Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies
|
|
- Gregory Gibbs
- 6 years ago
- Views:
Transcription
1 Understanding Applications for Alternate Refrigerants Ron Bonear Emerson Climate Technologies
2 Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants Performance Development Thermophysical Comparison of Refrigerants Refrigerant Performance Reliability Evaluation Effect of New Refrigerants on Compressor Components Reliability Assessment R-448A/R-449A Development Summary and Conclusions Brief Update on Alternate Refrigerants R-450A/R-513A and R-452A Update on ECT s Alternate Refrigerant Facilities Development Plan
3 R-448A/R-449A Refrigerant Evaluation Methodology Alternate Refrigerant Evaluation Performance Focus on Developing Fast/Flexible Refrigerant Release Sidney Refrigeration Engineering Team Developed Test Strategy for Simultaneous Approval of R-448A and R-449A Equivalent Chemical Composition Between the Two Refrigerants Thermophysical Comparison, Miscibility and Compatibility Analysis Performed on R-448A/R-449A
4 UL Qualification Strategy Objective: Reduce UL Qualification Time Due to Chemical Equivalency of Refrigerants, UL Agreed to Full Model Line Approvals of Both R-448A/R-449A by Testing Only R-448A Testing Required to Show That R-448A MCC Amp Values Were +10% Above R-404A In All Instances, R-448A Met This Criteria The Majority of MCC Values Fall Below That of R-404A As a Result, R-448A Has Been Released Using Existing R-404A MCC Values By Utilizing This Approach, It Was Possible to Significantly Reduce the Total Number of Compressors Tested: 8 Scroll Compressors 6 Semi-Hermetic Compressors (4 Discus / 2 KEL)
5 R-448A/R-449A Refrigerant Evaluation Methodology Alternate Refrigerant Evaluation Reliability Evaluation of the Interaction of Refrigerants With Oil Miscibility/Solubility/Viscosity Bearing Analysis Performed Using Mobility Analysis Full Operating Envelope and Reliability (CFM) Testing Performed Using R-448A/R-449A
6 Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants Performance Development Thermophysical Comparison of Refrigerants Refrigerant Performance Reliability Evaluation Effect of New Refrigerants on Compressor Components Reliability Assessment R-448A/R-449A Development Summary and Conclusions Brief Update on Alternate Refrigerants R-450A/R-513A and R-452A Update on ECT s Alternate Refrigerant Facilities Development Plan
7 Evaluation of Alternate Refrigerant Performance Evaluation of R-448A/R-449A Relative to Existing Medium- Pressure Refrigerants Evaluate Equivalency of R-448A Relative to R-449A Evaluate Refrigerant Chemical Compositions Evaluate R-448A Relative to R-404A and R-407A Thermophysical Comparison of Refrigerants Pressure Differential Density Enthalpy Refrigerant Performance Testing Comparison
8 Evaluation of Refrigerant Chemical Composition R-448A/R-449A Relative Comparison Both R-448A and R-449A are medium-pressure, A1 refrigerants Verify chemical composition ± 5% Honeywell R-448A Composition R-32 (26%) R-125 (26%) R-134a (21%) 1234yf (20%) 1234ze (7%) DuPont R-449A Composition R-32 (24%) R-125 (25%) R-134a (26%) 1234yf (25%) Determination Made That the Two Refrigerants Are Effectively Chemically Equivalent
9 Evaluation of Refrigerant Pressure Differential Evaluate R-448A P to R-404A/R-407A R-448A exhibits a lower pressure differential than R-404A. R-448A compressor loads will be lower. R-448a and R-407A have essentially identical pressure differentials.
10 Evaluation of Refrigerant Density Evaluate R-448A Density Relative to R-404A/R-407A
11 Evaluation of Refrigerant Enthalpy Evaluate R-448A Theoretical Enthalpy Relative to R-404A/R-407A
12 Scroll MT Mid/Dew Point Capacity R-404A Versus R-407A/R-448A (20/70)
13 Scroll MT Mid/Dew Point Capacity R-404A Versus R-407A/R-448A (20/120)
14 Scroll LT Mid/Dew Point Capacity R-404A Versus R-407A/R-448A (-25/70)
15 Scroll LT Mid/Dew Point Capacity R-404A Versus R-407A/R-448A (-25/105)
16 Scroll MT Mid/Dew Point Weighted EER R-404A Versus R-407A/R-448A
17 Scroll LT Mid / Dew Point Weighted EER R-404A Versus R-407A / R-448A
18 R-448A/R-449A Operating Envelopes Summary and Conclusions Following Operating Envelope Testing and CFM, R-448A/R-449A Will Use Same Envelope as R-407A R-448A/R-449A Demonstrated Thermophysical Equivalence Discharge Line Temperatures Are Similar to But Slightly Higher Than R-407A at HCR/MDP Conditions Reliability Testing Confirms Higher Temperatures at Envelope Corners Are Acceptable» Only Map Affected Is ZBK5 Envelope All R-448A/R-449A Are the Same Envelopes as R-407A Only Exception Is ZBK5 Envelope, With Slightly Reduced HCR Corner Point
19 Final R-448A/R-449A MT K5 Operating Envelope
20 Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants Performance Development Thermophysical Comparison of Refrigerants Refrigerant Performance Reliability Evaluation Effect of New Refrigerants on Compressor Components Reliability Assessment R-448A/R-449A Development Summary and Conclusions Brief Update on Alternate Refrigerants R-450A/R-513A and R-452A Update on ECT s Alternate Refrigerant Facilities Development Plan
21 Refrigerant Reliability Evaluation Refrigerant Reliability Assessment Reliability Bearing Analysis Miscibility Solubility/Viscosity Mobility Analysis DFMEA High RPN Failure Modes Drive CFM Test Strategy CFM Testing Summary
22 Refrigerant Reliability Evaluation Reliability Development Envelope
23 Miscibility Evaluation
24 Viscosity Evaluation
25 Mobility Analysis of R-448A Relative to R-404A
26 R-448A/R-449A CFM Summary Evaluated Full Range of Compressors Using Standard Reliability Engineering Procedure Performed CFM Testing at Envelope Corner Points HCR MDP High Load Flooded Start and Defrost Cycles Tested to Verify Miscibility Ensure Full Hydrodynamic Bearing Film Thickness Following Refrigerant Washout Mobility Used to Validate Minimum Oil Film Thickness to Surface Finish Ratio (ʎ) R-448A/R-449A Meets or Exceeds ʎ for R-404A All Scroll/Semi-Hermetic Compressors Passed Full Battery of CFM Testing
27 Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants Performance Development Thermophysical Comparison of Refrigerants Refrigerant Performance Reliability Evaluation Effect of New Refrigerants on Compressor Components Reliability Assessment R-448A/R-449A Development Summary and Conclusions Brief Update on Alternate Refrigerants R-450A/R-513A and R-452A Update on ECT s Alternate Refrigerant Facilities Development Plan
28 R-448A/R-449A Summary and Conclusions From R-448A/R-449A Qualification, the Sidney Refrigeration Engineering Team Has Utilized a Standardized Test Strategy for New Refrigerants - Comparative Evaluation of Refrigerant Properties - Full UL, Performance, Operating Maps and Reliability Testing Thermophysical Similarity of R-448A and R-449A Has Been Verified The Thermophysical Properties of R-448A Are Much Closer to R-407A Than R-404A - R-404A Is Much Denser Than R-448A; Higher Mass Flows - R-448A Exhibits Lower P; Lower Bearing Loading Than R-404A - R-404A Capacity Significantly Greater Than R-448A at LT Conditions, Roughly Equivalent on MT Applications
29 R-448A/R-449A Summary and Conclusions R-448A/R-449A Operating Envelopes Are Equivalent to Current R-407A - Ref ZB*K5 HCR Condensing Will Be Slightly Reduced to Accommodate R-448A/R-449A and R407A on One Map Bearing Analysis Performed by Evaluating Miscibility/Viscosity, Loads, M Mobility Analysis and CFM Comprehensive R-448A/R-449A Performance and Reliability Evaluation Complete Captured Lessons Learned in Standardized Document - Utilized for All New Refrigerant Releases Accuracy and Completeness of Data for Both Performance and Reliability Are Assured
30 Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants Performance Development Thermophysical Comparison of Refrigerants Refrigerant Performance Reliability Evaluation Effect of New Refrigerants on Compressor Components Reliability Assessment R-448A/R-449A Development Summary and Conclusions Brief Update on Alternate Refrigerants R-450A/R-513A and R-452A Update on ECT s Alternate Refrigerant Facilities Development Plan
31 Update on R-513A/R-450A and R-452A Performance and Initial Reliability Evaluations Underway for Low- Pressure R-513A/R-450A (Europe and U.S.) and for Medium-Pressure R-452A (U.S., Transport Scroll Only) Preliminary Performance Evaluation for Refrigerants Complete Initial Reliability Assessments of Both R-452A and R-513A Indicate Higher Solubility Index May Pose Challenge for Compressor Boundary Lubrication Higher Solubility Reduces Oil Viscosity and May Affect Boundary Lubrication During Liquid Applications Currently Evaluating Alternate, Higher Viscosity Oil as Countermeasure
32 R-450A/R-513A Refrigerant Performance Capacity
33 R-450A/R-513A Refrigerant Performance EER
34 R-452A Refrigerant Performance Capacity
35 R-452A Refrigerant Performance EER
36 Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants Performance Development Thermophysical Comparison of Refrigerants Refrigerant Performance Reliability Evaluation Effect of New Refrigerants on Compressor Components Reliability Assessment R-448A/R-449A Development Summary and Conclusions Brief Update on Alternate Refrigerants R-450A/R-513A and R-452A Update on ECT s Alternate Refrigerant Facilities Development Plan
37 Recap of Alternatives for Refrigeration Applications Pressure Building or Capacity CO 2 R-410A Like R-404A and R-407/22 Like 1 NH 3 R290 < R-446A, R-447A, ARM-71a R-32/HFO R32 Blends ~300 HDR110 DR3 ARM-20a A1 Non-Flammable A2L Mildly Flammable 4 R-444B = L20 L40, DR7 ARM-20b R-32/HFO Blends A3 Flammable B2L Toxic, Mildly Flam. R-448A = N40 R-449A = DR33 R-449B = ARM-32 N20 < 1,500 R-32/HFC/HFO Blends R-410A R-22 R-407A R-407C R-407F, R-452A = XP44 AR M-35 Qualitative Not to Scale 2 R-404A R-507A (3922) R-134a Like R-123 Like (V. Low Pr.) HFO 1234yf HFO 1234ze ARM-42 DR2, N12, ARC 1 HFC/HFO R-450A = N13 ~600 Blends R-513A = XP10 R134a ,000 1,500 2,000 GWP Level
38 Emerson s A3 / A2L Facilities Development Plan
39 Emerson s A3 / A2L Facilities Development Plan
40 Emerson s A3 / A2L Facilities Development Plan
41 Selecting a TXV for Use With R-448A / R-449A / R-513A Brad Hopson Emerson Climate Technologies
42 Selecting a TXV for Use With R-448A / R-449A / R-513A Brad Hopson Emerson Climate Technologies
43 TXV Selection Review 1. Refrigeration Type 2. Evaporator Temperature/Pressure 3. Evaporator Capacity 4. Condensing Temperature/Pressure 5. Liquid Temperature 6. Distributor Type (if used) Note: The valve is sized to the evaporator and not the compressor.
44 Glide and the p-h Diagram Zeotropic Blends Exhibit Glide Calculating Delta P at Expansion Device: Bubble Point (Saturated Liquid) for Condensing Pressure Dew Point (Saturated Vapor) for Evaporating Pressure
45 TXV Pressure Differential This Is Also the Delta P at the Expansion Device Lower Delta P Generally Lowers Valve Capacity In the Given Applications, the Change in Pressure Differential Is Very Small
46 Superheat Superheat Curves (and Other Secrets) Evaporator Temp. R-404A Bulb Charges Are NOT Optimized for R-448/449 Superheat Settings MUST Be Adjusted At Low Temps, the Superheat Tends to Rise
47 Low-Temp. Valve Capacity Adjustment Low-Temp. Applications Require Larger Valves In Practice, Choose a Valve With 50% More Capacity
48 Summary Pressure Differential: Use Bubble Point for Condensing Pressure Use Dew Point for Evaporating Pressure R-513A Use R-134A Tables R-448A/R-449A Medium-Temp Very Similar to R-404A Low-Temp Select Approximately 50% More Capacity
49 Thank You! Questions? DISCLAIMER Although all statements and information contained herein are believed to be accurate and reliable, they are presented without guarantee or warranty of any kind, expressed or implied. Information provided herein does not relieve the user from the responsibility of carrying out its own tests and experiments, and the user assumes all risks and liability for use of the information and results obtained. Statements or suggestions concerning the use of materials and processes are made without representation or warranty that any such use is free of patent infringement and are not recommendations to infringe on any patents. The user should not assume that all toxicity data and safety measures are indicated herein or that other measures may not be required.
Understanding Applications for Alternative Refrigerants
Understanding Applications for Alternative Refrigerants E360 Forum Raleigh, N.C. March 1, 2017 Todd DeVore Director Technical Support Services Emerson Disclaimer This presentation is intended to highlight
More informationUnderstanding Applications for Alternative Refrigerants
Understanding Applications for Alternative Refrigerants E360 Forum Chicago, IL October 5, 2017 Jason Prenger Director of Engineering Emerson Disclaimer This presentation is intended to highlight changing
More informationDOE and EPA Impacts to Commercial Refrigeration
DOE and EPA Impacts to Commercial Refrigeration E360 Forum Chicago, IL October 5, 2017 Ani Jayanth Director, Product Marketing Emerson Disclaimer This presentation is intended to highlight changing developments
More informationRefrigerants Management & Retrofits. Mike Saunders & Randy Tebbe Emerson Climate Technologies
Refrigerants Management & Retrofits Mike Saunders & Randy Tebbe Emerson Climate Technologies Agenda Refrigerant Landscape and Proposed Regulation Review Life Cycle Climate Performance Refrigerant Phase-Down
More informationRefrigerant and Energy Regulations Update
Refrigerant and Energy Regulations Update Focus on Refrigeration Applications Dr. Rajan Rajendran Emerson Climate Technologies Reference and Disclaimer Reference: Federal Register Vol. 80 No. 138, July
More informationTEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A
More informationSustainable Refrigerant Solutions for HVAC-R. Laurent Abbas, Wissam Rached, Brett Van Horn
Sustainable Refrigerant Solutions for HVAC-R Laurent Abbas, Wissam Rached, Brett Van Horn 2014 ASHRAE Annual Conference Seattle, WA July 1, 2014 Learning Objectives 1. Design refrigeration and air-conditioning
More informationTEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)
More informationREFRIGERANT CHANGEOVER
Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants
More informationRefrigerant & Energy Regulations Update
Refrigerant & Energy Regulations Update Focus on Refrigeration Applications Rajan Rajendran Emerson Climate Technologies Agenda A Quick History on Refrigerant Progression Environmental Protection Agency
More informationHow to Meet 2017/2020 Energy Regulations
How to Meet 2017/2020 Energy Regulations U.S. Commercial Foodservice February 18, 2016 Allen Wicher Emerson Climate Technologies % Energy Foodservice Channel and Business Dynamics Balancing Four Basic
More informationBRA FACT FINDER Number 19
BRA FACT FINDER Number 19 Issue: 1 Date: March 2017 A practical guide to using refrigerants with a temperature glide This document is the second in a series of bulletins produced by the BRA following the
More informationSolstice 452A (R-452A) Reduced GWP and Discharge Temperature for Transport Refrigeration, Plug-Ins and Condensing Units
Low- and MediumTemperature Refrigeration Reduced GWP and Discharge Temperature for Transport Refrigeration, Plug-Ins and Condensing Units Solstice 452A (R-452A) Characteristics Solstice 452A (R-452A) is
More informationNew Case studies on Low GWP alternative refrigerants for HFCs. ABHIJEET KUDVA
New Case studies on Low GWP alternative refrigerants for HFCs. ABHIJEET KUDVA 5 th March 2014 Honeywell $39-39.5B in sales* 54% sales outside U.S. 1,300 sites, 70 countries 132,000 employees Morristown,
More informationR-404A Alternative with Low Compressor Discharge Temperature
2175, Page 1 R-404A Alternative with Low Compressor Discharge Temperature Barbara MINOR 1 *, Vladimir SULC 2, Jeff BERGE 3, Michal KOLDA 4, Michal HEGAR 5 1 DuPont, Fluoroproducts, Wilmington, DE, USA
More informationLow GWP Refrigerants for Air Conditioning Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta
More informationANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS
ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS YANA MOTTA, S. (*), SPATZ, M., VERA BECERRA, E. (*) Honeywell International, 2 Peabody Street, Buffalo, NY 1421, Samuel.YanaMotta@honeywell.com
More informationSOLSTICE L40X (R-455A)
Marta San Román October, 2016 SOLSTICE L40X (R-455A) F-gas ready GWP10million
More informationMaking Sense of the Latest Rulemaking on Acceptable Refrigerants. E360 Webinar
Making Sense of the Latest Rulemaking on Acceptable Refrigerants E360 Webinar November 29, 2016 Disclaimer This presentation is intended to highlight changing developments in the law and industry topics.
More information2016 Annual Conference
2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance
More informationReference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.
GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant
More informationR-407A R-448A R-449A
GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9 R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants
More informationSECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING
SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING UNIT OBJECTIVES After studying this unit, the reader should be able to Describe how refrigerant is charged into systems in
More informationRefrigerant changeover guidelines
Refrigerant changeover guidelines HCFC R-22 to HFC R-407A/F, R-448A or R-449A for medium and low temperature applications HCFC R-22 to HFC R-407C for high, medium and low temperature applications HCFC
More informationGary Parker Refrigerants Product Manager
Gary Parker Refrigerants Product Manager Refrigerant History Status of the HCFC ( R22) Phase out Ozone Friendly Alternatives Choosing the Best Retrofit Solution Lubricants and how they impact performance
More informationHoneywell Refrigerants. Retrofit Guidelines. R-404A/R-507A to: R-448A Solstice N40
Honeywell Refrigerants Retrofit Guidelines R-404A/R-507A to: R-448A Solstice N40 Table of Contents Introduction... 1 Solstice Refrigerants... 1 R-448A is not a Drop-in Replacement... 1 Retrofit Procedures...
More informationGary Parker Refrigerants Product Manager
Gary Parker Refrigerants Product Manager Refrigerant f i t History Status of the HCFC ( R22) Phase out Ozone Friendly Alternativesti Choosing the Best Retrofit Solution Lubricants and how they impact performance
More informationAHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program
More informationJanuary 16 th, 2014 New York City
Compressor Calorimeter Test of R-404A Alternative Refrigerants ARM-31a, D2Y-65, L-40, and R-32/R- 134a (50/50) in Medium Temperature Refrigeration Scroll Compressor Som Shrestha Omar Abdelaziz January
More informationLower GWP Refrigerants Compared to R404A for Economizer Style Compressors
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Lars Sjoholm
More informationChillers for High Ambient Conditions: What Technologies and Fluids?
Chillers for High Ambient Conditions: What Technologies and Fluids? Paul de Larminat, Maher Mousa Montreal, 18 November 2017 Contents Current chiller technologies Refrigerants Compressor technologies Energy
More informationRecommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS
COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit
More informationSystem Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller
System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller Satheesh Kulankara, William McQuade, Scott Rauch and
More informationPREPARE FOR CHANGE LOW GWP ALTERNATIVES. November 17
PREPARE FOR CHANGE LOW GWP ALTERNATIVES November 17 F-GAS PHASE DOWN Where we are now F-Gas regulation places restrictions on the use of some HFC refrigerants of high GWP. This is indirectly achieved by
More informationTEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat
More informationRefrigerant Glide and Effect on Performances Declaration
Refrigerant Glide and Effect on Performances Declaration Scope and Purpose As a consequence of the EU regulation 517/2014 (F-gas), the future synthetic refrigerants with a low global warming potential
More informationSeminar 34 Refrigerants Today, Tomorrow, and Beyond
m Bianca W. Hydutsky, Ph.D. DuPont Chemicals & Fluoroproducts bianca.hydutsky@dupont.com Seminar 34 Refrigerants Today, Tomorrow, and Beyond Thermal Stability Studies to Evaluate Low-GWP Refrigerants 1
More informationTEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,
More informationThe R-404A Challenge. Commercial Opteon Refrigerant Solutions - The New Industry Standard
Opteon Refrigerants The R-404A Challenge. Commercial Opteon Refrigerant Solutions - The New Industry Standard Mark Hughes Business Development Manager Opteon Refrigerants Agenda Intro Chemours The Chemical
More informationDrop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle
More informationTEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #6 System Drop-in Tests of R-22 Alternative Fluids (ARM-32a,
More informationRefrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate Technologies, Inc. does not advocate
More informationDevelopment of centrifugal chiller and heat pump using low GWP refrigerant
Development of centrifugal chiller and heat pump using low GWP refrigerant Ryosuke Suemitsu 1*, Naoya Miyoshi 1, Yasushi Hasegawa 1, Kazuki Wajima 1, Yoshinori Shirakata 1, Kenji Ueda 1 1 Mitsubushi Heavy
More informationThe Case for R-290 in U.S. Commercial Foodservice
The Case for R-290 in U.S. Commercial Foodservice E360 Forum Chicago, IL October 5, 2017 Bryan Tonn Senior Engineering Manager H&K International Allen Wicher Director, Marketing Foodservice Emerson Disclaimer
More informationThe Current Path of Refrigerants
The Current Path of Refrigerants Rick Wentling NA Market Development Manager Opteon Stationary Refrigerants November 9, 2017 Prediction is very difficult; especially if it s about the future. - Neils Bohr
More informationApplication Engineering
Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved
More informationLow Global Warming Refrigerants For Commercial Refrigeration Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel
More informationHoneywell Refrigerant Update
Honeywell Refrigerant Update Honeywell s refrigerants key attributes Environment HONEYWELL - CONFIDENTIAL 2 Fluorine Products A history of innovation Energy efficiency Environmental compliance Montreal
More informationSystematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Systematic Study of the Solution Properties of Low Global Warming Potential
More informationTEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #2 System Drop-in Test of L-40, L-41a and N-40b in Ice Machines
More informationRefrigerant and Energy Regulations Update
Refrigerant and Energy Regulations Update Focus on Refrigeration Applications Dr. Rajan Rajendran Emerson Climate Technologies HFC Phase-Down Amendment to Montreal Protocol Closer to Reality North America
More informationDEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION
Thomas Leck, PhD DuPont Fluorochemicals 2010 NEXT ACR Tokyo International Exchange Center 17 Feb 2010 DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION
More informationTechnical Information
Date of last update: May-15 Ref: C7.19.2/0813-0515/E Application Engineering Europe ZF* REFRIGERATION COPELAND SCROLL COMPRESSORS USING R407A, R407F, R448A OR R449A IN LOW TEMPERATURE APPLICATIONS ZF*
More information4/19/2013. The Changing State of Refrigerants
4/19/2013 The Changing State of Refrigerants Refrigerant Chemistry CFC = Chlorofluorocarbon Rapid phase-out Stopped U.S. production in 1996 R-11, R-12, R-113, R-114, R-500, R-502 HCFC = Hydrochlorofluorocarbon
More informationTEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled
More informationComparative Performance of HFO Blends in a Condenser
The knowledge hub for refrigeration, air conditioning and heat pumps Nick Atkins MInstR Simon Jones MInstR Gary Bell Comparative Performance of HFO Blends in a Condenser Paper 2 research laboratory tests
More informationCarwin COMPRESSOR SELECTION PROGRAM
Carwin COMPRESSOR SELECTION PROGRAM IMPORTANT! READ CAREFULLY BEFORE USING By using this disk covering a software program entitled CARLYLE SELECTION PROGRAM WINDOWS (Software), you indicate your acceptance
More informationAE R4 July 2015 Guide for the Use of R-290 Refrigerant in Copeland Refrigeration Compressors
July 2015 Guide for the Use of R-290 Refrigerant in Copeland Refrigeration Compressors TABLE OF CONTENTS Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to Risk of
More informationTop Retailer Trends for Refrigeration, Controls and Facility Optimization. E360 Webinar March 6, 2018
Top Retailer Trends for Refrigeration, Controls and Facility Optimization E360 Webinar March 6, 2018 Disclaimer This presentation is intended to highlight changing developments in the law and industry
More informationDROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER
Numbers of Abstract/Session (given by NOC) - 1 - DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER Richard W. Murphy Van D. Baxter Edward A. Vineyard Randall L.
More informationStudy of R161 Refrigerant for Residential Airconditioning
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen
More informationEvaluation of HCFC Alternative Refrigerants
Evaluation of HCFC Alternative Refrigerants Shaobo Jia Global Innovation Heatcraft Worldwide Refrigeration shaobo.jia@heatcraftrpd.com Introduction It is well-known that HCFC refrigerants widely used in
More informationR32 Compressor for Air conditioning and Refrigeration applications in China
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 R32 Compressor for Air conditioning and Refrigeration applications in China Weihua
More informationRS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:
TECHNICAL DATA SHEET Features and uses of is a non-azeotropic blend of HFC with zero Ozone Depletion Potential et low Global Warming Potential (GWP), formulated to meet the requirements of the F-Gas Regulation
More informationTEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source
More informationLow GWP Refrigerants for Air Conditioning and Chiller Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Low GWP Refrigerants for Air Conditioning and Chiller Applications Ankit
More informationsee notes on refrigerant type Refrigerant Type ASHR AE Refrigerant Composition (Mass % ) Zeotropes
Refrigerants subject to the F-Gas Regulation 517/2014 September 20This list is not intended to be complete or definitive. Please refer to the latest edition of ASHRAE Standard 34 and all published addenda
More informationTechnical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler
Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System
More informationAIRAH Victoria Refrigerants Update
AIRAH Victoria Refrigerants Update 20 th October 2014 Agenda R22 Phase down Legislation and options Interim replacements and considerations New HFO refrigerants Legislation as a driver for change New HFO
More informationBehavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32
More informationTest Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration
Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration Soft Optimization Test of a R404A Alternative Refrigerant R452A (DR34) in a Trailer Refrigeration
More informationCO 2 transcritical FTE System Full Transcritical Efficiency
CO 2 transcritical FTE System Full Transcritical Efficiency FRANCESCO MASTRAPASQUA Marketing Manager Refrigeration Systems Francesco.Mastrapasqua@eptarefrigeration.com www.eptarefrigeration.com HFC refrigerants
More informationSystem Considerations for Refrigerant Blends with Temperature Glide
System Considerations for Refrigerant Blends with Temperature Glide Theory and Practical Retrofit Guidance Table of Contents 1 2 3 4 5 Blend and Glide Basics... 3 1.1 Superheat and Subcooling of Refrigerant
More informationPRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR /R a. R E Low, B E Gilbert, T W Dekleva.
PRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR- 1 2 5/R- 1 34 a R E Low, B E Gilbert, T W Dekleva IC1 Klea ABSTRACT IC1 Klea has developed HFC alternatives to R-22 and R-502 which include
More informationRefrigerants. Refrigerants with the Future in Mind
Refrigerants Refrigerants with the Future in Mind Honeywell Refrigerants Products Guide Commercial Refrigeration Replaces ASHRAE Number GWP AR4 AR5 Chemical Name Blend Components Molecular Weight (g/mol)
More informationGWP Alternative Refrigerants
Update on Phase II of the AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) Karim Amrane and Xudong Wang Air Conditioning, Heating, and Refrigeration Institute (AHRI) Technical Forum
More informationTEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #63 System Soft-optimization Tests of Refrigerant R-32, DR-5A,
More informationCommercial CO 2 Refrigeration Systems
Commercial CO 2 Refrigeration Systems Guide for Subcritical and Transcritical CO 2 Applications 2 Contents Chapter 1. Introduction 4 Chapter 2. CO 2 Basics and Considerations as a Refrigerant 5 Section
More informationETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming
ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming 88 KENJI UEDA *1 YOSHINORI SHIRAKATA *2 YASUSHI HASEGAWA *3 NORIYUKI MATSUKURA *4 NAOYA MIYOSHI
More informationTEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton
More informationThomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.
Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration
More informationCOMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22
COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22 2013.12.26 prepared by James M. Calm, P.E. Engineering Consultant 10887 Woodleaf Lane Great Falls, VA 22066-3003 USA for
More informationScroll Chillers Transition from HCFC-22 to HFCs
Scroll Chillers Transition from HCFC-22 to HFCs An HVAC Manufacturer s Perspective Todd Brown McQuay International Business Development Manager Chillers todd.brown@mcquay.com ICF Workshop, Montreal Canada,
More informationAE R21 September 2017
September 2017 Application Guidelines for Copeland AF, AR & AS Refrigeration Hermetic Compressors For Refrigerants R-22, R-134A, R-404A, R-507, R-290, R-450A, R-513A, R-448A, R-449A TABLE OF CONTENTS Revision
More informationEmbraco Position Paper: Light Commercial Refrigeration
Embraco Position Paper: Light Commercial Refrigeration Refrigerants Outlook 2018 www.embraco.com Introduction The global community, with Kigali Amendment to Montreal Protocol, made another important step
More informationNew Refrigerants Designation and Safety Classifications
New Refrigerants Designation and Safety Classifications E360 Forum Raleigh, N.C. March 1, 2017 Stefanie Kopchick North America Marketing Manager, Refrigerants Chemours Greg Relue Manager, Regulatory Compliance/Product
More informationAHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low Global Warming Potential Alternative Refrigerants Evaluation Program
More informationFlammability and the Low GWP Refrigerant Challenge
Flammability and the Low GWP Refrigerant Challenge A Presentation to the BSRA Presentation On Guy Fawkes Night 5 th November 2015 Presented by Dewi Garcia MSc, MInstR Technical Manager Harp International
More informationThe Service Sector Prepares for HFO-1234yf Paul DeGuiseppi MACS Worldwide Mary Koban, DuPont Fluoroproducts
The Service Sector Prepares for HFO-1234yf Paul DeGuiseppi MACS Worldwide Mary Koban, DuPont Fluoroproducts Agenda HFO-1234yf Review Service Differences Technician Training Recovery/Recycle/Recharge Equipment
More informationTechnical Note. EHPA Quality Label Model Range Definition Version
Technical Note EHPA Quality Label Model Range Definition Version 1.0 2.7. 2010 1. Technical Conditions for Model Range Qualification 2 2. Uniformity in Design for Model Range Qualification 2 3. Reference
More informationHFO-1234yf Performance in a Beverage Cooler
2422 Page 1 HFO-1234yf Performance in a Beverage Cooler Barbara MINOR 1 *, Carlos MONTOYA 2, Francisco Sandoval KASA 3 1 DuPont Fluoroproducts, Wilmington, DE, USA Phone: 302-999-2802, E-mail: barbara.h.minor@usa.dupont.com
More informationTEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #43 System Drop-in Tests of Refrigerants L-41-1, L-41-2, and
More informationDue to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.
TECHNICAL DATA SHEET R434A () Features and uses of R-434A () is a non-flammable HFC mixture. ODP = 0, compatible with traditional mineral lubricants, alkyl benzene and also with synthetic POE, so there
More informationPRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division
INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During
More informationAE R17 November 2016
AE4-1344 R17 November 2016 Application Guidelines for Copeland RFT, RRT, RST Compressors For Refrigerants R-134A, R-450A,R-513A, R-290, R-404A, R-448A, R-449A and R-507 Section TABLE OF CONTENTS Page Safety
More informationPublication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration
More informationOtherwise, you can continue reading the file on the following pages.
If you d like to be able to print this file out to study off-line or use on the job, a printable version is available for an administrative fee of $3.97 USD. To download the unlocked file, click here.
More informationTechnical Bulletin (TB-0037)
Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant
More information10/4/2013. The Changing State of Refrigerants
10/4/2013 The Changing State of Refrigerants Refrigerant Chemistry CFC = Chlorofluorocarbon Rapid phase-out Stopped U.S. production in 1996 R-11, R-12, R-113, R-114, R-500, R-502 HCFC = Hydrochlorofluorocarbon
More informationLarge AC units using a variety of low-gwp options
Large AC units using a variety of low-gwp options By : Dr Alaa Olama, consultant, Egypt. The Workshop on Management of HFCs: Technical Issues Bangkok, Thailand, 20 and 21 April 2015. Alternatives to currently
More information