C User manual

Size: px
Start display at page:

Download "C User manual"

Transcription

1 C User manual

2 Introduction COORIGO is a completely new range of controllers which has been designed to be easy to use and operate. The controllers have a display and built in panels for operation and alarm on the front and are operated by means of clearly defined buttons. The controllers have been designed for mounting on a DIN rail, in norm housing or on the front of a cabinet. The required functions are selected with the help of questions in normal script or by means of a code under the configuration menu depending on the type of application. The controller has a year-base clock and automatic summer/winter time changeover. The menu system works with different user-levels to show settings and to allow settings to be altered. This means that non-technical staff can feel secure while using the system since it is impossible, on the lower user-levels, to programme incorrect settings when checking operating status, parameter values, alarms etc. During normal operation, without pressing any buttons, the display also shows the most important operating statuses such as setpoint/current value, sequence-output control and time/date/version etc. We hope you will be satisfied with your CORRIGO and that it will provide you with simpler and more economic running of your control systems. Contents Model overview CORRIGO for ventilation systems 4 Technical data 5 Overview of inputs and outputs 6 Installation 10 Wiring Diagrams 11 Description of inputs and outputs 15 Using the CORRIGO menu system 19 Logging in 21 Configuration 23 Controlling temperature 33 Controlling pressure 34 Controlling humidity 34 Running mode 35 Inputs 35 Outputs 36 Scheduler 38 Alarm settings and lists 40 Settings (other) 42 Relay modules, accessories 44 Commissioning protocol 46 Configuration tables 48 3

3 Overview - air handling models There are four CORRIGO models for ventilation control each with certain differences in control function and the number of outputs and types of input. These are supplied either with or without LON Works communication. Temperature control C10 C10-LON Temperature control with up to three sequences. With LON Works communication Temperature and pressure control C20 C20-LON Temperature control with up to three sequences. Pressure control of supply air and exhaust air fans. With LON Works communication Temperature and humidity control C30 C30 LON Temperature control with up to three sequences. Humidity control two sequences. With LON Works communication. Temperature, humidity and pressure control C40 C40 LON Temperature control with up to three sequences. Humidity control two sequences. Pressure control supply air and exhaust air fans. With LON Works communication. Temperature control Pressure control Humidity control Number of digital outputs Number of analogue outputs ( V) Number of digital inputs Number of analogue inputs (PT1000) Number of analogue intputs ( V) Run-time indication with yellow LEDs Alarm indication in text and red LEDs One- or twospeed control of supply and exhaust air fans Individual start and stop of supply and exhaust air fans Efficiency monitoring Cooling recovery Automatic night cooling (free cooling) Periodic fire-damper exercising with alarm function Filter alarm and pressure alarm Active frost protection with stand-by heating when the system is shut down Automatic circulation pump control with periodic exercising Memory (48 hour backup time in event of a power-failiure) External setpoint Communication (Lon-versions) Year-base clock C10 C20 C30 C

4 Technical data Supply voltage 24V AC +/- 15% Power consumption 3VA Ambient temperature deg.c. Storage temperature deg.c. Ambient humidity Maximum 90% RH Dimensions (w x h x d) 105 x 112 (incl.terminals) x 58 mm. Protection class IP20. Front mounting IP40 Mounting On DIN-rail in a cabinet or standard housing. On cabinet front using mounting kit FMC Connections Disconnectable terminal strips Temp.sensor inputs PT1000 Analogue inputs V DC Digital inputs Potential free closure. Digital outputs 0.5 A, 24 V AC triac outputs Analogue outputs V DC, 5 ma. Short-circuit protected Memory Flash. All settings are stored in the event of power failure. Real-time clock with 48 hour reserve running time. Display Background illumination. LCD, 2 rows of 16 characters Running indication 7 in number steady shining yellow LEDs Alarm indication 7 in number steady shining/flashing red LEDs Alarms Steady shining/flashing LED and relay output, 1A 24V DC/AC. The alarm output can be blocked to prevent unprioritised alarms activating the alarm relay during the night or during holidays. This product conforms with the requirements of European EMC standards CENELEC EN and EN and carries the CE mark. Front mounting kit When mounting CORRIGO in a cabinet front use the FMk1 kit for easier mounting. The kit contains a front frame with see-through lid and an integrated mounting-rail. Protection class IP65. When mounting 2 CORRIGOs or one CORRIGO plus a relay unit next to each other in the cabinet front use the FMk2 mounting kit. It contains the same items as FMK1 above but in different dimensions. 5

5 CORRIGO - C10 6 analogue sensor inputs Pt digital inputs 3 analogue outputs V 7 digital outputs The controller has temperature control with up to three sequences, control DX-cooling,one- or two-speed operation, heat exchanger efficiency calculation, cooling recovery function, night setback etc. Analogue inputs - Temperature sensors AI3 Exhaust air temperature AI4 Extract air temperature or External setpoint or Exchanger return temperature (Liquid connected exchanger). AI5 Outdoor temperature AI6 Supply air temperature AI7 Room temperature AI8 Frost protection temperature. When frost protection function has been selected or High temperature limit. When using an electric heater Digital inputs - operation and alarm indication AI1 Fan monitor or pressure switch Supply air fan. AI2 Fan monitor or pressure switch Exhaust air fan. DI1 Filter guard(s) DI2 Circulation pump monitor, heater circuit DI3 Input for alarm from chiller(s) DI4 Rotation sentinel or ice build-up sentinel for heat exchanger DI5 Fire alarm DI6 External alarm, external switches not in Auto position or end-position indication for fire-damper (for firedamper exercising). DI7 Button or timer for extended running time (at single speed) / Extended running time high speed for two- speed fan systems). DI8 Button or timer for extended low speed running time (for two-speed fan systems). Analogue outputs - output signal V AO1 Y1 - Heating, cooling or damper AO2 Y2 - Heating, plate exchanger, rotating exchanger, liquid connected exchanger, damper or cooling AO3 Y3 Heating, cooling or not used Digital outputs DO1 Control supply air fan or Supply air fan high speed for two-speed fans DO2 Control exhaust air fan or Exhaust air fan high speed for two-speed fans DO3 Control circulation pump or Electric heating interlock DO4 Control chiller 1 (DX) or Supply air fan low speed for two-speed fans DO5 Control chiller 2 (DX) or Exhaust air fan low speed for two-speed fans DO6 Control external frost protection or Fire damper exercising DO7 Alarm output Example of an application suitable for controlling by the C10 model. 6

6 CORRIGO - C20 6 analogue sensor inputs Pt analogue inputs V 8 digital inputs 5 analogue outputs V 7 digital outputs The controller has temperature control with up to three sequences, control of DX-cooling, pressure control of supply air fan and exhaust air fan, heat exchanger efficiency calculation, cooling recovery function, free cooling etc. Analogue inputs - Pressure sensors V AI1 Pressure sensor, supply air fan AI2 Pressure sensor, exhaust air fan Analogue inputs - Temperature sensors AI3 Exhaust air temperature AI4 Extract air temperature or External setpoint or Exchanger return temperature (Liquid connected exchanger) AI5 Outdoor temperature AI6 Supply air temperature AI7 Room temperature AI8 Frost protection temperature When frost protection function has been selected or High temperature limit. When using an electric heater. Digital inputs - operation and alarm indication DI1 Filter guard(s) DI2 Circulation pump monitor, heater circuit DI3 Input for alarm from chiller(s) DI4 Rotation sentinel or ice build-up sentinel for heat exchanger DI5 Fire alarm DI6 External alarm, external switches not in Auto position or end-position indication for fire-damper (for firedamper exercising). DI7 Button or timer for extended running time at normal speed. DI8 Button or timer for extended running time at reduced speed. Analogue outputs - output signal V AO1 Y1 - Heating, cooling or damper AO2 Y2 - Heating, plate exchanger, rotating exchanger, liquid connected exchanger, damper or cooling AO3 Y3 Heating, cooling or not used AO4 Pressure control signal for supply air fan AO5 Pressure control signal for exhaust air fan Digital outputs DO1 Activate supply air fan DO2 Activate exhaust air fan DO3 Control circulation pump or Electric heating interlock DO4 Control chiller 1 (DX) DO5 Control chiller 2 (DX) DO6 Control external frost protection or Fire damper exercising DO7 Alarm output Example of an application suitable for controlling by the C20 model. 7

7 CORRIGO - C30 4 analogue sensor inputs Pt analogue V inputs 10 digital inputs 3 analogue outputs V 7 digital outputs The controller has temperature control with up to three sequences, humidity control (humidification, dehumidification or humidification in combination with dehumidification by using the cooling output, control of DX-cooling,one- or two-speed operation, cooling recovery function, night setback etc). Analogue inputs - Temperature sensors AI3 Room humidity sensor AI4 Duct humidity sensor (limiting sensor in supply air duct) Analogue inputs - Temperature sensors AI5 Outdoor temperature AI6 Supply air temperature AI7 Room temperature AI8 Frost protection temperature. When frost protection function has been selected or High temperature limit (When using an electric heater) Digital inputs - operation and alarm indication AI1 Fan monitor or pressure switch Supply air fan. AI2 Fan monitor or pressure switch Exhaust air fan. DI1 Filter guard(s) DI2 Circulation pump monitor, heater circuit DI3 Input for alarm from chiller(s) DI4 Rotation sentinel or Ice build-up sentinel for heat exchanger DI5 Fire alarm DI6 External alarm, external switches not in Auto position or end-position indication for fire-damper (for fire-damper exercising). DI7 Button or timer for extended running time (at single speed) / Extended running time high speed for two- speed fan systems). DI8 Button or timer for extended low speed running time (for two-speed fan systems). Analogue outputs - output signal V AO1 Y1 - Heating, cooling or damper AO2 Y2 - Heating, plate exchanger, rotating exchanger, liquid connected exchanger, damper or cooling AO3 Y3 Heating, cooling or not used AO6 Humidification / Dehumidification Digital outputs DO1 Control supply air fan or Supply air fan high speed for two-speed fans DO2 Control exhaust air fan or Exhaust air fan high speed for two-speed fans DO3 Control circulation pump or Electric heating interlock DO4 Control chiller 1 (DX) or Supply air fan low speed for two-speed fans DO5 Control chiller 2 (DX) or Exhaust air fan low speed for two-speed fans DO6 Control external frost protection or Fire damper exercising DO7 Alarm output Example of an application suitable for controlling by the C30 model. 8

8 CORRIGO - C40 Overview 4 analogue sensor inputs Pt analogue inputs V 8 digital inputs 6 analogue outputs V 7 digital outputs The controller has temperature control with up to three sequences, humidity control, control of DX-cooling, pressure control of supply air fan and exhaust air fan, heat exchanger efficiency calculation, cooling recovery function, free cooling etc. Analogue inputs - Pressure sensors / Humidity sensors V AI1 Pressure sensor, supply air fan AI2 Pressure sensor, exhaust air fan AI3 Room humidity sensor (Main sensor) AI4 Duct humidity sensor (Limiting sensor) Analogue inputs - Temperature sensors AI5 Outdoor temperature AI6 Supply air temperature AI7 Room temperature AI8 Frost protection temperature. When frost protection function has been selected or High temperature limit. When using an electric heater DI Digital inputs - operation and alarm indication DI1 Filter guard(s) DI2 Circulation pump monitor, heater circuit DI3 Input for alarm from chiller(s) DI4 Rotation sentinel or Ice build-up sentinel for heat exchanger DI5 Fire alarm DI6 External alarm, external switches not in Auto position or end-position indication for firedamper (for fire-damper exercising). DI7 Button or timer for extended running time at normal speed. DI8 Button or timer for extended running time at reduced speed. Analogue outputs - output signal V AO1 Y1 - Heating, cooling or damper AO2 Y2 - Heating, plate exchanger, rotating exchanger, liquid connected exchanger, damper or cooling AO3 Y3 Heating, cooling or not used AO4 Pressure control signal for supply air fan AO5 Pressure control signal for exhaust air fan AO6 Humidity control Digital outputs DO1 Activate supply air fan DO2 Activate exhaust air fan DO3 Control circulation pump or Electric heating interlock DO4 Control chiller 1 (DX) DO5 Control chiller 2 (DX) DO6 Control external frost protection or Fire damper exercising DO7 Alarm output Example of an application suitable for controlling by the C40 model. 9

9 Installation CORRIGO can be mounted in standard casing, on a DIN rail in a cabinet or in the front of a cabinet. Front mounting kit When CORRIGO is to be placed in a cabinet front mounting will be facilitated using the front mounting kit FMK1. The kit contains a front frame with see-through lid and an integrated mounting-rail. When placing two CORRIGOs or one CORRIGO and one relay unit RM6..-24/D next to each other in the front of the cabinet use the FMCR mounting kit. It contains the same parts as FMC above but they are of different dimensions. Supply voltage The controller is to be supplied with 24V AC. Terminal 43, system neutral, is internally connected to terminal 41, signal neutral for the analogue outputs, and terminals 24, 27, 30 och 33, signal neutral for the analogue inputs. Inputs The controller has common poles for signal neutral to transmitters (AI 1-8) and a common pole for digital input signals. Terminal 22 (common for digital input signals) is not the same as signal neutral for transmitters ( terminals 24,27,30 and 33) and they must not be interconnected. Signal neutral terminals for transmitters (24,27,30 and 33) are, however, internally connected and connected to system neutral on terminal 43. Outputs The analogue outputs give V DC. Signal neutral on terminal 41 is internally connected to system neutral on terminal 43. Important! Digital outputs are supplied in pairs with 24V AC on the terminals which are marked with 24V AC in (terminals 6,9 and 12). Each output has an internal triac which gives 24V AC. Terminals 6, 9 and 12 are also internally connected. Service pin On the LON-models the comissioning service pin is located behind a marked opening on the upper side of the CORRIGO. Service pin (LON models) Display contrast setting DO1...DO7 digital outputs DI1...DI8 digital inputs AI1...AI8 analogue in AO1... AO6 analogue out Supply voltage 24 V AC 10

10 Wiring diagram C10 Wiring example actuator Control signal V Signal neutral Supply voltage 24 V AC System neutral (24 V AC) 35 AO1 Y V DC 36 AO2 Y V DC 37 AO3 Y V DC 38 AO4 39 AO5 40 AO6 41 M Neutral for AO1-AO V AC N System neutral Ground Supply voltage 11

11 Wiring diagram C20 Wiring example actuator Signal V Signal neutral Supply voltage 24 V AC System neutral (24 V AC) AO1 AO2 AO3 AO4 AO5 Not connected M Neutral for AO1-AO5 Y V DC Y V DC Y V DC Supply air fan control V DC Exhaust air fan control V DC V AC N system neutral Ground Supply voltage 12

12 Wiring diagram C NetA LON-connector NetB LON-connector C30-LON only C30-LON only 24 V AC DO7 Alarm output DO7 Alarm output 1A 24 V AC/DC DO6 Frost protection / Fire damper exercising C5/6 24 V AC in DO5/DO6 DO5 Control DX 2 DO4 Control DX 1 C3/4 24 V AC in DO3/DO4 DO3 Control Circ. pump/ El. Heating interlock DO2 Activation Exhaust air fan C1/2 24 V AC in DO1/DO2 DO1 Activation Supply air fan DI8 Ext. running Reduced speed DI7 Ext. running Normal speed DI6 Fire damper indication DI5 Fire alarm DI4 Rotation sentinel DI3 Alarm from chillers DI2 Circulation pump alarm DI1 Filter guards DI+ Common supply DI1-DI V V AI1 M AI2 AI3 M AI4 AI5 M AI6 AI7 M AI8 Fan monitor Supply air fan Signal neutral Fan monitor Exhaust air fan Room humidity sensor Signal neutral Duct humidity sensor (limiting sensor) Outdoor temperature sensor Signal neutral Supply air temperature sensor Room temperature sensor Signal neutral Frost protection sensor AO1 AO2 AO3 Not connected Not connected Y V DC Y V DC Y V DC AO6 Humidity control output V DC M Neutral for AO1-AO3, AO6 Wiring example actuator V AC N Supply neutral Ground Supply voltage Control signal V Signal neutral Supply voltage 24 V AC System neutral (24 V AC) AO1 AO2 AO3 Not connected Not connected Y V DC Y V DC Y V DC AO6 Humidity control output V DC M Neutral for AO1-AO3, AO V AC System neutral Ground Supply voltage 13

13 Wiring diagram C Net A LON-connector Net B LON-connector C40-LON only C40-LON only 24 V AC DO7 Alarm output DO7 Alarm output 1A 24 V AC/DC DO6 Frost protection / Fire damper exercising C5/6 24 V AC in DO5/DO6 DO5 Control DX 2 DO4 Control DX 1 C3/4 24 V AC in DO3/DO4 DO3 Control Circ. pump / El. Heating Interlock DO2 Activation Exhaust air fan C1/2 24 V AC in DO1/DO2 DO1 Activation Supply air fan V V V V DI8 Ext. running Reduced speed DI7 Ext. running Normal speed DI6 Fire damper indication DI5 Fire alarm DI4 Rotation sentinel DI3 Alarm from chillers DI2 Circulation pump alarm DI1 Filter guards DI+ Common supply DI1-DI8 AI1 M AI2 AI3 M AI4 AI5 M AI6 AI7 M AI8 Fan monitor Supply air fan Signal neutral Fan monitor Exhaust air fan Room humidity sensor Signal neutral Duct humidity sensor (limiting sensor) Outdoor temperature sensor Signal neutral Supply air temperature sensor Room temperature sensor Signal neutral Frost protection sensor AO1 AO2 AO3 AO4 AO5 AO6 M Y V DC Y V DC Y V DC Supply air fan V DC Exhaust air fan V DC Humidity control output V DC Neutral for AO1...AO6 Wiring example actuator V AC N Supply neutral Ground Supply voltage Control signal V Signal neutral Supply voltage 24 V AC System neutral (24 V AC) AO1 AO2 AO3 AO4 AO5 AO6 M Y V DC Y V DC Y V DC Supply air fan control V DC Exhaust air fan control V DC Humidity control output V DC Neutral for AO1-AO V AC System neutral Ground Supply voltage 14

14 AI Analogue in CORRIGO has 8 analogue inputs, AI1...AI8 The function of some of the inputs varies depending on the choice of model and configuration. PT1000 type temperature sensors must be used on those inputs that are configured as temperature inputs. In certain cases an AI-input may be used as a digital input. It must then be connected to a voltage-free, closing contact. When active input signals are connected they must be V DC. AI-inputs must always use the signal neutral of the AI terminal block as reference. (terminals 24, 27, 30 or 33). AI1 and AI2 are used for connecting pressure switches/transmitters for monitoring and control of the supply air and exhaust air fans Note: These signals control vital functions in the CORRIGO. They must always be connected for correct control function. C10 and C30 Connect the inputs to pressure switches with voltage-free closing contacts, for example DTV, or to voltage-free closing contacts in the fan-motor relays. C20 and C40 Connect the inputs to pressure transmitters with a V DC output, for example DMD or DTL. Wiring, see example in the margin. The transmitter pressure range is set in the menu Settings, see page 42. AI3 och AI4 C10 and C20 AI3 Used for exhaust air temperature sensor, for example TG-K3/PT1000. AI4 Used for extract air temperature sensor or for minimum limiting sensor in the heat exhanger circuit when using a liquid connected heat exchanger. (See page 28). These functions are mutually exclusive, only one of them may be chosen. C30 and C40 AI3 Used for room humidity transmitter, for example HRT. AI4 Used for duct humidity sensor (limiting sensor), for example HDT3200. The sensors must have an output signal of V DC corresponding to % RH. Since neither of the supply voltage terminals is connected to the AI signal neutral it is necessary to make an external connection between the supply voltage pole chosen as G0 and the AI signal neutral. Note: If no limiting sensor is connected AI4 must be connected to signal neutral. AI5...AI8 AI5 Outdoor temperature sensor, for example TG-R6/PT1000. AI6 Supply air temperature sensor, for example TG-K3/PT1000. AI7 Room temperature sensor, for example TG-R5/PT1000. AI8 Frost protection sensor, for example TG-A1/PT1000 when the unit is configures for water heating. Input for high temperature limiting switch when the controller is configured for electric heating. Connect to voltage-free closing contact. (See page 27) 15

15 DI Digital inputs CORRIGO has 8 digital inputs, DI1...DI8 for activation of certain functions and input of external alarm signals. These inputs may only be wired to voltage-free contacts. These inputs may only refer to the common DI pole on terminal 22. Terminal 22 does not have the same potential as other signal neutrals in the CORRIGO and may not be connected to any other terminals except the DI inputs. Each input can be individually set, either so that closed contact activates the function/alarm, or so that open contact activates the function/alarm. See under menu Settings page 43. Important! DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 Input for filter monitor pressure switch(es). If there are several switches these should be wired in parallell. Circulation pump indication. Must be wired when CORRIGO is configured for water heating. A stopped pump will force the controller to go into shut down mode. Alarm from cooling machine(s). Rotation sentinel or ice build-up thermostat in plate exchanger. Fire alarm. External alarms or external switches not in Auto position (used when CORRIGO is used with relay module RM6H-24/D or fire damper end position switches (for fire damper exercising). Function depends on configuration settings (see page 30). Pushbutton or timer for extended running, single speed fan or high speed when using two-speed fans. Pushbutton or timer for extended running, low speed when using two-speed fans. Simultaneous closure of both DI7 and DI8 will force the CORRIGO to shut down. For installations with external switches for fan control, wire according to the figures below. DI7 and DI8 should then be configured as for timer. See page 31. H 0 Auto DI7 High speed Low speed 0 Auto DI7 DI8 DI8 single-speed fans 2-speed fans 16

16 AO Analogue outputs Depending on model, CORRIGO has analogue outputs, AO1...AO6. Output signal V DC, 5 ma. Short-circuit protected. These outputs should refer to terminal 41, signal neutral. Signal neutral G0, terminal 41, in the CORRIGO is internally connected to sytem neutral on terminal 43. It is therefore important that any actuators sharing the CORRIGO supply transformer are wired with their supply neutral connected to the same transformer pole as the CORRIGO terminal 43. AO1...AO3 is present in all models. These outputs comprise the temperature control sequence. The output function is dependant on the configuration settings but the actuating order is always Y3 before Y2 before Y1 on increasing heat demand. AO1 Y1 - Heating or mixing-dampers. AO2 Y2 - Heating, Plate exchanger, Rotating exchanger, liquid-connected exchanger or cooling. AO3 Y3 - Heating, cooling. AO4 Output signal for supply-air fan speed control. Models C20 and C40 only. AO5 Output signal for exhaust-fan speed control. Models C20 and C40 only. AO6 Humidification, dehumidification Models C30 and C40 only. Function, see page

17 DO Digital outputs CORRIGO has 7 digital outputs DO1...DO7. DO7, alarm output is a voltage free closing relay contact. 1 A, 24 V AC/DC. The outputs DO1...DO6 are triac controlled, 0.5 A, 24 V AC. Short term 1 A. The triac outputs are paired to common supply terminals for 24 V AC. DO6 out See figure in the margin. 24 V AC in For handling higher voltages or currents, use relay modules RM6-24/D or DO5 out RM6H-24/D that have been developed for this purpose. Some of the outputs have alternative functions depending on model and configuration. For example, this means that, in C10 and C30, DX cooling cannot be combined with control of two-speed fans DO1 DO2 DO3 DO4 DO5 DO6 DO7 Start supply-air fan (High speed for 2-speed fan in C10 and C30). Start exhaust-air fan (High speed for 2-speed fan in C10 and C30). Control of circulation pump or electric heating interlock. Must be wired when water heater is used. Stopped pump will force the CORRIGO to shut-down mode. DO3 is normally used for control of the circulation pump. When using electric heating, this is not used. Instead it can often be useful with an output for electric heating interlock, for example when a step-controller is used to control the heater. Step-controllers often have step-up/step-down time delay functions. This can lead to heating output during the cool-down period or even after the supply air fan has been shut down which will trip the heater high-limit thermostat. By wiring the heating relays via DO3 the heating output will be shut down as soon as CORRIGO switches from running mode to shutdown mode. When CORRIGO is configured for electric heating DO3 will be active during normal running mode and switched off in shut-down mode i.e. even during the cool-down period. Control of chiller 1 (DX1) or Start supply-air fan, low speed for 2-speed control in C10 and C30. Control of chiller 2 (DX2) or Start exhaust-air fan, low speed for 2-speed control in C10 and C30. External frost protection interlock or fire damper exercising. Function see page 30, Function DI6/DO6. Alarm output relay 18

18 Buttons on the front Esc OK Arrow up move upwards in the menu. In the Change position the button is used to INCREASE the value indicated. When the button is held in a depressed position the function is repeated. Arrow down move downwards in the menu. In the Change mode the button is used to DECREASE the value indicated. When the button is held in a depressed position the function is repeated. This is used to stop an ongoing operation or to move one level upwards in the menu. The Esc button is also used to move backwards in the menus which contain a number of values, thus it is possible to move forwards with OK and backwards with Esc. (enter). Is used to confirm an item in the menu. In the Change mode the button is used to confirm a set value and/or to continue to the next setting. Help menus: Press OK and the controller will show an explanatory text for the menu in question, provided that the menu is not in the Change position. Alarm opens the alarm queue. Press this button and active and nonacknowledged alarms will be displayed in the menu window. The LED for alarms placed above the alarm button is lit when there are alarms in the queue. If there are multiple alarms use and to move between them. An alarm can be acknowledged by using OK. To abort, press Esc. Change Goes over to Change mode. Use this button to change something in a menu, for example, a setpoint. You remain in the Change mode until you have confirmed the change by means of OK or aborted the operation by means of Esc. If the buttons are not activated the controller will stop the operation automatically after a minute or so. Changing language CORRIGO is supplied with the script in English. Apart from English, CORRIGO can also be set to show Swedish or Nowegian. The language selection function is activated by holding the button depressed during power up.the language menu is then shown: Language/Språk English To change language press! again and the marker will show the current language. Select the desired language by using the arrow buttons. Press OK to acknowlege. When the language has been changed or if no change is to be made, press OK and the controller s normal menu system will start up. 19

19 Information series - rolling display * CORRIGO C40 * Mo SF/Setp/Act/Out 275Pa/275Pa/70% Setpoint/Actual 20,0 C / 20,0 C EF/Setp/Act/Out 250Pa/250Pa/60% Y1 / Y2 / Y3 0% / 45% / 0% Setpoint/Actual 50% RH / 48% RH During normal running when the buttons are not in use a series of menu pages is shown. The display alternates between a general display with product description and clock, setpoint/actual temperature, output status for the control outputs Y1,Y2 and Y3 and setpoint, actual value and output status for supply air fan and exhaust air fan and sepoint and actual value for the humidity control. The initial display shows the product name, date and time. Program version number By pressing Esc when the gerneral display is active the product version number is displayed. For LON-models the 12 digit neuron ID-number is also displayed The information menu is started by leaving the main menu by means of Esc or by leaving the keyboard unused for a ten-minute period. First, the start window will be shown for 10 seconds and then the three displays shown above will alternate at three-second intervals. Main menu Press the OK button.the information menu will stop and the main menu will open immediately. The main menu consists of a number of menu headings and what can be seen and done is governed by the log-in level of the user, as described below. When the main menu is opened TEMP CONTROL is always displayed at the top of the display. >Temp control AI Analogue in The arrow marker to the left of TEMP CONTROL means that this heading is marked and pressing the OK button opens this menu and shows its submenus. Arrows at the right of the display indicate that there are headings above and below the text that is currently being displayed. Move by using the arrow buttons. The main menu has the following headings: Login Configuration Only shown at user level 3 Temp Control Pressure control Models C20 and C40 only Humidity control Models C30 and C40 only Running mode AI Analogue in DI Digital in AO Analogue out DO Digital out Scheduler Alarm settings Only shown at user level 1 or higher Settings Only shown at user level 2 or higher 20

20 Menu information If the user attempts to make changes that cannot be made or which lie outside his user level the controller will display the following information: Unauthorised Make new logon No changes in this menu Menu help text There are extra help-text to most of the menu pages. By pressing the OK button (except when in Change mode ) the extra text will be displayed. Alarms When alarms are activated they are displayed in the alarm queue and also as a blinking red light on the display panel on the front of the controller. Certain alarms cannot be traced to one of the 7 LEDs on the panel and therefore have no separate alarm on the front. The alarm lamp above the alarm button always blinks red, however, in the event of an alarm. Alarm queue To check the alarm queue press the alarm button. The display will then show active alarms, the date and time when the alarm became active and the alarm status. Alarm status Blinking AL indicates that the alarm is active and has not been acknowledged. Steady AL indicates that the alarm is active but has been acknowledged. Blinking OK indicates that the alarm has aborted but has not been acknowledged. Acknowledging an alarm Alarms are acknowledged by means of the OK button which will remove the alarm from the alarm list. If the alarms are still active they will remain in the alarm list but the blinking will be replaced by a steady AL and a steady red light on the alarm signals. Alarm chiller AL :20 Arrows on the right-hand side show when there are more alarms in the queue. Login CORRIGO has four different login levels to prevent the user from inadvertently changing any settings. 0 Without logging in all of the most important parameters can be viewed such as input and output status, alarms in the alarm queue, setpoints etc. Alarms can also be acknowledged. 1 Main setpoint, time and date can be set. Outputs can be manually set and the running mode can be set to manually on or off. Other parameters can be read off but not changed. 2 Gives access to most setpoints and running parameters such as outdoor compensation, control alarm deviations, time delays etc. 3 The highest user level giving total access. Used by the commissioning engineer for system configuration. 21

21 To log in to another user level. Press or until the cursor arrow points at Login. Press OK. The login menu will be displayed. Set your code 0000 Level:0 To log in press and a marker will be shown on the first digit. Press to change the value. Press OK to move to the next digit. To return to the previous digit press Esc. After the last digit the code is evaluated. The operation can be aborted by means of Esc. If an incorrect code is given an error message is displayed: Incorrect code try again The correct code will result in an acknowledging message showing the login level. Login ok Code:0 After 2 seconds the system automatically returns to the main menu. Factory set codes The codes for the three user levels are factory set as follows User level User level User level Changing codes The codes for the three user levels can easily be changed in user level 3. Enter the login menu: Set your code 0000 Level:3 The arrow means that there are menus below, press the arrow until the code for level 1, 2 or 3 is displayed. Code for level Code for level Code for level Change the code using.the cursor will start on the first digit. Change using the arrow buttons. To move to the next digit press OK. To return to the previous digit press Esc. By pressing OK after the last digit the code will be registered. To abort use Esc. DO NOT FORGET TO MEMORIZE THE NEW CODES or to write them down. This is especially important for user level 3. Should the code for level three be lost the system can be opened by means of a code number which can be obtained from REGIN. This code number is time dependent. Important! 22

22 Control funct. 0 Suppl.air cnt Config code Config code Configuration Configuration implies the commissioning setting of all the parameters in the CORRIGO. Parameters are set using script. Configuration codes There is also the option of setting parameters by means of two configuration codes. This function is particularly useful and time-saving when a number of controllers are to be configured in the same way. The first thing to be shown when the configuration menu is opened is the setting of the control function. Using the arrow up button the two configuration codes will be displayed and the arrow down button will give the parameters of the other configurations in script. The code digits in the configuration code correspond to the script parameters below in numerical sequence. This means that the first digit in CONFIG.CODE1 determines which control function the controller is to work with. The second digit refers to heater type etc. Before the corresponding selection in the script parameters there is a digit which corresponds to the code number in the configuration code. See the details below. Tables for configuration code There is also a special table to facilitate the choice of configuration code. This is always supplied together with the CORRIGO instruction sheet. In the table all the configuration parameters are shown as well as the selections that can be made. Basic selections are marked in bold type. By going through the parameters and filling in the figures beside the respective selections the configuration code can be obtained without difficulty. This can also act as a protocol of settings for CORRIGO. Automatic restart after changing When one or more parameters have been changed the controller will restart when the user leaves the configuration menu. CONFIGURATION-CORRIGO C40 A B C D. E F G H. I J K L Configuration code 1.. A Control function 0. Supply air control 0 1. Supply air control with outdoor temperature compensation 1 2. Room control with cascaded supply air temperature control 2 3. Room control with min/max limiting of supply air temp Room control, single sensor 4 5. Supply air control/room control. Outdoor temp dependent 5 6. Not available for Corrigo C40 - B Heater type 0. Water heater 0 1. Electric heater 1 C Output Y1 0. Not active 0 1. Heating 1 2. Damper 2 3. Cooling 3 D Output Y2 0. Not active 0 1. Plate heat exchanger 1 2. Rotating heat exchanger 2 3. Not available for Corrigo C40-4. Damper 4 5. Heating 5 6. Cooling 6 E Output Y3 0. Not active 0 1. Cooling 1 2. Heating 2 F Frost protection (Water heating only) 0. Not active 0 1. Active on Y Active on Y Active on Y1 with automatic alarm reset 3 4. Active on Y2 with automatic alarm reset 4 G Shutdown mode (Water heating only. Requires outdoor sensor) H Pump stop (Water heating only. Requires outdoor sensor) I Function not available for Corrigo C40 This code must always be set to 0 0 J DX-cooling 1. 1-step step step binary 3 K Cooling recovery L Free cooling 23

23 Configuration settings Some of the settings are only available on certain models. This because som of the inputs / outputs have different functions in different models. A. CONTROL FUNCTION B. HEATER TYPE C. SEQUENCE Y1 D. SEQUENCE Y2 E. SEQUENCE Y3 F. FROST PROTECTION G. SHUTDOWN MODE H. PUMP STOP I. FUNCTION NOT AVAILABLE FOR CORRIGO C40 J. ON/OFF-COOLING K. COOL RECOVERY L. FREE COOLING M. FUNCTION DI 6 / DO 6 N. FIRE ALARM O. FUNCTION DI 7 / DI 8 P. FUNCTION NOT AVAILABLE FOR CORRIGO C40 Q. FUNCTION NOT AVAILABLE FOR CORRIGO C40 R. DAYLIGHT SAVING TIME S. HUMIDITY CONTROL T. BASIC SETTING. Used to reset to factory values. A. The first question concerns the controller s control function. To change the parameter press, the marker appears by the digit. Press or to change to another control function. The various functions are described below. When the correct function has been selected, press OK to store. Application examples flow diagrams In all the examples below for the various control situations, water heating has been depicted with frost protection sensor, and electric heating with high temperature limiting/thermostat. All examples are drawn with rotating heat exchanger and water cooling. When configuring, the three output control sequences in CORRIGO are set individually to suit the appropriate application. Supply air temperature control The supply-air temperature sensor (AI6) controls the sequences to reach setpoint. Control funct. 0 Suppl.air cnt 0. Supply air temperature control Frost protection sensor 24

24 1. Supply air temperature control, outdoor temperature compensated. Supply air control with outdoor temperature compensation The temperature sensor Supply Air (AI6) controls the sequences to reach setpoint. The setpoint is compensated with respect to the temperature at outdoor temperature sensor (AI5). Parameters are set in the menu Temp control where menus for outdoor compensation will become accessible when this selection is made. Outdoor temperature compensation can be set with two breaking points and two end positions, see the section Temp control. Frost protection sensor Supply-air sensor 2. Room temperature control, cascade connected. Room temperature control with cascade control of the supply air temperature The temperature sensor Supply air (AI6) controls the sequence so that the setpoint is reached in the same way as with supply air control. The setpoint for the supply air temperature is determined by Room sensor (AI7) which, when heating is required, raises the setpoint for supply air according to the parameters set or, when cooling is required, lowers the setpoint. The cascade factor (by how much the setpoint should be changed on a one-degree deviation from the set room-temperature) is set under Temp control, see the appropriate section. N.B. Cascade control is a PI-control with settable I-time (Factory setting 10 minutes) and works with setpoints between set minimum and maximum limitation. (Current setpoint for supply air temperature is shown in the menu for cascade factor). Frost protection sensor Room sensor Supply-air sensor 25

25 Room-temperature control with min-/max limitation of supply-air temperature The room temperature sensor (AI7) controls the sequences so that the setpoint is reached. The supply-air temperature at the sensor (AI6) is kept within the set minimum and maximum limits. 3. Room temperature control with min/max limiting Frost protection sensor Room sensor Supply-air sensor Room temperature control without supply air sensor The temperature sensor Room (AI7) controls the sequences so that the setpoint is reached. 4. Room temperature control Frost protection sensor Room sensor Supply air temperature control with outdoor temperature compensation or room control with min/max limiting. Outdoor temperature dependent switchover The outdoor temperature sensor controls the change-over between supply air control (winter) and room control (summer). 1) The supply air sensor (AI6) controls the sequences to reach setpoint. The setpoint is outdoor temperature compensated by means of the outdoor temperature sensor (AI5). Parameters are set under the menu Temp. control. 2) The room sensor (AI7) controls the sequences to reach setpoint. The supply air temperature (AI6)can be min/max limited. Cooling is prevented from starting when the outdoor temperature is low. Parameters are set under Settings. 5. Room/supply air temperature control Frost protection sensor Room sensor Outdoor sensor Supply-air sensor 26

26 6. Exhaust air temp control with min/max limiting of the supply air temperature N.B. Not available for C30 and C40. This since AI3 is then used as humidity input. Exhaust air temperature control with minimum/maximum limiting of the supply air temperature The exhaust-air temperature sensor (AI3) controls the sequences to reach setpoint. The temperature at the supply-air sensor (AI6) is kept within the minimum/maximum temperatures set. Exhaust-air sensor Frost- protection sensor Supply-air sensor Heater type 0 Water heating B. Setting of heater type 0. Water heating. 1. Electric heating. When electric heating has been selected input A18 is set for closing contact from high temperature limit. The configuration parameters applicable to water heated circuits: frost protection sensor, shutdown mode, pump stop, are not shown when electric heating is selected. Control voltage Control voltage High limit thermostat Control relay Relay electric heating CORRIGO AI8 Wiring suggestion when using electric heating. High limit thermostat contacts drawn unactivated N.B. It is important that the high temperature limit switch is wired to dissconnect the power to the heater via a relay to ensure that the heating is properly disconnected when the limit switch is tripped. 27

27 Output signal Y1 Y2 Y3 Setpoint C. Output sequence Y1 0 When not in use 1. AO1 Heating 2. AO1 Damper 3. AO1 Cooling Temperature The function of the outputs can be set individually. The sequence order, however, is always the same: At increasing heat requirement Y3 is always activated first, then Y2 and finally Y1. Sequence Y1 1 AO1 Heating D. Output sequence Y2 0. When not in use Sequence Y2 1. AO2 Plate heat exchanger 1 AO2 Plateexch Means that the output controls e.g. a damper actuator for the heat exchanger bypass duct. Defrosting Ice-build up sensor is connected to DI4. On ice build-up the defrosting function is activated. -The heat exchanger is set to full bypass and the heating sequence works primarily when heating is required. If this is not sufficient to maintain the setpoint the heat exchanger is permitted to go in with up to 30% of capacity. -The fans continue operating. If the fans are of the two-speed type they will operate at low speed while the defrosting function is active. -Defrosting will continue until the ice build-up sensor returns to normal, with a deactivation delay of 10 minutes. If defrosting still is active after 30 minutes, the supply air fan will be shut off until the defrosting is completed. 2. AO2 Rot.Heat exchanger Alarm from the rotation sentinel is connected to input DI4. CORRIGO can be set to stop the fans on rotation sentinel alarm. Set under Settings 3. AO2 Liquid connected heat exchanger Extract air Exhaust air The valve is controlled in sequence and Sensor Return Exch Pump the temperature in the circuit is minimum limited via the sensor Return Exchanger connected to AI4. Control valve, exchanger N.B. This function can not be used with the CORRIGO C30 or C40 since there is no input for a minimum limiting sensor. Outdoor air Supply air 4. AO2 Damper Liquid connected exchanger 5. AO2 Heater 6. AO2 Cooler E. Sequence Y3 0. When not in use 1. AO3 Cooling 2. AO3 Heating Sequence Y3 1 AO3 Cooling 28

28 Frostprotection 1 Y1 Shutdown mode 0 No Pump stop 0 No Efficiency mon. 0 No This function can not be combined with liquid connected heat exchanger F. FROST PROTECTION 0. Not active 1. Y1 Y1 is forced open on frost risk 2. Y2 Y2 is forced open on frost risk 3. Y1 Aut Reset Y1 is forced open on frost risk. Automatic reset. 4. Y2 Aut Reset Y2 is forced open on frost risk. Automatic reset. The alarm limit for the frost protection sentinel is set under Settings. (Factory setting is 7 C.) The system begins to override the output signal to the valve when the temperature is 5K higher than the alarm limit. This means that the temperature when the output begins to be affected is 12 C for the factory setting of 7 C. G. SHUTDOWN MODE Controls the heating valve to maintain a preset temperature at the frost protection sensor when the system is shut down. The function is only activated if the circulation pump output DO3 is active. 0. No 1. Yes H. PUMP STOP The circulation pump is stopped when there is no heating demand and the outdoor temperature is above a preset temperature. The basic setting is +6 C. Activation delayed 15 minutes. Can be set under Settings. Stopped pump is exercised 5 minutes a day at 12 noon. This function requires an outdoor temperature sensor. 0. No 1. Yes I. EFFICIENCY MONITORING Not available for C30 and C40 Heat exchanger efficiency is calculated and presented under AI analogue in, on the last line. The function requires an outdoor sensor on AI5, an extract-air sensor on AI4 and, either an exhaust-air sensor on AI3, or a room sensor on AI7. So, if the CORRIGO has been configured for an application with room sensor it is not necessary to install an exhaust-air sensor. CORRIGO will automatically choose the room temperature sensor if an exhaust-air sensor has not been installed. At efficiency values <50% and full output on Y2 the alarm low efficiency is activated. 0. No 1. Yes Extract air Exhaust air temp temp T Exhaust - T Extract η= T Exhaus t - T Outdoor Outdoor temp 29

29 J. DX-COOLING The outputs DO4 and DO5 are used to control DX chillers in stages. 0. No 1. 1 stage 2. 2 stages 3. 3 stages binary K. COOLING RECOVERY The temperatures at the sensor Outdoor temp (AI5) and the Exhaust air sensor (AI3) are compared. If the exhaust air temperature is a preset number of degrees colder than the outdoor temperature the heat exchanger or mixing dampers will be set for maximum recovery. A heat exchanger will be set to full capacity and dampers to maximum recirculation. The value for minimum percentage outdoor air is set under the menu Settings. 0. No 1. Yes L. FREE COOLING If the night temperature at sensor Room (AI7) exceeds a preset temperature the supply and exhaust air fans are started to give free cooling. Heating, heat exchange and cooling are not used during free cooling. When two-speed fans have been configured the fans run at high speed during free cooling. Other prerequisites are that the outside temperature exceeds the preset value (basic setting +10 C.) to prevent condensation and that the outside temperature is a preset number of degrees lower than the room temperature (factory setting 3K). If this condition is not met, no cooling run will take place. 0. No 1. Yes M. FUNCTION INPUT DI6 OCH OUTPUT DO6 These can be changed for various functions. 0. External alarm + frost protection. DI6 receives an external alarm. The alarm is presented in the alarm queue as External alarm. DO6 is controlled to be on as long as the frost protection is in the normal position. When the frost alarm is activated the output is deactivated. This function is used when external switches for manual operation of the fans is desired. 1. Auto + Frost protection In this position DI6 receives a signal that external switches are not in the auto position. It is used primarily when the relay module RM6H-24/D with external switches is connected to the controller. If any one of the switches is not in the Auto position the alarm will be given after 5 minutes. DX Cooling 0 No N.B. Can not be combined with control of 2-speed fans in models C10 and C30 Cool recovery 0 No Free Cooling 0 No Funct. DI6/DO6 0 Ext.alarm+fro 2. Fire damper exercise DO6 is used to control fire dampers for exercising and testing. Exercising is carried out once every 24 hours at the time set under Settings. The basic setting is for 12 midnight. During the exercising the fans will be stopped even if free cooling is active. 30

30 Damper.. Damper 3 Damper 2 Damper 1 DO6 High Low High DI6 Low 0 90 max 5 minutes max 5 minutes DI6 Terminal 22 When exercising commences output DO6 is activated. Then the controller will wait for the damper s end position contact to open the input DI6. If the contacts do not open within 5 minutes the alarm will be given. After opening of the contacts has occured the controller will wait for the other set of contacts to close indicating that all dampers have reached the closed position. If the contacts do not close within 5 minutes the alarm will be given. After closing on DI6 has occurred DO6 is deactivated again and the controller will wait for the contacts to open again to input DI6. If the contacts do not open within 5 minutes the alarm will be given. After opening of the contacts has occured the controller will wait for the other set of contacts to close indicating that all dampers have once again reached the fully open position. If the contacts do not close within 5 minutes the alarm will be given. Fire alarm 0 Alarm only Function DI7/ Manual 0 Auto DI7 Fig 1. Switch for unit with single speed fans. High speed Low speed 0 Auto DI7 DI8 DI8 N. FIRE ALARM The signal from the fire alarm or smoke detector is connected to DI5. This function is used to set if fans are to continue running or are to be stopped in the event of alarm. 0. Alarm only (the fans continue to run). 1. Supply fan + Exhaust fan Stop 2. Supply fan Stop 3. Exhaust fan Stop O. FUNCTION DI7 / DI8 DI7 and DI8 are used for extended running when the scheduler is deactivated. For single speed fans DI7 is used for extended running.di7 controls extended running at normal speed while DI8 controls extended running at reduced speed. DI8 also has the following function at both low and high speed; If input DI8 is closed at the same time as DI7 is closed a stop signal will be given. This function can be used, for example, when an external, common Manual-0-Auto switch is mounted in the cabinet. See wiring suggestion for this type of switch fig.1. When an external switch as in fig.1 is used FUNCTION DI7/8 must be configured as 2 Timer. 0. This function is not used 1. Push button. Instantaneous closure gives extended running for preset time. (Factory setting 0 min). 2. Timer Extended running as long as the contact is closed. Fig 2. Switch for unit with two speed fans. 31

31 P. TWO-SPEED FANS (C10 and C30 only) Cannot be selected when DX-cooling has been configured. When two-speed fans are used the scheduler menu is automatically complemented with periods for low speed running. See under Scheduler. On startup the exhaust air fan will be started first, at low speed. After a preset time the supply air fan will start, at low speed. Should the scheduler or external switches/timer be set for high speed running the exhaust air fan will switch to high speed followed by the supply air fan.high speed is activated 1 second after low speed has been deactivated. When switching from high speed to low speed both fans are first switched off. After a retardation period of 10 seconds, low speed is activated for both fans. When free cooling is activated both fans run at high speed. The fans can be forced to low-speed at low outdoor temperatures. See under Settings 0. No 1. Yes Q. EXTERNAL SETPOINT (C10 and C20 only) When external setpoint is to be used. Set point device TG-R4/Pt1000 is connected to AI4. This function cannot be combined with efficiency monitoring or liquid connected heat exchanger. 0 No 1 Yes R. DAYLIGHT SAVING TIME The timer takes account of the spring and autumn time changes that are generally implemented according to European rules. Spring: At on the last Sunday in March the clock moves forward one hour. Autumn: At on the last Sunday in October the clock moves backwards one hour. If this function is not required set to 0 No. Two speed fans 0 No External setp 0 No Daylight saving 1 Yes 0. No 1. Yes S. HUMIDITY CONTROL (C30 and C40 only) Output AO6 is used for controlling dehumidification, humidification or humidification in combination with dehumidification by control of the output AO1...AO3 which is configured as a cooling output. 0. Humidification (AO6) / Dehumidification (by control of cooling output AO1...AO3) 1. Humidification (AO6) 2. Dehumidification (AO6) T. BASIC SETTING Use this function to reset to factory settings. Press the change button, choose Yes and confirm with OK. To abort at the change stage, press Esc. All parameters and settings revert to the original factory settings if the command Basic Settings is used. This command should only be used by the commissioning engineer. Humidity contr. 0 Humid/dehumid Basic setting No N.B Important! 32

32 Temperature control In this menu you can look at and set most control values for the temperature control. See also menu branch Settings. The control function that has been chosen and the selected login level will determine which of the following menus can be seen and which parameters can be set. The table shows all the menus and the control functions with which they are shown. Table of control functions 0. Supply air control 1. Supply air control with outdoor temperature compensation 2. Room temperature control with cascade function of supply air temperature 3. Room temperature control with minimum/maximum limiting of supply air temperature 4. Room temperature control without supply air sensor 5. Supply air control with outdoor compensation or room temperature control. Change-over point is outdoor temperature dependent. 6. Room temperature control with minimum/maximum limiting of supply air temperature. Setpoint/Actual 20.0 C/20.0 C 1. Setpoint/Actual temp. Control function 0,2,3,4. 2. Calculated setpoint/actual temp. Control function 1,5,6. 3. Output % for Y1,Y2,Y3. Control function 0,1,2,3,4,5,6. If the output is not used this will be shown as. 4. Setpoint Supply air/compensation. Control function 1,5. 5. Setpoint/Actual value of supply air. Control function Setpoint Room/Change-over temp. Control function Minimum/Maximum limiting. Control function 2,3,5,6. 8. P-band/I-time/Neutral zone. Control function 0,1,2,3,4,5,6. 9. Room P-band/I-factor. Control function 5 These factors set the P-band and I-time for the room temperature controller in control function 5. They are multiplication factors applied to the equivalent parameters set for supply air control in menu 8 above. 10. Cascade factor/i-time. Control function Outdoor temperature compensation. Breakpoint 1. Control function 1, Outdoor temperature compensation. Breakpoint 2. Control function 1, Outdoor temperature compensation. Breakpoint 3. Control function 1, Outdoor temperature compensation. Breakpoint 4. Control function 1,5. Setpoint Outdoor temp The breakpoints must be placed with 1 lowest and 4 highest. For each point both the temperature and compensation in degrees has to be set. For temperatures lower than point 1 and higher than point 4 the compensation is constant and equal to the value set for these points. 33

33 Pressure control C20 and C40 only In this menu you can look at and set most control values for the pressure control. See also menu branch Settings. The control function that has been chosen and the selected login level will determine which of the following menus can be seen and which parameters can be set. The table shows all the menus and the control functions with which they are shown. 1 SF Setp/Act/Out. Setpoint/Actual pressure/output status for the supply air fan control signal. Setpoint can not be changed in this menu. 2. EF Setp/Act/Out. Setpoint/Actual pressure/output status for the exhaust air fan control signal. Setpoint can not be changed in this menu. 3. Setpoint SF/EF. Menu for setting the desired supply air and exhaust air pressures for normal air flow. 4. Reduced SF/EF. Menu for setting the desired supply air and exhaust air pressures for reduced air flow. 5. SF P/I/D. Control parameters P-Band, I-Time and D-Factor for the supply air fan control. 6. EF P/I/D. Control parameters P-Band, I-Time and D-Factor for the exhaust air fan control. 7. Outdoor temperature compensation. Breakpoint Outdoor temperature compensation. Breakpoint Outdoor temperature compensation. Breakpoint Outdoor temperature compensation. Breakpoint 4. SF Setp/Act/Out 200Pa/190Pa/90% The breakpoints must be placed with 1 lowest and 4 highest. For each point both the outdoor temperature and compensation in Pa (+/-) has to be set. All breakpoints have factory set values that can easily be changed if necessary. For temperatures lower than point 1 and higher than point 4 the compensation is constant and equal to the value set for these points. Setpoint pressure Example, compensation curve Outdoor temperature Humidity control In this menu all the parameters for the humidity control can be set and are displayed. 1. Setpoint / Actual value Setpoint and actual value for the room humidity sensor (main sensor). 2. Maximum limit / Actual value Setpoint and actual value for the duct humidity sensor (limiting sensor). 3. Humidification / Dehumidification Output status for humidification and dehumidification signals. 4. P-band / I-time. Humidity control control parameters. C30 and C40 only Setpoint/Actual 55%RH/ 54%RH 34

34 Running mode Running mode Auto / On Can be read without logging in. Can be changed from user level 1 and higher. In this menu the unit s running mode can be seen and set to manual control. On the left the display shows Auto/Manual and on the right the present running mode. The running modes AUTO/NORMAL/REDUCED/OFF can be set. In the normal AUTO position the running mode is set by the scheduler or by input signals on DI7/ DI8 for extended running. If the setting is not reset to AUTO mode within 15 seconds an alarm will be activated. AI Analogue inputs In this menu the current input values on the analogue inputs are displayed. AI1 Supply-air fan pressure. C10 and C30 display On or Off, C20 and C40 display the current pressure. AI2 Exhaust-air fan pressure. C10 and C30 display On or Off, C20 and C40 display the current pressure. The inputs AI1 and AI2 must be wired to pressure transmitters (C20 and C40), pressure switches or other free contacts (C10 and C30) that are closed when the fans are running since they control functions vital to the running of CORRIGO. AI3 Exhaust air temperature (C10 and C20) or Room humidity sensor. (Main sensor) (C30 and C40). AI4 Extract air temperature (C10 and C20) or Duct humidity sensor. (Limiting sensor) (C30 and C40). AI5 Outdoor temperature sensor AI6 Supply air temperature sensor AI7 Room temperature sensor AI8 Frost protection sensor For water heating when frost protection has been chosen or High temperature limit. When electric heating has been chosen. Adjustment of sensor input values The values displayed for the inputs AI1 to AI8 can be changed by +/- 2.0 units. Log in to user level 3, go the the applicable sensor input AI3 to AI8, press. Adjust the display value using or. When completed, confirm using OK. Bear in mind that CORRIGO is always supplied with factory calibrated inputs. This applies also to sensor inputs thus no adjustment is normally necessary. In rare cases where,for example, long sensor leads give incorrect readings, however, the option to make adjustments is available. Be sure to measure the temperature at the sensor with a reliable and carefully calibrated measuring instrument and to check that the temperature at the sensor is stable at the time of measurement. Damping of sensor input values A damping factor can be set individually on any of the inputs if the readings show disturbing fluctuations. Set under the menu Settings. See page 43. Show min/max values Show Min/Max-temperatures for AI3...AI8. The lowest and highest values encountered since the last activation of the function are stored and will be displayed for each input. To reset and start a new logging, press and then confirm with OK. Both values will be set to the present input value. 35

35 DI Digital inputs DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 Filter guard (s) (Pressure switch monitoring the pressure drop across a filter) If there are several filter guards they should be wired in parallel Run indication for water circulation pump Must be connected when water heating is used. Pump standstill will prevent the system from running Alarm input from chiller (-s) Rotation sentinel or heat exchanger ice build-up sentinel Fire alarm External alarm, external switches not in Auto position or end position switches in fire dampers (for fire damper exercising) Pushbutton or timer for extended running at normal speed Pushbutton or timer for extended running at reduced speed AO Analogue outputs In this menu the current configurations and outputs for the analogue outputs are shown. The outputs are shown both in V DC and in %. AO1 Y1 - Heating, cooling or mixing dampers AO2 Y2 - Heating, plate exchanger, rotating exchanger, liquid connected exchanger or cooling AO3 Y3 - Heating or cooling AO4 Output signal for supply air fan pressure control (C20 and C40 only) AO5 Output signal for exhaust air fan pressure control (C20 and C40 only) AO6 HumidIfication or dehumidification (C30 and C40 only) The outputs AO1...AO3 can also be set to -, indicating that they are not in use. DO Digital outputs DO1 DO2 DO3 DO4 DO5 DO6 DO7 Start supply-air fan (High speed for 2-speed fan in C10 and C30). Start exhaust-air fan (High speed for 2-speed fan in C10 and C30). Control of circulation pump or electric heating interlock. Must be wired when water heater is used. Stopped pump will force the CORRIGO to shut-down mode. Control of chiller 1 (DX1) or Start supply-air fan, low speed for 2-speed control in C10 and C30. Control of chiller 2 (DX2) or Start exhaust-air fan, low speed for 2-speed control in C10 and C30. External frost protection interlock or fire damper exercising. Function see page 36, Function DI6/DO6. Alarm output relay 36

36 Setting outputs manually Both digital and analogue outputs can be set to manual mode for testing and for temporary running. AO1 Heating AUTO/ 50%/5.0 V DO1 SF AUTO OFF 1. Analogue outputs To set to manual mode press and change to HAND using or. Then press OK and confirm, then change the output value using the arrow buttons. Confirm the setting using OK. To revert to normal running mode press again and change to AUTO using or. Confirm using OK. If the setting is not reset to the AUTO mode within 15 seconds, an alarm will be activated. 2. Digital outputs To set to manual mode press and change to the desired mode ON or OFF using or. Then press OK and confirm. To return to normal running mode press again and change to AUTO using or. Confirm using OK. If the setting is not reset to the AUTO mode within 15 seconds, an alarm will be activated. 37

37 Scheduler CORRIGO has a year-base clock. This means that a week-schedule, individual holidays and holiday periods for a full year can be set. 1. Clock Accessible from user level 1. Here weekday, date and time are set. Clock Th :25 2. Scheduler period 1,2,3. Accessible from user level 2. For setting week-schedule. CORRIGO has 3 setting periods for week-schedule. Select using. Use or to determine whether or not the day displayed is to be included in the required week-schedule. When the first day has been selected/rejected confirm the setting using OK. The marker will then move on to the next day which is set in the same way, using the arrow buttons and confirming with OK. Move through all the settings in the menu using OK and select those required. The letter H signifies Holiday. This is set by means of the date settings. Periods 2 and 3 are used if separate running times for other days are required. Example: The system is to be running Monday to Friday from till 17:00 and Saturday from 8.00 till Do as follows: Set period 1 to: and period 2 to: Period 1 08:00 MTWTF -17:00 Period 1 07:00 MTWTF -17:00 Period 1 08:00 S -13:00 Using an external clockfunction If the CORRIGO is to be used with an external clock instead of the internal one all periods must be set to zero according to the following example. Period 1 00:00-00:00 3. Reduced 1, 2, 3 3 periods for programming reduced speed running will be displayed. Setting and function as described above but for reduced speed running. If the set times for normal running and reduced speed running overlap, normal speed running will be chosen. Reduced1 17:00 MTWTF -18:30 38

38 Holiday 1 / / Dates for holidays. Accessible from user level 2. A total of 10 individual holidays can be selected. Running time during a holiday is set by programming the day H into one of the three scheduler periods. If the system is to be closed down during a holiday no setting will be necessary for that holiday scheduler period. Holiday period Holiday periods. Accessible from level 2 and up. For longer holiday periods, e.g. the Christmas break, Summer holidays etc. the first and last dates of the period are set. Set the running times in the time period 1,2, or 3 above for the days that the holiday programme is to apply. If the system is to be closed down during a holiday no setting of schedule period will be necessary. 39

39 Alarm settings Here all settings for the alarm system are set including alarm parameters, delays, suppression times etc. 1. Temperature deviation alarm Should the actual temperature differ from the setpoint by more than the set value an alarm will be activated after a set time. 2. Outdoor temperature range within which the temperature deviation alarm can be activated To prevent alarms when the outdoor temperature leads to conditions beyond the system capacity. Example: If a system for supply air control does not have cooling an alarm will be given when the outside temperature exceeds 20 to 25 degrees since the temperature cannot be reduced. To avoid a false alarm the upper temperature limit is set at 20 degrees in this case. The same is true at the other extreme. If the outside temperature should fall below the set temperature a false alarm can be avoided by setting the lowest outside temperature limit to this temperature. N.B. This function is not available unless an outdoor sensor is connected to CORRIGO. 3. Pressure deviation alarm (C20 and C40 only) Should the actual pressure differ from the setpoint by more than the set value an alarm will be activated after a set time. 4. Alarm suppression Supply air fan A fan pressure deviation alarm is suppressed by a set time to avoid the alarm stopping the fan during start up before the pressure has reached the normal level. 5. Alarm suppression Exhaust air fan As for supply air fan above 6. Alarm output suppression The alarm output relay can be blocked so that unprioritised alarms will only be forwarded during the set time and not during the night or weekends, for example. Outside the set period only frost alarm, high temperature alarm and fire alarm will activate the alarm relay. Set the times in this menu when alarms are forwarded to the alarm relay output. Example: An alarm is only to activate the alarm output between and 17.00, Monday to Friday. The setting will be as follows: Temp.dev. alarm 5.0K / 2 min Outd.Temp range 20.0 C/-20.0 C Press.dev.alm 50 Pa / 2 min Alarm delay SF 30 sec Alarm delay EF 30 sec Alarm out 08:00 MTWTF -17:00 N.B. Even if the alarm output is blocked the alarm will be registered and indicated by the red flashing alarm diode and the alarm list menus will function as normal. 40

40 Stop Exch alarm No 7. Stop on alarm from rotating heat exchanger An alarm from a rotating heat exchanger can initiate a complete stop of the unit. This to prevent running at too low a temperature. Heat exchanger malfunction can also lead to unneccessarily high running costs which is avoided by stopping the unit when an alarm is indicated on input DI4. The function is only available if rotating heat exchanger has been configured. Alarms -Overview Operational failure Supply air fan AI1 Operational failure Exhaust air fan AI2 Operational failure, pump DI2 With water heater Frost protection AI8 With water heater High temperature limit AI8 With electric heater Fire alarm DI5 Fire damper DI6 Rotation sentinel, heat exchanger DI4 Chiller DI3 External alarm DI6 When DI6 is configured for external alarm Sensor failure AI3-AI8 Temperature deviation Pressure deviation Output in manual mode Manual running mode Switch not in Auto mode DI6 When DI6 is configured for this, external switch. 41

41 Settings This menu contains various settings that are normally only set at the comissioning of the CORRIGO. Which alternatives are shown depends on the model and the configuration settings. 1. Setpoint, frost protection function. Only when water heating with frost protection has been configured.see also pages 27 and 29. Factory setting 7 C. Range C. 2. Setpoint shutdown control. Only when water heating with frost protection has been configured.see also pages 27 and 29. Factory setting 25 C. Range C. 3. Pump stop. Only when water heating has been configured. Outside temperature above which the pump is permitted to stop with no heating requirement, i.e. output heat is less than 1%. Delay time for the pump can also be set. Factory setting 6 C. and 15 minutes. Range C. and min. 4. Supply air fan run on time for cooling electric heater. Only if electric heating has been configured. Factory setting 120 sec. Range sec. 5. Supply air fan delay at normal start up. Period for which heat exchanger is to run at 100% at start up. Startup is normally done with only the exhaust-air fan running. With C20 and C40 the fan will be running at reduced flow. With C10 and C30 the fan will be running at low speed it two-speed running has been configured, otherwise at normal speed. After the set time the supply-air fan is started at reduced flow level(c20 and C40)/ low speed (C10 and C30) if two-speed running has been configured. If the fans shall run at normal speed the exhaust-air fan will now switch to normal speed and 5 seconds later also the supply-air fan. If any of the temperature control outputs has been configured as heat exchanger, this output will at startup be set to 100%, that is to maximum heat exchange, for the set time. The other outputs will be held at 0 % output until the supply-air fan is started. If a cooling demand is at hand, the cooling output will not be activated until the exchanger startup period has run out. Factory setting 60 sec. and 90 sec. Range sec. and sec. 6. Extended running. When set for DI7/DI8 using pushbutton. See page 30. Sets required running time after using push button. The function is not additive i.e. multiple pressings of the button will not give longer running time. Factory setting 0 min. Range min. 7. P-band Y2,Y3. Factor of P-band for Y1. Multiplication factor compared to the proportional band set for output Y1. Does not normally need setting. Option available for plants where control enhancement for respective devices are different. Factory setting 0.5 / 0.5. Range and Minimum fresh air percentage when using mixing dampers on Y1 or Y2. See page 30. Factory setting 0%. Range %. 9. Free cooling. Lowest outdoor temperature and differential between room and outside temperature. See page 30. Factory setting 10 C. and 3K. Range C and K. 10.Free cooling. Setpoint for room temperature. See page 30. Factory setting 21 C. Range C. 11.Cooling recovery. Differential outdoor temperature/room temperature. See page 30. Factory setting 2K. Range K. 42

42 12.DX cooling. Minimum on and off times. See page 30. Factory setting 5 min. and 5 min. Range min and min. 13.Lowered minimum limit by DX cooling. See page 30. For control configurations with minimum limiting of the supply-air temperature (control functions 2, 3, 5 and 6) the minimum limit temperature will be lowered by the set number of degrees when the cooling is activated. This is to reduce the risk of the minimum limit causing a premature stopping of the cooling. Factory setting 5 K. Range K. 14.DX cooling.minimum outdoor temperature. Control function 5 only. At outdoor temperature lower than the set value the DXcooling outputs will not be activated. Factory setting 12 K. Range C. 15.Time for fire damper exercise. Factory setting 12 midnight. Can be set at any given time during the day or night. 16.Min. temp and P-band for liquid connected exchanger Factory setting 2 C and 5K Range C and 0...5K 17.Force low speed on fans when outdoor temp. is lower than set value. Factory setting Yes / -10 C. Range Yes/No and C 18.Range SF/EF. Pressure range for SF and EF pressure transmitters Factory setting 500/500 Pa. Range Pa 19.Damping factor, Analogue inputs AI1...AI8 Factory setting 1. Range Inversion of function for digital inputs DI1...DI8 Factory setting +. (Closed contact activates function/alarm) 21.Show Min/Max-temperatures for AI3...AI8. The lowest and highest values encountered since the last activation of the function are stored and will be displayed for each input under the menu Analogue in. Factory setting No. Range Yes or No LED s The LEDs are connected to the functions of certain in- and outputs. Normal running indication is yellow. A red LED signifies an error. From the text strip, cut out a part that suits the programmed configuration. Insert the strip through the rectangular slot above the text windows to the left of the LEDs. Diode Text Function yellow Function red 1 SF Supply fan on SF error 2 EF Exhaust fan on EF error 3 Pump Pump on Pump error 4 Y1 Output Y1 Over temp limit Heating or frost protection 5 Y2 Output Y2 Alarm Exch Blinks on defrost Heat exchanger 6 Y3 Cool Output Y3 Alarm chiller 7 Filter --- Filter alarm Alarm Alarm active 43

43 Relay modules Relay modules for digital outputs CORRIGO has digital outputs DO1 to DO6 carrying 24 V AC with up to 0.5 A. If higher voltage and/or capacity is required, relay module RM6-24/D or RM6H-24/D can be used. Model RM6-24/D contains 6 relays with change-over relays 10A / 230V AC. Model RM6H-24/D is as RM6-24/D but also has manual switches on the front, MANUAL-0-AUTO. When the relay module RM6H-24/D with manual switch is used in conjunction with CORRIGO, output DU6 must be configured for frost protection output and DI6 to receive the alarm switch not in AUTO-mode. The switch for DU6 on the relay module must always be in the AUTO mode. Model RM6-24/D Model RM6H-24/D RM6-24/D Relay unit intended for direct connection to CORRIGO Supply voltage 24V AC +/- 15% Consumption 3VA Ambient temperature 0-50 deg.c. Storage temperature deg.c. Ambient humidity Maximum 90% RH Dimensions (w x h x d) 105 x 110 (incl.terminal) x 59 mm Protection class IP20, for front mounting IP40 Mounting On a DIN-rail in a cabinet or normal housing. On cabinet front using mounting kit FMC. Connections Disconnectable terminal strips Inputs 6 in number, 24V AC from digital outputs on CORRIGO Outputs 6 in number, potential free change-over contacts 10 A / 230 V AC. RM6H-24/D Relay unit as above but with 6 Manual-0-Auto switches. The unit is 70 mm deep including the switches. This product conforms with the requirements of European EMC standards CENELEC EN and EN and carries the CE mark. This product conforms with the requirements of European LVD standards IEC and IEC

44 45 Wiring diagrams for relay modules DO3 NO NC DO4 NO NC DO5 NO NC NC NO DO2 NC NO DO1 NC NO 32 DO DO1 C1/2 DO2 DO3 C3/4 DO4 DO5 C5/6 DO V~ 24V~ 10A 250 V ~ RM6-24/D DO1 C1/2 DO2 DO3 C3/4 DO4 DO5 C5/6 DO6 Corrigo DO3 NO NC DO4 NO NC DO5 NO NC NC NO DO2 NC NO DO1 NC NO 32 DO DO1 C1/2 DO2 DO3 C3/4 DO4 DO5 C5/6 DO V~ 24V~ 10A 250 V ~ DO1 C1/2 DO2 DO3 C3/4 DO4 DO5 C5/6 DO6 Corrigo DI6 DI+ Auto Auto RM6H-24/D

45 Commissioning protocol Installation System Commiss. date Commiss. by Page 1 Configuration Factory setting Commissioning setting Config.code Config.code A. CONTROL FUNCT. 0 Supply air control B. HEATER TYPE 0 Water heater C. SEQUENCE Y1 1 Heating D. SEQUENCE Y2 1 Plate-exchanger E. SEQUENCE Y3 1 Cooling F. FROST PROTECTION 1 Y1 G. SHUTDOWN MODE 1 Yes H. PUMP STOP 0 No I. EFF MONITORING 0 No J. DX-COOLING 0 No K. COOLING RECOVERY 0 No L. FREE COOLING 0 No M. FUNCT. DI6/DU6 0 Ext.alarm+frost prot. N. FIRE ALARM 1 SF+EF Stop O. FUNCTION DI7/DI P. 2-SPEED FANS 0 No Q. EXTERNAL SETPOINT 0 No R. DAYLIGHT SAVING 1 Yes S. HUMIDITY CONTROL 0 Humidif/Dehumidification BASIC SETTING No Used to reset to factory settings C10 and C20 only C10 and C30 only C10 and C20 only C30 and C40 only Control Temp Setpoint / Actual 20.0 Min.limit / Max.limit 10.0 C / 30.0 C / PBand / Itime / Nz 20K / 60s / 2K / / Room P/I Factor 0.5 / 2.0 Casc.f / Itime 2.0 / --- Setp.Room/ Outdoor temp 22.0 / 12.0 Outdoor comp. point 1-20 C / 0.0 C Outdoor comp. point 2 20 C / 0.0 C Outdoor comp. point 3 25 C / 0.0 C Outdoor comp. point 4 30 C / 0.0 C Control Pressure Setpoint SF/EF 300 / 300Pa / Reduced SF/EF 200 / 200Pa / SF P / I / D 200Pa / 60s / 0.0 / / EF P / I / D 200Pa / 60s / 0.0 / / Outdoor comp. point 1-20 C / 0Pa Outdoor comp. point 2 20 C / 0Pa Outdoor comp. point 3 25 C / 0Pa Outdoor comp. point 4 30 C / 0Pa Control Humidity Setpoint / Actual --- / Max.limit / Actual 80%RH / --- / PBand / Itime 40%RH / 60s / C20 and C40 only C30 and C40 only 46

46 Commissioning protocol Installation System Commiss. date Commiss. by Page 2 Scheduler Factory setting Commissioning setting Period 1 MTWTF 08:00-17:00 Period 2 Period 3 Reduced speed 1 Reduced speed 2 Reduced speed 3 Holidays Alarm settings 1. Temp deviation alarm 5K och 2 minutes 2. Outdoor temp interval within which temp deviation alarm is active C 3. Pressure deviation alarm 50Pa / 2 minutes 4. Alarm delay, supply air fan 30 seconds 5. Alarm delay, exhaust air fan 30 seconds 6. Alarm output active Mo-Su 00:00-24:00 7. Stop on exchanger alarm No Settings 1. Setpoint frost protection 7 C 2. Setpoint shut-down mode 25 C 3. Pump stop. Min outdoor temp, 6 C start- stop delay 15 minutes 4. Cool-down (electric heating) 120 seconds 5. Delay supply air fan 60 seconds time with 100% Exch. at start 90 seconds 6. Extended running.pushbutton 0 minutes 7. P-band Y2,Y3. Factor 0,5 / 0,5 8. Min outdoor air, mix. damper Y2 0 % 9. Free cooling. Min outdoor temp 10 C difference outdoor/indoor 3 K 10.Free cooling. Setpoint room 21 C 11.Cooling recovery. Diff outdoor-/exhaust air temp 2 K 12.DX-cooling. Min. on-/off-times 5 min. and 5 min. 13.DX-cooling. Lowered min.lim. 5 K 14.DX-cooling. Min. outdoor temp. 12 C 15.Starttime damper exercising. 00:00 16.Min-temp and P-band, liquid conn. exch. 2 C and 5K 17.Force fan low speed on low outdoor temp Yes / -10 C 18.SF/EF pressure range 500/500 Pa 19.Damping factor AI1...AI8 1 _/ _/ _/ _/ _/ _/ _/_ 20.Function DI1...DI8 + _/ _/ _/ _/ _/ _/ _/_ 20.Show Min/Max-temp AI3...AI8 No 47

47 CONFIGURATION- Corrigo C10 A B C D. E F G H. I J K L Configuration code 1.. A Control function 0. Supply air control 0 1. Supply air control with outdoor temperature compensation 1 2. Room control with cascaded supply air temperature control 2 3. Room control with min/max limiting of supply air temp Room control, single sensor 4 5. Supply air control/room control. Outdoor temp dependent 5 6. Exhaust air control with min/max limit of supply air temp 6 B Heater type 0. Water heater 0 1. Electric heater 1 C Output Y1 0. Not active 0 1. Heating 1 2. Damper 2 3. Cooling 3 D Output Y2 0. Not active 0 1. Plate heat exchanger 1 2. Rotating heat exchanger 2 3. Liquid connected heat exchanger 3 4. Damper 4 5. Heating 5 6. Cooling 6 E Output Y3 0. Not active 0 1. Cooling 1 2. Heating 2 F Frost protection (Water heating only) 0. Not active 0 1. Active on Y Active on Y Active on Y1 with automatic alarm reset 3 4. Active on Y2 with automatic alarm reset 4 G Shutdown mode (Water heating only) H Pump stop (Water heating only. Requires outdoor sensor) I Efficiency monitoring J DX-cooling 1. 1-step step step binary 3 K Cooling recovery L Free cooling 48

48 CONFIGURATION- Corrigo C10 M N O P. Q R S Configuration code 2. 0 M Function DI6/DO6 0. External alarm & frost protection 0 1. Auto position & frost protection 1 2. Fire damper exercising N Fire alarm 0. Alarm only 0 1. Alarm + supply air and exhaust air fans stop 1 2. Alarm + supply air fan stops 2 3. Alarm + exhaust air fan stops 3 O Function DI7/DI8 0. Not active 0 1. Pushbutton 1 2. Timer 2 P 2-speed fans (Can not be combined with DX-cooling) Q External setpoint R Daylight saving time S This function is not available for Corrigo C10 The code must always be set to

49 CONFIGURATION- Corrigo C20 A B C D. E F G H. I J K L Configuration code 1.. A Control function 0. Supply air control 0 1. Supply air control with outdoor temperature compensation 1 2. Room control with cascaded supply air temperature control 2 3. Room control with min/max limiting of supply air temp Room control, single sensor 4 5. Supply air control/room control. Outdoor temp dependent 5 6. Exhaust air control with min/max limit of supply air temp 6 B Heater type 0. Water heater 0 1. Electric heater 1 C Output Y1 0. Not active 0 1. Heating 1 2. Damper 2 3. Cooling 3 D Output Y2 0. Not active 0 1. Plate heat exchanger 1 2. Rotating heat exchanger 2 3. Liquid connected heat exchanger 3 4. Damper 4 5. Heating 5 6. Cooling 6 E Output Y3 0. Not active 0 1. Cooling 1 2. Heating 2 F Frost protection (Water heating only) 0. Not active 0 1. Active on Y Active on Y Active on Y1 with automatic alarm reset 3 4. Active on Y2 with automatic alarm reset 4 G Shutdown mode (Water heating only. Requires outdoor sensor) H Pump stop (Water heating only. Requires outdoor sensor) I Efficiency monitoring J DX-cooling 1. 1-step step step binary 3 K Cooling recovery L Free cooling 50

50 CONFIGURATION- Corrigo C20 M N O P. Q R S Configuration code M Function DI6/DO6 0. External alarm & frost protection 0 1. Auto position & frost protection 1 2. Fire damper exercising N Fire alarm 0. Alarm only 0 1. Alarm + supply air and exhaust air fans stop 1 2. Alarm + supply air fan stops 2 3. Alarm + exhaust air fan stops 3 O Function DI7/DI8 0. Not active 0 1. Pushbutton 1 2. Timer 2 P Function not available for Corrigo C20 This code must always be set to 0 0 Q External setpoint R Daylight saving time S This function is not available for Corrigo C20 The code must always be set to

51 CONFIGURATION- Corrigo C30 A B C D. E F G H. I J K L Configuration code A Control function 0. Supply air control 0 1. Supply air control with outdoor temperature compensation 1 2. Room control with cascaded supply air temperature control 2 3. Room control with min/max limiting of supply air temp Room control, single sensor 4 5. Supply air control/room control. Outdoor temp dependent 5 6. Not available for Corrigo C30 - B Heater type 0. Water heater 0 1. Electric heater 1 C Output Y1 0. Not active 0 1. Heating 1 2. Damper 2 3. Cooling 3 D Output Y2 0. Not active 0 1. Plate heat exchanger 1 2. Rotating heat exchanger 2 3. Not available for Corrigo C30-4. Damper 4 5. Heating 5 6. Cooling 6 E Output Y3 0. Not active 0 1. Cooling 1 2. Heating 2 F Frost protection (Water heating only) 0. Not active 0 1. Active on Y Active on Y Active on Y1 with automatic alarm reset 3 4. Active on Y2 with automatic alarm reset 4 G Shutdown mode (Water heating only. Requires outdoor sensor) H Pump stop (Water heating only. Requires outdoor sensor) I Function not available for Corrigo C30 This code must always be set to 0 0 J DX-cooling 1. 1-step step step binary 3 K Cooling recovery L Free cooling 52

52 CONFIGURATION- Corrigo C30 M N O P. Q R S Configuration code 2. 0 M Function DI6/DO6 0. External alarm & frost protection 0 1. Auto position & frost protection 1 2. Fire damper exercising N Fire alarm 0. Alarm only 0 1. Alarm + supply air and exhaust air fans stop 1 2. Alarm + supply air fan stops 2 3. Alarm + exhaust air fan stops 3 O Function DI7/DI8 0. Not active 0 1. Pushbutton 1 2. Timer 2 P 2-speed fans (Can not be combined with DX-cooling) Q Function not available for Corrigo C30 This code must always be set to 0 0 R Daylight saving time S Humidity control 0. Humidification / Dehumidification 0 1. Humidification 1 2. Dehumidification 2 53

53 CONFIGURATION- Corrigo C40 A B C D. E F G H. I J K L Configuration code A Control function 0. Supply air control 0 1. Supply air control with outdoor temperature compensation 1 2. Room control with cascaded supply air temperature control 2 3. Room control with min/max limiting of supply air temp Room control, single sensor 4 5. Supply air control/room control. Outdoor temp dependent 5 6. Not available for Corrigo C40 - B Heater type 0. Water heater 0 1. Electric heater 1 C Output Y1 0. Not active 0 1. Heating 1 2. Damper 2 3. Cooling 3 D Output Y2 0. Not active 0 1. Plate heat exchanger 1 2. Rotating heat exchanger 2 3. Not available for Corrigo C40-4. Damper 4 5. Heating 5 6. Cooling 6 E Output Y3 0. Not active 0 1. Cooling 1 2. Heating 2 F Frost protection (Water heating only) 0. Not active 0 1. Active on Y Active on Y Active on Y1 with automatic alarm reset 3 4. Active on Y2 with automatic alarm reset 4 G Shutdown mode (Water heating only. Requires outdoor sensor) H Pump stop (Water heating only. Requires outdoor sensor) I Function not available for Corrigo C40 This code must always be set to 0 0 J DX-cooling 1. 1-step step step binary 3 K Cooling recovery L Free cooling 54

54 CONFIGURATION- Corrigo C40 M N O P. Q R S Configuration code M Function DI6/DO6 0. External alarm & frost protection 0 1. Auto position & frost protection 1 2. Fire damper exercising N Fire alarm 0. Alarm only 0 1. Alarm + supply air and exhaust air fans stop 1 2. Alarm + supply air fan stops 2 3. Alarm + exhaust air fan stops 3 O Function DI7/DI8 0. Not active 0 1. Pushbutton 1 2. Timer 2 P Function not available for Corrigo C40 This code must always be set to 0 0 Q Function not available for Corrigo C40 This code must always be set to 0 0 R Daylight saving time S Humidity control 0. Humidification / Dehumidification 0 1. Humidification 1 2. Dehumidification 2 55

55 Index A AI Analogue inputs 15, 35 Alarm settings 40 Alarms 21 Alarms -Overview 41 AO Analogue outputs 17, 36 Arrow-buttons 19 Auto + Frost protection 30 B Basic setting 32 Buttons on the front 19 C Changing codes 22 Changing language 19 Commissioning protocol 46 Configuration 23 Configuration codes 23 Control function 24 Cooling recovery 30 D Daylight saving time 32 Defrosting 28 DI Digital inputs 16, 36 Display contrast setting 10 DO Digital outputs 18, 36 DX Cooling 30 E Efficiency monitoring 29 Esc-button 19 Extended running 16, 42 External alarm + frost protection 30 External clockf 38 External setpoint 32 F Factory set codes 22 Factory setting 32 Fire alarm 31 Fire damper exercise 30 Free cooling 30 Front mounting kit 5 Frost protection 29 Function DI6/DO6 30 Function DI7 / DI8 31 H High limit thermostat 27 Holiday periods 39 Holidays 39 Humidity control 32, 34 I Information series 20 Installation 10 L Language 19 LED 43 Liquid connected heat exchanger 28 Login 21 M Main menu 20 Manual operation 37 Menu 20 AI Analogue inputs 35 Alarm settings 40 AO Analogue outputs 36 DI Digital inputs 36 DO Digital outputs 36 Help text 21 Humidity control 34 Pressure control 34 Running mode 35 Scheduler 38 Settings 42 Temperature control 33 Menu information 21 O OK-button 19 Outdoor temp. compensation 33, 34 Overview 4 P Pencil-button 19 Pressure control 34 Pump stop 29 R Relay modules 44 Wiring diagrams 45 RM6-24/D 44 RM6H-24/D 44 Running mode 35 S Scheduler 38 Sequence Y1 28 Sequence Y2 28 Sequence Y3 28 Service pin 10 Setting outputs manually 37 Settings 42 Shutdown mode 29 T Technical data 5 Temperature control 33 Two-speed fans 32 V Wiring diagram C10 11 C

56 Regin s business mission is to be a flexible, global partner providing first-rate products for indoor climate control. Our products are designed for creating a pleasant indoor climate while, at the same time, utilizing energy in the most cost-effective way possible. The product range consists of Regin s own products as well as products from leading manufacturers. Vår affärsidé är att vara din flexibla partner som globalt erbjuder ledande produkter för reglering av inneklimat. Dessa bidrar till att skapa ett behagligt inneklimat samtidigt som energin utnyttjas på ett kostnadseffektivt sätt. Programmet består av såväl egenutvecklade produkter som agenturprodukter från världsledande tillverkare. Visit our web site to get more information about our indoor climate product range. Besök vår hemsida för att läsa mer om vårt övriga sortiment. IMPROVING INDOOR CLIMATE CONTROL WORLDWIDE AB Regin Head office Sweden Phone: Fax: Hemsida: info@regin.se Regional office Asia Pacific Phone: Web site: Fax: info@regin.com.sg

C-series Controllers for air handling systems

C-series Controllers for air handling systems C-series Controllers for air handling systems Corrigo, C-series, is a range of digital controllers for air-handling systems designed to be easy to use and operate, having a large capacity, and a high degree

More information

Corrigo E - User Manual Ventilation

Corrigo E - User Manual Ventilation Corrigo E - User Manual Ventilation DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties as regards the contents of this

More information

Corrigo E. Second generation which contains all applications and languages

Corrigo E. Second generation which contains all applications and languages revision 05 2009 Corrigo E Second generation which contains all applications and languages The controllers in the Corrigo E series are intended for applications within heating, boiler and ventilation control

More information

Corrigo E - manual Ventilation application

Corrigo E - manual Ventilation application Corrigo E - manual Ventilation application DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties as regards the contents

More information

Copyright AB Regin, Sweden, Corrigo E manual Ventilation application

Copyright AB Regin, Sweden, Corrigo E manual Ventilation application Copyright AB Regin, Sweden, 2013 Corrigo E manual Ventilation application DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties

More information

Sauter flexotron 800 ventilation Manual

Sauter flexotron 800 ventilation Manual Manual P100012082 Table of contents DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Fr. Sauter AG however, makes no warranties as regards the contents

More information

SAUTER flexotron 800 Ventilation application User Guide

SAUTER flexotron 800 Ventilation application User Guide SAUTER flexotron 800 Ventilation application User Guide P100012091 1 Table of content P100012091 2 Table of content Table of content Table of content... 2 1 About this user guide... 4 2 About flexotron

More information

Corrigo E User Guide. Ventilation application

Corrigo E User Guide. Ventilation application Corrigo E User Guide Ventilation application Copyright AB Regin, Sweden, 2009 About this user guide This user guide covers all the models in the Corrigo E series used with the ventilation application.

More information

SAUTER flexotron800 V2 Ventilation V3.3. manual P P

SAUTER flexotron800 V2 Ventilation V3.3. manual P P SAUTER flexotron800 V2 Ventilation V3.3 manual 2/175 Content Content 1 Generell notes 9 1.1 Disclaimer 9 1.2 Trademarks 9 1.3 Safety information 9 1.3.1 Mandatory note 9 1.3.2 General note 10 1.4 Notes

More information

Room controllers with manual forced ventilation function

Room controllers with manual forced ventilation function revision 12 2016 RC-O Room controllers with manual forced ventilation function RC-O is a room controller from the Regio Mini series intended to control heating and cooling in a single zone. RC-O is a room

More information

User manual. User manual. CTS 600 by Nilan. Comfort Comfort Version: 10.00, Software-version: 2.30

User manual. User manual. CTS 600 by Nilan. Comfort Comfort Version: 10.00, Software-version: 2.30 User manual User manual CTS 600 by Nilan Comfort 1200 Comfort 5000 Version: 10.00, 13-04-2015 Software-version: 2.30 Contents Contents... 2 Introduction... 3 System types... 4 Temperature sensor overview...

More information

Operation and Maintenance Instructions

Operation and Maintenance Instructions Compact Air Handling Unit Operation and Maintenance Instructions Item# 415005 2015-06-23 Contents 1 Warnings...1 2 Product Description...1 2.1 Internal Components Topvex TR800-4000...1 2.2 Description

More information

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING Manual Contents Introduction...3 Valve compatibility...3 Features...3 Application examples...3 Ordering...3 Operating the EKC 347...4-5

More information

Topvex SX/C, Topvex TX/C Air Handling Unit

Topvex SX/C, Topvex TX/C Air Handling Unit Topvex SX/C, Topvex TX/C Air Handling Unit Operation and Maintenance Instructions Document in original language 131678 A003 GB Contents 1 Warnings...1 2 Product Description...2 2.1 Internal components...2

More information

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502* User's Guide VI.7B.D5.02 2005.10 P20 *VI7BD502* *087R8014* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8014* *VI7BD502* Boiler controller P20 VI.7B.D5.02

More information

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual EN Table of Contents 1. INSTALLATION MANUAL...3 1.1. Air Handling Units Sections Connection...3

More information

Room controller. RC is a room controller from the Regio Mini series intended to control heating and cooling in a single zone.

Room controller. RC is a room controller from the Regio Mini series intended to control heating and cooling in a single zone. revision 12 2016 RC Room controller RC is a room controller from the Regio Mini series intended to control heating and cooling in a single zone. RC is a room controller in the Regio series. The controller

More information

WE TAKE BUILDING AUTOMATION PERSONALLY MANUAL CORRIGO

WE TAKE BUILDING AUTOMATION PERSONALLY MANUAL CORRIGO WE TAKE BUILDING AUTOMATION PERSONALLY MANUAL CORRIGO Copyright AB Regin, Sweden, 2016 DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however,

More information

Product Manual SZ1022/SZ1031/SZ1035/

Product Manual SZ1022/SZ1031/SZ1035/ Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed

More information

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*

C66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502* User's Guide VI.7C.C5.02 2005.09 C66 *vi7cc502* *087R8069* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8069* *vi7cc502* Mixing controller with PI controlled

More information

Manual for the integration in BMS/GTC

Manual for the integration in BMS/GTC Manual for the integration in BMS/GTC Communication parameters MODBUS RTU and BACNET COMMUNICATION UTBS PRO-REG Software Version 3.6 EN ÍNDEX 1. GENERALITIES...2 1.1. Introduction...2 1.2. signals types...2

More information

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter VALLOX Product Code: 3158400 L 3158410 R SILENCER (OPTIONAL) INSTRUCTIONS FOR USE AND MAINTENANCE WATER CIRCULATED POST-HEATING UNIT (OPTIONAL) ELECTRIC POST-HEATING UNIT (OPTIONAL)) PREHEATER (OPTIONAL)

More information

Installation Guide. ECL Comfort 210, application A Table of Contents

Installation Guide. ECL Comfort 210, application A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................

More information

ECL Comfort 110, application 116

ECL Comfort 110, application 116 Operating Guide ECL Comfort 110, application 116 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*

C62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102* User's Guide VI.KM.E1.02 2005.09 C62 *VIKME102* *087R8091* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8091* *VIKME102* Double mixing controller C62 VI.KM.E1.02

More information

User manual. CTS 602 by Nilan VPL 15 VPL 15 TOP. Version: 9.02, Software-version: 2.21

User manual. CTS 602 by Nilan VPL 15 VPL 15 TOP. Version: 9.02, Software-version: 2.21 User manual CTS 602 by Nilan VPL 15 VPL 15 TOP Version: 9.02, 19-05-2014 Software-version: 2.21 Table of contents Table of contents... 2 Figure table... 2 Introduction... 3 Types of units... 4 Review of

More information

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*

C37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602* User's Guide VI.7C.E6.02 2005.09 C37 *VI7CE602* *087R8070* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8070* *VI7CE602* Mixing controller with ON / OFF controlled

More information

Copyright AB Regin, Sweden, Corrigo manual Ventilation application

Copyright AB Regin, Sweden, Corrigo manual Ventilation application Copyright AB Regin, Sweden, 2014 Corrigo manual Ventilation application DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties

More information

Topvex SR03, SR04, SR06 Compact Air Handling Unit

Topvex SR03, SR04, SR06 Compact Air Handling Unit Compact Air Handling Unit GB GB Corrigo ver. no. 1.2-1-00 Manufacturer Our products are manufactured in compliance with applicable international standards and regulations. Systemair AB Industrivägen 3

More information

Corrigo E - User Manual Heating

Corrigo E - User Manual Heating Corrigo E - User Manual Heating User manual Corrigo E Heating... 3 1. About Corrigo E... 3 2. Installation and wiring... 5 3. Commissioning... 10 4. Functional description... 11 5. Display, LEDs and buttons...

More information

Pre-programmed room controller with communication

Pre-programmed room controller with communication revision 01 2011 RC-C Pre-programmed room controller with communication RC-C is a complete pre-programmed room controller from the Regio Midi series intended to control heating and cooling in a zone control

More information

Operating Guide. ECL Comfort 210 / 296 / 310, application A247 / A Table of Contents

Operating Guide. ECL Comfort 210 / 296 / 310, application A247 / A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 6 2.1 Before you start.....................................................

More information

Self-learning Room Temperature Controller

Self-learning Room Temperature Controller 2 257 Self-learning Room emperature Controller 5 operating modes and menu selection via roller selector REV16 Mains-independent room temperature controller Straightforward, self-explanatory menu selection

More information

Optigo OP10 Manual. Copyright AB Regin, Sweden, 2007 R E A D Y - S T E A D Y - G O

Optigo OP10 Manual. Copyright AB Regin, Sweden, 2007 R E A D Y - S T E A D Y - G O O P T I G O Optigo OP10 Manual Copyright AB Regin, Sweden, 2007 R E A D Y - S T E A D Y - G O DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however,

More information

USER MANUAL S203. Controller for three circuits. - control for 2 heating circuits - 1 domestic hot water control. Saving energy, creating comfort

USER MANUAL S203. Controller for three circuits. - control for 2 heating circuits - 1 domestic hot water control. Saving energy, creating comfort USER MANUAL S203 Controller for three circuits - control for 2 heating circuits - 1 domestic hot water control Saving energy, creating comfort This user manual consists of two parts. Issues that are intended

More information

N M AirControl AHU. Control manual

N M AirControl AHU. Control manual N 10.63 M 03-2016 AirControl AHU Control manual EN CONTENTS PAGE 1 - MONITORING AND CONTROL 2 1.1 The program 2 1.2 The HMI terminal 2 1.3 The controller 4 1.4 Description of the air handling units 4

More information

Corrigo E - User Manual Heating

Corrigo E - User Manual Heating Corrigo E - User Manual Heating DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties as regards the contents of this manual

More information

User s Manual ELITE PROGRAMMABLE THERMOSTAT WITH MENU DRIVEN DISPLAY

User s Manual ELITE PROGRAMMABLE THERMOSTAT WITH MENU DRIVEN DISPLAY User s Manual ELITE PROGRAMMABLE THERMOSTAT WITH MENU DRIVEN DISPLAY Customizable programming options for every day, weekdays, weekends, or individual days. Smart recovery gradually adjusts indoor temperatures

More information

Pre-programmed room controller with communication and hidden setpoint

Pre-programmed room controller with communication and hidden setpoint revision 02 2016 RC-C3H Pre-programmed room controller with communication and hidden setpoint RC-C3H is a complete pre-programmed room controller from the Regio Midi series intended to control heating

More information

Topvex SR 09, 11, Topvex TR Compact Air Handling Units

Topvex SR 09, 11, Topvex TR Compact Air Handling Units Topvex SR 09, 11, Topvex TR 09-15 Compact Air Handling Units Operation and Maintenance Instructions Document in original language 125594 A004 GB Copyright Systemair AB All rights reserved E&OE Systemair

More information

Sensor Control Panel

Sensor Control Panel USER S MANUAL PU SENS 01 Sensor Control Panel V55-6EN-03(SENS).indd 1 18.08.2015 10:37:16 2 PU SENS 01 CONTENTS Safety Requirements 2 Main Technical Data 3 Control Panel Mounting 3 Control Panel Operation

More information

Controller for evaporator control AK-CC 750

Controller for evaporator control AK-CC 750 User Guide Controller for evaporator control AK-CC 750 ADAP-KOOL Refrigeration control systems Contents 1. Introduction...3 Application... 3 Principles... 4 2. Design of a controller...7 Module survey...

More information

Pre-programmed room controller with communication

Pre-programmed room controller with communication revision 02 2016 RC-C3 Pre-programmed room controller with communication RC-C3 is a complete pre-programmed room controller from the Regio Midi series intended to control heating and cooling in a zone

More information

USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel

USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel PU SENS 01 CONTENTS Safety requirements... 3 Purpose... 4 Technical data... 4 Overall dimensions [mm]... 4 Mounting and set-up... 5

More information

Weather compensated flow temperature control of heating and boiler systems

Weather compensated flow temperature control of heating and boiler systems Instructions ECL Comfort 110 Application 130 Weather compensated flow temperature control of heating and boiler systems User guide, Installation & Maintenance DH-SMT/DK VI.KT.G3.02 Danfoss 06/2008 How

More information

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating 2 526 Heating Controller including dhw heating Series C RVL472 Multifunctional heating controller for use in residential and non-residential buildings Suited for: Heating zone control with or without room

More information

Temperature-Relay TR210

Temperature-Relay TR210 Operating instructions Temperature-Relay TR210 Page 1 of 24 Table of contents 1. Application and Short description... 3 2. Overview of functions... 3 3. Connection Plan... 3 4. Display and operation parts...

More information

Operating instructions

Operating instructions Operating instructions Control unit - CGL Zone 0.0 C Friday 3/0/08 : 6 Wolf GmbH Postfach 380 D-84048 Mainburg Tel. +49 (0)875/74-0 Fax +49 (0)875/74600 Internet: www.wolf-heiztechnik.de Document no.:

More information

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH CONTROL PANEL INTERFACE USING THE AUTO/OFF/MANUAL SWITCH With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting occurs when utility power source

More information

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL Advanced Gen-set Controller OPERATOR S MANUAL Display readings Push-button functions Alarm handling Log list Document no.: 4189340607A SW version 3.5X.X or later Table of contents 1. ABOUT THIS DOCUMENT...3

More information

EXcon zone control. Control for up to 4 individual zones _ fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov

EXcon zone control. Control for up to 4 individual zones _ fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov 3005925_2018-02-05.fm EXcon zone control Control for up to 4 individual zones EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov Tel. +45 65 66 12 34 Fax +45 65 66 11 10 exhausto@exhausto.dk www.exhausto.dk OJ-Air2

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

NA G µair CONNECT 2

NA G µair CONNECT 2 NA 9.41 G 7-216 µair CONNECT 2 Control manual EN CONTENTS PAGE 1. GENERAL INFORMATION 2 2. COMPONENTS 3 2.1 On the front: 3 2.2 On the rear: 4 3. MENU TREE 7 4. ACCESS LEVEL (menu 8) 1 5. CONFIGURING

More information

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number ST71-KHJV.3 Temperature controller Order number 921.8 Wiring diagram Product description The switching outputs of the thermal controller can be programmed as -two-point controller with alarm -three-point

More information

ECL Comfort 110, application 130

ECL Comfort 110, application 130 Operating Guide ECL Comfort 110, application 130 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /

More information

Control solutions Biofloor

Control solutions Biofloor TEF234 Electronic room thermostat with display 230V & 24V COMAP proposes a new control system for heating and cooling underfloor. Consisting of a 6 or 10- channels controller (MCF234), analogic (TAF234)

More information

Synco 900 Operating instructions

Synco 900 Operating instructions Synco 900 Operating instructions Edition 2.0 Controller series B CE1B2707en 05.07.2007 We congratulate you on the selection of the Siemens Synco 900 system and thank you for your purchase of the central

More information

user s manual VUBMG102

user s manual VUBMG102 user s manual CONTROL SYSTEM DHP-R VUBMG102 2 Danfoss VUBMG102 Contents 1 Introduction... 5 2 Functional description... 7 2.1 Heating... 7 2.1.1 Primary supply temperature...7 2.1.2 Integral control...7

More information

RVP310. Heating Controller. Building Technologies HVAC Products

RVP310. Heating Controller. Building Technologies HVAC Products 2 475 Heating Controller RVP310 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or

More information

User's Guide. CTS6000 control panel

User's Guide. CTS6000 control panel User's Guide CTS6000 control panel Valid for: SW version 1,0092 Version 1.04, 2015-12-16 Contents Contents... 2 Figure... 2 Introduction... 3 Control panel menus... 4 Alarm log/event log... 4 Weekly program...

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

Document # R01

Document # R01 Viconics VT7600 Series PIR-Ready Rooftop Unit Controllers Part 1 General The VT7600 series is designed for single-stage and multi-stage control of heating/cooling equipment such as rooftop and self-contained

More information

VFL, VFLPG, VTL and VRA Rectangular electric duct heaters

VFL, VFLPG, VTL and VRA Rectangular electric duct heaters VFL, VFLPG, VTL and VRA Rectangular electric duct heaters VFL, VFLPG, VTL and VRA Rectangular electric duct heaters VEAB rectangular duct heaters are available in ratings of up to 2000 kw and are used

More information

TIREE FAN COIL CONTROLLER - T6580

TIREE FAN COIL CONTROLLER - T6580 TIREE FAN COIL CONTROLLER - T6580 PRODUCT SPECIFICATION SHEET 20 DESCRIPTION A pleasing and modern appearance makes the TIREE ideal for living quarter applications, in particular offices and hotels. In

More information

Automation System TROVIS 5400 Ventilation Controller TROVIS Mounting and Operating Instructions EB 5477 EN. Electronics from SAMSON

Automation System TROVIS 5400 Ventilation Controller TROVIS Mounting and Operating Instructions EB 5477 EN. Electronics from SAMSON Automation System TROVIS 5400 Ventilation Controller TROVIS 5477 ounting and Operating Instructions Electronics from SASON EB 5477 EN Firmware version 2.0x Edition April 2004 Disclaimer of liability Disclaimer

More information

ST Wiring diagram. Product description. Standard temperature controller. Order number

ST Wiring diagram. Product description. Standard temperature controller. Order number ST64-31.10 Standard temperature controller Order number 900197.007 Old Id.Nr.: 386169 Wiring diagram Product description The controller ST64-31.10 was developed for simple thermostatic controls. The round

More information

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data. The RVA63 controller can be utilized to control the following system configurations via LPB communication. Equipment Required

More information

ETO 2 - Controller for ice and snow melting

ETO 2 - Controller for ice and snow melting ETO 2 - Controller for ice and snow melting Advantages Simple adjustment knob with two functions Illuminated display where you can easily see the temperature status and other values Controls both pumps

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

5, SE GÅNGHESTER,

5, SE GÅNGHESTER, KSUB Control and monitoring unit Valid from week of manufacture 48/2005 Description The KSUB is a control and monitoring unit designed to control various types of fire/smoke dampers and fans in a flexible

More information

Refrigeration and Air Conditioning Technical leaflet. Electronic controller EKC 201 and EKC 301

Refrigeration and Air Conditioning Technical leaflet. Electronic controller EKC 201 and EKC 301 Refrigeration and Air Conditioning Technical leaflet Electronic controller EKC 201 and EKC 301 RC.5L.A1.02 RC.5L.A2.02 09-1998 Introduction EKC 201 and 301 are used for temperature control compressor control

More information

Service Information. WNes 2956 appliance documentation. Service Information no. 27/2004 LHG/TKD-Fe/June SI

Service Information. WNes 2956 appliance documentation. Service Information no. 27/2004 LHG/TKD-Fe/June SI After Sales Service International Service Information Service Information no. 27/2004 LHG/TKD-Fe/June 2004 WNes 2956 appliance documentation Page 1/26 Contents 2.0. Extract from Operating Instructions

More information

CTS 602 by Nilan. Compact P. Compact P Sun. Compact P Cool. Compact P Cool Sun. Version: 5.00, Software-version: 2.11

CTS 602 by Nilan. Compact P. Compact P Sun. Compact P Cool. Compact P Cool Sun. Version: 5.00, Software-version: 2.11 User manual CTS 602 by Nilan Compact P Compact P Sun Compact P Cool Compact P Cool Sun Version: 5.00, 13-06-2011 Software-version: 2.11 Contents Contents... 2 Figure table... 2 Introduction... 4 Types

More information

User manual for reversible heat pump

User manual for reversible heat pump User manual for reversible heat pump Heat pump system integrated in Geniox, DV or TIME air handling unit Manual version 1.01.14 Part number of this manual 90925374 Contents DECLARATION OF CONFORMITY EXAMPLE...2

More information

Quickheat 30 weather compensated boiler control

Quickheat 30 weather compensated boiler control Quickheat 0 weather compensated boiler control A compact and sophisticated heating controller The compact KM controller is designed for the control of fan assisted boilers with modulating burners. The

More information

Synco 900 Operating Instructions. Edition 1.0 Controller series 1 CE1B2707en Building Technologies HVAC Products

Synco 900 Operating Instructions. Edition 1.0 Controller series 1 CE1B2707en Building Technologies HVAC Products Synco 900 Operating Instructions Edition 1.0 Controller series 1 CE1B2707en 19.07.2006 Building Technologies HVAC Products We congratulate you on the selection of the Siemens Synco 900 system and thank

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

EXPERT TRI-STAR. Temperature controller. User s Manual

EXPERT TRI-STAR. Temperature controller. User s Manual Temperature controller r s Manual WARNINGS The warranty can be void if this product is used in a manner not specified by the manufacturer. Every effort has been made to ensure that this manual is complete,

More information

VEKA Integrated Control

VEKA Integrated Control VEKA Integrated Control Contents Overview...4 Properties...4 Safety...4 Requirements regarding personnel for installation and start-up...4 Safety regulations...4 Maintenance and service...5 Environmental

More information

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products 2 478 Heating Controller for 2 heating circuits, d.h.w. and boiler RVP331 Multi-functional heating controller for use in residential and non-residential buildings Suitable for weather-compensated flow

More information

SPECIFICATIONS for AIR CONDITIONING CONTROLLER ZONE CONTROL

SPECIFICATIONS for AIR CONDITIONING CONTROLLER ZONE CONTROL SPECIFICATIONS for AIR CONDITIONING CONTROLLER ZONE CONTROL 1. INTROUCTION Zone control is a two pieces fan coil thermostat available for Heat/Cool versions. Its application is for the duct type system

More information

AQUATROL Zone Synchronizing Universal Injection/Mixing Boiler Reset Controls AQ252

AQUATROL Zone Synchronizing Universal Injection/Mixing Boiler Reset Controls AQ252 AQUATROL Zone Synchronizing Universal Injection/Mixing Boiler Reset Controls AQ252 USER OPERATION AND MAINTENANCE WARNING Risk of electrical shock. Can cause severe injury, property damage or death. Only

More information

Digital Thermostat. Models: VS35W and VS35B INSTALLER / USER MANUAL

Digital Thermostat. Models: VS35W and VS35B INSTALLER / USER MANUAL Digital Thermostat Models: VS35W and VS35B INSTALLER / USER MANUAL Contents Contents Box Contents Introduction Product Compliance Installation User Guide Parameter Settings Installers Notes Warranty Icons

More information

User Guide

User Guide ABS control panel CP 112 212 ON ON ON ON ON ON User Guide www.absgroup.com ii ABS CONTROL PANEL CP 112 212, USER GUIDE Copyright 2008 ABS Group. All rights reserved. This manual, as well as the software

More information

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English Rectifier RC-series Manual RC-series English Manual Wall and 19 English Presentation The RC-series is a rectifier for either directly powering the load or for use together with batteries. It is designed

More information

Products no longer available

Products no longer available Technical data sheet MONICO-.. Turnkey automation station MONICO-.. Forms an efficient fire protection system together with the motorisation sets BF(G)24MP Completely wired controller in matching control

More information

eq PRIME COMMISSIONING

eq PRIME COMMISSIONING eq PRIME COMMISSIONING CONTENTS 1. 2. 3. 4. 5. 6. 7. 8.. 10. 11. 12. 13. 14. 15. Unit parts...4 Safety regulations... 10 Commissioning...11 Pressure balance over rotor... 12 Handheld terminal... 13 Overview

More information

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

1 DOCUMENT REVISION CONTROL ELEMENTS... 9 CONTENTS Contents 1 DOCUMENT REVISION... 8 2 SOFTWARE VERSION... 8 3 BASIC DESCRIPTION... 8 4 CONTROL ELEMENTS... 9 4.1 BASIC DISPLAYS...10 4.2 CONTROL KEYS...11 4.2.1 Rotary button (Press / Turn)...11

More information

HMC300. Control unit. Operating Instructions. EMS plus (2014/10) O

HMC300. Control unit. Operating Instructions. EMS plus (2014/10) O HMC300 Control unit EMS plus 6 720 808 471-00.1O Operating Instructions 6 720 813 192 (2014/10) Contents Contents Key to symbols and safety instructions................3 1.1 Key to symbols...........................

More information

Capacity controller for water chiller AK-CH 650

Capacity controller for water chiller AK-CH 650 Capacity controller for water chiller AK-CH 650 Menu operation via AKM Menu list This menu function can be used together with system software type AKM. The description is divided up into function groups

More information

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage LINETRAXX VME420 Multi-functional monitoring relay for undervoltage, overvoltage and frequency monitoring in AC/DC systems with separate supply voltage VME420_D00026_01_D_XXEN/06.2016 LINETRAXX VME420

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

Smart thermostat with Humidification/De-humidification control

Smart thermostat with Humidification/De-humidification control x Smart thermostat with Humidification/De-humidification control Enter/Confirm Scroll Right = Increase Left = Decrease Back/Cancel TABLE OF CONTENTS Everyday Use 1. Adjusting Temperature...3 2. Adjusting

More information

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1 Model TRO24T4XYZ1 Description The TRO24T4XYZ1 is a combination controller and thermostat. The VAV Thermostat Controller is designed for simple and accurate control of any variable air volume box in a number

More information

TOUCHSCREEN. COMFORTSENSE Day Programmable Thermostat. 4 Heat / 2 Cool Universal Multi Stage MODEL NUMBER IDENTIFICATION L U FEATURES

TOUCHSCREEN. COMFORTSENSE Day Programmable Thermostat. 4 Heat / 2 Cool Universal Multi Stage MODEL NUMBER IDENTIFICATION L U FEATURES P R O D U C T S P E C I F I C AT I O N S C O N T R O L S TOUCHSCREEN COMFORTSENSE 7000 7-Day Programmable Thermostat Bulletin No. 210515 June 2009 Supersedes February 2008 HOME SCHEDULE OPTIONS SET AT

More information

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating 2 477 Heating Controller for 2 heating circuits, dhw and boiler, communicating RVP330 Multi-functional heating controller for use in residential and non-residential buildings Suitable for weather-compensated

More information

Roth Touchline. German quality since Quick and easy user manual 1/10

Roth Touchline. German quality since Quick and easy user manual 1/10 Roth Touchline Quick and easy user manual German quality since 197 1/10 230 V Pump N N L L 230 V 230 V 2 V 2 V c/o in %H c/o out c/o in Trafo out /TB in N L eco 2V CH 1 CH 2 CH 3 CH 2V 2V 2V 2V 2V Touchline,

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation

More information

Boiler controller S-Tronic Plus

Boiler controller S-Tronic Plus Operating Instructions Boiler controller S-Tronic Plus Version 50.0 - Build 05.0 Translation of the original German operating instructions for technicians and operators Read and follow the instructions

More information