 600 control panel Figure 6: Main points of service menu Figure 7: "Heating element" menu Figure 8: "Air exchange" menu Figure 9: "Defrost" menu Figure 10: "Temp. control" menu Figure 11: "Inlet control" menu Figure 12: "Room control" menu Figure 13: "Restart" menu Figure 14: "Reset" menu Figure 15: "Manual" menu Figure 16: Guide to unit dimensions... 22

3 General information before installation Check that the following documents have been supplied with the unit: - Installation Guide (this document) - CTS 600 User Guide - Wiring diagram If you have any questions concerning installation after reading the guide, please contact your nearest Nilan dealer via The unit is designed for installation of supplementary heating elements (electric or water) for additional heating of inlet air. The unit is supplied as standard with filter classes F5 (EU5) for exhaust and F7 (EU7) for inlet air. The unit is operated by a CTS 600 control system, featuring a wide range of functions, e.g. menucontrolled operation, weekly programme, filter monitor with timer, adjustment of fan speed etc. (CTS 600 is described in a separate user guide supplied with the system). For spare parts and other accessories, see page 23. All rights reserved Page 3 of 24

4 Electrical installation Electrical installation/power supply (including safety switch) must be installed by an authorised electrician. Connect the unit according to the wiring diagram supplied. Each ventilation part must be connected to mains electricity before the unit can be started. The unit is supplied with a 1m test cable for the CTS 600 panel. The panel is connected to the CTS 600 control system in the unit by cable type 2 x 2 x 0.25 mm2 twisted pair (max. length 50 m). The CTS 600 panel must be placed in a dry, frost-free place. The integrated sensor prevents further cooling of the building in the event of breakdown of the primary heating supply, by stopping the ventilation unit if the panel sensor goes below its set value. (factory set at 10 C, can be set between 1 C and 20 C). Figure 1: CTS 600 control panel If an electric or water heating element is fitted in the unit, the regulation valve and circulation pump must be connected according to the wiring diagrams supplied. All rights reserved Page 4 of 24

5 Setting up VPM During set up, future service and maintenance should be taken into account. We recommend a minimum gap in front of/behind the unit according to N/M, O/P - measurements (see Figure 16Figure 16, page 22). The individual nozzles are labelled to simplify setting up. Please note the attached labels. The nozzles and duct system are connected by flexible pipes (flex-pipes, sound-insulated flex-pipes or other type). A non-return damper should be fitted to prevent condensation, frost and heat loss. Dampers can be controlled via the CTS 600 control system. The unit must be installed level for the sake of the condensation outlet. The condensation outlet requires clearance of min. 120 mm under the drain nozzle (see Figure 3, page 6). No additional insulation is required, as the unit is supplied with 50 mm of insulation as standard. If installed outdoors, the unit must be covered (above its top at the least) to prevent water getting in. Although the unit generates practically no noise or vibration, measures should be taken to prevent vibration radiating into the building. To separate the unit from the surface it stands on, we recommend placing it on vibration dampers. Top cover for outdoor installation. Toplåg for udvendig opstilling (Accessories) (tilbehør) Vibration absorber. Vibrationsdæmpere (Accessories) (tilbehør) Figure 2: Setting up the unit All rights reserved Page 5 of 24

6 Condensation outlet/water lock VPM models are supplied with a 20 mm condensation outlet (PVC, GF fittings). The drain is located under the discharge air nozzle. The unit is supplied with a fitting in front of the drain for protection during transportation. Remove the fitting before fitting the water lock. A water lock is required connected to the condensation outlet. A pipe with a consistent fall of at least 1 cm per metre must connect the condensation nozzle to the nearest drain. Protect the pipe from frost. It may be necessary to fit a heating cable to the condensation outlet to prevent icing, running from the unit to the house climate screen. The electrician is responsible for protecting the condensation outlet from frost. There can be underpressure of up to 500 Pa (= 50 mm water column) in the drain during operation. The height difference in the water lock must therefore be minimum 50 mm. The first bend in the water lock must be at least double the length to ensure flow of condensate water. The condensation outlet must be airtight from the unit to the water lock to ensure unobstructed flow of condensate water away from the unit. If the condensation outlet is not airtight, air will be drawn in and the water will not flow away from the unit. The water lock can dry out and prevent water from draining from the condensation tray. It should therefore be checked regularly, and topped up with water as required. Filling the water in the lock above the minimum requirement will reduce the need for topping up. Ø20mm drain VPM min. 50mm. min. 78mm min. 50mm. Figure 3: Installing water lock Once the water lock is installed, test its function as follows (the unit must be connected to the duct system, and covers in place): Fill the condensation tray with water. Start the unit at highest fan speed with the doors closed. Allow the unit to run for a few minutes. Check there is no water in the condensation tray when the test is concluded. All rights reserved Page 6 of 24

7 Heating element, water (option) Connection of the heating element must be performed by an authorised plumber. If the unit is installed outdoors, or outside the building's climate screen, protect the installation against frost damage. The heating element is installed inside the unit by the factory if ordered as an option. If retrofitting a water heating element, it must be activated in the CTS 600 control system as described on page 13. Pass the pipe connections to the element through the inlet nozzle side. It is important that the pipes are supported from the element where connected. See figure for recommended mixing loop. Connect, bleed and check the system for leaks. The unit can then be started. Check and clean the dirt trap after flushing the system. The distance between the water circulation system and heating element should not exceed 2 metres to ensure stable adjustment of the element. Avoid installing pipes in the unit such that the fan cannot be removed. 4 3 A 1 AB 2 5 Heating surface Flow B Reguleringsventil: PN = 16 bar Max. diff. Tryk = 3,5 bar Air flow Retur 4 T9 B3 Figure 4: Recommended water circulation system installation Note: Temperature sensor T9 and frost thermostat sensor B3 are fitted on the heating element's air exhaust side, near the return water connection. See wiring diagram for connection. 1: Actuator and regulating valve: VPM 120, type Danfoss AME 140/24V, - 3-way valve VZ3 DN15 Kv 0.63, (supplied by Nilan) VPM 240, type Danfoss AME 140/24V, - 3-way valve VZ3 DN15 Kv 1.6, (supplied by Nilan) VPM 360, type Danfoss AME 140/24V, - 3-way valve VZ3 DN15 Kv 2.5, (supplied by Nilan) VPM 480, type Danfoss AME 140/24V, - 3-way valve VZ3 DN15 Kv 4.0, (supplied by Nilan) VPM 560, type Danfoss AME 140/24V, - 3-way valve VZ3 DN15 Kv 4.0, (supplied by Nilan) 2: Circulation pump, e.g. Grundfos UPS or equivalent (not supplied by Nilan) 3: Dirt trap (not supplied by Nilan) 4: Shut-off cock (not supplied by Nilan) 5: Air vent (not supplied by Nilan) All rights reserved Page 7 of 24

8 Guide to performance data, water heating element The table below shows heat production at various supply and return temperatures - at 5 C inlet after the heat pump and before the heating element. Supply/return temperature Guide to performance data for VPM 120 water heating element Pipe connection: Ø15 (for factory-fitted element) Air volume Performance Inlet air temperature (at temperature of 5 C just before the element) Pressure drop on water side Pressure drop on air side Water volume [ C] [m3/h] [kw] [ C] [kpa] [Pa] [l/h] 40/ Recommended Kv value for valve , , / , , / Kv = , , Supply/return temperature Guide to performance data for VPM 240 water heating element Pipe connection: Ø22 (for factory-fitted element) Air volume Performance Inlet air temperature (at temperature of 5 C just before the element) Pressure drop on water side Pressure drop on air side Water volume [ C] [m3/h] [kw] [ C] [kpa] [Pa] [l/h] 40/ Recommended Kv value for valve 1, , , , / , , , , / Kv = 1.6 1, , , , All rights reserved Page 8 of 24

9 Supply/return temperature Guide to performance data for VPM 360 water heating element Pipe connection: Ø22 (for factory-fitted element) Air volume Performance Inlet air temperature (at temperature of 5 C just before the element) Pressure drop on water side Pressure drop on air side Water volume [ C] [m3/h] [kw] [ C] [kpa] [Pa] [l/h] 40/30 1, Recommended Kv value for valve 1, , , , /40 1, , , , , /40 1, Kv = 2.5 1, , , , Guide to performance data for VPM 480 water heating element Pipe connection: Ø22 (for factory-fitted element) Air volume Supply/return temperature Performance Inlet air temperature (at temperature of 5 C just before the element) Pressure drop on water side Pressure drop on air side Water volume [ C] [m3/h] [kw] [ C] [kpa] [Pa] [l/h] 40/30 1, , , , , /40 1, , , , , /40 1, , , , , Recommended Kv value for valve Kv = 4.0 All rights reserved Page 9 of 24

10 Guide to performance data for VPM 560 water heating element Pipe connection: Ø22 (for factory-fitted element) Air volume Supply/return temperature Performance Inlet air temperature (at temperature of 5 C just before the element) Pressure drop on water side Pressure drop on air side Water volume [ C] [m3/h] [kw] [ C] [kpa] [Pa] [l/h] 40/30 1, , , , , /40 1, , , , , /40 1, , , , , Recommended Kv value for valve Kv = 4.0 IMPORTANT, ref. Danfoss Actuator type AME 140: Refitting the actuator MUST be performed as follows: 1. Disconnect mains electricity and remove the actuator cover. 2. Release the gear by depressing the button under the housing whilst screwing the shaft upwards (counter clockwise) as far as it will go. 3. Fit the actuator and connect electricity. 4. DIP switch no. 1 switch to ON and then to. 5. Calibration will run automatically for up to 6 minutes. (Diode will flash during calibration and then be constantly lit). 6. Fit actuator cover. Ambient temperature for Danfoss Actuator type AME 140/24 V is 0 C to 55 C. All rights reserved Page 10 of 24

11 Heating element, electric (option) The electric heating element is installed by the factory if ordered as an option. If retrofitting an electric heating element, it must be activated in the CTS 600 control system as described on page 12. The element is binary controlled in 7 steps. The electric heating element must be connected by an authorised electrician. Guide to performance data for electric heating element The table below shows heat production for various air volumes - at 5 C inlet air after the heat pump and before the heating element. Guide to performance data for VPM 120 electric heating element Air volume Max. output Inlet air temperature (at temperature of 5 C just before the element) [m3/h] [kw] [ C] , , Guide to performance data for VPM 240 electric heating element Air volume Max. output Inlet air temperature (at temperature of 5 C just before the element) [m3/h] [kw] [ C] , , , , Guide to performance data for VPM 360 electric heating element Air volume Max. output Inlet air temperature (at temperature of 5 C just before the element) [m3/h] [kw] [ C] 1, , , , , All rights reserved Page 11 of 24

12 Setting up the CTS 600 control system This chapter focuses on the CTS 600 control system service menu. Daily use of the CTS 600 control system: see the CTS 600 user guide supplied. Use of the CTS600 panel: - press ESC to go one step back in the menu - press qpto move up or down in a menu or to adjust an activated menu - press to activate a menu - press to confirm a menu - press to turn off the unit - press ON to turn the unit on Figure 5: CTS 600 control panel Activating service menu Hold q and key down simultaneously for 10 secs. The service menu will now be available. Press the q key until SERVICE appears on the display. Press to open the service menu. Scroll through the menu using the pq keys. The main points of the service menu are shown below: SERVICE HEATING SURFACE AIR EXCHANGE DEFROST TEMP. ROOM KONTROL RESTART PRESET MANUEL Figure 6: Main points of service menu All rights reserved Page 12 of 24

13 Heating element The unit is prepared for installation of a supplementary heating element. If the element is supplied and fitted by Nilan, it will be activated in the CTS 600 control system. A water or electrical heating element can be retrofitted. The element must be activated in the CTS 600 control system to work as part of the unit, and to activate frost protection for the element. Use of the CTS600 panel: - press ESC to go one step back in the menu - press qpto move up or down in a menu or to adjust an activated menu - press to activate a menu - press to confirm a menu - press to turn off the unit - press ON to turn the unit on SERVICE HEATING SELECT SURFACE WATERSUP AIR EXCHANGE DEFROST TEMP. ROOM KONTROL RESTART PRESET MANUEL DELAY 0 MIN Delay between start of ventilators and heating surface (0 60 minutes) SELECT EB SUP SELECT EL SUP SELECT Without Heating Surface SELECT WATERSUP Should be chosen when installing a heating surface for water. Controlled via 0-10 V signal LMC-200 PCB should be installed. Otherwise Alarm 90 slave I/O occurs. Should be chosen when installing an electrical heating surface, binary controlled (connection of steps via relays on CTS 600 PCB) Should be chosen when installing an electrical heating surface, controlled via 0-10 V signal LMC-200 PCB should be installed. Otherwise Alarm 90 slave I/O occurs. Figure 7: "Heating element" menu All rights reserved Page 13 of 24

14 Air exchange The air exchange menu can be used to set 4 ventilation steps (air volumes) for the unit. Inlet air and exhaust air can be set individually for each ventilation step. A minimum ventilation step can be set for inlet, and min./max. ventilation steps for exhaust. A delay can be set from when the unit switches on until the fan starts, to give the non-return damper time to open. Use of the CTS600 panel: - press ESC to go one step back in the menu - press qpto move up or down in a menu or to adjust an activated menu - press to activate a menu - press to confirm a menu - press to turn off the unit - press ON to turn the unit on SERVICE HOTWATER AIR EXCHANGE DEFROST MIN 0 EXHAUST MIN 1 The lowest permissible ventilation step for fresh air/inlet (0-2) The lowest permissible ventilation step for outlet/exhaust (1-2) TEMP. EXHAUST MAX 4 The highest permissible ventilation step for outlet/exhaust (3-4) ROOM RESTART PRESET >1< 35% EXHAUST >1< 35% DELAY 2 MIN Settings of the 4 ventilation levels of inlet/supply air ( %) Factory settings: Level 1: 35 % Level 2: 50 % Level 3: 75 % Level 4: 100 % Settings of the 4 ventilation levels of exhaust/extract air ( %) Factory settings: Level 1: 35 % Level 2: 50 % Level 3: 75 % Level 4: 100 % Delay of fan start, enabling the damper to open completely before the fans start. (0-4 minutes) Figure 8: "Air exchange" menu All rights reserved Page 14 of 24

15 Defroster The Defrost menu is used to programme the unit for defrosting the condenser surface for exhaust. Use of the CTS600 panel: - press ESC to go one step back in the menu - press qpto move up or down in a menu or to adjust an activated menu - press to activate a menu - press to confirm a menu - press to turn off the unit - press ON to turn the unit on SERVICE HEATING SURFACE AIR EXCHANGE AIR EXCH LOW DEFROST TEMP. AIR EXCH USER AIR EXCH USER AIR EXCH Constant air flow during defrosting. ROOM RESTART Airflow stopped during defrosting (should be used when exhaust air temperature is less than 10 C). PRESET Figure 9: "Defrost" menu All rights reserved Page 15 of 24

16 Temp. control The Temperature control menu is used to select the master temperature sensor for the unit. A minimum value can be entered to stop the unit in the event of loss of the primary heating supply to prevent further cooling of the building. Use of the CTS600 panel: - press ESC to go one step back in the menu - press qpto move up or down in a menu or to adjust an activated menu - press to activate a menu - press to confirm a menu - press to turn off the unit - press ON to turn the unit on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST Indicates which sensor is to be the controlling one: ROOM: T15 (panel sensor) ROOM EXT: T10 (installed in an extract fitting of your choice) : T7 (Inlet air temperature is chosen in the menu. T7/2 is the controlling sensor. Max/ min limits are not active) SENSOR SENSOR EXTERNAL TEMP. SENSOR PANEL SENSOR PANEL PRIORITY HP+EXT PRIORITY HP+EXT ROOM ROOM LOW 10 C PRIORITY HP RESTART PRIORITY PRESET The unit stops at this room temperature (1-20 C) - - means that the function is unactive. - - should be chosen if the panel is placed in a cold environment. : ventilation without heatpump HP: ventilation only with heatpump activ HP+EXT: ventilation with heatpump and heating surface activ Figure 10: "Temp. control" menu All rights reserved Page 16 of 24

17 Inlet control The Inlet control menu can be used to set the regulator for the inlet air temperature. The parameters in the " menu should only be adjusted by authorised personnel. (To reset factory settings, see page 20). Use of the CTS600 panel: - press ESC to go one step back in the menu - press qpto move up or down in a menu or to adjust an activated menu - press to activate a menu - press to confirm a menu - press to turn off the unit - press ON to turn the unit on SERVICE HOTWATER AIR EXCHANGE DEFROST TEMP. GAIN 7.0%/ ROOM INTEGRAL 120s RESTART N- ZONE 2.0 C PRESET TMP- RAMP 0.10 /s PERIOD VERYFAST. CAP- RAMP 0.5%/s PERIOD FAST. The maximum condenser temperature can be adjusted to the ventilation system. Cooling mode: In case of outage of the high pressure sensitive switch, Max 55 C can be lowered to e.g. 50 C. When the cooling output is reduced due to hot gas bypass, Max 55 C can be raised to C. In case of high pressure outage, the temperature is lowered. COND MAX 55 C PERIOD AUTO HEATPUMP RST 6m PERIOD NORMAL PERIOD AUTO The minimum length of time (in minutes) the compressor must be stopped before restarting. Figure 11: "Inlet control" menu All rights reserved Page 17 of 24

18 Room control The Room control menu can be used to set the regulator for the room temperature. The menu will NOT appear if T7 is selected as the master sensor on the Temp. control menu. The parameters in the "ROOM menu should only be adjusted by authorised personnel. (To reset factory settings, see page 20). Use of the CTS600 panel: - press ESC to go one step back in the menu - press qpto move up or down in a menu or to adjust an activated menu - press to activate a menu - press to confirm a menu - press to turn off the unit - press ON to turn the unit on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST TEMP. RESPONSE USER RESPONSE USER RESPONSE FAST GAIN 6.0 / ROOM RESPONSE NORMAL RESPONSE NORMAL INTERGRAL 6m RESTART N-ZONE 0.5 C RESPONSE SLOW N-ZONE 0.5 C PRESET N-ZONE is the chosen neutral zone between heating and cooling mode, when you choose AUTO in the main menu. N-ZONE = 0.5: This setting activates the adjustment at 0.25 C above and below the desired room temperature in heating and cooling mode, respectively. If the N-ZONE is set to 2.0, the adjustment is activated at 1 C above and below the desired room temperature. Rum control parametres : Response Gain Integral Slow Normal Fast User Figure 12: "Room control" menu All rights reserved Page 18 of 24

19 Restart The Restart menu is used to set the unit for automatic restart in the event of a high/low pressure fault. The "HP/LP" setting in the Restart menu must not be used for normal operation. Use of the CTS600 panel: - press ESC to go one step back in the menu - press qpto move up or down in a menu or to adjust an activated menu - press to activate a menu - press to confirm a menu - press to turn off the unit - press ON to turn the unit on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST TEMP. ROOM RESTART PRESET RESTART HP/LP RESTART This function may not be used under normal conditions. (the function indicates that the unit should restart automatcally when high-pressure/lowpressure alarms occur.) Indicates that the unit should not restart automatically when highpressure/low-pressure alarms occur. Figure 13: "Restart" menu All rights reserved Page 19 of 24

20 Reset The Reset menu is used to restore the factory settings for the unit. Use of the CTS600 panel: - press ESC to go one step back in the menu - press qpto move up or down in a menu or to adjust an activated menu - press to activate a menu - press to confirm a menu - press to turn off the unit - press ON to turn the unit on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST TEMP. ROOM When standard is chosen all factory settings are reset. An eventual supplementary heating surface must be re-activated. A heating surface is NOT frost-protected until it is correctly installed and activated in the service menu. RESTART PRESET STANDARD PRESET PRESET Figure 14: "Reset" menu All rights reserved Page 20 of 24

21 Manual The Manual menu is used for performing a manual test of the unit's functions. Use of the CTS600 panel: - press ESC to go one step back in the menu - press qpto move up or down in a menu or to adjust an activated menu - press to activate a menu - press to confirm a menu - press to turn off the unit - press ON to turn the unit on tt SERVICE HEATING SURFACE AIR EXCHANGE DEFROST VEN+HEAT Manual test of ventilation & heat. Under test there are 50% signal to the heating surface TEMP. VENT+CPR Manual test of ventilation & compressor EXHAUST Manual test of exhaust ROOM Manual test of inlet RESTART PRESET FLAPS DEFROST Manual test of flaps Manual test of the defrost function. Manual test de-activated (normal working) Figure 15: "Manual" menu All rights reserved Page 21 of 24

22 Guide to unit dimensions The unit dimensions are shown on a left model (supply air on the left side, seen from the front). The dimensions are reversed for a right model. Feedthrough for water heatingelement Air Inlet Fresh Air Air Exhaust Air Dischange Condencation drain (20 MM) Recommended service distance Recommended service distance Figure 16: Guide to unit dimensions A W C D F G H I J VPM 120 1, , Ø VPM 240 2, ,240 1, Ø VPM 360 2, ,400 1, Ø K L M N O P Q R S VPM , , VPM , , VPM , , Weight excluding packaging [kg] Insurance [A] VPM x13 3x400 VPM x16 3x400 VPM x16 3x400 Mains electricity supply [V(AC)] All rights reserved Page 22 of 24

23 Accessories/spare parts VPM 120 Filter class Name Quantity Nilan item number F5 (Standard in exhaust) HI-FLO 490 x x F7 (Standard in inlet) HI-FLO 490 x x VPM 240 Filter class Name Quantity Nilan item number F5 (Standard in exhaust) HI-FLO 592 x x F7 (Standard in inlet) HI-FLO 592 x x VPM 360 Filter class Name Quantity Nilan item number F5 (Standard in exhaust) HI-FLO G3BG HI-FLO G3CG F7 (Standard in inlet) HI-FLO G3UFG 85/56 38 HI-FLO G3UFG 85/ VPM 480 Filter class Name Quantity Nilan item number F5 (Standard in exhaust) HI-FLO G3BG F7 (Standard in inlet) HI-FLO G3UFG 85/ VPM 560 Filter class Name Quantity Nilan item number F5 (Standard in exhaust) HI-FLO G3BG F7 (Standard in inlet) HI-FLO G3UFG 85/ Water heating element + regulator (internal) Unit Quantity Nilan item number VPM VPM VPM VPM VPM Electric heating element (internal) Unit Output Quantity Nilan item number VPM kw VPM kw VPM kw VPM kw VPM kw Cover for outdoor installation Unit Name Quantity Nilan item number VPM VPM 240 Cover for outdoor installation VPM Vibration absorbers Unit Name Quantity Nilan item number VPM 120 Sylomer (Green) VPM 240 Sylomer (Brown) VPM 360 Sylomer (Brown) VPM 480 Sylomer (Brown) VPM 560 Sylomer (Brown) All rights reserved Page 23 of 24

24 Heating cable for condensation outlet (frost protection) Unit Name Nilan item number VPM 120 VPM 240 VPM 360 VPM 480 VPM 560 Heating cable (state length when ordering) 2172 Non-return damper Unit Name Voltage Nilan item number VPM 120 DTBU VPM 240 DTBU V (AC) 8433 VPM 360 DTBU All rights reserved Page 24 of 24

Installation instruction

Installation instruction Installation instruction CTS 600 by Nilan VPL 15 VPL 15 Top VPL 25 Version: 5.02, 13-05-2011 Table of contents Table of contents... 2 Figure table... 2 Introduction... 3 Power supply... 4 Assembly of VPL

More information

Installation instruction

Installation instruction Installation instruction CTS 600 by Nilan VP 18 M2 Version: 5.01, 15-04-2011 Table of contents Table of contents... 2 Figure table... 2 Introduction... 3 Power supply... 4 Assembly of VP 18 M2... 5 Condensation

More information

Installation instruction

Installation instruction Installation instruction CTS 600 by Nilan VP 18 10P Version: 5.03, 15-04-2011 Contents Contents... 2 List of figures... 2 Before starting... 3 Electrical connection... 4 VP 18-10P installation... 5 Condensation

More information

Installation instruction

Installation instruction Installation instruction CTS 602 by Nilan VP 18 M2 Version: 10.00, 13-04-2015 Software-version: 2.30 Table of contents Table of contents... 2 Figure table... 2 Introduction... 4 Power supply... 5 Assembly

More information

Installation instruction

Installation instruction Installation instruction CTS 602 by Nilan Compact P Compact P Sun Compact P Cool Compact P Cool Sun Version: 5.00, 13-05-2011 Contents Contents... 2 Figure table... 2 Before starting... 3 Electrical connection...

More information

PRODUCT DATA COMFORT 1200 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 1400 m 3 /h

PRODUCT DATA COMFORT 1200 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 1400 m 3 /h PRODUCT DATA COMFORT 00 BY NILAN Ventilation & passive heat recovery Commercial Passive heat recovery Ventilation < 00 m /h COMFORT 00 The Comfort 00 is a ventilation unit suitable for central ventilation

More information

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h PRODUCT DATA COMFORT 40 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 40 m /h COMFORT 40 Product description The Comfort 40 is an energy-efficient ventilation

More information

PRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h

PRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h PRODUCT DATA COMFORT 00 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 800 m /h COMFORT 00 Product description The Comfort 00 is an energy-efficient ventilation

More information

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h PRODUCT DATA COMFORT 5000 BY NILAN Ventilation & passive heat recovery Commercial Passive heat recovery Ventilation < 5300 m 3 /h COMFORT 5000 The Comfort 5000 is a ventilation unit suitable for central

More information

User manual. CTS 602 by Nilan VPL 15 VPL 15 TOP. Version: 9.02, Software-version: 2.21

User manual. CTS 602 by Nilan VPL 15 VPL 15 TOP. Version: 9.02, Software-version: 2.21 User manual CTS 602 by Nilan VPL 15 VPL 15 TOP Version: 9.02, 19-05-2014 Software-version: 2.21 Table of contents Table of contents... 2 Figure table... 2 Introduction... 3 Types of units... 4 Review of

More information

CTS 602 by Nilan. Compact P. Compact P Sun. Compact P Cool. Compact P Cool Sun. Version: 5.00, Software-version: 2.11

CTS 602 by Nilan. Compact P. Compact P Sun. Compact P Cool. Compact P Cool Sun. Version: 5.00, Software-version: 2.11 User manual CTS 602 by Nilan Compact P Compact P Sun Compact P Cool Compact P Cool Sun Version: 5.00, 13-06-2011 Software-version: 2.11 Contents Contents... 2 Figure table... 2 Introduction... 4 Types

More information

PRODUCT DATA COMBI 300 POLAR BY NILAN. Ventilation with passive & active heat recovery. Active heat recovery. Passive heat recovery.

PRODUCT DATA COMBI 300 POLAR BY NILAN. Ventilation with passive & active heat recovery. Active heat recovery. Passive heat recovery. PRODUCT DATA COMBI 300 POLAR BY NILAN Ventilation with passive & active heat recovery Domestic Passive heat recovery Active heat recovery Ventilation < 350 m 3 /h Comfort heating Comfort cooling COMBI

More information

PRODUCT DATA COMFORT 300 TOP BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 325 m 3 /h

PRODUCT DATA COMFORT 300 TOP BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 325 m 3 /h PRODUCT DATA COMFORT 300 TOP BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 325 m 3 /h COMFORT 300 TOP Product description The Comfort 300 Top is an energy-efficient

More information

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h PRODUCT DATA COMFORT 450 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 450 m 3 /h COMFORT 450 Product description The Comfort 450 is an energy-efficient ventilation

More information

User manual. User manual. CTS 600 by Nilan. Comfort Comfort Version: 10.00, Software-version: 2.30

User manual. User manual. CTS 600 by Nilan. Comfort Comfort Version: 10.00, Software-version: 2.30 User manual User manual CTS 600 by Nilan Comfort 1200 Comfort 5000 Version: 10.00, 13-04-2015 Software-version: 2.30 Contents Contents... 2 Introduction... 3 System types... 4 Temperature sensor overview...

More information

PRODUCT DATA VPL 15 TOP M2 BY NILAN. Ventilation & active heat recovery. Active heat recovery. Comfort heating. Comfort cooling.

PRODUCT DATA VPL 15 TOP M2 BY NILAN. Ventilation & active heat recovery. Active heat recovery. Comfort heating. Comfort cooling. PRODUCT DATA VPL 15 TOP M2 BY NILAN Ventilation & active heat recovery Domestic Active heat recovery Ventilation < 400 m 3 /h Comfort heating Comfort cooling VPL 15 TOP M2 Product description VPL 15 Top

More information

Danfoss Air Heating Surfaces

Danfoss Air Heating Surfaces MAKING MODERN LIVING POSSIBLE Installation Guide www.heating.danfoss.com Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English

More information

PRODUCT DATA VPL 28 BY NILAN. Ventilation & active heat recovery. Active heat recovery. Comfort heating. Comfort cooling.

PRODUCT DATA VPL 28 BY NILAN. Ventilation & active heat recovery. Active heat recovery. Comfort heating. Comfort cooling. PRODUCT DATA VPL 28 BY NILAN Ventilation & active heat recovery Domestic Active heat recovery Ventilation < 1000 m 3 /h Comfort heating Comfort cooling VPL 28 Product description VPL 28 is an energy-efficient

More information

PROGRAMMABLE 7-DAY RF THERMOSTAT

PROGRAMMABLE 7-DAY RF THERMOSTAT PROGRAMMABLE 7-DAY RF THERMOSTAT Installation and user instruction This instructions to be retained by the user 1 Thank you for choosing Beretta s radio frequency (RF) Radiostat. This central heating control

More information

MAKING MODERN LIVING POSSIBLE. Danfoss Air. Installation guide for Danfoss Heating Surfaces DANFOSS HEATING

MAKING MODERN LIVING POSSIBLE. Danfoss Air. Installation guide for Danfoss Heating Surfaces DANFOSS HEATING MAKING MODERN LIVING POSSIBLE Danfoss Air Installation guide for Danfoss Heating Surfaces DANFOSS HEATING Installation The Danfoss Air system Heating surfaces Index 1.0 Mounting electrical heating surfaces

More information

User's Guide. CTS6000 control panel

User's Guide. CTS6000 control panel User's Guide CTS6000 control panel Valid for: SW version 1,0092 Version 1.04, 2015-12-16 Contents Contents... 2 Figure... 2 Introduction... 3 Control panel menus... 4 Alarm log/event log... 4 Weekly program...

More information

PROGRAMMABLE 7-DAY THERMOSTAT

PROGRAMMABLE 7-DAY THERMOSTAT PROGRAMMABLE 7-DAY THERMOSTAT Installation and user instruction This instructions to be retained by the user 1 Thank you for choosing Riello s weekly programmer.. This central heating control device is

More information

PRODUCT DATA COMFORT 302 TOP BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 345 m 3 /h

PRODUCT DATA COMFORT 302 TOP BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 345 m 3 /h PRODUCT DATA COMFORT 302 TOP BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 345 m 3 /h COMFORT 302 TOP Product description The Comfort 302 Top is an energy efficient

More information

VEX100 series Air handling units with cross-flow heat exchanger

VEX100 series Air handling units with cross-flow heat exchanger Product information - Version 6 VEX100 series Air handling units with cross-flow heat exchanger VEX140: 400-2200 m 3 /h VEX150: 700-3600 m 3 /h VEX160: 1100-5000 m 3 /h VEX170: 1400-8400 m 3 /h Contents

More information

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery. PRODUCT DATA COMPACT P - SERIES BY NILAN Domestic Passive heat recovery Active heat recovery Ventilation < 300 m 3 /h Comfort heating Comfort cooling Sanitary hot water production Heating THE VENTILATION

More information

The CAB & DAB Air Curtains

The CAB & DAB Air Curtains The CAB & DAB Air Curtains Frequently Asked Questions General Positioning Page 2 Electrical & Connection Page 4 Electric Heated Page 5 Electronic door triggered shutdown feature (Electric) Page 5 Electronic

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

User Manual. Vanvex Optima 180 Domestic Hot Water. Version

User Manual. Vanvex Optima 180 Domestic Hot Water. Version GB User Manual Vanvex Optima 180 Domestic Hot Water Version 3.07-0310 Table of contents Page 1. Users Guide 1.1 Use... 3 1.2 Altering of the operation data... 3 1.3 Operating menu... 4 1.4 Factory default

More information

Installation Guide. ECL Comfort 210, application A Table of Contents

Installation Guide. ECL Comfort 210, application A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................

More information

N M AirControl AHU. Control manual

N M AirControl AHU. Control manual N 10.63 M 03-2016 AirControl AHU Control manual EN CONTENTS PAGE 1 - MONITORING AND CONTROL 2 1.1 The program 2 1.2 The HMI terminal 2 1.3 The controller 4 1.4 Description of the air handling units 4

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS - SPLIT DUCTED SYSTEMS CONGRATULATIONS on your purchase of an ActronAir air conditioning system. This energy efficient unit has been precision designed, manufactured from high quality

More information

PRODUCT DATA COMPACT S BY NILAN. Sanitary hot water production. Passive heat recovery. Comfort heating. Ventilation < 375 m 3 /h. Active heat recovery

PRODUCT DATA COMPACT S BY NILAN. Sanitary hot water production. Passive heat recovery. Comfort heating. Ventilation < 375 m 3 /h. Active heat recovery PRODUCT DATA COMPACT S BY NILAN Domestic Passive heat recovery Active heat recovery Ventilation < 375 m 3 /h Comfort heating Comfort cooling Sanitary hot water production COMPACT S Product description

More information

ECL Comfort 110, application 116

ECL Comfort 110, application 116 Operating Guide ECL Comfort 110, application 116 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS COMFORT CONTROL CENTER 2 THERMOSTAT OPERATING INSTRUCTIONS PROGRAMMABLE THERMOSTAT MODEL 3314080.000 BLACK 3314080.015 WHITE USA SERVICE OFFICE Dometic Corporation 1120 North Main Street Elkhart, IN 46514

More information

Weather compensated flow temperature control of heating and boiler systems

Weather compensated flow temperature control of heating and boiler systems Instructions ECL Comfort 110 Application 130 Weather compensated flow temperature control of heating and boiler systems User guide, Installation & Maintenance DH-SMT/DK VI.KT.G3.02 Danfoss 06/2008 How

More information

User instructions DHP-AT

User instructions DHP-AT User instructions DHP-AT VUGFC202 If these instructions are not followed during installation and service, Danfoss A/S liability according to the applicable warranty is not binding. Danfoss A/S retains

More information

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits CommStat 4 PRODUCT DATA SHEET Controller for Redundant Telecom HVAC Systems General Description The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners,

More information

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS HP727S Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS 1. General Description 2. Specifications 3. Installation Instructions 4. Electrical Wiring 5. Instrument Wiring

More information

5, SE GÅNGHESTER,

5, SE GÅNGHESTER, KSUB Control and monitoring unit Valid from week of manufacture 48/2005 Description The KSUB is a control and monitoring unit designed to control various types of fire/smoke dampers and fans in a flexible

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

ECL Comfort 110, application 130

ECL Comfort 110, application 130 Operating Guide ECL Comfort 110, application 130 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

Demand Duo Principle of Operation:

Demand Duo Principle of Operation: Page 1 of 25 8/23/2010 Contents: Demand Duo Principle of Operation:... 3 Schematic of Demand Duo:... 4 Demand Duo Fault Finding Check List:... 4 Basic operating principle of Demand Duo Thermostat:... 4

More information

ir-range 8G /03.15 Changes reserved.

ir-range 8G /03.15 Changes reserved. U s e r m a n u a l ic-range is-range ir-range 8G.52.80.00/03.15 Changes reserved. Contents 1. Introduction...3 2. Safety...5 3. Boiler description...6 4. Display and functions...7 4.1 DHW and Heating

More information

Planning guide. Atec.

Planning guide. Atec. www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.

More information

Installation and maintenance

Installation and maintenance Installation and maintenance CTS 700 by Nilan Compact P GEO 3 Compact Polar GEO 6 Version: 1.02, 01-06-2016 We reserve the right to make changes Page 1 of 40 Table of contents Table of contents... 2 General

More information

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502* User's Guide VI.7C.C5.02 2005.09 C66 *vi7cc502* *087R8069* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8069* *vi7cc502* Mixing controller with PI controlled

More information

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A cod. 6272262A GENERAL DATA Heating Data Heat Output Input (Adjustable) (Adjustable) Format 34i 11.2 34KW 45 145MJ/hr Format 34e 11.2 34KW 45 145MJ/hr General Specifications FORMAT 34i 34e Main burner injectors

More information

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA OWNER S MANUAL Vintage Classic HEAT COOL models Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support 888-475-7443 Manufacturing High Quality, High Efficiency Heat Pump

More information

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter VALLOX Product Code: 3158400 L 3158410 R SILENCER (OPTIONAL) INSTRUCTIONS FOR USE AND MAINTENANCE WATER CIRCULATED POST-HEATING UNIT (OPTIONAL) ELECTRIC POST-HEATING UNIT (OPTIONAL)) PREHEATER (OPTIONAL)

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS CTS700-TOUCH BY NILAN Compact P / Compact P Polar - EK (English) Version 2.10-27.04.2017 TABLE OF CONTENTS Safety Power supply... 4 Heat pump domestic hot water...4 Disposal...

More information

OWNER S MANUAL. Evaporative Cooler. (English) (EA, EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY

OWNER S MANUAL. Evaporative Cooler. (English) (EA, EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY OWNER S MANUAL Evaporative Cooler REMOTE CONTROL AUTO COOL FAN SPEED PM ECONOMY ILL239-D ILL1140-A (English) (EA, EXH, EZH) Hello and congratulations on purchasing a Breezair Ducted Cooler for your home.

More information

REMOTE CONTROL FAN SPEED ECONOMY BATTERY LOW. owner s manual

REMOTE CONTROL FAN SPEED ECONOMY BATTERY LOW. owner s manual REMOTE CONTROL AUTO FAN SPEED COOL PM ECONOMY BATTERY LOW owner s manual Hello and congratulations on purchasing a Breezair Ducted Cooler for your home. Breezair coolers have been designed to provide quiet,

More information

OWNER S MANUAL. Evaporative Cooler. (English) (EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY

OWNER S MANUAL. Evaporative Cooler. (English) (EXH, EZH) ILL239-D ILL1140-A FAN SPEED REMOTE CONTROL ECONOMY OWNER S MANUAL Evaporative Cooler REMOTE CONTROL AUTO COOL FAN SPEED PM ECONOMY ILL239-D ILL1140-A (English) (EXH, EZH) Introduction...4 Remote Thermostat Control...5 Wall Mounted Thermostat Control...11

More information

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual EN Table of Contents 1. INSTALLATION MANUAL...3 1.1. Air Handling Units Sections Connection...3

More information

SILENT 12 PORTABLE AIR CONDITIONER USER MANUAL

SILENT 12 PORTABLE AIR CONDITIONER USER MANUAL SILENT 12 PORTABLE AIR CONDITIONER USER MANUAL Thank you for choosing ElectriQ Please read this user manual before using this innovative Air Conditioner and keep it safe for future reference. Visit our

More information

Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061

Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061 Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061 Imported by: Zwembad BVBA Industrieweg 9 3190 Boortmeerbeek België www.harmopool.eu 0 Table of content Introduction... 2 Safety instructions...

More information

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102* User's Guide VI.KM.E1.02 2005.09 C62 *VIKME102* *087R8091* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8091* *VIKME102* Double mixing controller C62 VI.KM.E1.02

More information

XWA11V. Walk-In Temp / Door /Alarm / Light Module

XWA11V. Walk-In Temp / Door /Alarm / Light Module XWA11V Walk-In Temp / Door /Alarm / Light Module 1. GENERAL DESCRIPTION Model XWA11V, 100x64 mm format, is a microprocessor-based controller, suitable for temperature monitoring and alarming in a walk-in

More information

ADAPT PARASOL a. Installation - Commissioning - Maintenance ADAPT Parasol - m

ADAPT PARASOL a. Installation - Commissioning - Maintenance ADAPT Parasol - m ADAPT PARASOL a Installation - Commissioning - Maintenance 2013-12-04 ADAPT Parasol 600 / 600 PF ADAPT Parasol 1200 / 1200 PF M6 1 Water Position of waterpipes ADAPT Parasol 600 / 600 PF 600 Värme retur/

More information

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602* User's Guide VI.7C.E6.02 2005.09 C37 *VI7CE602* *087R8070* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8070* *VI7CE602* Mixing controller with ON / OFF controlled

More information

ETO 2 - Controller for ice and snow melting

ETO 2 - Controller for ice and snow melting ETO 2 - Controller for ice and snow melting Advantages Simple adjustment knob with two functions Illuminated display where you can easily see the temperature status and other values Controls both pumps

More information

Swegon CASA. duct coils for heating. the supply air

Swegon CASA. duct coils for heating. the supply air Swegon CASA the supply air duct coils for heating Instructions for installation, operation and maintenance For design engineers, installation engineers and service personnel SDHW_c_EN m ! Important information

More information

Logic+ Combi

Logic+ Combi USER GUIDE Logic+ Combi 24 30 35 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use

More information

XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring 1. GENERAL DESCRIPTION Model XWA11V-KIT, 100x64 mm format, is a microprocessor based light and alarm management controller,

More information

Oxiperm C 164 Fully automatic chlorine dioxide processing plant C, -6000C, -7500C, C. Service manual. Oxiperm 164C 4-10 kg Service en

Oxiperm C 164 Fully automatic chlorine dioxide processing plant C, -6000C, -7500C, C. Service manual. Oxiperm 164C 4-10 kg Service en Oxiperm 164C 4-10 kg Service en Oxiperm C 164 Fully automatic chlorine dioxide processing plant 164-4000C, -6000C, -7500C, -10000C Service manual 15.710138-V2.0 1 Imprint Oxiperm C 164 Fully automatic

More information

SENSA MRE DDM MR

SENSA MRE DDM MR 96239831 SENSA MRE DDM MR Contents Section Contents Page 1 Dimensional information 1 2 Description and operation 2 3 Wiring and fixing 3 4 Programming 6 5 Wiring diagrams 8 6 Detection pattern diagrams

More information

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL 500644 FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES A047-001 FIGURE 1: Demand Defrost Control Module ANTI-SHORT CYCLE DELAY

More information

The Book of AERMEC NRL Sequence of Operation

The Book of AERMEC NRL Sequence of Operation The Book of AERMEC NRL Sequence of Operation Heating and cooling operation. 2 Sequence of operation Aermec air to water chiller/heat pump use Hydronic s in conjunction with refrigerant to provide heating

More information

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS OWNER S MANUAL High-Wall Fan Coil Unit Page GENERAL 2,3 OPERATING MODES 2 REMOTE CONTROL 2 OPERATION 3-9 REMOTE CONTROL OPERATION 3 INDOOR UNIT DISPLAY 5 EMERGENCY OPERATION 5 PRESSING THE ON/OFF BUTTON

More information

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel.

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel. DEHUMIDIFICATION 9 CDS 80 FUNCTION The CDS 80 works in accordance with the condensation principle. A fan draws the humid air into the dehumidifier and through an evaporator coil. When passing through the

More information

C User manual

C User manual C10...40 User manual Introduction COORIGO is a completely new range of controllers which has been designed to be easy to use and operate. The controllers have a display and built in panels for operation

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

CWS AIR-CONDITIONERS

CWS AIR-CONDITIONERS CWS AIR-CONDITIONERS MODUL & MODUL XL INSTALLATION, OPERATION AND MAINTENANCE MANUAL MODUL_GB_2007.doc page 1 of 28 10/04/07 CWS air-conditioners 1 - Installation CONTENTS 1 Installation 2 Commissioning

More information

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40 USER GUIDE VOGUE COMBI GEN2 C26 C32 C40 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not

More information

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side s Frost detector for use on the air side QAF64.2-J QAF64.6-J With active capillary tube sensing element for acquiring the lowest temperature within a range of 0 15 C With startup function Operating voltage

More information

BasicTroubleshooting Information and Guidelines

BasicTroubleshooting Information and Guidelines BasicTroubleshooting Information and Guidelines BasicTroubleshooting Information and Guidelines Information and Guidelines May 2017 BasicTroubleshooting PRIOR TO CONTACTING CLIMATEMASTER TECHNICAL SUPPORT,

More information

Swedish design and manufacture since 1967

Swedish design and manufacture since 1967 Swedish design and manufacture since 167 PVP MA20-14 rev.2 Manual User manual Copyright 2017 Pahlén AB, Box 728, SE-14 27 Upplands Väsby, Sweden Tel. +46 8 54 110 50, Fax +46 8 50 868 80, e-mail: info@pahlen.se,

More information

Installation, operation and care. Pellmax UB. Burner not included Replaces:

Installation, operation and care. Pellmax UB. Burner not included Replaces: Installation, operation and care Burner not included 2011-11-11 ver: Replaces: Contents 11.11 otes...3 General...4 Function...4 Technical data...5 System principle Pellmax with radiator and tank-in-tank

More information

LC2200 Level Controller Installation and Maintenance Instructions

LC2200 Level Controller Installation and Maintenance Instructions 4025250/9 IM-P402-77 AB Issue 9 LC2200 Level Controller Installation and Maintenance Instructions LC2200 ALARM TEST >50% >100%

More information

DC INVERTER SERIES AIR TO WATER

DC INVERTER SERIES AIR TO WATER DC INVERTER SERIES AIR TO WATER INSTALLATION AND OPERATING INSTRUCTIONS MODELS: KS50-DC / KS70-DC / KS90-DC / KS120-DC / KS150-DC Please read this instruction manual before using the heat pump Introduction

More information

EUKC Cooling Unit. Compulsory declaration and recurring. The unit must NOT be used in any other way than as a cooling unit!

EUKC Cooling Unit. Compulsory declaration and recurring. The unit must NOT be used in any other way than as a cooling unit! Safety Precautions IMPORTANT INFORMATION! The unit must NOT be used in any other way than as a cooling unit! Carefully read, study and understand the Operation and Maintenance Instructions before you commission

More information

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort

Application guide FLATAIR - FLCK/FLHK. Providing indoor climate comfort Application guide FLATAIR - FLCK/FLHK Providing indoor climate comfort MSL60E-0701 12-2006 Congratulations you have made a wise choice and we feel sure that it will meet your expectation INDEX CONTENTS

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

OWNER S MANUAL. EXQ / EZQ / EXS Evaporative Coolers. Original English Instructions. (English)

OWNER S MANUAL. EXQ / EZQ / EXS Evaporative Coolers. Original English Instructions. (English) OWNER S MANUAL EXQ / EZQ / EXS Evaporative Coolers (English) Original English Instructions Hello and congratulations on purchasing a Breezair evaporative cooler for your home. At Seeley International

More information

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News VA 23606 Telephone (757) 873-6800 FAX (757) 873-3632 Website: www.ebacusa.com INTRODUCTION

More information

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

EBC20. Instructions for fitting, installation and operation. Read and save these instructions! EBC20 UK Instructions for fitting, installation and operation Read and save these instructions! 2 3002878 EBC20 UK 290415 1. Product information............................................... 4 1.1 Delivery.............................................................

More information

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

1 DOCUMENT REVISION CONTROL ELEMENTS... 9 CONTENTS Contents 1 DOCUMENT REVISION... 8 2 SOFTWARE VERSION... 8 3 BASIC DESCRIPTION... 8 4 CONTROL ELEMENTS... 9 4.1 BASIC DISPLAYS...10 4.2 CONTROL KEYS...11 4.2.1 Rotary button (Press / Turn)...11

More information

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE - SOLARE TERMICO Installation and operating instructions Temperature difference controller 6 inputs, 3 outputs, integrated data logger for

More information

AUTOMATED PRODUCTION SYSTEMS, INC Pine Road Huntingdon Va l l ey PA P h o n e : (215) FA X : (215)

AUTOMATED PRODUCTION SYSTEMS, INC Pine Road Huntingdon Va l l ey PA P h o n e : (215) FA X : (215) SERIAL NO. TM AUTOMATED PRODUCTION SYSTEMS, INC. 2840 Pine Road Huntingdon Va l l ey PA 19006 P h o n e : (215) 938-1000 FA X : (215) 938-8480 The Finest in Equipment for the Electronics Industry INSTRUCTION

More information

High wall fan coils Climmy FHW/FHW-ECM. Technical Catalogue

High wall fan coils Climmy FHW/FHW-ECM. Technical Catalogue High wall fan coils Climmy FHW/FHW-ECM Technical Catalogue Versions and Main components MODELS WITHOUT ELECTRIC HEATER All versions are available without valves, with 2 way valve or with 3 way valve fitted

More information

ivector HEATER/COOLER 2 AND 4-PIPE MODELS.

ivector HEATER/COOLER 2 AND 4-PIPE MODELS. 25278 ivector Installation Guide US 02/01/2013 09:24 Page 2 ivector HEATER/COOLER 2 AND 4-PIPE MODELS. INSTALLATION, OPERATING, MAINTENANCE & AFTER SALES MANUAL JANUARY 2013, ISSUE 1 Product Serial Number:

More information

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N V:\Technical\ARTWORK\Fitting & Wiring\Word Files COMPLETE\442073Q.doc Sentinel Kinetic MVHR and Kinetic Plus MVHR Operation & Monitoring Stock Ref. N 438222 Kinetic B 438222A Kinetic BS 443319 Kinetic

More information

Sentinel Kinetic MVHR RANGE

Sentinel Kinetic MVHR RANGE V:\Technical\ARTWORK\Fitting & Wiring\Word Files COMPLETE\442073 W.doc Sentinel Kinetic MVHR RANGE User Instructions Stock Ref. N 438342 Kinetic V 438222 Kinetic B Right 438222L Kinetic B Left 443319 Kinetic

More information

Adconair 76. Comfort air conditioning unit with counterflow plate heat exchanger. AIR VOLUME FLOW: 2,600 23,600 m³/h

Adconair 76. Comfort air conditioning unit with counterflow plate heat exchanger. AIR VOLUME FLOW: 2,600 23,600 m³/h Comfort air conditioning 76 Comfort air conditioning unit with counterflow plate heat exchanger Automatically selects the most economical operating mode! 76 13 76 01 13 with 01 - Adiabatic simplified Pro

More information

Technical specifications

Technical specifications Technical specifications Compact p by nilan Certified for use in passive houses A single compact ventilation and ing system - five efficient features The ventilation and ing solution of the future Compact

More information

air systems Large Rooftop DIC-BIH-DIG 360 to 480 G

air systems Large Rooftop DIC-BIH-DIG 360 to 480 G Large Rooftop DIC-BIH-DIG 360 to 480 G Large Rooftop DIC-BIH-DIG A complete range from 119.1 kw up to 155.6 kw R407C Features Adjustable roof curb types YKlon 33 board Duct work configuration side or down

More information

Metering systems 0548EN April 2014

Metering systems 0548EN April 2014 08EN April 0 0U8 GEY - Y - Y (GE- series) 900 000/ 00 00A/ 800 00L/ Versions and product codes Product code Type Heat exchanger nominal power GEY, - GEY and production GEY and production Table - Product

More information

Adsolair 56/58. Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system

Adsolair 56/58. Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system Comfort air conditioning 56/58 Comfort air conditioning unit with double plate heat exchanger and adiabatic evaporative cooling system 58 3 0 - simplified illustration Automatically selects the most economical

More information

Operating Instructions

Operating Instructions S-type Separation System Operating Instructions Printed Book No. Nov 2002 1810571-02 V 5 Alfa Laval reserves the right to make changes at any time without prior notice. Any comments regarding possible

More information