System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller
|
|
- Candice Edwards
- 5 years ago
- Views:
Transcription
1 System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller Satheesh Kulankara, William McQuade, Scott Rauch and Justin Kauffman Building Efficiency Johnson Controls
2 Overview Introduction Overall Approach to Evaluation Air-Cooled Screw Chiller Details and Test Results Water-Cooled Centrifugal Chiller Details and Test Results Summary 2
3 Introduction This presentation covers results from the testing of lower GWP refrigerant alternatives for R-134a in chillers Two lower GWP refrigerants were tested and compared against R-134a ARM-42a (GWP < 150, azeotropic mixture, R-134a/R-152a/R-1234yf (7/11/82% by mass) R-1234ze(E) (GWP = 6, single component) Both refrigerants are classified as A2L per ASHRAE 34 Two types of chillers were evaluated Variable speed air-cooled screw chiller Variable speed water-cooled centrifugal chiller Testing was conducted to optimize both full load and integrated part load efficiency (IPLV) IPLV is described in AHRI 550/590 3
4 Overall Approach to Testing Two types of tests as defined in the AREP handbook were conducted Drop-in tests of ARM-42a in air-cooled screw chiller and water-cooled centrifugal chiller Drop-in tests of R-1234ze(E) in water-cooled centrifugal chiller Soft-Optimized tests of ARM-42a and R-1234ze(E) in water-cooled centrifugal chiller Test conditions followed AHRI 550/590 requirements All tests were conducted sequentially No modifications were made to the chillers during the course of testing Same instrumentation was used for all tests Soft-Optimized tests on the centrifugal chiller were tests with varying compressor speeds Data was averaged over a minimum of 15 minutes of steady state operation 4
5 Air-Cooled Screw Chiller Configuration Economized cycle Variable speed screw compressor Micro-channel condenser coils Falling film evaporator Electronic expansion valves POE oil Both refrigerants were tested with the same compressor speed at full load 5
6 Air-Cooled Screw Chiller Drop-In Test Results (ARM-42a) TEST # % CAPACITY AIR TEMP ( F) Ratio The full load capacity of the chiller with ARM-42a was equal to that with R-134a The part load of the chiller at 50% was different for the two refrigerants due to the number of fans operating. Chiller control was optimized for R-134a. It is possible to optimize chiller controls to improve at 50% to match R- 134a 6
7 Water-Cooled Centrifugal Chiller Configuration Variable speed centrifugal compressor Magnetic bearings Pre-rotation vanes Shell and tube condenser External subcooler Flooded evaporator Oil free chiller 7
8 Water-Cooled Centrifugal Chiller Drop-In Test Results With R-1234ze(E) Compressor speed that result in highest full load with R-134a was held constant for all tests Full load capacity of the chiller with R-1234ze(E) drop-in is 8.8% lower % CAPACITY R-134a R-1234ze(E) Ratio IPLV
9 Water-Cooled Centrifugal Chiller Soft-Optimized Test Results With R- 1234ze(E): Maximum IPLV Compressor speed optimized for each test condition to get maximum IPLV for each refrigerant Full load capacity of the chiller with R-1234ze(E) is 19.5% lower % CAPACITY R-134a R-1234ze(E) Ratio IPLV
10 Water-Cooled Centrifugal Chiller Soft-Optimized Test Results With R- 1234ze(E): Maximum Full Load Compressor speed optimized for each test condition to get maximum full load efficiency for each refrigerant Full load capacity of the chiller with R-1234ze(E) is 8.8% lower % CAPACITY R-134a R-1234ze(E) Ratio IPLV
11 Water-Cooled Centrifugal Chiller Drop-In Test Results With ARM-42a Compressor speed that result in highest full load with R-134a was held constant for all tests Full load capacity of the chiller with ARM-42a drop-in is 14.2% higher % CAPACITY R-134a ARM-42a Ratio IPLV
12 Water-Cooled Centrifugal Chiller Soft-Optimized Test Results With ARM-42a: Maximum IPLV Compressor speed optimized for each test condition to get maximum IPLV for each refrigerant Full load capacity of the chiller with ARM-42a is equal % CAPACITY R-134a ARM-42a Ratio IPLV
13 Water-Cooled Centrifugal Chiller Soft-Optimized Test Results With ARM-42a: Maximum Full Load Compressor speed optimized for each test condition to get maximum full load for each refrigerant Full load capacity of the chiller with ARM-42a is 14.2% higher % CAPACITY R-134a ARM-42a Ratio IPLV
14 ARM-42a SUMMARY Variable speed air-cooled screw chiller Equal capacity 3.5% lower full load efficiency Equal IPLV possible with changes to chiller control Variable speed water-cooled centrifugal chiller A range of design options with capacity ranging from equal to 14% higher Full load efficiency with ARM-42a is 8.5 to 9.7% lower IPLV is 9.0 to 16.3% lower Possible improvements in compressor and heat exchanger designs to increase chiller efficiency need to be evaluated 14
15 R-1234ze(E) SUMMARY Only tested in a variable speed, water-cooled centrifugal chiller A range of design options with capacity ranging from 9 to 20% lower Full load efficiency ranges from 0.6 to 5.8% lower IPLV ranges from 0.7% higher to 5% lower Possible improvements in compressor and heat exchanger designs to increase chiller efficiency need to be evaluated 15
TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled
More informationMidea VFD Centrifugal Chiller Technology
Midea VFD Centrifugal Chiller Technology Content Why VFD VFD centrifugal chiller technology Solution 2 HVAC major issues Energy conservation Global warming reduction 3 Why VFD No Compressor A/C Lower GWP
More informationJanuary 16 th, 2014 New York City
Compressor Calorimeter Test of R-404A Alternative Refrigerants ARM-31a, D2Y-65, L-40, and R-32/R- 134a (50/50) in Medium Temperature Refrigeration Scroll Compressor Som Shrestha Omar Abdelaziz January
More informationTEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)
More informationDevelopment of centrifugal chiller and heat pump using low GWP refrigerant
Development of centrifugal chiller and heat pump using low GWP refrigerant Ryosuke Suemitsu 1*, Naoya Miyoshi 1, Yasushi Hasegawa 1, Kazuki Wajima 1, Yoshinori Shirakata 1, Kenji Ueda 1 1 Mitsubushi Heavy
More informationAPS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017
APS Chiller Seminar Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017 Agenda for today Refrigeration Cycle Chiller Types and Refrigerants Compressor Styles Chilled Water Pumping Systems
More informationTEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #2 System Drop-in Test of L-40, L-41a and N-40b in Ice Machines
More informationAHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low Global Warming Potential Alternative Refrigerants Evaluation Program
More informationTEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat
More informationAHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP)
AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) 2014 Purdue Conferences Xudong Wang and Karim Amrane Air Conditioning, Heating, and Refrigeration Institute (AHRI) Low GWP AREP Introduction
More informationPresented By: John Dolan, P.E.
Variable Speed Compressor Technologies Presented By: John Dolan, P.E. President - Thermosystems, Inc. BS in Mechanical Engineering from UIUC 29 years HVAC Equipment Application Experience jdolan@thermohvac.com
More informationTEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A
More informationAHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program
More informationsee notes on refrigerant type Refrigerant Type ASHR AE Refrigerant Composition (Mass % ) Zeotropes
Refrigerants subject to the F-Gas Regulation 517/2014 September 20This list is not intended to be complete or definitive. Please refer to the latest edition of ASHRAE Standard 34 and all published addenda
More informationGWP Alternative Refrigerants
Update on Phase II of the AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) Karim Amrane and Xudong Wang Air Conditioning, Heating, and Refrigeration Institute (AHRI) Technical Forum
More informationAC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT
AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT Central Chiller Plant (with Cooling Tower and Chilled Water distribution) The other AC configuration is called a Chilled Water or Larger Cooler system. It
More informationReference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.
GUIDELINES FOR THE UTILIZATION OF R-404A R-452A Page 1 of 10 GUIDELINES FOR THE UTILIZATION OF R-404A AND R-452A For many years, R-404A has emerged as the industry's major choice as an alternative refrigerant
More informationTEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,
More informationTest Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration
Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration Soft Optimization Test of a R404A Alternative Refrigerant R452A (DR34) in a Trailer Refrigeration
More informationTEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source
More informationHVAC Water chiller selection and optimisation of operation
HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water
More informationKELVIN Clim F497. Kelvin air conditioning
KELVIN Clim F497 Cooling Capacity: 400 ~ 1260 kw Free-Cooling Capacity: 497 ~ 1492 kw Packaged air cooled liquid chillers with free-cooling system in A class energy efficiency for outdoor installation,
More informationChiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.
TURBOCOR COMPRESOR CHILLERS General Description Microprocessor controlled, water chiller using HFC 134a refrigerant, two stage centrifugal oil free variable speed compressor's and electronic expansion
More informationTechnical Development Program
Technical Development Program COMMERCIAL HVAC CHILLER EQUIPMENT Water-Cooled Chillers PRESENTED BY: Omar Rojas Sales Engineer Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7
More informationScroll Chillers Transition from HCFC-22 to HFCs
Scroll Chillers Transition from HCFC-22 to HFCs An HVAC Manufacturer s Perspective Todd Brown McQuay International Business Development Manager Chillers todd.brown@mcquay.com ICF Workshop, Montreal Canada,
More informationTEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #6 System Drop-in Tests of R-22 Alternative Fluids (ARM-32a,
More informationUnderstanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies
Understanding Applications for Alternate Refrigerants Ron Bonear Emerson Climate Technologies Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants
More informationTEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton
More informationChapter-8 Capacity Control of Refrigeration Systems
Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control
More informationTEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #12 System Drop-In Tests of Refrigerant Blends N-13a and AC5
More informationKelvin air conditioning. KELVIN Clim W250. Cooling Capacity: 250 ~ 1240 kw
Cooling Capacity: 250 ~ 1240 kw Water cooled liquid chillers in A class energy efficiency for indoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded
More informationResearch to Assist in the Development of Safety Standards and Building Codes for the Use of Flammable Refrigerants
Research to Assist in the Development of Safety Standards and Building Codes for the Use of Flammable Refrigerants Karim Amrane, Ph.D. Senior Vice President Low GWP AREP Cooperative research & testing
More informationThe Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.
The Refrigeration Cycle Jerry Cohen President Jacco & Assoc. Basic Refrigerant Cycle P/h Chart Compressor Options Condenser Options Head Pressure Control Thermal Expansion Evaporator Options Lift Evaporative
More informationEconomic Perspectives from Chiller Design to Operation. Ir K.T. Cheuk 1 Dec 2017
Economic Perspectives from Chiller Design to Operation Ir K.T. Cheuk 1 Dec 2017 2 Design x Construction Building Operation Design x Construction Acoustic Treatment Electrical Installation High Efficiency
More informationChillers, air and water cooled, featuring centrifugal compressors with magnetic levitation, from 200 to kw
Chillers, air and water cooled, featuring centrifugal compressors with magnetic levitation, from 200 to 1.99 kw Centrifugal compressor with magnetic levitation This is a miniaturized, highly innovative
More informationDevelopment of centrifugal chiller and heat pump using low GWP refrigerant
Development of centrifugal chiller and heat pump using low GWP refrigerant Abstract Ryosuke Suemitsu 1 *, Naoya Miyoshi 1, Yasushi Hasegawa 1, Kazuki Wajima 1, Yoshinori Shirakata 1, Kenji Ueda 1 1 Mitsubushi
More informationMethod to test HVAC equipment at part load conditions
IPLV Method to test HVAC equipment at part load conditions For water cooled chillers: 100% load ( % hrs) + 75% ( Hrs ) + 50% ( Hrs ) + 25% ( Hrs ) = IPLV value Manufacturer can favor this number by tweaking
More informationturb new unico turbo frigo turbo fl Liquid chiller equipped with magnetic levitation twostage centrifugal compressors RCGROUP SpA C_GNR_0711
89 TURBO turb Liquid chiller equipped with magnetic levitation twostage unico new frigo fl cooling capacity 260,0 1524,0 kw compressors centrifugal refrigerant R134a fan type axial (UNICO series) microprocessor
More informationOptimised for high ambient operation (up to 55 C ambient) EWAD-MZ. Air cooled chiller
Optimised for high ambient operation (up to 55 C ambient) EWAD-MZ Air cooled chiller Why choose Daikin? Daikin were the among first to pioneer the use of inverters in air cooled screw chillers. And today,
More informationUpdate on Codes and Standards Research. Karim Amrane, Ph.D. Senior Vice President
Update on Codes and Standards Research Karim Amrane, Ph.D. Senior Vice President Low-GWP AREP Cooperative research & testing program to identify suitable alternatives to high GWP refrigerants Evaluation
More informationETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming
ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming 88 KENJI UEDA *1 YOSHINORI SHIRAKATA *2 YASUSHI HASEGAWA *3 NORIYUKI MATSUKURA *4 NAOYA MIYOSHI
More informationKelvin air conditioning. KELVIN Clim W280. Cooling Capacity: 280 ~ 1840 kw
Cooling Capacity: 280 ~ 1840 kw Water cooled liquid chillers in A class energy efficiency for indoor installation, equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded
More information2016 Annual Conference
2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance
More informationLow GWP Refrigerants for Air Conditioning and Chiller Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Low GWP Refrigerants for Air Conditioning and Chiller Applications Ankit
More informationTEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #43 System Drop-in Tests of Refrigerants L-41-1, L-41-2, and
More information"ETI-Z, GART-ZE/ZEI" Centrifugal Chillers using Low-GWP Refrigerants for Full Capacity Range
3 "ETI-Z, GART-ZE/ZEI" Centrifugal Chillers using Low-GWP Refrigerants for Full Capacity Range YOSHIE TOGANO *1 JUN MIYAMOTO *1 YOSHIE KANKI *1 KAZUMI SHIMIZU *1 TAKAAKI MIURA *2 YASUSHI HASEGAWA *3 In
More informationHow to Select and Size a Chiller
How to Select and Size a Chiller -What is process cooling -Which chiller type is best for your application Dimplex Thermal Solutions FABTECH November 9-12, 2015 What is an Industrial Process Chiller? Uses
More informationSeries. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost
LL Chillers and Outdoor Mechanical Rooms Air-Cooled Features: Air-cooled condenser chillers with capacities from 35-345 tons Evaporative-cooled condenser chillers with capacities from 35-540 tons Variable
More informationDEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION
Thomas Leck, PhD DuPont Fluorochemicals 2010 NEXT ACR Tokyo International Exchange Center 17 Feb 2010 DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION
More information100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION
100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest
More informationSmardt Oil-Free Chillers
Smardt Oil-Free Chillers Company History in Brief Turbocor compressor invented in Australia in 1993 Turbocor was relocated to Montreal in 1999 Danfoss forms 50/50 partnership in 2004 Smardt was founded
More informationSECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
More informationUnderstanding Applications for Alternative Refrigerants
Understanding Applications for Alternative Refrigerants E360 Forum Chicago, IL October 5, 2017 Jason Prenger Director of Engineering Emerson Disclaimer This presentation is intended to highlight changing
More informationMidwest Industrial Initiative Webinar: Industrial Refrigeration
Midwest Industrial Initiative Webinar: Industrial Refrigeration Opportunities for Energy Efficiency and Cost Savings Thursday, June 6, 2013 www.kw-engineering.com Bryan Hackett, PE kw Engineering What
More informationR-407A R-448A R-449A
GUIDELINES FOR THE UTILIZATION OF R-407A R-448A R-449A 2018 Tecumseh Products Company LLC. All rights reserved. Page 1 of 9 R-407A, R-448A, and R-449A are recognized as suitable alternative refrigerants
More informationTEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #63 System Soft-optimization Tests of Refrigerant R-32, DR-5A,
More informationTest Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning
Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning System Drop-In Tests of R134a and R407C Alternative Refrigerants In Bus Air-Conditioning Units
More informationUpdate on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research
Update on Next Generation Low GWP Refrigerants for Chillers Products Steve Kujak Director, Next Generation Refrigerant Research The International Symposium on New Refrigerants and Environmental Technology
More informationMagnetic Bearing Technology: Achievements in Higher Efficiency
Magnetic Bearing Technology: Achievements in Higher Efficiency Magnetic Bearing Compressor 100% Oil Freeeliminates oil system maintenance costs. R134a Refrigerantmeets Montreal protocol and is not subject
More informationMaking Sense of the Latest Rulemaking on Acceptable Refrigerants. E360 Webinar
Making Sense of the Latest Rulemaking on Acceptable Refrigerants E360 Webinar November 29, 2016 Disclaimer This presentation is intended to highlight changing developments in the law and industry topics.
More informationProduct Line Introduction. Karl Zhang Technical support engineer
Product Line Introduction Karl Zhang Technical support engineer Air Conditioning Solutions Heating & Hot Water Solutions Control Solutions Air Conditioning Solutions Residential Application Commercial
More information2. CURRICULUM. Sl. No.
. CURRICULUM Sl. No. Code Title No. of Lecture Hours 1 RAC 001 Fundamentals of Refrigeration and Air 60 conditioning RAC 00 Psychrometry, Heat load Estimation for 70 Air conditioning and Refrigeration
More informationNew Case studies on Low GWP alternative refrigerants for HFCs. ABHIJEET KUDVA
New Case studies on Low GWP alternative refrigerants for HFCs. ABHIJEET KUDVA 5 th March 2014 Honeywell $39-39.5B in sales* 54% sales outside U.S. 1,300 sites, 70 countries 132,000 employees Morristown,
More informationLife Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint. Daryl Showalter ChillerApplications Manager McQuay International
Life Cycle Cost Of Selecting Chiller Equipment: Manufacturer s Viewpoint Daryl Showalter ChillerApplications Manager McQuay International Equipment Using Different Kinds Of Equipment Or Different Performance
More informationLow Global Warming Refrigerants For Commercial Refrigeration Systems
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel
More informationCommercial Refrigeration
Commercial Refrigeration A science of vague assumptions based upon debatable figures taken from inconclusive experiments performed with instruments of problematical accuracy by persons of doubtful reliability
More informationPerformance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in
More informationTranscritical CO2 Bottle Cooler Development
Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains
More informationVariable refrigerant flow (VRF) systems
SBS5311 HVACR II http://ibse.hk/sbs5311/ Variable refrigerant flow (VRF) systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents System Overview Components
More informationSustainable Refrigerant Solutions for HVAC-R. Laurent Abbas, Wissam Rached, Brett Van Horn
Sustainable Refrigerant Solutions for HVAC-R Laurent Abbas, Wissam Rached, Brett Van Horn 2014 ASHRAE Annual Conference Seattle, WA July 1, 2014 Learning Objectives 1. Design refrigeration and air-conditioning
More information4th IIR International Conference on Thermophysical Properties and Transfer Processes of Refrigerants 2013
4th IIR International Conference on Thermophysical Properties and Transfer Processes of Refrigerants 2013 Refrigeration Science and Technology Proceedings 2013-3 Delft, The Netherlands 17-19 June 2013
More informationAlternatives in the AC & Chiller Sectors. Sukumar Devotta and Lambert Kuijpers OORG Refrigeration
Alternatives in the AC & Chiller Sectors Sukumar Devotta and Lambert Kuijpers OORG Refrigeration 1 Outline ASHRAE position paper summary which marks a difference in the US approach dealing with various
More informationunico turbo fl kw R134a MICRO CHANNEL OIL FREE INVERTER FLOODED CLASS E C Energy Class RCGROUP SpA fiftycoolyears C_GNR_0113
tu 137 IR COOLED Liquid chiller equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded evaporator and microchannel CONDENSING coils 280 1500 kw Energy Class More efficient
More informationMarch 2014 AHRI Presents Research Findings at Low-GWP AREP Conference
March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference In addition to its regular research activities, AHRI is conducting the Low-Global Warming Potential Alternative Refrigerants Evaluation
More informationCOLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd
COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd Abstract This paper presents the design approach adopted for the expansion of a large existing
More informationSabroe Factory NetTraining COMP1 and sales tools
SABROE FACTORY Sabroe Factory NetTraining COMP1 and sales tools By Michael A. Jensen Sabroe Factory NetTraining COMP1 Select and templates 2 Johnson Controls PowerPoint Guidelines February 8, 2008 - basics
More information60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES
60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,
More informationFull and Partial Load Performances of RAC and CAC Heat Pump using R-32
Paper O.1.2.4-1 - Full and Partial Load Performances of RAC and CAC Heat Pump using R-32 Sungjin In, Graduate student, Sungkyunkwan University, Suwon, Gyunggi-do, 440-746, Korea Keumnam Cho, Professor,
More informationEffect of magnetic field on the performance of new refrigerant mixtures
INTERNATIONAL JOURNAL OF ENERGY RESEARCH Int. J. Energy Res. 2003; 27: 203 214 (DOI: 10.1002/er.868) Effect of magnetic field on the performance of new refrigerant mixtures Samuel M. Sami n,y and Shawn
More informationSystematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Systematic Study of the Solution Properties of Low Global Warming Potential
More informationFACT SHEET 9 Large Air-Conditioning (air-to-air)
UNEP Ozone Secretariat UNEP Ozone Secretariat Background Material on HFC Management Fact Sheets on HFCs and Low GWP Alternatives October 205 FACT SHEET 9 Large Air-Conditioning (air-to-air). Description
More informationPartial Load Performance Of Refrigeration System
Chapter 11 Partial Load Performance Of Refrigeration System Copy Right By: Thomas T.S. Wan 温到祥著 Sept. 3, 2008 All rights reserved Hot Gas Bypass & Liquid Injection: When the compressor is under surge condition,
More informationDue to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.
TECHNICAL DATA SHEET R434A () Features and uses of R-434A () is a non-flammable HFC mixture. ODP = 0, compatible with traditional mineral lubricants, alkyl benzene and also with synthetic POE, so there
More informationEffects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 0 Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of
More informationHFO-1234yf Performance in a Beverage Cooler
2422 Page 1 HFO-1234yf Performance in a Beverage Cooler Barbara MINOR 1 *, Carlos MONTOYA 2, Francisco Sandoval KASA 3 1 DuPont Fluoroproducts, Wilmington, DE, USA Phone: 302-999-2802, E-mail: barbara.h.minor@usa.dupont.com
More informationDOE and EPA Impacts to Commercial Refrigeration
DOE and EPA Impacts to Commercial Refrigeration E360 Forum Chicago, IL October 5, 2017 Ani Jayanth Director, Product Marketing Emerson Disclaimer This presentation is intended to highlight changing developments
More informationAir conditioning 23XRV
High-Efficiency ChillerS with screw compressors Air conditioning Control CCN - Carrier Comfort Network Features The Evergreen range offers superior solutions with record capacities from 970 to 1880 kw,
More informationAir Conditioning Components
Air Conditioning Components Agenda AC Components Compressor & Clutch Condenser Receiver-drier or Accumulator Expansion Valve or Orifice Tube Evaporator Compressor 2 primary purposes Increase pressure &
More informationComparison of Oil Retention in R134a and CO 2 Climate Control Systems
Comparison of Oil Retention in R134a and CO 2 Climate Control Systems Lorenzo Cremaschi Yunho Hwang,Ph.D. Reinhard Radermacher, Ph.D. CEEE University of Maryland Objective: Introduction Research Overview
More informationWeek 9. Refrigeration Cycles I. GENESYS Laboratory
Week 9. Refrigeration Cycles I Objectives 1. Introduce the concepts of refrigerators and heat pumps and the measure of their performance. 2. Analyze the ideal vapor-compression refrigeration cycle. 3.
More informationThe rotary type compressor consists of an integrally formed rotor and shaft, five vanes, and a cylinder.
W1860BE.book Page 12 Tuesday, January 28, 2003 11:01 PM 2. Cooling System A: COMPRESSOR The rotary type compressor consists of an integrally formed rotor and shaft, five vanes, and a cylinder. As the rotor
More informationUnderstanding Applications for Alternative Refrigerants
Understanding Applications for Alternative Refrigerants E360 Forum Raleigh, N.C. March 1, 2017 Todd DeVore Director Technical Support Services Emerson Disclaimer This presentation is intended to highlight
More informationThomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.
Thomas J Kelly Sr. Engineering Instructor Carrier Corporation August 20, 2003 1 SESSION OBJECTIVES At the conclusion of this session you should be able to: 1. Describe the basics principles of refrigeration
More informationWater-cooled chillers with High Speed Centrifugal Compressors
Water-cooled chillers with High Speed Centrifugal Compressors Refrigerant R134a 190-760 (395 to 2660 kw) Refrigerant R1234ze 135 G - 505 G (310 to 1820 kw) Table of Contents Introduction...3 Features and
More informationnext NEXT EVO CW kw UP FLOW DOWN FLOW CHILLED WATER E C CLOSE CONTROL AIR CONDITIONERS FOR CHILLED WATER FEEDING,
next CLOSE CONTROL AIR CONDITIONERS FOR CHILLED WATER FEEDING, NEXT EVO CW WITH UPFLOW OR DOWNFLOW AIR DELIVERY 6 261 kw CHILLED WATER E C UP FLOW DOWN FLOW 2 next evo cw INTRODUCTION The NEXT EVO CW series
More informationGEA Blu chillers. GEA BluAstrum, GEA BluGenium, GEA BluAir: A new generation of compact ammonia chillers
GEA Blu chillers GEA BluAstrum, GEA BluGenium, GEA BluAir: A new generation of compact ammonia chillers 3 Balanced to your benefit, in a class of their own Whether for food and beverage industry, process
More informationDIRA S.L. (Desenvolupament, Investigació i Recerca Aplicada S.L.)
: new refrigerant replacement for R-22 with low Global Warming Potential (GWP). Performance comparison with six existing refrigerants. CARRIED OUT BY DIRA S.L. (Desenvolupament, Investigació i Recerca
More informationMODELS LIST. Nominal Capacity RT
1. MODELS LIST. NOMENCLATURE 3. FEATURES 4. PRODUCT DATA 5. PERFORMANCE CORRECTION 6. ANTIFREEZE 7. INSTALLATION 8. ELECTRICAL DATA 9. SCHEMATIC WIRING DIAGRAM 10.MICROPROCESSOR CONTROLLER 11.APPLICATION
More informationR-404A Alternative with Low Compressor Discharge Temperature
2175, Page 1 R-404A Alternative with Low Compressor Discharge Temperature Barbara MINOR 1 *, Vladimir SULC 2, Jeff BERGE 3, Michal KOLDA 4, Michal HEGAR 5 1 DuPont, Fluoroproducts, Wilmington, DE, USA
More informationYour Chiller Solution For Efficiency And Reliability. McQuay Dual Compressor Centrifugal Chillers 160 to 2500 Tons
Your Chiller Solution For Efficiency And Reliability McQuay Dual Compressor Centrifugal Chillers 160 to 2500 Tons McQuay Dual Compressor Centrifugal Chillers Superior part load efficiency, reliability
More information