TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor
|
|
- Julianna Harmon
- 6 years ago
- Views:
Transcription
1 Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor Rajan Rajendran Autumn Nicholson Emerson Climate Technologies, Inc West Campbell Rd. Sidney, OH April 14, 2014 This report has been made available to the public as part of the author company s participation in the AHRI s Low-GWP AREP.
2 List of Tested Refrigerants Compositions (Mass%) DR-7 R-32/R-1234yf (36/64)
3 Contents Introduction... 3 Details of Test Setup... 4 Description of Test Refrigerant-Lubricant and Charge... 4 Description of Compressor... 4 Table 1. Compressor Calorimeter Test Points... 4 Description and Size of Test Loop... 5 Figure 1. Simplified System Diagram of Test Setup... 5 Table 2. Test Loop Component Accuracy... 6 Results... 7 Table 3. DuPont DR-7 Test Results (20F Superheat)- Dew Point... 8 Performance Curves and Coefficients... 9 Figure 2. DR-7 10-Coefficient Polynomial Equations for Cooling Capacity and Power (20F Superheat, 0F Subcool)... 9 Figure 3a and 3b. ZF18K4E-TFD R-404A Low Temperature and Medium Temperature Operating Map-With Liquid Injection (65 F Return Gas, 0F Subcool)... 9 Figure 4. R-404A Cooling Capacity vs. Evaporating Temperature (Dew Point)...10 Figure 5. DR-7 Cooling Capacity vs. Evaporating Temperature (Dew Point)...11 Figure 6. R-404A Input Power vs. Evaporating Temperature (Dew Point)...12 Figure 7. DR-7 Input Power vs. Evaporating Temperature (Dew Point)...13 Figure 8. R-404A Cooling COP vs. Evaporating Temperature (Dew Point)...14 Figure 9. DR-7 Cooling COP vs. Evaporating Temperature (Dew Point)...15 Comparative Analysis...16 Figure 10. DR-7/R-404A Cooling COP vs. Evaporating Temperature (Dew Point)...17 Figure 11. DR-7/R-404A Cooling Capacity vs. Evaporating Temperature (Dew Point)...18 Summary
4 Introduction This Report covers the calorimeter testing results of DuPont DR-7 performed by Emerson Climate Technologies, Inc. (Emerson) for the AHRI Low-GWP AREP study. The testing was done in Emerson s A2L Research calorimeter lab test facility located in Sidney, Ohio. The refrigerant was tested with a R-404A Copeland Scroll compressor ZF18K4E-TFD for refrigeration applications. This report is based on a drop-in test. No optimization, oil or hardware changes were made to account for the alternative refrigerant. All compressor tests are performed at a refrigerant s dew point temperature for suction and discharge pressure conditions, per AHRI Standard 540 requirements. This does not have an impact on comparing compressor performance between two or more refrigerants that do not exhibit temperature glide. However, when refrigerants exhibit temperature glide, it is important to note that actual systems operate closer to the mid-point condition. When comparing compressor performance of one refrigerant with glide to another refrigerant without glide, or comparing two refrigerants with significantly different glides, comparison at pressures corresponding to the mid-point of the temperature glide rather than the dew point will yield results that are more representative of actual operation in a system. 3
5 Details of Test Setup Description of Test Refrigerant-Lubricant and Charge Refrigerant/Refrigerant Blend tested: DuPont DR-7 o Initial Refrigerant Charge: 3.3 lbs (1.5 kg) Lubricant: o 32-3MAF POE Oil o Viscosity grade: 32 cst o Any modifications to base lubricant? No Description of Compressor Copeland R-404A Scroll No compressor modifications Emerson Climate Technologies, Inc. Copeland Brand Model No. ZF18K4E-TFD, Serial No. 12A5735AD Motor Nameplate Rating: 460V-3Ø-60Hz, 2 hp, 8.9A RLA (MCC/1.4), 3500 RPM (nominal) Displacement: in 3 /rev Air Flow Required (Y/N?): Yes Quantity: 1,360 ft 3 /min (38.5 m 3 /min) Velocity and Temperature of Air: 95 F Ambient Orientation of Air Flow In Relation to the compressor: Perpendicular to the vertical axis of the compressor Compressor Test Points (see Test Points in Table 1) Table 1. Compressor Calorimeter Test Points Refrigerant Vapor Saturated Saturated Suction Ambient Air Suction Temperature Discharge Discharge Discharge Volts-Phase- Temperature Temperature Pressure Entering Pressure Temperature Temperature 1 Frequency (Dew Point) Compressor (Dew Point) Speed F C psia Bar F C F C psia Bar F C F C V-Ø-Hz RPM , , , , , , , , , , , , , , , , Measured on Discharge Line 6" from Compressor Discharge Port. 4
6 Description and Size of Test Loop Test Loop Components: See Figure 1. Instrumentation/Accuracy: See Table 2. Figure 1. Simplified System Diagram of Test Setup 5
7 Table 2. Test Loop Component Accuracy Device Instrumentation Accuracy Full Scale/Span 3051S1TA3A2E11A2AT1 Suction Pressure Transducer +/ % span 300 psia Discharge Pressure Transducer +/ % span 800 psia EVI Pressure Transducer +/ % span 400 psia G4AD3 Suction Pressure Signal Conditioning Module +/_ 0.08% full scale 300 psia Discharge Pressure Signal Conditioning Module +/_ 0.08% full scale 800 psia EVI Pressure Signal Conditioning Module +/_ 0.08% full scale 400 psia 3144PD1A1NA Suction Temperature Transducer ± 0.45⁰F ±0.02% of span 200 ᴼF Discharge Temperature Transducer ± 0.45⁰F ±0.02% of span 400 ᴼF Compressor Ambient Temperature Transducer ± 0.45⁰F ±0.02% of span 200 ᴼF G4AD3 Suction Temperature Signal Conditioning Module +/_ 0.08% full scale 200 ᴼF Discharge Temperature Signal Conditioning Module +/_ 0.08% full scale 400 ᴼF Compressor Ambient Temperature Signal Conditioning Module +/_ 0.08% full scale 200 ᴼF G4AD18 EVI Temperature Signal Conditioning Module ± 1.62 F 435 ᴼF DSP-1Y25A125 Watts +/- 0.1% reading +/- 0.01% full scale kW Volts +/- 0.1% full scale 720 V Amps +/- 0.1% full scale 125 A CMF025 W/MVD Transmitter Compressor Mass Flow ±0.35% of rate CMF010 W/MVD Transmitter Oil Circulation Mass Flow ±0.1% of rate 6
8 Results Table 3 shows the test results from drop-in compressor testing with DR-7. The R-404A baseline data is from published nominal rating data (capacity and EER within ±5% of test data). Capacity calculations for DR-7 are done via measured mass flow multiplied by enthalpy change using the refrigerant properties supplied by the chemical manufacturer. All compressor performance is based on dew temperature/pressure and was tested per AHRI Standard The comparison is only provided for 20F compressor superheat, as running at higher superheat / return gas conditions resulted in discharge line temperatures greater than Copeland application guidelines permit without additional discharge temperature protection (i.e. liquid injection). 7
9 1 Measured on Discharge Line 6" from Compressor Discharge Port. COP Base 2 Evaporating Temperature, F ( C) Dew Point Evaporator Glide, F (C) Condensing Temperature, F ( C) Dew Point Table 3. DuPont DR-7 Test Results (20F Superheat)- Dew Point Condenser Glide, F (C) Discharge Temperature 1 F ( C) Applicable Superheating, F (C) Applicable Subcooling, F (C) Cooling Compressor Capacity, Btu/hr (W) Refrigerant Mass Flow Rate, lbm/hr (kg/hr) Amperes, A (A) Input Power, W Cooling EER, Btu/W-hr Cooling COP, W/W -40 (-40) 10.8 (6) 70 (21.1) 10.7 (5.9) 202 (94.4) 20 (11) 0 (0) (3812) 177 (80) 5.1 2, (-40) 10.8 (6) 90 (32.2) 10.3 (5.7) 235 (112.8) 20 (11) 0 (0) (3331) 173 (79) 5.4 2, (-40) 10.8 (6) 108 (42.2) 9.7 (5.4) 274 (134.4) 20 (11) 0 (0) 9813 (2876) 168 (76) 5.9 3, (-32) 10.8 (6) 105 (40.6) 9.8 (5.5) 232 (111.1) 20 (11) 0 (0) (4666) 257 (117) 6.3 3, (-29) 10.9 (6) 70 (21.1) 10.7 (5.9) 171 (77.2) 20 (11) 0 (0) (6657) 297 (135) 5.5 2, (-29) 10.9 (6) 90 (32.2) 10.3 (5.7) 197 (91.7) 20 (11) 0 (0) (6005) 298 (135) 6.0 3, (-29) 10.9 (6) 128 (53.3) 8.8 (4.9) 276 (135.6) 20 (11) 0 (0) (4203) 274 (124) 7.5 4, (-18) 11 (6.1) 80 (26.7) 10.5 (5.8) 161 (71.7) 20 (11) 0 (0) (10366) 468 (213) 6.3 3, (-18) 11 (6.1) 100 (37.8) 10 (5.5) 188 (86.7) 20 (11) 0 (0) (9156) 462 (210) 7.0 4, (-18) 11 (6.1) 120 (48.9) 9.2 (5.1) 221 (105) 20 (11) 0 (0) (7832) 453 (206) 7.9 5, (-18) 11 (6.1) 135 (57.2) 8.3 (4.6) 254 (123.3) 20 (11) 0 (0) (6565) 431 (196) 8.8 5, (-7) 11 (6.1) 80 (26.7) 10.5 (5.8) 146 (63.3) 20 (11) 0 (0) (16574) 722 (328) 6.9 4, (-7) 11 (6.1) 100 (37.8) 10 (5.5) 169 (76.1) 20 (11) 0 (0) (14560) 706 (321) 7.6 4, (-7) 11 (6.1) 120 (48.9) 9.2 (5.1) 196 (91.1) 20 (11) 0 (0) (12866) 711 (323) 8.8 5, (-7) 11 (6.1) 120 (48.9) 9.2 (5.1) 193 (89.4) 20 (11) 0 (0) (13143) 726 (330) 8.7 5, (-7) 11 (6.1) 140 (60) 7.9 (4.4) 231 (110.6) 20 (11) 0 (0) (10272) 672 (305) , (7) 10.9 (6.1) 100 (37.8) 10 (5.5) 159 (70.6) 20 (11) 0 (0) (24716) 1146 (521) 8.9 6, (7) 10.9 (6.1) 120 (48.9) 9.2 (5.1) 180 (82.2) 20 (11) 0 (0) (21451) 1127 (512) 9.9 6, (7) 10.9 (6.1) 140 (60) 7.9 (4.4) 207 (97.2) 20 (11) 0 (0) (17959) 1107 (503) , Base Refrigerant is R-404A Cooling COP alt / 8
10 Performance Curves and Coefficients The following plots show baseline R-404A and LGWP alternative DR-7 capacity, input power and COP using the 10-Coefficient polynomial equation for each refrigerant (see Figure 2 for DR- 7 Coefficients). These coefficients should only be applied within the acceptable compressor operating envelope to avoid excessive extrapolation error in the results. Testing was only run between -25 F and 30 F evaporating temperatures in order to maintain acceptable discharge temperatures without requiring liquid injection. The R-404A operating envelope(s) for the test compressor is shown in Figure 3. The x and y axes show dew point temperatures. COOLING CAPACITY (Btu/hr): C0 C1 C2 C3 C4 C5 C6 C7 C8 C POWER (W): P0 P1 P2 P3 P4 P5 P6 P7 P8 P Figure 2. DR-7 10-Coefficient Polynomial Equations for Cooling Capacity and Power (20F Superheat, 0F Subcool) a. Low Temperature Liquid Injected Map b. Medium Temperature Liquid Injected Map Figure 3a and 3b. ZF18K4E-TFD R-404A Low Temperature and Medium Temperature Operating Map-With Liquid Injection (65 F Return Gas, 0F Subcool) 9
11 Figure 4. R-404A Cooling Capacity vs. Evaporating Temperature (Dew Point) 10
12 Figure 5. DR-7 Cooling Capacity vs. Evaporating Temperature (Dew Point) 11
13 Figure 6. R-404A Input Power vs. Evaporating Temperature (Dew Point) 12
14 Figure 7. DR-7 Input Power vs. Evaporating Temperature (Dew Point) 13
15 Figure 8. R-404A Cooling COP vs. Evaporating Temperature (Dew Point) 14
16 Figure 9. DR-7 Cooling COP vs. Evaporating Temperature (Dew Point) 15
17 Comparative Analysis Figures 10 through 11 show the ratio of DR-7 to R-404A cooling COP and cooling capacity, respectively, versus evaporating temperature. At extreme operating conditions, testing uncertainties could lead to higher than normal variability in reported results. 16
18 Figure 10. DR-7/R-404A Cooling COP vs. Evaporating Temperature (Dew Point) 17
19 Figure 11. DR-7/R-404A Cooling Capacity vs. Evaporating Temperature (Dew Point) 18
20 Summary The compressor calorimeter testing of DuPont DR-7 was carried out at dew point conditions and compared to R-404A. DR-7 has moderate refrigerant glide of about 11F (6C). The compressor capacity versus R-404A is within 90 to 110% of rated performance across the operating map of the tested compressor (refer back to Figures 3a and 3b). The capacity was less than R-404A capacity at condensing temperatures less than 110 F (43.3 C). The compressor COP of DR-7 is between about 100 and 115% of R-404A across the reduced compressor operating envelope (less liquid injection). 19
TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)
More informationTEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,
More informationTEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled
More informationTEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton
More informationTEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat
More informationTEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source
More informationTEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #6 System Drop-in Tests of R-22 Alternative Fluids (ARM-32a,
More informationTEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #63 System Soft-optimization Tests of Refrigerant R-32, DR-5A,
More informationUnderstanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies
Understanding Applications for Alternate Refrigerants Ron Bonear Emerson Climate Technologies Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants
More informationJanuary 16 th, 2014 New York City
Compressor Calorimeter Test of R-404A Alternative Refrigerants ARM-31a, D2Y-65, L-40, and R-32/R- 134a (50/50) in Medium Temperature Refrigeration Scroll Compressor Som Shrestha Omar Abdelaziz January
More informationTEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #43 System Drop-in Tests of Refrigerants L-41-1, L-41-2, and
More informationAHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program
More informationApplication Engineering
Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved
More informationTEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Progra (Low-GWP AREP) TEST REPORT #68 Syste Drop-in Test of (R-448a) in a R04A Low and Mediu Teperature
More informationFigure 1: Schematic of internal heat exchanger vapor-injection cycle
Vapor-injection technique Development Guideline 1. Introduction This guideline shows the advantage and characteristics of Mitsubishi vapor injected-scroll compressor. The vapor injected-scroll compressor
More informationPressure Enthalpy Charts
Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance
More informationBehavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32
More informationTechnical Information
Date of last update: May-15 Ref: C7.19.2/0813-0515/E Application Engineering Europe ZF* REFRIGERATION COPELAND SCROLL COMPRESSORS USING R407A, R407F, R448A OR R449A IN LOW TEMPERATURE APPLICATIONS ZF*
More information2016 Annual Conference
2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance
More informationTest Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning
Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning System Drop-In Tests of R134a and R407C Alternative Refrigerants In Bus Air-Conditioning Units
More informationTest Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration
Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration Soft Optimization Test of a R404A Alternative Refrigerant R452A (DR34) in a Trailer Refrigeration
More informationPerformance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for
More informationLow GWP Refrigerants for Air Conditioning Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta
More informationR32 Compressor for Air conditioning and Refrigeration applications in China
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 R32 Compressor for Air conditioning and Refrigeration applications in China Weihua
More informationPerformance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units
ANSI/AHRI Standard 366 (SI) 2009 Standard for Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units Approved by ANSI on 4 January 2011 IMPORTANT SAFETY DISCLAIMER AHRI
More informationApplication of two hybrid control methods of expansion valves and vapor injected compression to heat pumps
AM-4249223-1 - Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps Christian K. Bach, Graduate Student, Eckhard A. Groll, Reilly Professor, James
More informationGWP Alternative Refrigerants
Update on Phase II of the AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) Karim Amrane and Xudong Wang Air Conditioning, Heating, and Refrigeration Institute (AHRI) Technical Forum
More informationSystem Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller
System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller Satheesh Kulankara, William McQuade, Scott Rauch and
More informationUP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM
EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors
More informationR-404A Alternative with Low Compressor Discharge Temperature
2175, Page 1 R-404A Alternative with Low Compressor Discharge Temperature Barbara MINOR 1 *, Vladimir SULC 2, Jeff BERGE 3, Michal KOLDA 4, Michal HEGAR 5 1 DuPont, Fluoroproducts, Wilmington, DE, USA
More informationThe Refrigeration Cycle
Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.
More informationREFRIGERANT CHANGEOVER
Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants
More informationSECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS
SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure
More informationSECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES
SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES After studying this unit, the reader should be able to Explain what conditions will cause the evaporator pressure
More informationThe Refrigeration Cycle
Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.
More informationTEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #12 System Drop-In Tests of Refrigerant Blends N-13a and AC5
More informationLow Global Warming Refrigerants For Commercial Refrigeration Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel
More informationPerformance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in
More informationN4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz
ENVIRONMENTALLY SOUND REFRIGERANT N4H4 Performance Series Product Specifications 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION
More informationR4H4. Product Specifications
R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY BALANCED REFRIGERANT 1-1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Scroll compressors on
More informationTechnical Information
Date of last update: May-12 Ref: : Application Engineering Europe ENHANCED VAPOUR INJECTION (EVI) FOR ZH*KVE SCROLL COMPRESSORS 1 Introduction... 2 2 Principle of operation... 2 3 Capacity effect... 3
More informationRefrigerant Glide and Effect on Performances Declaration
Refrigerant Glide and Effect on Performances Declaration Scope and Purpose As a consequence of the EU regulation 517/2014 (F-gas), the future synthetic refrigerants with a low global warming potential
More informationLower GWP Refrigerants Compared to R404A for Economizer Style Compressors
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Lars Sjoholm
More informationR4H4. Product Specifications
ENVIRONMENTALLY SOUND REFRIGERANT R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION
More informationTEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #2 System Drop-in Test of L-40, L-41a and N-40b in Ice Machines
More informationRecommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS
COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit
More informationCopeland Scroll Condensing Units for the Food Service Market
Copeland Scroll Condensing Units for the Food Service Market...with Best In Class Emerson System Protection Components Medium and Low Temperature Refrigeration Applications R-404A 1.5 to 10 Hp Reliable
More informationApplication and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS
Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A900-22007), 120/208/240/1/60, R404A, LT/MT APPS Introduction The superheat controller is designed
More informationPRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division
INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During
More informationAE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A
AE4-1392 July 2014 Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A Section TABLE OF CONTENTS Page Safety Safety Instructions...2 Safety Icon Explanation...2 Instructions
More informationEffects of Flash and Vapor Injection on the Air-to- Air Heat Pump System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System
More informationAE R13 August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS
August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS Safety Instructions... 3 Safety Icon Explanation... 3 Instructions Pertaining to Risk of Electrical Shock,
More informationAHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low Global Warming Potential Alternative Refrigerants Evaluation Program
More informationRefrigerants and lubricants
Refrigerants and lubricants GENERAL INFORMATION When choosing a refrigerant, different aspects must be taken into consideration: Legislation (now and in the future) Safety Application envelope in relation
More informationTechnical Bulletin (TB-0037)
Technical Bulletin (TB-0037) BITZER Software Guide Version 4, January 2015 DEFINITION OF TERMS Terms Found in the BITZER Software Condenser Capacity: The power needed to reject heat from the refrigerant
More informationTechnical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler
Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System
More informationPerformance Measurement of R32 Vapor Injection Heat Pump System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Performance Measurement of Vapor Injection Heat Pump System Yunho Hwang
More informationModeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration
Marquette University e-publications@marquette Mechanical Engineering Faculty Research and Publications Mechanical Engineering, Department of 1-1-2013 Modeling and Testing of an R-23/R-134a Mixed Refrigerant
More informationReport No CRT-414
Unit Nameplate Manufacturer: Available upon request form XDX Model No.YSC120E3RHAOWJX Serial No. 807103096L Volts: 208/230 Hertz: 60 Phase: 3 Refrigerant Type: R-410A Indoor Fan Motor Manufacturer: G.
More informationWCH5**4. Product Specifications
HEAT PUMP HIGH EFFICIENCY 15 SEER 1-1/2 THRU 5 TONS SPLIT SYSTEM ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 208 / 230 Volt, 1- phase, 60 Hz This product has been designed and manufactured to meet ENERGY
More informationAir Cooled Packaged Systems AIRAH Back to Basics
Air Cooled Packaged Systems AIRAH Back to Basics What s changed? New Refrigerants R410a MEPS EER / AEER / SEER Manufacturing Technologies Research, Development and Testing New technologies, controls, reliability
More informationStandard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units
ANSI/AHRI Standard 510-2006 (Formerly ARI Standard 510-2006) Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units Price $10.00 (M) $20.00 (NM) Printed
More informationN4H4. Product Specifications
14 SEER HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase, 208/230 Volt 3- phase, 460 Volt 3- phase; 60 Hz REFRIGERATION CIRCUIT S Scroll compressors
More informationSystematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Systematic Study of the Solution Properties of Low Global Warming Potential
More informationUnderstanding Applications for Alternative Refrigerants
Understanding Applications for Alternative Refrigerants E360 Forum Chicago, IL October 5, 2017 Jason Prenger Director of Engineering Emerson Disclaimer This presentation is intended to highlight changing
More informationTechnical Information
Date of last update: 02-08 Ref: Application Engineering Europe COPELAND SCROLL COMPRESSORS USING VAPOUR INJECTION FOR REFRIGERATION CONTENTS 1 Introduction...1 2 Principle of Operation...1 3 Capacity Effect...2
More informationSECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING
SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING UNIT OBJECTIVES After studying this unit, the reader should be able to Describe how refrigerant is charged into systems in
More informationSection 1: Theory of Heat Unit 3: Refrigeration and Refrigerants
Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants Unit Objectives After studying this chapter, you should be able to: Discuss applications for high-, medium-, and low temperature refrigeration.
More informationAHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers
AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers - ERRATA SHEET FOR AHRI STANDARD 1250 (I-P)-2009, PERFORMANCE RATING OF WALK-IN COOLERS AND FREEZERS December
More informationSystem Modeling of Gas Engine Driven Heat Pump
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 01 System Modeling of Gas Engine Driven Heat Pump Isaac Mahderekal shenb@ornl.gov
More informationEffects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 0 Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of
More informationA WET-VAPOUR INJECTION AND VARIABLE SPEED SCROLL COMPRESSOR AIR TO WATER HEAT PUMP MODEL AND ITS FIELD TEST VALIDATION
Paper O.2.2.4-1 - A WET-VAPOUR INJECTION AND VARIABLE SPEED SCROLL COMPRESSOR AIR TO WATER HEAT PUMP MODEL AND ITS FIELD TEST VALIDATION Laurent Dardenne*, Enrico Fraccari*, Alessandro Maggioni**, Luca
More informationR-407A R-448A R-449A
GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9 R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants
More informationScroll Compressor for Mobile HVAC/R Application
Purdue University Purdue e-pubs International ompressor Engineering onference School of Mechanical Engineering 2004 Scroll ompressor for Mobile HVA/R Application Michael M. Perevozchikov opeland orporation
More informationDrop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle
More informationComparative Performance of HFO Blends in a Condenser
The knowledge hub for refrigeration, air conditioning and heat pumps Nick Atkins MInstR Simon Jones MInstR Gary Bell Comparative Performance of HFO Blends in a Condenser Paper 2 research laboratory tests
More informationANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS
ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS YANA MOTTA, S. (*), SPATZ, M., VERA BECERRA, E. (*) Honeywell International, 2 Peabody Street, Buffalo, NY 1421, Samuel.YanaMotta@honeywell.com
More informationTHE FIVE W s SYSTEMES LMP MECHANICAL SUB-COOLING. I.G.A. GIRARD, TERREBONNE, Qc. INCREASED SYSTEM EFFICIENCY & LOWER ENERGY COSTS
THE FIVE W s WHO: WHAT: WHERE: WHY: SYSTEMES LMP MECHANICAL SUB-COOLING I.G.A. GIRARD, TERREBONNE, Qc. INCREASED SYSTEM EFFICIENCY & LOWER ENERGY COSTS WHEN: TIME LAPSE May 2013 to May 2014 Système LMP`s
More informationDOE and EPA Impacts to Commercial Refrigeration
DOE and EPA Impacts to Commercial Refrigeration E360 Forum Chicago, IL October 5, 2017 Ani Jayanth Director, Product Marketing Emerson Disclaimer This presentation is intended to highlight changing developments
More informationExhaust. a) For an arbitrary ambient temperature develop an expression for Q chiller in terms of M amb and M total.
1. State 2 75 o F Exhaust M amb T amb State 3 Room Q chiller State 1 60 o F M total A room at steady state has a supply air stream of cool air entering at 60 o F. The lights, office appliances and people
More informationREFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis
REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system
More informationSummary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000
SAE Alternate Refrigerant Cooperative Research Program Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 To: Alternate Refrigerant Task Force Members From: Ward Atkinson
More informationCopeland Scroll ( HP) ZB*KA and ZF*KA for Refrigeration
Copeland Scroll (0.75-1.25HP) ZB*KA and ZF*KA for Refrigeration Copeland Scroll ZB*KA: Medium Temperature Copeland Scroll ZF*KA: Low Temperature 1 Contents Market Dynamics GWP Refrigerant Update Current
More informationEvaluation of HCFC Alternative Refrigerants
Evaluation of HCFC Alternative Refrigerants Shaobo Jia Global Innovation Heatcraft Worldwide Refrigeration shaobo.jia@heatcraftrpd.com Introduction It is well-known that HCFC refrigerants widely used in
More informationTranscritical CO2 Bottle Cooler Development
Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains
More informationUnderstanding Applications for Alternative Refrigerants
Understanding Applications for Alternative Refrigerants E360 Forum Raleigh, N.C. March 1, 2017 Todd DeVore Director Technical Support Services Emerson Disclaimer This presentation is intended to highlight
More informationOxyvap Evaporative Cooling Applications
Oxyvap Evaporative Cooling Applications Oxycom Fresh Air BV March 9th, 2015 Abstract This paper shows two highly efficient applications of the Oxyvap direct evaporative cooling technology, developed by
More informationTechnical Development Program
Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7
More informationINDEXING AND CLASSIFICATION SYSTEM
Application Engineering Bulletin Index November 10, 2016 APPLICATION ENGINEERING MANUALS (Manuals come in a separate binder which can be ordered) AE-101 Fundamentals of Refrigeration AE-102 Refrigeration
More informationMAC N-407 Air-Cooled Chiller
MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=
More informationCommercial High-Efficiency Condensing Units
FORM NO. A22-194 REV. 2 Supersedes Form No. A22-194 Rev. 1 Commercial High-Efficiency Condensing Units RAWL High Efficiency 6.5 & 7.5 TON MODEL [22.86 & 26.38 kw] TABLE OF CONTENTS Model Number Designation...2
More informationSingle Screw Ammonia Heat Pumps. Harness Your Heat... Don t Reject It
Single Screw Ammonia Heat Pumps Harness Your Heat... Don t Reject It Harness Your Heat Don't Reject It Industrial processes consume considerable energy from two primary sources in the production of their
More informationNH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT
ENVIRONMENTALLY SOUND REFRIGERANT NH4H4 Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS, 208/230
More informationRefrigerant Cycle. Performance Data 1) Electric. Acoustic Pressure Level. Compressor. Connections, Dimensions
TECHNICAL DATA SHEET HP08L-M-WEB Performance Data 1) A-7W35 A2W35 A10W35 A2W50 Heating capacity 8,67 kw 11,14 kw 14,91 kw 9,87 kw Cooling capacity 6,16 kw 8,58 kw 12,33 kw 6,43 kw Input 2,51 kw 2,56 kw
More information100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION
100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest
More informationPackaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE
Service Facts Customer Property: Contains wiring and service information. Please retain. WC*240-SF-1H Library Service Literature Product Section Unitary Product Package Air Conditioner Model WC* Literature
More informationMath. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.
HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +
More informationEXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE
Karthikeyan, K. et al.: Experimental Investigations on Automobile Air S515 EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE by Karthikeyan
More informationRefrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate Technologies, Inc. does not advocate
More informationScroll Chillers Transition from HCFC-22 to HFCs
Scroll Chillers Transition from HCFC-22 to HFCs An HVAC Manufacturer s Perspective Todd Brown McQuay International Business Development Manager Chillers todd.brown@mcquay.com ICF Workshop, Montreal Canada,
More information