1 Installation instruction CTS 600 by Nilan VPL 15 VPL 15 Top VPL 25 Version: 5.02,

2 Table of contents Table of contents... 2 Figure table... 2 Introduction... 3 Power supply... 4 Assembly of VPL 15/15T/ Condensation drain / water seal... 6 Ducting... 7 Heating surface, water... 8 Heating surface, electrical (retrofitting) Starting and set up of the CTS 600 control Starting Set up of the CTS 600 control Activating the service menu Heating surface Air exchange Defrost Temp. control Inlet control Room control Restart Preset Manual System dimension Accessories / spare parts Figure table Figure 1: CTS 600 control... 4 Figure 2: Mounting the VPL-Unit... 5 Figure 3: Condensation drain / water seal... 6 Figure 4: Insulation of ducting... 7 Figure 5: Connecting the heating surface, suggestion... 8 Figure 6: CTS 600 control Figure 7: Headlines in the servicemenu Figure 8: The "Heating surface" menu Figure 9: The "Air exchange" menu Figure 10: The "Defrost" menu Figure 11: The "Temp. control" menu Figure 12: The "Inlet control" menu Figure 13: The "Room control" menu Figure 14: The "Restart" menu Figure 15: The "Preset" menu Figure 16: The "Manual" menu Figure 17: System dimension... 22

3 Introduction Please control that the following documents have been delivered together with the unit: - Directions for assembly & use (this document) - CTS 600 directions - Electrical chart Should you have any questions on how to operate the system, contact your nearest Nilan dealer, who you can find at VPL 15/15T/25 is a ventilation unit with heat recovery. The unit can yield up to 325/700m 3 /h at 100Pa external back pressure. The unit can be equipped with different accessories e.g. hygrostat and filter box with pollen filter. Operating the unit is done with the CTS 600 control. The control has many functions such as menu based attendance, week programme, time controlled filter guard and adjustment of the velocity of the ventilator. (Directions for the CTS 600 control is described in another document delivered with the unit.) For accessories see page 23. We recommend that the system as well as the installation are adjusted/checked to ensure a healthy indoor climate and optimal operation. This document may be subject to change Side 3 of 23

4 Power supply Power supply including safety switch must be installed by an authorized electrician. The VPL 15/15T/25 unit must be connected according to the attached electrical chart. The unit is delivered with 1m test cable for the CTS 600 panel. The panel should be connected to the CTS 600 control in the unit with cable type 2x2x0.25mm 2 twisted in pairs. (Maximum length 50m). The CTS 600 panel must be placed dry and frost-proof. The panels integrated feeler prevents further cooling of the building if the primary heat-supply stops by stopping the ventilation if the panel feeler gets below a specific value. (Factory setting is 10 C; the value can be set from 1 C to 20 C.) Figure 1: CTS 600 control If a water post-heating element is installed, the control valve and circulation pump must be electronically connected as described in the provided wiring diagrams. This document may be subject to change Side 4 of 23

5 Assembly of VPL 15/15T/25 When mounting the VPL-unit future service and maintenance should be considered. There is required a minimum of open space in front and behind the unit of 600mm. The system s connection pieces and the pipes are connected with a flexible transition (flex pipes/sound flex pipes or the like). The system must be level due to the condense outlet. The condense outlet requires a clearance height of minimum mm under the outlet connection piece. It is not necessary to re-insulate the system as it is delivered with a 20mm standard insulation. The system is low-noise and low-vibration. However, potential vibrations spreading from the system to the individual building parts must be taken into account. We recommend a minimum distance of 30 mm from building parts and other fixtures. To detach the system from the floor, we recommend that the system is placed on vibration absorbers as illustrated in figure 2 (See Accessories) : Vibration absorbers. 2: 22mm plywood/ chip board 3: Firm insulating batts 4: Wooden beam Figure 2: Mounting the VPL-Unit This document may be subject to change Side 5 of 23

6 Condensation drain / water seal The VPL unit is delivered with a 20mm condensation drain. (PVC, GF-fittings). The drain is placed under the discharge. The condensation drain should be carried with an even inclination of at least 1 cm per meter, frost-proof to the nearest outlet. The overflow from the safety valve should also be carried to the nearest outlet. To avoid frost problems it can be necessary to supply the condensation drain with a heating cable. It is the plumbers responsibility to secure the drain. When the system is running, there can be a vacuum of up to 500Pa (corresponding to 50mm water column) in the outlet. For this reason, the difference in height in the water seal must be minimum 50mm. This means that the first bend of the water seal must be at least twice as long in order for the system to be able to dispose of the condense water (see figure 3). The condensation drain must be airproof from the unit to the water seal in order for the condensation water to be let away from the unit. If the condensation drain is not airproof false air will be sucked in to the unit and the water will stay inside the unit. The water seal can dry out and avoid the water from running out of the unit. Therefore the water seal should be tested regularly and refilled with water if necessary. An elevated height of the water seal will reduce the need for refilling with water. Ø20 mm drain min. 50 mm. VPL min. 50 mm. min. 112,5 mm Figure 3: Condensation drain / water seal The water seal should be tested as described below. (the unit must be connected to the ducting and the front door should be closed): The condensation tray is filled with water and the unit is started at the highest ventilation step. The unit should run for a couple of minutes. Check that the condensation tray is empty when the test is finished. This document may be subject to change Side 6 of 23

7 Ducting We recommend that there are used ducts and fittings with rubber packing that meet sealing class B and that the connections between the unit and the ducting are made with 1 metre sound absorbing flexible transitions as regards sound reduction. The ducts should be shortened with a hacksaw or an angle grinder and laid out according to the working drawing. The ducts are typically laid out on the main beam of the truss frame and are secured with hole belts or they are being hanged in assembly belts. Please avoid any unnecessary area reductions and breaks of the ducting. The ducts should be insulated in some cases with the ordinary attic-insulation. All ducts should be insulated with 100mm mineral wool to avoid heat loss and condensation. This also applies for flexible transitions. It is recommended that the insulation is carried out with 2 layers of 50mm. If the ducts are laid out in an unheated room it will cause condensation problems if the unit are turned off for a longer period of time as the hot air from the heated room will rise to the ducts and cause condensation which can cause damp problems. Loft insulationmaterial Duct Granulate Figure 4: Insulation of ducting The discharge duct is leading the exhaust air away either above the roof or through the outer wall. It is important that the roof cowl has at least the same open space as the duct leading to the roof cowl. A reduction at this place will cause an unnecessary pressure drop which can lead to a reduced ventilation output. The holes for the inlet- and exhaust valves should be cut according to the mounting-frame for the prescribed valve. The frame for the valve must be secured with screws before placing the valve in the frame. The valves are placed in accordance with the size, construction and use of the room. As an example we would not recommend placing an inlet valve just above people with sedentary work because the inlet air in some cases would be experienced as a draught. This document may be subject to change Side 7 of 23

8 Heating surface, water Connecting the heating surface must be done by an authorized plumber. If the unit is placed outside or in a cold location the installation must frost secured. The heating unit is delivered as accessory and consists of: electrical box with LMC200-PCB, heating surface with temperature sensor T9 and frost-protection B3, actuator and regulating valve. The heating surface is to be installed in the inlet ducting just after the VPL unit. The heating surface must also be activated in the CTS 600 control as described on page 13. The mixing loop can be constructed as suggested below. The heating surface should be connected, scavenged and checked for any leakages before starting the unit. The dirt-catcher should be checked and cleaned after a thoroughly flushing of the system. 3 1 M 2 Heating surface Flow Air flow T9 Return B3 Note that the temperature sensor T9 and frost-protection B3 is placed at the heated side of the heating surface close to the return connection. See electrical chart. 1: Actuator and regulating valve: Danfoss AME 140/24V 0-10V signal, 2-way valve VZ2 Kv 0,4, (Nilan delivery) Kvs-value must be checked in accordance with supply. Differential pressure: 0,1 0,6bar There is calculated with a cooling of 20 C over the heating surface at a flow of 60 C. 2: Scavenging (not Nilan delivery) 3: Dirt-catcher (not Nilan delivery) Figure 5: Connecting the heating surface, suggestion This document may be subject to change Side 8 of 23

9 IMPORTANT regarding Danfoss Actuator type AME 140: Re-installing the actuator must be done as described below: 1. Disconnect the power supply and remove the cover of the actuator. 2. Liberate the gear by pressing down the button as the spindle is turned up (counter clockwise) 3. Re-install the actuator and turn on power. 4. DIP-switch nr. 1 should be moved to ON and then to. 5. The actuator is automatically calibrating for up to 6 minutes. (The LED is flashing when calibrating and is lit constantly when finished). 6. Re-install the cover of the actuator. The Danfoss Actuator type AME 140/24V should be placed in an environment of 0 C to 55 C. Electrical box with LMC200 PCB for heating surface: Power supply must be installed by an authorized electrician. The electrical box should be installed closed to the inlet branch of the unit. 230V power supply should be installed together with the ventilation unit. T9, temperature sensor of the heating surface, should be installed in the electrical box. T7, temperatur sensor of the inlet, should be let 3cm. into the inlet duct approximately 0,5m away from the ventilation unit. Danfoss Actuator should be connected to the clamps in the electrical box. B3 frost-protection should be connected to the CTS 600 PCB in the ventilation unit. See electrical chart. This document may be subject to change Side 9 of 23

10 Heating surface, electrical (retrofitting) Electrical heating surface should be installed in the ducting (Ø160/Ø200). When retrofitting an electrical heating surface it should be activated in the 600 control panel as described on page 15. Power supply must be installed by an authorized electrician. See electrical chart for the ventilation unit and electrical chart for LMC200 PCB A - H. This document may be subject to change Side 10 of 23

11 Starting and set up of the CTS 600 control Starting Before starting the VPL please check all functions as cooling, heating and heating surface if installed. Set up of the CTS 600 control In this passage we will go through the service menu of the CTS 600 control. For daily use of the CTS 600 control please see the CTS 600 directions. (delivered together with the VPL). Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on Figure 6: CTS 600 control This document may be subject to change Side 11 of 23

12 Activating the service menu Press q and at the same time for 10 seconds. The service menu is now available. Press q multiple times until the panel shows SERVICE. Press to enter the service menu. It is now possible to move around in the menu by using pq. The headlines of the service menu are shown below: SERVICE HEATING SURFACE Se side 13 AIR EXCHANGE Se side 14 DEFROST Se side 15 TEMP. Se side 16 Se side 17 ROOM Se side 18 Se side 19 PRESET Se side 20 MANUEL Se side 21 Figure 7: Headlines in the servicemenu This document may be subject to change Side 12 of 23

13 Heating surface The unit can be equipped with a heating surface. It is possible to retrofit a heating surface. The surface must be activated in the CTS 600 control in order to function together with the unit and for the frost-protection to be active. When installing a heating surface T7 is the temperature sensor in the inlet. Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SELECT SURFACE WATERSUP AIR EXCHANGE DEFROST TEMP. ROOM KONTROL MANUEL DELAY 0 MIN Delay between start of ventilators and heating surface (0 60 minutes) SELECT WATERSUP SELECT EB SUP SELECT EL SUP SELECT Indstilling vælges ved anlæg uden eftervarmeflade Should be chosen when installing a heating surface for water. Controlled via 0-10 V signal LMC-200 PCB should be installed. Otherwise Alarm 90 slave I/O occurs. Should be chosen when installing an electrical heating surface, binary controlled (connection of steps via relays on CTS 600 PCB) Should be chosen when installing an electrical heating surface, controlled via 0-10 V signal LMC-200 PCB should be installed. Otherwise Alarm 90 slave I/O occurs. Figure 8: The "Heating surface" menu This document may be subject to change Side 13 of 23

14 Air exchange In the Air exchange menu it is possible to adjust 4 steps of ventilation speed (air volume). Inlet and exhaust is to be adjusted individually at each level. The inlet speed can be adjusted to a minimum and the exhaust can be adjusted to both a maximum and a minimum. It is possible to delay the starting of the fan in order to give time to the register to open. Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HOTWATER AIR EXCHANGE MIN 0 The lowest permissible ventilation step for fresh air/inlet (0-2) DEFROST TEMP. EXHAUST MIN 1 EXHAUST MAX 4 The lowest permissible ventilation step for outlet/exhaust (1-2) ROOM >1< 23% >2< 40% The highest permissible ventilation step for outlet/exhaust (3-4). >3< 65% PRESET >4< 100% EXHAUST >1< 25% Each ventilation step can be set as a percentage of maximum fan speed. EXHAUST >2< 45% EXHAUST >3< 70% EXHAUST >4< 100% DELAY 2 MIN Delayed start of vent. This gives the valve time to open fully before the vents start (0-4 min.) Figure 9: The "Air exchange" menu This document may be subject to change Side 14 of 23

15 Defrost In the Defrost menu it is possible to chose how the unit should perform during defrosting of the evaporator in the exhaust. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE AIR EXCH LOW DEFROST TEMP. AIR EXCH USER AIR EXCH USER AIR EXCH Constant air flow during defrosting. ROOM Airflow stopped during defrosting (should be used when exhaust air temperature is less than 10 C). PRESET Figure 10: The "Defrost" menu This document may be subject to change Side 15 of 23

16 Temp. control In the Temp. control menu it is possible to chose a room temperature where the unit stops in order to avoid further cooling of the building if the primary heating shuts down. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST Indicates which sensor that needs to be the controlling one. PANEL T15 (Panel sensor). EXTERNAL T10 (to be installed in representative extraction fitting). SENSOR EXTERNAL TEMP. SENSOR PANEL SENSOR PANEL PRIORITY HP+EXT PRIORITY HP+EXT ROOM ROOM LOW 10 C PRIORITY HP EXTERNAL -1 C PRIORITY PRESET The unit stops at this room temperature (1-20 C) - - means that the function is unactive. - - should be chosen if the panel is placed in a cold environment. : ventilation without heatpump HP: ventilation only with heatpump activ HP+EXT: ventilation with heatpump and heating surface activ Figure 11: The "Temp. control" menu This document may be subject to change Side 16 of 23

17 Inlet control In the Inlet control menu it is possible to adjust the period of time before restart of the compressor. The Inlet control menu should only be adjusted by persons with knowledge of control engineering. (To restore factory settings, see page 19) indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HOTWATER AIR EXCHANGE DEFROST TEMP. GAIN 7.0%/ ROOM INTEGRAL 120s PRESET N- ZONE 2.0 C TMP- RAMP 0.10 /s The menu options are only accessible when the system has a postheating element KAP- RAMP 0.5%/s HEATPUMP RST 6m The minimum length of time (in minutes) the compressor must be stopped before restarting. Figure 12: The "Inlet control" menu This document may be subject to change Side 17 of 23

18 Room control In the Room control menu it is possible to adjust the regulator for controlling the room temperature. The Room control menu should only be adjusted by persons with knowledge of control engineering. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST TEMP. Heat demand: Neutral Zone for start and stop of the evaporator: Desired room temperature (21 C) + N-ZONE (2 C) = 20 C for start of the evaporator, 22 C for stop of the evaporator ROOM N-ZONE 2.0 C Can be set from 0,5-10 C. PRESET Figure 13: The "Room control" menu This document may be subject to change Side 18 of 23

19 Restart The Restart menu enables you to set the unit to automatically restart in connection with highpressure/low-pressure alarms. indicates that the menu point flashes and can be set to another value The setting HP/LP in the Restart menu may not be used under normal conditions. Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST TEMP. ROOM PRESET HP/LP This function may not be used under normal conditions. (the function indicates that the unit should restart automatcally when high-pressure/lowpressure alarms occur.) Indicates that the unit should not restart automatically when highpressure/low-pressure alarms occur. Figure 14: The "Restart" menu This document may be subject to change Side 19 of 23

20 Preset indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST TEMP. ROOM When standard is chosen all factory settings are reset. An eventual supplementary heating surface must be re-activated. A heating surface is NOT frost-protected until it is correctly installed and activated in the service menu. PRESET STANDARD PRESET PRESET Figure 15: The "Preset" menu This document may be subject to change Side 20 of 23

21 Manual In the Manual menu it is possible to test the functions of the unit manually. indicates that the menu point flashes and can be set to another value Use of t he CTS 600 panel : - pr ess ESC t o go one st ep back i n t he menu - pr ess qpt o move up or down i n a menu or t o adj ust an act i vat ed menu - pr ess t o act i vat e a menu - pr ess t o conf i r m a menu - pr ess t o t ur n of f t he uni t - pr ess ON t o t ur n t he uni t on SERVICE HEATING SURFACE AIR EXCHANGE DEFROST VEN+HEAT Manual test of ventilation & heat. Under test there are 50% signal to the heating surface TEMP. VENT+CPR Manual test of ventilation & compressor EXHAUST Manual test of exhaust ROOM Manual test of inlet PRESET FLAPS DEFROST Manual test of flaps Manual test of the defrost function. Manual test de-activated (normal working) Figure 16: The "Manual" menu This document may be subject to change Side 21 of 23

22 System dimension Right Front Left Figure 17: System dimension 1. Fresh air intake. 5. Compressor 9. Inlet fan 2. Exhaust 6. Condensator (hidden) 10. Exhaust fan 3. Inlet 7. Evaporator 11. Condensation drain 4. Discharge 8. Electrical connections Dimensions in mm: a b c d e f g h i j k l m n o p VPL Ø Ø20 VPL15T VPL Ø Ø20 Weight in kg.: VPL15 VPL15T VPL25 Unit Filterunit with Heat-pipe This document may be subject to change Side 22 of 23

23 Accessories / spare parts VPL 15 Filter types Qty. Nilan item no. F5 (exhaust) F7 (inlet) VPL 15T Filter types Designation Qty Nilan item no. T-filter, comlete Ø160mm Filter for item no Ø160mm VPL 25 Filterklasse Designation Qty. Nilan item no. T-filter, complete Ø250mm Filter for item no Ø250mm Heating surface, water Unit Qty. Nilan item no. VPL 15 + VPL 15T VPL Heating surface, electrical Unit Output Qty. Nilan item no. VPL 15 + VPL 15T 0,9kW VPL 25 6,0kW Filterunit FU Unit Filter type Qty. Nilan item no. FU15H G FU25H G Heating Cable for condensate drain (frost protection) Unit Designation Nilan item no. VPL 15 VPL 15T VPL 25 Heating Cable (specify length when ordering) 2172 Vibration Unit Designation Qty Nilan item no. VPL 15 Sylomer (Green) VPL 25 Sylomer (Green) FU15H Sylomer (Green) FU25H Sylomer (Green) This document may be subject to change Side 23 of 23

Installation instruction

Installation instruction Installation instruction CTS 600 by Nilan VP 18 M2 Version: 5.01, 15-04-2011 Table of contents Table of contents... 2 Figure table... 2 Introduction... 3 Power supply... 4 Assembly of VP 18 M2... 5 Condensation

More information

Installation Instruction

Installation Instruction Installation Instruction CTS 600 by Nilan VPM 120 VPM 240 VPM 360 VPM 480 VPM 560 Version: 5.02, 17-10-2011 Table of contents Table of contents... 2 Figures... 2 General information before installation...

More information

Installation instruction

Installation instruction Installation instruction CTS 602 by Nilan VP 18 M2 Version: 10.00, 13-04-2015 Software-version: 2.30 Table of contents Table of contents... 2 Figure table... 2 Introduction... 4 Power supply... 5 Assembly

More information

Installation instruction

Installation instruction Installation instruction CTS 600 by Nilan VP 18 10P Version: 5.03, 15-04-2011 Contents Contents... 2 List of figures... 2 Before starting... 3 Electrical connection... 4 VP 18-10P installation... 5 Condensation

More information

Installation instruction

Installation instruction Installation instruction CTS 602 by Nilan Compact P Compact P Sun Compact P Cool Compact P Cool Sun Version: 5.00, 13-05-2011 Contents Contents... 2 Figure table... 2 Before starting... 3 Electrical connection...

More information

User manual. CTS 602 by Nilan VPL 15 VPL 15 TOP. Version: 9.02, Software-version: 2.21

User manual. CTS 602 by Nilan VPL 15 VPL 15 TOP. Version: 9.02, Software-version: 2.21 User manual CTS 602 by Nilan VPL 15 VPL 15 TOP Version: 9.02, 19-05-2014 Software-version: 2.21 Table of contents Table of contents... 2 Figure table... 2 Introduction... 3 Types of units... 4 Review of

More information

CTS 602 by Nilan. Compact P. Compact P Sun. Compact P Cool. Compact P Cool Sun. Version: 5.00, Software-version: 2.11

CTS 602 by Nilan. Compact P. Compact P Sun. Compact P Cool. Compact P Cool Sun. Version: 5.00, Software-version: 2.11 User manual CTS 602 by Nilan Compact P Compact P Sun Compact P Cool Compact P Cool Sun Version: 5.00, 13-06-2011 Software-version: 2.11 Contents Contents... 2 Figure table... 2 Introduction... 4 Types

More information

PRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h

PRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h PRODUCT DATA COMFORT 00 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 800 m /h COMFORT 00 Product description The Comfort 00 is an energy-efficient ventilation

More information

User manual. User manual. CTS 600 by Nilan. Comfort Comfort Version: 10.00, Software-version: 2.30

User manual. User manual. CTS 600 by Nilan. Comfort Comfort Version: 10.00, Software-version: 2.30 User manual User manual CTS 600 by Nilan Comfort 1200 Comfort 5000 Version: 10.00, 13-04-2015 Software-version: 2.30 Contents Contents... 2 Introduction... 3 System types... 4 Temperature sensor overview...

More information

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h PRODUCT DATA COMFORT 40 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 40 m /h COMFORT 40 Product description The Comfort 40 is an energy-efficient ventilation

More information

PRODUCT DATA COMBI 300 POLAR BY NILAN. Ventilation with passive & active heat recovery. Active heat recovery. Passive heat recovery.

PRODUCT DATA COMBI 300 POLAR BY NILAN. Ventilation with passive & active heat recovery. Active heat recovery. Passive heat recovery. PRODUCT DATA COMBI 300 POLAR BY NILAN Ventilation with passive & active heat recovery Domestic Passive heat recovery Active heat recovery Ventilation < 350 m 3 /h Comfort heating Comfort cooling COMBI

More information

PRODUCT DATA VPL 15 TOP M2 BY NILAN. Ventilation & active heat recovery. Active heat recovery. Comfort heating. Comfort cooling.

PRODUCT DATA VPL 15 TOP M2 BY NILAN. Ventilation & active heat recovery. Active heat recovery. Comfort heating. Comfort cooling. PRODUCT DATA VPL 15 TOP M2 BY NILAN Ventilation & active heat recovery Domestic Active heat recovery Ventilation < 400 m 3 /h Comfort heating Comfort cooling VPL 15 TOP M2 Product description VPL 15 Top

More information

PRODUCT DATA VPL 28 BY NILAN. Ventilation & active heat recovery. Active heat recovery. Comfort heating. Comfort cooling.

PRODUCT DATA VPL 28 BY NILAN. Ventilation & active heat recovery. Active heat recovery. Comfort heating. Comfort cooling. PRODUCT DATA VPL 28 BY NILAN Ventilation & active heat recovery Domestic Active heat recovery Ventilation < 1000 m 3 /h Comfort heating Comfort cooling VPL 28 Product description VPL 28 is an energy-efficient

More information

CI/SfB (57.5) November 2008

CI/SfB (57.5) November 2008 CI/SfB (57.5) climate systems November 2008 High-comfort, low-energy ventilation An energy efficient, fresh, clean and healthy climate - all year round Ubbink Heat Recovery Ventilation (HRV) systems provide

More information

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h PRODUCT DATA COMFORT 5000 BY NILAN Ventilation & passive heat recovery Commercial Passive heat recovery Ventilation < 5300 m 3 /h COMFORT 5000 The Comfort 5000 is a ventilation unit suitable for central

More information

PRODUCT DATA COMFORT 1200 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 1400 m 3 /h

PRODUCT DATA COMFORT 1200 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 1400 m 3 /h PRODUCT DATA COMFORT 00 BY NILAN Ventilation & passive heat recovery Commercial Passive heat recovery Ventilation < 00 m /h COMFORT 00 The Comfort 00 is a ventilation unit suitable for central ventilation

More information

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter VALLOX Product Code: 3158400 L 3158410 R SILENCER (OPTIONAL) INSTRUCTIONS FOR USE AND MAINTENANCE WATER CIRCULATED POST-HEATING UNIT (OPTIONAL) ELECTRIC POST-HEATING UNIT (OPTIONAL)) PREHEATER (OPTIONAL)

More information

Danfoss Air Heating Surfaces

Danfoss Air Heating Surfaces MAKING MODERN LIVING POSSIBLE Installation Guide www.heating.danfoss.com Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English

More information

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery. PRODUCT DATA COMPACT P - SERIES BY NILAN Domestic Passive heat recovery Active heat recovery Ventilation < 300 m 3 /h Comfort heating Comfort cooling Sanitary hot water production Heating THE VENTILATION

More information

Comfortable indoor climate regardless of the season

Comfortable indoor climate regardless of the season Comfortable indoor climate regardless of the season VPL by nilan Heating and cooling in one system Ventilation with heat recovery Make your home your comfort zone Substantial benefits Take an active step

More information

VERSO Air Handling Units

VERSO Air Handling Units Energy efficient solutions for profitable indoor climate VERSO-S air supply units VERSO-R air handling units equipped with regeneration system VERSO-P air handling units equipped with recuperation system

More information

MAKING MODERN LIVING POSSIBLE. Danfoss Air. Installation guide for Danfoss Heating Surfaces DANFOSS HEATING

MAKING MODERN LIVING POSSIBLE. Danfoss Air. Installation guide for Danfoss Heating Surfaces DANFOSS HEATING MAKING MODERN LIVING POSSIBLE Danfoss Air Installation guide for Danfoss Heating Surfaces DANFOSS HEATING Installation The Danfoss Air system Heating surfaces Index 1.0 Mounting electrical heating surfaces

More information

VERSO Air Handling Units

VERSO Air Handling Units VERSO Air Handling Units Energy efficient solutions for profitable indoor climate VERSO Air Handling Units VERSO-S air supply units VERSO-R air handling units equipped with regeneration system VERSO-P

More information

PRODUCT DATA COMFORT 300 TOP BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 325 m 3 /h

PRODUCT DATA COMFORT 300 TOP BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 325 m 3 /h PRODUCT DATA COMFORT 300 TOP BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 325 m 3 /h COMFORT 300 TOP Product description The Comfort 300 Top is an energy-efficient

More information

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h PRODUCT DATA COMFORT 450 BY NILAN Ventilation & passive heat recovery Domestic Passive heat recovery Ventilation < 450 m 3 /h COMFORT 450 Product description The Comfort 450 is an energy-efficient ventilation

More information

Air Comfort. Installation instructions (English) A

Air Comfort. Installation instructions (English) A Air Comfort Installation instructions (English) WWW.BRINKAIRFORLIFE.NL 614788-A This appliance may be used by children as of 8 years of age, persons of reduced mental or physical capacities and those of

More information

Air heater/cooler in combination with ground source heat pump

Air heater/cooler in combination with ground source heat pump Swegon CASA Air heater/cooler in combination with ground source heat pump Installation, operation and maintenance instructions for design engineers, installation engineers and service personnel SDHWM_c_EN

More information

Swedish design and manufacture since 1967

Swedish design and manufacture since 1967 Swedish design and manufacture since 167 PVP MA20-14 rev.2 Manual User manual Copyright 2017 Pahlén AB, Box 728, SE-14 27 Upplands Väsby, Sweden Tel. +46 8 54 110 50, Fax +46 8 50 868 80, e-mail: info@pahlen.se,

More information

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel.

CDS 80. Continuous ventilation without dehumidification can be selected on the CDS 80 control panel. DEHUMIDIFICATION 9 CDS 80 FUNCTION The CDS 80 works in accordance with the condensation principle. A fan draws the humid air into the dehumidifier and through an evaporator coil. When passing through the

More information

PORTABLE AIR CONDITIONER

PORTABLE AIR CONDITIONER PORTABLE AIR CONDITIONER Model: PEL00461 1 CONTENTS Page No. Details 3 Important Safety Information 4 Introduction 4 Positioning 4 Installation 5 Control Panel 6 Remote Control 6 Operation Modes 7 Water

More information

TABLE OF CONTENTS FOR YOUR SAFETY

TABLE OF CONTENTS FOR YOUR SAFETY TABLE OF CONTENTS 1. SPECIFICATION & PARTS IDENTIFICATION...2 2. OPERATION & FUNCTION OF PARTS...2, 3 A. Cooling Operation B. Heating Operation C. Function of Parts 3. LOCATION REQUIREMENTS...3, 4 4. INSTALLATION

More information

- 1 - Updated on 18 March, 2010

- 1 - Updated on 18 March, 2010 - 1 - Updated on 18 March, 2010 TABLE OF CONTENTS 1. SPECIFICATION & PARTS IDENTIFICATION...3 2. OPERATION & FUNCTION OF PARTS...4, 5 A. Cooling Operation B. Heating Operation C. Function of Parts 3. LOCATION

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

Installation and operation manual

Installation and operation manual Installation and operation manual Drying cabinet FC 18 PODAB 2009 2 Contents Safety regulations 5 Specification 6 Dimensions 6 Technical information 6 Assembly instructions 7 Installation of the cabinet

More information

PORTABLE AIR CONDITIONER MODEL NO: AC9000

PORTABLE AIR CONDITIONER MODEL NO: AC9000 PORTABLE AIR CONDITIONER MODEL NO: AC9000 PART NO: 3230570 OPERATION & MAINTENANCE INSTRUCTIONS GC0113 INTRODUCTION Thank you for purchasing this CLARKE Portable Air Conditioner. Before attempting to operate

More information

SAVE VTC 700. Heat Recovery Ventilation Unit

SAVE VTC 700. Heat Recovery Ventilation Unit Heat Recovery Ventilation Unit 207581-EN_GB 23-08-2011V.A001 Contents 1 Warnings... 1 2 Introduction... 2 3 Interface description... 3 3.1 Control panel... 3 3.2 Display symbols... 4 4 Menu settings...

More information

Service Information. WNes 2956 appliance documentation. Service Information no. 27/2004 LHG/TKD-Fe/June SI

Service Information. WNes 2956 appliance documentation. Service Information no. 27/2004 LHG/TKD-Fe/June SI After Sales Service International Service Information Service Information no. 27/2004 LHG/TKD-Fe/June 2004 WNes 2956 appliance documentation Page 1/26 Contents 2.0. Extract from Operating Instructions

More information

Installation and maintenance

Installation and maintenance Installation and maintenance CTS 700 by Nilan Compact P GEO 3 Compact Polar GEO 6 Version: 1.02, 01-06-2016 We reserve the right to make changes Page 1 of 40 Table of contents Table of contents... 2 General

More information

Contents. Technical Description of the Air Handling Unit General, Specification Function, Functional Sections

Contents. Technical Description of the Air Handling Unit General, Specification Function, Functional Sections Room unit Contents Technical Description of the Air Handling Unit General, Specification... 146 Function, Functional Sections... 147 Control System Control Display, Airflow Control... 148 Temperature Control...

More information

Operating Instructions

Operating Instructions Operating Instructions Air Conditioner Model No. Indoor Unit CS-E12QD3RW CS-E18QD3RW Single Split Outdoor Unit CU-E12QD3R CU-E18QD3R Multi Split Outdoor Unit CU-4E23QBR CU-4E27QBR CU-5E34QBR Operating

More information

MODEL URS-1: FACTORY RETROFIT PROGRAM

MODEL URS-1: FACTORY RETROFIT PROGRAM MODEL URS-1: FACTORY RETROFIT PROGRAM The USR-1 unit has gone through extensive testing in order to attain maximum performance. It has been determined that in order to set the unit for all weather operation,

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

User Manual. Vanvex Optima 180 Domestic Hot Water. Version

User Manual. Vanvex Optima 180 Domestic Hot Water. Version GB User Manual Vanvex Optima 180 Domestic Hot Water Version 3.07-0310 Table of contents Page 1. Users Guide 1.1 Use... 3 1.2 Altering of the operation data... 3 1.3 Operating menu... 4 1.4 Factory default

More information

Glass and Dishwashers AMX / AUX Series

Glass and Dishwashers AMX / AUX Series Glass and Dishwashers AMX / AUX Series INSTALLATION OPERATION REV. 8.xx 04.07.2005 Installation and Operation Instructions for Models of AMX / AUX Series Content Page 1 Installation... 3 2 Connections...

More information

Installer manual GreenMaster-HP

Installer manual GreenMaster-HP Installer manual GreenMaster-HP Transport and installation Ventilation unit IHB EN 1747-2 8017172 2 GreenMaster-HP Transport and installation Introduction Here you can read about how best to handle the

More information

Operation and maintenance instructions

Operation and maintenance instructions Operation and maintenance instructions TX HomeVex Revision 2014.08.19 Table Of Content 1.0.0 Unit Description... 4 1.1.0 Application... 4 1.2.0 Supply Area... 4 1.3.0 Unit Principle... 4 1.4.0 The Manufacturer's

More information

Heat Recovery Units. Heat Recovery 1

Heat Recovery Units. Heat Recovery 1 Heat Recovery Units Heat Recovery 1 Heat Recovery Unit Why? A heat recovery unit (HRU) can help make mechanical ventilation more cost effective by reclaiming energy from exhaust airflows. HRUs use air-to-air

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction Air Comfort Air Treatment Energy Recovery eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction eco PREMIUM - Technical Instruction REDA 2 Contents Description Applications... 3 Quality & environment...

More information

Model 1750A/ 1770A Dehumidifier Installation Instructions

Model 1750A/ 1770A Dehumidifier Installation Instructions Model 1750A/ 1770A Dehumidifier Installation Instructions Safety Instructions WARNING 1. Improper installation may cause property damage or injury. Installation, service, and maintenance must be performed

More information

EUQA Humidifier, for circulated water

EUQA Humidifier, for circulated water Sizes 0 4, 50, 5 Sizes 44, 5 84 6 5 4 6 5 4 5 6 8 7 9 7 8 0. Control box, on the outside. Control box, on the inside. Shut-off valve (not included) 4. Water filter, max. 500 mm mesh (not included) 5. EUAZ-08

More information

Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061

Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061 Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061 Imported by: Zwembad BVBA Industrieweg 9 3190 Boortmeerbeek België www.harmopool.eu 0 Table of content Introduction... 2 Safety instructions...

More information

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS Published: June 2012 DENSO AUTOMOTIVE SYSTEMS AUSTRALIA PTY. LTD AL00500054E 2012 DENSO Automotive Systems Australia Pty. Ltd All rights reserved. This

More information

HRU SINGLE DWELLING HOUSES - BALANCED AIRFLOW WITH HEAT EXCHANGER AKOR ST HR Series

HRU SINGLE DWELLING HOUSES - BALANCED AIRFLOW WITH HEAT EXCHANGER AKOR ST HR Series AKOR ST HR Series AKOR ST HR Balanced-airflow for single dwelling houses, with crossflow heat exchanger. It guarantees continuous air replacement in single dwelling houses up to 92% of efficiency. It connects,

More information

OPERATING INSTRUCTIONS. Drying cabinet DC 7774 DC Read the instructions before using the machine.

OPERATING INSTRUCTIONS. Drying cabinet DC 7774 DC Read the instructions before using the machine. OPERATING INSTRUCTIONS Drying cabinet DC 7774 DC 7784 Read the instructions before using the machine. Dear ASKO customer, Congratulations on making an excellent choice, and welcome to the ASKO family,

More information

SPECIFICATIONS PART NAME

SPECIFICATIONS PART NAME SPECIFICATIONS MODEL High HEAT RATING Low FUEL TANK CAPACITY BURNING TIME DIMENSIONS(W x D x H) WEIGHT VOLTAGE / FREQUENCY ELECTRICAL CONSUMPTION LC-S27 9,900 BTU / 2.9 kw 2,900 BTU / 0.8 kw 4.0 lit. 14.2~

More information

OWNER S GUIDE TYPE A TYPE C TYPE B TYPE E TYPE F TYPE D COOL FAN OFF. CA Series << FAN SPEED COOL FAN AUTO SLEEP TIMER FAN SPEED

OWNER S GUIDE TYPE A TYPE C TYPE B TYPE E TYPE F TYPE D COOL FAN OFF. CA Series << FAN SPEED COOL FAN AUTO SLEEP TIMER FAN SPEED ON/ RESET RESET OWNER S GUIDE 1. Identify, using the pictures below, which controller type you have installed and turn to the relevant page for the operating instructions. 2. General information applies

More information

VEX100 series Air handling units with cross-flow heat exchanger

VEX100 series Air handling units with cross-flow heat exchanger Product information - Version 6 VEX100 series Air handling units with cross-flow heat exchanger VEX140: 400-2200 m 3 /h VEX150: 700-3600 m 3 /h VEX160: 1100-5000 m 3 /h VEX170: 1400-8400 m 3 /h Contents

More information

LQQA Humidifier, for circulated water

LQQA Humidifier, for circulated water Size -84 5 Fig. 4 5 4 6 8 7 9 7 8. Control box, on the outside. Control box, on the inside. Shut-off valve (not included) 4. Water filter, max. 5 mm mesh (not included) 5. LQAZ-8 Water trap (accessory)

More information

11,000 BTU Portable Air Conditioner with dehumidifier & Fan PE4-11R-03 Operating Instructions. Model No. PE4-11R Soleus Air International

11,000 BTU Portable Air Conditioner with dehumidifier & Fan PE4-11R-03 Operating Instructions. Model No. PE4-11R Soleus Air International 11,000 BTU Portable Air Conditioner with dehumidifier & Fan PE4-11R-03 Operating Instructions Model No. PE4-11R-03 2006 Soleus Air International Thank you for choosing a Soleus Air Portable Air Conditioner.

More information

PRODUCT RANGE: ROOFTOP PACKAGE

PRODUCT RANGE: ROOFTOP PACKAGE Packaged Air Cooled Reverse Cycle Type Air Conditioner Range 11-125kWr With Energy / Heat Recovery The Roof Top Packaged unit range is designed to be used when high fresh air quantities are required. They

More information

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G WINDOW TECHNICAL GUIDE Single package Cooling only and Heat pump Models YO-YM 09-24 R407C YM 09 V6 G YM 09 V7 G YO 12-19-24 V6 G YO 12-19-24 V7 G YORK List of Contents Page 1 - Safety...2 2 - Unit packaging...2

More information

Installation Guide. ECL Comfort 210, application A Table of Contents

Installation Guide. ECL Comfort 210, application A Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC iers.com

Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC iers.com Read and Save These Instructions Horizon Galaxy - Installation and Operations Manual Air Cleaning Equipment, Inc. 303 N. Main St. Broadway, NC 27505 www.horizondehumidif iers.com 1 Safety Notes: The Horizon

More information

Installation and Operating Manual Drying Cabinet

Installation and Operating Manual Drying Cabinet Drying Cabinet TS-4175 WW CONTENTS THIS USER MANUAL & DATA PLATE DETAILS Page 2 IMPORTANT SAFETY INSTRUCTIONS Page 3 INSTALLATION INSTRUCTIONS Page 4 OPERATING INSTRUCTIONS Page 8 MAINTENANCE INSTRUCTIONS

More information

MAKING MODERN LIVING POSSIBLE. Installation Guide. Danfoss Air Units.

MAKING MODERN LIVING POSSIBLE. Installation Guide. Danfoss Air Units. MAKING MODERN LIVING POSSIBLE Installation Guide www.heating.danfoss.com Danfoss A/S is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English

More information

LQQA Humidifier, for circulated water

LQQA Humidifier, for circulated water Size 5 Fig. 6 5 6 8 7 9 7 8. Control box, on the outside. Control box, on the inside. Shut-off valve (not included). Water filter, max. 5 mm mesh (not included) 5. LQAZ-8 Water trap (accessory) 6. Water

More information

DSR SERIES DEHUMIDIFIERS ENGLISH GENERAL INFORMATION EXPLODED VIEWS DSR-20 DSR-12 PARTS LISTS ATTENTION!

DSR SERIES DEHUMIDIFIERS ENGLISH GENERAL INFORMATION EXPLODED VIEWS DSR-20 DSR-12 PARTS LISTS ATTENTION! DEHUMIDIFIERS GENERAL INFORMATION EXPLODED VIEWS PARTS LISTS DSR SERIES DSR-20 DSR-12 ENGLISH ATTENTION! There is a time delay on all units fitted with DFC 1 Controller. When starting or re starting the

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS CTS700-TOUCH BY NILAN Compact P / Compact P Polar - EK (English) Version 2.10-27.04.2017 TABLE OF CONTENTS Safety Power supply... 4 Heat pump domestic hot water...4 Disposal...

More information

Glass and Dishwashers AMX / AUX Series

Glass and Dishwashers AMX / AUX Series Glass and Dishwashers AMX / AUX Series INSTALLATION OPERATION VERSION 24.02.04 Important Notes Use in Accordance with Regulations This machine is exclusively to be used to wash ware such as plates, cups,

More information

Topvex SR03, SR04, SR06 Compact Air Handling Unit

Topvex SR03, SR04, SR06 Compact Air Handling Unit Compact Air Handling Unit GB GB Corrigo ver. no. 1.2-1-00 Manufacturer Our products are manufactured in compliance with applicable international standards and regulations. Systemair AB Industrivägen 3

More information

The CAB & DAB Air Curtains

The CAB & DAB Air Curtains The CAB & DAB Air Curtains Frequently Asked Questions General Positioning Page 2 Electrical & Connection Page 4 Electric Heated Page 5 Electronic door triggered shutdown feature (Electric) Page 5 Electronic

More information

USER MANUAL SILENT16 PORTABLE AIR CONDITIONER

USER MANUAL SILENT16 PORTABLE AIR CONDITIONER USER MANUAL SILENT16 PORTABLE AIR CONDITIONER Thank you for choosing electriq Please read this user manual before using this innovative Air Conditioner and keep it safe for future reference. Visit our

More information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com UNPACKING

More information

Primo Hotel. General. Indoor climate units for hotel rooms

Primo Hotel. General. Indoor climate units for hotel rooms Indoor climate units for hotel rooms General Primo Hotel indoor climate unit Ceiling-mounted indoor climate units for ventilation, cooling and heating High capacity; occupies little space Dry system without

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual TX 250A TX 500A TX 750A TX 1000A Rev. 2014.10.01 Page 1 of 24 1.0.0 Table of contents 1.0.0 TABLE OF CONTENTS... 2 2.0.0 ILLUSTRATIONS... 2 3.0.0 GENERAL

More information

Bench-Top Vacuum Oven with 28 segments programmable controller

Bench-Top Vacuum Oven with 28 segments programmable controller Bench-Top Vacuum Oven with 28 segments programmable controller DZF-6000F Series Vacuum Oven MTI Corporation www.mtixtl.com 1 Safety notes DZF Vacuum Oven Please read the following safety notes carefully

More information

User instructions DHP-AT

User instructions DHP-AT User instructions DHP-AT VUGFC202 If these instructions are not followed during installation and service, Danfoss A/S liability according to the applicable warranty is not binding. Danfoss A/S retains

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

AirUnit. Operating manual. mfh systems modern floor heating. Decentralised domestic ventilation

AirUnit. Operating manual. mfh systems modern floor heating. Decentralised domestic ventilation mfh systems modern floor heating AirUnit Decentralised domestic ventilation Operating manual List of contents, Operating manual Page 1. General information... 02 2. Device description... 03 3. Adjustment

More information

PRODUCT DATA COMPACT S BY NILAN. Sanitary hot water production. Passive heat recovery. Comfort heating. Ventilation < 375 m 3 /h. Active heat recovery

PRODUCT DATA COMPACT S BY NILAN. Sanitary hot water production. Passive heat recovery. Comfort heating. Ventilation < 375 m 3 /h. Active heat recovery PRODUCT DATA COMPACT S BY NILAN Domestic Passive heat recovery Active heat recovery Ventilation < 375 m 3 /h Comfort heating Comfort cooling Sanitary hot water production COMPACT S Product description

More information

Heat Sensor Cable Alarm Units DT650L / DT950L

Heat Sensor Cable Alarm Units DT650L / DT950L Heat Sensor Cable Alarm Units DT650L / DT950L For conventional and 950 series analogue addressable systems Installation and Commissioning Manual Version 2.1 / May 2004 http://www.geindustrial.com/ge-interlogix/emea

More information

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS HP727S Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS 1. General Description 2. Specifications 3. Installation Instructions 4. Electrical Wiring 5. Instrument Wiring

More information

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N V:\Technical\ARTWORK\Fitting & Wiring\Word Files COMPLETE\442073Q.doc Sentinel Kinetic MVHR and Kinetic Plus MVHR Operation & Monitoring Stock Ref. N 438222 Kinetic B 438222A Kinetic BS 443319 Kinetic

More information

PORTABLE AIR CONDITIONER MODEL NO: AC7000

PORTABLE AIR CONDITIONER MODEL NO: AC7000 PORTABLE AIR CONDITIONER MODEL NO: AC7000 PART NO: 3230565 OPERATION & MAINTENANCE INSTRUCTIONS GC1214 INTRODUCTION Thank you for purchasing this CLARKE Portable Air Conditioner. Before attempting to operate

More information

CONTENTS. 1. Safety recommendations 2 Table of warning and attention plates 3. Description of the unit 4. Operation 5. Handling

CONTENTS. 1. Safety recommendations 2 Table of warning and attention plates 3. Description of the unit 4. Operation 5. Handling CONTENTS 1. Safety recommendations 2 Table of warning and attention plates 3. Description of the unit 4. Operation 5. Handling 6. Installation 6.1 Plates 6.2 Dimensions 6.3 Location 6.4 Free room 6.5 Installation

More information

Description of the functions, IQlogic

Description of the functions, IQlogic , IQlogic General Control...168 Status...168 IQnavigator hand-held terminal and image management...169 Dashboard...169 Main setup...170 Air flow Regulation mode...171 Boost...171 Unit...171 Air adjustment...171

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC AQB8J6WC_IM_E_25864 2006.4.4 3:29 PM Page 7 INSTALLATION MANUAL Indoor Unit AQB8J6WC AQB24J2WC Outdoor Unit UQB8J6WC UQB24J2WC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

DIGI3U. Zoning Systems. Installation Guide. That s all we do. Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications

DIGI3U. Zoning Systems. Installation Guide. That s all we do. Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications Installation Guide DIGIU Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications -Zone Controller for the RNC Market Part #DMAN October 004 Zoning Systems That s all we do. INTRODUCTION

More information

CENTRAL AIR CONDITIONER SPLIT SYSTEM

CENTRAL AIR CONDITIONER SPLIT SYSTEM CENTRAL AIR CONDITIONER SPLIT SYSTEM WITH ELECTRONIC CONTROL SERIES: DS INSTALLATION INSTRUCTIONS INDEX GENERAL... 2 UNIT LOCATION CRITERIA... 2 DIMENSIONAL DRAWINGS... 3 INDOOR UNIT INSTALLATION... 5

More information

Packaged air conditioning unit condensed by air model RTC 07L to 30L. Technical information. Ref.: Y-R

Packaged air conditioning unit condensed by air model RTC 07L to 30L. Technical information. Ref.: Y-R Packaged air conditioning unit condensed by air model RTC 07L to 30L Ref.: Y-R70167 0707 Technical information I S O 9 0 0 1 ER-0028/1991 Johnson Controls Manufacturing España, S.L. is participating in

More information

NR-20DU. Keep this manual near this remote controller for future reference whenever maintenance or service is required.

NR-20DU. Keep this manual near this remote controller for future reference whenever maintenance or service is required. NR-20DU Keep this manual near this remote controller for future reference whenever maintenance or service is required. Contents Safety Instructions 3 Included Items 4 Connecting the Extension Cable 5 Attaching

More information

MARVAIR SCHOLAR III HEAT PUMPS & AIR CONDITIONERS MODELS VAIA & VAISA EXPLODED VIEW PARTS ID

MARVAIR SCHOLAR III HEAT PUMPS & AIR CONDITIONERS MODELS VAIA & VAISA EXPLODED VIEW PARTS ID CABINET SHEET METAL (OUTER PANELS) 1 CABINET SHEET METAL (OUTER PANELS) 1 2 Left Side Door, Includes Exterior Panel and Perforated Interior Panel Right Side Door, Includes Exterior Panel and Perforated

More information

Capacity controller for water chiller AK-CH 650

Capacity controller for water chiller AK-CH 650 Capacity controller for water chiller AK-CH 650 Menu operation via AKM Menu list This menu function can be used together with system software type AKM. The description is divided up into function groups

More information

USER MANUAL. Portable Air Conditioner and Heater With Heat Pump Technology PAC18. Please read this manual carefully prior to operating the product.

USER MANUAL. Portable Air Conditioner and Heater With Heat Pump Technology PAC18. Please read this manual carefully prior to operating the product. USER MANUAL Portable Air Conditioner and Heater With Heat Pump Technology PAC12 PAC15 PAC18 Please read this manual carefully prior to operating the product. TABLE OF CONTENTS INTRODUCTION... 3 IMPORTANT

More information

FDM Series. User Manual. SKOPE Food Display Cabinet Integral models: FDM900i/1200i/1500i. Model FDM1200i

FDM Series. User Manual. SKOPE Food Display Cabinet Integral models: FDM900i/1200i/1500i. Model FDM1200i FDM Series SKOPE Food Display Cabinet Integral models: FDM900i/1200i/1500i Model FDM1200i MAN2056O Rev 2.0 Aug. 2010 Integral models: FDM900i/1200i/1500i SKOPE Food Display Cabinet MAN2056O Rev 2.0 Aug

More information

- 1 - Updated on 18 March, 2010

- 1 - Updated on 18 March, 2010 - 1 - Updated on 18 March, 2010 TABLE OF CONTENTS 1. SPECIFICATION & PARTS IDENTIFICATION...3 2. OPERATION & FUNCTION OF PARTS...4, 5 A. Cooling Operation B. Heating Operation C. Function of Parts 3. LOCATION

More information

USER MANUAL CTS700 TOUCH BY NILAN. Compact P / Compact P Polar (English)

USER MANUAL CTS700 TOUCH BY NILAN. Compact P / Compact P Polar (English) USER MANUAL CTS700 TOUCH BY NILAN Compact P / Compact P Polar (English) Version 2.00-03.10.2016 TABLE OF CONTENTS Safety Important information...4 Power supply... 4 Heat pump domestic hot water...4 Disposal...

More information

Table of contents. Installing the charcoal filter 18 Cleaning the prefilter 18 Long term storage 18 Troubleshooting 19 Limited warranty 22

Table of contents. Installing the charcoal filter 18 Cleaning the prefilter 18 Long term storage 18 Troubleshooting 19 Limited warranty 22 Table of contents Table of contents 1 Thank you 2 Energy saving tips 2 Notes 2 Specifications 3 Safety precautions 3 Parts 5 Front view 5 Rear view 5 Accessories 6 Installation 7 Installing the exhaust

More information