AIR TO WATER HEAT PUMP USER MANUAL

Size: px
Start display at page:

Download "AIR TO WATER HEAT PUMP USER MANUAL"

Transcription

1 AIR TO WATER HEAT PUMP Domestic Hot Water Series USER MANUAL Installation Operation Maintenance MODELS: AKRS-35B/N-L AKRS-50B/N-L AKRS-7B/N-L AKRS-90B/N-L READ AND SAVE THIS MANUAL V.01304

2 CONTENTS 1. Feature/Benefits. Notes/Precautions 3. Model Number Nomenclature 4. Technical Data 4. 1 Parameter table 4. Dimension 4.3 Performance curves 4.4 System diagram 4.5 Components Installation 5.1 Heat pump unit installation 5. Water system installation 5..1 Water tank installation 5.. Water piping installation 5.3 Power source installation 5.4 Wire controller installation Commissioning 6.1 Preparation before commissioning 6. Commissioning Controller Operation 7.1 Illustration for the keys 7. Illustration for LCD display 7.3 Water temperature setting 7.4 Clock setting 7.5 ON/OFF time setting 7.6 Timer mode setting 7.7 Timer cancelling Circuit Drawing 9. Maintenance and Trouble Shooting 9.1 Maintenance 9. Failure code checking 9.3 Common failures code 9.4 Parameter checking and adjustment 9.5 Parameter number and description table 9.6 The manometer instruction 9.7 Trouble Shooting

3 1 Features/Benefits Application Ranges The Thermal Master Series is designed for Domestic hot water for houses, small commercial buildings such as hotels, offices, hospitals, apartments, butcheries, bakeries, hairdressing salons and numerous other applications. The hot water outlet range is wide from minus 0 C to 60 C, meeting requirements for most hot water projects. The unit performs in an ambient temperature range from Minus 10 to 43 C. A modular control system is available to meet the demand of larger hot water projects. Designed for high efficiency performance over a lifetime of operation. The annual average COP is up to 4.5 depending on the ambient conditions. The water pipes and refrigerant pipes must be well insulated to minimize heat loss. Durable and Long Life High efficiency compressors are standard on all units, with safety features for protection against high temperature and high pressure. The tube in shell heat exchangers are capable of dealing with corrosion, hard water, high pressure and power outages. Strong Cabinet Standard unit fabrication consists of heavy gage galvanized sheet metal cabinet construction that provides maximum strength. All interior sheet metal surfaces are powder-painted for maximum corrosion protection to ensure long term durability. Compact, stackable cabinets are designed to minimize installation space. Notes/Precautions The installation, commissioning and maintenance of the system should only be done by qualified personnel with adequate knowledge of the relevant standards and local regulations as well as experience with similar systems. Please make sure the water flow is sufficient all the time. All ground line connections must be prepared in accordance with relevant local regulations. To reduce the risk of electrical insulation faults, you first make the connection of the protective conductor of the heat pump safe according to local regulations. When installation,make sure that the inside Hot Water Series Low Noise Levels Compressor rubber feet are especially selected for reducing vibration. Compressor sound jackets are standard for every unit. Well balanced fans and fan motors, with optimized fan mounting, contributes to low noise operation. The cabinet internally is insulated to reduce noise transmission Reliable Design and Strict Quality Control Standard safety features for the refrigerant circuit include high pressure switch and low pressure protection to detect loss of refrigerant, as well as low water flow. Equipment safety features include water loop temperature monitoring, voltage protection, water coil freeze protection. All safety features are tested and run at the factory to assure proper operation of all components and safety switches. All components are carefully designed and selected for endurance, durability and carefree day to day operation. Each unit is fully tested for performance and safeties prior to leaving the factory. Simple Maintenance and Serviceability Full access for maintenance or service is provided from the maintenance panel, for better flexibility in confined spaces. Easy removal of control the box from the unit provides access to all refrigerant components. The refrigerant circuit can be easily tested and serviced through the use of high and low pressure ports integrated on the refrigerant circuit. wires are apart from hot or moving parts [eg: compressor, fan] of the system to avoid damage to the wires. Anti-freezing measures must be well done to avoid damage to the water system and the heat pump water heating exchanger prior to switching on. Please make sure the lifting and transportation is safely undertaken, according to the heat pump size, weight and structure. It is very dangerous to work on any of these units without first isolating the electricity from the mains power source. When installing the system, please ensure that no contaminants enter the water cycle system. 1

4 3 Model Number Nomenclature AKRS- 50 B/ N-L Seri es of disti ncti on Refrigerant Type Power Supply Case Structure Heating Capacity Heat Pump Type L- L Series N - R410a S - 3 phase Omit - Single phase B- horizontal fan discharge 35-1 HP HP 7 - HP HP AKRS - air to water 4. Technical Data 4. 1 Parameter table AKRS-35B/N-L AK RS-50 B/N -L AKRS-7B/N-L AKRS-90B/N-L Heating Capacity kw Power Supply V/Ph/Hz 0/1/50 0/1/50 0/1/50 0/1/50 Input Power kw Running Current A Max. Input Power kw Max. Running Current A Refrigerant R410a R410a R410a R410a Compressor Mitsubishi Toshiba Mitsubishi Toshiba Compressor Type Rotary Rotary Rotary Rotary Compressor Quantity Outlet Water Temp ºC Max. Outlet Water Temp ºC Hot Water Yield L/h Water Flow 3 m /h Condenser Tube in shell Tube in shell Tube in shell Tube in shell Water Pressure Drop Kpa Water Connection Tube mm Dn0 Dn0 Dn0 Dn0 Noise db(a) <5 <53 <54 <55 Electric Protection I I I I Mechanical Protection IPX4 IPX4 IPX4 IPX4 Net/Gross Weight kg 40/48 55/65 65/79 73/87 Dimension mm 750*64* *8* *30*60 100*30*60 Packing Dimension mm 875*370* *380* *395* *395*760 Measuring condition: Dry/wet bulb temp 0ºC/15ºC; Water inlet/outlet temp 15ºC/55ºC.

5 4. Dimension H L A W B Model AKRS-35B/N-L AKRS-50B/N-L Length(mm) Wide(mm) 64 8 Height(mm) A(mm) B(mm) AKRS-7B/N-L AKRS-90B/N-L High Pressure Gauge Water Outlet Water Inlet Controller Cable Hole Power Cable Hole 3

6 4.3 Performance curves Model: AKRS-35B/N-L 5000 Heating Capacity Curves 4500 Heating Capacity (W) Ambient Temp. ( ) C O P C u r v e s C O P A m b i e n t T e m p. ( ) 4

7 Model: AKRS-50B/N-L Heating Capacity (W) Heating Capacity Curves Ambient Temp. ( ) C O P C u r v e s C O P A m b i e n t T e m p. ( ) 5

8 Model: AKRS-7B/N-L Heating Capacity Curves 9000 H eating C apacity (W) Ambient Temp. ( ) C O P C u r v e s C O P A m b i e n t T e m p. ( ) 6

9 Model: AKRS-90B/N-L H eating C apacity (W) Heating Capacity Curves Ambient Temp. ( ) C O P C u r v e s C O P A m b i e n t T e m p. ( ) 7

10 4.4 System diagram Heating Mode Water outlet Water inlet High pressure switch Condenser (Tube in shell) 4 way valve Throttling element Compressor Low pressure switch Suction accumulator Evaporator (fin-tube) Defrosting Mode Water outlet Water inlet High pressure switch Evaporator (Tube in shell) 4 way valve Throttling element Compressor Low pressure switch Suction accumulator Condenser (fin-tube) 8

11 4.5 Components Components Photo Features/Advantages Compressor The reliable high efficiency compressor, with R410a gas, can achieve high water temperatures of up to 60 C, while ensuring long life of the compressor. 4-Way valve The 4-way-valve prevents gas mixing and ensures stable defrosting. Condenser The Tube In shell heat exchanger has a large heat exchanging are and is very efficient. Circulation pump Circulation pumps used are Wilo brand and can operate at high temperatures. Evaporator Fan The hydrophilic fin coils have a large surface area and good fin spacing allowing highly efficient heat exchanging to take place, thus significantly improving heat transfer and efficient defrosting. The exterior fan motor, with multiple fan blades, is well balanced. The multiple fan blades run at slower RPM rates, and produce high air volumes, thus reducing noise levels.down 9

12 5. Installation 5.1 Heat pump unit installation Selection of installation position 1. Installation must be simple and allow easy access for later work or servicing.. If the unit is to be installed on the floor, its undercarriage should be raised to avoid being flooded by water in rainy seasons. In snow areas, it is important to prevent accumulated snow from blocking up the air outlet. 3. Drain points or other facilities should be provided next to the unit below the units installed level, to avoid the build-up of condensate water during operation. 4. If installing the unit on a balcony or roof of a building, the installation site must meet the allowable load bearing capacity of the building structure, without compromising the structural safety. 5. Ensure the unit is well ventilated and the direction of air exhaust is kept away from windows of neighbouring buildings and ensure the cold exhaust air cannot cycle back onto the coil. Moreover, adequate service clearance should be maintained around the unit. 6. The unit should not be installed In places with oil, flammable gas or corrosive atmospheres. E.g. sulphur compounds, sulphuric or other acids, heavily polluted air or high-frequency equipment to avoid induction interference. 7. The unit must be installed on reliable a base or framework. Weight capacity of framework should be 3 times of the weight and safeguard measures should be taken to avoid failure of fastenings. 8. Wall mounted installations should be avoided as much as possible as machines may overtime, fall down causing accidents. 9. Do not install the heat pump close to road, garden or path to avoid horizontal splashing on the unit from the road or irrigation systems as this may cause fan bearing or other failures. 10. Keep the unit out of reach of children. Installation in exceptional circumstances(unit:mm)

13 5. Water system installation 5..1 Water tank installation 1. The water tank should be in a place where It is suggested to install the heat pump, the water ambient temperature is as high as possible. tank and the circulation pump on the same level. The height difference between the heat pump. It can be installed either outdoors or on the and the water tank should be no more than roof (some factors such as the size of the water meters, when water tank position is higher than tank and the load bearing capability of the that of a heat pump. building structure should be considered). Installation on rooftops should be on supports 4. Do not install the water tank in a polluted or such as crossbeams or pillars. corrosive area. 3. The water tank should be installed lower than the base of the heat pump. 5.. Water piping installation 1. Drainpipe and overflow pipes should be temperatures) to avoid icing up of the water installed near the unit for draining water more supply pipe and valves. efficiently. Discharge valves are necessary on the drainpipe. 6. Keep the water pipes straight and the pipeline position reasonable; reduce pipe run. Service valves need to be installed before distances as much as possible to reduce water the magnet-valves on the system pipeline for resistance. further inspection 7. Ensure the pipeline and the connections 3. The pressure of the water outlet should be have no water leakage. between 0.3MPa and 0.6MPa 8. The water pressure capability of each part of 4. Please ensure only approved piping SANS the piping system should be tested after the or SABS compliant is used. Final connections installation is finished; drainage should be done must be done in copper as per SANS to maintain a clean internal system. requirements. 9. Measures of heat preservation for the hot 5. In winter, heat preservation may be need to water pipeline need to be conducted after be carried out for water supply valve and the stop checking that there are no water leaks. valve of the system (according to local ambient 11

14 Heat pump installation Check Valve Solenoid Valve Shut Off Valve Y-Shape Filter Water Pump Elec Heater Flow Switch Water Tank Heat Pump Controller Dinning Hall Guest Room Sauna Room Heat Pump Flow Switch (can omit) Filter Water tank temp. sensor Drainage Filter Check Valve 5.3 Power source installation Recommended wire specification Model AKRS-35B/N-L AKRS-50B/N-L AKRS-7B/N-L AKRS-90B/N-L Power Cable Water Pump LCD controller Sensor 3x1.5mm 3x1.5mm 3x.5mm 3x.5mm 3x0.75mm 3x0.75mm 3x0.75mm 3x0.75mm 3x0.35mm 3x0.35mm 3x0.35mm 3x0.35mm x0.35mm x0.35mm x0.35mm x0.35mm Note: the above specification is the minimum size we recommend. Please choose large wires if additional power is required. 1

15 M 5.4. Wire control installation Hot Water Series The wired controller is fixed standard on the maintenance door of the machine; please refer to steps below if you want to remotely install it on the wall: 1. Take down the controller from the machine. Please ensure that the communication wire is connected with the circuit board, separate them from where they match.. Use a screwdriver to open the clip as picture 1, separate the controller as parts, as picture. 3. On the wall that you are going to install the controller, drill holes at a level parallel to the sight line as picture 3. The hole distance needs to be 60mm, diameter is 8mm. 4. Place the plastic screws of the enclosure into the hole, and use the tapping screw (ST4*16 D-1) enclosed to fix the back cover of the controller on the wall, as picture Match the front and back covers perfectly, as picture 5, make sure that it is fixed firmly on the wall. 6. Connect the communication wire well. 1 The front cover The back cover SET mm Φ8 5 6 Outlet of the communication wire M SET Attention: Please do not use sharp edged objects to hit the controller face and keys or it may cause damage. When the controller is fixed on the wall, do not pull the communication wire, or it may cause a poor contact. 13

16 6 Commissioning 6.1 Preparation before commissioning Inspection on the heat pump Check if the outside case and the inside system of the heat pump have been damaged during the transportation. Check if there is still air inside the water system. If there is, use the air vents on the water system and circulation pumps, to purge the air. Inspection on the piping system Check if the water piping system, including water supply pipe, return water pipe, pressure gauge, thermometer, valves, water level switch are installed correctly. All hot water pipes should be lagged. Inspection on the power source system Make sure the power source is in accordance with the specification in the manual or on the heat pump nameplate. Make sure all power connections and control circuits are in place. Make sure all the wiring, grounding and all terminals are strong and reliable. 6. Commissioning The commissioning should be carried out by a qualified professional. Comprehensive inspection of the entire system should make sure that all piping points, and water levels in the tank are higher than the cycling heating outlet and the water outlet, before the commissioning. supply and correct the phases order. Make sure the compressor current is within normal operating range. After switching the power on, turn on the heat pump by pressing the on/off key on the wire control panel. Please check if the fan and the circulation pump are running in the right direction if the unit running from a three phase power source. If not, shut down the power 14

17 7. Controller Operation LCD display Clock and timer ON/OFF Mode selection Up Down Parameter setting 7.1 Illustration for the keys ON/OFF Press it to switch on or off heat pump. Mode selection Press it to select the mode. The sequence is: cooling-heating. Long press it for more than 6 seconds,heat pump will come to defrosting. During parameter setting, press it to adjust parameters; During clock and timer setting, press it to choose the hour value or minute value. Up and Down Press them to adjust the value of water temperature, clock, timer, parameters; During failure checking and parameter checking, press any of them to exit checking. Setting checking and confirm Long press it for more than 6 seconds, you can check and adjust the parameters. Press the UP/DOWN key to exit operation. When a failure occurs, press it for no more than seconds, you can check the failure code. Press it again you can check the other failure code if more than one occurs. Press the UP/DOWN key to exit checking. Clock and timer Key Press it to set clock and timer. Detailed operation will be described in following pages. During parameter setting, press it to change the rolling direction of parameters. 15

18 7. Illustration for LCD display Top area Middle area Temperature setting symbol, the figure under is the temperature value. Water tank temperature symbol, the figure under is the temperature value. Parameter number symbol, the figure under is the parameter number. Outllet water temperature symbol, the figure under is the temperature value. Parameter value symbol, the figure under is the parameter value. Failure symbol. Bottom area ON Turning on timer symbol. It appears when setting turn on timer. OFF Circulation pump running. Cooling mode symbol / Defrosting symbol(flash). Heating mode symbol. Auxiliary heat source start. Turning off timer symbol. It appears when setting turn off timer. Clock symbol. It appears when setting time. This symbol means heat pump has two compressors. 7.3 Water temperature setting When the heat pump is switched on, just press or to adjust water temperature. For example press Initial state 16

19 7.4 Clock setting! ATTENTION! At the first time, the time should be defined according to local time zone; Otherwise, the accuracy of Timer on/timer off would be influenced. Set the system time according to the local time as follows: Step 1 Step Step 3 Press the to start clock setting, symbol flashes. Press to select hour and the hour value flashes. Press or to adjust the hour value. Step 4 Step 5 Step 6 Press to select minute and the minute value flashes. Press or to adjust the minute value. Press to confirm the value and return to normal display. Normal display The current time is adjusted from 13:0 to 15:30 17

20 7.5 ON/OFF timer setting! ATTENTION! If you want to use the function of Timer on/timer off, the system time has to be detected whether it is correct in advance. The setting method is referred to page 0 Clock setting. With this function, the heat pump can turn on or turn off automatically at the set time. When the time point of Timer on is arrived, the heat pump starts; thereafter, the on/off could be controlled automatically based on the setting temperature. When the time point of Timer off is arrived, the heat pump is shut down; subsequently, the machine could no longer be controlled automatically based on the setting temperature; it will be restarted until the next time point of Timer on is arrived or the key is pressed. Totally 1 ON/OFF timers can be set. And they can be applied to use for every day or only one day. In timer setting status, the figure below NO represents the timer sequence. If it shows --:--- on bottom, it means timer invalid. Below examples show how to set the heat pump to switch on at 9:10 and switch off at 1:30. Step 1 Step Step 3 Press setting. twice to start ON time Press to select hour and the hour value flashes. Press or to adjust the hour value. Step 4 Step 5 Step 6 please turn to the next page Press to select minute and the minute value flashes. Press or to adjust the minute value. Press to confirm the value and turn to normal display. 18

21 Refer to the previous page or brought forward (b.f.) Step 7 Step 8 Step 9 Press setting. to start OFF time Press to select hour and the hour value flashes. Press or to adjust the hour value. Step 10 Step 11 Step 1 Press to select minute and the minute value flashes. Press or to adjust the minute value. Press to confirm the value and turn to normal display. Normal display 19

22 7.6 Timer mode setting: Hot Water Series Timer is effective either on the day or on every day, where the default is the latter. If you want to set only Timer on the day is effective, please modify the [No.1] parameter in the table on page 30 through wired controller. The default mode is timer recurrence. Please refer to following steps to set one-day timer: Step 1 State of running Initial state Long press( 6 seconds) State of standby Step Step 3 No.1 The incoming electric memorized sign 1 represent on every day is effective Step 4 Parameter No. Value [ Please correspond to the serial number in the table on page 34] Press to turn to parameter No.1 Press to select the value Adjust the value Step 5 0 represent on the day is effective Press or Confirm State of running State of standby 0

23 7.7 Timer cancelling: To cancel the timer, please refer to the instruction for timer setting and set it to be ---:--- via the M key. Please check below example for cancelling timer. Step 1 Step Step 3 Press for twice Press M button Step 4 Step 5 Press M button Step 6 Press M button Step 7 Confirm of Timer on is canceled and enter into the normal display. Step 8 Press to turn to Timer off adjustment. Step 9 Press M button Step 10 Press M button Normal display Press M button Confirm the section of Timer off is canceled and enter into the normal display. Represent the section of Timer has been canceled. 1

24 8. Circuit drawing Model: AKRS-35B/N-L, AKRS-50B/N-L, AKRS-7B/N-L

25 Model: AKRS-90B/N-L 3

26 9. Maintenance and Trouble Shooting 9.1 Maintenance The reliability and operation life of the heat pump can be increased by regular inspection and effective maintenance. The external water filter strainer should be cleaned regularly to ensure the cleanness of the water in the system and avoid damage caused by a blockage in the filter. All protective settings in the unit have been set in the factory and should not be changed. Regular inspection is required of the power source and the wiring connections of the electrical system. Loose wiring connections and electric components should be repaired immediately to avoid damage. The water supply system, pressure relief valve of the water tank, water level control device and air discharge device need to be checked regularly in case of low circulation water volume caused by air entering the system, and to ensure enough capacity and reliability of the heat pump. Check the water pump and the valves on the pipes if they work well and make sure there is no leakage from connectors or final connections. Check the internal pipes and refrigerant service port for oil. Make sure there is no refrigerant leakage Before switching off the heat pump for a prolonged period of time, drain out all water in the pipes, and shut off the power supply. Full inspection and commissioning of the system is required before start up again. Clean the condenser coils with diluted phosphoric acid of 15% consistence under the temperature of 50C-60C. Run the circulation for 3 hours and then flush with fresh water 3 times. When installing the pipes, add a 3-way valve on the pipes and shut off on outlet of it, for cleaning use. Corrosive or harmful substances used as washing liquid is forbidden to clean the condenser as this may be ingested by a person after the service work has been completed and the system is operational again. Clean the inside of the water tank after being used for a period(usually two months, and according to local water quality.) Keep the surrounding area of the heat pump dry, clean and ventilated. Regularly clean the evaporator to maintain high heat exchanging efficiency. 4

27 9. Failure code checking When a failure occurs, it will show failure symbol on the screen.press ( seconds) you can check the failure code. You can press it again to check another failure code if more than one occurs.press or to exit. State of turning on Failure code display area, E- means no failure. If another faiure code, please refer to the bottom of this page in [Common failures and maintenance], the corresponding failure to understand the cause and solutions. Hot Water Series Normal display Short press ( seconds) Press or button to exit. State of turning off Normal display Short press ( seconds) 9.3 Common failures code failures Refrigerant leak(system 1) Refrigerant leak(system ) Press or button to exit. Low pressure protection/pressure valve break down (system 1) Low pressure protection/pressure valve break down (system ) High pressure protection/pressure valve break down (system 1) High pressure protection/pressure valve break down (system ) Water tank temp. sensor failure Water outlet temp. sensor failure Evaporator coil temp. sensor failure (system 1) Evaporator coil temp. sensor failure (system ) Discharge gas temp. sensor failure (system 1) Discharge gas temp. sensor failure (system ) Discharge temp. protection( Discharge temp. is too high)(system1) Discharge temp. protection(discharge temp. is too high)(system) Error phase or lack of phase with power supply Ambient temp.sensor failure Water flow fault or water flow switch breakdowm LCD controller fault PCB s memory fault 5 Display P9 EA PF EF E4 E8 P3 E1 P1 P5 P P6 E3 E7 PA P7 Pd En E5

28 9.4 Parameter checking and adjustment The system parameters can be checked and adjusted via the controller. But they should not be changed casually, especially by house owners.! Warning! This operation is reserved to facilitate future service and maintenance. All parameters should not be changed casually, especially by house owners! How to check and adjust parameters: Parameter No. [ Please correspond to the serial Step 1 number in the table on page 31. ] Step Step 3 Value Long press ( 6 seconds) to enter parameter checking mode. Press (short press) again and again Press to start parameter to choose parameter that needs adjusting. setting and the parameter flashes. If press, the rolling directionwill be converted(+ to - or - to +). Step 4 Step 5 Press or to adjust the value.. Press to confirm the value Press or to return to normal display. Normal display 6

29 9.5 Paramete r number and descriptio n are liste d in th e fo llowing ta ble. No. Content Scope Default Memorized station 0 The incoming electric memorized sign 0-no effective 1-effective 1 The main board 1 Daily circulation sign 0-no effective 1-effective 1 the wire control panel the setting area X ~10,Unit: 3 The main board 3 the setting area Y 0 ~3,Unit: 0 The main board 4 The interval for defrosting 15~99,Unit:minute 45 The main board 5 Defrosting-on temperature -9~5, Unit: -3 The main board 6 Defrosting-off temperature 5~0,Unit: 10 The main board 7 Compressor s exhaust air protection 90~10,Unit: b8: means 118 The main board 8 Evaporator coil temperature 1 Unit: Scope:-9-80 No Setting 9 Discharge gas temperature 1 Unit: 98: means 98 A8: means 108 b8: means 118 No Setting 10 ambient temperature Unit: Scope:-9-80 No Setting 11 Compressor continuous running time Unit:minute Scope:0-99 No Setting 1 Fan continuous running time 1/4 Unit:Second No Setting 13 Compressor auto-off code 1 No Setting 14 On-off imported state Especial:sixteen No Setting 4 Auxiliary heat source 0-no effective 1-effective 0 The main board 5 Water tank temp./water outlet temp. -5~5, Unit: compensation 1 The main board 9 Evaporator coil temperature Unit: Scope:-9-80 No Setting 3 Compressor auto-off code No Setting 37 Discharge gas temperature Unit: 98: means 98 A8: means 108 b8: means 118 No Setting 48 Start ambient temp.(auxiliary heat source) ~15, Unit: 7 The main board Remark:the machine off code(the No. 13, No. 3 parameter in the previous table): :Water tank temp. sensor breakdown 0:Defrosting preparation 3:Evaporator coil temp. sensor breakdown 1:Defrosting finish 4:Discharge temp. sensor breakdown :Error phase or lack of phase with power supply, 5:Discharge temp.is too high, thanshop the machine then shop the machine 11:Anti-frozen finishing,than shop the machine 7:Low-pressure switch cutting 1:High-pressure switch cutting :High-pressure switch cutting during water tank 13:Meet set temp temp. is high 14:Controller power off 3:High-pressure switch cutting during dofrosting 19:Water flow switch breakdown 9.6 Hot Water Series The manometer is a kind of high pressure equipment, when the heat pump is on, the manometer pointer would point to the pressure value of refrigerant, the max. value of protection is 4kg/Cm. When the heat pump is off, the pointer would point to the same value as actual ambient temperature (e.g. 8 C) and related air pressure (e.g.18kg/ Cm ). Please check the manometer when you restart the heat pump after not using for a long time, if it shows ambient temperature valve is smaller than C(When the ambient temp. is higher than C), it means that refrigerant has leaked a lot, and you need to confirm with professional engineer as soon as possible. 7

30 9.7 Trouble shooting Users should contact with the professional maintenance staff when there is a problem with the heat pump. Maintenance stuff may need to refer to the following table for troubleshooting. Malfunction Possible Problems Disposing Methods Heat pump unit is out of operation. 1. Power source fault.. Loose connection of power wire. 3. Power fuse burnt out. 4. Low water level switch is not on. 1. Cut off the power source and check.. check the power wire connection. 3. Check the fuse. 4. Supply water until the water level switch is on. Water pump is running but no water circulation or much noise made by water pump 1. Few water in the system.. Air exists in the water system. 3. Some valves are not opened. 4. The water filters is blocked up. 1. Fill water into the water supply system.. Discharge air from the water system. 3. Open all the valves in the system. 4. Clean the water filter. Low heating capacity. Heavy frosting, low heating capacity. High noise of compressor. 1. Lack of refrigerant.. Bad water system heat preservation. 3. Low evaporator heat transferring. 4. Low water flow volume. 1. The evaporator is too dirty.. Defrost sensor fault. 3. The 4 way valve can not change direction. 4. Over long defrosting duration. 1. Liquid refrigerant into the compressor.. Interior component of the compressor is faulty. 1. leakage hunting and fix it, discharge all the refrigerant and inject the right amount.. improve the heat preservation. 3. Wash the evaporator. 4. Clean the water filter. 1. Wash the evaporator.. Change a new defrost sensor. 3. Check the solenoid if it is energized. 4. Change the temperature for entering defrost and the duration. 1. Check if the thermostatic expansion valve is faulty.. Change the compressor. 8

31 Compressor is out of operation. 1. Power source fault.. Compressor AC contactor damaged. 3. Loosen wire connection. 4. Over-heat protection. 5. Over-high water temp. 6. Low water flow volume. 1. Check the power source and change faulty components.. Change the contactor. 3. Check every wire connection of compressor. 4. Check refrigerant leakage. 5. Bring down the water temp. set value. 6. Clean the filter and check if there is air inside the water system. Fan is out of operation. 1. Fan motor wire loosen.. Fan motor burnt. 3. Fan AC contactor fault. 1. Check every wire of the fan connection.. change the motor. 3. change the AC contactor. Low water flow volume protection. 1. Circulation pump fault.. Circulation pump is too small. 3. Water filter blockage. 4. Flow volume control device restore. 1. Check the operation of the circulation pump and fix it.. Change a bigger pump. 3. Wash the water filter. 4. Adjust or change the flow volume control device. Over-high compressor discharge pressure 1. Low water flow volume.. Thermostatic expansion valve openings is not correct, or blockage. 1. Check the circulation pump, and the water filter.. Check and adjust the openings, or directly change the expansion valve. Over-low compressor suction pressure. 1. Not enough refrigerant.. Over-big pressure drop through the heat exchanger. 1. Check refrigerant leakage.. Check and adjust the expansion valve openings. Shortage of oil in compressor. Shortage of lubricant oil. Find out the suitable kind of oil for the compressor and inject some amount. Thermostatic throttle valve can not start. 1. The switch for it is not open.. Low water pressure, oversmall water pipe diameter, over-long pipe. 1. Inspect the power source of the solenoid valve.. Check if there is blockage in the pipes, and add boosting pump when necessary. 9

32 01304KT

LOW AMBIENT Air Source Heat Pump

LOW AMBIENT Air Source Heat Pump EVI LOW AMBIENT Air Source Heat Pump Manual Installation Operation Maintenance Zhongshan Sundez Eco-energy Solution Co., Ltd. www.sundez.cn info@sundez.cn INSTALLATION & OPERATION MANUAL Contents 1. Features/Benefits...1

More information

INSTALLATION AND USER MANUAL

INSTALLATION AND USER MANUAL INSTALLATION AND USER MANUAL Thank you for choosing our product and trusting our company. This manual is to provide you with necessary information for optimal use and maintenance, please read carefully

More information

CONTROL PANEL INSTRUCTIONS RSQ-4

CONTROL PANEL INSTRUCTIONS RSQ-4 CONTROL PANEL INSTRUCTIONS RSQ-4 FOR SIRAC AIR TO WATER HEAT PUMP (SINGLE COMPRESSOR, AIR TO WATER) 1) System Configuration This system is composed of mainboard and wire control panel. 146mm Φ4 4 Mainboard

More information

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table)

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table) 1 2 Warning: - Do not place your hand or any other objects into the air outlet and fan. It could damage the heat pump and cause injuries; - In case of any abnormality with the heat pump, cut off the power

More information

INSTALLATION AND USER MANUAL

INSTALLATION AND USER MANUAL INSTALLATION AND USER MANUAL t Thank you for choosing Aqua inverter heat pump. This manual provides you necessary information for optimal use and maintenance, please read it carefully and keep it for subsequent

More information

INSTALLATION AND USER MANUAL

INSTALLATION AND USER MANUAL INSTALLATION AND USER MANUAL Thank you for choosing inverter heat pump. This manual provides you necessary information for optimal use and maintenance, please read it carefully and keep it for subsequent

More information

HIGH TEMPERATURE AIR SOURCE HEAT PUMP WATER HEATER

HIGH TEMPERATURE AIR SOURCE HEAT PUMP WATER HEATER HIGH TEMPERATURE AIR SOURCE HEAT PUMP WATER HEATER BIGGER-H SERIES JIAXING MES NEW ENERGY TECHNOLOGY CO.,LTD. High quality- We believe that quality is the best business plan R&D team- Professional R&D

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

OPERATING & MAINTENANCE MANUAL HORIZONTAL WATER SOURCE HEAT PUMP. World class comfort.

OPERATING & MAINTENANCE MANUAL HORIZONTAL WATER SOURCE HEAT PUMP. World class comfort. OPERATING & MAINTENANCE MANUAL HORIZONTAL WATER SOURCE HEAT PUMP World class comfort. welcome Congratulations on your selection of Ice Air Water Source Heat Pumps (WSHPs) for your comfort conditioning

More information

Models: DE-75W/D DE-92W/D DE-105W/D DE-27W/D DE-36W/D DE-46W/D DE-52W/D DE-27W/C DE-36W/C DE-46W/C DE-180W/D DE-225W/D DE-270W/D

Models: DE-75W/D DE-92W/D DE-105W/D DE-27W/D DE-36W/D DE-46W/D DE-52W/D DE-27W/C DE-36W/C DE-46W/C DE-180W/D DE-225W/D DE-270W/D Brief introduction: This series of air source heat pump is designed for the common area of ambient temperature between -10 C, to 45 C,. The unit is designed for residential sanitary hot water of bathroom,

More information

DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: , Fax#: ,

DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: , Fax#: , DOLPHIN RADIATOR & COOLING SYSTEMS P.O.Box: 1424,Ph#: +971-6-5432526, Fax#: +971-6-5432415, Email: dolcool@emirates.net.ae, web site: www.dolphinheattransfer.com NOMENCLATURE: INTRODUCTION DOLCOOL branded

More information

SWIMMING POOL HEAT PUMP UNIT Installation & Instruction Manual Duratech - series

SWIMMING POOL HEAT PUMP UNIT Installation & Instruction Manual Duratech - series SWIMMING POOL HEAT PUMP UNIT Installation & Instruction Manual Duratech - series Rev. 3.32 26.01.2007 CONTENTS 1. Preface 3 2. Specifications 4 2.1 Performance Data of swimming Pool Heat Pump Unit 4 2.2

More information

TOSHIBA AIR CONDITIONING

TOSHIBA AIR CONDITIONING Introduction The following specification describes the Toshiba Estia Air to Water Heat Pump system(s) to be installed at the site below: (ADD SITE NAME) The system(s) shall consist of the following components.

More information

DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX45

DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX45 DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX45 Installation and Operation Manual Version 1 1 Table of Contents Safety Precautions... 3 Components... 4 Hydronic piping and design

More information

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points Epsilon Echos+ 5 38 kw General information Air-Water unit with scroll compressors driven by DC inverter Configuration /LN: Low noise unit /HP: Reversible heat pump /LE /HP: Reversible condensing unit Unique

More information

Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061

Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061 Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061 Imported by: Zwembad BVBA Industrieweg 9 3190 Boortmeerbeek België www.harmopool.eu 0 Table of content Introduction... 2 Safety instructions...

More information

THROUGH-WALL AIR-TO-AIR HEAT PUMP AND AIR CONDITIONER. Instruction Manual. Model AMB-12H

THROUGH-WALL AIR-TO-AIR HEAT PUMP AND AIR CONDITIONER. Instruction Manual. Model AMB-12H THROUGH-WALL AIR-TO-AIR HEAT PUMP AND AIR CONDITIONER Instruction Manual Model AMB-12H PLEASE READ THIS INSTRUCTION MANUAL CAREFULLY BEFORE USING THIS UNIT. Table of Contents 1. SAFETY WARNINGS 2 2. CONSTRUCTION...

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

INSTALLATION & OPERATION MANUAL

INSTALLATION & OPERATION MANUAL DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX30 INSTALLATION & OPERATION MANUAL Version 1.5 1 Table of Contents Safety Precautions... 3 Components... 4 Hydronic piping and design

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

Portable Air-conditioner

Portable Air-conditioner Use and Care Manual Portable Air-conditioner Thank you very much for selecting this new model of Portable Air Conditioner, please read this Use and Care Manual carefully before installing and using this

More information

Dehumidifier User Manual. (For the series of DP40~DP70)

Dehumidifier User Manual. (For the series of DP40~DP70) Dehumidifier User Manual (For the series of DP40~DP70) Content I. Please read immediately... 1 II. Application... 2 III. Features... 2 IV. Technical Parameters... 3 V. Overall Dimension... 4 VI. Installation

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

Local Air Conditioner

Local Air Conditioner Local Air Conditioner Thank you for selecting this air-conditioner. Please keep this User s Manual for future reference. Read the User s Manual carefully before operating this unit. IMPORTANT SAFEGUARDS

More information

MODELS LIST. Nominal Capacity RT

MODELS LIST. Nominal Capacity RT 1. MODELS LIST. NOMENCLATURE 3. FEATURES 4. PRODUCT DATA 5. PERFORMANCE CORRECTION 6. ANTIFREEZE 7. INSTALLATION 8. ELECTRICAL DATA 9. SCHEMATIC WIRING DIAGRAM 10.MICROPROCESSOR CONTROLLER 11.APPLICATION

More information

Harmo Powerpack Horizontal Units Installation & instruction manual

Harmo Powerpack Horizontal Units Installation & instruction manual Imported by: Zwembad BVBA Industrieweg 9 3190 Boortmeerbeek België www.harmopool.eu Harmo Powerpack Horizontal Units Installation & instruction manual Table of content Introduction... 3 Characteristics...

More information

Technicians Manual Single Compressor

Technicians Manual Single Compressor Technicians Manual Single Compressor HAC-FF-D WALL PAD Operating Manual Version PCB Version V2.3.5 Version wall pad Version Manual Page 1 Contents 1. Main features 2. Main technical data 3. Wall pad 4.

More information

Contents. Specifications. Description SV HP 55 SV HP 90. Specifications Warnings Introduction Overview... 4

Contents. Specifications. Description SV HP 55 SV HP 90. Specifications Warnings Introduction Overview... 4 Contents Specifications Specifications... 1 Warnings... 2 Introduction... 3 Overview... 4 Installation Instructions... 5 Cable Connections... 6 Plumbing Diagram... 7 Electrical Wiring Diagram... 8 SV System

More information

Owner s Manual AIR TO WATER HEAT PUMP. Hydro Unit HWS-804XWHM3-E HWS-804XWHT6-E HWS-804XWHT9-E HWS-1404XWHM3-E HWS-1404XWHT6-E HWS-1404XWHT9-E

Owner s Manual AIR TO WATER HEAT PUMP. Hydro Unit HWS-804XWHM3-E HWS-804XWHT6-E HWS-804XWHT9-E HWS-1404XWHM3-E HWS-1404XWHT6-E HWS-1404XWHT9-E AIR TO WATER HEAT PUMP Hydro Unit Model name: HWS-804XWHM3-E HWS-804XWHT6-E HWS-804XWHT9-E HWS-1404XWHM3-E HWS-1404XWHT6-E HWS-1404XWHT9-E English Thank you very much for purchasing TOSHIBA Air to Water

More information

Contents. Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79

Contents. Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79 MCAC-TSM-2008-02 Contents Part 1 General Information...2 Part 2 Outdoor units...7 Part 3 Installation...63 Part 4 Controller...79 Contents i MCAC-TSM-2008-02 Introduction Introduction Midea Mini Unitary

More information

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA OWNER S MANUAL Vintage Classic HEAT COOL models Proudly Made in the USA support@aquacomfort.com www.aquacomfort.com/service-and-support 888-475-7443 Manufacturing High Quality, High Efficiency Heat Pump

More information

PORTABLE AIR CONDITIONER

PORTABLE AIR CONDITIONER PORTABLE AIR CONDITIONER Model: PEL00460 1 CONTENTS Page No. Details 2 Important Safety Information 3 Product Overview 3 Positioning & Installation 4 Installation Errors 4 Control Panel 5 Screen IMPORTANT

More information

MAC-A R410A Series Air cooled Modular Chiller

MAC-A R410A Series Air cooled Modular Chiller Catalogue MAC R410A 2011(60Hz) MAC-A R410A Series Air cooled Modular Chiller Model: Refrigerant: Co ling Capacity: MAC210A5 R410A 72kW Overview Based on the successful McQuay air-cooled modular chiller,

More information

SWIMMING POOL HEAT PUMP UNIT ECO - series. Installation & Instruction manual

SWIMMING POOL HEAT PUMP UNIT ECO - series. Installation & Instruction manual SWIMMING POOL HEAT PUMP UNIT ECO - series Installation & Instruction manual Rev. 1.00 28.11.2007 Contents SWIMMING POOL HEAT PUMP UNIT 1 CONTENTS 2 1. PREFACE 3 2. SPECIFICATIONS 4 2.1 Performance data

More information

MAC-D R410A Series Air-cooled Modular Chiller/Heat pump

MAC-D R410A Series Air-cooled Modular Chiller/Heat pump Catalogue MAC-D-2013 (50Hz) MAC-D R410A Series Air-cooled Modular Chiller/Heat pump Model: Refrigerant: Cooling Capacity: Heating Capacity: MAC210D5-MAC1680D5 MAC230D5-MAC1840D5 MAC210DR5-MAC1680DR5 MAC230DR5-MAC1840DR5

More information

Product Data. Features/Benefits. 30RQ Air-cooled Modular Chiller R22 & R410A & R407C

Product Data. Features/Benefits. 30RQ Air-cooled Modular Chiller R22 & R410A & R407C Product Data 30RQ Air-cooled Modular Chiller R22 & R410A & R407C Introduction Air-cooled modular chiller is a kind of central airconditioning unit which adopts air as the cooling (or heating) source and

More information

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors infolinia: +48 691 262 691-15 C +63 C +43 C E.V.I. HP The series of high efficiency heat pumps has been specifically designed for use with

More information

PDA20DX Air Purifying Dehumdifier Manual

PDA20DX Air Purifying Dehumdifier Manual PDA20DX Air Purifying Dehumdifier Manual Index Important Safe Guards Ambient Environment For Operating Components Diagrams---Parts Names Operating Introduction---How to operate - Functions of Control Panel

More information

Inverter Swimming Pool Heat Pump

Inverter Swimming Pool Heat Pump P Inverter Swimming Pool Heat Pump Content I. Application... 2 II. Features... 2 III. Technical Parameter... 3 IV. Dimension... 4 V. Installation instruction... 5 VI. Operation instruction... 9 VII. Testing...

More information

Portable Air-conditioner Use and Care Manual

Portable Air-conditioner Use and Care Manual Portable Air-conditioner Use and Care Manual Part Number: 048-GM-48266 Thank you very much for selecting this new model of Portable Air Conditioner, please read this Use and Care Manual carefully before

More information

VRF D4 PLUS System. Highlights. Digital Scroll Series. Dealer information. Commercial Air Conditioner Business Units Midea Group

VRF D4 PLUS System. Highlights. Digital Scroll Series. Dealer information. Commercial Air Conditioner Business Units Midea Group VRF D4 PLUS System Digital Scroll Series GD Midea Heating & Ventilating Equipment Co., Ltd. Is certified under the ISO 9001 International standard for quality assurance. NO.01 100 019209 GD Midea Heating

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC Revision D: MUFZ-KJ25VE - E2, ER2, ET2, MUFZ- KJ35VE - E2, ER2, ET2 and MUFZ- KJ50VE - E2, ER2, ET2 have been added. Please void OBH667 REVISED EDITION-C. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A.

More information

DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX30

DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX30 DC INVERTER AIR TO WATER HEAT PUMP AC series Heating & Cooling series CX30 Installation and Operation Manual Version 1.7 1 Table of Contents Safety Precautions... 3 Components... 4 Hydronic piping and

More information

Wired controller KJR-08B/BE. Run. Fault. TB Tot. Out. Query. Heat. Net-On. Turn-On Mode

Wired controller KJR-08B/BE. Run. Fault. TB Tot. Out. Query. Heat. Net-On. Turn-On Mode R0A (kw-0kw) 0Hz KJR-0B/BE is a human-machine interaction(hmi) used for the communication between chiller operator and main board on the chiller itself. The setting and operation order can be send to the

More information

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL DATE OF PURCHASE: MODEL: SERIAL NO.: Record above information from nameplate. Retain this information for future reference.

More information

INSTALLATION AND USER MANUAL

INSTALLATION AND USER MANUAL Swimming Pool Heat Pump Swimming Pool Heat Pump INSTALLATION AND USER MANUAL Thank you for choosing our product and trusting our company. This manual is to provide you with necessary information for optimal

More information

AIR COOLED PACKAGED CHILLER

AIR COOLED PACKAGED CHILLER AIR COOLED PACKAGED CHILLER UNIC sal is equipped to produce a wide range of COOLER Air conditioning and Refrigeration units, conforming to the international standards and works continually to improve its

More information

Service Manual & Installation Manual

Service Manual & Installation Manual GE Consumer & Industrial Appliances Service Manual & Installation Manual Split System Air Conditioner Model numbers: GE AIR F24 GE AIR F34 GE AIR F41 1 2 3 Introduction and Features Model Remarks GE AIR

More information

Air source heat pump. (water heating module-18kw)

Air source heat pump. (water heating module-18kw) Air source heat pump (water heating module-8kw) User Manual Before use Safety precautions 2 Features and advantages 3 Main components 4 Outlines and dimensions 5 Working principles 6 Technical data 7

More information

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017 Zeta Rev LN HP 10.2 Configured unit accessories 1PS - One user-side pump with tank LN - Low noise RG - Condensation control with fan speed regulator CSP - Set point compensation depending on external air

More information

Contour TM Screw Compressors

Contour TM Screw Compressors Contour TM Screw Compressors Semi-Hermetic Compact Operating Instruction SCH1 High Temp Compressors Form No. 99-77 1. Introduction This series of semi-hermetic compact screw compressors is designed for

More information

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual Instructions Manual 1. Important safety notes - Please read... 1 1.1. Transportation... 1 1.2 Positioning... 1 1.3 Installation... 1 1.4 Before operating... 1 1.5 Maintenance by an engineer... 1 1.6 Maintenance

More information

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH624 REVISED EDITION-A Models MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE

More information

C&H NORDIC Commercial 4 SERVICE MANUAL

C&H NORDIC Commercial 4 SERVICE MANUAL C&H NORDIC Commercial 4 SERVICE MANUAL CONTENTS PRODUCT...3 1 MODELS LIST... 3 1.1 Outdoor Unit.... 3 1.2 Indoor Unit.... 4 2 PRODUCT DATA.... 5 2.1 Product Data of Indoor Unit... 5 2.2 Operation Range...

More information

Portable Air Conditioner USER MANUAL

Portable Air Conditioner USER MANUAL AC12 AC12HP Portable Air Conditioner USER MANUAL Thank you for choosing this innovative Amcor air conditioner. We suggest that you keep this manual in a safe place for future reference. It describes the

More information

BLUEWAY DC INVERTER AIR TO WATER HEAT PUMP

BLUEWAY DC INVERTER AIR TO WATER HEAT PUMP BLUEWAY DC INVERTER AIR TO WATER HEAT PUMP 1 Enjoy comfortable life with BLUEWAY DC Inverter Air to Water Heat Pump is an innovative system of house heating, domestic hot water and even space cooling,

More information

High Wall Split Systems Cool Only 9K - 12K - 18K - 24K. Auto. Auto. Fan Speed. Smart LCD Wireless Control. Auto Mode.

High Wall Split Systems Cool Only 9K - 12K - 18K - 24K. Auto. Auto. Fan Speed. Smart LCD Wireless Control. Auto Mode. HFC4 1 0 A 0-40V ~, 0Hz 1Ph High Wall Split Systems Cool Only 9K - 1K - 18K - 4K R-410A IAQ $ Auto Auto Fan Speed Timer s Easy Flexible Installation Smart LCD Wireless Control Auto Mode Auto Restart Easy

More information

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw Air-Cooled Liquid Chillers Nominal cooling capacity 21-94 kw Carrier is participating in the Eurovent Certification Programme. Products are as listed in the Eurovent Directory of Certified Products. The

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control.

V ~, 50Hz 1Ph. High Wall Split Systems Heat Pump 9K - 12K - 18K - 24K - 28K. Auto. Auto Fan Speed. Auto. Smart LCD Wireless Control. HFC4 1 0 A 0-40V ~, 0Hz 1Ph High Wall Split Systems Heat Pump 9K - 1K - 18K - 4K - 8K R-410A Compressor Super Quiet AMS Anti-dust Filters Auto Fan Speed Timer Functions Defrost Protection Smart LCD Wireless

More information

User instructions DHP-AT

User instructions DHP-AT User instructions DHP-AT VUGFC202 If these instructions are not followed during installation and service, Danfoss A/S liability according to the applicable warranty is not binding. Danfoss A/S retains

More information

USER MANUAL SILENT12 PORTABLE AIR CONDITIONER

USER MANUAL SILENT12 PORTABLE AIR CONDITIONER USER MANUAL SILENT12 PORTABLE AIR CONDITIONER Thank you for choosing electriq Please read this user manual before using this innovative Air Conditioner and keep it safe for future reference. Visit our

More information

AIR SOURCE HEAT PUMP WATER HEATER

AIR SOURCE HEAT PUMP WATER HEATER AIR SOURCE HEAT PUMP WATER HEATER Installation & Instruction Manual Model: SWBC-3.H-B SWBC-9.H-B-S SWBC-4.0H-A-S SWBC-4.0H-B-S Contents CONTENTS Ⅰ.To our customers(before installation) -------------------------------------------------

More information

Wired Controller XK60

Wired Controller XK60 Owner's Manual Commercial Air Conditioners Thank you for choosing Commercial Air Conditioners, please read this owner s manual carefully before operation and retain it for future reference. User Notice

More information

COMPACT PORTABLE AIR CONDITIONER USER MANUAL

COMPACT PORTABLE AIR CONDITIONER USER MANUAL COMPACT PORTABLE AIR CONDITIONER USER MANUAL Thank you for choosing ElectriQ Please read this user manual before using this innovative Air Conditioner and keep it safe for future reference. Visit our page

More information

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw SPECIFICATION GUIDE NEOSYS Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw Air-to-water Heat Pump for outdoor installation (NAH) Nominal cooling capacity:

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

Advance Split

Advance Split Engineering Data Manual Aqu@Scop Advance Split Air-to-Water DC Inverter Split Heat Pumps Models 005, 008, 012 & 014 2 to 16 kw Strength Points Most efficient heating technology with variable speed compressor.

More information

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL WM150 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the WM150 is a rugged, industrial unit, which utilizes an

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

Air Cooled Scroll Chiller

Air Cooled Scroll Chiller Air Cooled Scroll Chiller Midea chillers use H shape heat at air side and single unit s capacity from kw to 0kW. Super chillers are divided to SS,SS-LA, SP-LA and SP-HMLA series according to their water

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

Hot Water Heating Systems

Hot Water Heating Systems Hot Water Heating Systems Find out more at www.greeonline.com Key Wide Range of Operation Conditions Heating -26 C 46 C Features The Ultra Hot Water system is specifically designed to be flexible in its

More information

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD.

Technical Support Division GD CHIGO HEATING & VENTILATION EQUIPMENT CO., LTD. Technical Support Division 2017-4-25 New CMV System - Floor ceiling Indoor Unit 1 1. External appearance 2. Nomenclature 3. Specifications 4. Dimensions 5. Service space 6. Piping diagram 7. Wiring diagram

More information

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI

GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI Change for life Models: GFH(09)EA-K6DNA1B/I GFH(12)EA-K6DNA1B/I GFH(18)EA-K6DNA1B/I GFH(21)EA-K6DNA1B/I Models: GFH(24)EA-K6DNA1B/I (Refrigerant R32) GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI Table of Contents

More information

PORTABLE AIR CONDITIONER

PORTABLE AIR CONDITIONER PORTABLE AIR CONDITIONER A001-07KR/C, A001-08KR/C, A001-09KR/C, A001-10KR/C SERIES IMPORTANT SAFEGUARDS Please read following safeguards carefully before using the unit and retain for future reference

More information

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

INSTALLATION, COMMISSIONING AND OPERATING MANUAL INSTALLATION, COMMISSIONING AND OPERATING MANUAL 1 YTBV-D-CE42_0109 CONTENT Available models and capacities Supplier information Warranty Safety Emergency stops/ shutdowns About this manual Models Physical

More information

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies Pakistan s Largest Manufacturers of Air-Conditioners PACKAGE TYPE UNIT FOR MOBILE APPLICATIONS Provides Turnkey Projects Conceptual Planning to Commissioning of HVACR Projects THE LARGEST MANUFACTURER

More information

OWNER S MANUAL DLFCAB / DLFCHB / DLFDAB / DLFDHB High Wall Ductless System Sizes 09 36

OWNER S MANUAL DLFCAB / DLFCHB / DLFDAB / DLFDHB High Wall Ductless System Sizes 09 36 OWNER S MANUAL DLFCAB / DLFCHB / DLFDAB / DLFDHB High Wall Ductless System Sizes 09 36 TABLE OF CONTENTS PAGE SAFETY PRECAUTIONS... 2 GENERAL... 2 INDOOR UNIT PART NAMES... 3 REMOTE CONTROL PART NAMES...

More information

Swimming Pool Heat Pump

Swimming Pool Heat Pump Swimming Pool Heat Pump Operation and Installation Manual MODEL FH-020 CONTENTS INTRODUCTION Index............ 2 The unit...... 2 SAFETY INSTRUCTIONS... 4 Electrical Installation Warning.. 4 Location Warning

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

ULTRA SERIES CIRCULATING AIR SOURSE HEAT PUMP WATER HEATER

ULTRA SERIES CIRCULATING AIR SOURSE HEAT PUMP WATER HEATER ULTRA SERIES CIRCULATING AIR SOURSE HEAT PUMP WATER HEATER (GC201503- ) TTER CONDITIONERS GREE MAKING BETTER CONDITIONERS GREE MAKING BETTER CONDITIONERS GREE MAKING BETTER CONDI TECHNICAL SALES GUIDE-50Hz

More information

Service manual. MIV V4+ Mini

Service manual. MIV V4+ Mini DM12-01.01.05en Service manual MIV V4+ Mini DC INVERTER R410A (~220V, 50Hz, 1Ph) MVUH80A-VA1 Contents Part 1 General Information... 1 Part 2 Outdoor Units... 6 Part 3 Installation... 44 DM12-01.01.05en

More information

USER MANUAL SILENT16 PORTABLE AIR CONDITIONER

USER MANUAL SILENT16 PORTABLE AIR CONDITIONER USER MANUAL SILENT16 PORTABLE AIR CONDITIONER Thank you for choosing electriq Please read this user manual before using this innovative Air Conditioner and keep it safe for future reference. Visit our

More information

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB T_SMT_0609_GB 4,9 49,5 kw Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans INDEX SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 CE CONFORMITY... 3 WORKING

More information

3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS

3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS 3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: 32305600 OPERATION & MAINTENANCE INSTRUCTIONS 0304 Parts List Item Part No Description Qty 1 FT900001 Top Cover 1 2 FT900002 Filter

More information

PDF Created with deskpdf PDF Writer - Trial ::

PDF Created with deskpdf PDF Writer - Trial :: Instruction Manual Index Introduction Uncrating and Checking for Damage Locating Your Unit Installation Fill Tank Process Connections Pre Startup Startup Sequence Trouble Shooting Chart Operating Lights

More information

LZT High efficiency air to water heat pumps with E.V.I. compressors

LZT High efficiency air to water heat pumps with E.V.I. compressors High efficiency air to water heat pumps with E.V.I. compressors -20 C +43 C +65 C E.V.I. C.O.P. 4,1 The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating

More information

Swedish design and manufacture since 1967

Swedish design and manufacture since 1967 Swedish design and manufacture since 167 PVP MA20-14 rev.2 Manual User manual Copyright 2017 Pahlén AB, Box 728, SE-14 27 Upplands Väsby, Sweden Tel. +46 8 54 110 50, Fax +46 8 50 868 80, e-mail: info@pahlen.se,

More information

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC. WYETH-AYERST CANADA INC. 1025, BOUL. MARCEL-LAURIN S T - L A U R E N T, Q U É B E C INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER MODEL P448800LT--55WC--22C66S Prepared par Claude Gadoury, P.

More information

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3) www.dometic.com Freightliner Refrigerator Troubleshooting Guide For Before initiating troubleshooting, the following equipment is recommended: Multimeter, 20 gauge (min) wires to use as jumpers, and 12Vdc

More information

OWNER S MANUAL. R 410A Ductless Split System Air Conditioner and Heat Pump

OWNER S MANUAL. R 410A Ductless Split System Air Conditioner and Heat Pump R 410A Ductless Split System Air Conditioner and Heat Pump Models DLC4(A/H) Outdoor Unit, DLF4(A/H) Indoor Unit Sizes 9K, 12K, 18K, 24K, 30K and 36K Please read the operating instructions and safety precautions

More information

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES

CZT CZT E.V.I. High efficiency air to water heat pumps with E.V.I. compressors OTHER VERSIONS ACCESSORIES High efficiency air to water heat pumps with E.V.I. compressors -15 C +63 C E.V.I. The series of high efficiency heat pumps has been specifically designed for use with radiant floor heating systems or

More information

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A

SERVICE MANUAL MUY-GL24NA - U1. No. OBH733. Models HFC. Revision B: REVISED EDITION-B R410A Revision B: MUZ-GL09NA- U8 and MUZ-GL09NAH- U8 have been added. Please void OBH733 REVISED EDITION-A. OUTDOOR INDOOR UNIT UNIT SERVICE MANUAL HFC utilized R410A. OBH733 REVISED EDITION-B Models MUZ-GL09NA

More information

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System PART 1 SYSTEM DESCRIPTION 1.1 The HVAC system is based on the CGC HYBRID Hydronic Heat Pump System. 1.2 The system will automatically

More information

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions ! Condensate Return Systems General Installation, Operation, & Service Instructions INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. SAFETY INSTRUCTIONS This safety alert symbol will be used in this

More information

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the MYSTICOOL Max Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

SWIMMING POOL HEAT PUMP UNIT Installation & Instruction Manual

SWIMMING POOL HEAT PUMP UNIT Installation & Instruction Manual SWIMMING POOL HEAT PUMP UNIT Installation & Instruction Manual OASIS C10 HEAT PUMP Head Office 62 Parkhurst Drive Knoxfield VIC 3180 T: 03 9887 2131 New South Wales Unit 1, 20-22 Foundry Road Seven Hills

More information