Installer manual GreenMaster-HP

Size: px
Start display at page:

Download "Installer manual GreenMaster-HP"

Transcription

1 Installer manual GreenMaster-HP Transport and installation Ventilation unit IHB EN

2 2 GreenMaster-HP Transport and installation

3 Introduction Here you can read about how best to handle the GreenMaster-HP heat pump unit. The instructions consist of basic information and recommendations regarding transport and installation. 1 The instructions should be complied with to ensure safe, trouble-free operation. The key to trouble-free and safe operation of the unit is to carefully read this manual, together with the corresponding manual for the heat pump unit. Use the unit in accordance with the guidelines provided, and follow all safety provisions. Index 1. Transport Unloading and lifting with forklift trucks or pallet trucks Unloading and lifting with a crane Storage before installation Angle Separated version due to narrow transport route Installation Installation of unit and ducting Load-bearing surface Protection of chassis for outdoor installation Joining unit sections Installation of ducting Electrical installation and pipe laying Electricity for unit including control unit GreenManager control unit Cable drawing and installation of external components Pressure sensor Switches Certifications The owner's responsibility Specific risks Switches Water traps for condensation Pipe connections to the coil Valves Wastewater and water traps Protective measures Dismantling/recycling General NB! All service and installation work should be carried out by experienced or trained staff. 1 Air-Site retains the right to make changes and improvements to the content of this manual without prior notice. Transport and installation GreenMaster-HP 3

4 1. Transport The GreenMaster-HP is normally delivered complete, in composite version, and filled with cooling media, with a bottom frame attached under the heat pump section. Upon request, the unit can be delivered without liquid for easy dismantling and reinstallation in a fan room. See section 1.5 Separated version due to narrow transport route. Loading, unloading and transport on site should be carried out using forklift trucks, pallet trucks or cranes. Suitable lifting straps must always be used. 1.1 Unloading and lifting with forklift trucks or pallet trucks The forks of the truck must be long enough that no damage is caused to the underside of the unit. Ensure that the forks reach through to the other side of the unit. 1.2 Unloading and lifting with a crane A unit delivered on a wooden pallet must be lifted off with straps according to the figure below. A unit delivered with pre-installed machine feet must be lifted with the straps inside the machine feet and with the straps fully tightened. A unit delivered without machine feet must be lifted with the straps through the lifting hole of the bottom frames and with the straps fully tightened. Lifting beams should be positioned so that there is no risk of the unit falling. Ensure that the beams are strong enough to lift the load and the straps are not rubbing against and damaging the upper part of the unit. Use beams or a lifting yoke to keep the straps away from the upper part of the unit. NB! Use flat beams and ensure that the straps are fully tightened. 1.3 Storage before installation The unit must be protected from weather and impacts. The packaging must be removed, and the unit covered with a tarpaulin or similar. To ensure as little condensation as possible, good air circulation must be provided between the protective cover and the unit. 4 GreenMaster-HP Transport and installation

5 1.4 Angle The unit should be transported upright or with less than a 30 angle. 1.5 Separated version due to narrow transport route Upon request, the unit can be delivered without cooling media, which means that the unit can be divided into six parts + bottom frame. This design is intended for units to be moved into fan rooms in properties where the transport route is narrow and where drilling for lifting into position is not possible. NB! Don't forget to disconnect the control cables and pipe couplings before separating parts for lifting into position. Start by placing the bottom frame in position and checking that it is completely horizontal. Then install the remaining parts one by one on top of the bottom frame into the pre-drilled holes that attached the parts on delivery. NB! Read and follow the instructions under point Joining unit sections. Cooling media pipes between the heat pump module/modules and the cooling coil in the ventilation section must be connected on site. The weight per section is provided in the unit specification for installed units. 2. Installation 2.1 Installation of unit and ducting Important! When a unit is installed, we recommend a free space in front of the unit of at least 950 mm but ideally as large as the unit is wide, to facilitate maintenance and inspection. NB! To be able to screw together the unit sections and to carry out future servicing, we recommend a minimum distance between wall and unit of 600 mm Load-bearing surface The surface under the unit should be level, so that the unit's final position is and remains completely horizontal. The machine feet can be used to adjust the chassis so that the unit achieves a horizontal position. The surface must be able to support the load of the unit. If the installation uses lightweight constructions or has particularly sensitive areas, the unit should be placed on a vibration absorbing foundation with the required characteristics. Remember! Ducting must be vibration and noise insulated and may not be installed directly on joists, trusses or other critical building sections Protection of chassis for outdoor installation The unit has no drip plates between the unit and the chassis. A local installer must therefore install additional protection and insulation for the chassis, so that the water does not run down beneath the unit. Air-Site's design assumes that the unit will be installed on a watertight roof, which does not risk moisture damage because of water run-off from the condensation trough or external moisture such as rain or snow. NB! Water traps placed outdoors must be protected with a heating cable (accessory kit; electrical heating loop) to avoid freezing when subject to cold outdoor temperatures Joining unit sections Prior to dismantling for transport to the fan room, note which sections are positioned where to facilitate installation when the sections are in the fan room. Transport and installation GreenMaster-HP 5

6 1. Start by placing the bottom frame in position and checking that it is completely horizontal. 2. Then position the first heat pump section and ensure that it is completely horizontal. Screw it to the bottom frame in the pre-drilled holes to which it was attached on delivery. 3. Continue with the middle section in the lower part and screw to the bottom frame as for the previous section. 6 GreenMaster-HP Transport and installation

7 4. Then install the last section of the heat pump section and screw to the bottom frame as for the previous section. After this, all sections should be screwed together with their connection brackets as was the case on delivery. Screw or clamp cooling media pipes and check that they are completely tight before installing the upper part/ventilation section on top of the heat pump section. 5. Install the fan section as shown in the image. Note that the fan section can be positioned on the right if the unit is delivered as a right-hand inspection version. In the example below, the unit is a left inspection version. 6. Install the coil section in the middle according to the image. NB! Cooling media pipes between the coil and heat pump section must be screwed or clamped together by an authorised HVAC and sanitation Transport and installation GreenMaster-HP 7

8 installer/pipefitter. The inspection/service hatch is accessible from both in front and behind on the coil section to access the pipe connection between the ventilation and heat pump sections. 7. Finally, install the filter unit (which includes the control panel) according to the image. After this, all sections should be screwed together with their connection brackets as was the case on delivery. Connection brackets are also used between the upper and lower level, both front and back. NB! Don't forget to reconnect cables in the relevant couplings/connection boxes. NB! Do not open the doors of the sections before they are positioned closely together, and you have ensured that they are level both vertically and horizontally. 8 GreenMaster-HP Transport and installation

9 NB! The recommended minimum distance between wall and unit is 600 mm. Connection brackets are generally used on the outside of the sections, but where it is not possible to screw together the sections with external connection brackets and where extra stability and rigidity may be required, internal connection brackets can be used. Carefully check each section so that no connection brackets are missed when joining parts together. The standard version of the GreenMaster-HP uses 12 connection brackets on sizes 2 and 3. On sizes 4 and 5, 16 connection brackets are used Installation of ducting If flexible connections are to be used between the unit and ducting, ensure that the duct connections are almost completely taut, but with a little play to prevent damage to the fabric. At the fan outlet, the duct size should be as like the outlet size as possible. For the minimum distance between the fan wheel and the nearest ducting part, please read the unit specification for the installed unit. Avoid blocking and creating turbulence at the fan outlet. 2.2 Electrical installation and pipe laying Electricity for unit including control unit The control system is configured according to specifications in the order. A report containing the final test is supplied together with the GreenMaster unit. Transport and installation GreenMaster-HP 9

10 GreenManager control unit Indoor version: The control unit for the ventilation section is installed inside the filter unit in the ventilation section according to the drawing in the unit specification. Internal and external connections belonging to the unit's components are as a rule pre-installed and function tested. An extension cable is present in the heat pump section, electrically linking the ventilation parts. Hoses are pre-installed according to the same principle. The control unit for the heat pump section is placed in the middle of the heat pump section, together with the supply box for the entire unit. These are internally connected with the control unit in the ventilation section, so that the only external connections required to the unit are one network connection (RJ45) and one supply cable. Please read the unit specification for the rated electrical data. Outdoor version: The control unit for the ventilation section is installed inside the filter unit in the ventilation section according to the drawing in the unit specification. Internal and external connections belonging to the unit's components are as a rule pre-installed and function tested. An extension cable is present in the heat pump section, electrically linking the ventilation parts. Hoses are pre-installed according to the same principle. The control unit for the heat pump section is placed in the middle of the heat pump section, together with the supply box for the entire unit. These are internally connected with the control unit in the ventilation section, so that the only external connections required to the unit are one network connection (RJ45) and one supply cable. Please read the unit specification for the rated electrical data Cable drawing and installation of external components Indoor version: Temperature sensors, hoses and other ordered components will be supplied in a box inside or beside the unit. External cabling should be connected to the control unit according to the circuit diagram in the technical specification. NB! Where the unit is delivered in separate sections, some parts of the electrical cabling may be disconnected. An authorised electrician or Air-Site representative must be present when this cabling is connected. External components such as dampers are installed with guide strips and corners. You should then follow the circuit diagram for connection to the relevant control unit. Outdoor version: Temperature sensors, hoses and other ordered components will be supplied in a box inside or beside the unit. External cabling should be connected to the control unit according to the circuit diagram in the technical specification. NB! Where the unit is delivered in separate sections, some parts of the electrical cabling may be disconnected. An authorised electrician or Air-Site representative must be present when this cabling is connected. External components such as dampers are installed with guide strips and corners. You should then follow the circuit diagram for connection to the relevant control unit Pressure sensor A differential pressure transmitter for flow control is pre-installed in the plenum. A pressure sensor for regulation of duct pressure is integrated into the GreenManager, and measures the duct pressure directly outside the filter section. If an extension of the duct pressure hose is required, this should be undone internally in the filter section and an external hose extended further on in the extract air duct. 10 GreenMaster-HP Transport and installation

11 A pressure sensor for the extract air filter is integrated into the GreenManager and is generally pre-connected to the control unit. A pressure sensor for measuring pressure over the coil is integrated into the GreenManager and is generally pre-connected to the control unit. Hoses Unit deliveries where the control unit is included are pre-equipped with pressure hoses for pressure regulation, extract air filter and pressure measurement of the coil. Each measurement outlet on the GreenMaster unit is marked with the object's designations. The hoses on the GreenMaster-HP unit are generally pre-connected at both ends, but may be disconnected if the unit was delivered in separate sections. When installing the unit, it is therefore important for all hoses which will be used in the installation to be installed correctly according to the markings on the unit and control unit Switches The main switch is generally delivered installed and connected. An authorised electrician must lay the supply cable to the unit's main switch Certifications According to the Swedish Work Environment Authority s regulations, an authorised HVAC and sanitation installer/pipefitter must carry out the work required on the cooling and heating sections and relating to external pipe connections. Electrical connections must be carried out by unauthorised electrician The owner's responsibility The owner is responsible for informing local authorities of the below information. Similar provisions apply in other countries to a certain extent. Information about the site, function, size and maintenance schedule Specific risks Uncertified technicians may never open the cooling circuit when it is under pressure from the cooling media. Changes and repairs to the cooling circuit may only be carried out by trained technicians from certified companies. Never open the inspection hatch before the fans have been switched off Switches The main switch must be installed in accordance with applicable regulations. Study the circuit diagram supplied carefully! Water traps for condensation An integrated water trap is installed inside the GreenMaster-HP unit, and run-off tubes are positioned along the outside of the unit in proximity to the external pipe connection. This must be connected to an external wastewater line/drain. Any external water traps must function for underpressure and be installed according to the principle in Section Wastewater and water traps. NB! Condensation run-off hoses for compressors in the heat pump section are at the front edge of the unit and must also be connected to run-off/wastewater line/drain. Transport and installation GreenMaster-HP 11

12 2.2.5 Pipe connections to the coil If the unit is delivered in separate sections, be careful to check that all of the pipes have been connected correctly according to the delivery principle. Normally all pipe parts are pressure tested together with the unit, but if the unit is refilled after delivery, the pipe connection must be pressure tested after refilling. Pipe connections are checked during Air-Site's factory tests Valves The connection pipe is externally threaded. Any valves and valve motors included in the delivery will be in a box inside the unit. Connect actuators according to the circuit diagram Wastewater and water traps Drip trays/troughs are installed under any cooling hoses and heat exchangers to collect condensation water. All drip trays are equipped with drainage outlets. The water traps ensure that water can run away from the trays. The water traps are delivered in a box inside or beside the unit. To ensure that the water can run away in a secure manner, Air-Site's water traps should be used. NB! Insulate the pipe to avoid it freezing. Installation at the underpressure The water trap is connected to the unit where the condensation outlet and underpressure (suction fan) is located. The condensation outlet and underpressure are present on the plate heat exchanger (GreenMaster-XXL), coil heat exchanger, coil recycling (GreenMaster-HP) etc. The water trap can be rotated to the right or left. The non-return valve should always be in a vertical position. The outlet of the water trap should be positioned so that damage does not occur to adjacent unit sections or building constructions. Drainage that leads to a cold space should be insulated against cold. A heating cable may be required, for example in the case of installation outdoors. Height A (distance between the unit's run-off level and the water trap's run-off level) must be at least as big in millimetres as the underpressure in the unit is in Pa/10 (Example: Underpressure 250 Pa/10 = 25 mm). If necessary for space reasons, pipes can be cut or inclined, provided that the conditions above are fulfilled. Installation at the overpressure The water trap is connected to the section where the condensation outlet and overpressure (pusher fan) is located. The condensation outlet and overpressure normally only occur on cooling coils (air coolers). Remove the cover and the ball inside the non-return valve so that air can pass freely. Replace the cover. The included pipe and T-connection are installed according to the sketch. Pipes from the T-connection can be adapted if necessary by cutting the pipe (or a corresponding pipe) so that it leads to a floor drain. See below and sketch. Height A (distance between the water surface and end of the pipe) must be at least as big in millimetres as the overpressure in the relevant section is in Pa/10 (Example: Overpressure 250 Pa/10 = 25 mm). 12 GreenMaster-HP Transport and installation

13 If there are additional drainage outlets, a water trap is required at each outlet. The diameter of the pipe in the water trap and wastewater system must agree with the diameter of the pipe in the drainage outlet. 3. Protective measures Read the description in the operating manual (OHB). 4. Dismantling/recycling Disconnect all electrical and pipe connections before dismantling. Any liquids must be emptied from the unit and the unit must then be recycled according to current local regulations. When the unit has been dismantled, the sections must be taken to pieces and all parts sorted by material type. The material must then be transported to the intended location. More information is available in the maintenance instructions. 5. General For additional information, read the operating manual (OHB). Transport and installation GreenMaster-HP 13

14 Notes 14 GreenMaster-HP Transport and installation

15 Notes Transport and installation GreenMaster-HP 15

16 Air-Site AB Elementvägen LINDOME Sweden Phone: info@air-site.se

GreenMaster HP Exhaust air heat pump for residential properties

GreenMaster HP Exhaust air heat pump for residential properties GreenMaster HP Exhaust air heat pump for residential properties Air-Site We are a Swedish company that likes air and energy recovery. That's why we develop products that use air to heat, cool and provide

More information

lindab we simplify construction Lindab Modular air handling units Transport and assembly manual

lindab we simplify construction Lindab Modular air handling units Transport and assembly manual lindab we simplify construction Lindab Modular air handling units Transport and assembly manual Transport and assembly manual 1 General... 3 2 Warnings & Tips... 3 3 Transportation... 3 3.1 Truck loading

More information

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES Using the air handling unit... Free space for service and repair work... GENERAL INSTRUCTION Checking prior to commissioning...3

More information

User manual for TIME. Air handling unit. Manual version Part number of this manual

User manual for TIME. Air handling unit. Manual version Part number of this manual User manual for TIME Air handling unit Manual version 1.01.13 Part number of this manual 90925370 Detailed table of contents on the following pages General description a. Manufacturer b. Name of machines

More information

PROPER WALL MOUNTING OF THE SUITMATE

PROPER WALL MOUNTING OF THE SUITMATE The SUITMATE Swimsuit Water Extractor has been designed and manufactured with safety as our primary consideration. Therefore, it is important that the unit be installed correctly. It is also important

More information

General Characteristics.3. S.M.A.R.T System Set-up...5. Start-up Procedures.6. Shut-down Procedures 8. General Maintenance..8

General Characteristics.3. S.M.A.R.T System Set-up...5. Start-up Procedures.6. Shut-down Procedures 8. General Maintenance..8 1-800-661-3842 1 TABLE OF CONTENTS General Characteristics.3 How the S.M.A.R.T System Works..3 S.M.A.R.T Technical Specifications..3 Erecting the S.M.A.R.T System..4 S.M.A.R.T System Set-up...5 Start-up

More information

Instructions for the BASIC Air Handling System, Sizes General 1.1 Description of the System

Instructions for the BASIC Air Handling System, Sizes General 1.1 Description of the System Instructions for the BASIC Air Handling System, Sizes 004 055 1. General 1.1 Description of the System The BASIC System is a complete modular air handling unit. The unit consists of blocks, i.e. a number

More information

TopMaster Air Handling unit. Installation instructions

TopMaster Air Handling unit. Installation instructions Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into

More information

Installation and maintenance instructions for cabin units type vertical IDAC (V50)

Installation and maintenance instructions for cabin units type vertical IDAC (V50) GB Installation and maintenance instructions for cabin units type vertical IDAC (V50). Application. Bundled parts. Handling. Marking. Weight. Transport. Storage 5. Installation 5. Mounting 5. Water trap

More information

GREEN LOO DRY COMPOSTING TOILET Owners Installation Operation Manual. for the. GT 120 Family and GT 330

GREEN LOO DRY COMPOSTING TOILET Owners Installation Operation Manual. for the. GT 120 Family and GT 330 GREEN LOO DRY COMPOSTING TOILET Owners Installation Operation Manual for the GT 120 Family and GT 330 2 INSTALLATION PLANNING It's all in the planning! For proper operation of the toilet you should consider

More information

Geniox Comfort with control system Air handling unit. User Manual

Geniox Comfort with control system Air handling unit. User Manual Geniox Comfort with control system Air handling unit User Manual GB Document in original language Part number of this manual 90925xxx Detailed table of contents on the following pages General description

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

Smoke extraction duct of sheet steel

Smoke extraction duct of sheet steel Smoke extraction duct of sheet steel The accessories that are available, as for example inspection openings, steel grilles, plenum boxes, ceiling diffusers, splitter attenuators, bends, tees and connecting

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

VETO CLEANER 500 FLUE GAS CLEANER

VETO CLEANER 500 FLUE GAS CLEANER As of serial number 3100 0001 VETO CLEANER 500 FLUE GAS CLEANER USER MANUAL SPARE PARTS LIST Manufacturer: ALA TALKKARI Veljekset Ala-Talkkari Oy FI-62130 HELLANMAA TEL. +358 6 433 6333 FAX +358 6 437

More information

User manual. Juice machine Torn U / EN Rev Your retail dealer

User manual. Juice machine Torn U / EN Rev Your retail dealer User manual Juice machine Torn Your retail dealer U / EN...... Rev. 090914 List of contents List of contents page 2 Dispenser description page 3-7 Installation page 8-9 Cleaning instructions page 10 Trouble

More information

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material 1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside

More information

Service Bulletin Trucks Date Number Page

Service Bulletin Trucks Date Number Page Mack Trucks, Inc. Allentown, PA USA (Does not apply to Mack Trucks Australia) (Supersedes SB215025 dated 03/27/07) Service Bulletin Trucks Date Number Page 11/04/08 SB215025 1(25) Cooling System Revisions

More information

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents

Operating Guide. Termix Compact 28 VX-FI / HWP / HWS. 1.0 Table of Contents. 1.0 Table of Contents 1.0 Table of Contents 1.0 Table of Contents... 1........................................................................ 2 2.0 Functional description... 3 3.0 Safety notes... 4 3.1 Safety Notes general............................................

More information

39 HQ Air Handling Units AiroVision

39 HQ Air Handling Units AiroVision VDI 6022 39 HQ Air Handling Units AiroVision Assembly/Installation, Commissioning, Maintenance Manual Type tested Production monitored AHU N : 08.02.251 Range: 39HQ DIN 1946-4 EN 13053 2 Code No: B.8.1.3i

More information

Refrigerator BRFB1920SS BRFB1900FBI BRFB1920FBI

Refrigerator BRFB1920SS BRFB1900FBI BRFB1920FBI Refrigerator BRFB1920SS BRFB1900FBI BRFB1920FBI Table of Contents Symbols and Their Meanings... 3 Product weight... 5 Load bearing capacity of the doors... 5 Climate class... 5 Product Information:...

More information

Novenco Air Handling Units

Novenco Air Handling Units Novenco Air Handling Units Climaster ZCF Guide 919432-0 GB Important This document is provided As is and is subject to change without notice. Novenco reserves this right due to continuous product development.

More information

FLOW-THROUGH FURNACE HUMIDIFIER

FLOW-THROUGH FURNACE HUMIDIFIER FLOW-THROUGH FURNACE HUMIDIFIER Installation Warranty Maintenance Troubleshooting Guide 2 Installation READ COMPLETE INSTALLATION INSTRUCTIONS AND TEMPLATE BEFORE STARTING Attention Installer: Installation

More information

AHU INSTALLATION & OPERATION MANUAL

AHU INSTALLATION & OPERATION MANUAL AHU INSTALLATION & OPERATION MANUAL VERSION 2 AIR HANDLING UNIT MODELS: AHU 500, AHU 900, AHU 1200, AHU 1700, AHU 2000, AHU 2500, AHU3500, AHU 4500, AHU 5000, AHU 6000, AHU 7000, AHU 8000, AHU 10000, AHU

More information

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450 1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside

More information

OIL COOLER INSTRUCTION HANDBOOK

OIL COOLER INSTRUCTION HANDBOOK OIL COOLER INSTRUCTION HANDBOOK INDEX 1. GENERALITY 2 1.1 OPERATING RANGE 1.2 IMPORTANT 2. INSTALLATION 3 2.1 TRANSPORTATION 2.2 INSTALLATION LOCATION 2.3 PIPING 2.4 WIRING (see the electrical diagram

More information

Installation Instructions

Installation Instructions 38MHR Outdoor Unit Single Zone Ductless System Sizes 09 to 24 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. NOTE: Images are for illustration purposes

More information

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS 6720 Columbus Road Mississauga, Ontario Canada, L5T 2G1 Tel: (905) 670 3595 Fax: (905) 670 3592 Web: www.temspec.com TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS INSTALLATION AND MAINTENANCE

More information

G-10s. Instruction Manual. G-Series Cooler UPRIGHT COOLER. Part No.11IPA

G-10s. Instruction Manual. G-Series Cooler UPRIGHT COOLER. Part No.11IPA G-Series Cooler UPRIGHT COOLER Part No.11IPA-062800 Instruction Manual FOR YOUR FUTURE REFERENCE Thank you for using our product. This manual will guide you in getting the best use of your cooler. Remember

More information

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit DC Heat Recovery Unit MVHR Wholehouse heat recovery unit Stock Ref. N DC Heat Recovery Unit MVHR 443423 Installation, Maintenance & Users Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

More information

Air handling unit. X-CUBE compact. GB/en. Transport and installation manual. including X-CUBE compact accessories

Air handling unit. X-CUBE compact. GB/en. Transport and installation manual. including X-CUBE compact accessories Transport and installation manual GB/en Air handling unit X-CUBE compact including X-CUBE compact accessories Read the instructions prior to performing any task! TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn

More information

Media Service Instructions 1500 Series BAT Media Plants

Media Service Instructions 1500 Series BAT Media Plants R Media Service Instructions 1500 Series BAT Media Plants J-500 MEDIA SERVICE Read these instructions and perform every step. After servicing 2 or 3 installations, you will only have to refer to these

More information

INSTALLATION & MAINTENANCE

INSTALLATION & MAINTENANCE INSTALLATION AND MAINTENANCE INSTRUCTIONS 1 INSTALLATION & MAINTENANCE FIBRE-REINFORCED PLASTIC AIR HANDLING UNITS fibre-reinforced plastic AHU 2 INSTALLATION AND MAINTENANCE INSTRUCTIONS Table of contents

More information

DOMEKT ReCU 400VE(W)CF-EC-C4 Series Air Handling Units Installation and Maintenance Service Manual

DOMEKT ReCU 400VE(W)CF-EC-C4 Series Air Handling Units Installation and Maintenance Service Manual DOMEKT ReCU 400VE(W)CF-EC-C4 Series Air Handling Units Installation and Maintenance Service Manual EN Content Safety Requirements...3 Transportation...3 Brief Description of the Unit...5 Installation...6

More information

ZEST HOOD. Instructions Manual.

ZEST HOOD. Instructions Manual. ZEST HOOD Instructions Manual www.rangemaster.co.uk INDEX EN RECOMMENDATIONS AND SUGGESTIONS... 3 CHARACTERISTICS... 4 INSTALLATION... 6 USE... 14 MAINTENANCE... 16 2 RECOMMENDATIONS AND SUGGESTIONS The

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

INSTALLER S MANUAL. Evaporative Air Coolers. Safety Information Installation Commissioning. Models

INSTALLER S MANUAL. Evaporative Air Coolers. Safety Information Installation Commissioning. Models INSTALLER S MANUAL Safety Information Installation Commissioning Models Classic : KC17 KC21 KC27 KC32 Low Profile : KL16 KL22 KL25 KL28 Kaden Installer's Manual TABLE OF CONTENTS Warnings and Important

More information

WYND DC 54 CEILING FAN Installation Manual

WYND DC 54 CEILING FAN Installation Manual WYND DC 54 CEILING FAN Installation Manual CFFCWY4XXX Remote control included YOUR FANCO WYND 54 DC CEILING FAN Congratulations on purchasing your new Fanco Wynd 54 DC Ceiling Fan. Before attempting to

More information

INSTALLATION GUIDE NZ AU

INSTALLATION GUIDE NZ AU DISHWASHER DW60U6I & DW60U2I models INSTALLATION GUIDE NZ AU 1 SAFETY AND WARNINGS 100 lb 45 kg! WARNING! Electrical shock hazard Before installing the dishwasher, remove the house fuse or open the circuit

More information

MJC Cartridge Filter Unit Operation & Maintenance

MJC Cartridge Filter Unit Operation & Maintenance 1 of 19 Hodge Clemco Ltd MJC Cartridge Filter Unit Operation & Maintenance Owner s Manual Date of Issue: 19.07.04 TSSM536.1a Hodge Clemco Ltd Orgreave Drive Sheffield S13 9NR Tel: 0114 254 8811 Fax: 0114

More information

MIST MAX MODEL MM800. Important: Installation and Operation Manual

MIST MAX MODEL MM800. Important: Installation and Operation Manual MIST MAX MODEL MM800 Installation and Operation Manual TM Important: This manual contains specific cautionary statements relative to worker safety. Read this manual thoroughly and follow as directed. It

More information

LINE SET DUCT AND ACCESSORY PRODUCT CATALOG

LINE SET DUCT AND ACCESSORY PRODUCT CATALOG VAC LINE SET DUCT AND ACCESSORY PRODUCT CATALOG Correctly installing an air conditioner requires the use of dedicated accessories. When the customer invests in an air conditioner, he relies on the professional

More information

SportChamp SC2. For cleaning and maintaining sand or granulate infilled artificial turf surfaces and other fully synthetic sports surfaces

SportChamp SC2. For cleaning and maintaining sand or granulate infilled artificial turf surfaces and other fully synthetic sports surfaces 108 For cleaning and maintaining sand or granulate infilled artificial turf surfaces and other fully synthetic sports surfaces The SportChamp, the leading machine in the world market, is the solution for

More information

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h PRODUCT DATA COMFORT 5000 BY NILAN Ventilation & passive heat recovery Commercial Passive heat recovery Ventilation < 5300 m 3 /h COMFORT 5000 The Comfort 5000 is a ventilation unit suitable for central

More information

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS DLCSRA INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes only.

More information

Operating instructions for the DA 8-2 Extractor

Operating instructions for the DA 8-2 Extractor Operating instructions for the DA 8-2 Extractor ]ö M.-Nr. 03 997 810 Description of the appliance Description of the appliance 1 2 6 5 4 3 2 Description of the appliance Description of the appliance The

More information

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS Contents Page User instructions 3-5 General 3 Fan installation 3-4 Maintenance 3 Electrical installation 5 Troubleshooting 5 Technical description 6-8 General

More information

SERVICE MANUAL FOR 6636A & 6636B SERIES TWO TON HIGH EFFICIENCY PACKAGED AIR CONDITIONERS

SERVICE MANUAL FOR 6636A & 6636B SERIES TWO TON HIGH EFFICIENCY PACKAGED AIR CONDITIONERS SERVICE MANUAL FOR 6636A & 6636B SERIES TWO TON HIGH EFFICIENCY PACKAGED AIR CONDITIONERS TABLE OF CONTENTS 1. Warnings & Component Match-Up............................................ 2 2. Unit Specifications..........................................................

More information

TTK 75 ECO OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN

TTK 75 ECO OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN TTK 75 ECO EN OPERATING MANUAL DEHUMIDIFIER TRT-BA-TTK75ECO-TC-002-EN Table of contents Notes regarding the operating manual... 01 Information about the device... 02 Safety... 04 Transport...05 Start-up...05

More information

PLEASE READ ALL SECTIONS OF THIS GUIDE BEFORE COMMENCING YOUR INSTALLATION AND IN CONJUNCTION WITH YOUR DRAWINGS.

PLEASE READ ALL SECTIONS OF THIS GUIDE BEFORE COMMENCING YOUR INSTALLATION AND IN CONJUNCTION WITH YOUR DRAWINGS. Installation Guide This information is provided as a guide and may differ from project to project. It is assumed that the property is a two storey dwelling. Obviously a bungalow represents a simpler task,

More information

Vertical Stack Fan Coil Units Models: TVA, TVE, TVS

Vertical Stack Fan Coil Units Models: TVA, TVE, TVS 6720 Columbus Road Mississauga, Ontario Canada, L5T 2G1 Tel: (905) 670 3595 Fax: (905) 670 3592 www.temspec.com Vertical Stack Fan Coil Units Models: TVA, TVE, TVS INSTALLATION, OPERATION AND MAINTENANCE

More information

Air heater/cooler in combination with ground source heat pump

Air heater/cooler in combination with ground source heat pump Swegon CASA Air heater/cooler in combination with ground source heat pump Installation, operation and maintenance instructions for design engineers, installation engineers and service personnel SDHWM_c_EN

More information

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. INSTALLATION, OPERATION & SERVICE MANUAL FOR COOLER TYPES OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. 1. Introduction This manual is a guide for the installation, maintenance

More information

If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally ventilated solution is a viable option.

If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally ventilated solution is a viable option. Air handling units Aesthetic Not to add significantly to the existing ambient noise levels. Functional requirements If a peak space temperature to about 28ºC is acceptable to the occupants then a naturally

More information

an ISO 9001:2015 Registered Company

an ISO 9001:2015 Registered Company an ISO 9001:2015 Registered Company Mark IV (672001-VHY) 18865 Goll St. San Antonio, TX 78266 Phone: 800-862-6658 Sales: sales@vintageair.com Tech Support: tech@vintageair.com www.vintageair.com 902001-VHY

More information

Topvex SR 09, 11, Topvex TR Compact Air Handling Units

Topvex SR 09, 11, Topvex TR Compact Air Handling Units Topvex SR 09, 11, Topvex TR 09-15 Compact Air Handling Units Installation instructions Document in original language 125593 A003 GB Copyright Systemair AB All rights reserved E&OE Systemair AB reserves

More information

PURest Air Dryer Installation and Maintenance

PURest Air Dryer Installation and Maintenance PURest Air Dryer Installation and Maintenance L31170 Rev. 4/04 The Haldex PURest is a desiccant type dryer that effectively removes moisture, oil and contaminants from the compressed air system. This reduces

More information

Supply air unit VEKA Installation & Maintenance

Supply air unit VEKA Installation & Maintenance November 2008 Safety instructions Operating the air treatment unit and accessory components WARNING Before the air treatment unit is taken into service, any free connections must be provided with protective

More information

CLe-series Dishwashers

CLe-series Dishwashers CLe-series Dishwashers Blower-dryer electric (CLe SERIES) ML-138211 ML-138212 ML-138213 ML-138214 electric (CLeR SERIES) ML-138325 ML-138326 ML-138327 ML-138328 STEAM (CLe SERIES) ML-138226 ML-138227 ML-138228

More information

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS for HOAM and VOAM Open Air Merchandisers

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS for HOAM and VOAM Open Air Merchandisers INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS for HOAM and VOAM Open Air Merchandisers TABLE OF CONTENTS INTRODUCTION 2 STORE CONDITIONS / LOCATION 2 WARNING LABELS AND SAFETY INSTRUCTIONS 3 PRE-INSTALLATION

More information

Installation Manual PS-225 & PS-275

Installation Manual PS-225 & PS-275 Installation Manual PS-225 & PS-275 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal

More information

XC-18. NOTE: *Machine shown without Lift-Up Safety Guard. This guard is included with machine. Machine should not be operated without this guard.

XC-18. NOTE: *Machine shown without Lift-Up Safety Guard. This guard is included with machine. Machine should not be operated without this guard. XC-18 NOTE: *Machine shown without Lift-Up Safety Guard. This guard is included with machine. Machine should not be operated without this guard. EXTREMA MACHINERY COMPANY, INC. PO BOX 1450, ALBANY, LOUISIANA

More information

an ISO 9001:2008 Registered Company GOLL ST. - SAN ANTONIO, TX ph fax MINI SPACE SAVER HEAT /COOL

an ISO 9001:2008 Registered Company GOLL ST. - SAN ANTONIO, TX ph fax MINI SPACE SAVER HEAT /COOL an ISO 9001:2008 Registered Company 18865 GOLL ST. - SAN ANTONIO, TX. - 78266 - ph.210-654-7171 - fax 210-654-3113 MINI SPACE SAVER HEAT /COOL 01000-QUX-A 01000-VUX-A 900101-VUX-A REV C 3/5/14, MINI SPACE

More information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT Carrier International Sdn. Bhd. Malaysia INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT 40LM 120-200 50Hz CONTENTS: Physical Data & Dimension 1-3 Safety Considerations 4 Rigging

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Air Cooled Condensers 8-2016 Rev 0 Table of Contents General Safety Information 2 Inspection 2 Installation 2 6 Rigging and Assembly 2 Unit Location

More information

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2 Cleaning unit for coolant :_decftez`_>r_fr] Book No.: 1271526-02 V2 Alfa Laval Separation AB Separator Manuals, dept. SKEL S-147 80 Tumba, Sweden Telephone: +46 8 53 06 50 00 Telefax: +46 8 53 03 10 40

More information

Handling, transportation and Storage procedure for Optical Fiber Cable Drums

Handling, transportation and Storage procedure for Optical Fiber Cable Drums Application Notes Handling, transportation and Storage procedure for Optical Fiber Cable Drums Author xxxxxxx Issued August 2013 Abstract This document provides the guidelines for handling and storage

More information

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4 Installation Operation Maintenance Ductable water unit FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic hi l PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST FORD TRUCK

specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic hi l PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST FORD TRUCK specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic hi l PERFECT FIT SERIES IN-DASH HEAT/ COOL/ DEFROST 1967-72 FORD TRUCK CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect

More information

ECOJET GREASE LEVEL SENSOR

ECOJET GREASE LEVEL SENSOR ACO Passavant Installation guide ECOJET GREASE LEVEL SENSOR AUTHOR Kate Jennings DATE COMPLETED 8 August 2016 DATE COMPLETED V13 ACO Polycrete, 134-140 Old Bathurst Road, Emu Plains, NSW 2750 Tel: +61

More information

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual DOMEKT ReGO 400VE(W)-B Series Air Handling Units EN Content Safety Requirements...3 Transportation...3 Brief Description of the Unit...5 Installation...6 Maintenance...11 Technical Information......13

More information

Installation Instructions

Installation Instructions 38MPRA Outdoor Unit Single Zone Ductless System Sizes 09 to 12 Installation Instructions NOTES: Read the entire instruction manual before starting the installation. Images are for illustration purposes

More information

MAXI PUMP INSTRUCTION MANUAL NE6151B /NE6171B READ THIS MANUAL CAREFULLY BEFORE USING YOUR MAXI PUMP

MAXI PUMP INSTRUCTION MANUAL NE6151B /NE6171B READ THIS MANUAL CAREFULLY BEFORE USING YOUR MAXI PUMP MAXI PUMP INSTRUCTION MANUAL NE6151B /NE6171B READ THIS MANUAL CAREFULLY BEFORE USING YOUR MAXI PUMP 8104 MAXI-PUMP PARTS BREAKDOWN Re f # 1 2 3 4 5 6 7a 7b 8 9 10 11 12 13 14 15 16 2 Part # NEP2134 NEP2135

More information

REI-M-4B - Installation Manual Rev 1 October SOLID BOSS Installation Manual Deck Drainage Applications

REI-M-4B - Installation Manual Rev 1 October SOLID BOSS Installation Manual Deck Drainage Applications SOLID BOSS Installation Manual Deck Drainage Applications 1 Contents 1. Unpacking & Inspection... 3 A. Testing, Preparation for Shipment and Storage... 3 B. Delivery Inspection & Reporting... 3 C. Storing

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

BLADE BATH SHOWER MIXER DECK MOUNTED CHR WITH KIT INSTALLATION INSTRUCTIONS P BS-E A/2

BLADE BATH SHOWER MIXER DECK MOUNTED CHR WITH KIT INSTALLATION INSTRUCTIONS P BS-E A/2 BLADE BATH MIXER DECK MOUNTED CHR WITH KIT 20007014600 INSTRUCTIONS P5-65511339-1-BS-E A/2 20007014600 INTRODUCTION DIMENSIONS Please read these instructions carefully and keep in a safe place for future

More information

GOLF TECHNICAL BULLETIN

GOLF TECHNICAL BULLETIN *NOTE This correspondence is being delivered to golf sales managers at s authorized distributor organizations. Please distribute to your team at your discretion. Thank you. To The Customer GTB # 16-01

More information

GCG-10. Instruction Manual. G-Series Cooler. Manual is for the following models: GCG-10-N33EB G-10-N33EB UPRIGHT COOLER

GCG-10. Instruction Manual. G-Series Cooler. Manual is for the following models: GCG-10-N33EB G-10-N33EB UPRIGHT COOLER G-Series Cooler GCG-10 UPRIGHT COOLER Manual is for the following models: GCG-10-N33EB G-10-N33EB Instruction Manual Manual is for the following models: GCG-10-N33EB G-10-N33EB Instruction Manual GCG-10

More information

PRE-INSTALLATION PROCEDURE

PRE-INSTALLATION PROCEDURE PRE-INSTALLATION PROCEDURE Required with each BLUPURA Water Treatment System. 1 each External Filter 1 each Chiller 1 each CO 2 Regulator 1 each External Filter 1 each Water Pressure Regulator 1 each 4

More information

Installation plan Commercial Washing Machine PW 413 PW 418

Installation plan Commercial Washing Machine PW 413 PW 418 Installation plan Commercial Washing Machine PW 413 PW 418 To avoid the risk of accidents or damage to the machine, it is essential to read these instructions before it is installed and used for the first

More information

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 1 INTRODUCTION... 1 INSTALLATION...

More information

Installer manual AG-WL10

Installer manual AG-WL10 LEK LED CLEAN TIMER OPERATION Installer manual Indoor unit air/air heat pump IHB GB 1637-1 331827 Table of Contents 1 Important information Safety information Read before starting the installation Electrical

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance DUCTABLE WATER UNIT FWD 08-12 - 20-30 - 45 General Information Foreword These installation, operation and maintenance instructions are given as a guide to good practice

More information

Installation Operation Maintenance

Installation Operation Maintenance Installation Operation Maintenance Voyager I Rooftop Units Cooling-only TSD/TSH 060 072 102 120 Reversible WSD/WSH 060 072 090 Gas-fired YSD/YSH 060 072 090 102 120 RT-SVX20D-E4 Original instruction Table

More information

TECHNICAL MANUAL YEFB HIGH PRESSURE DUCTED UNIT

TECHNICAL MANUAL YEFB HIGH PRESSURE DUCTED UNIT 1. GENERAL INFORMATION 1.1 Applications page 2 1.2 Operation» 2 1.3 Performances» 2 1.4 Product range» 2 1.5 Selection software» 2 2. DIMENSIONS AND WEIGHTS» 3 3. COMPONENTS 3.1 Structure» 4 3.2 Coils»

More information

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. Irene 52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V. 60Hz TABLE OF CONTENTS Tools and Materials Required... 1 Package Contents... 1 Safety Rules... 2 Mounting Options... 3 Hanging

More information

TM Series. Induced Draft, Counter Flow Optional Accessories

TM Series. Induced Draft, Counter Flow Optional Accessories ANTIFREEZE PACKAGE / RESISTANCE HEATING OPTION The antifreeze package is supplied to provide protection against freezing of standing water in the cooling tower sump due to shutdown during winter operation.

More information

M2 Series Startup Form

M2 Series Startup Form M Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is there

More information

Installing the Turbo Floor Model System

Installing the Turbo Floor Model System Installing the Turbo Floor Model System Location 1. Locate as close as possible to water supply source. 2. Locate as close as possible to a three-prong grounding receptacle. 3. Locate the System on a smooth

More information

Instructions for installation and use English. More documents on: H B /09

Instructions for installation and use English. More documents on:  H B /09 TM Instructions for installation and use English EN More documents on: www.zodiac-poolcare.com H0538700.B - 2015/09 Read this manual carefully before installing, maintaining or repairing this appliance!

More information

G-7s. Instruction Manual. G-Series Cooler COUNTERTOP COOLER. Part No.11IPA

G-7s. Instruction Manual. G-Series Cooler COUNTERTOP COOLER. Part No.11IPA G-Series Cooler COUNTERTOP COOLER Part No.11IPA-061000 Instruction Manual FOR YOUR FUTURE REFERENCE This easy-to-use manual will guide you in getting the best use of your cooler. Remember to record the

More information

Table of Contents SPECIFICATIONS Page 2. FOR THE INSTALLER Page 3. FOR THE PLUMBER Page 4. INSTALLATION Page 5. INITIAL START UP Page 6

Table of Contents SPECIFICATIONS Page 2. FOR THE INSTALLER Page 3. FOR THE PLUMBER Page 4. INSTALLATION Page 5. INITIAL START UP Page 6 INTRODUCTION This service manual covers the installation, operation, maintenance and service of this ice machine. Table of Contents SPECIFICATIONS Page 2 FOR THE INSTALLER Page 3 FOR THE PLUMBER Page 4

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

Index BEFORE USING THE APPLIANCE Safety Instructions... 2 Recommendations... 3 Switching On the Appliance... 4 HOW TO OPERATE THE FREEZER...

Index BEFORE USING THE APPLIANCE Safety Instructions... 2 Recommendations... 3 Switching On the Appliance... 4 HOW TO OPERATE THE FREEZER... Index BEFORE USING THE APPLIANCE... 2 Safety Instructions... 2 Recommendations... 3 Switching On the Appliance... 4 HOW TO OPERATE THE FREEZER... 5 Thermostat Setting... 5 Display Panel... 5 FOOD STORAGE

More information

ACTIVA SERIES ROOF TOP Air Conditioners 017/040

ACTIVA SERIES ROOF TOP Air Conditioners 017/040 ACTIVA SERIES ROOF TOP Air Conditioners 017/040 Installation manual Ref.: N-40388_EN 0112 Index Index 1 Installation manual...1 1.1 Safety instructions...2 1.2 Icons used in this document...2 1.3 Instructions

More information

BLAST-IT-ALL BUMPER BLASTER

BLAST-IT-ALL BUMPER BLASTER LARRY HESS AND ASSOCIATES, INC 185 PIPER LANE / SALISBURY, NC 28147 PHONE: 1-800-535-2612 / FAX: 1-704-638-9311 WWW.BLAST-IT-ALL.COM BLAST-IT-ALL BUMPER BLASTER SUCTION BLAST CABINET NOTE: It is the responsibility

More information

2 SPEED PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR 2 SPEED PUMP

2 SPEED PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR 2 SPEED PUMP 2 SPEED PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR 2 SPEED PUMP 8308 PUMP PARTS BREAKDOWN Ref # Part # Manf. # Descrip on 1 NEP2134 AC 81361 PUMP LID 2 NEP2135 AC 81396 PUMP LID

More information

TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL

TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR PUMP 88 PUMP PARTS BREAKDOWN REF # Order # Mfr # Description 1 NEP4 AC 348 Lid Knobs NEP AC 380 Strainer Lid 3 NEP6

More information

Installation Manual PS-200 & PS-201

Installation Manual PS-200 & PS-201 Installation Manual PS-200 & PS-201 Table of Contents Pre-Uncrating Checklist... 1 Verifying System Requirements... 2 Verifying System Direction... 2 Verifying the Electrical Requirements... 2 Removal

More information

INSTALLATION AND OPERATING MANUAL

INSTALLATION AND OPERATING MANUAL INSTALLATION AND OPERATING MANUAL COMPACTAIR KVCK KVHA / KVHK TABLE OF CONTENTS POINTS TO KEEP IN MIND PAGE 2 DATA PAGE FOR UNIT COMMISSIONING PAGE 3 1.- GENERAL CHARACTERISTICS PAGE 1.1.- PHYSICAL DATA

More information