Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning

Size: px
Start display at page:

Download "Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning"

Transcription

1 Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning System Drop-In Tests of R134a and R407C Alternative Refrigerants In Bus Air-Conditioning Units

2 Acknowledgements Thanks to the following companies for supplying the refrigerant samples tested: - Honeywell Mexichem Daikin To those who performed the work: - Markéta Kopecká - Michal Hegar - Prague Lab Team - Vladimír Šulc 2

3 Purpose Evaluate selected alternative refrigerant blends to determine their performance as drop-in replacements for R134a and R407C in bus air-conditioning systems 3

4 Summary Two different low GWP refrigerants were tested as possible replacements of R134a in a bus air conditioning application. Two different low GWP refrigerants were tested as possible replacements of R407C in a bus air conditioning application. Testing was run at the same combination of conditions (ambient temperature / box temperature / box air humidity/ compressor speed/evaporator fan speed) as current units charged with R134a or R407C. 4

5 Evaluated Refrigerants Test Refrigerants N-13a R134a/R1234yf/R1234ze 42/18/40%wt GWP 604 AC5 R32/R152a/R1234ze 12/5/83%wt GWP 92 L-20 R32/R152a/R1234ze 45/20/35%wt GWP 331 D52Y R32/R125/R1234yf 15/25/60%wt GWP 979 5

6 Test Setup R134a Application: Roof Mounted Bus A/C, 24 kw Cooling Capacity Under Standard Rating Conditions 6

7 Test Setup, Cont. R407C Application: Roof Mounted Bus A/C, 32 kw Cooling Capacity Under Standard Rating Conditions 7

8 Test Conditions Multiple compressor and fan speeds tested 8

9 Test Results R134a system 9

10 Test Results, Cont. R134a system 10

11 Test Results, Cont. R134a system 11

12 Test Results, Cont. R134a system 12

13 Test Results, Cont. R407C system 13

14 Test Results, Cont. R407C system 14

15 Test Results, Cont. R407C system 15

16 Test Results, Cont. R407C system 16

17 Conclusion Refrigerants with lower GWP values can be formulated to replace R134a and R407C in bus air-conditioning systems The refrigerants tested are not true drop-in replacements. Use of the current alternatives will require changes to the design of existing bus air-conditioning systems Several refrigerants tested are rated A2L and risk assessment work must be carried out to determine safe operation in the bus air conditioning application 17

18 Questions? 18

19 APPENDIX 19

20 Test Setup Units basic description: - Compressor: 4 cylinder reciprocating open shaft, 30 in 3 displacement - Lubricant: 35 cst, POE - Refrigeration system schematic diagram: 20

21 Test Setup, Cont. Monitored quantities: 21

22 Test Setup, Cont. Testing chamber: Wind tunnel with the set of nozzles, air temperature and humidity control Compressor connected with the torque sensor and driven by the electric motor Measurement uncertainty = ±5% 22

23 Test Evaluation Compared Variables The unit cooling capacity is determined based on the control volume energy input and output balance Cooling capacity Qo = m_air*(h_evap_in h_evap_out) Total input power P_Unit = P_Compressor + P_Fans Compressor input power P_Compressor = Torque * ω - Tq [N*m] torque - ω [s^-1] angular speed 23

24 Test Evaluation Compared Variables, Cont. Evaporator temperatures difference: d EVOT EVOT EVOT / Evaporator superheat difference: d ESH ESH ESH / Condensing temperatures difference: d PGOT PGOT PGOT / Suction pressures difference: d PVIP PVIP PVIP / Suction temperatures difference: d PVIT PVIT PVIT / Discharge pressures difference: d PGOP PGOP PGOP / Discharge temperatures difference: d PGOT PGOT PGOT / Diesel consumption ratio: C C C / Net cooling capacity ratio: Q Q Q / Refrigerant charge ratio: Charge Charge Charge / COP: COP COP COP / 24

25 Comments on results Different parameters were observed, evaluated, and compared to the same parameters obtained with R134a or R407C. - Cooling capacity: R134a - AC5 has lower capacity at all conditions except two. The two conditions are within the experimental error of the test facility. - N-13a has lower capacity at all conditions. R407C - L-20 has slightly higher or same capacity at all conditions except one. The one condition is within the experimental error of the test facility. - D52Y has lower capacity at all conditions. 25

26 Comments on results - Unit COP: R134a - AC5 has lower COP values at all conditions except one. - N-13a COP varies from -4% to +3%. Considering test facility accuracy, COP is similar to R134a. R407C - L-20 has slightly higher COP values at all conditions except two. - D52Y COP values are lower at all conditions. 26

27 Comments on results - Discharge pressure: R134a - AC5 has higher pressure at all conditions except two. The pressure differences vary from -1 psid to +15 psid. - N13a has the discharge pressure lower at all conditions. The pressure differences vary from 0 psid to -10 psid. R407C - L-20 has generally higher pressure at higher box (104 F & 120 F) and simultaneously higher ambient conditions (104 F & 120 F). The pressure differences vary from psid to psid. - D52Y has the discharge pressure lower at all conditions. The pressure differences vary from -2 psid to -45 psid. 27

28 Comments on results - Discharge temperature: R134a - AC5 has generally lower discharge temperatures (to -15 F). - N13a has lower discharge temperature at all conditions (to -26 F). R407C - L-20 has generally higher discharge temperatures, especially at the combination of lower box and ambient temperatures (to +30 F). - D52Y has generally lower discharge temperature, especially at the combination of lower box and ambient temperatures (to -38 F). 28

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #12 System Drop-In Tests of Refrigerant Blends N-13a and AC5

More information

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration Soft Optimization Test of a R404A Alternative Refrigerant R452A (DR34) in a Trailer Refrigeration

More information

R-404A Alternative with Low Compressor Discharge Temperature

R-404A Alternative with Low Compressor Discharge Temperature 2175, Page 1 R-404A Alternative with Low Compressor Discharge Temperature Barbara MINOR 1 *, Vladimir SULC 2, Jeff BERGE 3, Michal KOLDA 4, Michal HEGAR 5 1 DuPont, Fluoroproducts, Wilmington, DE, USA

More information

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)

More information

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled

More information

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A

More information

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #43 System Drop-in Tests of Refrigerants L-41-1, L-41-2, and

More information

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,

More information

January 16 th, 2014 New York City

January 16 th, 2014 New York City Compressor Calorimeter Test of R-404A Alternative Refrigerants ARM-31a, D2Y-65, L-40, and R-32/R- 134a (50/50) in Medium Temperature Refrigeration Scroll Compressor Som Shrestha Omar Abdelaziz January

More information

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006 Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat

More information

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton

More information

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #6 System Drop-in Tests of R-22 Alternative Fluids (ARM-32a,

More information

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low Global Warming Potential Alternative Refrigerants Evaluation Program

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program

More information

Low GWP Refrigerants for Air Conditioning Applications

Low GWP Refrigerants for Air Conditioning Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta

More information

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS YANA MOTTA, S. (*), SPATZ, M., VERA BECERRA, E. (*) Honeywell International, 2 Peabody Street, Buffalo, NY 1421, Samuel.YanaMotta@honeywell.com

More information

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source

More information

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #2 System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

More information

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #63 System Soft-optimization Tests of Refrigerant R-32, DR-5A,

More information

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube ISSN: 2347-3215 Volume 1 Number 4 (2013) pp. 46-54 www.ijcrar.com Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube Richa Soni 1*, P.K.Jhinge

More information

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Oil Return Measurements In A Unitary Split System Air Conditioner Using

More information

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Lars Sjoholm

More information

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller Satheesh Kulankara, William McQuade, Scott Rauch and

More information

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants CHENNUCHETTY CHINNARAJ * Associate Professor in Mechanical Engineering, Government College of

More information

DIRA S.L. (Desenvolupament, Investigació i Recerca Aplicada S.L.)

DIRA S.L. (Desenvolupament, Investigació i Recerca Aplicada S.L.) : new refrigerant replacement for R-22 with low Global Warming Potential (GWP). Performance comparison with six existing refrigerants. CARRIED OUT BY DIRA S.L. (Desenvolupament, Investigació i Recerca

More information

Comparison of Oil Retention in R134a and CO 2 Climate Control Systems

Comparison of Oil Retention in R134a and CO 2 Climate Control Systems Comparison of Oil Retention in R134a and CO 2 Climate Control Systems Lorenzo Cremaschi Yunho Hwang,Ph.D. Reinhard Radermacher, Ph.D. CEEE University of Maryland Objective: Introduction Research Overview

More information

DEEPAK PALIWAL, S.P.S.RAJPUT

DEEPAK PALIWAL, S.P.S.RAJPUT International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-15 623 EXPERIMENTAL ANALYSIS OF HYDROCARBON MIXTURES AS THE NEW REFRIGERANT IN DOMESTIC REFRIGERATION SYSTEM DEEPAK PALIWAL,

More information

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Low Global Warming Refrigerants For Commercial Refrigeration Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel

More information

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for

More information

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32

More information

A study on retrofit methodologies for legacy air-conditioning systems to reduce their impact on global warming and ozone depletion

A study on retrofit methodologies for legacy air-conditioning systems to reduce their impact on global warming and ozone depletion A study on retrofit methodologies for legacy air-conditioning systems to reduce their impact on global warming and ozone depletion Prepared for the Public Commenting Meeting of Ph.D program February 28,

More information

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

Figure 1: Schematic of internal heat exchanger vapor-injection cycle Vapor-injection technique Development Guideline 1. Introduction This guideline shows the advantage and characteristics of Mitsubishi vapor injected-scroll compressor. The vapor injected-scroll compressor

More information

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research Update on Next Generation Low GWP Refrigerants for Chillers Products Steve Kujak Director, Next Generation Refrigerant Research The International Symposium on New Refrigerants and Environmental Technology

More information

Study of R161 Refrigerant for Residential Airconditioning

Study of R161 Refrigerant for Residential Airconditioning Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen

More information

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

The Design Of A New Generation Of Twin Screw Refrigeration Compressors Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2002 The Design Of A New Generation Of Twin Screw Refrigeration Compressors Z. Xing Xi an

More information

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

AIR COOLED CONDENSING UNITS

AIR COOLED CONDENSING UNITS AIR COOLED CONDENSING UNITS 50 Hz // ECOLITE ADVANCED SERIES BITZER ECOLITE air-cooled condensing units The new ECOLITE air-cooled condensing units for coercial refrigeration perfectly complement BITZER

More information

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units ANSI/AHRI Standard 510-2006 (Formerly ARI Standard 510-2006) Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units Price $10.00 (M) $20.00 (NM) Printed

More information

AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP)

AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) 2014 Purdue Conferences Xudong Wang and Karim Amrane Air Conditioning, Heating, and Refrigeration Institute (AHRI) Low GWP AREP Introduction

More information

A New Dedicated Outdoor Air System with Exhaust Air heat recovery

A New Dedicated Outdoor Air System with Exhaust Air heat recovery 12 th IEA HEAT PUMP Conference Paper number O1.2.4 A New Dedicated Outdoor Air System with Exhaust Air heat recovery GREATLAB Zi-Yang Zhang, Xiang Cao, Zhi Yang, Liang-Liang Shao, Chun-Lu Zhang, Yue Yu

More information

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Progra (Low-GWP AREP) TEST REPORT #68 Syste Drop-in Test of (R-448a) in a R04A Low and Mediu Teperature

More information

Gary Parker Refrigerants Product Manager

Gary Parker Refrigerants Product Manager Gary Parker Refrigerants Product Manager Refrigerant History Status of the HCFC ( R22) Phase out Ozone Friendly Alternatives Choosing the Best Retrofit Solution Lubricants and how they impact performance

More information

Tube-in-tube heat exchanger Type HE

Tube-in-tube heat exchanger Type HE Data sheet Tube-in-tube heat exchanger Type HE Tube-in-tube heat exchanger type HE is used primarily for heat transfer between the liquid and suction lines of the refrigeration plant. The purpose is to

More information

Experimental Performance Analysis of an Automotive Air Conditioning and Heat Pump System using R134a with and without Internal Heat Exchanger

Experimental Performance Analysis of an Automotive Air Conditioning and Heat Pump System using R134a with and without Internal Heat Exchanger Experimental Performance Analysis of an Automotive Air Conditioning and Heat Pump System using R134a with and without Internal Heat Exchanger Erkutay ASDEMIRCI, Ertan ALPEKIN, Murat HOSOZ Abstract In this

More information

PERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION

PERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION PERFORMANCE EVALUAION OF CO 2 HEA PUMP HEAING SYSEM O. KUWABARA (a), M. KOBAYASHI (a), H. MUKAIYAMA (a) M. ISHIKAWA (b), K. MUKUNOKI (b), N. HONMA (b) (a) R&D Headquarters, Sanyo Electric Co., Ltd. 1-1-1,

More information

Santanu Prasad Datta (Student) P. K. Das & S. Mukhopadhyay

Santanu Prasad Datta (Student) P. K. Das & S. Mukhopadhyay Effect of Refrigerant Charge, Compressor Speed and Air Flow through the Evaporator on the Performance of an Automotive Air Conditioning System 15 th International Refrigeration and Air July 14-17, 2014

More information

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle

More information

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators

More information

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Research On Gas Injection High Temperature Heat Pump With

More information

R32 Compressor for Air conditioning and Refrigeration applications in China

R32 Compressor for Air conditioning and Refrigeration applications in China Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 R32 Compressor for Air conditioning and Refrigeration applications in China Weihua

More information

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 26 Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants Jit Guan

More information

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Low GWP Refrigerants for Air Conditioning and Chiller Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Low GWP Refrigerants for Air Conditioning and Chiller Applications Ankit

More information

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures Experimental Study on Performance Parameters for Refrigerants, R41a and R44a at Various Air Outlet Temperatures P. Nagaraju P. G. Student Sanketika Institute of Technology and Management Ch. Kiran Kumar

More information

Embraco Position Paper: Light Commercial Refrigeration

Embraco Position Paper: Light Commercial Refrigeration Embraco Position Paper: Light Commercial Refrigeration Refrigerants Outlook 2018 www.embraco.com Introduction The global community, with Kigali Amendment to Montreal Protocol, made another important step

More information

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 SAE Alternate Refrigerant Cooperative Research Program Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 To: Alternate Refrigerant Task Force Members From: Ward Atkinson

More information

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Systematic Study of the Solution Properties of Low Global Warming Potential

More information

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration

More information

EN aquatech.piovan.com

EN aquatech.piovan.com EN aquatech.piovan.com Refrigeration Technologies: scroll-compressor chillers The scroll compressor is the most suitable component for the small and medium duty requirements in the industrial applications.

More information

The lowest energy consumption when using R290 LBP fixed speed compressors in a plug in ice cream conservator

The lowest energy consumption when using R290 LBP fixed speed compressors in a plug in ice cream conservator The lowest energy consumption when using R290 LBP fixed speed compressors in a plug in ice cream conservator Vicente Guilabert HUAYI COMPRESSOR BARCELONA, S.L The Company Huayi Compressor Barcelona, S.L.

More information

ZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS

ZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS ZERO ZONE USER GUIDE TO THE 2017 EPA RETAIL FOOD REFRIGERATION REGULATIONS Per the EPA: Retail food refrigeration, or commercial refrigeration, includes equipment designed to store and display chilled

More information

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1. 568, Page Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors Jose N. FONSECA *, Rodrigo KREMER, Thiago DUTRA 2 EMBRACO, Research & Development Group, Joinville, Santa Catarina,

More information

Department of MCE, Islamic University of Technology 2. Abstract

Department of MCE, Islamic University of Technology 2. Abstract Paper ID: TE-85 Study of power consumption characteristics of LPG and R134a in a vapor compression refrigeration system Md. Abu Shaid Sujon 1, Rakibul Hossain Ahmed 2, Dr. A.K.M. Sadrul Islam 3, Sk. Suzauddin

More information

PREPARE FOR CHANGE LOW GWP ALTERNATIVES. November 17

PREPARE FOR CHANGE LOW GWP ALTERNATIVES. November 17 PREPARE FOR CHANGE LOW GWP ALTERNATIVES November 17 F-GAS PHASE DOWN Where we are now F-Gas regulation places restrictions on the use of some HFC refrigerants of high GWP. This is indirectly achieved by

More information

Gary Parker Refrigerants Product Manager

Gary Parker Refrigerants Product Manager Gary Parker Refrigerants Product Manager Refrigerant f i t History Status of the HCFC ( R22) Phase out Ozone Friendly Alternativesti Choosing the Best Retrofit Solution Lubricants and how they impact performance

More information

Performance Measurement of R32 Vapor Injection Heat Pump System

Performance Measurement of R32 Vapor Injection Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Performance Measurement of Vapor Injection Heat Pump System Yunho Hwang

More information

Evaluation and Development of Air-conditioners using Low GWP Refrigerant

Evaluation and Development of Air-conditioners using Low GWP Refrigerant th IEA Heat Pump Conference 07 Rotterdam Evaluation and Development of Air-conditioners using Low GWP Refrigerant Shigeharu TAIRA, Tomoyuki HAIKAWA *, Tomoatsu MINAMIDA DAIKIN INDUSTRIES, LTD. 6th, May,

More information

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS Int. J. Chem. Sci.: 14(S2), 2016, 665-674 ISSN 0972-768X www.sadgurupublications.com PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS J. THAVAMANI *, MARRIPUDAGALA KOMALI, SHAIK

More information

AIR COOLED CONDENSING UNIT

AIR COOLED CONDENSING UNIT EVOLUTION SERIES AIR COOLED CONDENSING UNIT OUTDOOR AIR COOLED CONDENSING UNIT ORIGINAL MANUFACTURED EQUIPMENT CONCISE BROCHURE VERSION Evolution Series 1-6 BA-503-5 AUS Concise Evolution Air Cooled Condensing

More information

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Dr. R. A. Kathar 1, S. D. Surushe 2 1 Associate Professor, Mechanical

More information

Tube-in-tube heat exchanger Type HE

Tube-in-tube heat exchanger Type HE MAKING MODERN LIVING POSSIBLE Data sheet Tube-in-tube heat exchanger Type HE Tube-in-tube heat exchanger type HE is used primarily for heat transfer between the liquid and suction lines of the refrigeration

More information

COMPARATIVE STUDY OF NEW ECOLOGICAL GASES

COMPARATIVE STUDY OF NEW ECOLOGICAL GASES 2017 COMPARATIVE STUDY OF NEW ECOLOGICAL GASES JOSE LUIS URIBE-ECHEBARRIA JAVIER MARTINEZ DE ILARDUYA ANARTZ ITURRIOTZ LEIRE LONBIDE INTXAUSTI FRINSA S.L. 1. INTRODUCTION The purpose of the study is to

More information

AIRAH Victoria Refrigerants Update

AIRAH Victoria Refrigerants Update AIRAH Victoria Refrigerants Update 20 th October 2014 Agenda R22 Phase down Legislation and options Interim replacements and considerations New HFO refrigerants Legislation as a driver for change New HFO

More information

Danfoss Scroll for Refrigeration MLM / MLZ

Danfoss Scroll for Refrigeration MLM / MLZ s Danfoss Scroll for Refrigeration MLM / MLZ 50-60 Hz - R404A - R507 - R134a - R22 - R407A - R407F http://danfoss.us.com/ Contents Features... 6 Scroll compression principle... 7 The scroll compression

More information

FACT SHEET 9 Large Air-Conditioning (air-to-air)

FACT SHEET 9 Large Air-Conditioning (air-to-air) FACT SHEET 9 Large Air-Conditioning (air-to-air) UNEP Ozone Secretariat UNEP Ozone Secretariat Background Workshop Material for on HFC HFC Workshop, management: 205 technical issues Bangkok, 20 and 2 April

More information

Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386

Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386 Review of Temperature and Humidity Control Technology for Air Conditioning and Heat Pump Systems Paper 2386 Xiaojie LIN 1, Yunho HWANG 1, Reinhard RADERMACHER 1, Saikee OH 2 1 Center for Environmental

More information

SEMI-HERMETIC SCREW COMPRESSORS

SEMI-HERMETIC SCREW COMPRESSORS SEMI-HERMETIC SCREW COMPRESSORS 50 Hz // SP-00-5 EN HS.53 // HS.64 // HS.74 // HS.5 // HS.95 WITH IQ MODULE BIGGER MODELS BITZER Innovation Targets Semi-hermetic screw compressors Products for refrigerants

More information

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers - ERRATA SHEET FOR AHRI STANDARD 1250 (I-P)-2009, PERFORMANCE RATING OF WALK-IN COOLERS AND FREEZERS December

More information

The Current Path of Refrigerants

The Current Path of Refrigerants The Current Path of Refrigerants Rick Wentling NA Market Development Manager Opteon Stationary Refrigerants November 9, 2017 Prediction is very difficult; especially if it s about the future. - Neils Bohr

More information

Harold Ag & Mobile Products

Harold Ag & Mobile Products TM Harold Ag & Mobile Products Your Ag A/C Parts Specialist 1-800-541-8910 www.heco.net R E F R I G E R A N T S 6-18-13 FR-12 COMPARED TO OTHER BLENDS UL Classified A1/A1 (non-flammable!) ASHRAE Listed

More information

Torad Rotary Spool Compressor

Torad Rotary Spool Compressor Torad Rotary Spool Compressor Communication White Paper By: Torad Engineering, LLC Cumming, Georgia USA Torad Rotary Spool Compressor Introduction: The rotary spool compressor shares various attributes

More information

Refrigerants and lubricants

Refrigerants and lubricants Refrigerants and lubricants GENERAL INFORMATION When choosing a refrigerant, different aspects must be taken into consideration: Legislation (now and in the future) Safety Application envelope in relation

More information

Optimised for high ambient operation (up to 55 C ambient) EWAD-MZ. Air cooled chiller

Optimised for high ambient operation (up to 55 C ambient) EWAD-MZ. Air cooled chiller Optimised for high ambient operation (up to 55 C ambient) EWAD-MZ Air cooled chiller Why choose Daikin? Daikin were the among first to pioneer the use of inverters in air cooled screw chillers. And today,

More information

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2018 Evaluation and Optimization of System Performance using HFO-mix Refrigerants

More information

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes

More information

2016 Annual Conference

2016 Annual Conference 2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance

More information

Homework Chapter2. Homework Chapter3

Homework Chapter2. Homework Chapter3 Homework Chapter2 2/1 A storage tank holds methane at 120 K, with a quality of 25 %, and it warms up by 5 C per hour due to a failure in the refrigeration system. How long time will it take before the

More information

Mechanical Heat Pump R515

Mechanical Heat Pump R515 P.A.Hilton Ltd Mechanical Heat Pump R515 Above: R515 shown fitted with standard wattmeter Stabilises in minutes allowing many tests to be conducted in a typical laboratory period. Allows a complete refrigerant

More information

The analysis proceeded by adopting the ASHRAE guideline for conventional HVAC chiller applications. This guideline is summarized in Table II.

The analysis proceeded by adopting the ASHRAE guideline for conventional HVAC chiller applications. This guideline is summarized in Table II. Comparison of R134a and R1234ze for New Chiller Systems and for Fluid (Drop-In) in Existing Systems Francis A. Di Bella, P.E. Adam Weaver Colin Osborne Executive Summary A chiller cycle analysis is presented

More information

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies Understanding Applications for Alternate Refrigerants Ron Bonear Emerson Climate Technologies Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants

More information

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Study

More information

APS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017

APS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017 APS Chiller Seminar Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017 Agenda for today Refrigeration Cycle Chiller Types and Refrigerants Compressor Styles Chilled Water Pumping Systems

More information

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation Volume 6, Issue 3(201)199-204 ISSN 2347-325 Comparative Performance Evaluation of Vapor Compression Refrigeration System for drop-in Replacement of R22 Vaibhav Jain *, Dhruva Gupta, Himank Gupta, Anirudh

More information

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE Karthikeyan, K. et al.: Experimental Investigations on Automobile Air S515 EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE by Karthikeyan

More information

HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT

HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT THERMAL SCIENCE, Year 2011, Vol. 15, Suppl. 2, pp. S391-S398 391 HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT by Thirupandiyur Selvanambi RAVIKUMAR a* and Dhasan MOHAN LAL b a Department

More information

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE Proceedings of the Asian Conference on Thermal Sciences 2017, 1st ACTS March 26-30, 2017, Jeju Island, Korea ACTS-P00385 THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK

More information

GWP Alternative Refrigerants

GWP Alternative Refrigerants Update on Phase II of the AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) Karim Amrane and Xudong Wang Air Conditioning, Heating, and Refrigeration Institute (AHRI) Technical Forum

More information

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2010 Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear

More information

Technical Note. EHPA Quality Label Model Range Definition Version

Technical Note. EHPA Quality Label Model Range Definition Version Technical Note EHPA Quality Label Model Range Definition Version 1.0 2.7. 2010 1. Technical Conditions for Model Range Qualification 2 2. Uniformity in Design for Model Range Qualification 2 3. Reference

More information