TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

Size: px
Start display at page:

Download "TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)"

Transcription

1 Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #63 System Soft-optimization Tests of Refrigerant R-32, DR-5A, and DR-55 in a R-410A 4-ton Unitary Rooftop Heat Pump-Heating Mode Performance Ken Schultz Marcos Perez-Blanco Steve Kujak Ingersoll Rand 3600 Pammel Creek Road La Crosse, WI January 18, 2016 This report has been made available to the public as part of the author company s participation in the AHRI s Low-GWP AREP.

2 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 2 of 12 INTRODUCTION This report documents tests performed on a 4 RT (14 kw) rooftop heat pump, to evaluate the performance of lower GWP refrigerants as alternatives to R410A in unitary air-conditioning and heat pump equipment. Compositions and GWPs are listed below in Table 1. The unit was run at the rating conditions specified in AHRI Standard 210/240 for heating mode performance. Tests were run using R410A (baseline), DR-55, R32, and DR-5A with performance of the three alternatives compared to the baseline R410A. The tests were performed in controlled ambient chambers at Ingersoll Rand/Trane s La Crosse Development Laboratory in La Crosse, Wisconsin, from late-may through early-august Table 1. Refrigerants tested, with compositions and global warming potentials (GWPs). Name composition (%wt) GWP (AR4) GWP (AR5) R410A 50% R32 / 50% R DR-55 67% R32 / 7% R125 / 26% R1234yf R32 100% R DR-5A 68.9% R32 / 31.1% R1234yf The thermodynamic properties of R410A and R32 are based on NIST s REFPROP v The thermodynamic properties of DR-55 and DR-5A are based on REFPROP v9.1 using mixing parameters for the R32/R1234yf and R125/R1234yf pairs provided Chemours (formerly DuPont). DETAILS OF TEST SETUP Description of Baseline System A Precedent model WSC048E3ROA1J rooftop unit, manufactured by Trane, was chosen for refrigerant testing purposes. The unit is rated at a net heating capacity of 44,000 BTU/hr (12.9 kw) heating capacity and 3.40 COP, with a catalog refrigerant charge of 9.0 lbm (4.1 kg) of R410A. The unit is driven by an Alliance model SXA044B2BPA fixed speed scroll compressor with a displacement of ft³/rev (2.56 in³/rev or L/rev) lubricated with Emkarate RL32H POE oil. The compressor runs at 3500 RPM at 60 Hz input frequency for a displacement of 311 ft³/hr (8.82 m³/hr). The indoor and outdoor heat exchangers are of aluminum-fin/copper-tube construction with fixed speed fans. Description of Modifications to System The original factory-installed fixed TXVs for cooling and heating were both replaced with adjustable TXVs of the same size. Additionally the compressor was fitted with a variable frequency drive (VFD, Trane TR200 P5K5), which allowed the compressor speed (volumetric capacity) to be varied so that all the refrigerants could be tested at the same thermodynamic capacity. Measure- 1 The descriptions of R410A and R32 have not changed from REFPROP v8.1 to the current v9.1. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

3 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 3 of 12 ment of input power was made upstream of the VFD, however, the efficiency of the AFD is essentially constant (cataloged at 0.97) over the range of power and speed tested, so it has no effect on the comparisons between refrigerants. Description of Tests Conducted The method of test was consistent with Appendix M of AHRI Standard 210/240 with Addenda 1 and 2 (2008/2012), with operating conditions generally held within tighter tolerances. The indoor (ID) airflow rate was fixed at the catalog value of 1600 scfm for all tests. Figure 1 shows a diagram of the Precedent unit. In this diagram, the reversing valve is in the heating mode position. The points in the cycle at which measurements such as pressure and temperature were taken are indicated on the diagram. The accuracies of the various instrument types are listed in Table 2. Table 2. Instrumentation accuracies. measurement accuracy thermocouples (uncalibrated) ±1 RTD sensors (calibrated) ±0.1 air-side pressure differences (calibrated) Rosemount 1151DP3S12 (30 inh 2 O full scale) ±0.075% of span pressure transducers (calibrated) Honeywell DS-750 (750 psi full scale) ±0.1% full scale refrigerant turbine meter (calibrated) Flow Technology FT4-8NE00-LEAH4 ±0.5% of reading electrical power (calibrated) YEW WT230 (6 kw full scale) ± (0.1% of reading + 0.1% of range) The reported heating capacities were calculated from airside flow rate and temperature (dry bulb and wet bulb) measurements. For confirmation, capacity was also calculated from refrigerant side flow rate and enthalpy measurements around the indoor coil, providing a check on energy balance. Internal property codes, consistent with ASHRAE and NIST REFPROP descriptions, were used for calculation of air and refrigerant thermodynamic properties. Tests were carried out at the rating points called out in AHRI Standard 210/240 for heating performance, listed in Table 3. The H2 conditions produce frosting on the outdoor evaporator coil, resulting in cyclic heat/defrost operation. The capacity and efficiency values reported here are integrated averages over a number of heat/defrost cycles acquired after several heat/defrost cycles had occurred and periodic steady-state had been established. Although the H3 conditions also result in frosting of the outdoor coil, the build-up rate is slow enough to allow essentially steady-state behavior. Performance at the H3 conditions was determined by averaging capacity and power consumption for 30 minute period following the termination of a defrost cycle. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

4 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 4 of 12 Table 3. Conditions for the H1, H2, and H3 heating mode rating tests. test indoor Tdb indoor Twb outdoor Tdb outdoor Twb H1 70 / 21.1 C 60 / 15.6 C 47 / 8.3 C 43 / 6.1 C H2 70 / 21.1 C 60 / 15.6 C 35 / 1.7 C 33 / 0.6 C H3 70 / 21.1 C 60 / 15.6 C 17 / 8.3 C 15 / 9.4 C Refrigerant charge and compressor speed were taken from the A cooling condition as described in the previous report 2 and summarized in Table 4. A charge sweep run with R410A in heating mode at the H1 conditions showed a peak in COP at the same 9.0 lbm (4.1 kg) charge determined from the cooling mode tests. The heating mode TXV was adjusted at the H1 conditions with each alternative refrigerant to deliver the same compressor suction superheat as obtained with R410A (~10/5.6 C). RESULTS Table 4 shows the refrigerant charge, TXV setting, and compressor speed used for each refrigerant. Also shown is the heating mode capacity and COP measured at the H1 rating point. Air-side capacities relative to the average of the R410A test points are shown in Figure 2. Capacity was very repeatable within ±1.5% for each refrigerant at the H1 point. Unit capacity was very similar with all refrigerants being within 2.5% of R410A. COP data are shown in Figure 3. COP was also very repeatable at the H1 point, generally within ±0.5% to ±1% for each refrigerant. DR-55 and DR-5A provided COPs ~1.5% better than R410A; R32 s COP was ~3% higher. Table 4. Refrigerant charge, TXV position, and compressor speed selected for each refrigerant, along with the average capacity and COP obtained at the H1 point for each. Refrig # of Charge TXV AFD wrt wrt CAP COP runs (lbm) (turns) (Hz) R410A R410A R410A , DR CW 60 45, % % R CW 55 45, % % DR-5A ½ CW 61 45, % % CW is clockwise (in/closed), CAP is Air-side Capacity in BTU/hr. The air-side heating capacities and COPs (as integrated averages over a number of heating/defrost cycles) taken under the H2 conditions are shown in Figure 4 and Figure 5, respectively. Significant variability in performance was observed during the H2 tests, especially with R410A. This can be attributed to several potential causes, one being variability in the frost build process and the (in)ability of the facility to hold chamber conditions perfectly as the unit switches between operating modes. 2 TEST REPORT #56, SOFT-OPTIMIZED SYSTEM TEST OF R410A, DR-55, R32, AND DR-5A IN A 4-TON UNITARY ROOFTOP HEAT PUMP, Schultz, Perez-Blanco, and Kujak, submitted to AHRI Low GWP AREP 29-Sep IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

5 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 5 of 12 Under the H2 defrost conditions, DR-55 provided about 10% additional capacity over R410A and R32 15% to 20% more capacity along with significantly higher efficiencies. Figure 6 shows time traces of heat pump status and compressor power draw during operating under H2 conditions for each refrigerant. As shown in Figure 7, the fraction of time spent in defrost mode with R32 was shorter than for the other refrigerants. The defrost period for R32 ranged from 2.5 to 3 minutes while being 5 to 10 minutes for the other refrigerants. Heating periods ranged from 35 to 50 minutes for all refrigerants. The differences in defrost periods appear to be driven by differences in controls response. Defrost mode is supposed to terminate when the outdoor coil sensor (attached to the inlet to the bottom circuit) reading (OCT) is a specified offset above the outdoor air temperature. With R32 in the unit, defrost periods terminated when OCT was slightly above the setpoint. With R410A and DR-5A, the OCT reading was 20d to 30d beyond the setpoint before defrost ended. With DR-55, the OCT reading was 10d to 20d higher than the setpoint when defrost stopped. Although this phenomenon was generally repeatable, it is not understood how or why the controls response should be dependent on the refrigerant present. 3 Given the similarities in properties of these four refrigerants, it would be expected that similar levels of performance should be obtained if defrost occurred at common initiation and termination temperatures. (This also suggests that the level of performance obtained with R32 should be approachable with the other refrigerants.) Heating capacities and COPs relative to R410A at the H3 conditions are shown in Figure 11. At this colder outdoor condition, all refrigerants produced slightly lower capacities, ranging from R32 being 1% lower to DR-55 being 4% lower than R410A. COPs were equal to 1% lower with DR-5A and DR-55 and up by 4% with R32. The compressor discharge temperatures (CDTs) measured are shown in Figure 9 for the H1 tests and in Figure 10 for the H3 tests. R32 ran about 20d higher than the baseline R410A. DR-5A ran about 10d to 14d higher and DR-55 ran only 8d higher. Similar results were obtained during the heating segments of the H2 tests. All CDTs were well below the maximum operating temperature limit of 250. Heating mode cyclic degradation coefficients (C Dh ), calculated from the H1C (cyclic) tests with each refrigerant, are shown in Figure 11, along with percent differences relative to R410A. All the C Dh values are quite small, so the differences between them are of little significance. SUMMARY Performance tests have been run on a standard production rooftop unit of nominal 44,000 BTU/hr heating capacity and 3.40 COP with R410A, serving as the baseline, and alternative refrigerants DR-55, R32, and DR-5A. No alterations were made to the unit other than replacing the fixed TXVs with adjustable TXVs to allow keeping the superheats with the low GWP refrigerants consistent with the R410A baseline, and installing a VFD on the compressor to match the baseline capacity. 3 The OCT values used here are readings from a thermocouple attached to the OCT sensor well. The OCT thermocouple readings closely matched readings from another thermocouple attached to the same circuit approximately 3 inches upstream. Although there might have been an offset between the OCT sensor and thermocouple readings, it would be expected to be a fixed value not dependent on the refrigerant being used. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

6 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 6 of 12 At the H1 and H3 (continuous run) heating points, all three alternative refrigerants showed a small (1% to 4%) decrease in capacity. All three alternatives showed small improvements in COP at the H1 point (1% to 2%). DR-55 showed a small decrease (~1%) at the H3 point while R32 showed a small increase (~4%). At the H2 cyclic defrost test condition, there was a modest increase in capacity with DR-55 (~10%) and a significant increase (~20%) with R32. There was a large improvement in COP at the H2 condition when running with DR-55 (10% to 15%) and R32 (~25%). This was driven mainly by the shorter defrost periods with DR-55 and especially so with R32. This appears to have been driven by the controller tripping the end of defrost at quite different temperatures between the refrigerants. It is unclear at this time why this happened. It is expected that differences in performance under frosting conditions between the refrigerants would be much smaller with consistent trip points. Compressor discharge temperatures (CDTs) were slightly higher when running with DR-55 and DR-5A, typically 5 d to 10 d (3 Cd to 6 Cd). As expected, the highest discharge temperatures were measured with R32, being roughly 20 d higher than with R410A. Figure 1. Precedent unit test setup indicating measurement locations. Heating mode flow directions are shown. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

7 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 7 of 12 Figure 2. Air-side heating capacity at the H1 conditions relative to the average of the R410A baseline points. Figure 3. Heating COP at the H1 conditions relative to the average of the R410A baseline points. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

8 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 8 of 12 Figure 4. Air-side heating capacity (as an integrated average over a number of heating/defrost cycles) at the H2 conditions relative to the average of the R410A baseline points. Note the order of runs, starting with R410A, progressing with DR-55, R32, and DR-5A through Run 127. Additional runs were then collected with R410A, R32, and DR-55 (in that order). Figure 5. Heating COP (as an integrated average over a number of heating/defrost cycles) at the H2 conditions relative to the average of the R410A baseline points. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

9 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 9 of 12 R410A R32 DR-55 DR-5A Figure 6. Traces with time (in minutes) of compressor power (in kw on left axis) and heat pump status (right axis, 0 = defrost mode, 500 = heating mode) while operating at the H2 conditions. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

10 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 10 of 12 Figure 7. Fraction of time that unit spent in heating mode (bottom segment of the columns) and defrost mode (upper segment of the columns) during H2 tests. Figure 8. Performance under H3 conditions. Left) Air-side capacity relative to R410A. Right) Heating COP relative to R410A. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

11 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 11 of 12 Figure 9. Compressor discharge temperatures measured during operation at the H1 test conditions. Figure 10. Compressor discharge temperatures measured during operation at the H3 test conditions. Figure 11. Left: Cyclic degradation coefficients determined by the H1C test. Right: Percent difference of cyclic degradation coefficients relative to R410A. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

12 Soft-Optimized Tests of a 4-RT Unitary Rooftop Heat Pump with R410A, DR-55, R32, and DR-5A Heating Mode Performance page 12 of 12 DATA TABLES Tables of data recorded for the H1 and H3 test points from selected runs for each refrigerant follow. Note: The value for the compressor/unit lubricant charge is unknown (not listed on any of the unit labels nor in the catalog). The standard production lubricant charged was used for both the cooling and heating tests. IRUnitaryHeatPumpTestReport_Htg_v5b.docx Marcos E. Perez-Blanco & Ken Schultz Technology Validation Group Modeling & Simulation NoE

13 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H1 Basic Information Alternative Refrigerant DR 55 Run #70 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #12 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz Hz 1.00 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge kg lbm 0.91 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 47 Air Wet Bulb 6.1 C 43 EB = Qrefrig/Qair % % Air side Capacity kw 46,590 45,640 Btu/hr Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input kw kw Power to Compressor kw kw COP or EER (total) [] [] COP or EER (compressor only) [] [] Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

14 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H1 Baseline Refrig: R410A Run #12 Alternate Refrig: DR 55 Run #70 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure kpa psia Evaporator (fin &tube coil) fluid flow rate air L/hr scfm entering DBT C d entering WBT C d entering DPT C d leaving DBT C d leaving WBT C d leaving DPT C d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT C d entering DPT C d entering w kgw/kgda lbmw/lbmda Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet outlet outlet subcooling Expansion Device (TXV) inlet inlet subcooling Evaporator (refrig to air fin & tube coil) inlet (header) outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet HP outlet

15 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H3 Basic Information Alternative Refrigerant DR 55 Run #145 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #29 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz Hz 1.00 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge kg lbm 0.91 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 17 Air Wet Bulb 9.4 C 15 EB = Qrefrig/Qair % % Air side Capacity kw 25,270 24,230 Btu/hr Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input kw kw Power to Compressor kw kw COP or EER (total) [] [] COP or EER (compressor only) [] [] Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

16 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H3 Baseline Refrig: R410A Run #29 Alternate Refrig: DR 55 Run #145 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure kpa psia Evaporator (fin &tube coil) fluid flow rate air L/hr scfm entering DBT C d entering WBT C d entering DPT C d leaving DBT C d leaving WBT C d leaving DPT C d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT C d entering DPT C d entering w kgw/kgda lbmw/lbmda Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet outlet outlet subcooling Expansion Device (TXV) inlet inlet subcooling Evaporator (refrig to air fin & tube coil) inlet (header) outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet HP outlet

17 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H1 Basic Information Alternative Refrigerant R32 Run #102 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #12 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz Hz 0.92 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge kg lbm 0.81 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 47 Air Wet Bulb 6.1 C 43 EB = Qrefrig/Qair % % Air side Capacity kw 46,590 45,360 Btu/hr Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input kw kw Power to Compressor kw kw COP or EER (total) [] [] COP or EER (compressor only) [] [] Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

18 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H1 Baseline Refrig: R410A Run #12 Alternate Refrig: R32 Run #102 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure kpa psia Evaporator (fin &tube coil) fluid flow rate air L/hr scfm entering DBT C d entering WBT C d entering DPT C d leaving DBT C d leaving WBT C d leaving DPT C d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT C d entering DPT C d entering w kgw/kgda lbmw/lbmda Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet outlet outlet subcooling Expansion Device (TXV) inlet inlet subcooling Evaporator (refrig to air fin & tube coil) inlet (header) outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet HP outlet

19 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H3 Basic Information Alternative Refrigerant R32 Run #100 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #29 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz Hz 0.92 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge kg lbm 0.81 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 17 Air Wet Bulb 9.4 C 15 EB = Qrefrig/Qair % % Air side Capacity kw 25,270 25,010 Btu/hr Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input kw kw Power to Compressor kw kw COP or EER (total) [] [] COP or EER (compressor only) [] [] Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

20 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H3 Baseline Refrig: R410A Run #29 Alternate Refrig: R32 Run #100 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure kpa psia Evaporator (fin &tube coil) fluid flow rate air L/hr scfm entering DBT C d entering WBT C d entering DPT C d leaving DBT C d leaving WBT C d leaving DPT C d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT C d entering DPT C d entering w kgw/kgda lbmw/lbmda Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet outlet outlet subcooling Expansion Device (TXV) inlet inlet subcooling Evaporator (refrig to air fin & tube coil) inlet (header) outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet HP outlet

21 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H1 Basic Information Alternative Refrigerant DR 5A Run #125 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #12 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz Hz 1.02 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge kg lbm 0.91 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 47 Air Wet Bulb 6.1 C 43 EB = Qrefrig/Qair % % Air side Capacity kw 46,590 45,800 Btu/hr Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input kw kw Power to Compressor kw kw COP or EER (total) [] [] COP or EER (compressor only) [] [] Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

22 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H1 Baseline Refrig: R410A Run #12 Alternate Refrig: DR 5A Run #125 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure kpa psia Evaporator (fin &tube coil) fluid flow rate air L/hr scfm entering DBT C d entering WBT C d entering DPT C d leaving DBT C d leaving WBT C d leaving DPT C d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT C d entering DPT C d entering w kgw/kgda lbmw/lbmda Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet outlet outlet subcooling Expansion Device (TXV) inlet inlet subcooling Evaporator (refrig to air fin & tube coil) inlet (header) outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet HP outlet

23 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 1 04/Nov/2015 Manufacturer: Trane Test Point: H3 Basic Information Alternative Refrigerant DR 5A Run #128 Alternative Lubricant Type and ISO Viscosity POE Emkarate RL32H Baseline Refrigerant R410A Run #29 Baseline Lubricant Type and ISO Viscosity POE Emkarate RL32H Make and Model of System Precedent Rooftop Heat Pump, WSC048E3 Nominal Capacity and Type of System 48,500 Btu/hr cooling (A) / 44,000 Btu/hr heating (H1) Comparison Data Base Alt. SI Units Base Alt. IP Units Ratio Mode (heating/cooling) heating Compressor Type scroll, Alliance model SXA044B2BPA Compressor Displacement 8.82 m³/hr 311 ft³/hr Nominal Motor Size 2.83 kw 3.8 hp Motor Speed (w/60 Hz input) 3500 Hz Hz 1.02 Expansion Device Type TXV (Emerson: cooling = AACE4 ZW195, heating = AAE3 ZW195) Lubricant Charge? L? qt Refrigerant Charge kg lbm 0.91 Indoor Entering DBT 21.1 C 70 Air Entering WBT 15.6 C 60 Target Flow rate (mixed) 45.3 m³/min 1600 scfm Outdoor Dry Bulb 8.3 C 17 Air Wet Bulb 9.4 C 15 EB = Qrefrig/Qair % % Air side Capacity kw 25,270 24,530 Btu/hr Sensible Capacity n/a n/a kw n/a n/a Btu/hr n/a Total System Power Input kw kw Power to Compressor kw kw COP or EER (total) [] [] COP or EER (compressor only) [] [] Refrigerant Mass Flow Rate kg/hr lbm/hr Other System Changes The unit tested was modified from original production by replacing fixed TXVs with adjustable TXVs of the same size and installing a VFD on the compressor to allow matching baseline capacity. Compressor speed was set by matching cooling capacity at the "A" conditions. Refrigerant charge was chosen to maximize EER at the "A" conditions (essentially the same as matching the baseline condenser exit subcooling). continued on next page

24 Low GWP AREP SOFT OPTIMIZED SYSTEM TEST DATA FORM page 2 04/Nov/2015 Type of System: Precedent RTU HP Test Point: H3 Baseline Refrig: R410A Run #29 Alternate Refrig: DR 5A Run #128 Water/Air Side Data Base Alt. SI Units Base Alt. IP Units Ratio barametric pressure kpa psia Evaporator (fin &tube coil) fluid flow rate air L/hr scfm entering DBT C d entering WBT C d entering DPT C d leaving DBT C d leaving WBT C d leaving DPT C d Condenser (fin & tube coil) fluid air flow rate not msrd L/hr not msrd scfm entering DBT C d entering DPT C d entering w kgw/kgda lbmw/lbmda Refrigerant Side Base Alt. Base Alt. T ( C) P (kpa) T ( C) P (kpa) T () P (psia) T () P (psia) Compressor (scroll) suction discharge suction SH Condenser (refrig to air fin & tube coil) inlet outlet outlet subcooling Expansion Device (TXV) inlet inlet subcooling Evaporator (refrig to air fin & tube coil) inlet (header) outlet outlet superheat Refrigerant Reversing Valve LP inlet LP outlet HP inlet HP outlet

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #6 System Drop-in Tests of R-22 Alternative Fluids (ARM-32a,

More information

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #53 System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton

More information

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #47 System Drop-in Test of R-32 and Refrigerant Blends ARM-71a,

More information

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006 Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #4 System Drop-in Test of Refrigerant R-32 in Split System Heat

More information

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32

More information

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #14 System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled

More information

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #43 System Drop-in Tests of Refrigerants L-41-1, L-41-2, and

More information

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #32 System Soft-Optimized Test of Refrigerant D2Y60 in Air Source

More information

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #34 Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A

More information

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #65 Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A)

More information

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10 Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2000 Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in

More information

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Low Global Warming Refrigerants For Commercial Refrigeration Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Low Global Warming Refrigerants For Commercial Refrigeration Systems Samuel

More information

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America

TEST REPORT #68. Chiao M. Lee Paul Laurentius. Hussmann Corporation St. Charles Rock Road Bridgeton, MO United States of America Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Progra (Low-GWP AREP) TEST REPORT #68 Syste Drop-in Test of (R-448a) in a R04A Low and Mediu Teperature

More information

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle

More information

GWP Alternative Refrigerants

GWP Alternative Refrigerants Update on Phase II of the AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) Karim Amrane and Xudong Wang Air Conditioning, Heating, and Refrigeration Institute (AHRI) Technical Forum

More information

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps AM-4249223-1 - Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps Christian K. Bach, Graduate Student, Eckhard A. Groll, Reilly Professor, James

More information

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program

More information

Low GWP Refrigerants for Air Conditioning Applications

Low GWP Refrigerants for Air Conditioning Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low GWP Refrigerants for Air Conditioning Applications Samuel F. Yana Motta

More information

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #12 System Drop-In Tests of Refrigerant Blends N-13a and AC5

More information

January 16 th, 2014 New York City

January 16 th, 2014 New York City Compressor Calorimeter Test of R-404A Alternative Refrigerants ARM-31a, D2Y-65, L-40, and R-32/R- 134a (50/50) in Medium Temperature Refrigeration Scroll Compressor Som Shrestha Omar Abdelaziz January

More information

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Low GWP Refrigerants for Air Conditioning and Chiller Applications Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Low GWP Refrigerants for Air Conditioning and Chiller Applications Ankit

More information

Report No CRT-414

Report No CRT-414 Unit Nameplate Manufacturer: Available upon request form XDX Model No.YSC120E3RHAOWJX Serial No. 807103096L Volts: 208/230 Hertz: 60 Phase: 3 Refrigerant Type: R-410A Indoor Fan Motor Manufacturer: G.

More information

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration Soft Optimization Test of a R404A Alternative Refrigerant R452A (DR34) in a Trailer Refrigeration

More information

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors Lars Sjoholm

More information

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #2 System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

More information

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning System Drop-In Tests of R134a and R407C Alternative Refrigerants In Bus Air-Conditioning Units

More information

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

Application of a hybrid control of expansion valves to a 3-ton large room cooling system 2123, Page 1 Application of a hybrid control of expansion valves to a 3-ton large room cooling system Christian K. Bach*, Eckhard A. Groll, James E. Braun Ray W. Herrick Laboratories, Purdue University,

More information

Evaluation of HCFC Alternative Refrigerants

Evaluation of HCFC Alternative Refrigerants Evaluation of HCFC Alternative Refrigerants Shaobo Jia Global Innovation Heatcraft Worldwide Refrigeration shaobo.jia@heatcraftrpd.com Introduction It is well-known that HCFC refrigerants widely used in

More information

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS

ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS ANALYSIS OF LGWP ALTERNATIVES FOR SMALL REFRIGERATION (PLUGIN) APPLICATIONS YANA MOTTA, S. (*), SPATZ, M., VERA BECERRA, E. (*) Honeywell International, 2 Peabody Street, Buffalo, NY 1421, Samuel.YanaMotta@honeywell.com

More information

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research Update on Next Generation Low GWP Refrigerants for Chillers Products Steve Kujak Director, Next Generation Refrigerant Research The International Symposium on New Refrigerants and Environmental Technology

More information

Steady and Cyclic Performance Testing of Packaged R-410A Units

Steady and Cyclic Performance Testing of Packaged R-410A Units Prepared by: Bo Shen, James E. Braun, and Eckhard A. Groll Ray W. Herrick Laboratories The School of Mechanical Engineering Purdue University Steady and Cyclic Performance Testing of Packaged R-410A Units

More information

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller Satheesh Kulankara, William McQuade, Scott Rauch and

More information

System Modeling of Gas Engine Driven Heat Pump

System Modeling of Gas Engine Driven Heat Pump Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 01 System Modeling of Gas Engine Driven Heat Pump Isaac Mahderekal shenb@ornl.gov

More information

Transcritical CO2 Bottle Cooler Development

Transcritical CO2 Bottle Cooler Development Transcritical CO2 Bottle Cooler Development C. Rohrer Ingersoll Rand Climate Control, 12999 St. Charles Rock Rd. Bridgeton, MO, United States 314 298-4765, clay_rohrer@irco.com ABSTRACT This paper contains

More information

R32 Compressor for Air conditioning and Refrigeration applications in China

R32 Compressor for Air conditioning and Refrigeration applications in China Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 R32 Compressor for Air conditioning and Refrigeration applications in China Weihua

More information

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

More information

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment AHRI Standard 1230 with Addendum 1 2014 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment AHRI STANDARD 1230-2014 WITH ADDENDUM 1,

More information

Study of R161 Refrigerant for Residential Airconditioning

Study of R161 Refrigerant for Residential Airconditioning Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Study of Refrigerant for Residential Airconditioning Applications Yingwen

More information

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Comparison of Performance of a Residential Air- Conditioning System Using

More information

Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units

Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units ANSI/AHRI Standard 366 (SI) 2009 Standard for Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units Approved by ANSI on 4 January 2011 IMPORTANT SAFETY DISCLAIMER AHRI

More information

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM Hantz, D., Gulyas, G., Bensafi, A. Centre Technique des Industries Aéraulique et Thermique (CETIAT) BP 2042

More information

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Low Global Warming Potential Alternative Refrigerants Evaluation Program

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information

Purdue e-pubs. Purdue University

Purdue e-pubs. Purdue University Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 206 Experimental Investigation of the Refrigerant Flow Distribution Characteristic

More information

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps

More information

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition Purdue University Purdue e-pubs nternational Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2 Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

More information

Performance Measurement of R32 Vapor Injection Heat Pump System

Performance Measurement of R32 Vapor Injection Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Performance Measurement of Vapor Injection Heat Pump System Yunho Hwang

More information

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs Abstract Fan and coil evaporators as used in the industrial refrigeration industry can be certified for performance per ANSI/AHRI Standard 420-2008, Performance Rating of Forced-Circulation Free-Delivery

More information

Application Engineering

Application Engineering Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved

More information

Summary of Research Activities. Eckhard A. Groll Professor of Mechanical Engineering

Summary of Research Activities. Eckhard A. Groll Professor of Mechanical Engineering Summary of Research Activities Eckhard A. Groll Professor of Mechanical Engineering Ray W. Herrick Laboratories Purdue University West Lafayette, IN 47907 Main Driving Factors for Research are Energy and

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

*Corresponding author;

*Corresponding author; PERFORMANCE ANALYSIS OF AUTOMOTIVE AIR CONDITIONING SYSTEM WITH AN INTERNAL HEAT EXCHANGER USING R1234YF UNDER DIFFERENT EVAPORATION AND CONDENSATION TEMPERATURES by Mehmet DIREK a *and Alper KELESOGLU

More information

AIR CONDITIONER PERFORMANCE RATING

AIR CONDITIONER PERFORMANCE RATING HPRATE V5.1 AIR CONDITIONER PERFORMANCE RATING by G.L. Morrison MechLab The University of New South Wales.EDU.AU September 2012 Version 5.1 HPRATE 5 Air Conditioner Performance Rating 1 HPRATE AIR CONDITIONER

More information

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2002 Performance Comparisons Of A Unitary Split System Using Microchannel and

More information

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a CHAPTER 9 REFRIGERATION & AIR-CONDITIONING YEAR 2012 ONE MARK Common Data For Q. 1 and Q.2 A refrigerator operates between 120 kpa and 800 kpa in an ideal vapour compression cycle with R-134a as the refrigerant.

More information

COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22

COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22 COMPARATIVE PROPERTIES AND EFFICIENCY OF R-421A FOR RETROFIT USE TO REPLACE R-22 2013.12.26 prepared by James M. Calm, P.E. Engineering Consultant 10887 Woodleaf Lane Great Falls, VA 22066-3003 USA for

More information

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration Marquette University e-publications@marquette Mechanical Engineering Faculty Research and Publications Mechanical Engineering, Department of 1-1-2013 Modeling and Testing of an R-23/R-134a Mixed Refrigerant

More information

R-404A Alternative with Low Compressor Discharge Temperature

R-404A Alternative with Low Compressor Discharge Temperature 2175, Page 1 R-404A Alternative with Low Compressor Discharge Temperature Barbara MINOR 1 *, Vladimir SULC 2, Jeff BERGE 3, Michal KOLDA 4, Michal HEGAR 5 1 DuPont, Fluoroproducts, Wilmington, DE, USA

More information

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 SAE Alternate Refrigerant Cooperative Research Program Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000 To: Alternate Refrigerant Task Force Members From: Ward Atkinson

More information

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Technical Development Program COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler Menu Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Introduction System

More information

System Considerations for Refrigerant Blends with Temperature Glide

System Considerations for Refrigerant Blends with Temperature Glide System Considerations for Refrigerant Blends with Temperature Glide Theory and Practical Retrofit Guidance Table of Contents 1 2 3 4 5 Blend and Glide Basics... 3 1.1 Superheat and Subcooling of Refrigerant

More information

AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP)

AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP) 2014 Purdue Conferences Xudong Wang and Karim Amrane Air Conditioning, Heating, and Refrigeration Institute (AHRI) Low GWP AREP Introduction

More information

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature. Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Evaluation of Heat pump System using and ed Refrigerant in

More information

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power energy center Paper Report Summary 210-1 174-2 Fixed and Floating Head Pressure Comparison for Madison Ice Arena Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power July 1998 April,

More information

Superheat charging curves for technicians

Superheat charging curves for technicians This website requires certain cookies to work and uses other cookies to help you have the best experience. By visiting this website, certain cookies have already been set, which you may delete and block.

More information

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz ENVIRONMENTALLY SOUND REFRIGERANT N4H4 Performance Series Product Specifications 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

The Refrigeration Cycle

The Refrigeration Cycle Job Sheet 4 The Refrigeration Cycle OBJECTIVES In this job sheet, you will plot the refrigeration cycle on a pressure-enthalpy diagram using pressures and temperatures measured on your training system.

More information

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw) FALCON Rooftop Units ACPSE 50/60Hz Cooling : 36 to 1388 MBH (11 to 407 ) Heating : 40 to 1298 MBH (12 to 380 ) R Products that perform...by people who care NOMENCLATURE 6 AC P S E 435 P - HP G Q 6-60 Hz

More information

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT ENVIRONMENTALLY SOUND REFRIGERANT NH4H4 Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS, 208/230

More information

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION 2597, Page 1 Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump Ian H. BELL 1 *, James E. BRAUN 2 1 Bell Thermal Consultants ian.h.bell@gmail.com 2 Purdue

More information

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Investigation of Refrigerant Vapor- Injection Technique for

More information

Product Data. Fig. 1 - Unit 50VR -A

Product Data. Fig. 1 - Unit 50VR -A 50VR---A Performancet 15 SEER 2---Stage Packaged Heat Pump tem with PuronR (R---410A) Refrigerant Single and Three Phase 2to5NominalTons(Sizes24---60) Product Data Fig. 1 - Unit 50VR -A A09033 Single-Packaged

More information

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers - ERRATA SHEET FOR AHRI STANDARD 1250 (I-P)-2009, PERFORMANCE RATING OF WALK-IN COOLERS AND FREEZERS December

More information

Implications of GHP Fan Control Strategies on Humidity Control in Commercial Applications

Implications of GHP Fan Control Strategies on Humidity Control in Commercial Applications Implications of GHP Fan Control Strategies on Humidity Control in Commercial Applications ASHRAE Winter Meeting February 9, 2005 Hugh I. Henderson, Jr., P.E. CDH Energy Corp. Cazenovia, NY DOE/NETL Project

More information

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants CHENNUCHETTY CHINNARAJ * Associate Professor in Mechanical Engineering, Government College of

More information

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors

More information

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube ISSN: 2347-3215 Volume 1 Number 4 (2013) pp. 46-54 www.ijcrar.com Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube Richa Soni 1*, P.K.Jhinge

More information

Effect of magnetic field on the performance of new refrigerant mixtures

Effect of magnetic field on the performance of new refrigerant mixtures INTERNATIONAL JOURNAL OF ENERGY RESEARCH Int. J. Energy Res. 2003; 27: 203 214 (DOI: 10.1002/er.868) Effect of magnetic field on the performance of new refrigerant mixtures Samuel M. Sami n,y and Shawn

More information

SERVICE ASSISTANT OVERVIEW FDSI Online Training

SERVICE ASSISTANT OVERVIEW FDSI Online Training Author: Dale T. Rossi Online Editor: Zachary Williams SERVICE ASSISTANT OVERVIEW FDSI Online Training May 5, 2009 Table Service Assistant Description... 2 Installing the Main Unit... 3 Ambient Temperature...

More information

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation Marco Alexandre Onofre Dias This paper presents a model that was implemented

More information

recooler HP EQKR HEAT PUMP

recooler HP EQKR HEAT PUMP AIR COMFORT AIR TREATMENT 9566 GB 2016.03.17 recooler HP EQKR HEAT PUMP» TECHNICAL CATALOGUE 2 ReCooler HP EQKR Technical Catalogue Content ReCOOLER HP EQKR HEAT PUMP 3 product presentation. 3 applications.

More information

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies Understanding Applications for Alternate Refrigerants Ron Bonear Emerson Climate Technologies Agenda Overview of R-448A/R-449A Refrigerant Development Methodology Evaluation Strategy R-448A /R-449A Refrigerants

More information

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2018 Evaluation and Optimization of System Performance using HFO-mix Refrigerants

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Single Package Rooftop, High---Efficiency Heat Pump Units With Field---Installed Electric Heat Sizes 08 --- 14 with Puron R (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS

More information

On Balance: Heat Rejection Control a Packaged Solution

On Balance: Heat Rejection Control a Packaged Solution On Balance: Heat Rejection Control a Packaged Solution Echelon Americas Channel Partner Conference March 11, 2005 Presented by Doug Scott VaCom Technologies La Verne, California Opportunity An integrated

More information

R4H4. Product Specifications

R4H4. Product Specifications ENVIRONMENTALLY SOUND REFRIGERANT R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

Air Cooled Packaged Systems AIRAH Back to Basics

Air Cooled Packaged Systems AIRAH Back to Basics Air Cooled Packaged Systems AIRAH Back to Basics What s changed? New Refrigerants R410a MEPS EER / AEER / SEER Manufacturing Technologies Research, Development and Testing New technologies, controls, reliability

More information

R4H4. Product Specifications

R4H4. Product Specifications R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY BALANCED REFRIGERANT 1-1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Scroll compressors on

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

INVERTER SCROLL. LG Electronics Distributed by. Copyright 2017 LG Electronics. All rights reserved.

INVERTER SCROLL. LG Electronics     Distributed by. Copyright 2017 LG Electronics. All rights reserved. LG Electronics http://www.lg.com http://partner.lge.com Distributed by Copyright 2017 LG Electronics. All rights reserved. FEATURES & BENEFITS High Efficient Inverter Technologies EER 2.65 / COP 3.2 /

More information

2016 Annual Conference

2016 Annual Conference 2016 Annual Conference Joe Sanchez Engineering Manager BITZER US, INC St. Louis, Missouri Engineering Chair of Compressor Section for AHRI Session 13 Advancements in Compressor Design, Testing and Performance

More information

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 111 CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM 7.1 INTRODUCTION Energy is the primary component to run any system in the world. According to

More information

Pressure Enthalpy Charts

Pressure Enthalpy Charts Pressure Enthalpy Charts What is a p-h Diagram? A p-h diagram is a diagram with a vertical axis of absolute pressure and a horizontal axis of specific enthalpy. "Enthalpy is the amount of energy in a substance

More information

Refrigeration/Troubleshooting Manual

Refrigeration/Troubleshooting Manual Refrigeration/Troubleshooting Manual P.O. Box 245 Syracuse, NY 13211 www.roth-america.com 888-266-7684 P/N: 2300100910 Table of Contents: Section 1: Geothermal Refrigeration Circuits Overview... 2 Water-to-Air

More information

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE Service Facts Customer Property: Contains wiring and service information. Please retain. WC*240-SF-1H Library Service Literature Product Section Unitary Product Package Air Conditioner Model WC* Literature

More information

Improved R134A Mobile Air Conditioning Systems

Improved R134A Mobile Air Conditioning Systems University of Illinois at Urbana-Champaign Air Conditioning and Refrigeration Center A National Science Foundation/University Cooperative Research Center Improved R134A Mobile Air Conditioning Systems

More information

How to Cut Chiller Energy Costs by 30%

How to Cut Chiller Energy Costs by 30% How to Cut Chiller Energy Costs by 30% Pre-packaged retrofit cuts centrifugal compressor chiller energy costs by 30% while reducing required maintenance and extending operating life at Duke Realty Corporation

More information

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON 7D- -A EVOLUTIONr 15 SEER SINGLE-PACKAGED HEAT PUMP SYSTEM WITH PURONr (R-410A) REFRIGERANT SINGLE PHASE 2-5 NOMINAL TONS (SIZES 24-) Fig. 1 - Unit 7D - -A Product Data A09032 Single-Packaged Products

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information