1 : new refrigerant replacement for R-22 with low Global Warming Potential (GWP). Performance comparison with six existing refrigerants. CARRIED OUT BY DIRA S.L. (Desenvolupament, Investigació i Recerca Aplicada S.L.) Summary The cooling performance results of refrigerant, tested in a calorimeter designed to emulate the cooling conditions, demonstrate that the refrigerant has good energy efficiency, provides high cooling performances with reduced power consumption, and can be conveniently used, therefore, as a suitable replacement for R-22. Index 1. Objective 2. Refrigerants 3. Calorimeter circuit 3.1. Measuring instruments 4. Methods 4.1. Introduction 4.2. Dynamic tests 4.3. Stable state tests 4.4. Suction superheat 5. Results and conclusions 5.1. Cooling capacity, power input and COP 5.2. Suction pressure, discharge pressure and compression ratio 5.3. Discharge temperature 1
2 1. Objective GRIT S. L. (Gases: Research, Innovation & Technology SL), based in Barcelona, asked DIRA SL (Desenvolupament, Investigació i Recerca Aplicada SL) to test and compare the performance of seven refrigerants with regard to energy efficiency and other properties that can be used to obtain a deeper understanding of their behaviour. These tests were performed in DIRA SL (Carretera del Mig, 92, L'Hospitalet de Llobregat), by means of a suitable calorimeter to that effect. Specifically, two types of tests were performed: Dynamic tests Stable state tests 2. Refrigerants GRIT S. L. supplied to DIRA S. L. seven refrigerants, six of which were identified only as numbered samples, so that those in charge of conducting the tests were unaware of their identity. Thus, the set of tests consisted of blind tests. Only the R-22 sample was identified for commissioning the calorimeter, get a reference for determining the evaporation temperature of the different refrigerants and calibrate the sensors installed to monitor the system. The samples were supplied in conventional gas cylinders between 4 and 7 litres. The following designations indicate the different refrigerants: Sample 1 - Sample 2 R-22 Sample 3 MO99 (R438A) Sample 4 MO29 (R422D) Sample 5 MO59 (R417A) Sample 6 RS44 (R424A) Sample 7 RS-45 (R434A) These codes are also used in the graphs and the tables below. 3. Calorimeter circuit The circuit of the calorimeter used in the tests was specifically designed to estimate the performance characteristics of new refrigerants. Compressor Model 1,5 HP K7.2X from GELPHA Equipment designed for R-404A y R-507 Capable of operating in a wide range of temperatures Condenser Air-cooled Model Type HRT/ PN 2
3 Expansion device Danfoss valve TES2 designed for R404A o R507 external balance; then a 3-output capillary distributor was mounted. Evaporator and inertia thermal load The load consisted of a mixture of 25 litres of propylene-glycol and 25 litres of water, contained in a 50 litres cylinder. This load was stirred magnetically in order to achieve good heat transfer and quick thermal equilibrium inside. The evaporator is composed of three copper coils, each one of 15 m of length, wrapped around the container of the thermal load and contained in an outer cylinder. The narrow space between the inner and outer cylinders was filled with a mixture of ethylene glycol and water. 5 litres of each element was introduced to achieve a good heat transfer between the heat load and the evaporator coils Measuring instruments All tests were performed with the same cooling circuit, in the same conditions and with the same tracking equipment. Pressures were measured with a Testo recorder, while temperatures were stored by means of three recorders equipped with four temperature probes each: Testo 177-T4 (1 unit) and Testo 176- T4 (2 units). To these temperature recorders, it must be added a Testo 925, with which the temperature of the mixture of water and propylene glycol was measured. Finally, the power consumption was recorded by electricity meters Landis Gyr. With all this equipment it is possible to measure and record the following variables: Condensing and evaporating pressure. Temperature at the end of condenser. Temperature at the middle of condenser. Compressor discharge temperature. Output liquid temperature from condenser. Surface temperature of the outer cylinder at the top. Surface temperature of the outer cylinder at the middle. Surface temperature of the outer cylinder at the bottom. Evaporator outlet temperature. Inlet liquid temperature into expansion valve. Temperature of the blend propylene glycol-water. Power consumption of the compressor. 4. Methods 4.1. Introduction To cover the full range of required conditions it was necessary to combine dynamic tests with stable-state tests Dynamic tests All refrigerants have been tested using the method described below: First, the mixture of water and propylene glycol is heated using resistors to +50 C in order to provide a heat source to the evaporator. After reaching this temperature, the compressor starts to operate the refrigeration circuit. Heating the mixture to 50 C ensures that the temperature of the evaporator starts at least at +7 C, the maximum temperature required by the evaporator. 3
4 Condensing temperature is kept constant throughout the process at +45 C. This temperature is obtained by controlling the air flow to the condenser. The test ends when the mixture of water and propylene glycol reaches +32 C or reaches stability state conditions. The collected data were recorded and analyzed using Excel software, calculating following key parameters to characterize system performance: The electric power of the compressor (Pot Abs) was obtained by measuring the wattmeter. The cooling capacity of the refrigerant (Pot Frig) was obtained by the sum of the power of the heat load and the contribution of the environment.. Thus, the cooling power is obtained as follows: The COP of the system was obtained from the ratio of Pot Pot Frig and Abs Stable state tests All refrigerants have also been tested in stable conditions to achieve a low evaporating temperature, heating the mixture of water and propylene glycol with thermal loads of 2000, 1500, 1000W, 500W and 0W, maintaining at all times the condenser at +45 C. The Thermal gain obtained from the environment load was calculated using the following expressions: 4.4. Suction superheat Due to the fact that the identity of refrigerants was unknown (except R22) during the tests, it was not possible to calculate the suction superheat using thermodynamic tables. That is why several thermal probes placed around the evaporator were used. 4
5 It is estimated the average evaporation temperature of each refrigerant from data obtained with R22. The final temperature of evaporation can be obtained by adding half the glide to this temperature. From this temperature, it has been tried to have at all times an average of 5 C superheat at the evaporator outlet, since this temperature varies due to the expansion valve. 5. Results and conclusions 5.1. Cooling capacity, power input and COP 5
6 6
7 As seen both in the tables and graphs above, the COP of the (sample 1) is of the same magnitude as that of R-22 (sample 2), achieving high cooling capacities with low consumption Suction pressure, discharge pressure and compression ratio The pressures shown in the following table are obtained from the experimental measurements. These pressures do not precisely coincide with the pressure that would correspond to the different condensing and evaporating temperatures. The values of the power shown in the preceding paragraph have been corrected taking into account the above. 7
8 In the graph it can be observed how the suction pressure of the is a bit lower than that of R-22 in all operating ranges, being very similar to the suction pressure of sample 3. 8
9 5.3. Discharge temperature 9
COMPARATIVE STUDY OF NEW ECOLOGICAL GASES
2017 COMPARATIVE STUDY OF NEW ECOLOGICAL GASES JOSE LUIS URIBE-ECHEBARRIA JAVIER MARTINEZ DE ILARDUYA ANARTZ ITURRIOTZ LEIRE LONBIDE INTXAUSTI FRINSA S.L. 1. INTRODUCTION The purpose of the study is to
More informationDEEPAK PALIWAL, S.P.S.RAJPUT
International Journal of Scientific & Engineering Research, Volume 6, Issue 6, June-15 623 EXPERIMENTAL ANALYSIS OF HYDROCARBON MIXTURES AS THE NEW REFRIGERANT IN DOMESTIC REFRIGERATION SYSTEM DEEPAK PALIWAL,
More informationTranscritical CO2 Bottle Cooler Development
Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains
More informationLow Global Warming Refrigerants For Commercial Refrigeration Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel
More informationAN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS
AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS V. La Rocca 1, A. Messineo 2, D. Panno 1 1 Department of Energy, University of Palermo 2 Engineering Faculty, Kore
More informationRefrigeration Cycle Demonstration Unit R633
Refrigeration Cycle Demonstration Unit R633 Figure 1: R633 Unit Ozone friendly, low pressure, non-toxic working fluid allows evaporation and condensation to be seen in glass cylinders. A Bench top unit
More informationPressure Enthalpy Charts
Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance
More informationAvailable online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 109 (2017 ) 56 63 International Conference on Recent Advancement in Air Conditioning and Refrigeration, RAAR 2016, 10-12 November
More informationImplementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation
Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Marco Alexandre Onofre Dias This paper presents a model that was implemented
More informationInternational Journal of Informative & Futuristic Research ISSN (Online):
Reviewed Paper Volume 2 Issue 9 May 2015 International Journal of Informative & Futuristic Research ISSN (Online): 2347-1697 Performance Comparison of R22 and R290 Refrigerants Using Smaller Paper ID IJIFR/
More informationRecommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS
COMMERCIAL REFRIGERATION RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS www.tecumseh.com Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) 1-HCFCs & HFCs Retrofit
More informationR-404A Alternative with Low Compressor Discharge Temperature
2175, Page 1 R-404A Alternative with Low Compressor Discharge Temperature Barbara MINOR 1 *, Vladimir SULC 2, Jeff BERGE 3, Michal KOLDA 4, Michal HEGAR 5 1 DuPont, Fluoroproducts, Wilmington, DE, USA
More informationComparative Performance of HFO Blends in a Condenser
The knowledge hub for refrigeration, air conditioning and heat pumps Nick Atkins MInstR Simon Jones MInstR Gary Bell Comparative Performance of HFO Blends in a Condenser Paper 2 research laboratory tests
More informationExecutive Summary. Number of Low Number of High Number of Faults , Number of OK
Unit Lower limit Upper limit Air on Model no evap. F Air off evap. F dt air evap. F Executive Summary Evapo. F This is a summary chart for quick reference and view of all the systems tested. Red boxes
More informationRefrigeration Cycle Demonstration Unit R634
Refrigeration Cycle Demonstration Unit R634 Figure 1: R634 Unit shown with R634A and R634B fitted Ozone friendly, low pressure, non-toxic working fluid allows evaporation and condensation to be safely
More informationChapter 2. Alternatives to HCFCs and their Characteristics
Alternatives to HCFCs and their Characteristics Refrigerant - General Chemical used in a cooling system, such as an air conditioner or refrigerator, as the heat carrier which changes from vapour to liquid
More informationEffect of capillary diameter on the power consumption of VCRS using different refrigerants
Effect of capillary diameter on the power consumption of VCRS using different refrigerants Dr. A. G. Matani 1, Mukesh K. Agrawal 2 1 Asso. Professor, Mechanical Engineering Department, Govt. College of
More informationPERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION
PERFORMANCE EVALUAION OF CO 2 HEA PUMP HEAING SYSEM O. KUWABARA (a), M. KOBAYASHI (a), H. MUKAIYAMA (a) M. ISHIKAWA (b), K. MUKUNOKI (b), N. HONMA (b) (a) R&D Headquarters, Sanyo Electric Co., Ltd. 1-1-1,
More informationTest Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning
Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning System Drop-In Tests of R134a and R407C Alternative Refrigerants In Bus Air-Conditioning Units
More informationCHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM
111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to
More informationAIR COOLED CONDENSING UNITS
AIR COOLED CONDENSING UNITS 50 Hz // ECOLITE ADVANCED SERIES BITZER ECOLITE air-cooled condensing units The new ECOLITE air-cooled condensing units for coercial refrigeration perfectly complement BITZER
More informationEffects of Flash and Vapor Injection on the Air-to- Air Heat Pump System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System
More informationPerformance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in
More informationReference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.
GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant
More informationHigh-Performance, High-Reliability Gas Heat Pump
62 High-Performance, High-Reliability Gas Heat Pump Hideaki Kasahara* 1 Atsushi Yoshimura* 1 Ryuuji Morishima* 2 Hisao Iwata* 2 In order to response to annually increasing customer needs for economic efficiency
More informationEvaluation of Vapour Compression Refrigeration System Using Different Refrigerants
Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants Mukesh K. Agrawal, Dr. Ashok G. Matani Abstract- The performance of heat transfer is one of the most important research
More informationLAB EQUIPMENT DETAILS
DEPARTMENT OF MECHANICAL ENGINEERING LAB EQUIPMENT DETAILS S. N o Name of the Equipment Manufacturer Equipment Photo Description Applications Cost of the Equipment 1 Guarded plate The consists of main
More informationEnvironmentally friendly refrigeration systems for industrial use
compindustri Environmentally friendly refrigeration systems for industrial use CO ² refrigeration systems of the future GENERAL INFORMATION compindustri More than 10 years of development of refrigeration
More informationDrop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle
More informationTEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled
More informationOptimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf
Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf Gaurav #1, Raj Kumar* 2 1# Research Scholar, Department of Mechanical Engineering,
More informationEvaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2018 Evaluation and Optimization of System Performance using HFO-mix Refrigerants
More informationTEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat
More informationCHAPTER 1 INTRODUCTION
1 CHAPTER 1 INTRODUCTION 1.1 Background The science which deals with creating a controlled climate in indoor space is called air conditioning. Earlier days the air-conditioning was treated as a luxury,
More informationCHAPTER 1 INTRODUCTION
CHAPTER 1 INTRODUCTION 1.1 CFC REFRIGERANTS Since the 1930s, chlorofluorocarbons (CFCs) have been widely used as foam blowing agents, aerosols and especially refrigerants due to their pre-eminent properties
More informationPRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division
INTRODUCTION PRESSURE-ENTHALPY CHARTS AND THEIR USE The refrigerant in a refrigeration system, regardless of type, is present in two different states. It is present as liquid and as vapor (or gas). During
More informationAir & Water Heat Pump R832
Figure 1 : R832 P.A. Hilton Ltd Air & Water Heat Pump R832 Vapour Compression Heat Pump that allows Performance Investigation from both Air and Water Sources. Rapid Stabilisation enables detailed Investigation
More informationR-407A R-448A R-449A
GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9 R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants
More informationEffects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling
ISSN 2395-1621 Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling #1 Mr. Sachin Das, #2 Prof. M. V. Khot #1 Student, Mechanical
More informationSystem Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller
System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller Satheesh Kulankara, William McQuade, Scott Rauch and
More informationSERVICE ASSISTANT OVERVIEW FDSI Online Training
Author: Dale T. Rossi Online Editor: Zachary Williams SERVICE ASSISTANT OVERVIEW FDSI Online Training May 5, 2009 Table Service Assistant Description... 2 Installing the Main Unit... 3 Ambient Temperature...
More informationRole of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview
International Journal of Research in Engineering and Innovation Vol-2, Issue-1 (2018), 21-28 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com
More informationThe First 100+ Terms
A collection of short pointed topical papers. September 2007 Whether it s Air Conditioning or Refrigeration by: Garth Denison Senior Application Engineer If you are viewing a copy, but would like to receive
More informationThe Refrigeration Cycle
Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.
More informationLow GWP Refrigerants for Air Conditioning Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta
More informationPerformance of window air conditioner using alternative refrigerants with different configurations of capillary tube
ISSN: 2347-3215 Volume 1 Number 4 (2013) pp. 46-54 www.ijcrar.com Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube Richa Soni 1*, P.K.Jhinge
More informationIJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December
Performance Analysis of Eco-Friendly HC Mixture (R290/R600a) Refrigerant as an Alternative to in a Vapour Compression Refrigeration System for Sub-cooling using Heat Exchanger at Condenser Outlet and Diffuser
More informationNumerical Study on Improvement of COP of Vapour Compression Refrigeration System
Numerical Study on Improvement of COP of Vapour Compression Refrigeration System Sanath Kumar K H 1, Arun Kumara K S 2, Nissar Ahmed 3 Assistant Professor, Department of Mechanical Engineering, VVIT, Bangalore,
More informationREFRIGERANT CHANGEOVER
Date of last update: Dec-17 Ref: CC7.26.5/0117-1217/E Application Engineering Europe REFRIGERANT CHANGEOVER FROM HFC R134a TO HFC/HFO R450A & R513A WARNING Use only Emerson approved refrigerants and lubricants
More informationTEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)
More informationThe Refrigeration Cycle
Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.
More informationKelvin air conditioning. KELVIN Clim W250. Cooling Capacity: 250 ~ 1240 kw
Cooling Capacity: 250 ~ 1240 kw Water cooled liquid chillers in A class energy efficiency for indoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded
More informationAdsorption refrigeration system using waste heat
Adsorption refrigeration system using waste heat 1 RISHI SREEKUMAR, 2 SANJEEV SINGH, 3 HIMANSHU SHEKHAR, 4 RAUSHAN KUMAR, 5 Dr. R. S. BINDU 1,2,3,4 BE Students, 5 Professor Mechanical Engineering Department
More informationExperimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2016 Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during
More informationRefrigerant Dryers DRY with PDP Indicator
Refrigerant Dryers DRY with PDP Indicator Refrigerant dryers range From 333 lt./min up to 21.000 lt./min PDP: 5 C at reference conditions Whole range with the PDP indicator Max. working pressure: 16 bar
More informationDesign of LPG Refrigeration System
Design of LPG Refrigeration System Sethu Sathayan 1, Gopakumar M G 2, Jaya Krishnan S 3, Nanda Gopan 4, Nithin S 6 Assistant Professor, Department of Mechanical Engineering, SNIT Adoor, Kerala, India 1
More information2. CURRICULUM. Sl. No.
. CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration
More informationEvaluation and Development of Air-conditioners using Low GWP Refrigerant
th IEA Heat Pump Conference 07 Rotterdam Evaluation and Development of Air-conditioners using Low GWP Refrigerant Shigeharu TAIRA, Tomoyuki HAIKAWA *, Tomoatsu MINAMIDA DAIKIN INDUSTRIES, LTD. 6th, May,
More informationImproving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a
ISSN (e): 0 00 Vol, 0 Issue, 8 August 0 International Journal of Computational Engineering Research (IJCER) Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants
More informationMechanical Heat Pump R515
P.A.Hilton Ltd Mechanical Heat Pump R515 Above: R515 shown fitted with standard wattmeter Stabilises in minutes allowing many tests to be conducted in a typical laboratory period. Allows a complete refrigerant
More informationExperimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures
Experimental Study on Performance Parameters for Refrigerants, R41a and R44a at Various Air Outlet Temperatures P. Nagaraju P. G. Student Sanketika Institute of Technology and Management Ch. Kiran Kumar
More informationEnergy Use in Refrigeration Systems
2012 Rocky Mountain ASHRAE Technical Conference Energy Use in Refrigeration Systems PRESENTED BY: Scott Martin, PE, LEED AP BD+C Objectives Understand mechanical refrigeration terms Describe how heat is
More informationEXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE
Karthikeyan, K. et al.: Experimental Investigations on Automobile Air S515 EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE by Karthikeyan
More informationExperimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator
Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator Dr. R. A. Kathar 1, S. D. Surushe 2 1 Associate Professor, Mechanical
More informationJanuary 16 th, 2014 New York City
Compressor Calorimeter Test of R-404A Alternative Refrigerants ARM-31a, D2Y-65, L-40, and R-32/R- 134a (50/50) in Medium Temperature Refrigeration Scroll Compressor Som Shrestha Omar Abdelaziz January
More informationrecooler HP EQKR HEAT PUMP
AIR COMFORT AIR TREATMENT 9566 GB 2016.03.17 recooler HP EQKR HEAT PUMP» TECHNICAL CATALOGUE 2 ReCooler HP EQKR Technical Catalogue Content ReCOOLER HP EQKR HEAT PUMP 3 product presentation. 3 applications.
More informationH4T R410A. refrigerant
H4T INDEX Polyvalent unit working modes...pag. 4 Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R410A...pag. 5 Scroll compressors...pag.
More informationTHERMAL ENGINEERING LABORATORY II. To train the students with principles and operation of thermal Engineering equipments.
AIM: THERMAL ENGINEERING LABORATORY II To train the students with principles and operation of thermal Engineering equipments. OBJECTIVES: To experimentally analyze conduction, convection and radiation.
More informationKelvin air conditioning. KELVIN Clim W280. Cooling Capacity: 280 ~ 1840 kw
Cooling Capacity: 280 ~ 1840 kw Water cooled liquid chillers in A class energy efficiency for indoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded
More informationExperimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 14, Issue 1 Ver. V (Jan. - Feb. 2017), PP 75-82 www.iosrjournals.org Experimental Evaluation of
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical
More informationEXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER
EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER Gourav Roy; Taliv Hussain; Rahul Wandra Department of Mechanical Engineering, Lovely Professional
More informationBRA FACT FINDER Number 19
BRA FACT FINDER Number 19 Issue: 1 Date: March 2017 A practical guide to using refrigerants with a temperature glide This document is the second in a series of bulletins produced by the BRA following the
More informationIntroduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 200 Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid Haruhisa
More informationAIR CONDITIONING. Carrier Corporation 2002 Cat. No
AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)
More information4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)
4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao
More informationA Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes
ISSN 2395-1621 A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes #1 N. Dhekale, #2 Dr. P. A. Patil 1 amardhekale@gmail.com #12 Research Laboratory, Department
More informationPerformance Enhancement of Mini Refrigerator with Phase Change Materials
Performance Enhancement of Mini Refrigerator with Phase Change Materials Souptik Acharya 1, Manu Jose 2 and Risikesh Choudhury 3 Souptik Achraya,student at St. Martin s Engineering College Manu Jose T,
More informationExperimental Evaluation of a Gas Engine Driven Heat Pump Incorporated with Heat Recovery Subsystems for Water Heating Applications
Experimental Evaluation of a Gas Engine Driven Heat Pump Incorporated with Heat Recovery Subsystems for Water Heating Applications E. Elgendy 1,*, G. Boye 1, J. Schmidt 1, A. Khalil 2, M. Fatouh 3 1 Institute
More informationThe Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 The Development Of High Efficiency Air Conditioner With Two Compressors
More informationSubscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid
Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance
More informationPerformance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger
Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Shoeb Inamdar 1, H. S. Farkade 2 P.G. Student, Department of Mechanical Engineering, Govt. College of Engg. Amravati. Maharashtra,
More informationRefrigerant Glide and Effect on Performances Declaration
Refrigerant Glide and Effect on Performances Declaration Scope and Purpose As a consequence of the EU regulation 517/2014 (F-gas), the future synthetic refrigerants with a low global warming potential
More informationApplication of a hybrid control of expansion valves to a 3-ton large room cooling system
2123, Page 1 Application of a hybrid control of expansion valves to a 3-ton large room cooling system Christian K. Bach*, Eckhard A. Groll, James E. Braun Ray W. Herrick Laboratories, Purdue University,
More informationHFO-1234yf Performance in a Beverage Cooler
2422 Page 1 HFO-1234yf Performance in a Beverage Cooler Barbara MINOR 1 *, Carlos MONTOYA 2, Francisco Sandoval KASA 3 1 DuPont Fluoroproducts, Wilmington, DE, USA Phone: 302-999-2802, E-mail: barbara.h.minor@usa.dupont.com
More informationVolume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation
Use of Hydrocarbons in Low Temperature Circuit in Terms of First Law and Second Law of Four Stage Cascade Refrigeration of Semen Preservation R.S. Mishra Department of Mechanical Engineering, Delhi Technological
More informationSMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB
T_SMT_0609_GB 4,9 49,5 kw Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans INDEX SERIES IDENTIFICATION... 3 MODEL IDENTIFICATION... 3 CE CONFORMITY... 3 WORKING
More informationThe lowest energy consumption when using R290 LBP fixed speed compressors in a plug in ice cream conservator
The lowest energy consumption when using R290 LBP fixed speed compressors in a plug in ice cream conservator Vicente Guilabert HUAYI COMPRESSOR BARCELONA, S.L The Company Huayi Compressor Barcelona, S.L.
More informationAn Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters
An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters #1 Harshad D Kopurwar, #2 Pravin T Nitnaware, #3 Tapobrata Dey 1 harshvardhan1590@gmail.com #1 Mechanical
More informationCommercial Refrigeration
Commercial Refrigeration A science of vague assumptions based upon debatable figures taken from inconclusive experiments performed with instruments of problematical accuracy by persons of doubtful reliability
More informationARV.
ARV www.coldinnovation.it 1 INDEX Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R134a...pag. 5 Semi-hermetic screw compressor...pag.
More informationAn Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 An Investigation Into The Influence Of Improved Refrigeration Cycle And
More informationPerformance Assessment of Water Cooled Condenser Refrigeration System
Energy and Power 2017, 7(3): 70-74 DOI: 10.5923/j.ep.20170703.03 Performance Assessment of Water Cooled Condenser Refrigeration System Sheetal Narayan Shetty *, Prashanth Kamath Department of Mechanical
More informationTEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A
More informationPublication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS Refrigerant R22 is widely used for residential and commercial air conditioning, as well as commercial refrigeration
More informationKELVIN Clim F497. Kelvin air conditioning
KELVIN Clim F497 Cooling Capacity: 400 ~ 1260 kw Free-Cooling Capacity: 497 ~ 1492 kw Packaged air cooled liquid chillers with free-cooling system in A class energy efficiency for outdoor installation,
More informationEXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)
EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a) Abstract- With the recent government regulations, of banning the ozone depleting substances and Kyoto protocol
More informationENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou
Condensers ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM A. Hadawey, Y. T. Ge, S. A. Tassou 4 7 8 5 3 2 6 1 Produced by: The Centre for Energy and Built Environment
More informationRSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs
Lesson 1 - Introduction to Refrigeration and Air Conditioning Define refrigeration. Identify the basic components of a refrigeration cycle. Identify the various gas laws and their importance to a basic
More informationExperimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor
Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor Mingyue Huang a, Xiangfei Liang a,b *, Rong Zhuang a a Gree Electric Appliances, Inc.of Zhuhai,Zhuhai 519070,China
More information